Y22-765_Meadow_Woods_Rec_Center_Drawings.pdf
PDF 12 MB Posted
- Solicitation number
- Y22-765
- Issued by
- Orange County, Orlando City, Florida
About this file
The provided documents are construction and engineering drawings for a standby generator installation project for the Meadow Woods Magic Gym, located at 1751 Rhode Island Woods Circle in Orlando, Florida, prepared by Hanson Professional Services Inc. for Orange County Government. The project involves installing a new standby power generator system to provide emergency electrical power during extended outages caused by hurricanes or other inclement weather. The drawings, dated October 18, 2021, include detailed site plans, electrical diagrams, structural specifications, and equipment placement details for a comprehensive generator installation.
The project scope requires the contractor to provide and install a complete standby power system, including a new exterior automatic transfer switch to replace the existing manual transfer switch, new electrical feeders, and associated equipment. The generator will be situated on a concrete slab with a vinyl-coated chain link fence enclosure and service platforms to facilitate maintenance. The installation must comply with multiple building codes, including the Florida Building Code (7th Edition, 2020), Florida Energy Conservation Code, and National Electrical Code. The documents specify detailed technical requirements for electrical connections, grounding, equipment placement, and safety considerations to ensure a fully functional emergency power system for the Meadow Woods Magic Gym facility.
View the file
Other files
Show all 16
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
COVER SHEET
T-0.1
OCTOBER 18, 2021
MEADOW WOODS MAGIC GYM
HANSON PROFESSIONAL SERVICES INC.
720 N. Maitland Ave., Suite 102
Maitland, FL 32751
(407) 622-2050
1751 RHODE ISLAND WOODS CIRCLE
ORLANDO, FL 32824
ELECTRICAL & CIVIL ENGINEERING
PROJECT LOCATION
PROJECT LOCATION
CODES IN EFFECT AT TIME OF
DRAWING SUBMITTAL
FLORIDA BUILDING CODE, SEVENTH EDITION (2020)
FLORIDA ENERGY CONSERVATION CODE, SEVENTH EDITION
(2020)
FLORIDA ACCESSIBILITY CODE, SEVENTH EDITION (2020)
FLORIDA FIRE PREVENTION CODE, SEVENTH EDITION (2020)
NFPA 1 FIRE CODE, 2012 EDITION
NFPA 101 (LIFE SAFETY CODE) 2012 EDITION WITH FL
AMENDMENTS
NFPA 13 (2007 EDITION)
NEC (NFPA 70) 2014 EDITION
TO THE BEST OF THE ENGINEER'S KNOWLEDGE, THE
PLANS AND SPECIFICATIONS COMPLY WITH THE 2017
FLORIDA BUILDING CODE WITH ALL CURRENT
AMENDMENTS.
PROJECT INFORMATION
1.
2.
3.
4.
SCOPE OF WORK
CONTRACTOR SHALL PROVIDE AND INSTALL ALL
WORK AND MATERIALS NECESSARY FOR A
COMPLETE AND OPERABLE STANDBY POWER
SYSTEM UPON PROJECT COMPLETION.
Engineering | Planning | Allied Services
Offices Nationwide www.hanson-inc.com
Hanson Professional Services Inc.
CONSULTANTS
EB0007061
AA0003116
IB0001058
SHEET TITLE
REVIEWED BY:
DRAWN BY:
DESIGN BY:
PROJECT NO:
ISSUE:
© Copyright Hanson Professional Services Inc. 2020
54321 6
E
D
C
B
A
54321 6
MARK DATE DESCRIPTION
720 N. Maitland Ave., Suite 102 Maitland, FL 32751
(407) 622-2050
(407) 622-2051
MEADOW WOODS
MAGIC GYM
STANDBY
GENERATOR
INSTALLATION
1751 RHODE ISLAND
WOODS CIRCLE
ORLANDO, FL 32824
10/18/2021 18G0011B-1500
DLH
TAGS
SP
SEAL
This item has been digitally signed and sealed by Salvador Perez P.E. on the date listed using a digital signature.
Printed copies of this document are not considered sign and sealed and the SHA authentication code must be verified on any electronic copies.
ISSUED FOR BIDDING
CONSTRUCTION DOCS
CONSTRUCTION DOCUMENTS
SCOPE OF WORK ENCOMPASS AN OWNER PROVIDED
CONTRACTOR INSTALLED STANDBY POWER GENERATOR
SYSTEM FOR THIS ORANGE COUNTY GOVERNMENT MAGIC
GYM FACILITY. STANDBY POWER GENERATOR WILL
PROVIDE THE MEANS FOR PERMANENT EMERGENCY
POWER GENERATION TO THE EXISTING ELECTRICAL SERVICE
EQUIPMENT FEEDING THE FACILITY AS NECESSARY TO
MAINTAIN ELECTRICAL SERVICES IN OPERATION DURING
TIMES OF EXTENDED POWER OUTAGES DUE TO
HURRICANES OR OTHER INCLEMENT WEATHER OR
UNFORESEEN EVENTS.
CONSTRUCTION DOCUMENTS AND SPECIFICATIONS
INCLUDE THE DESIGN AND WORK NECESSARY TO
INTERCEPT THE EXISTING FACILITY ELECTRICAL SERVICE FOR
THE INSTALLATION OF THE OWNER PROVIDED STANDBY
POWER GENERATOR AND ASSOCIATED CONTRACTOR
PROVIDED AND INSTALLED POWER TRANSFER EQUIPMENT
TO SERVE THE FACILITY ELECTRICAL POWER SYSTEM.
NEW EXTERIOR AUTOMATIC TRANSFER SWITCH TO BE
PROVIDED AND INSTALLED TO REPLACE THE EXISTING
MANUAL TRANSFER SWITCH DOWNSTREAM OF THE
EXISTING MAIN SERVICE DISCONNECTING MEANS AT THE
FACILITY. THE EXISTING SECONDARY SERVICE FEEDERS WILL
BE INTERCEPTED AT THE EXISTING MANUAL TRANSFER
SWITCH AND CONNECTED TO THE NEW AUTOMATIC
TRANSFER SWITCH. CONTRACTOR SHALL SCHEDULE AND
COORDINATE ALL POWER OUTAGES WITH THE OWNER AND
LOCAL POWER COMPANY AS NECESSARY TO COMPLETE
THE WORK. ADDITIONAL EQUIPMENT AND FEEDERS SHALL
BE PROVIDED AND INSTALLED BY THE CONTRACTOR AS
INDICATED IN THESE CONSTRUCTION DOCUMENTS TO
COMPLETE THE STANDBY GENERATOR INSTALLATION.
STANDBY POWER GENERATOR
INDEX OF DRAWINGS
CAD CONSULTANT
STRUCTURAL ENGINEERING
AutoCAD SHX Text Copyright © 2020 by Hanson Professional Services Inc. All rights reserved. This 2020 by Hanson Professional Services Inc. All rights reserved. This document is intended solely for the use of the individual or the entity to which it is addressed. The information contained in this document shall not be duplicated, stored electronically, or distributed, in whole or in part, without the express written permission of Hanson Professional Services Inc., 1525 S. Sixth St., Springfield, IL 62703, (217) 788-2450, www.hanson-inc.com. Unauthorized reproduction or transmission of any part of this document is a violation of federal law.
AutoCAD SHX Text
STATE OF
AutoCAD SHX Text S
AutoCAD SHX Text A
AutoCAD SHX Text L
AutoCAD SHX Text V
AutoCAD SHX Text A
AutoCAD SHX Text D
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text P
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text Z
AutoCAD SHX Text P
AutoCAD SHX Text R
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text I
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text L
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text F
AutoCAD SHX Text L
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text I
AutoCAD SHX Text D
AutoCAD SHX Text A
AutoCAD SHX Text L
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text S
AutoCAD SHX Text E
AutoCAD SHX Text No.
AutoCAD SHX Text 50064
AutoCAD SHX Text E-0.1
AutoCAD SHX Text E-1.1
AutoCAD SHX Text
ELECTRICAL SITE PLAN
AutoCAD SHX Text E-2.1
AutoCAD SHX Text
ELECTRICAL GENERATOR LOCATION PLAN
AutoCAD SHX Text E-4.1
AutoCAD SHX Text
EXISTING ELECTRICAL DISTRIBUTION SYSTEM - ONE-LINE DIAGRAM
AutoCAD SHX Text E-5.1
AutoCAD SHX Text
NEW ELECTRICAL DISTRIBUTION SYSTEM - ONE-LINE DIAGRAM
AutoCAD SHX Text
ELECTRICAL LEGEND AND GENERAL NOTES
AutoCAD SHX Text E-3.1
AutoCAD SHX Text
ELECTRICAL GENERATOR SITE PLAN DETAILS
AutoCAD SHX Text T-0.1
AutoCAD SHX Text
TITLE AND COVER SHEET
AutoCAD SHX Text S-2.1
AutoCAD SHX Text
STRUCTURAL NOTES, PLAN AND DETAILS
AutoCAD SHX Text C-1.1
AutoCAD SHX Text
CIVIL SITE PLAN
AutoCAD SHX Text C-1.2
AutoCAD SHX Text
CIVIL DETAILS
AutoCAD SHX Text E-3.2
AutoCAD SHX Text
ELECTRICAL GENERATOR EQUIPMENT DETAILS
AutoCAD SHX Text SPECIAL CONSTRUCTION SCHEDULE NOTE: ORANGE COUNTY DESIRES TO HAVE GENERATOR POWER AVAILABLE AS SOON AS POSSIBLE IN THE EVENT OF A HURRICANE OR SIMILAR INCLEMENT WEATHER EVENT. ORANGE COUNTY WOULD LIKE TO AT LEAST HAVE THE GENERATOR PERMANENTLY SET IN PLACE ON ITS CONCRETE PAD, GENERATOR STARTUP COMPLETED WITH TANK FUELED AND READY FOR OPERATION AS SOON AS POSSIBLE IN THE CONSTRUCTION PROCESS WITH TEMPORARY CONNECTING CABLES AVAILABLE ON SITE TO CONNECT FROM THE GENERATOR TO THE EXISTING MANUAL TRANSFER SWITCH IN THE EVENT OF A HURRICANE WHILE CONSTRUCTION IS UNDERWAY. CONTRACTOR SHALL REVIEW AND COORDINATE SHELTER POWER NEEDS WITH OWNER AS NECESSARY TO PROVIDE STANDBY POWER SERVICES DURING INCLEMENT WEATHER.
