Y22-772_Drawings.pdf
PDF 13 MB Posted
- Solicitation number
- Y22-772
- Issued by
- Orange County, Orlando City, Florida
About this file
This document is a comprehensive set of technical drawings and engineering plans for the Orange County Corrections Genesis Sanitary Piping Replacement project located in Orlando, Florida. The project involves a complete sanitary piping replacement at the Orange County Corrections Genesis facility, with work spanning underground and first floor plumbing systems. The drawings, prepared by Atkins and dated September 13, 2021, include detailed plans for demolition, site and utility mapping, erosion control, structural details, architectural modifications, and plumbing system redesigns. The project involves removing existing sanitary piping, installing new piping inside and outside the building, reconnecting fixtures, and making necessary structural modifications to accommodate the new plumbing infrastructure.
The estimated project cost is $1,800,000.00, with the work focused on upgrading the sanitary piping system across multiple bathroom and facility areas. The technical drawings indicate a comprehensive approach that includes preserving and reinstalling existing fixtures where possible, installing new plumbing carriers, reconnecting vent and water pipes, and ensuring compliance with Florida Plumbing Code standards. The project involves multiple facility areas including men's and women's restrooms, staff toilets, janitor's closets, and various support spaces. The drawings suggest a meticulous renovation strategy that minimizes disruption by carefully planning demolition, pipe routing, and fixture reinstallation while maintaining the facility's operational capabilities.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Y22-772.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PROFESSIONAL SEAL
Jose Castellanos
AR0017791
Sheet Number:Drawn By:
JOB No.
Phase:
Designed By:
Date Issued:
PROFESSIONAL SEALS:
CLIENT:
SHEET TITLE:
ISSUE LOG
CONSULTANT:
Checked By:
SHEET INFORMATION:
PROJECT NAME:
No. Date Description
O
RA
N G
E C
O U
N
TY
C O
RR
EC
TI
O
N S
G
EN
ES
IS
SA
N
IT
AR
Y
PI
PI
N G
R
EP
LA
C
EM
EN
T
3r d
S tr ee t, O rla nd o, F L
482 SOUTH KELLER ROAD
ORLANDO, FL 32810
PHONE: 407.647.7275 FAX: 407.740.8958
NOT FOR CONSTRUCTION
100%
PROJECT CONTACTS:
SITE: 2400 33rd Street, Orlando, FL 32839
STATE: Florida LOCAL: Orange County
DISCIPLINE: Architectural
COMPANY ADDRESS: 4030 W. Boy Scout Boulevard Suite 700 Tampa, Florida 33607
PHONE NUMBER: 813.262.8571
PROJECT MANAGER: Jose Castellanos, AIA
DISCIPLINE: Civil
COMPANY ADDRESS: 482 South Keller Road Orlando, FL 32810
PHONE NUMBER: 407.806.4103
PROJECT MANAGER: Chris Thompson, PE
DISCIPLINE: Structural DISCIPLINE: Plumbing and Fire Protection
ORANGE COUNTY MAYOR
JERRY L. DEMINGS
DISTRICT 1 COMMISSIONER
NICOLE H. WILSON
DISTRICT 2 COMMISSIONER
CHRISTINE MOORE
DISTRICT 3 COMMISSIONER
MAYRA URIBE
DISTRICT 4 COMMISSIONER
MARIBEL GOMEZ CORDERO
DISTRICT 5 COMMISSIONER
EMILY BONILLA
DISTRICT 6 COMMISSIONER
VICTORIA P. SIPLIN
COMPANY ADDRESS: 482 South Keller Road Orlando, FL 32810
PHONE NUMBER: 407.806.4130
PROJECT MANAGER: John A. Ilter, PE
COMPANY ADDRESS: 482 South Keller Road Orlando, FL 32810
PHONE NUMBER: 407.806.4148
PROJECT MANAGER: Clifton J. Alford, PE
09/13/2021
ATKINS PROJECT NUMBER:
B
IM
/1
-O ra n g e C o u n ty
C o rr e c ti o n s G
/1
O C
C G e n e si s A
.r vt
G-001
100075349
COVER SHEET
JLC
JTH
MFT
09/13/2021
ORANGE COUNTY CORRECTIONS
GENESIS SANITARY PIPING
REPLACEMENT
100075349
100% CONSTRUCTION DOCUMENTS
09/13/2021 e: 100% CDNOT FOR CONSTRUCTION
C1 View Name
1/8" = 1'-0"
GRID LINE
DOOR/OPENING
WALL TYPE
ROOM
LEVEL /
ELEVATION
PROJECT NORTH
REVISION
BUILDING SECTION
WALL SECTION
DETAIL
SPOT ELEVATION
CENTER-LINE
ALL DETAIL IDENTIFIERS:
TOP NUMBER INDICATES DETAIL NUMBER;
BOTTOM NUMBER INDICATES SHEET NUMBER;
SIM INDICATES SIMILAR CONDITION
DRAWING
WINDOW / LOUVER
DRAFTING SYMBOL LEGEND
EXTERIOR ELEVATION
INTERIOR ELEVATION
A-1011
A101
A101
A101
1t
ROOM NAME
Name
Elevation
N
A-101
A#
TOILET ACCESSORIES XXXX.#
A#A#A
KEYNOTEXX XXXX
SCOPE OF WORK
REMOVE EXISTING PLUMBING FIXTURES FROM WALLS. DEMOLISH EXISTING WALLS AS SHOWN TO PROVIDE ACCESS TO EXISTING PIPING AND FIXTURE CARRIERS. DEMOLISH EXISTING SANITARY PIPING FROM WALLS, CHASES, AND INTERIOR FLOOR SLABS. INSTALL NEW WALLS AS SHOWN. INSTAL NEW SANITARY PIPING INSIDE THE BUILDING AND ROUTE TO BUILDING EXTERIOR. INSTALL NEW SANITARY PIPING ALONG THE BUILDING EXTERIOR PERIMETER. CONNECT NEW EXTERIOR SANITARY PIPING TO EXISTING SANITARY MANOLE. INSTALL NEW PLUMBING FIXTURES PROVIDED BY THE
OWNER AND CONNECT TO NEW PIPING.
PROFESSIONAL SEAL
Jose Castellanos
AR0017791
N
Sheet Number:Drawn By:
JOB No.
Phase:
Designed By:
Date Issued:
PROFESSIONAL SEALS:
CLIENT:
SHEET TITLE:
ISSUE LOG
CONSULTANT:
Checked By:
SHEET INFORMATION:
PROJECT NAME:
No. Date Description
O
RA
N G
E C
O U
N
TY
C O
RR
EC
TI
O
N S
G
EN
IT
AR
Y
PI
PI
N G
R
EP
LA
C
EM
EN
T
3r d
S tr ee t, O rla nd o, F L
482 SOUTH KELLER ROAD
ORLANDO, FL 32810
PHONE: 407.647.7275 FAX: 407.740.8958
NOT FOR CONSTRUCTION
100%B
IM
/1
-O ra n g e C o u n ty
C o rr e c ti o n s G
/1
O C
C G e n e si s A
.r vt
G-010
100075349
DRAWING INDEX,
ANNOTATION LEGEND &
ABBREVIATIONS
JLC
JTH
MFT
09/13/2021
ORANGE COUNTY CORRECTIONS GENESIS SANITARY PIPING
REPLACEMENT INDEX OF DRAWINGS
SHT. REF.
NO. TITLE
GENERAL INFORMATION
G-001 COVER SHEET
G-010 DRAWING INDEX, ANNOTATION LEGEND & ABBREVIATIONS
CIVIL
C-200 DEMO, EROSION CONTROL, SITE AND UTILITY PLAN
C-500 EROSION CONTROL, SITE, & UTILITY DETAILS
C-501 STORMWATER POLLUTION PREVENTION PLAN
STRUCTURAL
S-001 GENERAL NOTES, ABBREVIATIONS & SYMBOLS
S-100 MASONRY WALL AND SLAB DETAILS
S-101 TYPICAL MASONRY DETAILS
ARCHITECTURE
AD-101 DEMO FIRST FLOOR PLAN
A-111 FIRST FLOOR PLAN
A-401 LARGE SCALE PLANS TOILET ROOMS & INTERIOR
ELEVATIONS
PLUMBING
P-001 PLUMBING LEGEND
PD-111 UNDERGROUND PLUMBING DEMOLITION PLAN
PD-112 FIRST FLOOR PLUMBING DEMOLITION PLAN
P-111 UNDERGROUND PLUMBING PLAN
P-112 FIRST FLOOR PLUMBING PLAN
P-401 ENLARGED PLUMBING PLANS
P-402 ENLARGED PLUMBING PLANS
P-501 PLUMBING DETAILS
P-601 RISER DIAGRAMS
ABBREVIATIONS
MH MANHOLE
MICRO MICROWAVE
MIN MINIMUM
MISC MISCELLANEOUS
mm MILLIMETERS
MO MASONRY OPENING
MTD MOUNTED EL
MTL METAL
__________ N __________
N NORTH
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
NIC NOT IN CONTRACT
NOM NOMINAL
NTS NOT TO SCALE
__________ O __________
OC ON CENTER
OD OUTSIDE DIAMETER
OFF OFFICE
OPNG OPENING
OPP OPPOSITE
__________ P __________
PART PARTITION
PL PLATE
PLAM PLASTIC LAMINATE
PLAS PLASTER
PLYWD PLYWOOD
PNL PANEL
POS POINT OF SALE
PR PAIR
PRCST PRECAST
PREFAB PREFABRICATED
PROP PROPERTY
PSI POUNDS PER SQUARE INCH
PSIG POUNDS PER SQUARE INCH GAUGE
PT POINT
PTD PAINTED
__________ Q __________
QTY QUANTITY
__________ R __________
R RISER OR RADIUS
RCP REFLECTED CEILING PLAN
RD ROOF DRAIN
REF REFER / REFERENCE
REG REGISTER
REINF REINFORCING
REQ'D REQUIRED
RFG REFRIGERATOR
RG RANGE
RM ROOM
RO ROUGH OPENING
RTS RUBBER TRANSITION STRIP
RWC RAIN WATER CONDUCTOR
__________ S __________
S SOUTH
