Airfield leaking transformer
Closed Solicitation Posted
- Solicitation number
- 31125260000817
- Agency
-
Coast Guard
Department of Homeland Security
- Responses due
- Set-aside
- Total Small Business
Opportunity facts
- NAICS code
- 811310 Commercial and Industrial Machinery and Equipment (except Automotive and Electronic) Repair and Maintenance
- Place of performance
- Buzzards Bay, Massachusetts 02542, United States
Notice details come from SAM.gov. Updated .
About this opportunity
The U.S. Coast Guard seeks removal and replacement of airfield lighting transformers at Base Cape Cod, Buzzards Bay, Massachusetts, with proposals due August 15. The procurement is a 100 percent Women-Owned Small Business (WOSB) set-aside.
The base scope covers three transformers: a 37 KVA McGraw Edison single-phase unit (serial 74ZD743004) adjacent to building 614 and runway 23; a 37 KVA McGraw Edison single-phase unit (serial 73ZE858030) adjacent to building 614 and runway 14; and a 1000/1120 KVA ABB three-phase unit (serial 11JC573270001) adjacent to hangar 3181, which requires investigation and feasibility analysis for oil leaks. An optional fourth transformer—a 15 KVA Southeastern Transformer unit (serial 1019102) adjacent to building 195—may be added. Replacements must be refurbished, certified, and warranted units meeting IEEE and ANSI standards, installed in kind or equal to existing specifications, with three-year warranties on refurbished units and one-year warranties on all work performed.
Place of performance is Buzzards Bay, Massachusetts. The contractor must secure power, remove and dispose of existing units at its expense off-base, comply with NFPA 70 National Electrical Code and FAA regulations, perform operational tests, and restore power. Performance period is 45 calendar days from Notice to Proceed, with normal working hours 7:00 A.M. to 4:00 P.M. Monday through Friday. All contractor personnel require NCIC background checks processed at least 7 calendar days prior to base access. The contractor is responsible for hazardous materials handling, proper disposal documentation, and Massachusetts VOC emission compliance. Davis-Bacon Act prevailing wage rates apply. The NAICS code is 811310, and the PSC code is J061.
Notice text
3 versions
Update #3 · Latest ·
SCOPE: The Contractor shall provide all personnel, equipment, tools, materials, supervision, and other items and services necessary to remove and dispose of existing airfield lighting transformers and replace with refurbished, certified, and warrantied transformers (Fig. 1-11) at the U.S. Coast Guard, Base Cape Cod, on Joint Base Cape Cod, Buzzards Bay, MA, 02542.
1.1.1 Existing transformers: Contractors shall verify transformer specifications. 1) Transformer 413 (Fig. 1-3), adjacent to building 614 and runway 23. MANUFACTURER - McGraw Edison, Power System Division, Canonsburg, PA, 15317, single phase, 60 hertz, KVA 37 ½, 65° RISE, serial number 74ZD743004, voltage rating 4160GRD.Y/2400x12470GRD.Y/7200x13800GRD.Y/7970 240/120, cat nc. AAVL 115079A-37-K1, class OA, % IMP. 1.9 - 1.8, WDG MAT L.V. AL HV CU, wt.lb. 855, H.V. CONNECTION: VOLTAGE 2400 – SWITCH POSITION 2.4, VOLTAGE 7200 – SWITCH POSITION 7.2, VOLTAGE 7970 – SWITCH POSITION 7.9. Replace transformers in kind, or equal.
2) Transformer 523 (Fig. 4-6), adjacent to building 614 and runway 14, MANUFACTURER - McGraw Edison, Power System Division, Canonsburg, PA, 15317, single phase, 60 hertz, KVA 37 ½, 65° rise, serial number 73ZE858030, voltage rating 4160GRD.Y/2400x12470GRD.Y/7200x13800GRD.Y/7970 240/120, cat nc. AAVL 115079A-37-K1, class OA, % imp. 1.9 - 1.8, WDG MAT L.V. AL HV CU, wt.lb. 855, H.V. CONNECTION: VOLTAGE 2400 – SWITCH POSITION 2.4, VOLTAGE 7200 – SWITCH POSITION 7.2, VOLTAGE 7970 – SWITCH POSITION 7.9. Replace transformers in kind, or equal.
