zmp-1203733-m001 Rev A Signed.pdf

PDF 590 KB Posted

Attached to
Minneapolis Air Route Traffic Control Center (ZMP) Multiple Projects
Solicitation number
697DCK-25-R-00392
Issued by

About this file

This engineering drawing details a boiler stack and breeching replacement project for the Federal Aviation Administration's Air Route Traffic Control Center (ARTCC) in Minneapolis. The technical drawing provides a comprehensive plan for replacing the existing boiler exhaust stack in the Admin Wing basement, including specific requirements for new 20" ID stainless steel double-walled metal vent stacks, new metal breeching, and associated supporting infrastructure. Key technical specifications include removing the existing 30" OD stack, installing new stack pipes with 1" air space between walls, adding a 15"x15" bolted hand door, providing steel supports and bracing, and ensuring proper flashing, insulation, and weather sealing.

The drawing includes detailed notes requiring the contractor to verify existing conditions, coordinate work with the FAA Contracting Officer's Representative (COR) to minimize operational disruptions, perform boiler tuning and combustion reports after installation, and conform to all applicable ordinances and codes. The project is part of a broader solicitation (697DCK-25-R-00392) for multiple improvement projects at the Minneapolis ARTCC, with an estimated price range between $400,000-$500,000. The technical documentation emphasizes professional workmanship, precise measurements, and maintaining existing system functionality during the replacement process.

View the file

Other files

Show all 13

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

8'-0" 12'-0" 20'-0" 20'-0" 16'-0"

WATER HEATERS

DOMESTIC HOT

SOFTENER

WATER

SEE DETAIL 2

BUS

ESSENTIAL

WALL STACK

NEW DOUBLE

M024

B

BOILER ROOM

ROOM

MONITORING

CHILLER ROOM

B116

VESTIBULE

MECHANICAL ROOM

B O

IL

E R

B

B

B O

IL

E R

B

A B

O

IL

E R

B

C

COVERED DRAINAGE TRENCH

PUMP

P-2C

PUMP

P-2B

PUMP

P-2A

A C

A

A C

B

(7' ABV FLOOR)

EXPANSION TANK

HOT WATER

DOMESTIC

FUEL TANK

285 GALLON

A-6A-5A-4A-3A-2A-1

C H

IL

L E

R

C H

IL

L E

R

C H

IL

L E

R

C H

IL

L E

R

B115

COMPRESSORS

CAFETERIA

P-1D

PUMP

P-1C

PUMP

P-1B

PUMP

P-1A

PUMP

B117

DOWN

RAMP

DN

UP

B118

B119

AHU-24 AH-23

AHU-21 AH-22

ABOVE

ROOF

CONC

UP

PUMPS

SUMP

N

SCALE: 1/8" = 1'-0"

PARTIAL ADMIN WING BASEMENT PARTIAL PLAN

A

1 8

TO BLR 1A

TANK

BRINE

ELEV. 86.5' BASEMENT FLOOR

ELEV. 100.5' FIRST FLOOR

ELEV. 112.0' TPO ROOF

ENCLOSURE

EXISTING

ELEV. 123.0' ADMIN ROOF

BALL VALVE

EXISTING AND NEW WORK

POINT OF CONTACT BETWEEN

WING

ADMINISTRATION

CONTROL WING

WING

AUTOMATION

NOT TO SCALE

ELEVATION VIEW - CHIMNEY STACKB

LEGEND:

BLR 1C

TO

BLR 1B

TO

1A

TO BLR

WITH LIMITED SPACE

CONE ANGLE EVEN

MAX 10 DEGREE

KEY PLAN

8' 0 8' 16'

SCALE: 1/8" = 1'-0"

2 4 5

SEE DETAIL 1 (TYP)

WALL STACK

NEW DOUBLE

WALL STACK

NEW DOUBLE

WALL STACK

NEW DOUBLE

NOT TO SCALE

STACK/BREECHING TRANSITION DETAIL

NOT TO SCALE

CLEANOUT WITH DRAIN

EXIST BRICK WALL

L4x4x1/4"

VERTICAL ANGLE)

EMBED = 3 1/8" (AT EACH

W/ A36 ROD AND A MIN

HILTI 1/2" DIAM HY270(6)

DIAGONAL STRIPES AT 4" OC

YELLOW WITH 1" WIDE BLACK

PAINT MTL FRAMING HAZARD

L6x6x5/16"

STACK,TYP

NEW FLUE

MTL HOOD

NEW FIELD FABRICATED

ROOF ASSEMBLY

ROOF DECKING

PATCH AND REPAIR

EXISTING ROOF JOIST

M

IN

SCALE: 1/2" = 1'-0"-

5/16"

5/16"

5/16"

5/16"

FLUE STACK SUPPORT DETAIL

L4x4x1/4"

HOOD BELOW

NEW METAL RAIN

WALL

EXIST BRICK

STACK, TYP

NEW BOILER

L4x4x1/4"

L6x6x5/16"

FLUE STACK

WELDED TO METAL

CONTINUOUSLY

HATCHING

AS INDICATED BY

SHEET METAL CAP

FRAME, TYP

WELD TO NEW

(VIF)

TYP

1/4"

SCALE: 1/2" = 1'-0"-

WELD BAND TO FRAME

EXIST HOT WATER VENT

FLUE STACK SUPPORT PLAN DETAIL

FEDERAL AVIATION ADMINISTRATION

DEPARTMENT OF TRANSPORTATION

REV DESCRIPTION JCN

DATE

REDLINE

APVD

SUBMITTED BY APPROVED BY

JCN

DRAWN

CHECKED

REV

ISSUED BY

H

G

F

E

D

C

B

A

8 1234567

DATE

DRAWING NO

DESIGNED

REVIEWED BY

/1

/2

:4

:3

P

M P lo tt e d b y S

R V

C -C

A E

G -E

D M

S -C

O O

R D

DATE

APPROVED

z m p -1

-m

.d w g

8 234567

H

G

F

E

D

C

A

B

GENERAL NOTES:

NEW WORK NOTES:

1) ALL WORK, MATERIAL AND INSTALLATION SHALL CONFORM TO THE

REQUIREMENTS OF THE ORDINANCE AND CODE HAVING JURISDICTION.