SAN SANITARY
SCHD SCHEDULE
SEC SECTION
SF SQUARE FOOT
SIM SIMILAR
SPKLR SPRINKLER
SQ SQUARE
SQ FT SQUARE FOOT
SS STAINLESS STEEL
STD STANDARD
STL STEEL
STN STAINED
STOR STORAGE
SUSP SUSPEND, SUSPENDED, OR SUSPENSION
SYS SYSTEM
__________ T __________
"T" TEE (BAR OR W)
T TREAD
T/ TOP OF
T/C TOP OF CURB
TB TACKBOARD
TC TERRA COTTA
TEL TELEPHONE
TEMP TEMPERED OR TEMPERATURE
TERM TERMINATE / TERMINAL
THRESH THRESHOLD
TLT TOILET
TV TELEVISION
TYP TYPICAL
__________ U __________
UH UNIT HEATER
UL UNDERWRITER'S LABORATORY
UMCT UNGLAZED MOSAIC CERAMIC TILE
UNO UNLESS NOTED OTHERWISE
__________ V __________
VEST VESTIBULE
VIF VERIFY IN FIELD
__________ W __________
W WEST
W/ WITH
W/O WITHOUT
WC WATER CLOSET
WIN WINDOW
WP WATERPROOF(ING)
WSCT WAINSCOT
WT WEIGHT
WWF WELDED WIRE REINFORCEMENT
ABBREVIATIONS
__________ A __________
& AND
@ AT
A/ ABOVE
ACP ACOUSTIC CEILING PANEL
ADJ ADJACENT, ADJUSTABLE
AED AUTOMATED EXTERNAL DEFIBRILLATOR
AFF ABOVE FINISHED FLOOR
AP ACCESS PANEL
APPROX APPROXIMATE(LY)
ARCH ARCHITECT OR ARCHITECTURAL
ASTM AMERICAN SOCIETY FOR TESTING
MATERIAL
ATTEN ATTENUATE, ATTENUATION
AVG AVERAGE
__________ B __________
B/ BOTTOM OF
B/C BOTTOM OF CURB
BC BASE CABINET
BD BOARD
BLDG BUILDING
__________ C __________
CL CENTER LINE
CLG CEILING
CLG HT CEILING HEIGHT
CLR CLEAR
CMU CONCRETE MASONRY UNIT
CO CLEAN OUT
COL COLUMN
CONC CONCRETE
CONT CONTINUOUS
CORR CORRIDOR
CT CERAMIC TILE
CY CUBIC YARD
__________ D __________
DF DRINKING FOUNTAIN
DIA DIAMETER
DIM DIMENSION
DN DOWN
DW DISHWASHER
DWG DRAWING
__________ E __________
E EAST
EA EACH
EIFS EXTERIOR INSULATION FINISH SYSTEM
EJ EXPANSION JOINT
ELEC ELECTRICAL
EMER EMERGENCY
ENCL ENCLOSE(URE)
EP ELECTRICAL PANEL
EQ EQUAL
EQUIP EQUIPMENT
EWC ELECTRIC WATER COOLER
EXIST EXISTING
EXT EXTERIOR
__________ F __________
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET
FHC FIRE HOSE CABINET
FL FLOOR
FL CO FLOOR CLEANOUT
FP FIRE PROTECTION
FPRF FIREPROOF(ING)
FR FIRE RATED OR FRAME
FT FOOT/FEET
__________ G __________
GA GAUGE
GL GLASS OR GLAZING
GRD GROUND
GWB GYPSUM WALL BOARD
__________ H __________
HB HOSE BIBB
HC HANDICAP(PED)
HDW HARDWARE
HM HOLLOW METAL
HOR HORIZONTAL
HP HIGH POINT
HTR HEATER
__________ I __________
ID INSIDE DIAMETER
IN INCH(ES)
INT INTERIOR
__________ J __________
JB JAMB
JST JOIST
JT JOINT
__________ L __________
LAM LAMINATE
LAN LOCAL AREA NETWORK CONNECTION
LAV LAVATORY
LB POUND
LF LINEAL FOOT
LP LOW POINT
LTL LINTEL
__________ M __________ m METERS
MAS MASONRY
MAX MAXIMUM
MDF MEDIUM DENSITY FIBERBOARD
MECH MECHANICAL
MEZZ MEZZANINE
MFR MANUFACTURE
B
F
O
C
B
BFOC(B)
BFOC(B)
B F
O
C B
B F
O
C
B
B F
O
C
B
BFOC(B)
B F
O C
(B
BFOC(B
BFOC(B)
B F
O C
(B
B
F
O
C
B
B
F
O
C
B
B
F
O
C
B
BFOC(B)
B F
O C
(B
BFOC(B)
BFOC(B)
B
F O
C
B
B
F
O
C
B
B
F
O
C
B
B
F
O
C
B
B
F
O
C
B
B
F
O
C
B
G
B
G B
G B
G B
G B
G B
G(B)
G
B
G
B
G(B)
G(B)
B
F
O
C
B
BFOC(B)
BFOC(B)
BFOC(B)
BFOC(B)
BFO
C(B)
BFOC(B)
BFOC(B)
BFOC(B)
BFOC(B)
B
F
O
C
B
G
B
G(B)
G(B)
G(B)
G(B)
G(B)
G(B)
G(B)
G
B
G
B
G
B
G
B
G
B
G
B
S (B
S (B
S B
S
B
S
B
PROPOSED ASPHALT PAVEMENT
SEE DETAIL 1 ON SHEET C-500
PROPOSED VEHICULAR
CONCRETE PAVEMENT
SEE DETAIL 3 ON SHEET C-500
PROPOSED ASPHALT
PAVEMENT
SEE DETAIL 1 ON SHEET C-500
PROPOSED PEDESTRIAN
CONCRETE PAVEMENT
SEE DETAIL 2 ON SHEET C-500
PROPOSED 6" CONCRETE
CURB. SEE DETAIL 6 ON
SHEET C-500
PROPOSED 6" CONCRETE
CURB. SEE DETAIL 6 ON
SHEET C-500
PROPOSED 6" CONCRETE
CURB. SEE DETAIL 6 ON
SHEET C-500
PROPOSED 6" CONCRETE
CURB. SEE DETAIL 6 ON
SHEET C-500
CONNECT TO EXISTING MANHOLE
WITH DROP CONNECTIONS
N INV = 86.30
SE INV = 88.27
SEE DETAIL 8 ON SHEET C-500 FOR
CONNECTION DETAILS.
POINT OF CONNECTION
INV = 88.30
POINT OF
CONNECTION
INV = 86.33'
OCC GENESIS BUILDING
PROPOSED
SANITARY LINE.
SEE PLUMBING
PLANS (TYP)
PROPOSED
SANITARY LINE.
SEE PLUMBING
PLANS (TYP)
3 LF 6" PVC PIPE
3 LF 6" PVC PIPE
PROPOSED ISOLATION JOINTS
ALONG BUILDING EDGE (TYP.)
SEE DETAIL 4 ON SHEET C-500
PROPOSED ISOLATION JOINT
ALONG BUILDING EDGE (TYP.)
SEE DETAIL 4 ON SHEET C-500
B
F
O
C
B
BFOC(B)
BFOC(B)
B F
O
C B
B F
O
C
B
B F
O
C
B
BFOC(B)
B F
O C
(B
BFOC(B
BFOC(B)
B F
O C
(B
B
F
O
C
B
B
F
O
C
B
B
F
O
C
B
BFOC(B)
B F
O C
(B
BFOC(B)
BFOC(B)
B
F O
C
B
B
F
O
C
B
B
F
O
C
B
B
F
O
C
B
B
F
O
C
B
B
F
O
C
B
G
B
G B
G B
G B
G B
G B
G(B)
G
B
G
B
G(B)
G(B)
B
F
O
C
B
BFOC(B)
BFOC(B)
BFOC(B)
BFOC(B)
BFO
C(B)
BFOC(B)
BFOC(B)
BFOC(B)
BFOC(B)
B
F
O
C
B
G
B
G(B)
G(B)
G(B)
G(B)
G(B)
G(B)
G(B)
G
B
G
B
G
B
G
B
G
B
G
B
S (B
S (B
S B
S
B
S
B
SAWCUT CLEAN
JOINTS (TYP)
SAWCUT CLEAN
JOINTS (TYP)
EXISTING PAVEMENT
TO BE REMOVED (TYP)
EXISTING PAVEMENT
TO BE REMOVED (TYP)
SAWCUT CLEAN
JOINTS (TYP)
EXISTING PAVEMENT
TO BE REMOVED (TYP)
SAWCUT CLEAN
JOINTS (TYP)
EXISTING DRAINAGE
STRUCTURE TO BE
PROTECTED (TYP)
LIMITS OF
EXISTING CURB TO
BE REMOVED
LIMITS OF
EXISTING CURB
TO BE REMOVED
LIMITS OF EXISTING
CURB TO BE REMOVED
OCC GENESIS BUILDING
LIMITS OF EXISTING
CURB TO BE REMOVED
DEMOLISH
EXISTING EXISTING
6" AND 8" SANITARY
CONNECTIONS AS
NEEDED AND PLUG
PROTECT
EXISTING
LIGHT POLE
PROTECT
EXISTING FIBER
OPTIC CABLE
S
F
S
F
S
F
S
F
S
F
S
F
S
F
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
S
F
S
F
SF
SF
SF SF
SF
SF
INSTALL DOUBLE ROW
SILT FENCE. SEE SHEET
C500 FOR DETAILS
PROTECT EXISTING
FIBER OPTIC CABLE
PROTECT
EXISTING
LIGHT POLE
PROTECT
EXISTING FIBER
OPTIC CABLE
PROTECT EXISTING
CHILLED WATER UTILITES
PROTECT EXISTING
CHILLED WATER UTILITES
Sheet Number:Designed By:
JOB No.100075349
Phase:
Checked By:
Date Issued:SEPTEMBER 19, 2021
PROFESSIONAL SEALS:
CLIENT:
SHEET TITLE:
ISSUE LOG
CONSULTANT:
QC Review:
SHEET INFORMATION:
PROJECT NAME:
482 SOUTH KELLER ROAD
ORLANDO, FL 32810
PHONE: 407.647.7275 FAX: 407.740.8958
No. Date Description
O
RA
NG
E
CO
UN
TY
C
O
RR
EC
TI
O
NS
G
EN
ES
IS
SA
NI
TA
RY
P
IP
IN
G
R
EP
LA
CE
M
EN
T
3R D
St re et , O rla nd o, F
L
100% CD
1 6/11/21 60% DESIGN DOCUMENTS
2 8/02/21 90% DESIGN DOCUMENTS
3 9/13/21 100% CONSTRUCTION DOCUMENTS
C-200
DEMO, EROSION CONTROL,
SITE & UTILITY PLAN
RDB
CLT
RAR
N
0 20' 40'
FULL SCALE: 1"=20'
HALF SCALE: 1"=40'
LEGEND
DEMO EXISTING PAVEMENT FOR UTILITY INSTALLATION.
PROPOSED ASPHALT PAVEMENT SECTION. SEE DETAIL 1 ON SHEET C-500.
PROPOSED PEDESTRIAN CONCRETE PAVEMENT SECTION. SEE DETAIL 2 ON SHEET C-500.
PROPOSED VEHICULAR CONCRETE PAVEMENT SECTION. SEE DETAIL 3 ON SHEET C-500.
INLET SEDIMENT FILTER
DEMOLITION NOTES
1. CONTRACTOR TO DEMOLISH AND REMOVE ALL LANDSCAPING AND IMPROVEMENTS AS
NEEDED TO COMPLETE IMPROVEMENTS.
2. THE CONTRACTOR SHALL UTILIZE SUITABLE EROSION CONTROL DURING DEMOLITION.
3. THE CONTRACTOR IS RESPONSIBLE FOR THE LEGAL DISPOSAL OF ALL DEMOLITION
DEBRIS.
4. THE CONTRACTOR SHALL LOCATE ALL EXISTING UTILITIES PRIOR TO DEMOLITION AND
WILL BE RESPONSIBLE FOR THE DAMAGE OF ANY ON-SITE OR OFF-SITE UTILITIES THAT
ARE OR ARE NOT A PART OF THIS PROJECT OR ARE NOT IDENTIFIED TO BE REMOVED.
5. THE CONTRACTOR SHALL BARRICADE THE SITE AND CONTROL TRAFFIC PER CURRENT
FDOT TRAFFIC CONTROL STANDARDS.
6. SAW CUT CLEAN, STRAIGHT EDGES WHEN REMOVING EXISTING CONCRETE PAVEMENT.
7. ALL PROTECTED INLETS AND DRAINS ARE TO BE CLEANED OUT AT THE CONCLUSION OF
CONSTRUCTION.
