This file is a set of engineering design and utility drawings for the Texas Avenue Water Main Relocation project in Orange County, Florida, prepared by Inwood Consulting Engineers for the Orlando Utilities Commission (OUC). The project involves relocating water mains along Texas Avenue from north of Duskin Avenue to south of Holden Avenue, spanning approximately 0.901 miles. The drawings detail the proposed water main infrastructure, including pipe sizes ranging from 4" to 12" in diameter, primarily using ductile iron pipe (DIP) and PVC materials. The project includes installing new water services, fire hydrant assemblies, gate valves, and removing existing water infrastructure.
The total estimated project length is 4,755.55 linear feet, with work concentrated in Orange County's District 6. The design includes detailed utility adjustments, profile and plan views, and standard technical specifications for water main installation. The project involves coordination with multiple utility providers, including OUC, AT&T, Bright House Networks, TECO Peoples Gas, and others. The drawings provide comprehensive technical specifications for pipe materials, installation methods, restraint requirements, and testing protocols, ensuring compliance with Orlando Utilities Commission and American Water Works Association (AWWA) standards.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Y22-718_Drawings2.pdf | ||
| Y22-718_Part_G&H.pdf | ||
| Y22-718_Drawings4.pdf | ||
| Y22-718.pdf | ||
| Y22-718_Drawings1.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
D A
Y T
O N
A
T O
R
L A
N D
O
1/30/2020 10:23:16 AM F:\Projects\ORC-010-01\North\utils\Utility Design\KEYSUW01.DGNdledgerwood
DESCRIPTIONSHEET
CERTIFICATION TO PLANS
ENGINEER:DATE: REG. NO.
CHRISTMAS
SEMINOLE COUNTY
OSCEOLA COUNTY
ORLANDO
INTERNATIONAL
AIRPORT
L A
K E C
O U
N T
Y
WINTER
GARDEN
ORLANDO
LAKE COUNTY
B R
E V
A R
D C
O U
N T
Y
OSCEOLA COUNTY
LAKE APOPKA
FLORIDA
T
PK
E-W
E
W
GALLOWAY DR.
1-4
1-4
I-4
0 1 2
N
Mile
BRIDGES
NET LENGTH OF PROJ.
EXCEPTIONS
GROSS LENGTH OF PROJ.
LENGTH OF PROJECT
LINEAR FT. MILES
KEY SHEET
GENERAL NOTES
PLAN & PROFILE SHEETS
ELEV. = 100.30'
STA. 109+18.15, 9.46' LT.
RAILROAD SPIKE ON POWER POLE (#419E3)
ORANGE COUNTY BM R-368-010
ELEV. = 99.77'
STA. 159+15.39, 71.78' LT.
3" DISK AT SANITARY LIFT STATION
ORANGE COUNTY BM L-1225-015
M
IA
M I
M P
A
COCOA
TO
W
IL
D W
O O D
FOR TEXAS AVENUE
SOURCE OF BENCH MARK DATUM
NOTE: THE SCALE OF THESE PLANS MAY
HAVE CHANGED DUE TO REPRODUCTION.
PLANS WERE PREPARED TO AVAILABLE INFORMATION TO ADEQUATELY ADDRESS CONDITIONS AS
THEY EXISTED AT THE TIME OF PLANS PREPARATION. DEEDS, CONDITIONS AND OWNERSHIP OF
PROPERTIES MAY HAVE CHANGED SINCE PROJECT DESIGN. THE COUNTY'S REPRESENTATIVE WILL
ADDRESS CHANGES AND NEEDS WITH THE PROPERTY OWNER OR THEIR REPRESENTATIVES.
CONTRACTOR SHALL WORK WITH THE COUNTYER'S REPRESENTATIVE IN ADDRESSING AND MEETING
NEEDS AND CONDITIONS THAT MAY HAVE CHANGED SINCE PLANS PREPERATION.
NOTE
tel. 407.971.8850
Certificate No. 7074
Oviedo, FL 32765
3000 Dovera Drive, Suite 200
OF TRANSPORTATION PURSUANT TO SUBSECTION 336.045 ( 1 ) OF THE FLORIDA STATUTES.
HIGHWAYS" IN EFFECT ON THIS DATE AS ADOPTED BY THE FLORIDA DEPARTMENT
STANDARDS FOR DESIGN, CONSTRUCTION AND MAINTENANCE FOR STREETS AND
STANDARDS CONTAINED IN THE EDITION OF THE "MANUAL FOR UNIFORM MINIMUM
OF THE FLORIDA STATUTES AND ARE IN SUBSTANTIAL COMFORMANCE WITH THE
CONSTRUCTION PLANS COMPLY WITH THE REQUIREMENTS OF SECTION 336.045
I HEREBY CERTIFY THAT THE DESIGN FOR THIS PROJECT AND THE ATTACHED
SECS. 15,16,21,22 TWP. 23 SOUTH RGE. 29 EAST
LOCATION MAP
INDEX OF SHEETS
PROJECT NO:
OF
SHEET 1
BYDATEREVISIONS
VICINITY MAP
LOCATION
PROJECT
OUC
The OneReliable
ORANGE COUNTY, FLORIDA
WATER MAIN RELOCATION
TEXAS AVENUE
U-1
U-2
U-3
U-5 - U-15
PROJECT LAYOUT
SUMMARY OF QUANTITIES
STANDARD DETAILS
DESIGNED BY: DKL
DRAWN BY : DKL
CHECKED BY: DGC
APPROVED BY: DGC
UTILITY 4755.55
4755.55
4755.55
0.901
0.901
0.901
OUC-002-01
STA. 181+40.00
END UTILITY PROJECT
U-16
DAVID K. LEDGERWOOD, P.E. 70585
407-532-8509
UTILITIES ENCOUNTERED
CABLE: BRIGHT HOUSE NETWORKS
WATER & ELECTRIC: OUC
PHONE: AT&T
407-254-9718
407-236-9651
407-351-8180
GAS: TECO PEOPLES GAS 407-420-2678
480-596-4595
888-623-0931
TRAFFIC: AMERICAN TRAFFIC SOLUTIONS
COMMUNICATIONS: CROWN CASTLE
COMMUNICATIONS: LEVEL 3 COMM.
WATER & SEWER: ORANGE COUNTY UTIL.
407-754-0106
DISTRICT NO. 6
CIP NO. 5027B
TO SOUTH OF HOLDEN AVENUE
FROM NORTH OF DUSKIN AVENUE
U-4
STA. 133+84.45
BEGIN UTILITY PROJECT
DISTRICT 1
DISTRICT 2
DISTRICT 3
DISTRICT 4
DISTRICT 5
DISTRICT 6
COMMISSIONERS
BOARD OF COUNTY
MARK MASSARO, P.E., PUBLIC WORKS DIRECTOR
PETE CLARKE
TERESA JACOBS, COUNTY MAYOR
JENNIFER THOMPSON
BRYAN NELSON
EMILY BONILLA
VICTORIA P. SIPLIN
betsy vanderley
N
T
IC
E
T H
E
F
F
IC
IA
L
C O
IS
S
E E
E
C T
R O
N
IC
F
IL
IG
N
A L
U
D
L E
1G
.0
F .A .C
UTILITY PLAN SHEET SYMBOL LEGENDUTILITY PLAN SHEET ABBREVIATIONS
B
A
REDUCER
45° BEND
90° BEND
TAPPING SLEEVE AND VALVE
TEE
45° BEND (ROLLED DOWN)
45° BEND (ROLLED UP)
GATE VALVE
WYE
CAP
FIRE HYDRANT ASSEMBLY
BLOW-OFF VALVE ASSEMBLY
AIR RELEASE VACUUM VALVE ASSEMBLY
SINGLE WATER SERVICE
22.5° BEND
EXISTING
GAS MAIN
MINIMUM
STATION
TYPICAL
BCATV
BE
BFO
BT
EXIST.
FM
GM
MIN.
CONST.
RT
LT
STA.
TYP.
WM
OE
BURIED TELEVISION CABLE
BURIED ELECTRIC
BURIED FIBER OPTIC CABLE
BURIED TELEPHONE
FORCE MAIN
LEFT
CONSTRUCT
RIGHT
WATER MAIN
OVERHEAD ELECTRIC
LINE STOP
PLUG
PLUG VALVE
PCCP PRESTRESSED CONCRETE CYLINDER PIPE
DIP
PVC
DUCTILE IRON PIPE
POLYVINYL CHLORIDE
STATION OFFSET LT/RT
ELEVATION
GROUND
EXISTING
ELEVATION
TOP
Vvh # SIZE MATERIALS
(Owner, type)
UTILITY DESCRIPTION
95.04
95.07
95.50
94.28
98.79
99.12
95.50
95.98
93.46 90.69
93.72 90.45
111 94.16 90.78
112 94.10 91.54
113 94.25 91.53
114 96.57 94.82
115 96.10 93.22
116 98.01 95.03
118 96.98 93.98
119 97.19 94.09
120 97.20 94.71
121 97.05 94.75
122 98.53 95.33
123 97.11 93.13
124 97.89 93.89
127 94.36 89.16
129 95.00 93.50
130 97.95 94.45
131 96.96 94.81
LT.
LT.
LT.
LT.
LT.
LT.
LT.
LT.
LT.
LT.
RT.
LT.
LT.
LT.
LT.
LT.
LT.
RT.
LT.
RT.
LT.
LT.
LT.
27.36'
42.65'
45.77'
17.62'
16.03'
17.80'
19.67'
19.02'
19.40'
29.46'
18.31
27.33'
26.52'
25.86'
22.46'
18.75'
33.71'
52.23'
17.97'
40.31'
40.09'
8"
8"
8"
8"
D.I.
D.I.
D.I.
D.I.
D.I.
D.I.
D.I.
D.I.
D.I.
D.I.
D.I.
95.98
95.46
98.41
98.55
LT.
LT.
8.83'
23.44'
D.I.
D.I.
SUMMARY OF VERIFIED UTILITIES
C/L
OUC
The OneReliable
1/30/2020 10:23:17 AM F:\Projects\ORC-010-01\North\utils\Utility Design\GNNTUW01.DGN
U-2
NO.
SHEET
GENERAL NOTES
dledgerwood
BY DESCRIPTIONDATE BY DESCRIPTIONDATE
REVISIONS
OUC WATER MAIN 8" 114+48
8" 117+18
8"
8"
8"
8"
8"
8"
8"
D.I.
D.I.
D.I.
D.I.
117+99
119+03
120+17
133+55 29.46'
143+50
142+42
140+40
8"
4"
6"
12"
12"
12"
D.I.
D.I.
D.I.
148+50
147+61
154+98
152+02
158+52
177+29
170+20
168+71
12"
12"
D.I.
165+73
163+14
173+02
161+02
12"
8"
8"
8"
146+22D.I.
D.I.
D.I.
D.I.
36.25'
151+98
127+47
131+22
134 95.94 91.94
135 98.78 95.26
139 99.32 98.36
144 98.76 98.01
145 98.73 98.03
146 98.77 97.97
147 98.63 97.87
149 99.35 98.75
150 98.25 95.03
151 98.36 94.21
LT.
LT.
LT.
RT.
RT.
RT.
LT.
RT.
LT.
RT.
24.13'
30.61'
61.69'
53.34
53.34'
56.86'
65.84'
60.53'
24.33'
47.16'
8"
PVC
PVC
PVC
PVC
D.I.
D.I.
8" D.I. 136+00
2"
1"
0.5"
16"
D.I.