AutoCAD SHX Text GENERATOR DELIVERY AND MOVEMENT TO SITE NOTE: ORANGE COUNTY INTENDS TO TAKE DELIVERY OF THE PRE-PURCHASED GENERATORS AT THE COUNTY WAREHOUSE FACILITIES LOCATED AT 1651 N. ORANGE BLOSSOM TRAIL IN ORLANDO, FL 32804. THE CONTRACTOR SHALL BE RESPONSIBLE TO COORDINATE WITH ORANGE COUNTY FOR THE MOVEMENT OF THE PRE-PURCHASED GENERATOR FOR THIS PROJECT LOCATION FROM THE COUNTY WAREHOUSE LOCATION TO THE SITE ONCE THE CONCRETE GENERATOR PAD AND ASSOCIATED UTILITIES ARE IN PLACE TO ACCEPT INSTALLATION OF THE NEW GENERATOR. THE CONTRACTOR SHALL PROVIDE TRANSPORTATION OF THE GENERATOR FROM THE COUNTY WAREHOUSE TO THE SITE AS WELL AS SUPPLYING CRANES FOR BOTH PICKING UP THE GENERATOR FROM THE COUNTY WAREHOUSE FACILITY AND FOR THE SETTING/INSTALLATION OF THE GENERATOR AT THE SITE. THE CONTRACTOR WILL BE RESPONSIBLE FOR THE COMPLETE INSTALLATION, FINAL CONNECTIONS, FUELING, TESTING, AND CARE OF THE GENERATOR FROM THE TIME OF MOVEMENT FROM THE COUNTY WAREHOUSE TO THE SITE UNTIL FINAL COMPELETION OF THE PROJECT.
AutoCAD SHX Text GENERAL SITE CONDITIONS/SURVEYING NOTES: GENERATOR IS NOT LOCATED IN ANY FLOOD ZONE. FLOOD ZONE STUDIES OF THE SITE WERE CONDUCTED DURING DESIGN. FLOOD ZONE STUDY INFORMATION CAN BE MADE AVAILABLE TO THE CONTRACTOR AWARDED THE PROJECT UPON REQUEST IF NEEDED. THE CONTRACTOR MAY HAVE SURVEYING RESPONSIBILITIES BUT ONLY IN AS MUCH AS MAY BE NECESSARY TO PROPERLY LOCATE THE GENERATOR COMPOUND FENCING, GENERATOR CONCRETE SLAB, OR OTHER MINOR ALTERATIONS PARTICULAR TO THE SITE AS NECESSARY TO COMPLETE THE WORK OF THE CONSTRUCTION DOCUMENTS.
AutoCAD SHX Text GENERAL PROJECT CONTRACT NOTES: 1. ORANGE COUNTY HAS NOTED THAT DAVIS-BACON WAGES ARE EFFECTIVE FOR THE PROJECT. ORANGE COUNTY HAS NOTED THAT DAVIS-BACON WAGES ARE EFFECTIVE FOR THE PROJECT. CONTRACTOR SHALL OBTAIN THE PROJECT SPECIFIC WAGE INFORMATION FROM THE OWNER AS NECESSARY FOR THE WORK OF THESE CONTRACT DOCUMENTS. 2. THE CONTRACTOR IS RESPONSIBLE FOR OBTAINING ALL PERMITS INCLUDING ANY SEPARATE THE CONTRACTOR IS RESPONSIBLE FOR OBTAINING ALL PERMITS INCLUDING ANY SEPARATE SUB-CONTRACT/TRADE PERMITS THAT MAY BE REQUIRED FOR COMPLETION OF THE PROJECT. ORANGE COUNTY (OWNER) WILL PAY FOR ALL PERMITS, LICENSES, AND FEES IMPOSED BY THE WORK/ PROJECT BY AGENCIES OF THE ORANGE COUNTY BOARD OF COMMISSIONERS. 3. THIS PROJECT IS ONE OF EIGHT SEPARATE BUT SIMILAR PROJECTS BEING CONSTRUCTED BY THIS PROJECT IS ONE OF EIGHT SEPARATE BUT SIMILAR PROJECTS BEING CONSTRUCTED BY ORANGE COUNTY UNDER THIS DESIGN PROFESSIONAL'S CONTRACT. THE CONTRACTOR SHALL NOTE THAT SINCE ALL PROJECTS ARE INTENDED TO BE CONSTRUCTED CONCURRENTLY, THE PROJECT SCHEDULE (NUMBER OF DAYS TO COMPLETION) WILL RUN CONCURRENTLY FOR ALL EIGHT PROJECTS AND MANPOWER, CONCRETE SCHEDULING, GENERATOR DELIVERIES, AND OTHER CRITICAL PATH CONSTRUCTION EVENTS MAY BE IMPACTED FOR CONTRACTORS THAT COULD BE AWARDED MULTIPLE PROJECTS AND CONTRACTOR SHALL PLAN ACCORDINGLY FOR MAINTAING CONCURRENT CONSTRUCTION SCHEDULES IF SUCCESSFUL IN THEIR BIDS FOR MULTIPLE PROJECTS. 4. THE GENERATOR INDICATED IN THESE CONSTRUCTION DOCUMENTS IS BEING PROVIDED BY THE THE GENERATOR INDICATED IN THESE CONSTRUCTION DOCUMENTS IS BEING PROVIDED BY THE OWNER. THE CONTRACTOR IS RESPONSIBLE FOR ALL OTHER ASPECTS OF THE GENERATOR DELIVERY TO THE SITE AND SUBSEQUENT INSTALLATION AS NECESSARY FOR A COMPLATE AND OPERABLE SYSTEM AS SHOWN IN THESE CONSTRUCTION DOCUMENTS. 5. DAILY SITE SECURITY IS NOT FORESEEN AS A REQUIREMENT FOR THIS PROJECT HOWEVER, THE DAILY SITE SECURITY IS NOT FORESEEN AS A REQUIREMENT FOR THIS PROJECT HOWEVER, THE CONTRACTOR IS RESPONSIBLE FOR SECURING THE PROJECT WORK AREA(S) AT THE END OF EACH DAY UNTIL THE WORK IS SUBSTANTIALLY COMPLETE. SEE SECTION 01 01 00 OF THE CONTRACT SPECIFICATIONS FOR ADDITIONAL INFORMATION. 5. CONTRACTOR SHALL BE RESPONSIBLE FOR TEMPORARY TOILETS, DRINKING WATER FOR ITS CONTRACTOR SHALL BE RESPONSIBLE FOR TEMPORARY TOILETS, DRINKING WATER FOR ITS EMPLOYEES, AND TEMPORARY POWER FOR CONSTRUCTION IF PERMANENT POWER IS NOT READILY AVAILABLE. OTHER ITEMS INDICATED IN SECTION 01 50 00 OF THE CONTRACT SPECIFICATIONS ARE GENERALLY NOT NECESSARY OR APPLICABLE TO THIS PROJECT PER ORANGE COUNTY (OWNER). 6. CONTRACTOR IS RESPONSIBLE FOR TERMITE CONTROL/TREATMENT UNDER THE GENERATOR SLAB(S) CONTRACTOR IS RESPONSIBLE FOR TERMITE CONTROL/TREATMENT UNDER THE GENERATOR SLAB(S) UNDER PROJECT CLOSEOUT REQUIREMENTS. OTHERWISE, NO OTHER PEST CONTROL IS REQUIRED.
PROPOSED 6" CRUSHED LIMESTONE
ON FILTER FABRIC
PROPOSED CONCRETE SLAB
(SEE SHEET S-2-1)
PROPOSED VINYL COATED
CHAIN LINK FENCE
EXISTING FENCE
8'-8" 4'3'-4"
16'
8'
'-6
DOUBLE SWING GATE
EXISTING FENCE
EXISITING CURB
3' -4
3'
-5
'-8
3'-0" SINGLE MAN GATE
Civil Site Plan
C-1.1
N
S
W E
Engineering | Planning | Allied Services
Offices Nationwide www.hanson-inc.com
Hanson Professional Services Inc.
CONSULTANTS
EB0007061
AA0003116
IB0001058
SHEET TITLE
REVIEWED BY:
DRAWN BY:
DESIGN BY:
PROJECT NO:
ISSUE:
© Copyright Hanson Professional Services Inc. 2020
54321 6
E
D
C
B
A
54321 6
MARK DATE DESCRIPTION
720 N. Maitland Ave., Suite 102 Maitland, FL 32751
(407) 622-2050
(407) 622-2051
MEADOW WOODS
MAGIC GYM
STANDBY
GENERATOR
INSTALLATION
1751 RHODE ISLAND
WOODS CIRCLE
ORLANDO, FL 32824
10/18/2021 18G0011B-1500
DS
DS
DAW
ISSUED FOR BIDDING
CONSTRUCTION DOCS
1" = 5'
GENERAL NOTES:
1. CONTRACTOR SHALL VERIFY ALL SITE CONDITIONS PRIOR TO ALL CONSTRUCTION ACTIVITIES.
CONTRACTOR SHALL CONTACT THE ENGINEER OF RECORD REGARDING ANY DIFFERENCES IN THE SITE
CONDITIONS.
2. LIMITS OF CONSTRUCTION TO BE DETERMINED BY CONTRACTOR DURING ON-SITE INSPECTION.
3. APPROVED EROSION AND SEDIMENT CONTROL MEASURES SHALL BE INSTALLED PRIOR TO ANY CLEARING, GRADING, EXCAVATION, FILLING, OR OTHER LAND-DISTURBING ACTIVITIES EXCEPT THOSE OPERATIONS
NEEDED TO INSTALL SUCH MEASURES.