8. LIMITS OF ASPHALT DEMOLITION SHOWN CAN BE INCREASED OR DECREASED BASED ON
CONTRACTOR'S MEANS AND METHODS.
SITE NOTES:
1. CONTRACTOR TO MATCH EXISTING GRADE OF CONCRETE AND ASPHALT
REPLACEMENT.
1. THE PAVED STREET ADJACENT TO THE SITE ENTRANCE WILL BE SWEPT
DAILY TO REMOVE ANY EXCESS MUD, DIRT OR ROCK TRACKED FROM THE
SITE. DUMP TRUCKS HAULING MATERIAL FROM THE CONSTRUCTION SITE
WILL BE COVERED WITH A TARPAULIN.
OFFSITE VEHICLE TRACKING:
1. HORIZONTAL COORDINATES SHOWN HEREON ARE BASED UPON GPS - VRS OBSERVATIONS AND THE
FLORIDA STATE PLANE COORDINATE SYSTEM FLORIDA WEST NAD83 - 2011 ADJUSTMENT TIED TO
HORIZONTAL CONTROL POINT PID- GIS 146, ORANGE COUNTY ENGINNERING DEPARTMENT CONTROL
NETWORK.
2. BASED BEARING N 07° 56’ 53” E WAS CALCULATED BETWEEN THE SET TBM #101 AND SET TBM #100 BASED
ON THE STATE PLANE COORDINATE SYSTEM FOR THE EAST ZONE OF FLORIDA, NORTH AMERICAN DATUM
OF 1983 (NAD83).
3. THE ELEVATIONS SHOWN HEREON ARE REFERENCED TO THE NORTH AMERICAN VERTICAL
DATUM OF 1988 (NAVD88) BASED ON THE FOLLOWING ORANGE COUNTY ENGINEERING DEPARTMENT
SURVEY BENCHMARKS:
S1450002
“SET 3" O.C. SURVEY MARK DISC ON CONCRETE CURB INLET, STAMPED S-1450-002”
ELEVATION = 98.38 FT.
AND
PROVED WITH A GPS OBSERVATION. NO OTHER COUNTY BENCHMARK WAS FOUND ON THE VICINITY OF
THE PROJECT SITE.
4. THE ELEVATIONS OF WELL-IDENTIFIED FEATURES AS DEPICTED ON THIS SURVEY AND MAP WERE
MEASURED TO AN ESTIMATED VERTICAL POSITIONAL ACCURACY OF 1/10 FOOT FOR NATURAL GROUND
AND 1/100 FOOT FOR HARDSCAPE SURFACES.
5. FIELD WORK WAS COMPLETED ON MAY 19, 2021.
6. THIS PRODUCT DOES NOT REPRESENT A BOUNDARY SURVEY.
7. THIS TOPOGRAPHIC SURVEY WAS PREPARED IN CONFORMANCE WITH THE STANDARDS OF PRACTICE AS
SET FORTH BY THE FLORIDA BOARD OF PROFESSIONAL SURVEYORS AND MAPPERS IN CHAPTER 5J-17, FLORIDA ADMINISTRATIVE CODE PURSUANT TO SECTION 472.027, FLORIDA STATUTES.
SURVEY NOTES
N
0 20' 40'
FULL SCALE: 1"=20'
HALF SCALE: 1"=40'
EXISTING SANITARY MANHOLE
EXISTING STORM SEWER MANHOLE
EXISTING SANITARY SEWER LINE
EXISTING STORM SEWER PIPE
EXISTING WATER LINE
EXISTING BURIED POWER CABLE
EXISTING BURIED GAS
S(B)
W(B)
BE(B)
G(B)
EXISTING BURIED FIBER OPTIC CABLE
PROPOSED SANITARY SEWER PIPE.
PROPOSED SANITARY SEWER PIPE BY OTHERS. SEE
SHEET P-120 IN PLUMBING PLANS FOR ADDITIONAL
INFORMATION.
PROPOSED DOUBLE-ROW SILT FENCE
BFOC(B)
DEMO & EROSION CONTROL PLAN SITE & UTILITY PLAN
UTILITY NOTES:
1. CONTRACTOR TO NOTIFY ALL UTILITY COMPANIES FOR EXACT LOCATION OF
UNDERGROUND UTILITIES PRIOR TO CONSTRUCTION.
2. CONTRACTOR RESPONSIBLE TO PROTECT FROM DAMAGE FOR ALL
UNDERGROUND CONDUITS AND SLEEVES FOR ELECTRICAL, IRRIGATION AND
COMMUNICATIONS.
3. THE CONTRACTOR SHALL EXERCISE EXTREME CAUTION WHEN EXCAVATING
IN PROXIMITY OF ALL UTILITIES. EXISTING UTILITY LOCATIONS SHOWN ON
PLANS ARE NOT EXACT OR GUARANTEED.
4. CONTRACTOR TO COORDINATE ANY TEMPORARY RELOCATION OF ANY
UTILITIES NEEDED FOR CONSTRUCTION.
SFSF
Sheet Number:Designed By:
JOB No.100075349
Phase:
Checked By:
Date Issued:SEPTEMBER 19, 2021
PROFESSIONAL SEALS:
CLIENT:
SHEET TITLE:
ISSUE LOG
CONSULTANT:
QC Review:
SHEET INFORMATION:
PROJECT NAME:
482 SOUTH KELLER ROAD
ORLANDO, FL 32810
PHONE: 407.647.7275 FAX: 407.740.8958
No. Date Description
O
RA
NG
E
CO
UN
TY
C
O
RR
EC
TI
O
NS
G
EN
ES
IS
SA
NI
TA
RY
P
IP
IN
G
R
EP
LA
CE
M
EN
T
3R D
St re et , O rla nd o, F
L
100% CD
1 6/11/21 60% DESIGN DOCUMENTS
2 8/02/21 90% DESIGN DOCUMENTS
3 9/13/21 100% CONSTRUCTION DOCUMENTS
C-500
EROSION CONTROL,
RDB
CLT
RAR
PVC
PRECAST
MANHOLE
WALL
STAINLESS STEEL BAND
RESILIENT CONNECTOR
STAINLESS STEEL PIPE CLAMP
NEW AND EXISTING MANHOLES
NOTES:
1. DROP PIPE AND FITTINGS SHALL BE OF EQUAL SIZE AND MATERIAL AS THE INFLUENT
SEWER.
2. AN OUTSIDE DROP CONNECTION SHALL BE REQUIRED FOR ALL INFLUENT LINES WHICH
HAVE AN INVERT 2' OR MORE ABOVE THE MANHOLE INVERT.
3. CONTRACTOR TO COORDINATE THE PRESENCE OF UTILITIES INSPECTOR DURING
CORING AND CONNECTIONS TO EXISTING MANHOLES.
C-500
GRAVITY MANHOLE CONNECTION
SCALE: NTS
S
E
O T
E
T R
E N
C H
A C
K F
I L L
W/ SIZE OF PIPE
VARIES
SEE NOTE 4
PIPE O.D.
COMMON FILL
12" (TYP)
FINISHED GRADE
NOTES:
1. INITIAL BACKFILL AND HAUNCHING: SELECT COMMON FILL COMPACTED TO 95% (98%
UNDER PAVEMENT) OF THE MAXIMUM DENSITY AS PER AASHTO T-180.
2. TRENCH BACKFILL: COMMON FILL COMPACTED TO 95% (98% UNDER PAVEMENT) OF THE
MAXIMUM DENSITY AS PER AASHTO T-180.
3. PIPE BEDDING UTILIZING SELECT COMMON FILL OR BEDDING ROCK IN ACCORDANCE
WITH TYPE A BEDDING AND TRENCHING DETAIL MAY BE REQUIRED AS DIRECTED BY
UTILITIES.
4. 15" MAX. (12" MIN.) FOR PIPE DIAMETER LESS THAN 24" AND 24" MAX (12" MIN) FOR PIPE
DIAMETER 24" AND LARGER.
5. WATER SHALL NOT BE PERMITTED IN THE TRENCH DURING CONSTRUCTION.
6. ALL PIPE TO BE INSTALLED WITH BELL FACING UPSTREAM TO THE DIRECTION OF THE
FLOW.
7. FINAL RESTORATION IN IMPROVED AREAS SHALL BE IN COMPLIANCE WITH ALL
APPLICABLE REGULATIONS OF GOVERNING AGENCIES. SURFACE RESTORATION
WITHIN ORANGE COUNTY RIGHT-OF-WAY SHALL COMPLY WITH REQUIREMENTS OF
RIGHT-OF-WAY UTILIZATION REGULATIONS AND ROAD CONSTRUCTION
SPECIFICATIONS.
TRENCH WIDTH
SELECT COMMON
FILL
INITIAL
BACKFILL
S
T
E
HAUNCHING
L I F
T S
M
X
I M
U M
UNDISTURBED EARTH
(SEE NOTE 3)
C-500
BEDDING AND TRENCHING - TYPE A
SCALE: NTS
S
T
E
T R
E N
H
C
K F
I L L
L I F
S
X
I M
U M
W/ SIZE OF PIPE
VARIES
SEE NOTE 4
PIPE O.D.
COMMON FILL
BEDDING MATERIAL
12" (TYP)
UNDISTURBED EARTH
FINISHED GRADE
NOTES:
1. INITIAL BACKFILL: SELECT COMMON FILL COMPACTED TO 95% (98% UNDER PAVEMENT) OF
THE MAXIMUM DENSITY AS PER AASHTO T-180.
2. TRENCH BACKFILL: COMMON FILL COMPACTED TO 95% (98% UNDER PAVEMENT) OF THE
MAXIMUM DENSITY AS PER AASHTO T-180.
3. TYPE A BEDDING MATERIAL SHALL CONFORM TO FDOT NO. 57 AGGREGATE.
4. 15" MAX. (12" MIN.) FOR PIPE DIAMETER LESS THAN 24" AND 24" MAX (12" MIN) FOR PIPE
DIAMETER 24" AND LARGER.
5. WATER SHALL NOT BE PERMITTED IN THE TRENCH DURING CONSTRUCTION.
6. ALL PIPE TO BE INSTALLED WITH BELL FACING UPSTREAM TO THE DIRECTION OF THE
FLOW.
7. BEDDING DEPTH SHALL BE 4" MINIMUM FOR PIPE DIAMETER UP TO 12" AND 6" MINIMUM FOR
PIPE DIAMETER 16" AND LARGER.
8. DEPTH FOR REMOVAL OF UNSUITABLE MATERIAL SHALL GOVERN DEPTH OF BEDDING
ROCK BELOW THE PIPE. UTILITIES SHALL DETERMINE IN THE FIELD REQUIRED REMOVAL OF
UNSUITABLE MATERIAL TO REACH SUITABLE FOUNDATION.
9. FINAL RESTORATION IN IMPROVED AREAS SHALL BE IN COMPLIANCE WITH ALL APPLICABLE
REGULATIONS OF GOVERNING AGENCIES. SURFACE RESTORATION WITHIN ORANGE
COUNTY RIGHT-OF-WAY SHALL COMPLY WITH REQUIREMENTS OF R/W UTILIZATION
REGULATIONS AND ROAD CONSTRUCTION SPECIFICATIONS.