PVC
PVC
123+45
106+26
160+47
160+47
160+43
160+44
159+16
160+26
16" 160+24
2-1.25"
1.5"
2-1.5"
OUC WATER MAIN
OUC WATER MAIN
OUC WATER MAIN
OUC WATER MAIN
OUC WATER MAIN
OUC WATER MAIN
OUC WATER MAIN
OUC WATER MAIN
OUC WATER MAIN
OUC WATER MAIN
OUC WATER MAIN
OUC WATER MAIN
OUC WATER MAIN
OUC WATER MAIN
OUC WATER MAIN
OUC WATER MAIN
OUC WATER MAIN
OUC WATER MAIN
OUC WATER MAIN
OUC WATER MAIN
OUC WATER MAIN
OUC WATER MAIN
OUC WATER MAIN
OUC WATER MAIN
OUC WATER MAIN
OUC WATER MAIN
OUC WATER MAIN
OUC WATER MAIN
OUC WATER MAIN
OUC WATER MAIN
OUC WATER MAIN
OUC WATER MAIN
OUC WATER MAIN
OUC WATER MAIN
16.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
15.
14.
GENERAL SPECIFICATIONS GENERAL MATERIAL SPECIFICATIONS
1.
2.
3.
4.
5.
6.
7.
(407) 244-8786 OR VISIT OUR WEB SITE AT http//www.ouc.com/vendor
CONTACT: OUC WATER DISTRIBUTION STANDARDS AND SPECIFICATIONS
SPECIAL NOTICE: OUC SPECIFICATIONS OFTEN ADD TO THE MANUFACTURER'S SPECIFICATIONS. IF YOU HAVE ANY QUESTIONS, PLEASE
ALL VALVE BOXES SHALL BE CAST IRON SLIDING TYPE. SCREW TYPE ARE NOT APPROVED.
CONFORM TO ANSI/AWWA C504 OR LATEST REVISION.
TO ANSI/AWWA STANDARD C509 OR LATEST REVISION. ALL VALVES 16" AND LARGER SHALL BE BUTTERFLY, HAVE EPOXY COATING AND
ALL VALVES 4" THROUGH 12" SHALL BE RESILIENT SEAT/WEDGE GATE VALVES WITH EPOXY COATING INTERNALLY/EXTERNALLY AND CONFORM
FIRE HYDRANTS SHALL BE TRAFFIC DRY BARREL TYPE AND MEET OUC SPECIFICATIONS.
SLOTTED HOLES ON THE FLANGE FACE ARE REQUIRED. PADLOCK WINGS MUST BE INCLUDED ON EACH CURB STOP OR BALL METER VALVE.
2" SERVICES REQUIRE SERVICE CLAMPS AND TO ACCOMMODATE 1-1/2" OR 2" METERS, 2" BALL ANGLE METER VALVES (CTS X FLANGE) WITH
CORPORATION STOPS USED WITH DIRECT PIPE TAPPING ON DUCTILE IRON PIPE OR WITH SERVICE CLAMPS ON PVC PIPE INSTALLATION OF
W/AWWA C800. FLARED FITTINGS ARE ACCEPTABLE UNDER CONTROLLED CONDITIONS. AN AWWA (CC) THREADING IS REQUIRED ON ALL 1"
SERVICE MATERIAL (CORP. STOPS, CURB STOPS, ETC.) FOR 1", AND 2" SERVICES SHALL BE BRASS COMPRESSION FITTINGS IN ACCORDANCE
C. SERVICE MATERIAL FOR 2" LONG SIDE SERVICES SHALL INCLUDE 2" RESTRAINED JOINT (SDR 17/CLASS 250) PVC PIPE (IPS-O.D.).
B. SERVICE MATERIAL FOR 2" SHORT SIDE SERVICES SHALL INCLUDE 2" CTS TYPE-K HARD COPPER PIPE.
A. SERVICE MATERIAL FOR 1" SHALL INCLUDE SOFT ANNEALED TYPE-K COPPER TUBING.
JOINT ENDS. ALL PIPE FITTINGS 30" OR LARGER SHALL BE CEMENT LINED (CLASS 250) DUCTILE IRON, WITH MECHANICAL JOINT ENDS.
ALL PIPE FITTINGS 4" UP TO 30" SHALL BE CEMENT OR EPOXY LINED (CLASS 350) AWWA C153 "COMPACT" DUCTILE IRON, WITH MECHANICAL
SHALL NOT BE PLACED FOR AT LEAST 30 MINUTES FOLLOWING PAINT APPLICATION.
FOR PIPE 4-12 INCH IN DIAMETER AND FOUR (4) INCHES IN WIDTH FOR LARGER PIPE, AND SHALL BE BLUE IN COLOR. BACKFILL
CONTINUOUS STRIPES SPACED AT NO MORE THAN 90° AROUND THE PIPE. THE STRIPE SHALL BE MINIMUM TWO INCHES IN WIDTH
3. DUCTILE IRON POTABLE WATER MAINS REQUIRE SPECIAL IDENTIFICATION, SUCH IDENTIFICATION SHALL INCLUDE A MINIMUM OF 4
POTABLE WATER USE.
2. PVC PIPE MUST BE BLUE IN COLOR OR HAVING CONTINUOUS BLUE MARKINGS TO CONFORM TO AWWA COLORS WITH NSF LOGO FOR
1. THE USE OF 2" AND/OR 4" PVC PIPE MUST APPROVED BY O.U.C. WATER ENGINEERING.
NOTE:
C150/A21.50 AND ANSI/AWWA C151/A21.51.
- THIRTY INCH (30") AND LARGER WATER MAINS SHALL BE PRESSURE CLASS 250 D.I. PIPE IN ACCORDANCE WITH ANSI/AWWA
ANSI/AWWA C150/A21.50 AND ANSI/AWWA C151/A21.51.
- SIX INCH (6") THROUGH TWENTY FOUR INCH (24") WATER MAINS SHALL BE PRESSURE CLASS 350 D.I. PIPE IN ACCORDANCE WITH
C150/A21.50-96 AND ANSI/AWWA C151/A21.51 OR, AS CONDITIONS WARRANT, C900 SDR18 CLASS 150 PVC PIPE.
- FOUR INCH (4") WATER MAINS SHALL BE EITHER PRESSURE CLASS 350 DUCTILE IRON (D.I.) IN ACCORDANCE WITH ANSI/AWWA
- TWO INCH (2") WATER MAIN UNDER ROADWAY REQUIRES 2" RESTRAINT JOINT SDR 17/CLASS 250 PIPE.
- TWO INCH (2") WATER MAINS SHALL BE ASTM 2241 CLASS 200 SDR21 POLYVINYL CHLORIDE (PVC) PIPE.
THE TYPICAL O.U.C. DISTRIBUTION SYSTEM PIPE SIZES AND MATERIAL USED ARE:
MANUAL.
SPECIFICATIONS OF INSTALLATIONS. MOST CENTRAL FLORIDA UTILITY SUPPLY COMPANIES HAVE A COPY OF OUC'S SPECIFICATION STANDARDS
PREPARATION OF CONSTRUCTION PLANS AND SPECIFICATIONS, AND IN NO WAY LIMITS OUC'S RIGHT TO APPROVE OR DISAPPROVE PLANS, OUC WATER DISTRIBUTION'S SPECIFICATION STANDARDS MANUAL. THE FOLLOWING INFORMATION IS TO PROVIDE GENERAL GUIDANCE IN THE
MATERIAL USED IN THE CONTRUCTION OF THE WATER DISTRIBUTION SYSTEM SHALL ADHERE TO THE REQUIREMENTS OUTLINED IN THE
BACTERIOLOGICAL SAMPLE POINT
ALL OUC OWNED SERVICE ASSEMBLIES SHALL HAVE A MINIMUM OF 10' SEPARATION FROM STRUCTURES AND TREES.
ALL TAPS ON ACTIVE WATER MAINS SHALL BE PERFORMED BY AN OUC APPROVED TAPPING CONTRACTOR.
SPECIFICATIONS FOR CONSTRUCTION.
TO BE RELOCATED OR REPLACED SHALL BE INSTALLED IN ACCORDANCE WITH OUC'S CURRENT
THE CONTRACTOR SHALL VERIFY THE SIZE OF ALL SERVICES IDENTIFIED ON THE PLANS. ALL SERVICES
407-649-4436.
A PRE-CONSTRUCTION MEETING FOR THE INSTALLATION OF WATER FACILITIES IS REQUIRED. CONTACT: OUC WATER CONSTRUCTION
BY THE OUC PROJECT ENGINEER OR THEIR REPRESENTATIVE.
ALL OUC WATER DISTRIBUTION SYSTEM PIPE SHALL HAVE A MINIMUM OF THIRTY-SIX (36) INCHES OF COVER, UNLESS OTHERWISE DIRECTED
RECEIVED FROM OUC CROSS CONNECTION CONTROL DEPT.
BACKFLOW PREVENTERS SHALL BE LOCATED NO MORE THAN 10 FEET FROM POINT OF SERVICE UNLESS PRIOR APPROVAL HAS BEEN
PROTECTION - CHAPTER 62-555 "PERMITTING AND CONSTRUCTION OF PUBLIC WATER SYSTEMS."
CROSS CONNECTION CONTROL SHALL BE IN ACCORDANCE WITH RULES AND REQUIREMENTS OF THE DEPARTMENT OF ENVIRONMENTAL
BY O.U.C.
REQUIREMENTS SET FORTH IN ANSI/AWWA STANDARDS C651. CHLORINATION IS A 5 DAY PROCESS, STARTING ON MONDAYS UNLESS APPROVED
CHAPTER 62-555 "PERMITTING AND CONSTRUCTION OF PUBLIC WATER SYSTEMS." THE PROCEDURE WILL MEET AND EXCEED THE
THE DISINFECTION OF WATER MAINS SHALL BE IN COMPLIANCE WITH RULES OF THE DEPARTMENT OF ENVIRONMENTAL REGULATION -
TESTING, AND MAINTAINING A PRESSURE IN THE NEW PIPING UNTIL A FDEP LETTER OF CLEARANCE IS OBTAINED.
PROVISIONS ARE REQUIRED TO PROTECT EXISTING ACTIVE WATER MAINS FROM BACKFLOW CONTAMINATION DURING FILLING, FLUSHING, ALL HYDROSTATIC TESTING SHALL BE IN ACCORDANCE WITH ANSI/AWWA C600 FOR D.I. PIPE AND ANSI/AWWA C605 FOR PVC PIPE.
SEPARATION OF 12".
EDGE) FROM THE POTABLE WATER MAIN. RECLAIMED WATER MAINS SHALL BE BELOW POTABLE WATER MAINS WITH A MINIMUM VERTICAL
IF IT IS NOT PRACTICAL, THE RECLAIMED WATER MAIN SHALL BE INSTALLED AT A MINIMUM HORIZONTAL DISTANCE OF 3 FEET (EDGE TO
THE RECLAIMED WATER MAIN SHALL BE ON THE OPPOSITE SIDE OF THE STREET FROM THE POTABLE WATER MAIN WHERE PRACTICAL.
ALL CONDUIT TO BE A MINIMUM 2' FROM ALL WATER MAINS, AND APPURTENANCES.
BE OBSERVED WITH NO STANDARD MITIGATION ALLOWED. A MINIMUM OF 18' SEPARATION FROM BUILDINGS AND STRUCTURES IS REQUIRED.
SEPARATION REQUIREMENTS FROM SANITARY FORCE MAINS, AT LEAST A 6' HORIZONTAL AND 12" VERTICAL SEPARATION AT CROSSINGS, MUST
WATER MAIN SEPARATION FROM SEWER, STORM, AND RECLAIM LINES WILL BE IN COMPLIANCE WITH FDEP GUIDELINES. THE MINIMUM
THE PROJECT.