4. CONTRACTOR SHALL COMPLY WITH ALL LOCAL, STATE, AND FEDERAL REGULATIONS CONCERNING EROSION AND SEDIMENT CONTROL. ADDITIONAL MEASURES MAY BE REQUIRED BY THE ENVIRONMENTAL INSPECTOR TO CONTROL SEDIMENTS. ANY ADDITIONAL EROSION AND SEDIMENT CONTROL DEVICES REQUIRED TO PREVENT SEDIMENTS FROM LEAVING THE SITE SHALL BE THE RESPONSIBILITY OF THE
CONTRACTOR.
5. ALL EROSION AND SEDIMENT CONTROL DEVICES SHALL BE CONTINUOUSLY MAINTAINED BY THE
CONTRACTOR DURING THE CONSTRUCTION PHASE OF THE PROJECT.
6. IN THE EVENT OF A CONFLICT BETWEEN THESE PLANS AND ANY APPLICABLE LOCAL CODES, THE LOCAL
CODES WILL GOVERN.
7. SECURED MOBILIZATION AREAS FOR THIS PROJECT WILL BE DETERMINED PRIOR TO CONSTRUCTION
THROUGH AGREEMENT BETWEEN THE CONTRACTOR AND THE LOCAL GOVERNMENT.
8. COARSE AGGREGATE SHALL BE CA-57 CRUSHED LIMESTONE PER FDOT STANDARD SPECS SECTION 901.
9. GEOTEXTILE FABRIC SHALL BE TYPE D3 PER FDOT STANDARDS SPECS SECTION 514.
10. PROPOSED TOP OF SLAB ELEVATIONS FOR REFERENCE USE ONLY. CONTRACTOR SHALL VERIFY SITE CONDITIONS, INCLUDING GRADING OF THE SITE, AND SHALL CONTACT THE ENGINEER OF RECORD FOR
ALTERNATE ELEVATIONS.
11. CONTRACTOR SHALL RESTORE TO ORIGINAL CONDITION ALL PROJECT DISTURBED SOIL, SOD, SIDEWALKS, ASPHALT, CURBS, GUTTERS, AND UTILITIES AFFECTED BY THIS PROJECT. ASPHALT CUTS SHALL BE RESTORED WITH CONCRETE PER OWNER'S DIRECTION. ASPHALT COLD PATCH SHALL NOT BE USED PER
OWNERS DIRECTION.
AutoCAD SHX Text Copyright © 2020 by Hanson Professional Services Inc. All rights reserved. This 2020 by Hanson Professional Services Inc. All rights reserved. This document is intended solely for the use of the individual or the entity to which it is addressed. The information contained in this document shall not be duplicated, stored electronically, or distributed, in whole or in part, without the express written permission of Hanson Professional Services Inc., 1525 S. Sixth St., Springfield, IL 62703, (217) 788-2450, www.hanson-inc.com. Unauthorized reproduction or transmission of any part of this document is a violation of federal law.
AutoCAD SHX Text
AutoCAD SHX Text
GRAPHIC SCALE IN FEET
AutoCAD SHX Text
AutoCAD SHX Text 2.5
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text
STATE OF
AutoCAD SHX Text R
AutoCAD SHX Text S
AutoCAD SHX Text E
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text I
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text L
AutoCAD SHX Text O
AutoCAD SHX Text L
AutoCAD SHX Text F
AutoCAD SHX Text S
AutoCAD SHX Text A
AutoCAD SHX Text I
AutoCAD SHX Text R
AutoCAD SHX Text D
AutoCAD SHX Text P
AutoCAD SHX Text No 78974
AutoCAD SHX Text C
AutoCAD SHX Text I
AutoCAD SHX Text L
AutoCAD SHX Text S
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text N
AutoCAD SHX Text G
AutoCAD SHX Text I
R
FINISHED GRADE 6" CA-57
CRUSHED LIMESTONE
POST DIA. 10"POST DIA. 10" POST DIA. 8"
10'-0" MAXIMUM 10'-0" MAXIMUM
CHAIN LINK FENCE DETAIL
C-1.2
NOTES:
N.T.S
LINE POST DETAIL GATE, CORNER, OR TERMINATION POST DETAIL
WIRE TIES FOR TOP OR BRACE RAIL TENSION BAND
BAND FOR WIRE STRETCHING
TERMINATION OR GATE POST DETAIL
WIRE TIE POST DETAIL
DOOR
SINGLE MAN GATE
N.T.S. N.T.S. N.T.S.
N.T.S.N.T.S.N.T.S.
N.T.S. N.T.S.
DOUBLE SWING GATE DETAIL
N.T.S.
DROP RECEIVER DETAIL
N.T.S.
3000 PSI
CONCRETE
4'-0" 4'-0"
BOX OUT (TYP)
8" GATE FRAME
SCH.40
CENTER STOP
12"X12"X12"
(SEE DETAIL 10)
PAVEMENT
FINISHED GRADE
8" ADJ.
TRUSS RODS
3" GATE POST
SCH.40(TYP) GATE
CORNER
C-1.2 C-1.2
C-1.2 C-1.2 C-1.2
C-1.2 C-1.2 C-1.2
C-1.2
C-1.2
3,000 PSI CONCRETE
FDOT SECTION 347
PORTLAND CEMENT
CONCRETE-CLASS NS
EXISTING GROUND
EXISTING GROUND
D3 FILTER FABRIC
FINISHED GRADE 6" CA-57
CRUSHED LIMESTONE
NATIVE SOIL COMPACTED TO 95%
MAXIMUM DRY DENSITY,
STANDARD PROCTOR
NATIVE SOIL COMPACTED TO 95%
MAXIMUM DRY DENSITY, STANDARD
PROCTOR
3000 PSI CONCRETE (TYP)
FDOT SECTION 347
LINE POST
TOP AND BOTTOM OF FABRIC SHALL
BE TWISTED AND KNUCKLED
#9 GUAGE VINYL
COATED FABRIC
1. ALL CHAIN LINK FENCING FABRIC SHALL BE VINYL COATED. COLOR: BLACK
2. ALL POSTS AND ACCESSORIES SHALL BE PAINTED BLACK TO MATCH FABRIC COLOR.
COILED SPRING
REINFORCING WIRE
BRACE
TRUSS ROD
8" MINIMUM DIA.
CORNER POST BRACE POST
TOP RAIL
TOP OR BRACE RAIL,
TIE WIRE 24" ON
CENTER MAX
FABRIC
8" CARRIAGE BOLT
STRETCHER BAR
(WIRE SIMILAR)
STRETCHER BAR TO
ENGAGE EACH FABRIC LINE
FABRIC
8" CARRIAGE BOLT
TENSION BAND TO BE
4" MAX. FROM TOP & BOTTOM
5 PER BAR EQUALLY SPACED < 15"
8" CARRIAGE BOLT
COIL SPRING WIRE
TIE WIRE 24"
ON CENTER MAX
FABRIC
LATCH
FLUSH W/CA-57 CRUSHED LIMESTONE
ENCASE 1" PVC SLEEVE
IN CONCRETE FOR DROP
RECIEVER
CONCRETE SHALL BE CROWNED 1"
ABOVE NATURAL GROUND AT
ALL POSTS (TYP)
3,000 PSI CONCRETE
FDOT SECTION 347
PORTLAND CEMENT
CONCRETE-CLASS NS
D3 FILTER FABRIC
FDOT INDEX 550-002
INSIDE OF SITEOUTSIDE OF SITE
FDOT INDEX 550-002
INSIDE OF SITEOUTSIDE OF SITE
Engineering | Planning | Allied Services
Offices Nationwide www.hanson-inc.com
Hanson Professional Services Inc.
CONSULTANTS
EB0007061
AA0003116
IB0001058
SHEET TITLE
REVIEWED BY:
DRAWN BY:
DESIGN BY:
PROJECT NO:
ISSUE:
© Copyright Hanson Professional Services Inc. 2020
54321 6
E
D
C
B
A
54321 6
MARK DATE DESCRIPTION
720 N. Maitland Ave., Suite 102 Maitland, FL 32751
(407) 622-2050
(407) 622-2051
MEADOW WOODS
MAGIC GYM
STANDBY
GENERATOR
INSTALLATION
1751 RHODE ISLAND
WOODS CIRCLE
ORLANDO, FL 32824
10/18/2021 18G0011B-1500
DS
DS
DAW
ISSUED FOR BIDDING
CONSTRUCTION DOCS
Civil Details
C-1.2
GENERAL NOTES
1. THE FABRIC, POSTS, FASTENINGS, FITTINGS AND OTHER ACCESSORIES FOR CHAIN LINK FENCE
SHALL MEET THE REQUIREMENTS OF FDOT INDEX 550-002, FENCE TYPE B
2. STEEL MATERIALS SHALL BE HOT-DIPPED GALVANIZED
3. THE BASE METAL OF THE FABRIC SHALL BE A GOOD COMMERCIAL QUALITY 9-GAUGE STEEL WIRE.
4. THE FABRIC SHALL BE OF UNIFORM QUALITY AND SHALL BE 6-FOOT HIGH WITH A 2-INCH MESH
SIZE AND SHALL BE BLACK VINYL COATED.
5. ALL POSTS AND RAILS AND MISCELLANEOUS FITTINGS SHALL BE PAINTED BLACK.
6. POST CAPS, DESIGNED TO PROVIDE A DRIVE FIT OVER THE TOP OF THE TUBULAR POST TO
EXCLUDE MOISTURE, SHALL BE PROVIDED.
7. THE FABRIC SHALL NOT BE PLACED UNTIL THE POSTS HAVE BEEN PERMANENTLY POSITIONED
AND CONCRETE FOUNDATIONS HAVE ATTAINED ADEQUATE STRENGTH. THE FABRIC SHALL BE
PLACED BY SECURING ONE END AND APPLYING SUFFICIENT TENSION TO REMOVE ALL SLACK
BEFORE MAKING PERMANENT ATTACHMENTS AT INTERMEDIATE POINTS.
8. THE FABRIC SHALL BE FASTENED TO ALL CORNER, END AND PULL POSTS BY SUBSTANTIAL AND
APPROVED MEANS. TENSION FOR STRETCHING THE FABRIC SHALL BE APPLIED BY MECHANICAL
FENCE STRETCHERS.