TRENCH WIDTH
SELECT COMMON
FILL
INITIAL
BACKFILL
S
E E
N O
S
E E
N O
HAUNCHING
BEDDING
(SEE NOTES 7 & 8)
C-500
BEDDING AND TRENCHING - TYPE B
SCALE: NTS
SEWER MAIN
LATERAL
DOUBLE
SPRING LINE
LATERAL
SINGLE
R
W
NOTES:
1. INVERT OF SERVICE LATERAL SHALL NOT ENTER SEWER MAIN BELOW SPRING LINE.
2. SERVICE LATERAL SHALL BE CAPPED BY DEVELOPER'S SITE-WORK CONTRACTOR.
3. WYE TO BE NO SHALLOWER THAN 3-FEET AND NO DEEPER THAN 5-FEET.
4. LOCATOR BALLS TO BE INSTALLED BY DEVELOPER'S SITE-WORK CONTRACTOR, ONE
PER SERVICE.
5. ALL FITTINGS SHOWN ARE TO BE INSTALLED.
6. SERVICE CONNECTIONS SHALL BE PERMANENTLY MARKED BY CUTTING AN "S" IN THE
CURB DIRECTLY OVER THE LATERAL.
7. BUILDER'S PLUMBER WILL REMOVE PLUG, INSTALL CLEANOUT, AND CONNECT SERVICE
LATERAL TO HOUSE.
6" 45°
BEND
WYE WITH
6" BRANCH
S
6" 45°
BEND
WYE WITH
6" BRANCH
SEWER MAIN
SIZE VARIES
DOUBLE
WYE WITH
6" BRANCH
CLEAN-OUT
(TYP)
ROTATE
30° (TYP.)
LOT
LINE
SLOPE TO TERMINAL DEPTH
@ 1.0% MIN (TYP.)
CURB (SEE NOTE 4)
M
I N
S
T
E
TEMP PLUG
(TYP.) (SEE
NOTES 2 AND 7)
R
W
R
W
R
W
STAKE TO SHOW LOCATION OF
TEMPORARY PLUG. (TYP.)
(TYP.) BUILDER'S
PLUMBER (SEE
NOTE 7)
(TYP.) TEMP. PLUG
(SEE NOTES 2 AND 7)
PROFILE
NTS
PLAN
NTS
(TYP.)
BUILDER'S
PLUMBER
(SEE NOTE 7)
LOCATOR BALL
6" MAX BELOW PIPE
(TYP) SEE NOTE 4
FINISHED
GRADE
C-500
SERVICE LATERAL
SCALE: NTS
GRAVITY OUTSIDE DROP CONNECTION (EXISTING MANHOLE)
6" MIN
6"
MIN
#4 90° HOOK AT 8" O.C.E.W.
C-500
ASPHALT PAVEMENT SECTION
SCALE: NTS
EXISITNG SOIL.
10" CRUSHED CONCRETE BASE (LBR 150)
FROM APPROVED FDOT SOURCE.
12" SUBGRADE COMPACTED TO MIN DENSITY OF 98% MODIFIED
PROCTOR MAXIMUM DRY DENSITY (ASTM D-1557, AASHTO T-180)
AND STABILIZED TO MIN LBR 40.
C-500
ASPHALT PAVEMENT SPLICE DETAIL
SCALE: NTS
C-500
CONCRETE JOINT DETAILS
SCALE: NTS
C-500
VEHICULAR CONCRETE PAVEMENT SECTION
SCALE: NTS
SUB-GRADE
CONCRETE 8" THICKNESS, 4,000 PSI CONC, MIN 28 DAY COMPRESSIVE
STRENGTH W/ FIBER MESH @ 1.5 LBS/CY.
12" COMPACTED SUB-GRADE LBR 40 COMPACTED TO 98%
AASHTO T-180
SUB-GRADE
CONCRETE
8"
12"
SINGLE-COMPONENT
POLYURETHANE SEALANT 3/4" THICK
CLOSED CELL SEMI-RIGID
PLASTIC JOINT FILLER
SINGLE-COMPONENT
POLYURETHANE SEALANT 3/4"
THICK
CLOSED CELL SEMI-RIGID PLASTIC
JOINT FILLER
OR
CONSTRUCTION JOINT
0.2*D
0.1*D
1/2"
STRUCTURE
D
ISOLATION JOINT
D
1/2"
1/4"
D/4
D
CONTROL JOINT
EXPANSION JOINT
D
FILTERED WATER
SECTION
PLAN
PAVEMENT (TYP)
GRATE
1" TYP1" TYP
ROCK / SAND BAGS OR BIOFILTER
BAGS (PLACED END TO END)
WRAP GRATE WITH FILTER
FABRIC WITH OVERLAPPING TOP
FLAPS
WRAP GRATE WITH FILTER
FABRIC WITH OVERLAPPING
TOP FLAPS
ROCK / SAND BAGS OR
BIOFILTER BAGS (PLACED
END TO END)
C-500
INLET SEDIMENT FILTER DETAIL
SCALE: NTS
2 1/2" SP 9.5 ASPHALTIC CONCRETE (TWO LIFTS)
EXISTING SUBGRADE PROPOSED SUBGRADE
1. PROVIDE ASPHALT SPLICE AT ALL TRANSITIONS BETWEEN NEW
AND EXISTING PAVEMENT SECTIONS.
2. 12-INCH MINIMUM ASPHALT REMOVAL, MAY VARY AT THE
DISCRETION OF THE OWNER'S REPRESENTATIVE. (MAYBE MORE
BUT NOT LESS THAN 12 INCHES)
3. RESTORE EXISTING BASE TO ORIGINAL CONDITION OR BETTER.
EXISTING BASE PROPOSED BASE
12"
SAWCUT, REMOVE AND REPLACE
12" OF EXISTING ASPHALT
PAVEMENT
PROPOSED ASPHALT
PAVEMENT
EXISTING ASPHALT
PAVEMENT
NOTES:
SPLICE
12" MIN12" MIN
M
I N
SUBGRADE
BASE
FINISH GRADE SHALL BE 2" BELOW
TOP OF CURB FOR SOD PLANTING.
6"
HARDSCAPE MATERIAL VARIES
6"x18" POURED IN PLACE CONCRETE
CURB, 3000 PSI.
C-500
6" CONCRETE CURB DETAIL
SCALE: NTS
C-500
PEDESTRIAN CONCRETE PAVEMENT SECTION
SCALE: NTS
SUB-GRADE
CONCRETE 4" THICKNESS, 3,000 PSI CONC, MIN 28 DAY COMPRESSIVE
STRENGTH W/ FIBER MESH @ 1.5 LBS/CY.
12" COMPACTED SUB-GRADE LBR 40 COMPACTED TO 98%
AASHTO T-180
SUB-GRADE
CONCRETE4"
12"
SITE, & UTILITY DETAILS
SECTION
S
I L
O
W
FILTER FABRIC
V E
R T
I C
A L
PRINCIPLE POST
POSITION
(CANTED 20°
TOWARD FLOW)
OPTIONAL POST
POSITIONS
ELEVATION
T
O
M
I N
M I N
POST OPTIONS:
SOFTWOOD 2-1/2" DIA
SOFTWOOD 2"x4"
HARDWOOD 1-1/2"x1-1/2"
STEEL 1.33 LBS/FT MIN)
6' MAX
FILTER FABRIC
(IN CONFORMANCE
WITH SEC. 985 FDOT
SPEC.)
C-500
SILT FENCE DETAIL (TYPE III PER FDOT INDEX 102)
SCALE: NTS
S
I
O
W
FILTER FABRIC
V E
R T
I C
A L
PRINCIPLE POST
POSITION
(CANTED 20°
TOWARD FLOW)
OPTIONAL POST
POSITIONS
3.0'
DOUBLE ROW
ONLY WHERE
SHOWN ON PLAN
NOTE: INSTALL IN ACCORDANCE WITH SILT
FENCE DETAIL, EXCEPT AS NOTED ABOVE.
C-500
SILT FENCE DETAIL
SCALE: NTS
STEEL PLATE
SLIP DOWELS
STEEL PLATE
SLIP DOWELS
Sheet Number:Designed By:
JOB No.100075349
Phase:
Checked By:
Date Issued:SEPTEMBER 19, 2021
PROFESSIONAL SEALS:
CLIENT:
SHEET TITLE:
ISSUE LOG
CONSULTANT:
QC Review:
SHEET INFORMATION:
PROJECT NAME:
482 SOUTH KELLER ROAD
ORLANDO, FL 32810
PHONE: 407.647.7275 FAX: 407.740.8958
No. Date Description
O
RA
NG
E
CO
UN
TY
C
O
RR
EC
TI
O
NS
G
EN
ES
IS
SA
NI
TA
RY
P
IP
IN
G
R
EP
LA
CE
M
EN
T
3R D
St re et , O rla nd o, F
L
100% CD
1 6/11/21 60% DESIGN DOCUMENTS
2 8/02/21 90% DESIGN DOCUMENTS
3 9/13/21 100% CONSTRUCTION DOCUMENTS
C-501
RDB
CLT
RAR
STORMWATER POLLUTION
PREVENTION PLAN
DISTRICT'S REQUIREMENTS CONTRACTOR'S REQUIREMENTS
SECTION / DETAIL
MARK
VARIES
SEE PLAN
ELEVATION MARK
RECESS IN
SLAB
N
NORTH ARROW
TYPICAL
OPENING
MOMENT
CONNECTION
FTG. OR PILE CAP MARK
T/ FTG. OR PILE CAP EL.
(WIDTH x DEPTH)
TYPICAL BEAM DIMENSIONS
SPAN DIRECTION
PLAN / DETAIL MARK
METAL DECK
SPAN DIRECTION
METAL DECK SPAN
DIRECTION W/
CONC. TOPPING
STRUCTURAL SYMBOLS
STRUCTURAL GENERAL NOTES
GENERAL STRUCTURAL CRITERIA
1. STRUCTURE IS DESIGNED TO BE SELF-SUPPORTING AND STABLE ONCE IN
SERVICE. NO CONSIDERATION FOR STABILITY AND SHORING IS ASSUMED
BY THE ENGINEER DURING THE BUILDING PROCESS. IT SHALL BE THE
CONTRACTOR'S RESPONSIBILITY TO INSURE THE STABILITY AND SAFETY
OF THE STRUCTURE AND ITS COMPONENTS BY DETERMINING AND
IMPLEMENTING ERECTION PROCEDURES AND SEQUENCE OF
CONSTRUCTION. THIS INCLUDES TEMPORARY BRACING AND SHORING AS
WELL AS SOIL STABILIZATION AND PROTECTIVE MEASURES FOR
ADJACENT EXISTING CONSTRUCTION.
2. STRUCTURAL DRAWINGS AND SPECIFICATIONS SHALL BE UTILIZED
CONCURRENTLY WITH ARCHITECTURAL, SITE, AND ENGINEERING
DRAWINGS OF OTHER DISCIPLINES TO CONSULT INFORMATION NOT
EXPLICITLY INDICATED ON STRUCTURAL DRAWINGS.
3. CONTRACTOR SHALL VERIFY DIMENSIONS AND SITE CONDITIONS PRIOR
TO PROCEEDING WITH PROCUREMENT OF MATERIALS AND LABOR,
FABRICATION, AND CONSTRUCTION WORK. WHERE DISCREPANCIES
EXIST, NOTIFY ARCHITECT / ENGINEER OF SUCH DISCREPANCIES IN
WRITING VIA A REQUEST FOR INFORMATION / INTERPRETATION (RFI)
BEFORE PROCEEDING WITH THE WORK IN THE AFFECTED AREA IN
QUESTION.