THE MANUFACTURERS RECOMMENDATIONS. ALL WATER FACILITIES WILL BE IN COMPLIANCE WITH THE CONDITIONS OF FDEP PERMIT FOR
MATERIAL, INSTALLATION, AND DISINFECTION. ALL MATERIAL AND EQUIPMENT SHALL BE STORED, INSTALLED, AND USED IN ACCORDANCE WITH
ALL CONSTRUCTION OF THE WATER DISTRIBUTION SYSTEM SHALL MEET CURRENT ORLANDO UTILITIES COMMISSION SPECIFICATIONS FOR
THE CONTRACT AND NO EXTRA COMPENSATION WILL BE ALLOWED.
ADJUSTMENTS AND COOPERATE WITH THE OWNER. ANY DELAY OR INCONVENIENCE OF THE VARIOUS UTILITIES SHALL BE INCIDENTAL TO
EXISTING STRUCTURES OR UTILITIES FROM CONSTRUCTION OF WATER FACILITIES. CONTRACTOR SHALL COORDINATE ANY NECESSARY
UNDERGROUND UTILITY, WHETHER SHOWN ON THESE PLANS OR FIELD LOCATED. CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTING ALL
SERVICE, OR CLARIFICATION OF ACTIVITY REGARDING SAID UTILITY. THE CONTRACTOR SHALL EXERCISE CAUTION WHEN CROSSING AN
NOTIFYING THE VARIOUS UTILITY COMPANIES TO MAKE THE NECESSARY ARRANGEMENTS FOR ANY RELOCATION, TEMPORARY DISRUPTION OF
THE CONTRACTOR SHALL BE RESPONSIBLE FOR LOCATING AND VERIFYING ALL EXISTING UTILITIES PRIOR TO CONSTRUCTION, AND FOR
BEGINNING ANY CONSTRUCTION.
IT SHALL BE THE RESPONSIBILITY OF THE DEVELOPER/CONTRACTOR TO ENSURE THAT ALL REQUIRED PERMITS ARE IN-HAND BEFORE
Certificate of Authorization No. 7074
PE No. 70585
David K. Ledgerwood, PE p 407.971.8850
Oviedo, Florida 32765
3000 Dovera Drive, Suite 200
WATER
WATER
W A
T E
R
WATER
WATER
W A
T E
R
W A
T E
R
WATER
W A
T E
R
W A
T E
R
W A
T E
R
W A
T E
R
W A
T E
R
W A
T E
R
W A
T E
R
W A
T E
R
WATER
W A
T E
R
W A
T E
R
W A
T E
R
WATER
W A
T E
R
W A
T E
R
WATER
W A
T E
R
WATER
WATER
WATER
W A
T E
R
WATER
W A
T E
R
W A
T E
R
W A
T E
R
WATER
WATER
WATER
W A
T E
R
W A
T E
R
WATERWATER
W A
T E
R
WATER
WATER
W A
T E
R
W A
T E
R
W A
T E
R
W A
T E
R
WATER
W A
T E
R
W A
T E
R
WATER
W A
T E
R
W A
T E
R
W A
T E
R
WATER
WATER
W A
T E
R
W A
T E
R
WATER
145 150 155 160 165 170 175 180
100 105 110
120 125 130 135 140 145
OUC
The OneReliable
1/30/2020 10:23:22 AM F:\Projects\ORC-010-01\North\utils\Utility Design\PLAYUW01.DGN
U-3
PROJECT LAYOUT
BY DESCRIPTIONDATE BY DESCRIPTIONDATE
REVISIONS
U-5 U-6
U-7 U-8 U-9 U-10 U-11 U-12 U-13
U-14
U-15
TEXAS AVENUE
TEXAS AVENUE
A M
E R
IC
A
B
V D
N
0 75 300
Feet
O
K
ID
G
A D
W A
K U
L
W
Y
P
IN
E W
Y
IV
E
R O
V D
B L
O S
S
M
R
D U S
IN
V
E
R
IV
E R
T R
C
IR
M Y
A K
IV
E
C
IT
R
V D
T R
A Z
V D
H O
N O
A D
N
0 75 300
Feet
Certificate of Authorization No. 7074
PE No. 70585
David K. Ledgerwood, PE p 407.971.8850
Oviedo, Florida 32765
3000 Dovera Drive, Suite 200
STA. 133+84.45
BEGIN UTILITY PROJECT
STA. 181+40.00
END UTILITY PROJECT
OUC
The OneReliable
1/30/2020 10:23:27 AM F:\Projects\ORC-010-01\North\utils\Utility Design\SUMQUW01.DGN
U-4
SUMMARY OF QUANTITIES
BY DESCRIPTIONDATE BY DESCRIPTIONDATE
REVISIONS
Certificate of Authorization No. 7074
PE No. 70585
David K. Ledgerwood, PE p 407.971.8850
Oviedo, Florida 32765
3000 Dovera Drive, Suite 200
TABULATION OF QUANTITIES
DESCRIPTION UNIT
SHEET NUMBERS
TOTAL GRAND REF.
PAY ITEM THIS TOTAL SHEET
NO. U-5 U-6 U-7 U-8 U-9 U-10 U-11 U-12 U-13 U-14 U-15 SHEET
PLAN FINAL PLAN FINAL PLAN FINAL PLAN FINAL PLAN FINAL PLAN FINAL PLAN FINAL PLAN FINAL PLAN FINAL PLAN FINAL PLAN FINAL PLAN FINAL PLAN FINAL
425-6 ADJUST EXISTING VALVE BOX EA 1 1 4 3 3 1 3 3 3 22 22
1050-11-222 4-INCH PVC WATER MAIN LF 73 40 113 113
1050-11-423 6-INCH DIP WATER MAIN LF 67 81 65 64 73 350 350
1050-11-424 8-INCH DIP WATER MAIN LF 210 413 40 80 743 743
1050-11-425 12-INCH DIP WATER MAIN LF 40 40 40 120 120
1050-16-002 REMOVAL OF 2-INCH OR LESS WATER MAIN LF 27 27 27
1050-16-003 REMOVAL OF 4-INCH WATER MAIN LF 500 134 35 669 669
1050-16-004 REMOVAL OF 6-INCH WATER MAIN LF 5 10 5 5 10 10 5 5 55 55
1050-16-005 REMOVAL OF 8-INCH WATER MAIN LF 212 420 35 70 737 737
1050-16-006 REMOVAL OF 12-INCH WATER MAIN LF 35 35 35 105 105
1055-11-412 4-INCH 45 DEGREE BEND EA 4 4 4
1055-11-414 8-INCH 45 DEGREE BEND EA 2 6 4 8 20 20
1055-11-415 8-INCH 90 DEGREE BEND EA 1 1 1
1055-11-416 12-INCH 45 DEGREE BEND EA 4 4 4 12 12
1055-11-424 8-INCH X 6-INCH TEE EA 1 1 1
1055-11-442 4-INCH SOLID SLEEVE EA 2 2 2
1055-11-444 8-INCH SOLID SLEEVE EA 2 2 2 4 10 10
1055-11-445 12-INCH SOLID SLEEVE EA 2 2 2 6 6
1055-11-452 4-INCH MJ PLUG EA 1 1 1
1055-11-453 8-INCH MJ PLUG EA 1 1 1
1055-11-454 6-INCH CAP EA 2 2 2
1080-11-201 SHORT SINGLE WATER SERVICE EA 6 6 6
1080-11-203 LONG SINGLE WATER SERVICE EA 2 2 2
1080-11-303 8-INCH X 4-INCH TAPPING SLEEVE EA 1 1 1
1080-11-304 8-INCH X 6-INCH TAPPING SLEEVE EA 2 2 2
1080-11-305 6-INCH GATE VALVE EA 1 1 1
1080-11-306 4-INCH TAPPING VALVE EA 1 1 1
1080-11-307 6-INCH TAPPING VALVE EA 2 1 3 3
1080-11-403 12-INCH X 6-INCH TAPPING SLEEVE EA 1 1 1
1080-11-404 8-INCH GATE VALVE EA 2 1 3 3
1080-16-201 REMOVAL OF EXISTING WATER METER EA 2 6 8 8
1644-113-08 FIRE HYDRANT ASSEMBLY EA 1 2 1 1 2 2 1 1 11 11
1644-900 REMOVAL OF EXISTING FIRE HYDRANT EA 1 2 1 1 2 2 1 1 11 11
134+00 135+00 136+00 137+00 138+00 139+00
98 98
1" = 4' VERTICAL
1" = 40' HORIZONTAL
SCALE:
OUC
The OneReliable
1/30/2020 10:23:32 AM F:\Projects\ORC-010-01\North\utils\Utility Design\PLPRUW07.dgn
U-5
PLAN & PROFILE
BY DESCRIPTIONDATE BY DESCRIPTIONDATE
REVISIONS
Certificate of Authorization No. 7074
PE No. 70585
David K. Ledgerwood, PE p 407.971.8850
Oviedo, Florida 32765
3000 Dovera Drive, Suite 200
.9
.6
SAN
WATER
SS
ELEC
SAN
SAN
TOP = 94.87'
SANITARY MANHOLE
TOP = 94.54'
SANITARY MANHOLE
TOP = 96.12'
SANITARY MANHOLE
S A
N
S A
N
S A
N
WATER
SHW
.9
134 P R
C
S
T A
.6
135 136 137 138
PT STA. 138+76.66
N
0 10 40
Feet
EXISTING R/W LINE
EXISTING EASEMENT
TEXAS AVENUE
PROPOSED SIGNAL POLE
PROPOSED R/W LINE
EXISTING R/W LINE
S-134
S-133
0-111
TO REMAIN
EXISTING 8" DIP WM
BOX TO FINISHED GRADE
ADJUST EXISTING 8" VALVE
PER RESTRAINT JOINT TABLE
RESTRAIN EXISTING 8" WM
TO BE REMOVED
EXISTING 8" DIP WM PROPOSED R/W LINE
EXISTING R/W LINE 6" DIP WM
67 LF OF PROPOSED
1-6" GATE VALVE
1-8"x6" TEE
STA. 134+47, 26' LT
PROPOSED R/W LINE
1-FIRE HYDRANT ASSEM.
STA. 134+44, 42' RT
EXISTING R/W LINE
POLE
PROPOSED SIGNAL
TO BE REMOVED
EXISTING FIRE HYDRANT
210 LF OF PROPOSED 8" DIP WM
1 BACTERIOLOGICAL SAMPLE POINT
1-8" SOLID SLEEVE
STA. 134+06, 29' LT
1 BACTERIOLOGICAL SAMPLE POINT
1-8" SOLID SLEEVE
2-8" 45° VERT. BENDS
8" DIP WATER MAIN:
CONNECT TO EXISTING
STA. 136+18, 23' LT
1-8" MJ PLUG
2-8" GATE VALVES
1-8" TEE
STA. 134+06, 28' LT
SHWSHW
EXISTING GROUND
PROFILE GRADE LINE
PROPOSED FIRE HYDRANT
PROPOSED 8" DIP WM
18" MIN.
TO BE REMOVED
EXISTING 8" DIP WM
TO REMAIN
EXISTING 8" DIP WM
PROPOSED 8" DIP WM
TO BE REMOVED
EXISTING 8" DIP WM
PROPOSED 6" DIP WM
140+00 141+00 142+00 143+00 144+00
1" = 4' VERTICAL
1" = 40' HORIZONTAL
SCALE:82 82
80 80
OUC
The OneReliable
1/30/2020 10:23:35 AM F:\Projects\ORC-010-01\North\utils\Utility Design\PLPRUW08.dgn
U-6
BY DESCRIPTIONDATE BY DESCRIPTIONDATE
REVISIONS
Certificate of Authorization No. 7074
PE No. 70585
David K. Ledgerwood, PE p 407.971.8850
Oviedo, Florida 32765
3000 Dovera Drive, Suite 200
.6
.5
.2
9 9 .2
18" RCP
18" RCP
FL 89.30
FL 88.30
FL 88.60
S-136
S-138
S-140
18" PIPE
18" RCP
FL 81.21
(-) 0.600%
(+) 0.300%
18" RCP
FL 86.00
FL 88.10
FL 88.30
24" RCP
DOUBLE 72" RCP
S-140C
S-140D
30" RCP
FL 87.60
FL 87.00
FL 86.70
30" RCP
S-140B
FL 89.30
18" PIPE
@ { OF CONST.