3) Transformer 138613 (Fig. 7-9), adjacent to hangar 3181 and taxiway Delta, Manufacturer ABB Jefferson City, MO, Style F25E017L67, Serial # 11JC573270001, KVA 1000/1120, AT CONTINUOUS RISE °C 55/65, MFG DATE JULY-2011, HIGH VOLTAGE 4160GRDY/2400, HV BIL KV 60, HV MTL AL, 5 IMPEDANCE 5.80, LOW VOLTAGE 480Y/277, LV BIL KV 30, LV MTL AL, GALLONS OIL 329, TOTAL WEIGHT IN POUNDS 7466. Replace transformers in kind, or equal.
1) Transformer 575 (Fig. 10-12), adjacent to building 195 and runway 5, Manufacturer Southeastern Transformer Co, Dunn, NC, single phase, 60 hertz, KVA 15, % imp. 3.6, serial number 1019102, volts 12470GRDY/7200-240/120. Replace transformers in kind, or equal.
SEE UPDATED SOW FOR FULL REQUIREMENTS
Update #2 ·
SCOPE: The Contractor shall provide all personnel, equipment, tools, materials, supervision, and other items and services necessary to remove and dispose of existing airfield lighting transformers and replace with new (Fig. 1-11) at the U.S. Coast Guard, Base Cape Cod, on Joint Base Cape Cod, Buzzards Bay, MA, 02542. Existing transformers: Contractors shall verify transformer specifications. Transformer 413 (Fig. 1-3), adjacent to building 614 and runway 23. MANUFACTURER - McGraw Edison, Power System Division, Canonsburg, PA, 15317, single phase, 60 hertz, KVA 37 ½, 65° RISE, serial number 74ZD743004, voltage rating 4160GRD.Y/2400x12470GRD.Y/7200x13800GRD.Y/7970 240/120, cat nc. AAVL 115079A-37-K1, class OA, % IMP. 1.9 - 1.8, WDG MAT L.V. AL HV CU, wt.lb. 855, H.V. CONNECTION: VOLTAGE 2400 – SWITCH POSITION 2.4, VOLTAGE 7200 – SWITCH POSITION 7.2, VOLTAGE 7970 – SWITCH POSITION 7.9 Transformer 523 (Fig. 4-6), adjacent to building 614 and runway 14, MANUFACTURER - McGraw Edison, Power System Division, Canonsburg, PA, 15317, single phase, 60 hertz, KVA 37 ½, 65° rise, serial number 73ZE858030, voltage rating 4160GRD.Y/2400x12470GRD.Y/7200x13800GRD.Y/7970 240/120, cat nc. AAVL 115079A-37-K1, class OA, % imp. 1.9 - 1.8, WDG MAT L.V. AL HV CU, wt.lb. 855, H.V. CONNECTION: VOLTAGE 2400 – SWITCH POSITION 2.4, VOLTAGE 7200 – SWITCH POSITION 7.2, VOLTAGE 7970 – SWITCH POSITION 7.9 Transformer 232177 (Fig. 7-9), adjacent to building 3181 parking. MANUFACTURER - ABB, Power System Division, Jefferson City, MD, 21755, Three phase distribution, 60 hertz, KVA 1500/1680, 55/65° RISE, style number F3HF147L66, serial number 11JC572250001, MFG Date Jun-11, voltage rating 22860GRDy13200, HV BIL KV 125, HV MTL AL, % Impedance 5.75, Low voltage 4160Y/2400, LV BIL KC 60, LV MTL AL, Mineral Oil 513 Gallons. NOTE: The Contractor shall investigate and determine the existence of oil leaks and provide analysis/feasibility for replacement or repair. Option Bid: Transformer 575 (Fig. 10-12), adjacent to building 195 and runway 5, Manufacturer Southeastern Transformer Co, Dunn, NC, single phase, 60 hertz, KVA 15, % imp. 3.6, serial number 1019102, volts 12470GRDY/7200-240/120.
Updated Section:
We discovered an issue with the Transformer replacement Statement of Work (SOW). There are two transformers that service building 3181 the wrong transformer is identified on in SOW.
- Statement of Work 1.1.1 transformer 3) description “Transformer 232177 (Fig. 7-9), adjacent to building 3181 parking. MANUFACTURER - ABB, Power System Division, Jefferson City, MD, 21755, Three phase distribution, 60 hertz, KVA 1500/1680, 55/65° RISE, style number F3HF147L66, serial number 11JC572250001, MFG Date Jun-11, voltage rating 22860GRDy13200, HV BIL KV 125, HV MTL AL, % Impedance 5.75, Low voltage 4160Y/2400, LV BIL KC 60, LV MTL AL, Mineral Oil 513 Gallons. NOTE: The Contractor shall investigate and determine the existence of oil leaks and provide analysis/feasibility for replacement or repair.”
