Y22-780_Drawings.pdf
PDF 13 MB Posted
- Attached to
- South Water Reclamation Facility North Plant Effluent Pump Station Pre-Engineered Building
- Solicitation number
- Y22-780
- Issued by
- Orange County, Orlando City, Florida
About this file
These are comprehensive construction documents prepared by Atkins for the Orange County Utilities Department for the South Water Reclamation Facility North Plant Effluent Pump Station Pre-Engineered Electrical Building project located in Orlando, Florida. The documents, dated February 2022, include architectural, structural, mechanical, electrical, and instrumentation drawings for a new pre-engineered electrical building with detailed plans for site work, grading, foundation, electrical systems, HVAC, and other technical specifications. The project involves constructing a 900 square foot electrical building with associated infrastructure, including electrical equipment, switchgear, motor control centers, grounding systems, lighting, and control systems.
The project documents indicate a total estimated project cost of $2,111,384.36, with bid documents prepared for Orange County Government and sealed offers originally scheduled to be accepted up to 4:00 pm EST on Thursday, March 17, 2022. The electrical building will be part of the South Water Reclamation Facility's North Plant, featuring a precast concrete structure with specific design considerations for electrical infrastructure, including 12.47kV main switchgear, motor control centers, and comprehensive instrumentation and control systems. The drawings provide extensive technical details on electrical distribution, grounding, lightning protection, fire alarm systems, and integration with existing plant infrastructure, suggesting a complex upgrade to the facility's electrical capabilities.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Y22-780.pdf | ||
| Y22-780_Specifications.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Orange County South Water Reclamation Facility North Plant Effluent Pump Station
CONSTRUCTION DOCUMENTS
APRIL 20, 2020
482 SOUTH KELLER ROAD
ORLANDO, FLORIDA 32810
ORANGE COUNTY MAYOR
JERRY DEMINGS
DISTRICT 1 COMMISSIONER
BETSY VANDERLEY
DISTRICT 2 COMMISSIONER
CHRISTINE MOORE
DISTRICT 3 COMMISSIONER
MAYRA URIBE
DISTRICT 4 COMMISSIONER
MARIBEL GOMEZ CORDERO
DISTRICT 5 COMMISSIONER
EMILY BONILLA
DISTRICT 6 COMMISSIONER
VICTORIA P. SIPLIN
Pre-Engineered Electrical Building
ORANGE COUNTY, FLORIDA
ORANGE COUNTY UTILITIES DEPARTMENT
ENGINEERING DIVISION
PLANS PREPARED BY:
6965 PIAZZA GRANDE AVE., STE. 412
ORLANDO, FLORIDA 32835
BOARD OF COUNTY COMMISSIONERS
N.T.S.
N
PROJECT
LOCATION
KEY WEST
MIAMI
WEST PALM BEACH
OKEECHOBEE
FT. PIERCE
LAKE
OKEECHOBEE
MELBOURNEHAINES CITY
KISSIMMEE
ORLANDO
LEESBURG
LAKELAND
TAMPA
BRADENTON
FT. MYERS
DAYTONA BEACHOCALA
GAINESVILLE
ST. AUGUSTINE
JACKSONVILLE
LA
KE
C
IT
Y
PERRY
TALLAHASSEE
APALACHICOLA
PANAMA
CITY
MARIANNA
P E
N S
A C
O L
A
LOCAL OFFICE:
482 SOUTH KELLER RD
ORLANDO, FL 32810
TEL. 407.647.7275
FAX. 407.806.4500
CORPORATE OFFICE:
4030 W. BOY SCOUT BLVD
TAMPA, FLORIDA 33607
FBPR CERTIFICATE OF
AUTHORIZATION NO.24
www.atkinsglobal.com
SHEET NO. REV.
S H
E E
T T
IT
L E
P R
O J E
C T
C L
IE
N
T
O R
A N
G E
C O
U N
T Y
F
L O
R
ID
A
S W
R F
N O
R T
H P
L A
N T
E F
F L
U E
N T
P U
M P
S T
A T
IO
N
P R
E -E
N G
IN
E
E R
E D
E L
E C
T R
IC
A
L B
U
IL
D
IN
G
DO NOT SCALE
IS
S
U E
D F
O R
IS
S
U E
D F
O R
R E
V D
A T
E R
E V
D A
T E
NO
TI
CE
Th e in fo rm at ion in th is do cu m en t w as p re pa re d by A
TK
IN
S, In c.
W hil e
AT
KI
NS
h as ta ke n all re as on ab le st ep s t o as su re th e ac cu ra cy o f t he in fo rm at ion c on ta ine d in th is do cu m en t, it ca nn ot g ua ra nt ee th at ch an ge s or a lte ra tio ns t o th is do cu m en t w ill no t be m ad e by p er so ns o th er th an
A
TK
IN
S pe rs on ne l a fte r t he d oc um en t le av es th e po ss es sio n of A
TK
IN
S.
C ha ng es o r a lte ra tio ns m ay b e sa fe ty re la te d an d re su lt i n da m ag e to p ro pe rty , p er so na l in ju ry o r d ea th
. I f v er ific at io n of th e inf or m at ion co nt ai ne d in th is do cu m en t is n ee de d, co nt ac t s ho ul d be m ad e di re ctl y wi th
A
TK
IN
S.
Th is do cu m en t m us t b e co m pa re d to th e or igi na l h ar d co py
, w ith c er tifi ed ra ise d se al if ap pl ica ble , i n or de r t o in su re th e ac cu ra cy o f t he in fo rm at ion c on ta in ed th er ei n an d to fu rth er in su re th at n o ch an ge s, alt er at io ns o r m od ific at io ns h av e be en m ad e to th e do cu m en t.
No re lia nc e sh ou ld e ve r b e m ad e on a d oc um en ta tio n tra ns m itt ed o r re vie we d by co m pu te r o r o th er e le ctr on ic m ea ns u nl es s i t is fi rs t c om pa re d to th e or ig ina l.
AT
KI
NS
m ak es n o wa rra nt ie s, e xp re ss o r i m pl ie d, co nc er nin g th e ac cu ra cy of th e inf or m at io n co nt ain ed in a ny d oc um en t t ra ns m itte d or re vie we d by c om pu te r o r ot he r e lec tro ni c m ea ns
APPROVED:
CHECKED:
DRAWN:
PROJECT ENG:
JOB NO.:
D A
V
ID
L
H E
ID
E
M A
N
P .E
F
L O
R
ID
A R
E G
N
O
C O
V E
R S
H E
E T
A N
D S
H E
E T
I N
D E
X
REP
TJF
DLH
G-001
DLH
100061852
DRAWING INDEX
SHEET
NUMBER SHEET NAME SCALE
G-000 COVER SHEET AND SHEET INDEX NO SCALE
S-001 GENERAL NOTES & WIND DESIGN CRITERIA NO SCALE
S-101
EFFLUENT PUMPING STATION - DEMOLITION
PLAN & TYPICAL DETAILS
VARIES
S-102
EFFLUENT PUMP STATION ELECTRICAL
BUILDING - FOUNDATION PLANS & DETAILS
VARIES
LS-001 LIFE SAFETY 1/4" = 1'-0"
VARIES
C-300 GRADING PLAN 1" = 10'-0"
M-001 HVAC SYMBOLS, LEGEND & GENERAL NOTES NO SCALE
M-101 HVAC PLAN 1/4" = 1'-0"
C-001 GENERAL NOTES & ABBREVIATIONS NO SCALE
C-100 DEMOLITION AND EROSION CONTROL PLAN 1'' = 10'-0"
C-190 EROSION CONTROL NOTES AND DETAILS NO SCALE
C-200 SITE PLAN 1" = 10'-0"
A-101.1 FLOOR PLAN & ELEVATIONS 1/4" = 1'-0"
A-301 ROOF PLANS AND SECTIONS VARIES
A-871 DETAILS
C-500 SITE DETAILS NO SCALE
A-131 REFLECTED CEILING PLAN - LEVEL 01 1/4" = 1'-0"
P A
U L R
IC
H
A R
D D
IC
IC
C O
P
.E
F L O
R
ID
A R
E G
N
O
C-501 SITE DETAILS NO SCALE
DRAWING INDEX
SHEET
NUMBER SHEET NAME SCALE
E-001 SYMBOLS, NOTES & ABBREVIATIONS NO SCALE
E-002 OVERALL SITE PLAN 1" = 80'-0"
E-003
12.47KV MAIN SWITCHGEAR SINGLE LINE
DIAGRAM
NO SCALE
E-004
EFFLUENT PUMPING STATION EXISTING
SINGLE LINE DIAGRAM
NO SCALE
E-005
EXISTING MCC-USFA & MCC-USFB
SINGLE LINE DEMOLITION DIAGRAMS
NO SCALE
E-006
EFFLUENT PUMPING STATION PROPOSED
SINGLE LINE DIAGRAM
NO SCALE
E-007 MCC-USFA PROPOSED SINGLE LINE DIAGRAM NO SCALE
E-008 MCC-USFB PROPOSED SINGLE LINE DIAGRAM NO SCALE
E-009 5K SWITCHGEAR FRONT ELEVATIONS NO SCALE
E-010 MCC-USFA & MCC-USFB FRONT ELEVATIONS NO SCALE
E-012
EFFLUENT PUMPING STATION
DEMOLITION PLAN
3/16" = 1'-0"
E-013
EFFLUENT PUMPING STATION
PROPOSED PLAN
3/16" = 1'-0"
E-014
EFFLUENT PUMP STATION ELECTRICAL
BUILDING GROUNDING & LIGHTING PLAN
1/4" = 1'-0"
E-015
PANEL AND LIGHTING SCHEDULES
NO SCALE
E-016
ELECTRICAL DETAILS I
NO SCALE
E-011 ELEMENTARY DIAGRAMS NO SCALE
E-018
ELECTRICAL DETAILS III
NO SCALE
E-019
4160 SWITCHGEAR BREAKER CONTROL
CONSOLE AND ELEVATIONS
NO SCALE
E-020
4160 SWITCHGEAR BREAKER CONTROL
CONSOLE SCHEMATIC
NO SCALE
FA-001
INSTRUMENTATION SYMBOLS &
ABBREVIATIONS
NO SCALE
FA-002
INSTRUMENTATION P&ID
NO SCALE
I-001
INSTRUMENTATION PLC SYSTEM RISER SHEET
NO SCALE
E-017
ELECTRICAL DETAILS II
NO SCALE
CONSTRUCTION
DOCUMENTS
JUNE 2021
E-021
EFFLUENT PUMP STATION ELECTRICAL
BUILDING GROUNDING & LIGHTING RISER
NO SCALE
E-022
EFFLUENT PUMP STATION ELECTRICAL
BUILDING GROUNDING & LIGHTING PLAN
NO SCALE
FIBER OPTIC SITE PLAN
SWRF SURGE FACILITY ELECTRICAL PLAN
I-002
I-003
I-004
SWITCHGEAR PROTECTIVE RELAY & POWER
MONITOR NETWORK ARCHITECTURE
NO SCALE
NO SCALE
NO SCALE
B
ID
S E
T
/2
FEBRUARY 2022
JWS
LOCAL OFFICE:
482 SOUTH KELLER RD
ORLANDO, FL 32810
TEL. 407.647.7275
FAX. 407.806.4500
CORPORATE OFFICE:
4030 W. BOY SCOUT BLVD
TAMPA, FLORIDA 33607
FBPR CERTIFICATE OF
AUTHORIZATION NO.24
www.atkinsglobal.com
SHEET NO.