EXISTING GROUND LINE
PROFILE GRADE LINE
ELEC
SS
SSSS
SS
SAN
WATERWATER
WATER
TOP = 94.41'
SANITARY MANHOLE
S S
S A
N
S A
N
W A
T E
R
W A
T E
R
P I
.0
E L
.4
(-) 0.600% (+) 0.300%
135' V.C.
.5
.9
.5
.6
.8
.7
.6
.6
.6
.6
.6
SHW
140 141 142 143 144
N
0 10 40
Feet
EXISTING EASEMENT
R
IV
E R
T R
IR
TEXAS AVENUE
PROPOSED R/W LINE
EXISTING R/W LINE
EXISTING R/W LINE
S-135
S-136
S-138
S-137
S-140
S-139
CD-2
S-140A
CD-2A
S-140B
TO REMAIN
EXISTING 2" WM
EXISTING R/W LINE
TO BE REMOVED
EXISTING 8" DIP WM
TO REMAIN
EXISTING 8" DIP WM
PER RESTRAINT JOINT TABLE
RESTRAIN EXISTING 8" WM
TO REMAIN
EXISTING WATER SERVICE
TO REMAIN
EXISTING 2" VALVE
2-8" 45° BENDS
STA. 143+63, 22' LT
PROPOSED R/W LINE6" GATE VALVE:
CONNECT TO EXISTING
STA. 139+21, 20' LT
EXISTING R/W LINE
1-FIRE HYDRANT ASSEM.
STA. 139+21, 44' RT
TO BE REMOVED
EXISTING FIRE HYDRANT
BOX TO FINISHED GRADE
ADJUST EXISTING 6" VALVE
62 LF OF PROPOSED 6" DIP WM
TO REMAIN
EXISTING 8" DIP WM
JOINT TABLE
8" WM PER RESTRAINT
RESTRAINT EXISTING
TO BE REMOVED
EXISTING FIRE HYDRANT
OF DRAINAGE PIPES
DURING INSTALLATION
TO BE SUPPORTED
NEW WATER MAIN
19 LF OF PROPOSED 6" DIP WM
1 BACTERIOLOGICAL SAMPLE POINT
VERT. BENDS2-8" 45°
1-8" SOLID SLEEVE
8" DIP WATER MAIN:
CONNECT TO EXISTING
STA. 140+30, 18' LT
1-8" BACTERIOLOGICAL SAMPLE POINT
1-8" SOLID SLEEVE
1-8" GATE VALVE
8" WATER MAIN:
CONNECT TO EXISTING
STA. 144+46, 19' LT
406 LF OF PROPOSED 8" DIP WM
1- 6" GATE VALVE
1-FIRE HYDRANT ASSEMBLY
STA. 144+29, 21' LT
SHWSHW
EXISTING GROUND
PROFILE GRADE LINE
PROPOSED FIRE HYDRANT
TO REMAIN
EXISTING 8" DIP WM
PROPOSED 8" DIP WM
PROPOSED FIRE HYDRANT
18" MIN.
TO BE REMOVED
EXISTING 8" DIP WM
TO REMAIN
149+00 150+00148+00147+00146+00145+00
1" = 4' VERTICAL
1" = 40' HORIZONTAL
SCALE:
OUC
The OneReliable
1/30/2020 10:23:37 AM F:\Projects\ORC-010-01\North\utils\Utility Design\PLPRUW09.dgn
U-7
BY DESCRIPTIONDATE BY DESCRIPTIONDATE
REVISIONS
Certificate of Authorization No. 7074
PE No. 70585
David K. Ledgerwood, PE p 407.971.8850
Oviedo, Florida 32765
3000 Dovera Drive, Suite 200
.5
.8
.5
@ { OF CONST.
EXISTING GROUND LINE
.2
24" RCP
24" RCP 24" RCP
FL 88.50
S-144 S-146
(+) 0.800%S-143
24" RCP
FL 88.30
FL 88.10
S-141
FL 88.00
24" RCP
SS
SS
WATER
WATER
WATER
WATER
W A
T E
R
T
P
.3
S A
N
IT
A
N H
O L E
W A
T E
R
WATER
WATER
W A
T E
R
W A
T E
R
W A
T E
R
P I
.8
E L
.4
(+) 0.300% (-) 0.300%
P I
.8
E L
.6
(-) 0.300% (+) 0.800%
198' V.C.
.8
E
L
.9
.8
E
L
.4
.9
.8
.8
.8
.9
.9
.0
.1
.2
.4
145 146 147 148 149 150
N
0 10 40
Feet
EXISTING R/W LINE
EXISTING R/W LINE
EXISTING R/W LINE
M Y
A K
IV
E
TEXAS AVENUE
EXISTING EASEMENT
TO REMAIN
EXISTING 8" DIP WM
TO BE RELOCATED
EXISTING 8"x2" DRM
PROPOSED R/W LINE
EXISTING EASEMENT
EXISTING R/W LINE
PROPOSED R/W LINE
TO BE REMOVED
EXISTING FIRE HYDRANT
S-141
S-142
S-144
S-143
S-145
S-146
TO REMAIN
EXISTING 8" DIP WM
TO BE REMOVED
EXISTING 8" DIP WM
TO REMAIN
EXISTING 8" DIP WM
TO REMAIN
EXISTING WATER SERVICE
BOXES TO FINISHED GRADE
ADJUST EXISTING 8" VALVE
TO REMAIN
EXISTING 8" DIP WM
TO REMAIN
EXISTING 16" CASING
TO REMAIN
EXISTING 8" DIP WM
1-8"x2" DRM
STA. 147+85, 50' LT
BOX TO FINISHED GRADE
ADJUST EXISTING 6" VALVE
PER RESTRAINT JOINT TABLE
RESTRAIN EXISTING 8" WM
PER RESTRAINT JOINT TABLE
RESTRAIN EXISTING 8" WM
TO REMAIN
EXISTING 8" VALVE
TO REMAIN
EXISTING FIRE HYDRANT
PROPOSED R/W LINE
TEMPORARY EASEMENT
8" DIP WM
35 LF OF PROPOSED
TO BE REMOVED
EXISTING 1" COPPER SERVICE
1-1" WATER SERVICE
STA. 145+38, 47' LT
1-FIRE HYDRANT ASSEMBLY
STA. 149+19, 44' RT
6" GATE VALVE:
CONNECT TO EXISTING
STA. 149+19, 22' LT
6" DIP WM
65 LF OF PROPOSED
1 BACTERIOLOGICAL SAMPLE POINT
2-8" 45° VERT. BENDS
1-8" SOLID SLEEVE
8" DIP WATER MAIN:
CONNECT TO EXISTING
STA. 147+43, 19' LT
2-8" 45° VERT. BENDS
1-8" SOLID SLEEVE
8" DIP WATER MAIN:
CONNECT TO EXISTING
STA. 147+78, 19' LT
SHW
GWT
P I
.8
E L
.4
SHW
GWT
SHW
GWT
EXISTING GROUNDPROFILE GRADE LINE
PROPOSED WATER SERVICE
PROPOSED WATER SERVICE
PROPOSED FIRE HYDRANT
PROPOSED 8" DIP WM
18" MIN.TO REMAIN
EXISTING 8" DIP WM
TO BE REMOVED
EXISTING 8" DIP WM TO REMAIN
151+00 152+00 153+00 154+00 155+00 156+00
98 98
1" = 4' VERTICAL
1" = 40' HORIZONTAL
SCALE:
OUC
The OneReliable
1/30/2020 10:23:39 AM F:\Projects\ORC-010-01\North\utils\Utility Design\PLPRUW10.dgn
U-8
BY DESCRIPTIONDATE BY DESCRIPTIONDATE
REVISIONS
Certificate of Authorization No. 7074
PE No. 70585
David K. Ledgerwood, PE p 407.971.8850
Oviedo, Florida 32765
3000 Dovera Drive, Suite 200
.8
.8
.5
.3
@ { OF CONST.
EXISTING GROUND LINE
24" RCP
24" RCP
FL 90.00
FL 92.70
FL 91.60
S-148
S-150
18" RCP
18" RCP
FL 89.00
24" RCP
S-148A
FL 89.50
24" RCP
(+) 0.800%
(+) 0.300%
SAN SAN
WATER
W A
T E
R
TOP = 95.10'
SANITARY MANHOLE
TOP = 96.59'
SANITARY MANHOLES
A
N
S A
N
W A
T E
R
WATER
W A
T E
R
P I
.0
E L
.2
(+) 0.800% (+) 0.300%
151 152 153 154 155 156
N
0 10 40
Feet
EXISTING EASEMENT
EXISTING R/W LINE
EXISTING EASEMENT
PROPOSED R/W LINE
T R
A Z
V D
C
IT
R
V D
TEXAS AVENUE
EXISTING EASEMENT
EXISTING R/W LINE
EXISTING R/W LINE
EXISTING R/W LINE
S-148
S-147
S-148A
S-150
S-149
TO REMAIN
EXISTING 8" DIP WM
TO BE REMOVED
EXISTING 8" DIP WM
TO REMAIN
EXISTING 8" DIP WM
TO BE REMOVED
EXISTING 8" DIP WM
TO BE REMOVED
EXISTING 4" PVC WM
TO REMAIN
EXISTING 8" DIP WM
TO REMAIN
EXISTING 16" CASING
FINISHED GRADE
VALVE BOX TO
ADJUST EXISTING 8"
1-4" MJ PLUG
TO BE CLOSED:
EXISTING 4" VALVE
STA. 151+01, 28' RT
BOX TO FINISHED GRADE
ADJUST EXISTING 6" VALVE
PER RESTRAINT JOINT TABLE
RESTRAIN EXISTING 8" WM
PER RESTRAINT JOINT TABLE
RESTRAIN EXISTING 8" WM
PER RESTRAINT JOINT TABLE
RESTRAIN EXISTING 8" WM
TO BE REMOVED
EXISTING FIRE HYDRANT
PER RESTRAINT JOINT TABLE
RESTRAIN EXISTING 8" WM
PROPOSED R/W LINE
BOX TO FINISHED GRADE
ADJUST EXISTING 4" VALVE
TEMPORARY EASEMENT
35 LF OF PROPOSED 8" DIP WM
35 LF OF PROPOSED 8" DIP WM
6" GATE VALVE:
CONNECT TO EXISTING
STA. 154+19, 21' LT
1-FIRE HYDRANT ASSEMBLY
STA. 154+19, 44' RT
6" DIP WM
64 LF OF PROPOSED
2-8" 45° VERT. BENDS
1-8" SOLID SLEEVE
8" DIP WATER MAIN:
CONNECT TO EXISTING
STA. 151+83, 18' LT
1 BACTERIOLOGICAL SAMPLE POINT
2-8" 45° VERT. BENDS
1-8" SOLID SLEEVE
8" DIP WATER MAIN:
CONNECT TO EXISTING
STA. 152+18, 18' LT
1 BACT. SAMPLE POINT
2-8" 45° VERT. BENDS
1-8" SOLID SLEEVE
8" DIP WATER MAIN:
CONNECT TO EXISTING
STA. 154+83, 20' LT
2-8" 45° VERT. BENDS
1-8" SOLID SLEEVE
8" DIP WATER MAIN:
CONNECT TO EXISTING
STA. 155+18, 19' LT
SHW
GWT
SHW
GWT
SHW
GWT
PROFILE GRADE LINE
PROPOSED 8" DIP WM
PROPOSED 8" DIP WM
18" MIN.