4. NO STRUCTURAL MEMBER OR COMPONENT SHALL BE CUT, NOTCHED, OR
OTHERWISE ALTERED UNLESS APPROVED IN WRITING BY STRUCTURAL
ENGINEER. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ANY AND ALL
COSTS INCURRED BY STRUCTURAL ENGINEER FOR REVIEW OF SUCH
DEVIATIONS AND IMPLEMENTATION OF APPROPRIATE SOLUTIONS.
5. PRIOR TO COMMENCING WORK, THE GENERAL CONTRACTOR SHALL BE
RESPONSIBLE FOR REVIEWING AND COORDINATING WITH THE SUB-
CONTRACTORS WORK INDICATED ON STRUCTURAL DRAWINGS WITH
ARCHITECTURE, SITE WORK, DELEGATED COMPONENTS, AND THE WORK
OF OTHER ENGINEERING DISCIPLINES.
6. THE STRUCTURAL DRAWINGS AND SPECIFICATIONS ARE
REPRESENTATIVE OF THE FINISHED STRUCTURE. THE STRUCTURAL
ENGINEER SHALL NOT BE IN RESPONSIBLE CHARGE AND CONTROL OF
CONSTRUCTION MEANS, METHODS, PROCEDURES AND CONSTRUCTION
TECHNIQUES, AND JOBSITE SAFETY. THIS SHALL BE THE RESPONSIBILITY
OF THE CONTRACTOR.
7. THE STRUCTURAL ENGINEER SHALL NOT BE CONSTRUED AS HAVING
CONTROL, CHARGE, AND RESPONSIBILITY FOR THE ACTS AND OMISSIONS
AND FOR FAILURE OF THE CONTRACTOR, SUB-CONTRACTOR, AND OTHER
PERSONS PERFORMING THE WORK TO CARRY OUT SUCH WORK IN
ACCORDANCE WITH THE STRUCTURAL DRAWINGS AND COLLECTIVE
CONTRACT DOCUMENTS.
8. PERIODIC SITE OBSERVATION BY THE STRUCTURAL ENGINEER AND HIS /
HER REPRESENTATIVES IS SOLELY FOR THE PURPOSE OF DETERMINING
IF THE WORK OF THE CONTRACTOR IS PROCEEDING IN GENERAL
ACCORDANCE WITH THE STRUCTURAL DRAWINGS AND SPECIFICATIONS.
THIS LIMITED SITE OBSERVATION SHALL NOT BE CONSTRUED AS AN
INSPECTION, EXHAUSTIVE, OR CONTINUOUS OBSERVATION TO VERIFY
THE QUALITY AND QUANTITY OF THE WORK.
9. THE USE OF REPRODUCTIONS OF THESE STRUCTURAL DRAWINGS AND
SPECIFICATIONS AND USE OF ELECTRONIC FILES AND MODELS BY ANY
CONTRACTOR, SUBCONTRACTOR, ERECTOR, FABRICATOR OR MATERIAL
SUPPLIER IN LIEU OF PREPARATION OF SHOP DRAWINGS IS PROHIBITED
UNLESS PRIOR WRITTEN APPROVAL IS OBTAINED FROM THE STRUCTURAL
ENGINEER.
10. IN THE EVENT THERE IS CONFLICTING INFORMATION BETWEEN THE
DRAWINGS, SPECIFICATIONS AND LOCAL CODE APPLICATIONS OR ANY
OTHER CONTROLLING AUTHORITY, THE MOST STRINGENT CONDITION
SHALL APPLY.
DEFLECTION CRITERIA
1. DEFLECTION CRITERIA SHALL BE IN ACCORDANCE WITH DEFLECTION
AND DRIFT LIMITS SET HEREIN.
2. THE DEFLECTION LIMITS SHALL BE COORDINATED WITH THE
ARCHITECTURAL DRAWINGS BASED ON THE MATERIALS SPECIFIED BY
THE ARCHITECT. MATERIALS THAT REQUIRE DEFLECTION CRITERIA THAT
EXCEED THE LIMITS INDICATED HEREIN PER THE MANUFACTURER'S
AND/OR ARCHITECT'S RECOMMENDATIONS SHALL MEET THE CRITERIA
RECOMMENDED BY THE MANUFACTURER AND/OR THE ARCHITECT.
3. DEFLECTION AND DRIFT LIMITS SHALL BE THE MORE STRINGENT OF THE
RATIO OR ABSOLUTE VALUES INDICATED HEREIN.
4. THE CONSTRUCTION OF THE BUILDING AND IT'S COMPONENTS SHALL BE
CONFIGURED TO ACCOMMODATE THESE MOVEMENTS.
DESIGN CRITERIA
1. STRUCTURAL WORK SHALL BE IN ACCORDANCE WITH:
FLORIDA BUILDING CODE 2020 EDITION 7 AS ADOPTED AND
SUPPLEMENTED BY LOCAL REGULATIONS AND ASCE 7-16.
2. REFER TO DRAWINGS OF OTHER DISCIPLINES FOR DIMENSIONS AND
ELEVATIONS NOT INDICATED ON STRUCTURAL DRAWINGS. NOTIFY
ARCHITECT / ENGINEER OF DISCREPANCIES PRIOR TO EXECUTION OF
WORK.
3. COORDINATE SIZES AND LOCATIONS OF OPENINGS IN FLOORS, WALLS
AND ROOFS WITH ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING
AND SITE REQUIREMENTS.
4. REFER TO ARCHITECTURAL, CIVIL, MECHANICAL, ELECTRICAL, PLUMBING
AND SITE DRAWINGS FOR MATERIALS, COMPONENTS, AND CONNECTIONS
NOT SHOWN HEREIN, AND FOR ANCHORED, SUPPORTED AND EMBEDDED
ITEMS WHICH AFFECT THE STRUCTURAL WORK. VERIFY DETAILS AND
DIMENSIONS WITH EQUIPMENT PURCHASED.
5. NO PROVISIONS HAVE BEEN MADE FOR FUTURE VERTICAL AND/OR
HORIZONTAL ADDITIONS, MODIFICATIONS, AND/OR EXPANSIONS EXCEPT
AS SHOWN ON THE STRUCTURAL DRAWINGS.
6. STRUCTURAL ENGINEER IS NOT RESPONSIBLE FOR THE DESIGN OF
PREFABRICATED STAIRS, HANDRAILS, CURTAIN WALL / WINDOW WALL
SYSTEMS, COLD-FORMED STEEL FRAMING, OR OTHER SYSTEMS
DELEGATED OR NOT SHOWN IN THE STRUCTURAL DRAWINGS. SUCH
SYSTEMS SHALL BE DESIGNED, FURNISHED, AND INSTALLED BY OTHER
PORTIONS OF THE CONTRACT DOCUMENTS.
7. REFERENCED DATUM FOR THE PROJECT SHALL BE TAKEN AS 0'-0"
ESTABLISHED FROM SLAB ON GRADE FINISH FLOOR. VERIFY ACTUAL
ELEVATIONS WITH CIVIL DRAWINGS.
MECHANICAL AREA
FLOOR
ROOF
GRAVITY LOADS
LIVE LOAD REDUCTION ON SUPPORTING ELEMENTS SHALL BE IN
ACCORDANCE WITH THE BUILDING CODE. NO LIVE LOAD REDUCTION
OF ROOF LOADING IS PERMITTED. UNIFORMED DEAD LOAD IS
ADDITIVE TO ACTUAL STRUCTURAL WEIGHTS.
LOCATION
UNIFORM
DEAD LOAD
(PSF)
CONC.
DEAD LOAD
(LBS)
UNIFORM
LIVE LOAD
(PSF)
--- 125
--- 80
--- 20
CONC.
LIVE LOAD
(PSF)
MATERIAL
WEIGHT
DESIGN LOADING
SHOP DRAWING SUBMITTALS
1. SHOP DRAWING SUBMITTALS ARE REQUIRED FOR ALL STRUCTURAL
FRAMING, ELEMENTS, COMPONENTS, AND SYSTEMS INDICATED ON THE
STRUCTURAL DRAWINGS. SHOP DRAWING SUBMITTALS INCLUDE BUT ARE
NOT LIMITED TO THE FOLLOWING:
A. CONCRETE MIX DESIGNS
B. CONCRETE FOUNDATION REINFORCING SUBMITTALS
C. CONCRETE AND MASONRY FRAMING SUBMITTALS W/ ELEVATION
DRAWINGS CLEARLY INDICATING REINFORCING, SPLICING, AND
LOCATION OF ALL CONCRETE AND MASONRY FRAMING
D. STRUCTURAL STEEL SUBMITTALS (*)
E. STEEL DECK SUBMITTALS (*)
F. STEEL JOISTS AND JOIST GIRDERS (*)
G. STRUCTURAL STEEL CONNECTIONS NOT DETAILED OTHERWISE ON
THESE DRAWINGS (*)
H. PRE-FABRICATED CANOPY AND AWNING STRUCTURES,
DECORATIVE BRACKETS, AND OTHER ARCHITECTURAL
COMPONENTS (*)
I. PRECAST LINTELS AND SILLS (*)
J. ANCHORAGE OF ROOFTOP EQUIPMENT (*),(#)
K. SHORING (*)
SHOP DRAWING SUBMITTALS FOR ITEMS NOT LISTED ABOVE SHALL BE
SUBMITTED FOR REVIEW UPON REQUEST BY THE STRUCTURAL
ENGINEER.
ITEMS MARKED (*) SHALL HAVE SHOP DRAWINGS SEALED BY A
PROFESSIONAL ENGINEER REGISTERED IN THE STATE OF FLORIDA.
ITEMS MARKED (#) SHALL BE SUBMITTED FOR ENGINEERS RECORD ONLY.
2. SHOP DRAWINGS SHALL BE REVIEWED BY THE STRUCTURAL ENGINEER
FOR COMPLIANCE WITH DESIGN INTENT AND FOR GENERAL
CONFORMANCE WITH THE CONSTRUCTION DOCUMENTS. CORRECTIONS
OR COMMENTS MADE ON THE SHOP DRAWINGS SHALL NOT RELIEVE THE
CONTRACTOR FROM COMPLIANCE WITH THE STRUCTURAL DRAWINGS
AND SPECIFICATIONS. THE CONTRACTOR SHALL BE RESPONSIBLE FOR
CONFORMING AND CORRELATING QUANTITIES, DIMENSIONS,
ELEVATIONS, AND LENGTHS, FOR SELECTING FABRICATION PROCESSES,
FOR SELECTING METHODS OF CONSTRUCTION, FOR COORDINATING SUB
TRADES AND FOR PERFORMING WORK IN A SAFE MANNER.
3. SHOP DRAWINGS SHALL BE REVIEWED BY THE CONTRACTOR AND
MARKED "APPROVED" PRIOR TO SUBMITTING THE DRAWINGS TO THE
ARCHITECT ENGINEER FOR REVIEW. SHOP DRAWINGS SHALL BE
MARKED WITH A REVIEW STAMP FROM THE CONTRACTOR INDICATING
REVIEW DISPOSITION AND SHALL BE DATED AND INITIALED. SHOP
DRAWINGS THAT HAVE NOT BEEN REVIEWED, STAMPED, DATED AND
INITIALED WILL BE CONSIDERED NOT REVIEWED BY THE CONTRACTOR
AND SHALL BE RETURNED NOT REVIEWED AND UNCHECKED BY THE
STRUCTURAL ENGINEER.