REV.
S H
E E
T
T
I T
L E
P R
O J E
C T
C L I E
N T
O R
A N
G E
U
N T
Y
F
L O
R I D
A
S W
R F
N
R
T H
P
L A
F
L U
E N
T
P
U M
P
S
T A
T I O
N
P R
E E
N G
I N
E E
R E
D
E
L E
C T
R I C
A
B
U I L
D I N
G
I S
S U
D
R
I S
S U
R
R E
V
D A
T E
R E
V
D A
T E
APPROVED:
CHECKED:
DRAWN:
PROJECT ENG:
JOB NO.:
O S
C A
R
E
B
E R
M U
D E
Z
P
E
F L O
R I D
A
R
E G
N
O
OEB
100061852
GENERAL NOTES:
1. COORDINATE CONSTRUCTION UNDER THIS CONTRACT WITH ALL OTHER SITE CONSTRUCTION
AND/OR ADJACENT OFF SITE CONSTRUCTION.
2. PROVIDE EROSION AND SEDIMENTATION CONTROL MEASURES CONSISTING OF STAKED SILT
FENCES ALONG THE PROPOSED LIMITS OF CONSTRUCTION OR AS INDICATED ON THE
DRAWINGS. PROVIDE ADDITIONAL MEASURES AS NECESSARY TO AVOID ADVERSE IMPACTS TO
JURISDICTIONAL AREAS (WETLANDS OR WATER BODIES) AND OFF SITE LANDS AND WATER
BODIES. MAINTAIN THESE MEASURES DAILY UNTIL CONSTRUCTION ACCEPTANCE BY THE
OWNER'S AUTHORIZED AGENT AND THEN REMOVE AND LEGALLY DISPOSE OF SAID MEASURES.
3. FIELD SURVEY THE CLEARING LIMITS AND INSTALL STAKES WITH COLORED RIBBONS FOR
OWNER'S AUTHORIZED AGENT REVIEW AND APPROVAL PRIOR TO CONSTRUCTION. AFTER
APPROVAL, INSTALL ALL REQUIRED EROSION AND SEDIMENTATION CONTROL MEASURES
PRIOR TO CLEARING.
4. DURING CONSTRUCTION, THE OWNER'S AUTHORIZED AGENT SHALL REVIEW THE ENTIRE AREA
WITHIN THE CLEARING LIMITS AND MAY IDENTIFY EXISTING TREES TO REMAIN OR BE
RELOCATED. AT THE OWNER'S AUTHORIZED AGENT DIRECTION, REVISE THE CLEARING LIMITS
TO EXCLUDE THESE DESIGNATED AREAS AND PROVIDE EROSION CONTROL AND TREE
PROTECTION MEASURES IN ACCORDANCE WITH THE CONTRACT DOCUMENTS.
5. CLEAR, GRUB AND STRIP ALL AREAS WITHIN THE LIMITS OF CONSTRUCTION UNLESS
OTHERWISE NOTED.
6. SURVEYOR: WOOD ENVIRONMENTAL AND INFRASTRUCTURE SOLUTIONS, INC. DATE OF
SURVEY 02/07/19.
7. GEOTECH ENGINEER: INTERTEK PSI. DATE: 05/28/19
8. HORIZONTAL DATUM IS RELATIVE TO THE NORTH AMERICAN DATUM OF 1983, 2011
ADJUSTMENT WITH COORDINATES EXPRESSED IN FLORIDA STATE PLANE COORDINATE
SYSTEM, EAST ZONE (901), U.S. SURVEY FEET. ELEVATIONS ARE RELATIVE TO THE NORTH
AMERICAN VERTICAL DATUM OF 1988 (NAVD88) BASED ON THE FOLLOWING ORANGE COUNTY
ENGINEERING DEPARTMENT BENCHMARKS.
9. PROTECT ANY PUBLIC LAND CORNER MONUMENT LOCATED WITHIN THE LIMITS OF
CONSTRUCTION. IF IN DANGER OR IF DAMAGED, NOTIFY THE CONSTRUCTION MANAGER
IMMEDIATELY.
10.THE LOCATION OF ALL EXISTING UTILITIES AND DRAINAGE STRUCTURES SHOWN ARE BASED
ON AVAILABLE INFORMATION. PRIOR TO CONSTRUCTION, FIELD LOCATE ALL EXISTING
FACILITIES WITHIN AND ADJACENT TO THE LIMITS OF CONSTRUCTION.
11. ALL FLORIDA DEPARTMENT OF TRANSPORTATION PLANS REFER TO THE LATEST EDITION OF
THE FDOT STANDARD PLANS FOR ROAD CONSTRUCTION.
12.MAINTAIN DAILY RECORD DRAWINGS AT ALL TIMES DURING CONSTRUCTION. RECORD
DRAWINGS INFORMATION SHALL INCLUDE (AT A MINIMUM) HORIZONTAL LOCATIONS AND
INVERT ELEVATIONS (AND TOP ELEVATION IF APPLICABLE) OF ALL DRAINAGE AND UTILITY PIPE
SYSTEMS INCLUDING IRRIGATION SLEEVES. INFORMATION SHALL BE LEGIBLY HAND WRITTEN
ON THE MOST CURRENT SET OF CONSTRUCTION DRAWINGS, AS WELL AS TYPE WRITTEN IN
TABULAR FORMAT. UPON COMPLETION OF THE PROJECT SUBMIT ONE COMPLETE SET OF
RECORD DRAWINGS CERTIFIED BY A PROFESSIONAL LAND SURVEYOR REGISTERED IN THE
STATE OF FLORIDA, AND TWO SETS ON COMPACT DISK.
13.PRIOR TO THE START OF ALL APPLICABLE CONSTRUCTION ACTIVITIES, THE CONTRACTOR IS TO
COORDINATE WITH ALL JURISDICTIONAL AGENCIES AND UTILITY PROVIDERS.
14.IF HISTORICAL OR ARCHEOLOGICAL ARTIFACTS, SUCH AS INDIAN CANOES, ARE DISCOVERED
AT ANY TIME WITHIN THE PROJECT SITE, IMMEDIATE NOTIFICATION SHALL BE PROVIDED TO
THE FOLLOWING:
A. THE OWNER'S AUTHORIZED AGENT.
B. THE OWNER.
C. THE SOUTH FLORIDA WATER MANAGEMENT DISTRICT OFFICE (407-858-6100).
D. THE BUREAU OF HISTORIC PRESERVATION, DIVISION OF HISTORICAL RESOURCES, R.A.
GRAY BUILDING, 500 S. BRONOUGH ST., TALLAHASSEE, FL 32399-0250.
15.NO DISCHARGE OF CONTAMINANTS ONTO THE SITE OR INTO THE STORMWATER MANAGEMENT
SYSTEM SHALL BE PERMITTED AT ANY TIME.
16.DAMAGE TO PROPERTIES ADJACENT TO CONSTRUCTION AREAS SHALL BE PREVENTED BY
DELINEATING THE LIMITS OF CONSTRUCTION, AND INSTALLING SEDIMENT BARRIERS PRIOR TO
THE COMMENCEMENT OF CONSTRUCTION ACTIVITIES, THEREBY RETAINING SEDIMENT WITHIN
THE CONSTRUCTION AREA. CONTRACTORS SHALL BE REQUIRED TO ADEQUATELY MAINTAIN
THESE PROTECTION MEASURES AT ALL TIMES.
17.EROSION CONTROL SHALL BE MAINTAINED WITHIN CONSTRUCTION AREAS BY QUICKLY
STABILIZING DISTURBED AREAS TO PREVENT THE RELEASE OF SEDIMENT. THIS SHALL BE
ACCOMPLISHED USING GRASS COVER, SILT FENCES, AND OTHER MEANS ACCEPTABLE TO
OWNER'S AUTHORIZED AGENT, ENGINEER AND REGULATORY AGENCIES.
18.DURING CONSTRUCTION THE CONTRACTOR SHALL MODIFY OR RELOCATE THE SILT FENCE
(WITH OWNER'S AUTHORIZED AGENT PRIOR APPROVAL) TO ALLOW FOR ITS ACCESS AND TO
COMPLETE CONSTRUCTION. IT IS THE CONTRACTOR'S RESPONSIBILITY TO MAINTAIN
ADEQUATE EROSION CONTROL AT ALL TIMES.
19. ALL EROSION PREVENTION AND CONTROL MEASURES MUST BE INSPECTED AND APPROVED BY
ORANGE COUNTY COMPLIANCE PERSONNEL PRIOR TO ANY CONSTRUCTION ACTIVITIES.
REMOVAL OF THESE SAME EROSION CONTROLS AND PREVENTION MEASURES MAY BE DONE
ONLY AFTER AUTHORIZATION BY COUNTY COMPLIANCE PERSONNEL IS OBTAINED.
20.DURING CONSTRUCTION THE CONTRACTOR WILL PROVIDE TEMPORARY SEEDING AND
MULCHING FOR AREAS THAT HAVE BEEN CLEARED AND NOT REWORKED WITHIN 7 CALENDAR
DAYS DURING THE WET SEASON (APRIL THROUGH SEPTEMBER) AND 14 CALENDAR DAYS
DURING THE DRY SEASON (OCTOBER THROUGH MARCH). ALSO, ALL SIDE SLOPES SHALL BE
SODDED OR SEEDED AND MULCHED WITHIN 7 DAYS DURING WET SEASON AND 14 DAYS
DURING THE DRY SEASON. ALL DISTURBED EARTH AREAS SHALL BE SODDED OR SEEDED AND
MULCHED UPON ACCEPTANCE BY THE OWNER AT THE COMPLETION OF CONSTRUCTION.
21.ALL SURFACE WATER DISCHARGE FROM SITE, INCLUDING DEWATERING DISCHARGE, SHALL
MEET ALL STATE WATER QUALITY STANDARDS PRIOR TO REACHING ANY WATERS OF THE
STATE, INCLUDING WETLANDS. ALL FINES FOR NON-COMPLIANCE WILL BE THE CONTRACTOR'S
RESPONSIBILITY.
22.IN THE EVENT THAT THE EROSION PREVENTION AND CONTROL DEVICES SHOWN IN THESE
DRAWINGS PROVE NOT TO BE EFFECTIVE, ALTERNATE METHODS FOR MAINTAINING STATE
WATER QUALITY STANDARDS FOR DISCHARGE FROM THE CONSTRUCTION SITE WILL BE
REQUIRED. ONE EFFECTIVE ALTERNATIVE METHOD INCLUDES THE INTRODUCTION OF
ALUMINUM SULFATE (ALUM) INTO DISCHARGE FROM THE CONSTRUCTION SITE. PLEASE NOTE
THAT ANY ALTERNATIVE EROSION PREVENTION AND CONTROL DEVICES MUST BE APPROVED
BY ORANGE COUNTY COMPLIANCE PERSONNEL PRIOR TO PLACEMENT.
23.ALL EXISTING UNSUITABLE SOIL MATERIAL ENCOUNTERED (ORGANICS, MUCK, CONFINING CLAY
LAYERS, ETC.), SHALL BE REMOVED AND REPLACED WITH SUITABLE CLEAN FILL MATERIAL AT
THE CONTRACTOR'S EXPENSE.