18" MIN.
TO REMAIN
EXISTING 8" DIP WM TO BE REMOVED
EXISTING 8" DIP WM TO REMAIN
EXISTING 8" DIP WM
TO REMAIN
EXISTING 8" DIP WM
TO BE REMOVED
EXISTING 8" DIP WM
EXISTING GROUND
PROPOSED FIRE HYDRANT
156+00 157+00 158+00 159+00 160+00 161+00
1" = 4' VERTICAL
1" = 40' HORIZONTAL
SCALE:
OUC
The OneReliable
1/30/2020 10:23:40 AM F:\Projects\ORC-010-01\North\utils\Utility Design\PLPRUW11.dgn
U-9
BY DESCRIPTIONDATE BY DESCRIPTIONDATE
REVISIONS
Certificate of Authorization No. 7074
PE No. 70585
David K. Ledgerwood, PE p 407.971.8850
Oviedo, Florida 32765
3000 Dovera Drive, Suite 200
PROFILE GRADE LINE
.8
.3
.9
@ { OF CONST.
EXISTING GROUND LINE
.9
24" RCP
FL 90.40
FL 90.70
FL 90.90
FL 93.50
S-151 S-152 S-154
S-200
24" RCP
24" RCP
24" RCP
{ CONST. TEXAS AVENUE
STA. 159+82.20
} SURVEY AMERICANA BLVD. =
STA. 1013+26.04
(+) 0.300%
(-) 0.300%
18" RCP
ELEC
SAN
ELEC
SAN
TEL
WATER
WATER
ELEC
TOP = 98.31'
SANITARY MANHOLE
TOP = 97.87'
SANITARY MANHOLE
SS
WATERWATER
WATERWATERWATERWATER
V
V
V
V
S A
N
S A
N
WATER
W A
T E
R
W A
T E
R
WATER
WATER
P I
.0
E L
.4
(+) 0.300% (-) 0.300%
SHW
GWT
156 157 158 159 160 161
SHW
GWT
N
0 10 40
Feet
EXISTING R/W LINE
EXISTING R/W LINE
A M
E R
IC
A
V D
{ CONST. TEXAS AVENUE
STA. 159+82.20
} SURVEY AMERICANA BLVD.=
STA. 1013+26.04
PROPOSED SIGNAL POLE
PROPOSED SIGNAL POLE
PROPOSED SIGNAL POLE
TEXAS AVENUE
TO REMAIN
EXISTING 16" DIP WM
PROPOSED R/W LINE
TO BE REMOVED
EXISTING FIRE HYDRANT
EXISTING R/W LINE
PROPOSED R/W LINE
PROPOSED SIGNAL POLE
S-151
S-152
S-154
S-153
S-155
0-200
S-200
S-200A
PROPOSED R/W LINE
TO BE REMOVED
EXISTING 4" PVC WM
TO REMAIN
EXISTING 8" DIP WM TO REMAIN
EXISTING 12" DIP WM
BOX TO FINISHED GRADE
ADJUST EXISTING 8" VALVE
FINISHED GRADE
8" VALVE BOX TO
ADJUST EXISTING
FINISHED GRADE
12" VALVE BOX TO
ADJUST EXISTING
TO BE REMOVED
EXISTING 6" VALVE
1 BACTERIOLOGICAL SAMPLE POINT
1-4" TAPPING VALVE
1-8"x4" TAPPING SLEEVE
STA. 157+01, 19' LT
1 BACTERIOLOGICAL SAMPLE POINT
1-2" WATER SERVICE METER BANK
5-1" WATER SERVICE AND
STA. 157+02, 57' RT
TO BE CLOSED AND PLUGGED
EXISTING 6" GATE VALVE
1-FIRE HYDRANT ASSEMBLY
STA. 157+93, 56' RT
6" DIP WM
73 LF OF PROPOSED
TEMPORARY EASEMENT
TO BE REMOVED
EXISTING FIRE HYDRANT 1-6" TAPPING VALVE
1-8"x6" TAPPING SLEEVE
STA. 157+93, 20' LT
4" DIP WM
73 LF OF PROPOSED
TO REMAIN
EXISTING 8" DIP WM
TO REMAIN
EXISTING 8" DIP WM
TO BE REMOVED
AND 1-2" COPPER SERVICE
EXISTING 5-1" COPPER SERVICE
EXISTING R/W LINE
PROPOSED R/W LINE
OF DRAINAGE PIPES
DURING INSTALLATION
TO BE SUPPORTED
EXISTING WATER MAIN
1-FIRE HYDRANT ASSEMBLY
1-6" TAPPING VALVE
1-8"x6" TAPPING SLEEVE
STA. 159+07, 20' LT
SHW
GWT
PROPOSED FIRE HYDRANT
EXISTING GROUND
PROPOSED 4" PVC WM
12" MIN.
TO REMAIN
EXISTING 8" DIP WM
TO REMAIN
EXISTING 12" DIP WM
PROFILE GRADE LINE
PROPOSED FIRE HYDRANT
162+00 163+00 164+00 165+00 166+00 167+00
1" = 4' VERTICAL
1" = 40' HORIZONTAL
SCALE:
86 86
OUC
The OneReliable
1/30/2020 10:23:42 AM F:\Projects\ORC-010-01\North\utils\Utility Design\PLPRUW12.DGN
U-10
BY DESCRIPTIONDATE BY DESCRIPTIONDATE
REVISIONS
Certificate of Authorization No. 7074
PE No. 70585
David K. Ledgerwood, PE p 407.971.8850
Oviedo, Florida 32765
3000 Dovera Drive, Suite 200
.9
.7
@ { OF CONST.
EXISTING GROUND LINE
.9
.5
18" RCP
18" RCP
18" RCP 24" RCP
FL 93.30
S-202 S-203
S-204
S-206
S-207
29" x 45" ERCP
TEXAS AVENUE
STA. 165+59.10 CL. CONST.
STA. 400+00.00 { CONST. POND B5
FL 87.80
FL 90.60
FL 90.50
FL 90.30
FL 90.10
FL 89.80
(-) 0.300% (-) 0.300%
29"X45" ERCP
42" RCP
18" RCP
FL 91.60
SAN
WATER
TOP = 98.02'
SANITARY MANHOLE
ELEC
SS
SS
SAN
S S
E INV. = 85.01'
W INV. = 84.97'
S INV. = 84.92'
TOP = 97.79'
SANITARY MANHOLE
S A
N
S A
N
W A
T E
R
WATER
P I
.0
E L
.4
(-) 0.300% (+) 0.300%
P I
.6
E L
.2
(+) 0.300% (-) 0.300%
SHW
GWT
P C
S
T A . 16
.5
163 164 165 166 P
R C
S
T A . 16
.3
SHW
GWT
SHW
GWT
PROPOSED FIRE HYDRANT
EXISTING GROUND
PROFILE GRADE LINE
PROPOSED 12" DIP WM
18" MIN.
TO REMAIN
EXISTING 12" DIP WM
TO BE REMOVED
EXISTING 12" DIP WM
TO REMAIN
EXISTING 12" DIP WM
N
0 10 40
Feet
TO BE REMOVED
EXISTING FIRE HYDRANT
{ CONST. TEXAS AVENUE
STA. 165+59.10
STA. 400+00.00 POND D5TEXAS AVENUE
PROPOSED R/W LINE
EXISTING R/W LINE
EXISTING R/W LINE
PROPOSED R/W LINE
EXISTING R/W LINE
EXISTING R/W LINE
S-201
S-202
O-200A
0-201
S-203
S-204
S-206
S-205
0-202
S-207
S-207A
TO BE REMOVED
EXISTING FIRE HYDRANT
PROPOSED R/W LINE
TO BE REMOVED
EXISTING 12" DIP WM
TO REMAIN
EXISTING 12" DIP WM
1-FIRE HYDRANT ASSEMBLY
6" GATE VALVE:
CONNECT TO EXISTING
STA. 162+35, 54' RT
BOX TO FINISHED GRADE
ADJUST EXISTING 6" VALVE
TO REMAIN
EXISTING 6" DIP WM
PER RESTRAINT JOINT TABLE
RESTRAIN EXISTING 12" WM
JOINT TABLE
WM PER RESTRAINT
RESTRAIN EXISTING 12"
12" DIP WM
35 LF OF PROPOSED
1 BACTERIOLOGICAL SAMPLE POINT
2-12" 45° VERT. BENDS
1-12" SOLID SLEEVE
12" DIP WATER MAIN:
CONNECT TO EXISTING
STA. 165+56, 22' LT
2-12" 45° VERT. BENDS
1-12" SOLID SLEEVE
12" DIP WATER MAIN:
STA. 165+91, 23' LT
1-FIRE HYDRANT ASSEMBLY
1-6" TAPPING VALVE
1-12"x6" TAPPING SLEEVE
STA. 166+69, 24' LT
OF DRAINAGE PIPES
DURING INSTALLATION
TO BE SUPPORTED
EXISTING WATER MAIN
OF DRAINAGE PIPES
DURING INSTALLATION
TO BE SUPPORTED
EXISTING WATER MAIN
TO REMAIN
EXISTING 12" DIP WM
168+00 169+00 170+00 171+00 172+00
1" = 4' VERTICAL
1" = 40' HORIZONTAL
SCALE:
86 86
OUC
The OneReliable
1/30/2020 10:23:44 AM F:\Projects\ORC-010-01\North\utils\Utility Design\PLPRUW13.dgn
U-11
BY DESCRIPTIONDATE BY DESCRIPTIONDATE
REVISIONS
Certificate of Authorization No. 7074
PE No. 70585
David K. Ledgerwood, PE p 407.971.8850
Oviedo, Florida 32765
3000 Dovera Drive, Suite 200
.1
.7
.0
.5
36" RCP
36" RCP
FL 90.10
FL 90.40FL 92.60 FL 90.60
S-213
S-215 S-217
S-218
FL 88.00
(-) 0.300% (+) 0.300%
FL 89.90
36" RCP
29" x 45" ERCP
36" RCP
18" RCP
W A
T E
R
W A
T E
R
W A
T E
R
P I
.0
E L
.0
(-) 0.300% (+) 0.300%
SHW
GWT
168 169 170 P
A
.8
171 172
SHW
GWT
SHW
GWT
EXISTING GROUND
PROFILE GRADE LINE
PROPOSED 12" DIP WM
18" MIN.TO REMAIN
EXISTING 12" DIP WM
TO BE REMOVED
EXISTING 12" DIP WM
TO REMAIN
EXISTING 12" DIP WM
N
0 10 40
Feet
PROPOSED R/W LINE
EXISTING R/W LINE
EXISTING R/W LINE
PROPOSED R/W LINE
EXISTING R/W LINE
TEXAS AVENUE
EXISTING R/W LINE
PROPOSED R/W LINE
S-213
S-215
S-212 S-214
S-217
S-218
S-216TO REMAIN
EXISTING 12" DIP WM
TO REMAIN
EXISTING 12" DIP WM
TO BE REMOVED
EXISTING 12" DIP WM
TO REMAIN
EXISTING 12" DIP WM
TO BE REMOVED
EXISTING FIRE HYDRANT
BOX TO FINISHED GRADE
ADJUST EXISTING 6" VALVE
TO REMAIN
EXISTING FIRE HYDRANT
BOX TO FINISHED GRADE
ADJUST EXISTING 4" VALVE
TO REMAIN
EXISTING 4" DIP WM
BOX TO FINISHED GRADE
ADJUST EXISTING 6" VALVE
PER RESTRAINT JOINT TABLE
RESTRAIN EXISTING 12" WM
PER RESTRAINT JOINT TABLE
RESTRAIN EXISTING 12" WM
12" DIP WM
35 LF OF PROPOSED
1 BACTERIOLOGICAL SAMPLE POINT
2-12" 45° VERT. BENDS
1-12" SOLID SLEEVE
12" DIP WATER MAIN:
CONNECT TO EXISTING
STA. 169+33, 27' LT
2-12" 45° VERT. BENDS
1-12" SOLID SLEEVE
12" DIP WATER MAIN:
CONNECT TO EXISTING
STA. 169+68, 27' LT
1-FIRE HYDRANT ASSEMBLY
6" GATE VALVE:
STA. 172+79, 26' LT
173+00 174+00 175+00 176+00 177+00 178+00
1" = 4' VERTICAL
1" = 40' HORIZONTAL
SCALE:
OUC
The OneReliable
1/30/2020 10:23:46 AM F:\Projects\ORC-010-01\North\utils\Utility Design\PLPRUW14.dgn
U-12
BY DESCRIPTIONDATE BY DESCRIPTIONDATE
REVISIONS
Certificate of Authorization No. 7074
PE No. 70585
David K. Ledgerwood, PE p 407.971.8850
Oviedo, Florida 32765
3000 Dovera Drive, Suite 200
.1
.1
.0
@ { OF CONST.