4. STRUCTURAL ENGINEER SHALL NOT BE RESPONSIBLE FOR DELAYS
CAUSED DUE TO THE REJECTION OF INCOMPLETE SUBMITTALS,
SUBMITTALS RETURNED DUE TO THE CONTRACTOR'S FAILURE TO
REVIEW DOCUMENTS PRIOR TO RECEIPT BY THE STRUCTURAL
ENGINEER, AND FOR THE ADDITIONAL TIME REQUIRED BY THE
CONTRACTOR'S SUB TRADES TO REVISE AND RE-SUBMIT THE DRAWINGS
AND FOR THE STRUCTURAL ENGINEER TO PERFORM ADDITIONAL
REVIEWS OF NON-CONFORMING SUBMITTALS.
5. UPON RECEIPT OF SHOP DRAWING SUBMITTALS FROM THE CONTRACTOR
THAT HAVE BEEN REVIEWED, STAMPED, DATED, AND INITIALED BY THE
CONTRACTOR, THE ENGINEER SHALL BEGIN REVIEW OF THE RECEIVED
SUBMITTALS. THE CONTRACTOR SHALL ALLOW FOURTEEN (14) WORKING
DAYS FOR SUBMITTAL REVIEW BY THE STRUCTURAL ENGINEER FROM
RECEIPT OF SHOP DRAWINGS. THE CONTRACTOR SHALL FURTHER
ALLOW TEN (10) WORKING DAYS FROM RECEIPT OF SHOP DRAWING RE-
SUBMITTALS FOR REVIEW BY THE STRUCTURAL ENGINEER.
6. THE STRUCTURAL ENGINEER'S OBLIGATIONS TO REVIEW SHOP
DRAWINGS AND OTHER SUBMITTALS AND TO RETURN THEM IN A TIMELY
MANNER ARE CONDITIONED UPON THE PRIOR REVIEW AND APPROVAL OF
THE SHOP DRAWINGS OR SUBMITTALS BY THE CONTRACTOR AS
REQUIRED IN THE CONSTRUCTION CONTRACT AND THE CONTRACTOR'S
SUBMITTAL OF THE SHOP DRAWINGS AND OTHER SUBMITTALS IN
ACCORDANCE WITH A WRITTEN SCHEDULE DISTRIBUTED IN ADVANCE TO
THE ENGINEER IDENTIFYING THE DATES FOR THE SUBMITTAL OF THE
VARIOUS SHOP DRAWINGS AND SUBMITTALS.
7. THE STRUCTURAL ENGINEER SHALL NOT BE RESPONSIBLE FOR
MATERIALS THAT ARE FABRICATED, DELIVERED, AND INSTALLED AT THE
SITE WITHOUT A SET OF SHOP SUBMITTALS THAT HAVE BEEN REVIEWED
AND APPROVED BY THE STRUCTURAL ENGINEER. COSTS ASSOCIATED
WITH THE REMOVAL OF UNAPPROVED MATERIALS AND THE DELAYS
ASSOCIATED WITH THE REPAIR, RECONFIGURATION, AND/OR REMOVAL
OF SUCH MATERIALS SHALL NOT BE THE RESPONSIBILITY OF THE
STRUCTURAL ENGINEER.
8. SHOP DRAWINGS REVIEWED BY THE STRUCTURAL ENGINEER AND
RETURNED WITH A MARK OF 'REJECTED' OR 'REVISE AND RESUBMIT'
SHALL BE RE-SUBMITTED FOR REVIEW BY THE STRUCTURAL ENGINEER.
REVISIONS MADE TO SHOP DRAWINGS SHALL BE CLEARLY MARKED AND
THE PURPOSE FOR THE RE-SUBMISSION SHALL BE CLEARLY NOTED ON
THE SHOP DRAWING TRANSMITTAL. REVISIONS SHALL BE ASSIGNED A
SEQUENTIAL REVISION NUMBER.
9. THE CONTRACT DOCUMENTS SHALL GOVERN OVER THE SHOP
DRAWINGS UNLESS OTHERWISE SPECIFIED IN WRITING BY THE
ENGINEER.
MISCELLANEOUS
1. CONCRETE PADS FOR MECHANICAL AND ELECTRICAL EQUIPMENT ON
FLOORS SHALL BE NO LESS THAN 4" HIGH UNLESS NOTED OTHERWISE
AND REINFORCED WITH #3 BARS ON 12" O.C. EACH WAY, 1 1/2" FROM
TOP OF SLAB. WHEN THE PAD EXCEEDS 10" IN THICKNESS, REINFORCE
WITH #3 BARS ON 12" O.C. EACH WAY, TOP AND BOTTOM. ANCHOR PAD
TO SLAB WITH #4 DOWELS AT 24" O.C. EACH WAY, CAST OR
CHEMICALLY ADHERED INTO SUPPORTING SLAB.
2. CONTRACTOR SHALL SUPPLY ALL ITEMS FOR ATTACHING MECHANICAL
AND ELECTRICAL EQUIPMENT TO THE BUILDING STRUCTURE TO RESIST
ALL LOADS INCLUDING WIND FORCES. ATTACHMENT SHALL BE MADE
SO AS NOT TO OVERSTRESS STRUCTURAL MEMBERS. COORDINATE
THE ATTACHMENTS AND LOCATIONS OF THE EQUIPMENT WITH THE
STRUCTURAL SHOP DRAWINGS. REFER TO THE MECHANICAL AND
ELECTRICAL DRAWINGS FOR ADDITIONAL REQUIREMENTS.
3. SUBSTITUTION OF EXPANSION ANCHORS FOR ADHESIVE ANCHORS OR
EMBEDDED ANCHORS SHOWN ON THE DRAWINGS WILL NOT BE
PERMITTED UNLESS APPROVED BY THE STRUCTURAL ENGINEER IN
ADVANCE.
4. THE CONTRACTOR SHALL PROVIDE THE FOLLOWING SERVICES AS
PART OF THE CONSTRUCTION SCOPE OF WORK:
A. VERIFICATION OF ALL DIMENSIONS, ELEVATIONS, OPENING
SIZES, MECHANICAL EQUIPMENT WEIGHTS PRIOR TO STARTING
WORK.
B. REMOVE ALL ABANDONED FOUNDATIONS, UTILITIES, PIPELINES,
ETC. THAT INTERFERE WITH NEW CONSTRUCTION.
C. REVIEW AND APPROVE ALL SHOP DRAWINGS PRIOR TO
SUBMITTAL, NOTING CHANGES MADE WHICH DO NOT COMPLY
WITH DESIGN DRAWINGS.
D. PROVIDE TEMPORARY BRACING AND SHORING TO PREVENT
EXCESSIVE DEFLECTIONS AND DAMAGE DURING
CONSTRUCTION. DESIGN OF TEMPORARY BRACING AND
SHORING SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR
AS INDICATED IN SECTION 010100.
E. SUPPORT OF CEILING SYSTEMS, FOLDING PARTITIONS, TOILET
PARTITIONS, COUNTERS, MISCELLANEOUS EQUIPMENT, AND
WINDOW SYSTEMS AS DEFINED IN THE ARCHITECTURAL PLANS.
SOIL PREPARATION AND FOUNDATIONS
1. NO GEOTECHNICAL REPORT WAS PROVIDED TO THE STRUCTURAL
ENGINEER INDICATING FOUNDATION RECOMMENDATIONS BASED ON
ACTUAL SOIL CONDITIONS. EXISTING STRUCTURAL DRAWINGS
PROVIDED AN ALLOWABLE FOOTING SOIL PRESSURE OF 2,500 PSF
SO THIS VALUE WAS USED AS A PRESUMPTIVE VALUE.
2. WHERE SATISFACTORY SUBSURFACE DATA IS NOT AVAILABLE OR
WHERE THE BUILDING OFFICIAL DETERMINES NECESSARY, THE
ALLOWABLE BEARING PRESSURE SHALL BE VERIFIED BY AN
INSPECTION AND TESTING FIRM BEFORE FOOTINGS ARE PLACED
AND THE FINDINGS SHALL BE PRESENTED IN THE FORM OF A
SIGNED AND SEALED GEOTECHNICAL REPORT TO THE STRUCTURAL
ENGINEER FOR REVIEW.
3. THE CONTRACTOR SHALL PERFORM SITE PREPARATION AND
DEWATERING REQUIREMENTS BASED ON THE FBC AND ACCEPTED
INDUSTRY STANDARDS.
4. REINFORCING SHALL BE SUPPORTED FROM ABOVE OR WITH 3" SBP
(WITH BOTTOM PLATE) AT 4'-0" O.C. MAXIMUM FOR ALL FOUNDATION
REINFORCING.
5. REMOVE FREE WATER FROM EXCAVATIONS BEFORE PLACING
CONCRETE.
6. BACKFILL BELOW STRUCTURAL ELEMENTS TO BE A GRANULAR
MATERIAL HAVING MAXIMUM SIZE OF 3" AND LESS THAN 12%
PASSING THE #200 SIEVE SIZE. FILL TO BE PLACED IN LIFTS OF ONE-
FOOT OR LESS COMPACTED TO A MINIMUM OF 95% OF THE
MAXIMUM DRY DENSITY AS DETERMINED BY THE MODIFIED
PROCTOR (ASTM:D1557).
7. THE CONTRACTOR SHALL COORDINATE THE ROUTING OF BELOW
GRADE PIPING TO INSURE THAT PIPING DOES NOT PENETRATE THE
MONOLITHIC FOUNDATION. NOTIFY THE STRUCTURAL ENGINEER OF
DISCREPANCIES PRIOR TO INSTALLING BELOW GRADE PIPING
THROUGH THE FOUNDATIONS. PIPING SHALL HAVE A MINIMUM
CLEARANCE BELOW FOUNDATIONS AS DETERMINED BY THE CIVIL
ENGINEER.
EXISTING STRUCTURE
1. INFORMATION SHOWN FOR THE EXISTING STRUCTURE ON THESE
DRAWINGS WAS TAKEN FROM THE FOLLOWING:
PREPARED BY: HANSEN LIND MEYER, INC.
ENTITLED: 200 BED DORMITORY FACILITY AT 33RD STREET
CORRECTIONAL COMPLEX FOR ORANGE COUNTY, FL.
DATE: 07/29/88
2. WORK SHOWN ON THESE DRAWINGS ASSUMES THAT THE ORIGINAL
CONSTRUCTION WAS PERFORMED IN ACCORDANCE WITH THE ABOVE
INDICATED ORIGINAL DRAWINGS INCLUDING (BUT NOT LIMITED TO)
DIMENSIONS, ELEVATIONS, MEMBER SIZES, MATERIALS, DETAILS, ETC.
IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY THE
CONDITIONS RELATING TO THE EXISTING STRUCTURE AND TO NOTIFY
THE ENGINEER IMMEDIATELY OF ANY DISCREPANCIES OR CONFLICTS.
DEMOLITION NOTES
1. THE CONTRACTOR IS REQUIRED TO PROVIDE ALL TEMPORARY
SCAFFOLDING, PLATFORMS, BARRICADES, RAILINGS, SCREENING,
ETC. NECESSARY TO PROTECT EXISTING FACILITIES, STRUCTURES
AND THE PUBLIC DURING DEMOLITION AND ERECTION OF THE NEW
CONSTRUCTION, AS WELL AS FOR JOB SAFETY. JOB SAFETY,
CONSTRUCTION AND DEMOLITION PROCEDURES ARE THE SOLE
RESPONSIBILITY OF THE CONTRACTOR. THE CONTRACTOR IS
REQUIRED TO TAKE ALL PRECAUTIONS TO MINIMIZE VIBRATION,
NOISE, DUST AND DEBRIS IN ALL AREAS ADJACENT TO AREAS OF
DEMOLITION.