SIDEWALK/RAMPS:
1. CLASS 'I' CONCRETE MINIMUM COMPRESSIVE STRENGTH SHALL BE 3,000 PSI AT 28 DAYS.
2. COMPLETE CONSTRUCTION WITHOUT IMPACTING THE NORMAL OPERATION OF TRAFFIC.
3. LEADING EDGE OF RAMP SHALL ALIGN WITH SIDEWALK OR RAMP ON OPPOSITE SIDE OF
CROSSING.
4. WHERE A CURB CUT RAMP IS CONSTRUCTED WITHIN AN EXISTING CURB, CURB AND GUTTER
AND/OR SIDEWALK, THE EXISTING CURB OR CURB AND GUTTER SHALL BE REMOVED TO THE
NEAREST JOINT BEYOND THE DROP CURB OR TO THE EXTENT THAT NO REMAINING SECTION
OF CURB OR CURB AND GUTTER IS LESS THAN 5' LONG. THE EXISTING SIDEWALK SHALL BE
REMOVED TO THE NEAREST JOINT BEYOND THE TRANSITION SLOPE OR WALK AROUND OR THE
EXTENT THAT NO REMAINING SECTION OF SIDEWALK IS LESS THAN 5' LONG.
5. THE EXISTING GRADES SHOWN ON THE DRAWINGS (IN PLAN OR IN SECTION) ARE
APPROXIMATE ONLY. THE CONTRACTOR IS RESPONSIBLE FOR GRADING, INCLUDING
PLACEMENT OR REMOVAL OF FILL MATERIAL AS APPROPRIATE, TO PROVIDE PROPER
RELATIONSHIP BETWEEN WALKS/RAMPS AND ADJACENT ROADWAYS, CURBS, LOTS, UTILITIES,
AND OTHER APPURTENANCES, AS INDICATED ON THE DRAWINGS.
6. ALL RAMPS SHALL HAVE A MAXIMUM LONGITUDINAL SLOPE OF 12:1. ALL CROSS WALKS AND
SIDEWALKS SHALL HAVE A MAXIMUM CROSS SLOPE OF 2% AND MAXIMUM LONGITUDINAL
SLOPE OF 5%.
7. EXISTING SIDEWALKS SHALL BE MAINTAINED OPEN DURING CONSTRUCTION, OR A SAFE,
TEMPORARY, APPROVED PEDESTRIAN PATH SHALL BE PROVIDED UNTIL SIDEWALK CAN BE
REOPENED.
SIGNING AND PAVEMENT MARKINGS:
1. ALL FINAL PAVEMENT MARKINGS SHALL BE ALKYD THERMOPLASTIC. ALL TEMPORARY
PAVEMENT MARKINGS SHALL BE PAINT.
2. CONTRACTOR TO RELOCATE EXISTING SIGNAGE WHERE INDICATED ON THE DRAWINGS.
3. SIGNING AND PAVEMENT MARKINGS ARE TO BE PLACED IN ACCORDANCE WITH THE MANUAL
ON UNIFORM TRAFFIC CONTROL DEVICES (MUTCD), THE FDOT STANDARD PLANS AND THE
STANDARD SPECIFICATIONS FOR ROAD AND BRIDGE CONSTRUCTION, LATEST EDITION.
4. PAVEMENT MARKINGS AT ALL EXISTING/PROPOSED INTERFACE LOCATIONS ARE TO MATCH IN
TERMS OR ALIGNMENT AND COLOR.
5. CAUTION SHOULD BE EXERCISED IN THE INSTALLATION OF POST MOUNTED SIGNS IN ORDER
TO PREVENT POSSIBLE DAMAGE TO BURIED UTILITIES.
6. SIGN ASSEMBLY LOCATIONS SHOWN ON THE DRAWINGS WHICH ARE IN CONFLICT WITH
LIGHTING, UTILITIES, DRIVEWAYS, WHEELCHAIR RAMPS, ETC., MAY BE ADJUSTED SLIGHTLY AS
DIRECTED BY THE OWNER'S AUTHORIZED AGENT. EXTREME LOCATION CHANGES MUST BE
APPROVED BY THE ENGINEER OF RECORD.
7. ALL EXISTING SIGNS ARE TO REMAIN UNLESS OTHERWISE NOTED. ANY SIGNS TO REMAIN THAT
ARE DAMAGED DURING THE CONSTRUCTION PROCESS SHALL BE REPLACED IN KIND AT THE
CONTRACTOR'S EXPENSE.
8. ANY EXISTING PAVEMENT MARKINGS SCHEDULED TO REMAIN WHICH ARE DAMAGED DURING
CONSTRUCTION SHALL BE REPLACED IN KIND AT THE CONTRACTORS EXPENSE.
G E
N E
R A
L
N
O T
S
B
R E
V I A
T I O
N S
C001
B
ID
S E
T
/2
LEGEND
1. SEE GENERAL NOTES SHEETS C001 FOR ADDITIONAL EROSION CONTROL,
SEDIMENTATION, AND DEMOLITION NOTES THAT APPLY TO THIS PLAN.
2. IN ALL DISTURBED AREAS, INSTALL SILT FENCE ALONG PERIMETER PRIOR TO
DEMOLITION.
3. CONTRACTOR SHALL TAKE DUE CARE WHEN INSTALLING SILT FENCE ACROSS
EXISTING UNDERGROUND UTILITIES.
3. CONTRACTOR MAY ADJUST SILT FENCE LOCATIONS WITHIN INDICATED LIMITS
OF CONSTRUCTION AS NEEDED TO PERFORM WORK.
4. THE CONTRACTOR SHALL PROVIDE EROSION CONTROL FOR ALL EXISTING
DRAINAGE STRUCTURES AS NOTED.
5. A TURBIDITY CONTROL PLAN/MEANS AND METHODS PLAN SHALL BE
SUBMITTED BY THE CONTRACTOR IN ADDITION TO THE SWPPP PLAN FOR
REVIEW AND APPROVAL BY ORANGE COUNTY UTILITIES COMPLIANCE PRIOR TO
COMMENCEMENT OF CONSTRUCTION.
6. EROSION CONTROL MEASURES SHOWN ON THIS PLAN ARE THE MINIMUM
REQUIRED. CONTRACTOR SHALL INSTALL ADDITIONAL EROSION CONTROL
MEASURES AS NECESSARY.
7. ALL DISTURBED AREAS SHALL BE RESTORED TO ORIGINAL OR BETTER
CONDITION.
8. DEMOLISHED SITE WILL REQUIRE STABILIZATION WITHIN 7 DAYS OF
COMPLETION. CONTRACTOR TO COORDINATE WITH ORANGE COUNTY
COMPLIANCE.
9. ANY FILL REMOVED FOR UNDERGROUND UTILITY CONSTRUCTION WILL BE
PLACED ON PLASTIC AND COVERED TO PREVENT WASHOUT DURING RAIN
EVENTS.
10. ALL UNSUITABLE MATERIALS, INCLUDING ORGANICS AND MUCK, MUST BE
EXCAVATED AND REMOVED FROM THE SITE PRIOR TO GRADING THE SITE WITH
CLEAN SAND.
11. ALL DISTURBED AREAS SHALL BE STABILIZED WITH ARGENTINE BAHIA GRASS
SOD UNLESS SPECIFIED OTHERWISE.
LIMITS OF WORK
SINGLE ROW OF SILT FENCE
EXISTING CONTOUR ELEVATION
EXISTING TREE TO BE REMOVED
EXISTING TREE TO BE PROTECTED
EROSION CONTROL NOTES
SF SF SF
APPROXIMATE SOIL BORING
LOCATION BASED ON
GEOTECHNICAL REPORT.
B-1
1. HORIZONTAL DATUM IS RELATIVE TO THE NORTH AMERICAN DATUM OF 1983,
2011 ADJUSTMENT WITH COORDINATES EXPRESSED IN FLORIDA STATE
PLANE COORDINATE SYSTEM, EAST ZONE (901), U.S. SURVEY FEET.
ELEVATIONS ARE RELATIVE TO THE NORTH AMERICAN VERTICAL DATUM OF
1988 (NAVD88) BASED ON THE FOLLOWING ORANGE COUNTY ENGINEERING
DEPARTMENT BENCHMARKS.
2. CONTRACTOR’S DESIGNATED PARKING AREA SHALL BE LOCATED IN THE
PARKING SPACES FOUND EAST OF THE EXISTING FUEL TANK, WHICH IS
LOCATED NORTH OF THE EFFLUENT PUMP STATION. IF ADDITIONAL PARKING
SPACES ARE NEEDED, THE CONTRACTOR SHALL SUBMIT A REQUEST FOR
ADDITIONAL CONTRACTOR’S DESIGNATED PARKING AREA TO ORANGE
COUNTY UTILITIES FOR APPROVAL.
GENERAL NOTES
R W
R W
R W
R W
R W
R W
R W
R W
R W
R W
R W
R W
R W
R W
R W
R W
R W
R W
R W
R W
R W
R W
R W
BE
B E
B E
B E
B E
B E
B E
RW
R W
R W
R W
R W
RW
RW
BE
BE
BE
BE
B E
B E
B E
B E
B E
B E
BE BE
BE
B E
B E
B E
B E ukn ukn ukn ukn ukn ukn
BEBE
BEBE
BE
BEBE
B E
B E
BE
BE
BE
BE
BEBEBEBEBEBEBEBEBEBE
BEBEBEBEBEBE
B E
B E
B E
B E
B E
B E
BE
BE
BE
B E
B E
BE
BE
BEBEBEBEBEBEBEBE
BE
BEBE
BE
BE
B E
B E
B E
BE
BE
BE
BE
BE
BE BE
BE
BE
BE
BE
BE
BE
BE
BE
BE
BE
BEBE
BE
BE
B E
B E
B E
B E
B E
AMECFW Nail: TRAVERSE
Elevation =88.64
TH1 HUB
Elevation =89.28
TH2 HUB
Elevation =89.10
WPB
TRNF
TRNF
MH
FFE: 89.3
30" Oak
34" Oak
20" Oak
18" Oak
18" Oak
20" Oak
WPB
24" Oak
H
Y D
BE
BE
BE
BE
BE
BE
B G
V
B G
V
B G
V
B G
V
BE BE
BE
BE
BE
SRVC
SRVC
ukn ukn
89 88
88 89
90 90
89 88 88
TRNF
TRNF
EFFLUENT PUMPING
STATION
ELECTRICAL
BUILDING
(TO REMAIN)
EXISTING
TRANSFORMER
(TO REMAIN)
EFFLUENT PUMP
STATION
(TO REMAIN)
SINGLE ROW SILT
FENCE (TYP).
EXISTING
MANHOLE TO
REMAIN
EXISTING
SIDEWALK TO
REMAIN
E
X
I S
T
I
P
H
A
L
T
R
O
A
D
M
A
I N
EXISTING PVC
PIPE TO REMAIN
LIMITS OF
WORK (TYP)
EXISTING
BOLLARD TO
REMAIN (TYP)
EXISTING BURIED
ELECTRICAL CONDUITS
TO REMAIN (TYP).
EXISTING BELOW
GRADE VAULT TO
REMAIN (TYP).