EXISTING GROUND LINE
36" RCP
FL 91.80
S-219
S-221
.1
30" RCP
FL 92.30
FL 91.50
FL 91.00
24" RCP
ELEC
SAN
E L E
C
SS
E L E
C
TOP = 97.35'
SANITARY MANHOLE
SAN
W A
T E
R
W A
T E
R
WATER
W A
T E
R
S A
N S
A N
P I
.9
E L
.1
(+) 0.300% (-) 0.300%
P I
.0
E L
.8
(-) 0.300% (+) 0.300%
SHW
GWT
173 174 175 176 177 178
SHW
GWT
SHW
GWT
EXISTING GROUND
PROPOSED FIRE HYDRANT
PROPOSED 12" DIP WM
18" MIN.
18" MIN.
PROPOSED 4" PVC WM
PROFILE GRADE LINE
TO REMAIN
EXISTING 12" DIP WM
TO REMAIN
EXISTING 12" DIP WM
TO BE REMOVED
EXISTING 12" DIP WM
N
0 10 40
Feet
EXISTING R/W LINE
EXISTING R/W LINE
EXISTING EASEMENT
H O
N O
U R
R O
A D
TEXAS AVENUE
EXISTING EASEMENT
PROPOSED R/W LINE
EXISTING R/W LINE
S-220
S-221S-219 S-223
S-222
TO BE REMOVED
EXISTING 4" WM
TO REMAIN
EXISTING 12" DIP WM
TO BE REMOVED
EXISTING 12" DIP WM
TO REMAIN
EXISTING 12" DIP WM
BOX TO FINISHED GRADE
ADJUST EXISTING 12" VALVE
BOX TO FINISHED GRADE
ADJUST EXISTING 4" VALVE
BOX TO FINISHED GRADE
ADJUST EXISTING 12" VALVE
TO REMAIN
EXISTING 12" WATER MAIN
TO REMAIN
EXISTING 2" WATER MAIN
EXISTING R/W LINE
PER RESTRAINT JOINT TABLE
RESTRAIN EXISTING 4" WM
PER RESTRAINT JOINT TABLE
RESTRAIN EXISTING 4" WM
S-219A
PER RESTRAINT JOINT TABLE
RESTRAIN EXISTING 12" WM
PER RESTRAINT JOINT TABLE
RESTRAIN EXISTING 12" WM
4" DIP WM
35 LF OF PROPOSED
35 LF OF PROPOSED 12" DIP WM
2-4" 45° VERT. BENDS
1-4" SOLID SLEEVE
4" WATER MAIN:
CONNECT TO EXISTING
STA. 173+02, 59' RT
1 BACTERIOLOGICAL SAMPLE POINT
2-4" 45° VERT. BENDS
1-4" SOLID SLEEVE
4" WATER MAIN:
CONNECT TO EXISTING
STA. 173+02, 23' RT
1 BACTERIOLOGICAL SAMPLE POINT
2-12" 45° VERT. BENDS
1-12" SOLID SLEEVE
12" DIP WATER MAIN:
CONNECT TO EXISTING
STA. 177+13, 27' LT
2-12" 45° VERT. BENDS
1-12" SOLID SLEEVE
12" DIP WATER MAIN:
STA. 177+48, 27' LT
179+00 180+00 181+00 182+00 183+00 184+00
1" = 4' VERTICAL
1" = 40' HORIZONTAL
SCALE:
86 86
OUC
The OneReliable
1/30/2020 10:23:48 AM F:\Projects\ORC-010-01\North\utils\Utility Design\PLPRUW15.dgn
U-13
BY DESCRIPTIONDATE BY DESCRIPTIONDATE
REVISIONS
Certificate of Authorization No. 7074
PE No. 70585
David K. Ledgerwood, PE p 407.971.8850
Oviedo, Florida 32765
3000 Dovera Drive, Suite 200
.1
.0
.1
(+) 0.300%
(+) 0.300%
CONSTRUCTION PROJECT NUMBER 20-096.01
THE EXISTING PROFILE IS BASED ON
EL. 99.08
{ CONST. TEXAS AVENUE
STA. 181+40.00
RESURFACING
BEGIN MILLING AND
END PROJECT
{ CONST. TEXAS AVENUE
STA. 183+71.69
END CONSTRUCTION
RESURFACING
END MILLING AND
WATER
W A
T E
R
SS
S S
WATER
W A
T E
R
W A
T E
R
.0
.0
179 180 181 182 183 184
EXISTING GROUND
PROPOSED FIRE HYDRANT
PROFILE GRADE LINE
TO REMAIN
EXISTING 12" DIP WM TO REMAIN
EXISTING 12" DIP WM
WATER
WATER
N
0 10 40
Feet
{ CONST.
STA.181+40.00
END WIDENING
END MILLING AND RESURFACING
END PROJECT
TEXAS AVENUE
EXISTING R/W LINE
S-224
S-225
TO BE REMOVED
EXISTING FH
TO REMAIN
EXISTING 12" DIP WM
TO REMAIN
EXISTING 6" DIP WM
BOX TO FINISHED GRADE
ADJUST EXISTING 10" VALVE
EXISTING R/W LINE
TO REMAIN
EXISTING 10" WM
BOXES TO FINISHED GRADE
ADJUST EXISTING 6" VALVE
EXISTING R/W LINE
1-FIRE HYDRANT ASSEMBLY
6" GATE VALVE:
CONNECT TO EXISTING
STA. 179+93, 27' LT
SIDEWALK
METER AT THE BACK OF PROPOSED
EXTEND WATER SERVICE AND INSTALL
SIDEWALK
METER AT THE BACK OF PROPOSED
EXTEND WATER SERVICE AND INSTALL
1012+001011+001009+00 1010+001007+00 1008+0088
1" = 4' VERTICAL
1" = 40' HORIZONTAL
SCALE:
S
I
L I
J
U S
T M
E
E E
T
M A
T
I
OUC
The OneReliable
1/30/2020 10:23:51 AM F:\Projects\ORC-010-01\North\utils\Utility Design\PLPRUW17.dgn
U-14
BY DESCRIPTIONDATE BY DESCRIPTIONDATE
REVISIONS
Certificate of Authorization No. 7074
PE No. 70585
David K. Ledgerwood, PE p 407.971.8850
Oviedo, Florida 32765
3000 Dovera Drive, Suite 200
SAN
WATER
WATER
(+) 0.300%
PGL RT
EL 97.80
STA. 1012+40.00
END PGL RT
EL 96.18
STA. 1007+00.00
BEGIN PGL RT
.1
.7
GWT
SHW
GWT
SHW
SHW
GWT
SHW
GWT
@ EDGE OF PAVT. RT.
EXIST. GROUND
WATER
1007 1008 1009 1010 1011 1012
N 0 10 40
Feet
AMERICANA BLVD.
S-157
EXISTING R/W LINE
EXISTING R/W LINE
} SURVEY AMERICANA BOULEVARD
STA. 1007+00.00
BEGIN CONSTRUCTION
S-158
18" RCP
117 LF OF
18" RCP
232 LF OF
} SURVEY AMERICANA BOULEVARD
TO REMAIN
EXISTING FIRE HYDRANT
TO REMAIN
EXISTING 8" DIP WM
TO REMAIN
EXISTING 16" DIP WM
TO REMAIN
EXISTING 16" DIP WM
TO REMAIN
EXISTING 8" VALVE
VALVE TO REMAIN
EXISTING 16" BUTTERFLY
PROPOSED R/W LINE
EXISTING EASEMENT
S-157S-158
18" PIPE
FL 92.20
18" PIPE
FL 92.00 TO REMAIN
EXISTING 16" DIP WMTO REMAIN
EXISTING 16" DIP WM
1015+00 1016+00 1017+00 1018+00 1019+0088
.5
1" = 4' VERTICAL
1" = 40' HORIZONTAL
SCALE:
.8
S
I
L I
J
U S
T M
E
E E
T
M A
T
I
A
OUC
The OneReliable
1/30/2020 1:05:11 PM F:\Projects\ORC-010-01\North\utils\Utility Design\PLPRUW18.dgn
U-15
NO.
SHEET
PLAN & PROFILE
dledgerwood
BY DESCRIPTIONDATE BY DESCRIPTIONDATE
REVISIONS
Certificate of Authorization No. 7074
PE No. 70585
David K. Ledgerwood, PE p 407.971.8850
Oviedo, Florida 32765
3000 Dovera Drive, Suite 200
ELEC
WATER
WATER
GASGASGAS
10" PALM
10" PALM
10" PALM
S O
U T
H
S O
U T
H
GRASS MEDIAN
10 PARKING SPACES
1" METAL
1" METAL
1" METAL
2FT CONCRETE
2FT CONCRETE
BOLLARD
BOLLARD
BOLLARD
BOLLARD
S T
P
H T
STOP
DO NOT DIG
L E
F T
24" PALM
6"
6"
10" PALM
10" PALM
8"
8"8"
8"
18"
18"
18"
18" 18"
18" 18"
18"
6" OAK
GRASS MEDIAN
BOC
CURB INLET
CURB INLET
CURB INLET
10 PARKING SPACES
(DOUBLE YELLOW LANE LINES)
15 PARKING SPACES
(DOUBLE YELLOW LANE LINES)
14 PARKING SPACES
1'X2' METAL COLUMN 20' PLAZA SIGN
R
H T
W A
T E
R
P C
S
T A . 10
1.7
P I
.0
E L
.1
(-) 0.600% (-) 0.409%
(MATCH EXISTING)
EL 96.53
STA. 1016+39.29
END PGL RTEL 97.58
STA. 1014+20
BEGIN PGL RT
.8
.0
SHW
GWT
@ EDGE OF PAVT. RT.
EXIST. GROUND
} SURVEY AMERICANA BOULEVARD
N
0 10 40
Feet
AMERICANA BLVD. } AMERICANA BOULEVARD
STA. 1016+66.07
END CONSTRUCTION
EXISTING R/W LINE
EXISTING R/W LINE
EXISTING R/W LINE
EXISTING R/W LINE
TO REMAIN
EXISTING 16" DIP WM
TO REMAIN
EXISTING 8" DIP WM
TO REMAIN
EXISTING 8" VALVE
TO REMAIN
EXISTING FIRE HYDRANT
TO REMAIN
EXISTING 16" DIP WM
(-) 0.600% (-) 0.409%
(MATCH EXISTING)
EL 96.53
STA. 1016+39.29
END PGL RTEL 97.58
STA. 1014+20
BEGIN PGL RT
.8
.0
@ EDGE OF PAVT. RT.