9. SWING GATES SHALL BE TWO, 4-FOOT WIDE DOUBLE-HUNG GATES AS INDICATED ON THE
DRAWINGS AND HINGED TO SWING THROUGH 180 DEGREES FROM CLOSED TO OPEN.GATES
SHALL BE COMPLETE WITH LATCHES, LOCKING DEVICE, STOPS KEEPER, HINGES, FABRIC AND
BRACES. EACH GATE OPENING SHALL HAVE BOX OUTS FOR HAND ACCESS TO INSTALL CHAIN AND LOCKS FOR SECURING GATES. GATES SHALL BE THE SAME HEIGHT AS THE FENCE AND THE GATE
FABRIC SHALL BE THE SAME AS THE FENCE FABRIC.
10. GATE LEAVES SHALL HAVE TRUSS RODS OR INTERMEDIATE BRACES. TO PROVIDE RIGID
CONSTRUCTION, FREE FROM SAG OR TWIST.
11. PROVIDE ADEQUATE WORKING CLEARANCES ABOUT ELECTRICAL EQUIPMENT, INCLUDING BUT
NOT LIMITED TO ENGINE GENERATORS AND ASSOCIATED EQUIPMENT, PER THE REQUIREMENTS
OF NATIONAL ELECTRICAL CODE 110.26 “SPACES ABOUT ELECTRICAL EQUIPMENT”.
ADJUST/INCREASE CLEARANCE FROM FENCE TO ENGINE GENERATORS AND ASSOCIATED
EQUIPMENT TO PROVIDE PROPER WORKING CLEARANCES.
12. PROVIDE CONSPICUOUS WARNING SIGNS AT EACH GATE FORBIDDING UNQUALIFIED PERSONS TO
ENTER THE FENCED AREA AROUND OF THE ENGINE GENERATOR TO COMPLY WITH NATIONAL
ELECTRICAL CODE 110.27 “GUARDING OF LIVE PARTS”. SIGNS SHALL BE LABELED “DANGER
STANDBY GENERATOR AUTOMATICALLY STARTS DURING POWER OUTAGE, THIS AREA
RESTRICTED TO AUTHORIZED PERSONNEL ONLY” OR SIMILAR NOTE. SIGNS SHALL MEET OSHA
STANDARDS AND THE AUTHORITY OF JURISDICTION. PROVIDE A SIGN FOR EACH GATE AND/OR
POINT OF ENTRY.
13. PROVIDE LOCKS ON EACH GATE TO PREVENT UNQUALIFIED PERSONS TO ENTER THE FENCED
AREA AROUND OF THE ENGINE GENERATOR. ACCESS TO THE FENCED AREA AROUND OF THE
ENGINE GENERATOR SHALL BE LIMITED TO QUALIFIED AUTHORIZED PERSONNEL ONLY.
14. ALL NON-CURRENT-CARRYING METAL PARTS OF FIXED, PORTABLE, AND MOBILE EQUIPMENT AND
ASSOCIATED FENCING, HOUSINGS, AND SUPPORTING STRUCTURES SHALL BE GROUNDED IN
ACCORDANCE WITH NATIONAL ELECTRICAL CODE 250.190 GROUNDING OF EQUIPMENT, AND
OTHER APPLICABLE SECTIONS OF NATIONAL ELECTRICAL CODE.
15. FENCE AROUND THE STANDBY GENERATOR AND ASSOCIATED EQUIPMENT SHALL BE GROUNDED.
THERE SHALL BE A GROUND LOCATED NEAR EACH GATE IN EACH SECTION OF THE FENCE
ADJACENT TO THE GATE. FENCE UNDER A POWER LINE SHALL BE GROUNDED BY THREE
GROUNDS; ONE DIRECTLY UNDER THE CROSSING AND ONE ON EACH SIDE 25 FEET TO 50 FEET
AWAY. A SINGLE GROUND SHALL BE LOCATED DIRECTLY UNDER EACH TELEPHONE WIRE OR
CABLE CROSSING. THE GROUND WIRE SHALL BE CONNECTED TO THE FENCE FABRIC AND
TENSION WIRE WITH UL LISTED FENCE FABRIC GROUND CLAMPS; BURNDY CAT. NO. FFGC6,
HARGER CAT, NO. FGC6 OR APPROVED. GROUNDING CONNECTORS SHALL BE SIZED AND
SUITABLE FOR THE RESPECTIVE APPLICATION. CONNECTIONS TO GROUND RODS SHALL BE WITH
UL LISTED GROUNDING CONNECTORS SUITABLE FOR DIRECT BURIAL IN EARTH OR EXOTHERMIC
WELD TYPE CONNECTORS, CADWELD BY PENTAIR ERICO PRODUCTS, INC., THERMOWELD BY
CONTINENTAL INDUSTRIES, INC., ULTRAWELD BY HARGER, OR APPROVED EQUAL. EXOTHERMIC
WELD CONNECTIONS SHALL BE INSTALLED IN CONFORMANCE WITH THE RESPECTIVE
MANUFACTURER'S DIRECTIONS USING MOLDS SUITABLE FOR EACH RESPECTIVE APPLICATION.
GROUND RODS FOR FENCING SHALL BE 5/8-IN. DIAMETER BY 8 FEET LONG (MINIMUM), UL-LISTED, COPPER-CLAD. THE GROUND WIRE USED TO BOND THE FENCE FABRIC AND TENSION WIRE TO
THE GROUND ROD SHALL BE #6 AWG (MINIMUM) BARE SOLID COPPER CONDUCTOR. FENCE
GROUNDING SHALL BE CONNECTED TO THE GROUNDING ELECTRODE SYSTEM AT THE ENGINE
GENERATOR SITE TO MAINTAIN EQUAL POTENTIAL.
16. MAKE SURE THE FENCE HAS ADEQUATE CLEARANCE FROM THE ENGINE GENERATOR EXHAUST TO
PREVENT DAMAGE DUE TO HEAT SOURCE.
AutoCAD SHX Text 2'-6"
AutoCAD SHX Text 3'-0'
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text 6'-0"
AutoCAD SHX Text 3'-6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 6'-0"
AutoCAD SHX Text 3'-0"
AutoCAD SHX Text 3'-8"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 3'-0'
AutoCAD SHX Text Copyright © 2020 by Hanson Professional Services Inc. All rights reserved. This 2020 by Hanson Professional Services Inc. All rights reserved. This document is intended solely for the use of the individual or the entity to which it is addressed. The information contained in this document shall not be duplicated, stored electronically, or distributed, in whole or in part, without the express written permission of Hanson Professional Services Inc., 1525 S. Sixth St., Springfield, IL 62703, (217) 788-2450, www.hanson-inc.com. Unauthorized reproduction or transmission of any part of this document is a violation of federal law.
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text
STATE OF
AutoCAD SHX Text R
AutoCAD SHX Text S
AutoCAD SHX Text E
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text I
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text L
AutoCAD SHX Text O
AutoCAD SHX Text L
AutoCAD SHX Text F
AutoCAD SHX Text S
AutoCAD SHX Text A
AutoCAD SHX Text I
AutoCAD SHX Text R
AutoCAD SHX Text D
AutoCAD SHX Text P
AutoCAD SHX Text No 78974
AutoCAD SHX Text C
AutoCAD SHX Text I
AutoCAD SHX Text L
AutoCAD SHX Text S
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text N
AutoCAD SHX Text G
AutoCAD SHX Text I
23'-6"
8' -8
12" SLAB-ON-GRADE REINF. W/#5 @ 12" O.C. EACH WAY TOP AND BOTTOM
G.C. TO COORDINATE SLAB SIZE WITH MANUFACTURER'S REQUIREMENTS.
1/S-2.1
TYP.
1/S-2.1
TYP.
Engineering | Planning | Allied Services
Offices Nationwide www.hanson-inc.com
Hanson Professional Services Inc.
CONSULTANTS
EB0007061
AA0003116
IB0001058
SHEET TITLE
REVIEWED BY:
DRAWN BY:
DESIGN BY:
PROJECT NO:
ISSUE:
© Copyright Hanson Professional Services Inc. 2020
54321 6
E
D
C
B
A
54321 6
MARK DATE DESCRIPTION
720 N. Maitland Ave., Suite 102 Maitland, FL 32751
(407) 622-2050
(407) 622-2051
MEADOW WOODS
MAGIC GYM
STANDBY
GENERATOR
INSTALLATION
1751 RHODE ISLAND
WOODS CIRCLE
ORLANDO, FL 32824
18G0011B-1500
SEAL
Printed copies of this document are not considered sign and sealed and the SHA authentication code must be verified on any electronic copies.
LBB
MR
SA
CERTIFICATE OF AUTHORIZATION No. 27343 LAURA BARBERO-BUFFA, P.E. No. 74027
1214 EAST CONCORD STREET
ORLANDO, FLORIDA 32803
P: 407.377.7227
Engineering + Construction | CGC 1521662
CONSULTANTS
TO
T
H E
BE
ST
O F
TH
E
EN
G
IN
EE
R 'S
K N
O W
LE
D
G E, T H
E
PL
AN
S
AN
D
S
PE
C
IF
IC
AT
IO
N
S C
O M
PL
Y
W
IT
H T
H E
FL
O
R
ID
A
BU
IL
D
IN
G
C O
D E
This item has been digitally signed and sealed by Laura Isabel Barbero Buffa, P.E. on the date listed using a digital signature.
10/18/2021
ISSUED FOR BIDDING
CONSTRUCTION DOCS
STRUCTURAL NOTES,
PLAN AND DETAILS
S-2.1
GENERAL
1. NO PROVISION OF ANY REFERENCED STANDARD SPECIFICATION, MANUAL OR CODE (WHETHER OR
NOT SPECIFICALLY INCORPORATED BY REFERENCE IN THE CONTRACT DOCUMENTS) SHALL BE
EFFECTIVE TO CHANGE THE DUTIES AND RESPONSIBILITIES OF OWNER, CONTRACTOR, DESIGN
PROFESSIONAL, SUPPLIER, OR ANY OF THEIR CONSULTANTS, AGENTS, OR EMPLOYEES FROM
THOSE SET FORTH IN THE CONTRACT DOCUMENTS. NOR SHALL IT BE EFFECTIVE TO ASSIGN TO
THE DESIGN PROFESSIONAL OF RECORD OR ANY OF THE DESIGN PROFESSIONAL OF RECORD'S
CONSULTANTS, AGENTS, OR EMPLOYEES ANY DUTY OR AUTHORITY TO SUPERVISE OR DIRECT THE
FURNISHING OR PERFORMANCE OF THE WORK OR ANY DUTY OR AUTHORITY TO UNDERTAKE
RESPONSIBILITIES CONTRARY TO THE PROVISIONS OF THE CONTRACT DOCUMENTS.