EXISTING AC
EQUIPMENT
PAD TO REMAIN
EXISTING SPEED
LIMIT SIGN TO
REMAIN
EXISTING TRANSFORMER
ON CONCRETE PAD TO
REMAIN (TYP)
EXISTING BELOW
GRADE ELECTRICAL
VAULT TO REMAIN
(TYP)
S
F
S
F
S
F
S
F
EXISTING BUILDING
OVERHANG
CONTRACTOR
STAGING AREA
B-2
B-1
S
F
S
F
S
F
S
F
S
F
S F
S F
SF
SF
SF
SF
SF
S F
S F
SF
S F
S F
S F
S
F
S
F
S F
S
F
S
F
S
F
S
F
S
F
S
F
S
F
S
F
S
F
S
F
S
F
S
F
S
F
S
F
S
F
S
F
S
F
S
F
S
F
S
F
S
F
S
F
S
F
S F
S F
S F
S F
S F
S F
S F
S
F
S
F
S
F
S F
S
F
S
F
S F
S
F
S
F
S
F
S F
S
F
S
F
S F
S
F
S
F
S
F
S
F
S
F
S
F
S
F
S
F
S
F
JWS
LOCAL OFFICE:
482 SOUTH KELLER RD
ORLANDO, FL 32810
TEL. 407.647.7275
FAX. 407.806.4500
CORPORATE OFFICE:
4030 W. BOY SCOUT BLVD
TAMPA, FLORIDA 33607
FBPR CERTIFICATE OF
AUTHORIZATION NO.24
www.atkinsglobal.com
SHEET NO.
REV.
S H
E E
T
T
I T
L E
P R
O J E
C T
C L I E
N T
O R
A N
U
N T
Y
F
L O
R I D
A
S W
R
A
F
L U
E N
T
P
U M
P
S
T A
T I O
N
P R
E E
N G
I N
E E
R E
D
E
L E
C T
R I C
I L
D I N
G
I S
S U
R
I S
S U
R
R E
V
D A
T E
R E
V
D A
T E
APPROVED:
CHECKED:
DRAWN:
PROJECT ENG:
JOB NO.:
O S
C A
R
E
B
E R
M U
D E
Z
P
E
F L O
R I D
A
R
E G
N
O
OEB
100061852
D E
M O
L I T
I O
N
A
O
S I O
N
C
O N
T R
A
N
C100
0 10' 20'
FULL SCALE: 1"=10'
HALF SCALE: 1"=20'
B
ID
S E
T
/2
482 SOUTH KELLER RD
ORLANDO, FL 32810
TEL. 407.647.7275
FAX. 407.806.4500
CORPORATE OFFICE:
4030 W. BOY SCOUT BLVD
TAMPA, FLORIDA 33607
FBPR CERTIFICATE OF
AUTHORIZATION NO.24
www.atkinsglobal.com
SHEET NO.
REV.
S H
E E
T
T
I T
L E
P R
O J E
C T
C L I E
N T
O R
A N
U
N T
Y
F
L O
R I D
A
S W
R
A
F
L U
E N
T
P
U M
P
S
T A
T I O
N
P R
E E
N G
I N
E E
R E
D
E
L E
C T
R I C
I L
D I N
G
I S
S U
R
I S
S U
R
R E
V
D A
T E
R E
V
D A
T E
APPROVED:
CHECKED:
DRAWN:
PROJECT ENG:
JOB NO.:
O S
C A
R
E
B
E R
M U
D E
Z
P
E
F L O
R I D
A
R
E G
N
O
OEB
100061852
SCALE:
NTS
EROSION CONTROL NOTES
SURFACE INLET SEDIMENT FILTER
FILTERED WATER
ROCK / SAND BAGS
OR BIOFILTER BAGS
(PLACED END TO END)
SECTION
PLAN
PAVEMENT (TYP)
GRATE
1" TYP1" TYP
ROCK / SAND BAGS OR BIOFILTER BAGS
(PLACED END TO END)
WRAP GRATE WITH FILTER FABRIC
WITH OVERLAPPING TOP FLAPS
WRAP GRATE WITH FILTER FABRIC
WITH OVERLAPPING TOP FLAPS
SPECIFIC APPLICATION
CURB INLET
FILTERED WATER
SAND BAG
RUNOFF
THIS METHOD OF INLET PROTECTION IS APPLICABLE AT CURB INLETS WHERE PONDING IN
FRONT OF THE STRUCTURE IS NOT LIKELY TO CAUSE INCONVENIENCE OR DAMAGE TO
ADJACENT STRUCTURES AND UNPROTECTED AREAS.
PERFORATED 6" ADS PIPE
WITH FILTER SOCK
CURB INLET SEDIMENT FILTER
1.
6.
ALL EROSION PREVENTION AND CONTROL MEASURES MUST BE INSPECTED AND APPROVED
BY COMPLIANCE PERSONNEL PRIOR TO ANY CONSTRUCTION ACTIVITIES. REMOVAL
OF THESE SAME EROSION CONTROLS AND PREVENTION MEASURES MAY BE DONE ONLY
AFTER AUTHORIZATION BY COMPLIANCE PERSONNEL IS OBTAINED.
7.
DURING CONSTRUCTION THE CONTRACTOR SHALL MODIFY OR RELOCATE THE SILT FENCE (WITH
OWNER'S PRIOR APPROVAL) TO ALLOW FOR ITS ACCESS AND TO COMPLETE CONSTRUCTION. IT IS
THE CONTRACTOR'S RESPONSIBILITY TO MAINTAIN ADEQUATE EROSION CONTROL AT ALL TIMES.
2.
3.
4.
ALL SURFACE WATER DISCHARGE FROM SITE, INCLUDING DEWATERING DISCHARGE,
SHALL MEET STATE WATER QUALITY STANDARDS (LESS THAN 29 NTU ABOVE
BACKGROUND) PRIOR TO REACHING ANY WATERS OF THE STATE INCLUDING
WETLANDS. IT IS THE CONTRACTOR'S RESPONSIBILITY TO REMAIN IN COMPLIANCE
WITH THE FDEP GENERAL PERMIT TO DISCHARGE PRODUCED GROUNDWATER OFFSITE.
IN THE EVENT THAT THE EROSION PREVENTION AND CONTROL DEVICES SHOWN IN THESE
DRAWINGS PROVE NOT TO BE EFFECTIVE, ALTERNATE METHODS FOR MAINTAINING STATE
WATER QUALITY STANDARDS FOR DISCHARGE FROM THE CONSTRUCTION SITE WILL BE
REQUIRED. ONE EFFECTIVE ALTERNATIVE METHOD INCLUDES THE INTRODUCTION OF
ALUMINUM SULFATE (ALUM) INTO DISCHARGE FROM THE CONSTRUCTION SITE. PLEASE
NOTE THAT ANY ALTERNATIVE EROSION PREVENTION AND CONTROL DEVICES MUST BE
APPROVED BY COMPLIANCE PERSONNEL PRIOR TO PLACEMENT.
EROSION AND DUST CONTROL SHALL BE MAINTAINED WITHIN CONSTRUCTION AREAS
BY QUICKLY STABILIZING DISTURBED AREAS TO PREVENT THE RELEASE OF SEDIMENT.
THIS SHALL BE ACCOMPLISED USING GRASS COVER, TURBIDITY FENCES, PERIODIC
WATERING, AND OTHER BEST MANAGEMENT PRACTICES FOUND IN THE STORMWATER
POLLUTION PREVENTION PLAN, WHICH ARE ACCEPTABLE TO CONSTRUCTION
MANAGER, ENGINEER, AND REGULATORY AGENCIES.
5.
8.
9.
PROVIDE EROSION AND SEDIMENTATION CONTROL MEASURES CONSISTING OF STAKED SILT
FENCES ALONG THE PROPOSED LIMITS OF CONSTRUCTION OR AS INDICATED ON THE
DRAWINGS. PROVIDE ADDITIONAL MEASURES AS NECESSARY UTILIZING INDUSTRY STANDARD
BEST MANAGEMENT PRACTICES TO AVOID ADVERSE IMPACTS TO JURISDICTIONAL AREAS
(WETLANDS OR WATER BODIES) AND OFF SITE LANDS AND WATER BODIES. MAINTAIN THESE
MEASURES DAILY UNTIL CONSTRUCTION ACCEPTANCE BY THE OWNER AND THEN REMOVE
AND LEGALLY DISPOSE OF SAID MEASURES.
EROSION CONTROL SHALL BE MAINTAINED WITHIN CONSTRUCTION AREAS BY QUICKLY
STABILIZING DISTURBED AREAS TO PREVENT THE RELEASE OF SEDIMENT. THIS SHALL BE
ACCOMPLISHED USING GRASS COVER, TURBIDITY FENCES, AND OTHER MEANS ACCEPTABLE TO
OWNER, ENGINEER AND REGULATORY AGENCIES.
ALL STORM DRAINAGE INLETS AND PIPES SHALL BE PROTECTED FROM SILT, SAND AND DEBRIS
DURING CONSTRUCTION. ANY ACCUMULATION WITHIN THE STORM DRAINAGE PIPE SYSTEM
SHALL BE REMOVED WITHOUT PUMPING OR FLUSHING INTO THE PONDS. STORM DRAINAGE
SYSTEM SHALL BE CLEANED AND FREE OF DEBRIS PRIOR TO CONSTRUCTION MANAGER'S
ACCEPTANCE.
PROVIDE SOCK DRAIN IN FRONT OF ALL DRAINAGE CURB INLETS AND PROVIDE FILTER FABRIC
UNDER THE GRATE OF ALL DITCH BOTTOM INLETS AFTER INITIAL COMPLETION OF THE
DRAINAGE STRUCTURES. MAINTAIN THESE MEASURES DAILY (WHICH MAY INCLUDE FULL
REPLACEMENT AT THE DISCRETION OF THE CONSTRUCTION MANAGER) TO MINIMIZE SILT
ACCUMULATION IN THE STORM DRAINAGE SYSTEM. UPON CONSTRUCTION ACCEPTANCE BY
THE OWNER, REMOVE AND LEGALLY DISPOSE OF SAID MEASURES.
NOTES:
1. PRIOR TO ANY DISTURBANCE OF PROPERTY, THE ENTIRE SILT FENCE MUST BE IN PLACE.
2. THE EROSION CONTROL PROVISIONS DELINEATED ON THE PLANS ARE THE MINIMUM
REQUIRED. ADDITIONAL EROSION AND SEDIMENT CONTROL MEASURES MAY BE NEEDED
DEPENDENT UPON ACTUAL SITE CONDITIONS AND CONSTRUCTION OPERATIONS.
3. ENSURE THAT POSTS AT CONNECTIONS ARE ROLLED AND WRAPPED PER FDOT INDEX 102,
2010 EDITION.
ELEVATION
T
O
M
I N
M I N
POST OPTIONS:
SOFTWOOD 2-1/2" DIA
SOFTWOOD 2"x4"
HARDWOOD 1-1/2"x1-1/2"
STEEL 1.33 LBS/FT MIN)
6' MAX
FILTER FABRIC (IN
CONFORMANCE WITH
SEC. 985 FDOT SPEC.)