Transformer 3) description SHOULD read “ Transformer 138613, adjacent to building 3181 apron, Manufacturer -ABB, Power System Division, Jefferson City, MD , 21755, 3 phase distribution, 60 hertz, KVA 1000/1120, 55/65°, style number F25E017L67, serial 11JC573270001, MFG Date July 11, voltage rating 4160GRDY/2400, HV AL, Impedance 5.80, low voltage 480Y/277, LV 30, mineral oil 329 gallons.
SEE UPDATED SOW FOR FULL REQUIREMENTS
Update #1 ·
SCOPE: The Contractor shall provide all personnel, equipment, tools, materials, supervision, and other items and services necessary to remove and dispose of existing airfield lighting transformers and replace with new (Fig. 1-11) at the U.S. Coast Guard, Base Cape Cod, on Joint Base Cape Cod, Buzzards Bay, MA, 02542. Existing transformers: Contractors shall verify transformer specifications. Transformer 413 (Fig. 1-3), adjacent to building 614 and runway 23. MANUFACTURER - McGraw Edison, Power System Division, Canonsburg, PA, 15317, single phase, 60 hertz, KVA 37 ½, 65° RISE, serial number 74ZD743004, voltage rating 4160GRD.Y/2400x12470GRD.Y/7200x13800GRD.Y/7970 240/120, cat nc. AAVL 115079A-37-K1, class OA, % IMP. 1.9 - 1.8, WDG MAT L.V. AL HV CU, wt.lb. 855, H.V. CONNECTION: VOLTAGE 2400 – SWITCH POSITION 2.4, VOLTAGE 7200 – SWITCH POSITION 7.2, VOLTAGE 7970 – SWITCH POSITION 7.9 Transformer 523 (Fig. 4-6), adjacent to building 614 and runway 14, MANUFACTURER - McGraw Edison, Power System Division, Canonsburg, PA, 15317, single phase, 60 hertz, KVA 37 ½, 65° rise, serial number 73ZE858030, voltage rating 4160GRD.Y/2400x12470GRD.Y/7200x13800GRD.Y/7970 240/120, cat nc. AAVL 115079A-37-K1, class OA, % imp. 1.9 - 1.8, WDG MAT L.V. AL HV CU, wt.lb. 855, H.V. CONNECTION: VOLTAGE 2400 – SWITCH POSITION 2.4, VOLTAGE 7200 – SWITCH POSITION 7.2, VOLTAGE 7970 – SWITCH POSITION 7.9 Transformer 232177 (Fig. 7-9), adjacent to building 3181 parking. MANUFACTURER - ABB, Power System Division, Jefferson City, MD, 21755, Three phase distribution, 60 hertz, KVA 1500/1680, 55/65° RISE, style number F3HF147L66, serial number 11JC572250001, MFG Date Jun-11, voltage rating 22860GRDy13200, HV BIL KV 125, HV MTL AL, % Impedance 5.75, Low voltage 4160Y/2400, LV BIL KC 60, LV MTL AL, Mineral Oil 513 Gallons. NOTE: The Contractor shall investigate and determine the existence of oil leaks and provide analysis/feasibility for replacement or repair. Option Bid: Transformer 575 (Fig. 10-12), adjacent to building 195 and runway 5, Manufacturer Southeastern Transformer Co, Dunn, NC, single phase, 60 hertz, KVA 15, % imp. 3.6, serial number 1019102, volts 12470GRDY/7200-240/120.
SEE SOW FOR FULL REQUIREMENTS
Files
| File | Type | Posted |
|---|---|---|
| SOW Replace (4) Airfield Transformers .pdf | ||
| 20260206_080225.jpg | JPG image | |
| 20260206_080243.jpg | JPG image | |
| SOW Replace Airfield Transformers (3) with (1) option.doc | DOC document | |
| Transformer_Standard Form 1449 - Solicitation_Contract_Order for Commercial Products and Commercial Services.pdf | ||
| DBA WAGES BARNSTABLE COUNTY.txt | TXT text file | |
| SOW Replace Airfield Transformers (3) with (1) option.doc | DOC document |