30 CES - Pad Mount Transformers (2 of 2)

Closed Solicitation Posted

This opportunity was awarded. See the award notice from .

Solicitation number
FA461025Q0034
Agency
Responses due
Set-aside
Total Small Business

Opportunity facts

Place of performance
Lompoc, California 93437, United States

Notice details come from SAM.gov. Updated .

About this opportunity

The Department of the Air Force Space Command is seeking five phase pad-mounted transformers with specific voltage ratings ranging from 112.5 KVA to 750 KVA for the 30th Contracting Squadron at Vandenberg Space Force Base. The transformers must meet rigorous technical specifications, including all stainless-steel construction (304L or 316L grade), dead-front design, copper windings, and compliance with 2016 DOE Efficiency Standards. The solicitation requires vendors to be registered in the System for Acquisition Management (SAM) and submit pricing valid for 90 days. Key technical requirements include specific features such as "Pentahead" cabinet locking mechanisms, externally clamped LV bushings, and a Munsell-Green exterior finish. The solicitation is open until May 30, 2025, with the procurement number FA461025Q0034 and an estimated performance period of 6 months after award.

This contract opportunity is set aside for total small business participation within the Power, Distribution, and Specialty Transformer Manufacturing sector (NAICS 335311), with a size standard of 800 employees. The place of performance is Lompoc, California, and the procurement involves detailed technical specifications for transformers including specific electrical requirements, oil-filled design, and comprehensive testing protocols. The transformers must feature specific characteristics like a two-position load break primary switch, five-position tap changer, automatic pressure relief device, and dial-type gauges for oil temperature and liquid level monitoring. While no incumbent contractors are mentioned, the solicitation indicates a need for precise engineering specifications and compliance with military electrical standards. The contract will require vendors to provide transformers with guaranteed performance metrics, including an average coil winding temperature of 65C rise over a 30C ambient air temperature.

Notice text

2 versions

Update #2 · Latest ·

**Reason for updated solicitation: UPDATED pricing sheet**

Five (5) phase pad-mounted transformers shall have the following voltage ratings: 
 
•112.5 KVA, 208Y/120, 12 kV
•150 KVA, 480Y/277, 12 kV
•300 KVA, 480Y/277, 12 kV
•500 KVA, 480Y/277, 12.47 kV
•750 KVA, 480Y/277, 12 kV
 
In addition, the five phase pad-mounted transformers shall meet VSFB electrical requirements below: 
 
•All stainless-steel construction (includes tank, cabinet, base, radiators, fasteners, hinges, etc.),stainless-steel grade shall be 304L or 316L (if available).
•"Pentahead" cabinet locking mechanism/device.
•Dead-Front construction (HV-200A load break elbows with shield adapters).
•Externally clamped LV bushings with threaded copper stud for full load current below 2,100.amperes  - NEMA spades shall be provided per ANSI hole requirements.
•Radial feed or Loop feed
•Frequency: 60Hz.
•Windings: HV/LV copper
•Mineral Oil-filled (Non-PCB): Type FR-3 Fluid.
•Standard impedance.
•Mild steel high-voltage/low-voltage compartment barriers.
•Cooling fins.
•Proper grounding provisions.
•Dial type gauges for oil temperature, liquid level and pressure/vacuum.
•Bay-O-Net fuses & current-limiting fuses: properly sized  - additionally, the transformer shouldbe equipped with three spare fuses.
•Two-position "ON/OFF" load break primary switch
•5-position tap changer: (-5%, -2 ½ %, 0, +2 ½ %, +5%)
•Automatic pressure relief device mounted on the terminal compartment.
•Oil drain valve with sampling device, and an oil-fill/oil-level plug.
•Nameplate and NEMA safety labels: include a "UL Listed" symbol on ratings label andnameplate.
•Compliant with 2016 DOE Efficiency Standard.
•Four (4) lifting lugs.
 
•Entire exterior of the pad-mount transformer and terminal components shall be painted with aMunsell-Green, outdoor color-finish.
•Guaranteed to have an average coil winding temperature of 65°C rise over an average ambient airtemperature of 30°C when operated at rated voltage and load conditions.
•Provide DGA test to verify conformance to performance requirements as outlined in the latestrevisions of ANSI C57.12.00 and ANSI C57.12.90.
    
 

Update #1 ·

Five (5) phase pad-mounted transformers shall have the following voltage ratings: 
 
•112.5 KVA, 208Y/120, 12 kV
•150 KVA, 480Y/277, 12 kV
•300 KVA, 480Y/277, 12 kV
•500 KVA, 480Y/277, 12.47 kV
•750 KVA, 480Y/277, 12 kV
 
In addition, the five phase pad-mounted transformers shall meet VSFB electrical requirements below: 
 
•All stainless-steel construction (includes tank, cabinet, base, radiators, fasteners, hinges, etc.),stainless-steel grade shall be 304L or 316L (if available).
•"Pentahead" cabinet locking mechanism/device.
•Dead-Front construction (HV-200A load break elbows with shield adapters).
•Externally clamped LV bushings with threaded copper stud for full load current below 2,100.amperes  - NEMA spades shall be provided per ANSI hole requirements.
•Radial feed or Loop feed
•Frequency: 60Hz.
•Windings: HV/LV copper
•Mineral Oil-filled (Non-PCB): Type FR-3 Fluid.
•Standard impedance.
•Mild steel high-voltage/low-voltage compartment barriers.
•Cooling fins.
•Proper grounding provisions.
•Dial type gauges for oil temperature, liquid level and pressure/vacuum.
•Bay-O-Net fuses & current-limiting fuses: properly sized  - additionally, the transformer shouldbe equipped with three spare fuses.
•Two-position "ON/OFF" load break primary switch
•5-position tap changer: (-5%, -2 ½ %, 0, +2 ½ %, +5%)
•Automatic pressure relief device mounted on the terminal compartment.
•Oil drain valve with sampling device, and an oil-fill/oil-level plug.
•Nameplate and NEMA safety labels: include a "UL Listed" symbol on ratings label andnameplate.
•Compliant with 2016 DOE Efficiency Standard.
•Four (4) lifting lugs.
 
•Entire exterior of the pad-mount transformer and terminal components shall be painted with aMunsell-Green, outdoor color-finish.
•Guaranteed to have an average coil winding temperature of 65°C rise over an average ambient airtemperature of 30°C when operated at rated voltage and load conditions.
•Provide DGA test to verify conformance to performance requirements as outlined in the latestrevisions of ANSI C57.12.00 and ANSI C57.12.90.
    
 

Files

File Type Posted
Atch 2_Price Sheet_R.xlsx XLSX spreadsheet
Atch 1_Transformers_SOW.pdf PDF
Atch 3_ClausesProvisions.pdf PDF
Transformers_RFQ.pdf PDF
Atch 2_PricingSheet.xlsx XLSX spreadsheet

Notice history

Notice Type Posted
30 CES - Pad Mount Transformers (2 of 2) Award Award Notice
This notice Latest solicitation Solicitation

Similar open opportunities

Opportunity Agency Set-aside Responses due
Transformer, power NAICS 334416 Naval Supply Systems Command No set-aside
Transformer, power NAICS 334413 Land and Maritime Total Small Business
Transformer, psrl NAICS 334416 Land and Maritime No set-aside
Transformer, power NAICS 335311 Land and Maritime No set-aside
Transformer assembl, in repair/modification of NAICS 334416 Naval Supply Systems Command No set-aside

On GovTribe

Work this opportunity

  • Track it in your pipeline
  • Find teaming partners
  • Similar opportunities
  • Ask GovTribe AI about this opportunity