EXIST. GROUND
T
IC
E
T
F
IC
IA
C O
E E
E
C T
R O
N
IC
F
N
A L
D
L E
1G
.0
F .A .C
OUC
The OneReliable
1/30/2020 10:24:01 AM F:\Projects\ORC-010-01\North\utils\Utility Design\UTDTUW01.DGN
U-16
STANDARD DETAILS
BY DESCRIPTIONDATE BY DESCRIPTIONDATE
REVISIONS
REQUIRED. CONTACT: OUC WATER CONSTRUCTION 407-649-4436.
FOR D.I. PIPE AND ANSI/AWWA C605 FOR PVC PIPE.
OF INSTALLATIONS. MOST CENTRAL FLORIDA UTILITY SUPPLY COMPANIES HAVE A COPY
AND IN NO WAY LIMITS OUC'S RIGHTS TO APPROVE OR DISAPPROVE PLANS, SPECIFICATIONS
GENERAL GUIDANCE IN THE PREPARATION OF CONSTRUCTION PLANS AND SPECIFICATIONS,
SPECIFICATION STANDARDS MANUAL. THE FOLLOWING INFORMATION IS TO PROVIDE
ADHERE TO THE REQUIREMENTS OUTLINED IN THE OUC WATER DISTRIBUTION'S
MATERIAL USED IN THE CONSTRUCTION OF THE WATER DISTRIBUTION SYSTEM SHALL
OF OUC'S SPECIFICATION STANDARDS MANUAL.
A PRE-CONSTRUCTION MEETING FOR THE INSTALLATION OF WATER FACILITIES IS
62-555 "PERMITTING AND CONSTRUCTION OF PUBLIC WATER SYSTEMS."
REQUIREMENTS OF THE DEPARTMENT OF ENVIRONMENTAL PROTECTION - CHAPTER
CROSS CONNECTION CONTROL SHALL BE IN ACCORDANCE WITH RULES AND
EXCEED THE REQUIREMENTS SET FORTH IN ANSI/AWWA STANDARDS C651.
CONSTRUCTION OF PUBLIC WATER SYSTEMS." THE PROCEDURE WILL MEET AND
DEPARTMENT OF ENVIRONMENTAL REGULATION - CHAPTER 62-555 "PERMITTING AND
THE DISINFECTION OF WATER MAINS SHALL BE IN COMPLIANCE WITH "RULES OF THE
ALL HYDROSTATIC TESTING SHALL BE IN ACCORDANCE WITH ANSI/AWWA C600
UTILITIES COMMISSION SPECIFICATIONS FOR MATERIAL, INSTALLATION, AND DISINFECTION.
ALL CONSTRUCTION OF THE WATER DISTRIBUTION SYSTEM SHALL MEET CURRENT ORLANDO
CONTRACT AND NO EXTRA COMPENSATION WILL BE ALLOWED.
ANY DELAY OR INCONVENIENCE OF THE VARIOUS UTILITIES SHALL BE INCIDENTAL TO THE
UNDERGROUND UTILITY, WHETHER SHOWN ON THESE PLANS OR FIELD LOCATED.
SAID UTILITY. THE CONTRACTOR SHALL EXERCISE CAUTION WHEN CROSSING AN
TEMPORARY DISRUPTION OF SERVICE, OR CLARIFICATION OF ACTIVITY REGARDING
UTILITY COMPANIES TO MAKE THE NECESSARY ARRANGEMENTS FOR ANY RELOCATION,
EXISTING UTILITIES PRIOR TO CONSTRUCTION, AND FOR NOTIFYING THE VARIOUS
THE CONTRACTOR SHALL BE RESPONSIBLE FOR LOCATING AND VERIFYING ALL
ALL REQUIRED PERMITS ARE IN-HAND BEFORE BEGINNING ANY CONSTRUCTION.
IT SHALL BE THE RESPONSIBILITY OF THE DEVELOPER/CONTRACTOR TO ENSURE THAT
A SERVICE MATERIAL FOR AND 1" SHALL INCLUDE SOFT ANNEALED TYPE-K
SPECIAL NOTICE: OUC SPECIFICATIONS OFTEN ADD TO THE MANUFACTURER'S
ANSI/AWWA STANDARD C509 OR LATEST REVISION. ALL VALVES 16" AND LARGER
WITH EPOXY COATING INTERNALLY/EXTERNALLY AND CONFORM TO
6. ALL VALVES 4" THROUGH 12" SHALL BE RESILIENT SEAT/WEDGE GATE VALVES
5. FIRE HYDRANTS SHALL BE TRAFFIC DRY BARREL TYPE AND MEET OUC SPECIFICATIONS.
PADLOCK WINGS MUST BE INCLUDED ON EACH CURB STOP OR BALL
FLANGE) WITH SLOTTED HOLES ON THE FLANGE FACE ARE REQUIRED.
ACCOMMODATE 1 1/2" OR 2" METERS, 2" BALL ANGLE METER VALVES (CTS X
INSTALLATION OF 2" SERVICES REQUIRE SERVICE CLAMPS AND TO
PIPE TAPPING ON DUCTILE IRON PIPE OR WITH SERVICE CLAMPS ON PVC PIPE.
THREADING IS REQUIRED ON ALL 1" CORPORATION STOPS USED WITH DIRECT
FLARED FITTINGS ARE ACCEPTABLE UNDER CONTROLLED CONDITIONS. AN AWWA (CC)
SHALL BE BRASS COMPRESSION FITTINGS IN ACCORDANCE W/AWWA C800.
SERVICE MATERIAL (CORP. STOPS, CURB STOPS, ETC.) FOR 1", AND 2" SERVICES
METER VALVE.
COPPER TUBING.
OUC WATER DISTRIBUTION STANDARDS AND SPECIFICATIONS
SPECIFICATIONS. IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
(407) 244-8786 OR VISIT OUR WEB SITE AT: http//www.ouc.com/vendor
GENERAL SPECIFICATIONS
GENERAL MATERIAL SPECIFICATIONS
SERVICE LINE DETAILS
WATER MAIN
CORPORATION STOP
COMPRESSION
TYPE "K" 1" COPPER TUBING
5/8" OR 1"
WATER METER
METER BOX
CURB STOP
COMPRESSION
TYPICAL 1" LONG SERVICE
TYPICAL 2" NEW LONG SERVICE
R
W
REDUCER
F L
O W
B
TEE
"A"
FITTING
SIZE-" TEE "A" REDUCER "B"
4 x 4
6 x 4
6 x 6
8 x 4
10 x 4
10 x 8
10 x 10
12 x 4
12 x 6
12 x 8
12 x 10
12 x 12
16 x 6
16 x 8
16 x 10
16 x 12
16 x 16
20 x 6
20 x 8
20 x 10
20 x 12
20 x 16
20 x 20
24 x 6
24 x 8
24 x 10
24 x 12
24 x 16
24 x 20
24 x 24
8 x 6
8 x 8
10 x 6
RESTRAINT FOR BEND
MINIMUM TOTAL LENGTH OF
FOR PLUG OR CAP
MINIMUM TOTAL LENGTH OF RESTRAINT
"C"
CAP
"C"
MINIMUM FOOTAGE OF PIPE TO BE RESTRAINED.
RESTRAINT "C" (LF)
FITTING
11-1/4"
22-1/2"
VALVE/PLUG/CAP
4" 6" 10" 12" 16" 20" 24" 30" 36"
3 4 4 5 5 6 7 9
6 8 9 11 11 13 15 18
12 16 19 22 22 26 31 36
29 38 46 53 53 64 74 88
61 80 96 113 112 136 159 191
8"
221'
101'
42'
20'
10'
NOTES:
1. ALL FITTINGS SHALL HAVE APPROPRIATE MECHANICAL THRUST RESTRAINT (WEDGE-
ACTION OR FULL CIRCUMFERENCE ARTICULTING WEDGE, EQUAL TO 1100
SERIES MEGALUG OR STAR-GRIP)
2. ALL COMPONENTS OF RESTRAINING MECHANISMS FOR PUSH-ON OR MECHANICAL
JOINTS SHALL BE OF CORROSION RESISTANT MATERIAL OR SUITABLY PROTECTED
AGAINST CORROSION.
3. THE PIPE LENGTHS IMMEDIATELY ON EITHER SIDE OF A FITTING SHALL BE ADEQUATELY
TIED TOGETHER USING PROPRIETARY LOCKING GASKETS SUCH AS FIELD LOC OR
FAST GRIP GASKETS.
4. INSTALL FULL LENGTH JOINTS WITH TOTAL LENGTH EQUAL TO OR GREATER THAN
SHOWN IN THE TABLE.
5. WHERE TWO OR MORE FITTINGS ARE TOGETHER, USE FITTING WHICH YIELDS GREATEST
LENGTH RESTRAINED PIPE. ALL ROAD CROSSINGS SHALL BE RESTRAINED AT EACH JOINT.
6. THROUGH RUN OF TEES OUTSIDE LIMITS OF RESTRAINED JOINTS FROM
OTHER FITTINGS NEED NOT BE RESTRAINED UNLESS OTHERWISE INDICATED.
7. LENGTHS SHOWN IN THE TABLE HAVE BEEN CALCULATED IN ACCORDANCE
WITH THE PROCEDURE OUTLINED IN "THRUST RESTRAINT DESIGN FOR
DUCTILE IRON PIPE" FOURTH EDITION 1997 AS PUBLISHED BY DIP,
THE MAXIMUM TEST PRESSURE IS 150 PI
THE LAYING CONDITION IS TYPE 2 (BACKFILL COMPACTED TO TOP OF PIPE)
DIP SILT #1
ALL BENDS ARE INSTALLED HORIZONTALLY
THE PIPE IS DUCTILE IRON PIPE
DEPTH OF COVER IS ASSUMED TO BE 3 FEET FOR 12" AND SMALLER WATER MAINS
DEPTH OF COVER IS ASSUMED TO BE 4 FEET FOR 16" AND LARGER WATER MAINS
NONE OF THE PIPE IS POLYWRAPPED.
2. ALL PIPE FITTINGS 4" UP TO 30" SHALL BE CEMENT OR EPOXY LINED (CLASS 350)
AWWA CI53 "COMPACT" DUCTILE IRON, WITH MECHANICAL JOINT ENDS. ALL PIPE FITTINGS
30" OR LARGER SHALL BE CEMENT LINED (CLASS 250) DUCTILE IRON, WITH MECHANICAL
RESTRAINED JOINT STANDARDS
CONTACT O.U.C. FOR SPECIAL RESTRAINT DETAILS FOR WORK ON EXISTING PIPING.
R
W
ADJUSTABLE VALVE BOX
(SEE VALVE SETTING DETAIL)
2" BALL ANGLE METER VALVE UNION (CTS x FLANGED)
TYPICAL 2" NEW SHORT SERVICE
1-1\2 OR 2" METER
COPPER SERVICE LINE
2" TYPE-K HARD
(CTS x CTS)
METER BOX
W/SLOTTED HOLES, PADLOCK WING
WATER MAIN
SERVICE
CLAMP
VALVE (FIPT x FIPT)
2" GATE SCREW
MAXIMUM ALLOWABLE LEAKAGE
PIPE SIZE
NOTE: 150 PSI TESTING, 2 HOUR LEAKAGE TESTS;
GALLONS
2"
4"
6"
8"
10"
12"
16"
20"
24"
30"
36"
42"
48"
0.42
0.72
1.10
1.48
1.84
2.20
2.94
3.68
4.42
5.52
6.62
7.73
8.83
MAXIMUM LEAKAGE ALLOWED PER 1000 LF OF PIPE.