SECTION
S
I
O
W
FILTER FABRIC
V E
R T
I C
A L
PRINCIPLE POST POSITION
(CANTED 20° TOWARD FLOW)
OPTIONAL POST
POSITIONS
3.0'
DOUBLE ROW
ONLY WHERE
SHOWN ON PLAN
SCALE:
NTS
SILT FENCE DETAIL
SCALE:
NTS
INLET SEDIMENT FILTER DETAILS
C190
E R
O S
I O
N
C
O N
T R
T
T
A I L
S
B
ID
S E
T
/2
LIMITS OF WORK
PROPOSED CONCRETE SIDEWALK
LEGEND
R W
R W
R W
R W
R W
R W
R W
R W
R W
R W
R W
R W
R W
R W
R W
R W
R W
R W
R W
R W
R W
R W
R W
BE
B E
B E
B E
B E
B E
B E
RW
R W
R W
R W
R W
RW
RW
BE
BE
BE
BE
B E
B E
B E
B E
B E
B E
BE BE
BE
B E
B E
B E
B E ukn ukn ukn ukn ukn ukn
BEBE
BEBE
BE
BEBE
B E
B E
BE
BE
BE
BE
BEBEBEBEBEBEBEBEBEBE
BEBEBEBEBEBE
B E
B E
B E
B E
B E
B E
BE
BE
BE
B E
B E
BE
BE
BEBEBEBEBEBEBEBE
BE
BEBE
BE
BE
B E
B E
B E
BE
BE
BE
BE
BE
BE BE
BE
BE
BE
BE
BE
BE
BE
BE
BE
BE
BEBE
BE
BE
B E
B E
B E
B E
B E
AMECFW Nail: TRAVERSE
Elevation =88.64
WPB
TRNF
TRNF
MH
FFE: 89.3
34" Oak
20" Oak
18" Oak
18" Oak
20" Oak
WPB
24" Oak
H
Y D
BE
BE
BE
BE
BE
BE
B G
V
B G
V
B G
V
B G
V
BE BE
BE
BE
BE
SRVC
SRVC
ukn ukn
TRNF
TRNF
EFFLUENT PUMPING
STATION
ELECTRICAL
BUILDING
(TO REMAIN)
EXISTING
TRANSFORMER
(TO REMAIN)
EFFLUENT PUMP
STATION
(TO REMAIN)
E
X
I S
T
I
P
H
A
L
T
R
O
A
D
M
A
I N
PROPOSED
BUILDING
FFE:89.3
30'
8'
LIMITS OF WORK
PROPOSED 5' CONCRETE
SIDEWALK (TYP)
EXISTING SPEED
LIMIT SIGN
EXISTING
BOLLARD
(TYP)
EXISTING
ELECTRICAL
VAULT (TYP)
EXISTING
CONCRETE
SIDEWALK
17.8'
24'
10.3'
CONNECT TO
EXISTING SIDEWALK
CONNECT TO
EXISTING SIDEWALK
PROPOSED
BUILDING
900 SF
EXISTING
ELECTRICAL
VAULT (TYP)
CONTRACTOR
STAGING AREA
24'
EXPANSION JOINT
(TYP)
SEE FDOT DESIGN
STANDARDS 2017-18
INDEX 522-003
EQUIPMENT PAD
N:1496021.62
E:515168.81
N:1495981.62
E:515169.09
N:1495981.79
E:515193.09
N:1496021.79
E:515192.81
N:1495986.07
E:515223.05
N:1496029.66
E:515176.75
N:1496030.05
E:515222.76
N:1495985.92
E:515205.26
N:1495978.82
E:515195.34
N:1495980.94
E:515206.88
N:1495973.83
E:515196.97
N:1495979.29
E:515170.28
N:1495971.62
E:515170.34
N:1495997.07
E:515152.31
N:1495960.55
E:515151.96
N:1495971.50
E:515153.87
N:1495993.19
E:515166.01
N:1495985.14
E:515158.07
N:1495985.06
E:515146.82
N:1496060.37
E:515139.83
N:1495992.52
E:515139.26
N:1496066.27
E:515161.10
N:1496073.50
E:515159.19
N:1496067.02
E:515138.00
R
R
N:1496064.63
E:515134.55
N:1496059.66
E:515135.79
N:1496073.24
E:515163.36
N:1496068.58
E:515164.74
A/C PAD
A/C PAD
EQUIPMENT
PAD
10'
R
N:1496047.11
E:515169.09
Y
P
EARTHEN WEIR
REINFORCED WITH GEOCELL
(SEE SHEET C501 FOR DETAIL)
2'X4'X4" CONCRETE.
PER SIDEWALK DETAIL
FFE 86.5
1.5'X4'X4" CONCRETE.
PER SIDEWALK DETAIL
FFE 85.5
JWS
LOCAL OFFICE:
482 SOUTH KELLER RD
ORLANDO, FL 32810
TEL. 407.647.7275
FAX. 407.806.4500
CORPORATE OFFICE:
4030 W. BOY SCOUT BLVD
TAMPA, FLORIDA 33607
FBPR CERTIFICATE OF
AUTHORIZATION NO.24
www.atkinsglobal.com
SHEET NO.
REV.
S H
E E
T
T
I T
L E
P R
O J E
C T
C L I E
N T
O R
A N
U
N T
Y
F
L O
R I D
A
S W
R
A
F
L U
E N
T
P
U M
P
S
T A
T I O
N
P R
E E
N G
I N
E E
R E
D
E
L E
C T
R I C
I L
D I N
G
I S
S U
R
I S
S U
R
R E
V
D A
T E
R E
V
D A
T E
APPROVED:
CHECKED:
DRAWN:
PROJECT ENG:
JOB NO.:
O S
C A
R
E
B
E R
M U
D E
Z
P
E
F L O
R I D
A
R
E G
N
O
OEB
100061852
S I T
E
P
L A
N
C200
0 10' 20'
FULL SCALE: 1"=10'
HALF SCALE: 1"=20'
B
ID
S E
T
/2
96.00
LIMITS OF WORK
EXISTING SPOT ELEVATION
PROPOSED SPOT ELEVATION
PROPOSED CONTOUR LINE
EXISTING CONTOUR LINE
GRADE BREAK LINE
PROPOSED SURFACE FLOW
LEGEND
HP
KEYNOTES
MATCH EXISTING PAVEMENT/SIDEWALK GRADE
R W
R W
R W
R W
R W
R W
R W
R W
R W
R W
R W
R W
R W
R W
R W
R W
R W
R W
R W
R W
R W
R W
R W
BE
B E
B E
B E
B E
B E
B E
RW
R W
R W
R W
R W
RW
RW
BE
BE
BE
BE
B E
B E
B E
B E
B E
B E
BE BE
BE
B E
B E
B E
B E ukn ukn ukn ukn ukn ukn
BEBE
BEBE
BE
BEBE
B E
B E
BE
BE
BE
BE
BEBEBEBEBEBEBEBEBEBE
BEBEBEBEBEBE
B E
B E
B E
B E
B E
B E
BE
BE
BE
B E
B E
BE
BE
BEBEBEBEBEBEBEBE
BE
BEBE
BE
BE
B E
B E
B E
BE
BE
BE
BE
BE
BE BE
BE
BE
BE
BE
BE
BE
BE
BE
BE
BE
BEBE
BE
BE
B E
B E
B E
B E
B E
AMECFW Nail: TRAVERSE
Elevation =88.64
TH1 HUB
Elevation =89.28
TH2 HUB
Elevation =89.10
WPB
TRNF
TRNF
MH
FFE: 89.3
WPB
H
Y D
BE
BE
BE
BE
BE
BE
B G
V
B G
V
B G
V
B G
V
BE BE
BE
BE
BE
SRVC
SRVC
ukn ukn
89 88
88 89
90 90
89 88 88
TRNF
TRNF
EFFLUENT PUMPING
STATION
ELECTRICAL
BUILDING
(TO REMAIN)
EXISTING
TRANSFORMER
(TO REMAIN)
EFFLUENT PUMP
STATION
(TO REMAIN)
E
X
I S
T
I
P
H
A
L
T
R
O
A
D
M
A
I N
PROPOSED
BUILDING
FFE:89.3
89.2089.20
89.2089.20
89.05
89.15
89.15
88.40
88.65
88.31
88.56
88.40
88.31
88.70
89.00
89.20
89.00
89.90
89.90
85.50
85.50
89.00
89.00
EARTHEN WEIR
REINFORCED WITH GEOCELL
INV: 87.12
(SEE SHEET C500 FOR
CROSS-SECTION)
29 LF-12"x18" ERCP
CLASS III
CONST. SIDE DRAIN MES
FDOT PLAN 430-022
FL 86.00
CONST. SIDE DRAIN MES
FDOT PLAN 430-022
FL 87.20
A
A
B
B
3" PVC ORIFICE
INV. 86.00
(SEE DETAIL ON SHEET C500)
3" PVC ORIFICE
INV. 85.70
(SEE DETAIL ON SHEET C500)
3" PVC @ 1.0% MIN.
JWS
LOCAL OFFICE:
482 SOUTH KELLER RD
ORLANDO, FL 32810
TEL. 407.647.7275
FAX. 407.806.4500
CORPORATE OFFICE:
4030 W. BOY SCOUT BLVD
TAMPA, FLORIDA 33607
FBPR CERTIFICATE OF
AUTHORIZATION NO.24
www.atkinsglobal.com
SHEET NO.
REV.
S H
E E
T
T
I T
L E
P R
O J E
C T
C L I E
N T
O R
A N
U
N T
Y
F
L O
R I D
A
S W
R
A
F
L U
E N
T
P
U M
P
S
T A
T I O
N
P R
E E
N G
I N
E E
R E
D
E
L E
C T
R I C
I L
D I N
G
I S
S U
R
I S
S U
R
R E
V
D A
T E
R E
V
D A
T E
APPROVED:
CHECKED:
DRAWN:
PROJECT ENG:
JOB NO.:
O S
C A
R
E
B
E R
M U
D E
Z
P
E
F L O
R I D
A
R
E G
N
O
OEB
100061852
G R
A D
I N
G
P
L A
N
C300
0 10' 20'
FULL SCALE: 1"=10'
HALF SCALE: 1"=20'
B
ID
S E
T
/2
482 SOUTH KELLER RD
ORLANDO, FL 32810
TEL. 407.647.7275
FAX. 407.806.4500
CORPORATE OFFICE:
4030 W. BOY SCOUT BLVD
TAMPA, FLORIDA 33607
FBPR CERTIFICATE OF
AUTHORIZATION NO.24
www.atkinsglobal.com
SHEET NO.
REV.
S H
E E
T
T
I T
L E
P R
O J E
C T
C L I E
N T
O R
A N
U
N T
Y
F
L O
R I D
A
S W
R
A
F
L U
E N
T
P
U M
P
S
T A
T I O
N
P R
E E
N G
I N
E E
R E
D
E
L E
C T
R I C
I L
D I N
G
I S
S U
R
I S
S U
R
R E
V
D A
T E
R E
V
D A
T E
APPROVED:
CHECKED:
DRAWN:
PROJECT ENG:
JOB NO.:
O S
C A
R
E
B
E R
M U
D E
Z
P
E
F L O
R I D
A
R
E G
N
O
OEB
100061852
C500
S I T
E
D
E T
A I L
S
SCALE:
CONCRETE (3000 PSI)
WITH LIGHT BROOM
FINISH
8" SUBGRADE COMPACTED TO MIN DENSITY
OF 95% MODIFIED PROCTOR MAXIMUM DRY
DENSITY (ASTM D-1557, AASHTO T-180)
EXISTING COMPACTED SOIL
W
6"
2.0% MAX.
NOTES:
1. SAWCUT CONTROL JOINTS @ 5' O.C.
2. CONTRACTOR TO INSTALL EXPANSION JOINT
AT PROPOSED AND EXISTING SIDEWALKS.
3. CONTRACTOR TO INSTALL EXPANSION JOINT
AT PROPOSED SIDEWALK AND BUILDING.
