500 KVA Liquid Fill Pad Mount Transformer Type

Closed Solicitation Posted

Solicitation number
47QSSC24Q8901
Agency
Responses due
Set-aside
No set-aside

Opportunity facts

Place of performance
San Diego, California, United States

Notice details come from SAM.gov. Updated .

About this opportunity

The GSA Federal Acquisition Service is seeking to procure one 500 KVA Liquid Fill Pad Mount Transformer Type, or equal, through this solicitation. The transformer must meet specific requirements, including a 12470 Delta high voltage and 480Y/277 low voltage, 3-phase, 60Hz configuration with various features and tests. Pricing will be evaluated for award, with no minimum order requirement. Vendors must provide descriptive literature to show compliance with the item purchase description and complete all required solicitation provisions and clauses. The offer due date is 9/3/2024.

This is an unrestricted solicitation, not set aside for any socioeconomic program. The government intends to evaluate quotes and make a single award without discussions. Delivery is required within 36 weeks after receipt of order to any CONUS location. The place of performance is San Diego, CA, USA. There are no incumbent contractors mentioned, and the government has not provided any estimated award value or budget range.

Notice text

Product: 500 KVA Liquid Fill Pad Mount Transformer Type, or Equal

MPD Naval Base San Diego is requesting a 500KVA fluid filled 12470-480/277 3Ph Pad mount Transformer 

^HITACHI 500 KVA Liquid Filled Padmounted Transformer Type. 

Padmounted 

HV 12470 Delta LV-480Y/277 3P 60HZ 

Description: 

Type CU/CU 

Padmounted Transformer Fluid Natural Ester Fluid 

Core Grain Oriented Steel Phase 3 Phase 

Frequency 60 Hz 

Average Winding Rise 65 °C Ambient Temperature 30 °C High Voltage 12470 Delta High Voltage Taps +2 -2 2.5%High Voltage BIL 95kV BIL Low Voltage 480Y/277 

Low Voltage BIL 30kV BIL Low Voltage Neutral XO bushing with ground strap 

Feed Configuration Loop feed Color Bell Green (Munsell 7GY 3.29/1.5) 

Customer Specification NONE Features (included in price): TANK & CABINET 

Dry Nitrogen Blanket 

304L Stainless Steel Transformer (Tank+Base+Cabinetry) 

6 parking stands 

Full Tank Weather cover Seismic rated transformer design with seismic anchors 

Penta-head cabinet handle bolt SST hardware 

GROUNDING 

2-hole ground pads (1 in HV and 1 in LV) 

BUSHINGS 

Threaded stud LV bushings x 4 Load break inserts 25 kV (dead front) x 6 

ANSI C57.12.34 Fig 9&11 HV 

bushing pattern (minimum) 

200-amp HV bushing wells x 6 

6-hole NEMA spade terminals x 4 Spade Supports 

ANSI C57.12.26 Fig 3&4a minimum stgrd LV bushing pattern ARRESTERS 

12 kV MCOV 10.20 elbow arrester - 25 kV interface x 3 

FUSES 

Oil retaining valve on bayonet x 3 

Scoop drip shield x 3 

Bayonet expulsion fuse no isolation link x 3 

Oil-immersed partial range current limiting fuse x 3 

Spare current limiting fuses x 3 SWITCHES 

4-position 200-amp T-blade make before break (closed transition) 

MONITORING 

Thermometer w 2 alarm contacts 1 NO & 1 NC each Qualitrol 

167-288-01 p/n 30C6637H01 Pressure Vac Gauge with Bleeder & Contacts 

Schrader valve 

Minco temperature sensor 

Liquid Level Gauge Qualitrol 

032-35E p/n 2810777H01 with one high and one low contact both are 

1 NO & 1.NC 

Large pressure relief device w 

INO & 1NC Contact 208-60F p/n 2B12401H01 

Pressure Relief Valve 

FITTINGS 

Drain valve and sampler MARKINGS 

Three (3) DANGER HIGH VOLTAGE Signs 

Non-PCB label 

UL Listed on Nameplate 

Stainless steel nameplate 

Fuse operation warning label 

"Non-PCB" on Nameplate 

Mr Ouch DANGER label internal OTHER 

9.5" x 17.5" Tank Handhole Cover 24" deep cabinet 

DOE Efficiency (2016) 

TESTS 

(1918DGA) DGA Before Shipment Six-hour leak test 

Contains less-flammable biodegradable natural ester fluid with no detectable level of PCB, less than 1PPM, at the time of manufacture. 

Files

File Type Posted
Form 1449-N6247A41917034.pdf PDF
RFQ N6247A41917034 - Transformer.pdf PDF

Similar open opportunities

Opportunity Agency Set-aside Responses due
Purchase Olsun Electrics 225 KVA Transformer San Diego, California 92136, United States · NAICS 334416 Federal Acquisition Service No set-aside
Purchase Olson Electrics 300k Pad Mount Transformer San Diego, California 92136, United States · NAICS 334416 Federal Acquisition Service No set-aside
Transformer, power NAICS 334416 Naval Supply Systems Command No set-aside
Power distribution NAICS 335311 Land and Maritime No set-aside