2) ALL WORK SHALL BE IN ACCORDANCE WITH THE PROJECT SPECIFICATION.

3) ALL WORK SHALL BE PERFORMED IN A NEAT, ACCURATE, WORKMAN-LIKE AND

PROFESSIONAL MANNER.

4) CONTRACTOR SHALL VERIFY ALL DEMOLITION WORK, EXISTING CONDITIONS,

DIMENSIONS AND NEW INSTALLATION PRIOR TO COMMENCEMENT OF WORK.

EXISTING HOT WATER HEATER VENT IS TO BE REMAIN IN PLACE AND

PROTECTED.

5) CONTRACTOR SHALL COORDINATE AND SCHEDULE ALL DEMOLITION & NEW

CONSTRUCTION WORK WITH FAA COR TO MINIMIZE OPERATION DISRUPTIONS

WHILE WORK IS IN PROGRESS.

TRANSITIONS, ELBOWS, ETC.

FIBER INSULATOR. REPLACEMENT SHALL INCLUDE ALL REQUIRED STEEL SUPPORTS,

METAL BREECHING WITH 1" SPACING BETWEEN WALLS AND FILLED WITH HIGH TEMPERATURE

REMOVE EXISTING BREECHING AND REPLACE WITH 16" ID STAINLESS STEEL DOUBLE WALLED

TEE AND ONE 45 DEGREE TEE FOR CONNECTIONS AND ALL REQUIRED TRANSITION PIECES.

1" AIR SPACE BETWEEN WALLS. PROVIDE CLEAN OUT SECTION, BOLT FLANGE, ONE 90 DEGREE

NEW STACK SHALL TO BE 20" ID STAINLESS STEEL DOUBLE WALLED METAL VENT STACKS WITH

REMOVE EXISTING 30" OD STACK INCLUDING RAIN HOOD AND REPLACE WITH NEW STACK PIPE.

FOR VALVES.

DEGREE ELBOW PIPE, 1 1/2" DRAIN LINE WITH BALL VALVE AND PIPE CAP. PROVIDE SUPPORTS

MODIFY STACK ENCLOSURE TO INCLUDE A ACCESSIBLE 15"X15" BOLTED HAND DOOR, 90

PROVIDE BRACING FOR VERTICAL VENT STACK.

SUPPORT TO CHIMNEYS AT EACH FLOOR AND PROVIDE EXPANSION JOINT/BAND AS REQUIRED.

NEW VENT STACKS INSTALLATION. PROVIDE GUY WIRES AND RIGID BRACES TO GIVE LATERAL

MODIFY EXISTING SUPPORTS OR PROVIDE ADDITIONAL STEEL SUPPORTS AS REQUIRED TO FIT

STACK HEIGHT AND ELEVATION. NEW STACK HEIGHT SHOULD BE SIMILAR TO EXISTING.

ELEVATION AND DIMENSIONS SHOWN ARE APPROXIMATE. CONTRACTOR TO VERIFY EXISTING

STEEL.

LIGHTNING RODS AND CABLES PER EXISTING CONDITIONS. RAIN HOOD TO BE 304 STAINLESS

PROVIDE REQUIRED RAIN HOODS AND SUPPORTS. CONTRACTOR TO RECONNECT ALL EXISTING

REMOVE AND DISPOSE OF EXISTING ENCLOSURE.

PROVIDE NEW HANGERS FOR SUPPORT OF HORIZONTAL BREECHING RUNS.

THERMAL PROTECTION.

FLASHING FOR WEATHER PROTECTION. PROVIDE INSULATION BELOW NEW METAL CAP TO ENSURE

PROVIDE 22-GA ALUMINIZED STEEL ROOF FLASHING AND 20-GA ALUMINIZED STEEL COUNTER

PROVIDE COMBUSTION REPORTS FOR BOTH FUELS.

AFTER INSTALLATION OF NEW BOILER BREECHING AND STACKS PERFORM BOILER TUNING AND

IS

S

U E

D F

O R

E D

M

06/30/2022

MGR: ENGINEERING

FARMINGTON

AZMP-1203733-M001

ARTCC

ADMIN WING BASEMENT

BOILER STACK & BREECHING REPLACEMENT

PLAN, ELEV. VIEWS, DETIALS AND NOTES

z m p -1

-m

.d w g

ENROUTE/FSS

ENGINEERING SERVICES

ATO - TECHNICAL OPERATIONS CENTRAL SERVICE AREA

C O

N S

T R

U C

T

IO

N

THIS DRAWING PRODUCED ON THE AGL REGION MICROSTATION SYSTEM

PROJECT ENGINEER

1203733

A 01/08/2024 ADDENDUM REPLACE BOILER STACK 1203733 01/08/2024 CAO

MN

10 PROVIDE FIRESTOP AND WEATHER SEAL FOR ALL PENETRATIONS.

zmp-1203733-m001

2025-07-09T10:01:49-0500
FRANCISCO MONTES
2024-01-19T13:53:32-0600
CODY A OLSON