4. SIDEWALK SLAB THICKNESS = D = 4"
5' CONCRETE SIDEWALK
SIDEWALK DETAIL
SCALE:
NTS
SINGLE-COMPONENT
POLYURETHANE SEALANT 3/4"
THICK
CLOSED CELL SEMI-RIGID
PLASTIC JOINT FILLER
D
1/2"
1/4"
D/4
D
EXPANSION JOINT
CONTROL JOINT
CONCRETE JOINT DETAILS
D
CROSS-SECTION A-A
N.T.S
10' 15.6' VARIES 4.5' VARIES
4:1 SLOPE
EARTHEN WEIR
INV.: 87.12
ELEV: 86.00
ELEV: 89.70
PROPOSED
DRIVEWAY
12'
4:1 SLOPE
4:1 SLOPE
ELEV: 87.12
ELEV: 89.00
7.4'21.5' VARIESVARIES
S L O
P E
V A
R
IE
S
S L O
P E
V A
R
IE
S
CROSS-SECTION B-B
N.T.S
" CONTRACTION JOINT
T
Y P
6" X 6" #10 MESH
NOTE:
1. 4000 PSI CONCRETE SPECIFIED
3" ORIFICE DETAIL
N.T.S
PLAN
SECTION
EARTHEN WEIR
" CONTRACTION JOINT
CONCRETE
APRON
T.O.B. ELEV: 89.00
12" STABILIZED & COMPACTED SUBGRADE
TO A MIN. DENSITY OF 98% OF THE MAX.
DENSITY VALUE AS DETERMINED BY
AASHTO T-180 (MODIFIED) MIN. LBR=40
12" 12"
7.4'
GEOCELL
(SEE SHEET C501 FOR DETAIL)
GEOCELL
(SEE SHEET C501 FOR DETAIL)
3" PVC ORIFICE
3" PVC ORIFICE
INV = 86.00
3" PVC ORIFICE
INV = 85.70
1.5'
85.5
4:1 SLOPE
3" PVC TEE
3" PVC @ 1.0% MIN.
POND BOTTOM @ 86.00
2'
1.5'X4'X4" CONCRETE.
PER SIDEWALK DETAIL
POND SIDE
SLOPE
3" PVC @ 1.0% MIN.
4:1 SLOPE
2'
85.70
DRIVEWAY DETAIL
N.T.S
INV. = 86.00
3" PVC @ 1.0%
2'X4'X4" CONCRETE.
PER SIDEWALK DETAIL
FIBER REINFORCED PER
THE SPECIFICATIONS
B
ID
S E
T
/2
482 SOUTH KELLER RD
ORLANDO, FL 32810
TEL. 407.647.7275
FAX. 407.806.4500
CORPORATE OFFICE:
4030 W. BOY SCOUT BLVD
TAMPA, FLORIDA 33607
FBPR CERTIFICATE OF
AUTHORIZATION NO.24
www.atkinsglobal.com
SHEET NO.
REV.
S H
E E
T
T
I T
L E
P R
O J E
C T
C L I E
N T
O R
A N
U
N T
Y
F
L O
R I D
A
S W
R
A
F
L U
E N
T
P
U M
P
S
T A
T I O
N
P R
E E
N G
I N
E E
R E
D
E
L E
C T
R I C
I L
D I N
G
I S
S U
R
I S
S U
R
R E
V
D A
T E
R E
V
D A
T E
APPROVED:
CHECKED:
DRAWN:
PROJECT ENG:
JOB NO.:
O S
C A
R
E
B
E R
M U
D E
Z
P
E
F L O
R I D
A
R
E G
N
O
OEB
100061852
C501
S I T
E
D
E T
A I L
S
Geocell GS Fixing Pin
Scale : N.T.S.
Notes:
The cellular system is normally suitable for slopes up to 45 deg. (1:1 Slope)
Slope Direction
Geocell GS Cellular Confinement System: Typical Pinning Diagram
Scale : N.T.S.
Geocell GS Cellular Confinement System: Typical Slope Construction Profile
Scale : N.T.S.
Note 1: Where weak and / or erosive conditions exist, these must be improved prior to placement of Geocell. Level the existing surface prior to applying Geocell.
Note 2: Use additional pins/pegs to secure as needed.
Note 3: For gravel applications, a
Note 4: After Geocell has been anchored in place, in-filling of the cells may be carried out. For general convenience, it is advisable to fill from the edge inward, or from the toe (bottom) of slope upward. Aggregate may be compacted into place using an appropriate method which will not damage the fabric of Geocell.
Note 5: Ensure Geocell is completely covered, prolonged exposure to sunlight will effect the products longevity.
Note 6: Do Not drive on surface prior to filling with crushed aggregate
Note 7: Advice on suitability for specific applications including the use of a geogrid layer is available from Polymer Group Inc.'s technical team.
DESIGN NOTES:
Cell Wall Tensile Strength: 20.7 kN/m - Cell Wall Permeability: 45 l/m.sec - Material: 70% Polypropylene & 30% Polyethylene
1:1 or 45° (Light Vehicle Load Capacity)
No.
Slope Recommendation (Typ.)
10.39In
Cell Length (Nominal)
14No.
Number of Cells in Width (W)
44No.
Number of Cells in Length (L)
9.84Ft
Panel Width (Nominal)
19.69Ft
Panel Length (Nominal)
6In
Cell Depth
10InCell Nominal Diameter
250/150Unit of Measurement
Physical Properties
Table 1 : Geocell Cellular Confinement System Product Specifications
4" or 6"
(Table 2)
10" typ.
Geocell Cellular Confinement System
(see Table 1)
Fixing Pins Installed on Downslope Side of Geotextile Wall (see Table 2 & Detail 1)
Existing Soil Profile
150 / PanelEa.22"x4"x0.32"dia.Steel Rod
Fixing Pins
Installation (Recommended)Qty/Pack
SizeMaterialProduct
Table 2 : Geocell Cellular Confinement System Fixing Pins
23'
Geocell Cellular Confinement System
(see Table 1)
3'
16.4'
Geocell .3" dia. Fixing Pins (seeTable 2
& Detail 3) Tension Cellular Confinement System and Anchor Panels in Place during the filling process
Gravel (see Note 5)
2"
Geocell .32" dia. Steel Rebar Fixing Pin
(see Table 2)
Fixing Pins remain after Geocell are filled
1'-9"
3'
10"
10"
Fixing Pin Head Oriented over
Geocell Wall (see Detail 2)
Gravel meeting the retirements of FDOT
Section 907 Coarse Aggregate, of the
Standard Specifications for Road and
Bridge Construction, Latest Edition.
Type D-2 Geo-textile Fabric, installed and meting the requirements of FDOT
Section 985 Geosynthetic Materials, of the Standard Specifications for Road and Bridge Construction, Latest
Edition.
Typar Geocell GS 250/150 or owner approved equivalent.
suitable geotextile, such asType D-2 Geo-textile Fabric, installed and meeting the requirements of FDOT Section 985 Geosynthetic Materials, of the Standard Specifications for Road and Bridge Construction, Latest Edition.
B
ID
S E
T
/2
STRUCTURAL GENERAL NOTES
GENERAL STRUCTURAL CRITERIA
1. STRUCTURE IS DESIGNED TO BE SELF-SUPPORTING AND STABLE
ONCE IN SERVICE. NO CONSIDERATION FOR STABILITY AND SHORING
IS ASSUMED BY THE ENGINEER DURING THE BUILDING PROCESS. IT
SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO ENSURE THE
STABILITY AND SAFETY OF THE STRUCTURE AND ITS COMPONENTS BY
DETERMINING AND IMPLEMENTING ERECTION PROCEDURES AND
SEQUENCE OF CONSTRUCTION. THIS INCLUDES TEMPORARY
BRACING AND SHORING AS WELL AS SOIL STABILIZATION AND
PROTECTIVE MEASURES FOR ADJACENT EXISTING CONSTRUCTION.
2. STRUCTURAL DRAWINGS SHALL BE UTILIZED CONCURRENTLY WITH
DRAWINGS OF OTHER DISCIPLINES TO CONSULT INFORMATION NOT
EXPLICITLY INDICATED ON STRUCTURAL DRAWINGS.
3. CONTRACTOR SHALL VERIFY DIMENSIONS AND SITE CONDITIONS
PRIOR TO PROCEEDING WITH PROCUREMENT OF MATERIALS AND
LABOR, FABRICATION, AND CONSTRUCTION WORK. WHERE
DISCREPANCIES EXIST, NOTIFY ENGINEER OF SUCH DISCREPANCIES
IN WRITING VIA A REQUEST FOR INFORMATION / INTERPRETATION
(RFI) BEFORE PROCEEDING WITH THE WORK IN THE AFFECTED AREA
IN QUESTION.
4. NO STRUCTURAL MEMBER OR COMPONENT SHALL BE CUT, NOTCHED,
OR OTHERWISE ALTERED UNLESS APPROVED IN WRITING BY
STRUCTURAL ENGINEER. THE CONTRACTOR SHALL BE RESPONSIBLE
FOR ANY AND ALL COSTS INCURRED BY STRUCTURAL ENGINEER FOR
REVIEW OF SUCH DEVIATIONS AND IMPLEMENTATION OF
APPROPRIATE SOLUTIONS.
5. PRIOR TO COMMENCING WORK, THE GENERAL CONTRACTOR SHALL
BE RESPONSIBLE FOR REVIEWING AND COORDINATING WITH THE
SUB-CONTRACTORS WORK INDICATED ON STRUCTURAL DRAWINGS
WITH DRAWINGS OF OTHER DISCIPLINES.
6. THE STRUCTURAL DRAWINGS ARE REPRESENTATIVE OF THE
FINISHED STRUCTURE. THE STRUCTURAL ENGINEER SHALL NOT BE IN
RESPONSIBLE CHARGE AND CONTROL OF CONSTRUCTION MEANS,
METHODS, PROCEDURES AND CONSTRUCTION TECHNIQUES, AND
JOBSITE SAFETY. THIS SHALL BE THE RESPONSIBILITY OF THE
CONTRACTOR.
7. THE STRUCTURAL ENGINEER SHALL NOT BE CONSTRUED AS HAVING
CONTROL, CHARGE, AND RESPONSIBILITY FOR THE ACTS AND
OMISSIONS AND FOR FAILURE OF THE CONTRACTOR, SUB-
CONTRACTOR, AND OTHER PERSONS PERFORMING THE WORK TO
CARRY OUT SUCH WORK IN ACCORDANCE WITH THE STRUCTURAL
DRAWINGS AND COLLECTIVE CONTRACT DOCUMENTS.
8. PERIODIC SITE OBSERVATION BY THE STRUCTURAL ENGINEER AND
HIS / HER REPRESENTATIVES IS SOLELY FOR THE PURPOSE OF
DETERMINING IF THE WORK OF THE CONTRACTOR IS PROCEEDING IN
GENERAL ACCORDANCE WITH THE STRUCTURAL DRAWINGS AND
SPECIFICATIONS. THIS LIMITED SITE OBSERVATION SHALL NOT BE
CONSTRUED AS AN INSPECTION, EXHAUSTIVE, OR CONTINUOUS
OBSERVATION TO VERIFY THE QUALITY AND QUANTITY OF THE WORK.
DESIGN CRITERIA
1. STRUCTURAL WORK SHALL BE IN ACCORDANCE WITH:
FLORIDA BUILDING CODE 2017 EDITION 6 AS ADOPTED AND
SUPPLEMENTED BY LOCAL REGULATIONS AND ASCE 7-10 MINIMUM
DESIGN LOADS FOR BUILDINGS AND OTHER STRUCTURES.