2. IT IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR TO OBTAIN ALL CONTRACT DOCUMENTS AND
LATEST ADDENDA AND TO SUBMIT SUCH DOCUMENTS TO ALL SUBCONTRACTORS AND MATERIAL
SUPPLIERS PRIOR TO THE SUBMITTAL OF SHOP DRAWINGS, FABRICATION OF ANY STRUCTURAL MEMBERS, AND ERECTION IN THE FIELD.
3. THE CONTRACT STRUCTURAL DRAWINGS AND SPECIFICATIONS REPRESENT THE FINISHED STRUCTURE, AND, EXCEPT WHERE SPECIFICALLY SHOWN, DO NOT INDICATE THE METHOD OR MEANS OF
CONSTRUCTION. THE CONTRACTOR SHALL SUPERVISE AND DIRECT THE WORK AND SHALL BE SOLELY RESPONSIBLE FOR ALL CONSTRUCTION MEANS, METHODS, PROCEDURES, TECHNIQUES, AND SEQUENCE.
4. REFERENCE TO STANDARD SPECIFICATIONS OF ANY TECHNICAL SOCIETY, ORGANIZATION, OR
ASSOCIATION OR TO CODES OF LOCAL OR STATE AUTHORITIES, SHALL MEAN THE LATEST
STANDARD, CODE, SPECIFICATION OR TENTATIVE SPECIFICATION ADOPTED AT THE DATE OF
TAKING BIDS, UNLESS SPECIFICALLY STATED OTHERWISE.
5. CONTRACT DOCUMENTS SHALL GOVERN IN THE EVENT OF A CONFLICT WITH THE CODE OF
PRACTICE OR SPECIFICATIONS OF ACI, PCI, AISC, OR OTHER STANDARDS. WHERE A CONFLICT
OCCURS WITHIN THE CONTRACT DOCUMENTS, THE STRICTEST REQUIREMENT SHALL GOVERN.
6. MATERIAL, WORKMANSHIP, AND DESIGN SHALL CONFORM TO THE REFERENCED BUILDING CODE.
7. STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH THE ELECTRICAL, SHOP
DRAWINGS AND SPECIFICATIONS. CONTRACTOR SHALL COORDINATE THE STRUCTURAL
DOCUMENTS WITH THE ELECTRICAL DOCUMENTS. DESIGN PROFESSIONAL SHALL BE NOTIFIED OF
ANY DISCREPANCY OR OMISSION. FOR DIMENSIONS NOT SHOWN ON THE STRUCTURAL DRAWINGS
SEE THE ELECTRICAL DRAWINGS.
8. CONTRACTOR SHALL VERIFY EXISTING DIMENSIONS, ELEVATIONS, AND SITE CONDITIONS BEFORE
STARTING WORK. DESIGN PROFESSIONAL SHALL BE NOTIFIED OF ANY DISCREPANCY.
9. OPENINGS THROUGH SLABS FOR CONDUIT SHALL BE COORDINATED BY THE CONTRACTOR.
CONTRACTOR HAS SOLE RESPONSIBILITY FOR MEANS, METHODS, TECHNIQUES, SEQUENCES, AND
PROCEDURES OF CONSTRUCTION.
10. THE STRUCTURE IS STABLE ONLY IN ITS COMPLETED FORM. TEMPORARY SUPPORTS REQUIRED
FOR STABILITY DURING ALL INTERMEDIATE STAGES OF CONSTRUCTION SHALL BE DESIGNED,
FURNISHED, AND INSTALLED BY THE CONTRACTOR.
11. CONTRACTOR HAS SOLE RESPONSIBILITY TO COMPLY WITH ALL OSHA REGULATIONS.
12. REVIEW OF SUBMITTALS OR SHOP DRAWINGS BY THE DESIGN PROFESSIONAL DOES NOT RELIEVE
THE CONTRACTOR OF THE SOLE RESPONSIBILITY TO REVIEW AND CHECK ALL SUBMITTALS AND
SHOP DRAWINGS BEFORE SUBMITTING TO THE DESIGN PROFESSIONAL. CONTRACTOR REMAINS
SOLELY RESPONSIBLE FOR ERRORS AND OMISSIONS ASSOCIATED WITH THE PREPARATION OF
SHOP DRAWINGS AS THEY PERTAIN TO MEMBER SIZES, DETAILS, AND DIMENSIONS SPECIFIED IN
THE CONTRACT DOCUMENTS.
13. CONTRACTOR TO ISSUE REQUEST FOR INFORMATION (RFI) FOR ANY INFORMATION NOT
CLEAR/NOT SHOWN IN THE DRAWINGS.
14. DO NOT SCALE DRAWINGS.
15. ANY MATERIALS OR PRODUCTS SUBMITTED FOR APPROVAL THAT ARE DIFFERENT FROM THE
MATERIAL OR PRODUCTS SPECIFIED IN THE STRUCTURAL CONTRACT DOCUMENTS WILL BE
APPROVED ONLY IF THE FOLLOWING CRITERIA ARE SATISFIED:
a. A COST SAVINGS TO THE OWNER IS DOCUMENTED AND SUBMITTED WITH THE REQUEST.
b. THE MATERIAL OR PRODUCT HAS BEEN APPROVED BY THE INTERNATIONAL CODE COUNCIL (ICC)
AND THE ICC REPORT IS SUBMITTED WITH THE REQUEST.
c. THE ICC ESR THAT IS SUBMITTED MUST REFERENCE THE BUILDING CODE UNDER WHICH THE
PROJECT IS PERMITTED. ICC REPORTS THAT HAVE BEEN DISCONTINUED AT THE TIME OF
PRODUCT INSTALLATION WILL NOT BE ACCEPTED.
SUBMITTALS NOT SATISFYING THE ABOVE CRITERIA WILL NOT BE CONSIDERED. REFER TO
SPECIFICATIONS FOR SUBSTITUTION PROCEDURES. BASE CONSULTANTS, INC. RETAINS THE RIGHT TO
REJECT ANY SUBSTITUTION REQUESTS.
CODE/DESIGN CRITERIA
1. STRUCTURE IS DESIGNED IN ACCORDANCE WITH THE FOLLOWING:
§ FLORIDA BUILDING CODE 2020.
§ ASCE 7-16
2. DESIGN WIND LOADS:
ULTIMATE WIND SPEED 150 MPH
NOMINAL WIND SPEED 115 MPH
RISK CATEGORY IV
EXPOSURE C
ULTIMATE LATERAL PRESSURE ON GENERATOR: 41.56 PSF (24.94 PSF NOMINAL). ULTIMATE UPLIFT
PRESSURE ON GENERATOR: 48.42 PSF (29.06 PSF NOMINAL). THESE PRESSURES ACT
SIMULTANEOUSLY ON THE EQUIPMENT.
REINFORCED CONCRETE
1. ALL CONCRETE SHALL CONFIRM TO THE REQUIREMENTS OF ACI 301- SPECIFICATIONS FOR
STRUCTURAL CONCRETE FOR BUILDINGS.
2. STANDARDS:
· DESIGN - ACI318
· DETAILS - ACI315
· MATERIALS - ACI 301
3. ALL CONCRETE CONSTRUCTION SHALL CONFORM TO THE CURRENT "ACI MANUAL OF CONCRETE
PRACTICE".
4. CONCRETE 28 DAY COMPRESSIVE STRENGTH AND DENSITY REQUIREMENTS:
USAGE STRENGTH TYPE
ALL CONCRETE 4000 NWT
a. INDICATED CONCRETE TYPES SHALL BE PROPORTIONED FOR MAXIMUM WATER CEMENT RATIO
OF 0.52.
b. NWT = NORMAL WEIGHT CONCRETE
c. ALL CONCRETE SHALL HAVE ALLOWABLE UNIT SHRINKAGE OF 0.03% AT 28 DAYS. (SEE ASTM
C157)
d. EXTERIOR CONCRETE SLABS SHALL HAVE 4% TO 6% ENTRAINED AIR
e. PORTLAND CEMENT SHALL CONFORM TO ASTM C-150, TYPE I OR II.
f. ALL AGGREGATE FOR NORMAL WEIGHT CONCRETE SHALL MEET ASTM C 33.
5. REINFORCING STEEL
a. ALL REINFORCING STEEL SHALL CONFORM TO ASTM A615, GRADE 60 UNLESS NOTED
OTHERWISE ON THE DRAWINGS.
b. REINFORCEMENT SHALL BE DETAILED AND PLACED IN ACCORDANCE WITH ACI 315.
c. REINFORCEMENT SHALL BE SECURELY PLACED TO PREVENT DISPLACEMENT DURING
CONCRETE PLACEMENT. PROVIDE THE CONCRETE COVER FOR REINFORCING PER TABLE 3.3.2.3
OF ACI 301-2010, UNLESS SPECIFICALLY DETAILED OTHERWISE.
d. REINFORCING STEEL COVERAGE SHOULD CONFORM TO THE REQUIREMENTS ACI 318 UNLESS
SPECIFIED OTHERWISE ON THE DRAWINGS. THE REINFORCING STEEL DETAILER SHALL ADJUST
REINFORCING STEEL CAGE SIZES AT INTERSECTING STRUCTURAL MEMBERS AS REQUIRED TO
ALLOW CLEARANCE FOR INTERSECTING REINFORCING BAR LAYERS WITH MINIMUM SPECIFIED
COVER.
e. CHAMFER ALL PERMANENTLY EXPOSED CONCRETE EDGES 3/4-INCH, UNO.
f. ALUMINUM SHALL NOT BE EMBEDDED IN ANY CONCRETE.