FINISH GRADE
WATER MAIN
2" GATE VALVE W/BOX
2" BRASS NIPPLE 2" (SCH 80) PVC
(FIPT x SLIP JOINT)
RESTRAINED JOINT
COUPLING
2" RESTRAINED JOINT (SDR 17/CLASS 250
2" (SCH 80) PVC
SLIP JOINT ELL-GLUED
SLIP JOINT ELL-GLUED
2" (SCH 80) PVC
R
W
2" (SCH 80)
2" BALL METER VALVE
W/SLOTTED HOLES,
2" (SCH 80) PVC
METER BOX
SERVICE CLAMP
ADJUSTABLE VALVE BOX
(SEE VALVE SETTING DETAIL)
DIRECT TAP
SERVICE CLAMP
PIPE
* ABSTESTOS CEMENT, STEEL,
GALVANIZED IRON PIPE, PVC, ETC.
DT DIRECT TAP MAY BE ALLOWED
SC SERVICE CLAMP IS REQUIRED
NA NOT ALLOWED
LEGEND
ALL REQUIRE A SERVICE SADDLE.
TAPPING FOR 1" CORP. STOP, & 2" GATE VALVE
WATER MAIN
1" TYPE "K"
COPPER TUBING
DUCTILE IRON WATER MAIN
SERVICE CLAMP
SERVICE CLAMP
PVC WATER MAIN
SIZE CORPORATION TAP SIZE
D.I.
PVC
12"
10"
8"
6"
4"
4" C-900
2"-SDR21
1" 2"
DT
DT
DT
DT
DT
SC
NA
PVC PIPE (IPS O.D.)
3.
B SERVICE MATERIAL FOR 2" SHORT SIDE SERVICES SHALL INCLUDE 2" CTS TYPE-K
C SERVICE MATERIAL FOR 2" LONG SIDE SERVICES SHALL INCLUDE 2" RESTRAINED
JOINT (SDR 17/CLASS 250) PVC PIPE (IPS-O.D.).
PER TWO (2) HOUR
HARD COPPER PIPE.
COUPLING-GLUED
PVC PIPE STUB
PADLOCK WINGS
3. METER SHOULD BE ON THE CUSTOMER SIDE OF THE RIGHT-OF-WAY
NO FURTHER THAN 2' BEYOND RIGHT-OF-WAY LINE AND ALWAYS
ALONG THE BACK SIDE OF CONC. SIDEWALK.
R
W
FINISH GRADE
FINISH GRADE
CONC. S/W
MEGALUGS
MEGALUG
MEGALUGS
PIPE
D.I.
1. O.U.C. SHALL FURNISH/INSTALL ALL WATER METERS.
2. O.U.C. SHALL FURNISH METER BOXES, DEVELOPER'S CONTRACTOR TO INSTALL.
2' (MAX)
CUT "W"
ON CURB
2' (MAX)
ON CURB
CUT "W"
CUT "W" ON CURB
2' (MAX)
SC
SC
D.I. PIPE RESTRAINT - (LF)
MEGALUGS
M
IN
IM
U M
TO
TA
L
L E N
TH
R E S
TR
A
IN
T F O R
B E N
D
"C
16 x 4 14 104
20 x 4 8 129
4.
1-1\2 OR 2" METER
MINIMUM FOOTAGE OF PIPE TO BE RESTRAINED.
1.
THE TYPICAL O.U.C. DISTRIBUTION SYSTEM PIPE SIZES AND MATERIAL USED ARE:
TWO INCH (2") WATER MAINS SHALL BE ASTM 2241 CLASS 200 SDR21 POLYVINYL
CHLORIDE (PVC) PIPE.
FOUR INCH (4") WATER MAINS SHALL BE EITHER PRESSURE CLASS 350 DUCTILE
IRON (D.I.) IN ACCORDANCE WITH ANSI/AWWA CI50/A21.50-96 AND
SIX INCH (6") THROUGH TWENTY FOUR INCH (24") WATER MAINS SHALL BE
PRESSURE CLASS 350 D.I. PIPE IN ACCORDANCE WITH ANSI/AWWA
THIRTY INCH (30") AND LARGER WATER MAINS SHALL BE PRESSURE CLASS
250 D.I. PIPE IN ACCORDANCE WITH ANSI/AWWA C150/A21.50 AND
NOTE:
1. THE USE OF 2" AND/OR 4" PVC PIPE MUST BE APPROVED BY O.U.C.
WATER ENGINEERING.
2. PVC PIPE MUST BE BLUE IN COLOR OR HAVING CONTINUOUS BLUE MARKINGS
TO CONFORM TO AWWA COLORS WITH NSF LOGO FOR POTABLE WATER USE.
WITH THE FOLLOWING ASSUMPTIONS:
BLOW OFF DETAILS
ANSI/AWWA C151/A21.51 OR, AS CONDITIONS WARRANT, C900 SDR18
CLASS 150 PVC PIPE.
C150/A21.50 AND ANSI/AWWA C151/A21.51.
ANSI/AWWA C151/A21.51.
D.I.
PIPE VALVE
INLINE VALVE RESTRAINT
MINIMUM TOTAL LENGTH OF RESTRAINT
FOR PLUG OR CAP
"C"
(TREAT AS PLUG OR CAP IN BOTH DIRECTIONS)
M.J. x M.J.
TOP ACCESS (FOR TESTING AND MAINTENANCE), INSTALLED, OWNED
CERTAIN THAT THE APPROPRIATE BACKFLOW DEVICE HAS BEEN INSTALLED ON THE
BE CONDUCTED BY A REPRESENTATIVE OF THE RECLAIM WATER PROVIDER TO MAKE
PRIOR TO ANY RECLAIM WATER SERVICE INSTALLATION, INSPECTION AND TESTING WILL
DOMESTIC WATER SERVICE.
DOUBLE CHECK VALVE ASSEMBLY BACKFLOW PREVENTER WITH
POTABLE WATER SYSTEM MUST BE PROTECTED BY AN APPROVED
WHERE RECLAIM WATER IS PROVIDED TO A PROPERTY, O.U.C.'S
HAVING RECLAIM WATER SERVICE.
SPECIAL NOTICE:
PROCEDURES FOR AN O.U.C. SINGLE FAMILY HOME
2 x 4 PAINTED BLUE ON TOP
SERVICE LINE/CURB STOP
TO SHOW LOCATION OF BURIED
A
36" (TYP.)
12" (TYP.)
BURIED WATER LINE
WARNING TAPE
CONTINUOUS BLUE INSULATED
10 GAUGE OR LARGER COPPER WIRE
(REFER TO GENERAL MATERIAL SPECIFICATIONS FOR LIMITATIONS ON USE)
PVC PIPE DETAIL
PVC PIPE
AND MAINTAINED BY OUC.
BACKFLOW PREVENTER.
NO CONNECTIONS ARE ALLOWED BETWEEN THE METER AND THE
2" BRASS
NIPPLE
2" STRAIGHT COUPLING
(COMP. x MIPT)
THE RECLAIMED WATER MAIN SHALL BE ON THE OPPOSITE SIDE OF THE STREET
FROM THE POTABLE WATER MAIN WHERE PRACTICAL. IF IT IS NOT PRACTICAL,
THE RECLAIMED WATER MAIN SHALL BE INSTALLED AT A MINIMUM HORIZONTAL
DISTANCE OF 3 FEET (EDGE TO EDGE) FROM THE POTABLE WATER MAIN.
RECLAIMED WATER MAINS SHALL BE BELOW POTABLE WATER MAINS WITH A
MINIMUM VERTICAL SEPARATION OF 12".
(SEE RESTRAINED JOINT STANDARDS)
RESTRAINT REQUIRED FOR INLINE VALVES
MEGALUGS
VALVE SETTING
SET WITHIN CURB
NO VALVE SHALL BE
NOTE:
FINISH GRADE
SET VALVE BOX PLUMB
CENTERED ON VALVE
(SLIDING TYPE ONLY)
ADJUSTABLE VALVE BOX
(CAST IRON TOP AND BOTTOM)
(5 1/4" SHAFT)
8. FOR PVC PIPE (4") MULTIPLY THE DUCTILE IRON FOOTAGE BY 1.1.
DUCTILE IRON PIPE
GALLONS
PER TWO (2) HOUR
PVC PIPE
N/A
0.65
0.38
DUCTILE IRON PIPE PVC PIPE
2"
REDUCER "B"
10 x 2
4 x 2
8 x 2
6 x 2
FITTING
SIZE-"
TEE "A"
2" PVC - PIPE RESTRAINT (LF)
2 x 2
USE LARGE
PIPE DEAD-
END/PLUG/
THE MINIMUM SEPARATION REQUIREMENTS FROM SANITARY FORCE MAINS,
AT LEAST A 6' HORIZONTAL AND AN 12" VERTICAL SEPARATION AT CROSSINGS,
MUST BE OBSERVED WITH NO STANDARD MITIGATION ALLOWED.
PROVISIONS ARE REQUIRED TO PROTECT EXISTING ACTIVE WATER MAINS FROM
BACKFLOW CONTAMINATION DURING FILLING, FLUSHING, TESTING, AND MAINTAINING
A PRESSURE IN THE NEW PIPING UNTIL A FDEP LETTER OF CLEARANCE IS
OBTAINED.
CAP FOOTAGE
BLOW-OFF SHALL BE
DIRECTED TO PROVIDE
(SEE VALVE SETTING DETAIL)
SIZE FOR SIZE OF THE NEWLY INSTALLED MAIN UP TO 12".
1. TEMPORARY BLOW-OFFS WILL BE INSTALLED
2. M.J. PLUG/CAP SHALL BE INSTALLED WHERE APPLICABLE.
M.J. GATE
MEGALUGS
TEMPORARY BLOW OFF (4" THROUGH 12") FOR CONSTRUCTION PURPOSE
MECHANICAL THRUST RESTRAINT
DUCTILE IRON WATER MAIN W/
NOTE:
ADJUSTABLE VALVE BOX
FINISH GRADE
VALVE
BEND
MEGALUGS
FLOW
D.I. PIPE STUB
MEGALUGS
PROPER DRAINAGE
NOTE:
BEND
D.I. PIPE
2" PVC DEAD END WITH PERMANENT BLOW OFF
4" PVC CAP
2" PVC MAIN
NOTE: ALL FITTINGS ARE SCHEDULE 80 PVC.
CONTINUOUS BLUE
CLASS 200 DR21
INSULATED 10 GAUGE
COPPER WIRE
GLUE LAST 3 JOINTS OR ALL IF SHORTER.
4" PVC STUB
2" GATE VALVE
NO GLUE
FINISH GRADE
WIRE FOR DIRECT
CONNECT LOCATING
2" FIPT x GLUE COUPLING
WITH 2" BRASS PLUG
2" PVC ELL-GLUED
2" SCH 80 PVC PIPE
METER BOX
PERMANENT BLOW OFF (4" AND LARGER)
2"
DUCTILE IRON WATER MAIN W/
MECHANICAL THRUST RESTRAINT
THIS IS A DEAD END BLOW-OFF,
NOT A "DISINFECTION/CHLORINATION" BLOW-OFF.
NOTE:
BRASS
MEGALUG
FINISH GRADE
4" PVC CAP
NO GLUE
4" PVC
2" GATE VALVE
2" PVC ELL-GLUED
M.J. CAP
METER BOX
2" SCH 80 PVC PIPE
ALL OUC WATER DISTRIBUTION SYSTEM PIPE SHALL HAVE A MINIMUM OF THIRTY-SIX
(36) INCHES OF COVER, UNLESS OTHERWISE DIRECTED BY THE OUC PROJECT ENGINEER
OR THEIR REPRESENTATIVE.
INSTALL ON ALL DEAD ENDS UNLESS OTHERWISE NOTED.
INSTALL ON ALL…