2. REFER TO DRAWINGS OF OTHER DISCIPLINES FOR DIMENSIONS AND
ELEVATIONS NOT INDICATED ON STRUCTURAL DRAWINGS. NOTIFY
ENGINEER OF DISCREPANCIES PRIOR TO EXECUTION OF WORK.
3. COORDINATE SIZES AND LOCATIONS OF OPENINGS IN FLOORS,
WALLS AND ROOFS WITH DRAWINGS OF OTHER DISCIPLINES.
4. REFER TO DRAWINGS OF OTHER DISCIPLINES FOR MATERIALS,
COMPONENTS, AND CONNECTIONS NOT SHOWN HEREIN, AND FOR
ANCHORED, SUPPORTED AND EMBEDDED ITEMS WHICH AFFECT THE
STRUCTURAL WORK. VERIFY DETAILS AND DIMENSIONS WITH
EQUIPMENT PURCHASED.
5. NO PROVISIONS HAVE BEEN MADE FOR FUTURE VERTICAL AND/OR
HORIZONTAL ADDITIONS, MODIFICATIONS, AND/OR EXPANSIONS
EXCEPT AS SHOWN ON THE STRUCTURAL DRAWINGS.
6. STRUCTURAL ENGINEER IS NOT RESPONSIBLE FOR THE DESIGN OF
PREFABRICATED STAIRS, HANDRAILS, CURTAIN WALL / WINDOW WALL
SYSTEMS, COLD-FORMED STEEL FRAMING, OR OTHER SYSTEMS
DELEGATED OR NOT SHOWN IN THE STRUCTURAL DRAWINGS. SUCH
SYSTEMS SHALL BE DESIGNED, FURNISHED, AND INSTALLED BY
OTHER PORTIONS OF THE CONTRACT DOCUMENTS.
7. REFERENCED DATUM FOR THE PROJECT SHALL BE TAKEN AS 0'-0"
ESTABLISHED FROM SLAB ON GRADE FINISH FLOOR. VERIFY ACTUAL
ELEVATIONS WITH CIVIL DRAWINGS.
ELECTRICAL ROOM
GRAVITY LOADS
LOCATION
UNIFORM
DEAD LOAD
(PSF)
CONC.
DEAD LOAD
(LBS)
UNIFORM
LIVE LOAD
(PSF)
200 --- 80
CONC.
LIVE LOAD
(PSF)
ROOF 20 --- 20 ---
DESIGN LOADING
ULTIMATE DESIGN WIND SPEED: Vult
RISK CATEGORY
WIND EXPOSURE
INTERNAL PRESSURE COEFFICIENT (ENCLOSED)
WIND LOADS
149 MPH
III
C
±0.18
EQUIVALENT ALLOWABLE WIND SPEED: Vasd 116 MPH
CAST-IN-PLACE CONCRETE
1. CONCRETE WORK SHALL CONFORM TO THE REQUIREMENTS OF THE
FOLLOWING CODES AND STANDARDS (LATEST EDITIONS):
A. ACI 318 "BUILDING CODE REQUIREMENTS FOR REINFORCED
CONCRETE."
2. CONCRETE SHALL BE NORMAL WEIGHT UNO AND SHALL CONFORM TO
ASTM C-94 IN ADDITION TO THE FOLLOWING:
A. PORTLAND CEMENT SHALL MEET ASTM C-150 TYPEI/II.
B1. AGGREGATES FOR SLAB ON GRADE SHALL MEET ASTM C-33
(1" MAX).
B2. AGGREGATES ELSEWHERE SHALL MEET ASTM C-33 (3/4" MAX).
C. AIR ENTRAINING AGENT SHALL MEET ASTM C-260.
D. WATER REDUCING AGENT SHALL MEET ASTM C-494.
E. CALCIUM CHLORIDE SHALL NOT BE USED IN THE MIX.
G. CURING COMPOUND SHALL MEET ASTM C309 TYPE 1 UNO.
3. CONCRETE SHALL HAVE THE MINIMUM ULTIMATE COMPRESSIVE
STRENGTH AT 28 DAYS AS INDICATED BELOW. MIX DESIGNS SHALL BE
APPROVED BY THE ENGINEER BEFORE USE.
CONCRETE MIX REQUIREMENTS
COMPONENT 28-DAY STRENGTH
4,000 PSI
4. FLY ASH, SUBSTITUTING FOR CEMENT, SHALL NOT EXCEED 25% BY
WEIGHT.
5. FOR MASS CONCRETE PLACEMENT AS DEFINED BY ACI 207 FLY ASH,
SUBSTITUTING FOR CEMENT, SHALL NOT EXCEED 30% BY WEIGHT.
6. REINF BARS USED IN CONCRETE SHALL BE GRADE 60 KSI
DEFORMED BAR CONFORMING TO ASTM SPECIFICATION A-615.
REINFORCEMENT SHALL BE RUST,OIL, AND SCALE FREE AND SHALL
BE PLACED AND BENT IN ACCORDANCE WITH THE REFERENCED
STANDARDS INDICATED IN NOTE 1 OF THIS SECTION. SHOP DWGS
FOR REINFORCEMENT LAYOUT, DETAILING, AND PLACING SHALL BE
APPROVED BY THE STRUCT ENGINEER PRIOR TO FABRICATION, SITE
DELIVERY, AND INSTALLATION.
7. WELDED WIRE FABRIC TO BE USED FOR CONCRETE REINFORCEMENT
WHERE INDICATED SHALL CONFORM TO ASTM A-185 AND SHALL BE
FURNISHED IN FLAT SHEETS (RATHER THAN ROLLS). FABRIC SHALL BE
SUPPORTED ON CHAIRS TO MAINTAIN THE PROPER LOCATION WITHIN
THE CONCRETE AND SHALL BE PLACED IN ACCORDANCE WITH THE
REFERENCED STANDARDS INDICATED IN NOTE 1 OF THIS SECTION.
MINIMUM LAP SHALL BE TWO PANELS.
8. CONCRETE SHALL BE CURED IN ACCORDANCE WITH ACI STANDARDS
THE CONTRACTOR SHALL BEGIN CONCRETE CURING IMMEDIATELY
AFTER FINISHING OPERATIONS ARE COMPLETED.
9. CONCRETE ADMIXTURES SHALL BE UTILIZED ONLY WITH PRIOR
APPROVAL FROM THE STRUCT ENGINEER.
10. CONCRETE ADDITIVES SHALL BE COORDINATED BY THE
CONTRACTOR TO INSURE COMPATIBILITY WITH FLOOR COVERINGS,
EXPOSED, POLISHED, AND STAINED FINISHES AS SPECIFIED BY THE
ARCH.
11. CONCRETE TESTING SHALL BE REQUIRED FOR CIP CONCRETE
ELEMENTS AND SHALL BE PERFORMED BY A QUALIFIED,
INDEPENDENT TESTING LAB. MINIMUM TESTING SHALL BE FOR SLUMP
IN ACCORDANCE WITH ASTM C143 AND FOR COMPRESSIVE STRENGTH
IN ACCORDANCE WITH ASTM C39.
12. COMPRESSIVE STRENGTH TESTING SHALL BE CONDUCTED FOR EACH
CLASS, FOR EVERY FIFTY CUBIC YARDS OF CONCRETE PLACED PER
DAY. PLACEMENTS LESS THAN FIFTY CUBIC YARDS SHALL ALSO BE
TESTED PER DAY FOR EACH CLASS. A MINIMUM OF FOUR LAB-CURED
AND SIX FIELD-CURED CYLINDERS SHALL BE COLLECTED. TWO
CYLINDERS SHALL BE KEPT IN RESERVE AND TESTED, IF NECESSARY,
WITH PRIOR APPROVAL FROM THE STRUCT ENGINEER.
13. MIX DESIGN SUBMITTALS SHALL BE SENT TO THE STRUCT
ENGINEER FOR REVIEW AND APPROVAL PRIOR TO CONCRETE
PLACEMENT AND SHALL BE UNIQUELY IDENTIFIED WITH MIX NUMBER
AND EXACT LOCATION WHERE MIX WILL BE PLACED ON THE
STRUCTURE. SUBMITTALS SHALL INCLUDE DATA FROM RECENT FIELD
AND LAB CYLINDER TESTS AND STATISTICAL, TESTED BACK-UP DATA
PER ACI 318.
14. CONCRETE TICKETS FOR CONCRETE MIXES DELIVERED TO THE SITE
SHALL IDENTIFY THE EXACT TIME THAT THE MIX IS BATCHED.
CONCRETE PLACEMENT SHALL OCCUR WITHIN ONE AND A HALF
HOURS FROM THE TIME THE PROPORTIONED MIXING WATER IS
ADDED TO THE MIX FOR PLACEMENT. MIXES SHALL BE DISCARDED IF
THIS TIMEFRAME IS EXCEED. IT SHALL BE THE RESPONSIBILITY OF THE
INDEPENDENT TESTING LAB TO ASSURE COMPLIANCE WITH PLACING
TIME AND TO NOTIFY THE CONTRACTOR AND OWNER OF NON-
COMPLIANCE.
15. CONCRETE FORMS SHALL NOT BE STRIPPED UNTIL CONCRETE HAS
ATTAINED A MINIMUM 70% OF THE SPECIFIED 28-DAY COMPRESSIVE
STRENGTH AS INDICATED BY TESTING SAMPLES.
16. LAP SPLICE LENGTHS SHALL BE A MINIMUM OF 48 BAR DIA UNO.
17. CONCRETE CLEAR COVER OVER REINF SHALL BE IN
ACCORDANCE WITH ACI 318 AS LISTED BELOW, UNLESS NOTED
OTHERWISE.
LOCATION CLEAR COVER
CAST AGAINST EARTH 3"
EXPOSED TO EARTH OR WEATHER #6 AND LARGER 2"
EXPOSED TO EARTH OR WEATHER #5 AND SMALLER 1 1/2"
SLABS AND WALLS NOT EXPOSED TO WEATHER 3/4"
BEAMS AND COLUMNS NOT EXPOSED TO WEATHER 1 1/2"
SLABS ON GRADE (COVER FROM TOP OF SLAB) 1 1/2"
18. VERT AND HORIZ REINF INDICATED ON THE DWGS SHALL BE
DOWELED OUT OF THE FOUNDATION OR THE ELEMENT WHERE THE
REINF ORIGINATES, (SLAB BEAM, THE BEAM, WALL, ETC.) UTILIZING AN
ACI STANDARD HOOK EMBEDDED TO DEVELOP THE FULL ULTIMATE
TENSILE STRENGTH OF THE BAR.
19. FORMWORK REMOVAL IS THE SOLE RESPONSIBILITY OF THE
CONTRACTOR. REMOVE FORMS IN SUCH A MANNER AS TO INSURE
JOB SAFETY AND TO PREVENT DAMAGE TO, AND CREEP DEFLECTION
OF THE STRUCTURE.
20. IMMEDIATELY AFTER REMOVAL OF FORMS, REPAIR HONEYCOMBED
OR DEFECTIVE AREAS WITH HIGH STRENGTH CEMENT GROUT. GROUT
SHALL BE APPROVED BY THE STRUCT ENGINEER. WHEN REINF IS
VISIBLE IN DEFECTIVE AREA, CONTACT THE STRUCT ENGINEER
IMMEDIATELY.