2. THE CONTRACTOR IS REQUIRED TO COORDINATE WITH THE OWNER
FOR THE TEMPORARY SUSPENSION OF USE OF ANY FACILITY OR
PORTION THEREOF, AND THE ASSOCIATED BARRICADING
REQUIREMENTS WITHIN A MINIMUM OF 7 DAYS PRIOR TO
COMMENCING WORK.
3. THE CONTRACTOR IS REQUIRED TO PERFORM HIS WORK IN A
MANNER, WHICH WILL NOT CONFLICT WITH ANY OPERATION, WHICH
IS TO REMAIN FUNCTIONAL DURING THE COURSE OF THE PROJECT,
UNTIL SUCH OPERATION IS SCHEDULED TO BE SHUT DOWN.
4. THE CONTRACTOR IS REQUIRED TO COORDINATE WITH OWNER FOR
THE TEMPORARY SUSPENSION OF USE OF ANY UTILITY SYSTEM, A
MINIMUM OF 3 DAYS PRIOR TO COMMENCING WORK.
5. AT ALL LOCATIONS WHERE NEW CONSTRUCTION WILL INTERFACE
WITH EXISTING ELEMENTS, CUT THROUGH EXISTING STRUCTURE IN
STRAIGHT AND TRUE LINES TO ENSURE A NEAT INTERFACE.
6. AT ALL LOCATIONS WHERE THE DEMOLITION OF A CONCRETE
MEMBER LEAVES THE ENDS OF REINFORCING STEEL EXPOSED,
PROVIDE THE FOLLOWING:
A. CHIP CONCRETE FROM AROUND THE STEEL TO A DEPTH OF 1”.
B. CUT OFF REINF STEEL NOT LESS THAN 3/4” BELOW THE
CONCRETE SURFACE.
C. FILL THE CAVITY FLUSH WITH A HIGH MODULUS GEL EPOXY.
7. BEFORE DEMOLISHING ANY STRUCTURAL ELEMENT, INSTALL ALL
REQUIRED TEMPORARY AND/OR PERMANENT BRACING AND
SUPPORTS.
8. PROVIDE TEMPORARY CLOSURE OF ALL ROOF FASCIA, WALL AND
OTHER OPENINGS TO PROTECT BUILDING FROM EXPOSURE TO
UNDESIRABLE ELEMENTS UNTIL NEW CONSTRUCTION IS
WEATHERPROOFED, AT WHICH TIME SUCH TEMPORARY
CONSTRUCTION SHALL BE REMOVED. ALL TEMPORARY EXTERIOR
WALLS THAT ARE SUBJECT TO WIND LOADS ARE TO BE DESIGNED BY
A DELEGATED ENGINEER.
9. UPON COMPLETION OF NEW CONSTRUCTION UNDER EACH PHASE,
ALL DEMOLISHED AREAS SHALL BE RESTORED TO ACCEPTABLE
USAGE ACCORDING TO THE CONTRACT DOCUMENTS AS DETERMINED
BY THE A/E.
10. REMOVE COMPLETELY FROM THE SITE AND LEGALLY DISPOSE ALL
DEBRIS GENERATED BY THE DEMOLITION WORK AS THE WORK
PROGRESSES. STOCKPILING OF DEBRIS AND BURNING OF DEBRIS
ON THE PREMISES IS STRICTLY PROHIBITED.
CAST-IN-PLACE CONCRETE
1. CONCRETE WORK SHALL CONFORM TO THE REQUIREMENTS OF THE
FOLLOWING CODES AND STANDARDS (LATEST EDITIONS):
A. ACI 318 "BUILDING CODE REQUIREMENTS FOR REINFORCED
CONCRETE."
B. CRSI "MANUAL OF STANDARD PRACTICE".
2. CONCRETE SHALL BE NORMAL WEIGHT UNLESS OTHERWISE NOTED
AND SHALL CONFORM TO ASTM C-94 IN ADDITION TO THE FOLLOWING:
A. PORTLAND CEMENT SHALL MEET ASTM C-150 TYPEI/II.
B1. AGGREGATES FOR SLAB ON GRADE SHALL MEET ASTM C-33
(1" MAX).
B2. AGGREGATES ELSEWHERE SHALL MEET ASTM C-33 (3/4" MAX).
C. AIR ENTRAINING AGENT SHALL MEET ASTM C-260.
D. WATER REDUCING AGENT SHALL MEET ASTM C-494.
E. CALCIUM CHLORIDE SHALL NOT BE USED IN THE MIX.
G. CURING COMPOUND SHALL MEET ASTM C309 TYPE 1 UNO.
3. CONCRETE SHALL HAVE THE MINIMUM ULTIMATE COMPRESSIVE
STRENGTH AT 28 DAYS AS INDICATED BELOW. MIX DESIGNS SHALL BE
APPROVED BY THE ENGINEER BEFORE USE.
COMPONENT FC 28-DAY STRENGTH
SLAB ON GRADE 4,000 PSI
FOUNDATIONS 4,000 PSI
CONCRETE CAST ABOVE GRADE 4,000 PSI
4. FLY ASH, SUBSTITUTING FOR CEMENT, SHALL NOT EXCEED 25% BY
WEIGHT.
5. FOR MASS CONCRETE PLACEMENT AS DEFINED BY ACI 207 FLY ASH,
SUBSTITUTING FOR CEMENT, SHALL NOT EXCEED 30% BY WEIGHT.
6. REINF BARS USED IN CONCRETE SHALL BE GRADE 60 KSI DEFORMED
BAR CONFORMING TO ASTM SPECIFICATION A-615. REINFORCEMENT
SHALL BE RUST,OIL, AND SCALE FREE AND SHALL BE PLACED AND
BENT IN ACCORDANCE WITH THE REFERENCED STANDARDS
INDICATED IN NOTE 1 OF THIS SECTION. SHOP DWGS FOR
REINFORCEMENT LAYOUT, DETAILING, AND PLACING SHALL BE
APPROVED BY THE STRUCT ENGINEER PRIOR TO FABRICATION, SITE
DELIVERY, AND INSTALLATION.
7. WELDED WIRE REINFORCING TO BE USED FOR CONCRETE
REINFORCEMENT WHERE INDICATED SHALL CONFORM TO ASTM
A-1064 AND SHALL BE FURNISHED IN FLAT SHEETS (RATHER THAN
ROLLS). REINFORCING SHALL BE SUPPORTED ON CHAIRS TO MAINTAIN
THE PROPER LOCATION WITHIN THE CONCRETE AND SHALL BE
PLACED IN ACCORDANCE WITH THE REFERENCED STANDARDS
INDICATED IN NOTE 1 OF THIS SECTION. MINIMUM LAP SHALL BE TWO
PANELS.
8. CONCRETE SHALL BE CURED IN ACCORDANCE WITH ACI STANDARDS
AND SPECIFICATIONS. THE CONTRACTOR SHALL BEGIN CONCRETE
CURING IMMEDIATELY AFTER FINISHING OPERATIONS ARE
COMPLETED.
9. CONCRETE ADMIXTURES SHALL BE UTILIZED ONLY WITH PRIOR
APPROVAL FROM THE STRUCT ENGINEER.
10. CONCRETE ADDITIVES SHALL BE COORDINATED BY THE CONTRACTOR
TO ENSURE COMPATIBILITY WITH FLOOR COVERINGS, EXPOSED,
POLISHED, AND STAINED FINISHES AS SPECIFIED BY THE ARCH.
11. CONCRETE TESTING SHALL BE REQUIRED FOR CIP CONCRETE
ELEMENTS AND SHALL BE PERFORMED BY A QUALIFIED, INDEPENDENT
TESTING LAB. MINIMUM TESTING SHALL BE FOR SLUMP IN
ACCORDANCE WITH ASTM C143 AND FOR COMPRESSIVE STRENGTH IN
ACCORDANCE WITH ASTM C39.
12. COMPRESSIVE STRENGTH TESTING SHALL BE CONDUCTED FOR EACH
CLASS, FOR EVERY FIFTY CUBIC YARDS OF CONCRETE PLACED PER
DAY. PLACEMENTS LESS THAN FIFTY CUBIC YARDS SHALL ALSO BE
TESTED PER DAY FOR EACH CLASS. A MINIMUM OF FOUR LAB-CURED
AND SIX FIELD-CURED CYLINDERS SHALL BE COLLECTED. TWO
CYLINDERS SHALL BE KEPT IN RESERVE AND TESTED, IF NECESSARY,
WITH PRIOR APPROVAL FROM THE STRUCT ENGINEER.
13. MIX DESIGN SUBMITTALS SHALL BE SENT TO THE STRUCT ENGINEER
FOR REVIEW AND APPROVAL PRIOR TO CONCRETE PLACEMENT AND
SHALL BE UNIQUELY IDENTIFIED WITH MIX NUMBER AND EXACT
LOCATION WHERE MIX WILL BE PLACED ON THE STRUCTURE.
SUBMITTALS SHALL INCLUDE DATA FROM RECENT FIELD AND LAB
CYLINDER TESTS AND STATISTICAL, TESTED BACK-UP DATA PER ACI
318.
14. CONCRETE TICKETS FOR CONCRETE MIXES DELIVERED TO THE SITE
SHALL IDENTIFY THE EXACT TIME THAT THE MIX IS BATCHED.
CONCRETE PLACEMENT SHALL OCCUR, DEPENDING ON AMBIENT
TEMPERATURE, WITHIN ONE AND A HALF HOURS FROM THE TIME THE
PROPORTIONED MIXING WATER IS ADDED TO THE MIX FOR
PLACEMENT. MIXES SHALL BE DISCARDED IF THIS TIMEFRAME IS
EXCEED. IT SHALL BE THE RESPONSIBILITY OF THE INDEPENDENT
TESTING LAB TO ASSURE COMPLIANCE WITH PLACING TIME AND TO
NOTIFY THE CONTRACTOR AND OWNER OF NON-COMPLIANCE.
15. CONCRETE FORMS SHALL NOT BE STRIPPED UNTIL CONCRETE HAS
ATTAINED A MINIMUM 70% OF THE SPECIFIED 28-DAY COMPRESSIVE
STRENGTH AS INDICATED BY TESTING SAMPLES.
16. LAP SPLICE LENGTHS SHALL BE A MINIMUM OF 48 BAR DIA UNO.
17. CONCRETE CLEAR COVER OVER REINF SHALL BE IN
ACCORDANCE WITH ACI 318 AS LISTED BELOW, UNLESS NOTED
OTHERWISE.
LOCATION CLEAR COVER
CAST AGAINST EARTH 3"
EXPOSED TO EARTH OR WEATHER #6 AND LARGER 2"
EXPOSED TO EARTH OR WEATHER #5 AND SMALLER 1 1/2"
SLABS AND WALLS NOT EXPOSED TO WEATHER 3/4"
BEAMS AND COLUMNS NOT EXPOSED TO WEATHER 1 1/2"
SLABS ON GRADE (COVER FROM TOP OF SLAB) 1 1/2"
18. VERT AND HORIZ REINF INDICATED ON THE DWGS SHALL BE
DOWELED OUT OF THE FOUNDATION OR THE ELEMENT WHERE THE
REINF ORIGINATES, (SLAB BEAM, THE BEAM, WALL, ETC.) UTILIZING AN
ACI STANDARD HOOK EMBEDDED TO DEVELOP THE FULL ULTIMATE
TENSILE STRENGTH OF THE BAR.
