B599--Air Balancing Sheridan VAMC Base with 4 option years
Closed Pre-Solicitation Posted
Not the latest version. See the latest solicitation from .
- Solicitation number
- 36C25921Q0064
- Agency
-
Veterans Integrated Service Network 19
Veterans Health Administration, Department of Veterans Affairs
- Responses due
- Set-aside
- Service-Disabled Veteran-Owned Small Business
Opportunity facts
- NAICS code
- 541380 Testing Laboratories and Services
- PSC
- B599 Special Studies/Analysis- Other
- Place of performance
- Sheridan Vamc 1898 Fort Road 82801 USA
Notice details come from SAM.gov. Updated .
Notice text
Veterans Affairs Healthcare Systems
Sheridan, Wyoming
Statement of Work (SOW)
Medical Center Air Flow Measurement and Testing
1. SCOPE OF WORK
1.1 Services are required monthly and bi-annually at the VA Medical Center in Sheridan, Wyoming to conduct air flow and balancing tests at various locations in the facility. Contractor is to provide written results required by USP 797 and per NEBB's Testing Adjusting and Balancing (TAB) procedures. Written results shall contain fan design data and test data including CFM, velocity, duct size, total static pressure across fan, external static pressure upstream of fan, and external static pressure downstream of fan. Locations are listed below:
2. MONTHLY DOCUMENTATION
2.1 Documentation is required for air exchanges and room pressure for the following areas:
Sterile Products Service Bld 71N:
1. Sterile Storage area Room 112
2. Locker Room 112A
3. Sterile Preparation Room 112B
4. Equipment Closet Room 112B
5. HAC Room 112C
6. Office Room 112D
7. Storage Room 112E
8. Common Area Room 112F
9. Medivator area Room 112G
10. Decontamination Room 108
11. Storage Room 108B
12. HAC room 108C
13. Restroom Room 107
14. Corridor Room C112
Sterile Product Distribution Bld. 7:
1. Breakout Room 003
2. Clean Storage Room 002
3. Bulk Storage Room 003B
Ambulatory Care Bld 71N
Exam Room 126
3. BI-ANNUAL DOCUMENTATION
3.1 Documentation is required for Supply Air flow readings in the following areas:
1. Micro Biology Room 208 (bld 71N Lab)
2. Lab Room 217 (bld 71N Lab) 2 VAV SÂ Â
3.2 Documentation is required for Pressure Differential Tests in the following areas:
1. Ambulatory Care (bld 71N) two negative air rooms Room 128 and 131
2. Medical Unit (bld 71) negative air rooms 316, 316A, 317, 318, and 318A
Files
| File | Type | Posted |
|---|---|---|
| 36C25921Q0064_1.docx | DOCX document |
Notice history
| Notice | Type | Posted |
|---|---|---|
| B599--Air Balancing Sheridan VAMC Base with 4 option years | Solicitation | |
| This notice | Pre-Solicitation |
On GovTribe
Work this opportunity
- Track it in your pipeline
- Find teaming partners
- Similar opportunities
- Ask GovTribe AI about this opportunity