SLAB-ON-GRADE 4,000 PSI
PRECAST 5,000 PSI
FOUNDATION
EXISTING STRUCTURE
1. INFORMATION SHOWN FOR THE EXISTING STRUCTURE ON THESE
DRAWINGS WAS TAKEN FROM THE FOLLOWING:
PREPARED BY: THIGPEN & TREON INC
ENTITLED: SOUTHWEST ORANGE COUNTY, REGIONAL WASTEWATER
TREATMENT PLANT
DATE: JUNE 1989
2. WORK SHOWN ON THESE DRAWINGS ASSUMES THAT THE ORIGINAL
CONSTRUCTION WAS PERFORMED IN ACCORDANCE WITH THE ABOVE
INDICATED ORIGINAL DRAWINGS INCLUDING (BUT NOT LIMITED TO)
DIMENSIONS, ELEVATIONS, MEMBER SIZES, MATERIALS, DETAILS, ETC.
IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY
THE CONDITIONS RELATING TO THE EXISTING STRUCTURE AND TO
NOTIFY THE ENGINEER IMMEDIATELY OF ANY DISCREPANCIES OR
CONFLICTS.
DEMOLITION NOTES
1. THE CONTRACTOR IS REQUIRED TO PROVIDE ALL TEMPORARY
SCAFFOLDING, PLATFORMS, BARRICADES, RAILINGS, SCREENING,
ETC. NECESSARY TO PROTECT EXISTING FACILITIES, STRUCTURES
AND THE PUBLIC DURING DEMOLITION AND ERECTION OF THE NEW
CONSTRUCTION, AS WELL AS FOR JOB SAFETY. JOB SAFETY,
CONSTRUCTION AND DEMOLITION PROCEDURES ARE THE SOLE
RESPONSIBILITY OF THE CONTRACTOR. THE CONTRACTOR IS
REQUIRED TO TAKE ALL PRECAUTIONS TO MINIMIZE VIBRATION,
NOISE, DUST AND DEBRIS IN ALL AREAS ADJACENT TO AREAS OF
DEMOLITION.
2. THE CONTRACTOR IS REQUIRED TO COORDINATE WITH THE OWNER
FOR THE TEMPORARY SUSPENSION OF USE OF ANY FACILITY OR
PORTION THEREOF, AND THE ASSOCIATED BARRICADING
REQUIREMENTS WITHIN A MINIMUM OF 7 DAYS PRIOR TO
COMMENCING WORK.
3. THE CONTRACTOR IS REQUIRED TO PERFORM HIS WORK IN A
MANNER, WHICH WILL NOT CONFLICT WITH ANY OPERATION, WHICH
IS TO REMAIN FUNCTIONAL DURING THE COURSE OF THE PROJECT,
UNTIL SUCH OPERATION IS SCHEDULED TO BE SHUT DOWN.
4. THE CONTRACTOR IS REQUIRED TO COORDINATE WITH OWNER FOR
THE TEMPORARY SUSPENSION OF USE OF ANY UTILITY SYSTEM, A
MINIMUM OF 3 DAYS PRIOR TO COMMENCING WORK.
5. AT ALL LOCATIONS WHERE NEW CONSTRUCTION WILL INTERFACE
WITH EXISTING ELEMENTS, CUT THROUGH EXISTING STRUCTURE IN
STRAIGHT AND TRUE LINES TO INSURE A NEAT INTERFACE.
6. AT ALL LOCATIONS WHERE THE DEMOLITION OF A CONCRETE
MEMBER LEAVES THE ENDS OF REINF STEEL EXPOSED, PROVIDE THE
FOLLOWING:
A. CHIP CONCRETE FROM AROUND THE STEEL TO A DEPTH OF 1”.
B. CUT OFF REINF STEEL NOT LESS THAN 3/4” BELOW THE
CONCRETE SURFACE.
C. FILL THE CAVITY FLUSH WITH A HIGH MODULUS GEL EPOXY.
7. BEFORE DEMOLISHING ANY STRUCT ELEMENT, INSTALL ALL
REQUIRED TEMPORARY AND/OR PERMANENT BRACING AND
SUPPORTS.
8. PROVIDE TEMPORARY CLOSURE OF ALL ROOF FASCIA, WALL AND
OTHER OPENINGS TO PROTECT BUILDING FROM EXPOSURE TO
UNDESIRABLE ELEMENTS UNTIL NEW CONSTRUCTION IS
WEATHERPROOFED, AT WHICH TIME SUCH TEMPORARY
CONSTRUCTION SHALL BE REMOVED. ALL TEMPORARY EXTERIOR
WALLS THAT ARE SUBJECT TO WIND LOADS ARE TO BE DESIGNED BY
A DELEGATED ENGINEER.
9. UPON COMPLETION OF NEW CONSTRUCTION UNDER EACH PHASE,
ALL DEMOLISHED AREAS SHALL BE RESTORED TO ACCEPTABLE
USAGE ACCORDING TO THE CONTRACT DOCUMENTS AS DETERMINED
BY THE ENGINEER.
10. REMOVE COMPLETELY FROM THE SITE AND LEGALLY DISPOSE ALL
DEBRIS GENERATED BY THE DEMOLITION WORK AS THE WORK
PROGRESSES. STOCKPILING OF DEBRIS AND BURNING OF DEBRIS
ON THE PREMISES IS STRICTLY PROHIBITED.
MISCELLANEOUS
1. CONTRACTOR SHALL SUPPLY ALL ITEMS FOR ATTACHING MECHANICAL
AND ELECTRICAL EQUIPMENT TO THE BUILDING STRUCTURE TO
RESIST ALL LOADS INCLUDING WIND FORCES. ATTACHMENT SHALL BE
MADE SO AS NOT TO OVERSTRESS STRUCTURAL MEMBERS.
COORDINATE THE ATTACHMENTS AND LOCATIONS OF THE EQUIPMENT
WITH THE STRUCTURAL SHOP DRAWINGS. REFER TO THE
MECHANICAL AND ELECTRICAL DRAWINGS FOR ADDITIONAL
REQUIREMENTS.
2. SUBSTITUTION OF EXPANSION ANCHORS FOR ADHESIVE ANCHORS OR
EMBEDDED ANCHORS SHOWN ON THE DRAWINGS WILL NOT BE
PERMITTED UNLESS APPROVED BY THE STRUCTURAL ENGINEER IN
ADVANCE.
3. THE CONTRACTOR SHALL PROVIDE THE FOLLOWING SERVICES AS
PART OF THE CONSTRUCTION SCOPE OF WORK:
A. VERIFICATION OF ALL DIMENSIONS, ELEVATIONS, OPENING
SIZES, MECHANICAL EQUIPMENT WEIGHTS PRIOR TO
STARTING WORK.
B. REMOVE ALL ABANDONED FOUNDATIONS, UTILITIES,
PIPELINES, ETC. THAT INTERFERE WITH NEW CONSTRUCTION.
C. REVIEW AND APPROVE ALL SHOP DRAWINGS PRIOR TO
SUBMITTAL, NOTING CHANGES MADE WHICH DO NOT COMPLY
WITH DESIGN DRAWINGS.
D. PROVIDE TEMPORARY BRACING AND SHORING TO PREVENT
EXCESSIVE DEFLECTIONS AND DAMAGE DURING
CONSTRUCTION. DESIGN OF TEMPORARY BRACING AND
SHORING SHALL BE THE RESPONSIBILITY OF THE
CONTRACTOR.
E. SUPPORT OF CEILING SYSTEMS, FOLDING PARTITIONS, TOILET
PARTITIONS, COUNTERS, MISCELLANEOUS EQUIPMENT, AND
WINDOW SYSTEMS AS DEFINED IN THE ARCHITECTURAL
PLANS.
DEFLECTION CRITERIA
1. DEFLECTION CRITERIA SHALL BE IN ACCORDANCE WITH DEFLECTION
AND DRIFT LIMITS SET HEREIN.
2. THE DEFLECTION LIMITS SHALL BE COORDINATED WITH THE
ARCHITECTURAL DRAWINGS BASED ON THE MATERIALS SPECIFIED BY
THE ARCHITECT. MATERIALS THAT REQUIRE DEFLECTION CRITERIA
THAT EXCEED THE LIMITS INDICATED HEREIN PER THE
MANUFACTURER'S AND/OR ARCHITECT'S RECOMMENDATIONS SHALL
MEET THE CRITERIA RECOMMENDED BY THE MANUFACTURER AND/OR
THE ARCHITECT.
3. DEFLECTION AND DRIFT LIMITS SHALL BE THE MORE STRINGENT OF
THE RATIO OR ABSOLUTE VALUES INDICATED HEREIN.
4. THE CONSTRUCTION OF THE BUILDING AND IT'S COMPONENTS SHALL
BE CONFIGURED TO ACCOMMODATE THESE MOVEMENTS.
LIVE LOAD/WIND LOAD
TOTAL DEAD & LIVE LOAD
DEFLECTION AND DRIFT LIMITS
ROOF STRUCTURE
EXTERIOR WALLS
WALLS RECEIVING STUCCO FINISH
OTHER WALLS NOT OTHERWISE SPECIFIED
WIND LOAD
DRIFT REQUIREMENTS
L/360
L/240
L/360
L/240
H/400
RATIO
3/4"
1"
ABSOLUTE
SHOP DRAWING SUBMITTALS
1. SHOP DRAWING SUBMITTALS ARE REQUIRED FOR ALL STRUCTURAL
FRAMING, ELEMENTS, COMPONENTS, AND SYSTEMS INDICATED ON
THE STRUCTURAL DRAWINGS. SHOP DRAWING SUBMITTALS INCLUDE
BUT ARE NOT LIMITED TO THE FOLLOWING:
A. CONCRETE MIX DESIGNS
B. CONCRETE FOUNDATION REINFORCING
C. PRE-ENGINEERED CONCRETE BUILDING (*)
D. ANCHORAGE OF EQUIPMENT (*),(#)
SHOP DRAWING SUBMITTALS FOR ITEMS NOT LISTED ABOVE SHALL BE
SUBMITTED FOR REVIEW UPON REQUEST BY THE STRUCTURAL
ENGINEER.
ITEMS MARKED (*) SHALL HAVE SHOP DRAWINGS SEALED BY A
PROFESSIONAL ENGINEER REGISTERED IN THE STATE OF FLORIDA.
ITEMS MARKED (#) SHALL BE SUBMITTED FOR ENGINEERS RECORD
ONLY.
2. SHOP DRAWINGS SHALL BE REVIEWED BY THE STRUCTURAL
ENGINEER FOR COMPLIANCE WITH DESIGN INTENT AND FOR
GENERAL CONFORMANCE WITH THE CONSTRUCTION DOCUMENTS.
CORRECTIONS OR COMMENTS MADE ON THE SHOP DRAWINGS SHALL
NOT RELIEVE THE CONTRACTOR FROM COMPLIANCE WITH THE
STRUCTURAL DRAWINGS AND SPECIFICATIONS. THE CONTRACTOR
SHALL BE RESPONSIBLE FOR CONFORMING AND CORRELATING
QUANTITIES, DIMENSIONS, ELEVATIONS, AND LENGTHS, FOR
SELECTING FABRICATION PROCESSES, FOR SELECTING METHODS OF
CONSTRUCTION, FOR COORDINATING SUB TRADES AND FOR
PERFORMING WORK IN A SAFE MANNER.
3. SHOP DRAWINGS SHALL BE REVIEWED BY THE CONTRACTOR AND
MARKED "APPROVED" PRIOR TO SUBMITTING THE DRAWINGS TO THE
ARCHITECT…
This is the start of the file's text. The full file is on GovTribe.