19. FORMWORK REMOVAL IS THE SOLE RESPONSIBILITY OF THE
CONTRACTOR. REMOVE FORMS IN SUCH A MANNER AS TO ENSURE
JOB SAFETY AND TO PREVENT DAMAGE TO, AND CREEP DEFLECTION
OF THE STRUCTURE.
20. IMMEDIATELY AFTER REMOVAL OF FORMS, REPAIR HONEYCOMBED OR
DEFECTIVE AREAS WITH HIGH STRENGTH CEMENT GROUT. GROUT
SHALL BE APPROVED BY THE STRUCT ENGINEER. WHEN REINF IS
VISIBLE IN DEFECTIVE AREA, CONTACT THE STRUCT ENGINEER
IMMEDIATELY.
MASONRY
1. CONFORM TO TMS 402/602-16 BUILDING CODE REQUIREMENTS AND
SPECIFICATIONS FOR MASONRY STRUCTURES. LATEST EDITION
REFERENCED IN BUILDING CODE.
2. CONCRETE MASONRY UNITS (CMU) MATERIALS SHALL BE:
A. ALL CONCRETE MASONRY UNITS (CMU) SHALL BE TWO CELL
NORMAL WEIGHT AGGREGATE UNITS WITH A SPECIFIED MINIMUM
COMPRESSIVE STRENGTH OF 1900 PSI ON NET AREA AT 28 DAYS
CONFORMING TO ASTM C90. CMU LOCATED BELOW GRADE, SHALL
BE NORMAL WEIGHT AGGREGATE UNITS.
B. ALL MORTAR SHALL BE TYPE "S" OR "M" WITH A MINIMUM MORTAR
COMPRESSIVE STRENGTH OF 2500 PSI AT 28 DAYS CONFORMING
TO ASTM C270. THE MINIMUM COMPRESSIVE STRENGTH (f'M) OF A
PRISM ASSEMBLED OF CMU AND MORTAR SHALL BE 1500 PSI AT 28
DAYS ON THE NET AREA.
C. CMU GROUT SHALL CONFORM TO ASTM C476 WITH 3/8"
AGGREGATE WITH THE FOLLOWING REQUIREMENTS: MIN. F'C=2500
PSI, MIN. CEMENT=611 PCY, MAX. W/C RATIO=0.65 AND SHALL HAVE
A SLUMP OF BETWEEN 8" AND 10". PROVIDE CLEAN OUTS AS
SHOWN ON DRAWINGS. PUMP 4'-0" MAXIMUM GROUT LIFTS WITH
60 MINUTE DELAY BETWEEN LIFTS.
D. REINFORCING STEEL SHALL MEET THE REQUIREMENTS OF ASTM
A615, GR 60.
E. JOINT REINFORCING STEEL SHALL MEET THE REQUIREMENTS OF
ASTM A1064 WIRE WITH A MINIMUM YIELD GREATER THAN 70 KSI.
LONGITUDINAL WIRES SHALL BE 9 GA (0.1483" DIA.) WITH LADDER
TYPE WIRES CONNECTED AT 16" CENTERS. REINFORCING SHALL
BE MILL GALVANIZED PER ASTM A641, CLASS 3.
F. WHERE CONCRETE BEAMS ARE INSTALLED IN CONCRETE BLOCK
WALL, SUPPORT CONCRETE WITH 6" WIDE CONTINUOUS STRIPS
OF 1/8 SQUARE MESH SOFFIT SCREENING OF PUR-O-STOP OR
EQUAL CENTERED OVER BLOCK WORK. USE OF ROOFING FELT
STRIPS WILL NOT BE PERMITTED.
3. HORIZONTAL WALL REINFORCING
A. PROVIDE BOND BEAM COURSES IN ALL WALLS AT THE TOP OF
WALL OR PARAPET, AT FLOOR LEVELS (ABOVE GRADE), AT TOP OF
OPENINGS OR IMMEDIATELY ABOVE LINTELS, BELOW OPENINGS
AND AT BEARING LOCATIONS. BOND BEAMS SHALL BE
REINFORCED AS SHOWN IN PLANS. ALL INTERIOR STRUCTURAL
WALLS (SHEAR AND/OR BEARING) SHALL HAVE INTERMEDIATE
BOND BEAMS LOCATED AT THE SAME LEVELS AS EXTERIOR BOND
BEAMS.
4. VERTICAL REINFORCING
A. PROVIDE VERTICAL REINFORCING (NORMAL REINFORCING) IN
GROUT FILLED CELLS IN ALL WALLS AS SHOWN ON PLANS AND
SCHEDULES.
B. PROVIDE AN ADDITIONAL VERTICAL REINFORCING BAR WITH
DOWELS INTO SUPPORTING MEMBERS, WITH SAME SIZE AND
LENGTH AS THE NORMAL REINFORCING BAR, AT THE FOLLOWING
LOCATIONS UNLESS NOTED OTHERWISE:
1. ON EACH SIDE OF A CONTROL OR ISOLATION JOINT
2. AT INTERSECTION OF WALLS
3. EACH SIDE OF A WALL OPENING
4. AT EACH END OF WALL
5. AT EACH BEAM BEARING
C. VERTICAL REINFORCING SHALL EXTEND CONTINUOUSLY FROM
THE TOP OF THE SUPPORTING MEMBER TO EMBED AT LEAST 6"
INTO THE TOP BOND BEAM. THERE SHALL BE A DOWEL, CAST
INTEGRAL WITH THE SUPPORTING MEMBER, FOR EACH VERTICAL
REINFORCING BAR EXCEPT AS NOTED.
5. REINFORCING SHALL MEET THE FOLLOWING LAP, SPLICE AND
EMBEDMENT REQUIREMENTS:
LAP OR FOUNDATION DOWELS
REINF. SPLICE EMBEDMENT STRAIGHT
BAR LENGTH WITH HOOK EMBEDMENT
SIZE IN WALL INTO FOUND. INTO FOUND.
JOINT 16" N/A N/A
4 24" 8" 15" 5 30" 10" 19" 6 36" 12" 23" 7 42" 14" 27" 8 48" 16" 30"
HOOKS IF USED SHALL BE ACI STANDARD HOOKS.
6. CELLS WHICH CONTAIN REINFORCING STEEL (VERTICAL CELLS, BOND
BEAMS, LINTELS AND PILASTERS) SHALL BE FILLED SOLIDLY WITH
GROUT AND UNITS SHALL BE LAID WITH FULL BED JOINTS AROUND
CELLS.
7. VERTICAL CELLS TO BE FILLED SHALL HAVE VERTICAL ALIGNMENT
SUFFICIENT TO MAINTAIN A CLEAR UNOBSTRUCTED CONTINUOUS
VERTICAL CELL.
8. BOND BEAM AND JOINT REINFORCING FOR INTERIOR AND EXTERIOR
WALLS SHALL BE CONTINUOUS THROUGHOUT, EXCEPT AT CONTROL
AND ISOLATION JOINTS, IT SHALL BE AS FOLLOWS:
A. INTERMEDIATE REINFORCING SHALL BE DISCONTINUOUS AT
CONTROL JOINTS. REINFORCEMENT IN BOND BEAMS AT FLOOR
AND ROOF DIAPHRAGM LEVELS SHALL BE CONTINUOUS.
B. AT ISOLATION JOINTS, ALL REINFORCING SHALL BE
DISCONTINUOUS.
9. BARS AROUND PERIMETER OF OPENINGS SHALL EXTEND NOT LESS
THAN 40 BAR DIAMETERS OR 24", WHICHEVER IS LARGER, BEYOND THE
CORNER OF THE OPENING. VERTICAL JAMB BARS SHALL BE THE SAME
SIZE AND NUMBER AS THE NORMAL VERTICAL REINFORCING.
10. SEE PLANS AND SCHEDULE FOR LINTELS OVER OPENINGS.
11. LOCATION AND DETAILS OF CONTROL JOINTS AND ISOLATION JOINTS
IN REINFORCED MASONRY SHALL BE AS SHOWN ON THE
ARCHITECTURAL DRAWINGS.
12. ALL MASONRY IN CONTACT WITH SOIL SHALL BE NORMAL WEIGHT
UNITS AND HAVE ALL VOIDS FILLED WITH GROUT.
13. MASONRY WALL TO INTERLOCK (50% MASONRY BOND) AT ALL
INTERSECTING WALLS.
N
John A. Ilter, P.E.
FL PE NO. 36205
Sheet Number:Drawn By:
JOB No.
Phase:
Designed By:
Date Issued:
PROFESSIONAL SEALS:
CLIENT:
SHEET TITLE:
ISSUE LOG
CONSULTANT:
Checked By:
SHEET INFORMATION:
PROJECT NAME:
No. Date Description
O
RA
N G
E C
O U
N
TY
C O
RR
EC
TI
O
N S
G
EN
IT
AR
Y
PI
PI
N G
R
EP
LA
C
EM
EN
T
3r d S tr ee t, O rla nd o, F
L
482 SOUTH KELLER ROAD
ORLANDO, FL 32810
PHONE: 407.647.7275 FAX: 407.740.8958
NOT FOR CONSTRUCTION
100%B
IM
/1
-O ra n g e C o u n ty
C o rr e c ti o n s G
/1
O C
C G e n e si s S
.r vt
S-001
100075349
GENERAL NOTES,
ABBREVIATIONS &
SYMBOLS
JAI
MR
JAI
09-13-2021
Ip MOMENT OF INERTIA
JST JOIST
JT JOINT
K 1,000 POUNDS (KIP)
KWY KEYWAY
L ANGLE
LDG LANDING
LG L LONG ANGLE
LGTH LENGTH
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LT WT LIGHT WEIGHT
MATL MATERIAL
MAX MAXIMUM
MB MASONRY BEAM, MACHINE BOLT
MECH MECHANICAL
MEP, M/E/P MECHANICAL,ELECTRICAL,PLUMBING
MET METAL
MFR MANUFACTURE/MANUFACTURER
MID MIDDLE
MIN MINIMUM
MISC MISCELLANEOUS
MO MASONRY OPENING
MPH MILES PER HOUR
NIC NOT IN CONTRACT
NO NUMBER
NS NEAR SIDE
NTS NOT TO SCALE
OC ON CENTERS
OD OUTSIDE DIAMETER
OF OUTSIDE FACE
OPNG OPENING
PAF POWDER ACTIVATED FASTENERS
PAR PARALLEL
PC PRECAST CONCRETE
PCF POUNDS PER CUBIC FEET
PCI PRECAST CONCRETE INSTITUTE
PCL PRECAST/PRESTRESSED CONCRETE
LINTEL
PEMB PRE ENGINEERED METAL BUILDING
PEN PENETRATION
PJF PREMOLDED BITUMINOUS JOINT
FILLER
PL PROPERTY LINE, PLATE
PLF POUNDS PER LINEAR FOOT
PLY PLYWOOD
PREFAB PREFABRICATED
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PT PRESSURE TREATED
RCP REINFORCED CONCRETE PIPE
RD ROOF DRAIN
REF REFERENCE
REINF REINFORCING
REQD REQUIRED
RTU ROOF TOP UNIT
RW RETAINING WALL
SBP SOIL BEARING PLATE
This is the start of the file's text. The full file is on GovTribe.