POST-INSTALLED ANCHORS
1. POST-INSTALLED ANCHORS SHALL ONLY BE USED WHERE SPECIFIED ON THE DRAWINGS.
2. CONTRACTOR SHALL OBTAIN APPROVAL FROM ENGINEER OF RECORD PRIOR TO USING
POST-INSTALLED ANCHORS FOR MISSING OR MISPLACED CAST-IN-PLACE ANCHORS.
3. CARE SHALL BE GIVEN TO AVOID CONFLICTS WITH EXISTING REBAR. HOLES SHALL BE DRILLED
AND CLEANED PER THE MANUFACTURER'S INSTRUCTIONS. ANCHORS SHALL BE INSTALLED PER
THE MANUFACTURER'S INSTALLATION INSTRUCTIONS AT NOT LESS THAN MINIMUM EDGE
DISTANCES AND/OR SPACINGS INDICATED IN THE MANUFACTURER'S LITERATURE. CONTACT
MANUFACTURER PRIOR TO ANCHOR INSTALLATION, IF TRAINING IS REQUIRED.
4. UNLESS SPECIFIED OTHERWISE, ANCHORS SHALL BE EMBEDDED IN THE APPROPRIATE SUBSTRATE
WITH A MINIMUM EMBEDMENT OF 8 TIMES THE NOMINAL ANCHOR DIAMETER OR THE EMBEDMENT
REQUIRED TO SUPPORT THE INTENDED LOAD.
5. DRILLING, CORING, SAW CUTTING AND ETC. INTO EXISTING CONCRETE SHALL MEET LATEST OSHA
REGULATIONS FOR SILICA DUST EXPOSURE
6. ACCEPTABLE PRODUCTS ARE:
a. "CRACKED CONCRETE" MECHANICAL ANCHORS:
· "HILTI KB-TZ" BY HILTI.
· "STRONG-BOLT" BY SIMPSON STRONG-TIE.
b. "CRACKED CONCRETE" ADHESIVE ANCHORS:
· "HIT RE500-SD" BY HILTI.
SUBMITTALS
1. THE GENERAL CONTRACTOR SHALL PREPARE A DETAILED LIST AND SCHEDULE OF ALL SUBMITTAL
ITEMS TO BE SENT TO THE STRUCTURAL ENGINEER PRIOR TO THE START OF CONSTRUCTION.
2. GENERAL CONTRACTORS SHALL REVIEW AND STAMP ALL SHOP DRAWINGS BEFORE SUBMITTING FOR REVIEW. SHOP DRAWINGS SHALL BE SUBMITTED TO THE ARCHITECT AND/OR ENGINEER AND
HAVE THE ENGINEER'S SHOP DRAWING APPROVAL STAMP AFFIXED PRIOR TO FABRICATION.
FABRICATION AND ERECTION SHALL BE FROM REVIEWED SHOP DRAWINGS.
3. A RECORD SET OF APPROVED SHOP DRAWINGS SHALL BE KEPT IN THE FIELD BY THE GENERAL
CONTRACTOR.
4. ANY DEVIATION FROM, ADDITION TO, SUBSTITUTION FOR, OR MODIFICATION TO THE STRUCTURE
OR ANY PART OF THE STRUCTURE DETAILED ON THE CONTRACT DOCUMENTS SHALL BE
SUBMITTED IN WRITING TO THE ENGINEER FOR REVIEW. SHOP DRAWINGS SUBMITTED FOR REVIEW DO NOT CONSTITUTE “IN-WRITING” UNLESS IT IS CLEARLY NOTED THAT SPECIFIC CHANGES ARE
BEING SUGGESTED.
5. THE OMISSION FROM THE SHOP DRAWINGS OF ANY MATERIALS REQUIRED BY THE CONTRACT
DOCUMENTS TO BE FURNISHED SHALL NOT RELIEVE THE CONTRACTOR OF THE RESPONSIBILITY
OF FURNISHING AND INSTALLING SUCH MATERIALS, REGARDLESS OF WHETHER THE SHOP
DRAWINGS HAVE BEEN REVIEWED AND APPROVED.
6. THE USE OF ELECTRONIC FILES OR REPRODUCTIONS OF THESE CONTRACT DOCUMENTS BY ANY
CONTRACTOR, SUBCONTRACTOR, ERECTOR, FABRICATOR, OR MATERIAL SUPPLIER IN LIEU OF
PREPARATION OF SHOP DRAWINGS SIGNIFIES THEIR ACCEPTANCE OF ALL INFORMATION SHOWN
HEREON AS CORRECT, AND OBLIGATES THEMSELVES TO ANY JOB EXPENSE, REAL OR IMPLIED,
RISING DUE TO ANY ERRORS THAT MAY OCCUR HEREON.
7. REQUEST FOR INFORMATION (RFI) SHALL BE ORIGINATED BY THE CONTRACTOR AND SHALL BE
SUBMITTED TO THE ENGINEER VIA ARCHITECT OR DIRECTLY TO ENGINEER WHEN APPROVED BY
ARCHITECT. RFI SHALL BE SUBMITTED IN A PROMPT MANNER TO AVOID DELAYS IN THE
CONTRACTORS WORK.
8. RFI RESPONSES ARE NOT INTENDED TO AUTHORIZE ANY INCREASE IN CONSTRUCTION COST, SCHEDULE OR CONFLICT WITH APPLICABLE STANDARDS OR CODES. IT IS THE RESPONSIBILITY OF
THE CONTRACTOR TO NOTIFY DESIGN TEAM IMMEDIATELY OF ANY PERCEIVED COST, SCHEDULE
OR SCOPE IMPACTS.
9. SUBMITTALS BY THE CONTRACTOR ARE NOT A PART OF THE CONTRACT DOCUMENTS.
10. CONTRACTOR SHALL DIRECT SPECIFIC ATTENTION ON THE SUBMITTAL TO ANY DEVIATION FROM
THE CONTRACT DOCUMENTS. CONTRACTOR SHALL STAMP AND SIGN SHOP DRAWINGS AND
PRODUCT DATA, AND SIGN OR INITIAL EACH SAMPLE TO CERTIFY COMPLIANCE WITH
REQUIREMENTS OF CONTRACT DOCUMENTS. SUBMITTALS RECEIVED WITHOUT THE
CONTRACTOR'S STAMP OF REVIEW WILL BE RETURNED TO THE CONTRACTOR FOR REVIEW AND
RESUBMITTAL.
11. WORK REQUIRING SHOP DRAWINGS, WHETHER CALLED FOR BY THE CONTRACT DOCUMENTS OR
REQUESTED BY THE CONTRACTOR, SHALL NOT COMMENCE UNTIL THE SUBMISSION HAS BEEN
REVIEWED BY THE DESIGN PROFESSIONAL. WORK MAY COMMENCE IF THE CONTRACTOR VERIFIES
THE ACCURACY OF THE DESIGN PROFESSIONAL'S CORRECTIONS AND NOTATIONS AND COMPLIES
WITH THEM WITHOUT EXCEPTION AND WITHOUT REQUESTING CHANGE IN CONTRACT SUM OR
CONTRACT TIME. A COPY OF THE MARKED STRUCTURAL SHOP DRAWINGS WITH THE DESIGN
PROFESSIONAL'S REVIEW STAMP IS TO BE MAINTAINED AT THE JOB SITE.
12. THE FOLLOWING SHOP DRAWINGS SHALL BE SUBMITTED BY THE CONTRACTOR FOR THE
ENGINEER'S REVIEW:
§ CONCRETE MIX DESIGNS
§ REINFORCING STEEL
§ POST-INSTALLED ANCHORS - PRODUCT DATA
ABBREVIATIONS
JT JOINT
P or PL P.S.F.
P.S.I.
REINF
REQ'D
STL
STD
GA.
GALV
EQ.
EXT
E.W.
GALVANIZE
GAGE, GAUGE
EQUAL
EXTERIOR
EACH WAY
EA.
E.J.
E.F.
EL.
EXPANSION JOINT
ELEVATION
EACH FACE
EACH
L
STEEL
STANDARD
REINFORCE(D) (ING)
PLATE
POUNDS PER SQUARE INCH
POUNDS PER SQUARE FOOT
LSH
LSV
L.S.H.
MAX
MECH
O.C.
OPNG
OPP
CONC
CONT
COL
C.M.U. CONCRETE MASONRY UNIT
CONCRETE
CONTINUOUS
COLUMN
A.I.S.C. AMERICAN INSTITUTE OF
STEEL CONSTRUCTION
A.B.
A.C.I. AMERICAN CONCRETE INSTITUTE
ANCHOR BOLT
OPENING
ON CENTER
OPPOSITE
MAXIMUM
MECHANICAL
LONG SIDE HORIZONTAL
LONG SLOTTED HOLES
LONG SIDE VERTICAL
WELDED WIRE REINFORCEMENT
VERTICAL
W/ WITH
WWR
VERT
C or CL CENTERLINE
DWG
DWL
DIA
DOWEL
DRAWING
DIAMETER
C.J. CONSTRUCTION JOINT
OR CONTROL JOINT
BOTT. BOTTOM
HORIZ HORIZONTAL
NTS NOT TO SCALE
REQUIRED
MIN. MINIMUM
U.N.O. UNLESS NOTED OTHERWISE
= REVISION MARK
= ELEVATION MARK ON DETAILS
= SECTION MARK ON DETAILS
SHEET NO.
SECTION NO.
STRUCTURAL SYMBOLS
SHEET NO.
SECTION NO.
= SECTION CUT ON PLANS
SECTION
0/S-00
NEW 12" SLAB-ON-GRADE
REINF. W/#5 @ 12" O.C.
EACH WAY TOP AND
BOTTOM
S-2.1
GENERATOR SLAB DETAIL
SCALE: N.T.S.
4" CHAMFER
(TYP.)
3" C
LR
2" CLR.
2" C
LR
SCALE:
02 GENERATOR SLAB PLAN
0 1' 2' 4'
1/2"=1'-0"
ATTACHMENT TO
CONCRETE FOUNDATION BY
STAIR/PLATFORM
MANUFACTURER
3'-0" 3"
C
LR
. T
YP
3'-0"x3'-0"x12"
FOUNDATION REINF.
W/(4)-#5 EA. WAY BOTTOM
BARS
NOTES:
1. COAT ALL METALS IN CONTACT WITH CONCRETE WITH BITUMINOUS PAINT ON THE
CONTACT SURFACE. NEOPRENE GASKETS CAN BE PROVIDED IN LIEU OF BITUMINOUS
PAINT.
1' -0
T.O. GRADE
T.O. FOUNDATION
S2-1
STAIR PLATFORM FOUNDATION
SCALE: 1" = 1'-0"
AutoCAD SHX Text Copyright © 2020 by Hanson Professional Services Inc. All rights reserved. This 2020 by Hanson Professional Services Inc. All rights reserved. This document is intended solely for the use of the individual or the entity to which it is addressed. The information contained in this document shall not be duplicated, stored electronically, or distributed, in whole or in part, without the express written permission of Hanson Professional Services Inc., 1525 S. Sixth St., Springfield, IL 62703, (217) 788-2450, www.hanson-inc.com. Unauthorized reproduction or transmission of any part of this document is a violation of federal law.
AutoCAD SHX Text
SCALE:
AutoCAD SHX Text 3/4" = 1'-0"
Engineering | Planning | Allied Services
Offices Nationwide www.hanson-inc.com
Hanson Professional Services Inc.
CONSULTANTS
EB0007061
AA0003116
IB0001058
SHEET TITLE
REVIEWED BY:
DRAWN BY:
DESIGN BY:
PROJECT NO:
ISSUE:
© Copyright Hanson Professional Services Inc. 2020
54321 6
E
D
C
B
A
54321 6
MARK DATE DESCRIPTION
720 N. Maitland Ave., Suite 102 Maitland, FL 32751
(407) 622-2050
(407) 622-2051
MEADOW WOODS
MAGIC GYM
STANDBY
GENERATOR
INSTALLATION
1751 RHODE ISLAND
WOODS CIRCLE
ORLANDO, FL 32824
10/18/2021 18G0011B-1500
DLH
TAGS
SP
SEAL
This item has been digitally signed and sealed by Salvador Perez P.E. on the date listed using a digital signature.
Printed copies of this document are not considered sign and sealed and the SHA authentication code must be verified on any electronic copies.
ISSUED FOR BIDDING
CONSTRUCTION DOCS
2 GENERATOR SITE LOCATION
NOT TO SCALE
1 NOT TO SCALE
BUILDING SITE LOCATION
ELECTRICAL LEGEND
ABBREVIATIONS ELECTRICAL SYMBOLS
GENERAL SYMBOLS
ELECTRICAL GENERAL NOTES
ELECTRICAL LEGEND
& GENERAL NOTES
E-0.1
AutoCAD SHX Text Copyright © 2020 by Hanson Professional Services Inc. All rights reserved. This 2020 by Hanson Professional Services Inc. All rights reserved. This document is intended solely for the use of the individual or the entity to which it is addressed. The information contained in this document shall not be duplicated, stored electronically, or distributed, in whole or in part, without the express written permission of Hanson Professional Services Inc., 1525 S. Sixth St., Springfield, IL 62703, (217) 788-2450, www.hanson-inc.com. Unauthorized reproduction or transmission of any part of this document is a violation of federal law.
AutoCAD SHX Text
STATE OF
AutoCAD SHX Text S
AutoCAD SHX Text A
AutoCAD SHX Text L
AutoCAD SHX Text V
AutoCAD SHX Text A
AutoCAD SHX Text D
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text P
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text Z
AutoCAD SHX Text P
AutoCAD SHX Text R
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text I
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text L
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text F
AutoCAD SHX Text L
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text I
AutoCAD SHX Text D
AutoCAD SHX Text A
AutoCAD SHX Text L
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text S
AutoCAD SHX Text E
AutoCAD SHX Text No.
AutoCAD SHX Text 50064
AutoCAD SHX Text
DISCONNECT SWITCH
AutoCAD SHX Text
FLUSH ELECTRICAL POWER OR APPLIANCE PANEL
AutoCAD SHX Text
ARROWHEAD INDICATES HOMERUN TO PANEL -
AutoCAD SHX Text
NUMBER AND SIZE OF CONDUCTORS AS PER
AutoCAD SHX Text
N.E.C. NUMBERS DENOTE PANEL AND CIRCUIT
AutoCAD SHX Text
QUAD (2-20A DUPLEX) RECEPTACLE MTD 6"
AutoCAD SHX Text
REFERENCED NOTES
AutoCAD SHX Text
DEMOLITION HATCHING - INDICATES ITEMS TO
AutoCAD SHX Text
BE REMOVED UNLESS OTHERWISE NOTED
AutoCAD SHX Text
ITEMS SHOWN DASHED AND RELATIVELY LIGHT
AutoCAD SHX Text
ARE EXISTING UNLESS NOTED OTHERWISE
AutoCAD SHX Text
REVISION CLOUD AND REFERENCE NUMBER
AutoCAD SHX Text
CENTERLINE
AutoCAD SHX Text
ROOM NUMBERS
AutoCAD SHX Text
SECTION/DETAIL DESIGNATIONS
AutoCAD SHX Text
EQUIPMENT DESIGNATION
AutoCAD SHX Text
TOP = EQUIPMENT TAG
AutoCAD SHX Text
X = SECTION (LETTER) OR DETAIL (NUMBER)
AutoCAD SHX Text
Y = SHEET WHERE DETAIL/SECTION IS REFERENCED
AutoCAD SHX Text
Z = SHEET WHERE DETAIL/SECTION IS SHOWN
AutoCAD SHX Text
BOTTOM = EQUIPMENT NUMBER
AutoCAD SHX Text L
AutoCAD SHX Text
AutoCAD SHX Text C
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text X
AutoCAD SHX Text Z
AutoCAD SHX Text X
AutoCAD SHX Text Z
AutoCAD SHX Text
TAG
AutoCAD SHX Text
AutoCAD SHX Text Y
AutoCAD SHX Text
NOTE: SOME SYMBOLS SHOWN IN ELECTRICAL LEGEND MAY NOT APPLY TO THIS PROJECT.
AutoCAD SHX Text
ELECTRICAL METER
AutoCAD SHX Text
CIRCUIT BREAKER
AutoCAD SHX Text
FUSE
AutoCAD SHX Text
MOTOR
AutoCAD SHX Text
CONTACTOR
AutoCAD SHX Text
JUNCTION BOX
AutoCAD SHX Text
SPECIAL RECEPTACLE, SEE POWER PLANS
AutoCAD SHX Text
240V OUTLET
AutoCAD SHX Text
TO CENTER ABOVE BACKSPLASH.
AutoCAD SHX Text A-1,3,5
AutoCAD SHX Text
CONDUIT RUN
AutoCAD SHX Text
ASC - APPLICATION SPECIFIC CONTROLLER
AutoCAD SHX Text
ATC - AUTOMATIC TEMPERATURE CONTROL
AutoCAD SHX Text
FAAP - FIRE ALARM ANNUNCIATOR PANEL
AutoCAD SHX Text
GAP - GENERATOR ANNUNCIATOR PANEL
AutoCAD SHX Text
FT - FOOT OR FEET
AutoCAD SHX Text
HP - HORSE POWER
AutoCAD SHX Text
FTU - FAN TERMINAL UNIT
AutoCAD SHX Text
GFI - GROUND FAULT INTERRUPTING
AutoCAD SHX Text G or GND - GROUND
AutoCAD SHX Text
HZ - HERTZ (CYCLES PER SECOND)
AutoCAD SHX Text
FCU - FAN COIL UNIT
AutoCAD SHX Text
FLA - FULL LOAD AMPS
AutoCAD SHX Text
EM - EMERGENCY
AutoCAD SHX Text
EWC - ELECTRIC WATER COOLER
AutoCAD SHX Text
EWH - ELECTRIC WATER HEATER
AutoCAD SHX Text
EX - EXISTING
AutoCAD SHX Text
EXTR - EXISTING TO REMAIN
AutoCAD SHX Text %%dF - DEGREES FAHRENHEIT
AutoCAD SHX Text
FACP - FIRE ALARM CONTROL PANEL
AutoCAD SHX Text
FATC - FIRE ALARM TERMINAL CABINET
AutoCAD SHX Text
EPO - EMERGENCY POWER OFF
AutoCAD SHX Text
CT - COOLING TOWER
AutoCAD SHX Text dB - DECIBELS
AutoCAD SHX Text
EF - EXHAUST FAN
AutoCAD SHX Text
EDH - ELECTRIC DUCT HEATER
AutoCAD SHX Text
ELEC - ELECTRIC OR ELECTRICAL
AutoCAD SHX Text %%dC - DEGREES CENTIGRADE
AutoCAD SHX Text
C - CONDUIT
AutoCAD SHX Text
CB - CIRCUIT BREAKER
AutoCAD SHX Text
CCTV - CLOSED CIRCUIT TELEVISION
AutoCAD SHX Text
D/D - DUSK TO DAWN
AutoCAD SHX Text
CONC - CONCRETE
AutoCAD SHX Text
COND - CONDUCTOR
AutoCAD SHX Text
DN - DOWN
AutoCAD SHX Text
- ALUMINUM
AutoCAD SHX Text
- AIR CONDITIONING
AutoCAD SHX Text
- ABOVE FINISHED FLOOR
AutoCAD SHX Text
- AIR HANDLING UNIT
AutoCAD SHX Text
AC - ALTERNATING CURRENT
AutoCAD SHX Text
AFG - ABOVE FINISHED GRADE
AutoCAD SHX Text
ATS - AUTOMATIC TRANSFER SWITCH
AutoCAD SHX Text
BG - BELOW GRADE
AutoCAD SHX Text
ABCLG - ABOVE CEILING
AutoCAD SHX Text
APPROX - APPROXIMATELY
AutoCAD SHX Text
BLDG - BUILDING
AutoCAD SHX Text A/C
AutoCAD SHX Text
AHU
AutoCAD SHX Text
AFF
AutoCAD SHX Text
AL
AutoCAD SHX Text
INDICATOR CIRCUIT
AutoCAD SHX Text
C=CEILING MOUNTED GFI=GROUND FAULT
AutoCAD SHX Text
QUAD (2-20A DUPLEX) RECEPTACLE
AutoCAD SHX Text
GFI=GROUND FAULT INDICATOR CIRCUIT
AutoCAD SHX Text
SS=SURGE SUPRESSION IG=ISOLATED GND.
AutoCAD SHX Text
DUPLEX RECEPTACLE 20A. C = CEILING MTD.
AutoCAD SHX Text
ABOVE BACKSPLASH. H=HORIZONTAL MOUNTED
AutoCAD SHX Text
DUPLEX RECEPTACLE 20A MTD 6" TO CENTER
AutoCAD SHX Text
INDICATES FIXTURE TYPE. SEE LIGHTING FIXTURE SCHEDULE.
AutoCAD SHX Text "a" - LOWER CASE LETTER ADJACENT TO LIGHT FIXTURE
AutoCAD SHX Text
"A" - CAPITAL LETTER ADJACENT TO LIGHT FIXTURE SYMBOL
AutoCAD SHX Text
SYMBOL INDICATES SWITCHING WHERE APPLICABLE.
AutoCAD SHX Text
%%ULIGHTING SYMBOL NOTES:
AutoCAD SHX Text
3-WAY TOGGLE SWITCH
AutoCAD SHX Text
4-WAY TOGGLE SWITCH
AutoCAD SHX Text
SPST TOGGLE SWITCH
AutoCAD SHX Text
PTAC - PACKAGED TERMINAL AIR CONDITIONER
AutoCAD SHX Text
UL - UNDERWRITER'S LABORATORIES
AutoCAD SHX Text
WH - WATER HEATER
AutoCAD SHX Text
VAV - VARIABLE AIR VOLUME
AutoCAD SHX Text
VFD - VARIABLE FREQUENCY DRIVE
AutoCAD SHX Text
WP - WEATHERPROOF
AutoCAD SHX Text
TYP - TYPICAL
AutoCAD SHX Text
RLA - RUNNING LOAD AMPS
AutoCAD SHX Text
SHT - SHEET
AutoCAD SHX Text
SF - SUPPLY FAN
AutoCAD SHX Text
RTU - ROOF TOP UNIT
AutoCAD SHX Text
UGE - UNDERGROUND ELECTRIC
AutoCAD SHX Text
TTC - TELEPHONE TERMINAL CABINET
AutoCAD SHX Text
TTB - TELEPHONE TERMINAL BOARD
AutoCAD SHX Text
ST - SHUNT TRIP
AutoCAD SHX Text
R - RELOCATE
AutoCAD SHX Text 2.
AutoCAD SHX Text 1.
AutoCAD SHX Text
MTD - MOUNTED
AutoCAD SHX Text
POAU - PACKAGED OUTDOOR AIR UNIT
AutoCAD SHX Text
OAU - OUTDOOR AIR HANDLING UNIT
AutoCAD SHX Text
P - PUMP
AutoCAD SHX Text PH or %%C - PHASE
AutoCAD SHX Text
NTS - NOT TO SCALE
AutoCAD SHX Text
OHE - OVERHEAD ELECTRIC
AutoCAD SHX Text
NO - NORMALLY OPEN
AutoCAD SHX Text
NL - NIGHT LIGHT
AutoCAD SHX Text
NF - NON-FUSED
AutoCAD SHX Text
NIC - NOT IN CONTRACT
AutoCAD SHX Text
NC - NORMALLY CLOSED
AutoCAD SHX Text
MCB - MAIN CIRCUIT BREAKER
AutoCAD SHX Text
MIN - MINIMUM
AutoCAD SHX Text
MAX - MAXIMUM
AutoCAD SHX Text
MH - MANHOLE
AutoCAD SHX Text
MDF - MAIN DISTRIBUTION FRAME
AutoCAD SHX Text
MCA - MINIMUM CIRCUIT AMPACITY
AutoCAD SHX Text
MLO - MAIN LUGS ONLY
AutoCAD SHX Text
GFI=GROUND FAULT INDICATOR CIRCUIT
AutoCAD SHX Text
SS=SURGE SUPRESSION IG=ISOLATED GND.
AutoCAD SHX Text
SIMPLEX RECEPTACLE 20A. C = CEILING MTD.
AutoCAD SHX Text
1. THE DRAWINGS AND APPLICABLE SPECIFICATIONS SHALL BE CONSIDERED SUPPLEMENTARY, ONE TO THE OTHER AND ARE THE DRAWINGS AND APPLICABLE SPECIFICATIONS SHALL BE CONSIDERED SUPPLEMENTARY, ONE TO THE OTHER AND ARE CONSIDERED THE "CONTRACT DOCUMENTS." ALL WORKMANSHIP, METHODS, AND/OR MATERIALS DESCRIBED OR IMPLIED BY ONE AND NOT DESCRIBED OR IMPLIED BY THE OTHER SHALL BE PROVIDED, FURNISHED, OR PERFORMED AS IF IT HAD APPEARED IN BOTH SECTIONS. THE TERM "CONTRACT DOCUMENTS" DESCRIBED HEREIN IS NOT LIMITED SOLELY TO THE ELECTRICAL PORTION OF THE DRAWINGS AND SPECIFICATIONS. 2. WHERE A DISCREPANCY OR CONFLICT IS FOUND BETWEEN ONE DRAWING AND ANOTHER, OR BETWEEN A DRAWING AND WHERE A DISCREPANCY OR CONFLICT IS FOUND BETWEEN ONE DRAWING AND ANOTHER, OR BETWEEN A DRAWING AND APPLICABLE SPECIFICATIONS, THE CONTRACTOR SHALL NOTIFY THE A/E IMMEDIATELY IN WRITTEN FORM. CONTRACTOR SHALL NOT PROCEED WITH THAT PORTION OF THE WORK UNTIL A WRITTEN DIRECTIVE HAS BEEN RETURNED. 3. THE DRAWINGS ARE DIAGRAMMATIC AND ARE NOT INTENDED TO SHOW EVERY DETAIL OF CONSTRUCTION, METHODS, THE DRAWINGS ARE DIAGRAMMATIC AND ARE NOT INTENDED TO SHOW EVERY DETAIL OF CONSTRUCTION, METHODS, MATERIALS AND EQUIPMENT, OR EXACT LOCATIONS, ROUTING, ETC. THEY INDICATE THE RESULT TO BE ACHIEVED BY THE ASSEMBLAGE OF SEVERAL SYSTEMS FOR A COMPLETE AND OPERATIONAL ELECTRICAL SYSTEM. DO NOT SCALE THE CONTRACT DOCUMENTS. COORDINATE EXACT EQUIPMENT LOCATIONS WITH THE ARCHITECTURAL AND STRUCTURAL PORTIONS OF THE CONTRACT DOCUMENTS, AS WELL AS FIELD CONDITIONS, APPROVED SHOP DRAWINGS, AND WORK OF ALL OTHER DIVISIONS/TRADES. 4. THE TERM "PROVIDE" USED IN THE CONTRACT DOCUMENTS INDICATES THAT THE CONTRACTOR SHALL FURNISH AND INSTALL THE TERM "PROVIDE" USED IN THE CONTRACT DOCUMENTS INDICATES THAT THE CONTRACTOR SHALL FURNISH AND INSTALL MATERIALS, INCLUDING ALL COST FOR SHIPPING, UNLOADING, STORAGE, UNPACKING, ERECTION, ANCHORING, ETC. REQUIRED FOR CORRECT INSTALLATION OF A COMPLETE SYSTEM. 5. UNLESS NOTED AS EXISTING, ALL ELECTRICAL INDICATED IN THE CONTRACT DOCUMENTS SHALL BE NEW, SHALL BE U.L. UNLESS NOTED AS EXISTING, ALL ELECTRICAL INDICATED IN THE CONTRACT DOCUMENTS SHALL BE NEW, SHALL BE U.L. LISTED, AND SHALL BEAR A U.L. LABEL. WHERE NO U.L. LABEL OR LISTING IS AVAILABLE THE MATERIAL SHALL BE LISTED WITH AN APPROVED, NATIONALLY RECOGNIZED ELECTRICAL TESTING AGENCY. WHERE NO LABELING OR LISTING IS AVAILABLE FOR MATERIAL, TEST DATA SHALL BE SUBMITTED TO THE A/E AS EVIDENCE THAT THE MATERIAL MEETS OR EXCEEDS AVAILABLE STANDARDS. EQUIPMENT SHALL BE INSTALLED AND USED IN ACCORDANCE WITH ANY INSTRUCTIONS INCLUDED IN THE LISTING OR LABELING. 6. ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH LATEST EDITION OF THE NATIONAL ELECTRICAL CODE (NEC), THE ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH LATEST EDITION OF THE NATIONAL ELECTRICAL CODE (NEC), THE FLORIDA BUILDING CODE, THE NATIONAL FIRE CODE, STATE REQUIREMENTS, AND ALL APPLICABLE LOCAL CODES, ORDINANCES AND ALL REQUIREMENTS OF THE AUTHORITY HAVING JURISDICTION (AHJ), AS A MINIMUM. 7. THE CONTRACTOR SHALL PROVIDE EXPERIENCED, QUALIFIED, AND RESPONSIBLE SUPERVISION FOR ALL WORK REQUIRED BY THE CONTRACTOR SHALL PROVIDE EXPERIENCED, QUALIFIED, AND RESPONSIBLE SUPERVISION FOR ALL WORK REQUIRED BY THE CONTRACT DOCUMENTS. ALL ELECTRICAL EQUIPMENT SHALL BE INSTALLED IN A NEAT AND WORKMANLIKE MANNER, TO THE SATISFACTION OF THE A/E AND OWNER. ALL WORK SHALL BE PERFORMED IN A FIRST-CLASS MANNER. 8. THE CONTRACTOR SHALL CARRY ALL INSURANCE REQUIRED TO PROTECT AGAINST PUBLIC LIABILITY AND PROPERTY DAMAGE THE CONTRACTOR SHALL CARRY ALL INSURANCE REQUIRED TO PROTECT AGAINST PUBLIC LIABILITY AND PROPERTY DAMAGE FOR THE DURATION OF THIS PROJECT. 9.