WWTP_Biosolids_Conveyor_FinalPlans_10Aug2021.pdf
PDF 10 MB Posted
- Attached to
- WWTP Biosolids Conveyor Replacement
- Solicitation number
- S-KN0010-00000471
- Issued by
- Klamath County, Neskowin CDP, Oregon
About this file
This document contains the drawings and specifications for the WWTP Biosolids Conveyor Replacement project in Newport, Oregon. The project involves replacing the existing biosolids belt conveyor with a new shaftless screw conveyor system, modifying the existing conveyor supports, and updating the SCADA and electrical systems. The project is being conducted by the City of Newport and Lincoln County. The drawings include site plans, demolition plans, mechanical plans and sections, structural details, and electrical one-line diagrams, legends, and wiring modifications.
The project requires the contractor to handle the demolition and disposal of the existing belt conveyor system. The new conveyor system includes a reversible, single-motor shaftless screw conveyor, a single-motor shaftless inclined screw conveyor, and a single-motor shaftless screw conveyor. The project has a completion date of December 31, 2022. The drawings indicate that the conveyors will be provided by the owner, and the contractor is responsible for the installation and integration of the new equipment with the existing SCADA and electrical systems.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CITY OF NEWPORT WWTP BIOSOLIDS
CONVEYOR REPLACEMENT PROJECT
VICINITY MAP
SCALE: 1"=5000'
19-2673.01
AUGUST 2021
NEWPORT
PROJECT
LOCATION
C U s e r s j u s t i n m o m a n D e s k t o p P r o j e c t
F o l d e r
S h o r t c u t s N e w p o r t C A D
S h e e t s O
R G d w g
G
P M
J U
S T I N
M
O M
A N s
L M
S
T e c h
ATTENTION: OREGON LAW REQUIRES THE CONTRACTOR TO FOLLOW THE RULES
ADOPTED BY THE OREGON UTILITY NOTIFICATION CENTER. THOSE RULES ARE SET
FORTH IN OAR 952-001-0010 THROUGH OAR 952-001-0090. THE CONTRACTOR MAY
OBTAIN COPIES OF THE RULES BY CALLING THE UTILITY NOTIFICATION CENTER.
(NOTE: THE TELEPHONE NUMBER FOR THE OREGON UTILITY NOTIFICATION CENTER IS
503-246-6699.)
888 SW 5TH AVENUE, SUITE 1170
PORTLAND, OREGON 97204
P 503.225.9010
SE 50TH ST
S
E
D
T
R
D
W
C
O
A
H
W
Y
INDEX OF DRAWINGS
GENERAL
1 G-1
TITLE, INDEX OF DRAWINGS AND VICINITY MAP
2 G-2
GENERAL NOTES, SYMBOLS, AND ABBREVIATIONS
CIVIL
3 C-1
CIVIL SITE, ACCESS, AND STAGING AREA PLAN
MECHANICAL
4 M-1 DEMOLITION PLAN
5 M-2 MECHANICAL PLAN
6 M-3 MECHANICAL SECTIONS
7 M-4 MECHANICAL DETAILS
STRUCTURAL
8 S-1 GENERAL STRUCTURAL NOTES AND ELEVATION
9 S-2 STRUCTURAL DETAILS
ELECTRICAL
10 E-1
ELECTRICAL LEGENDS, SYMBOLS, AND ABBREVIATIONS
11 E-2 ELECTRICAL PARTIAL BUILDING PLAN - DEMO
12 E-3 ELECTRICAL PARTIAL BUILDING PLAN
13 E-4 ELECTRICAL MCC ONE LINE AND ELEVATIONS
14 E-5 ELECTRICAL CONTROL DIAGRAMS
15 E-6 CONTROL PANEL MODIFICATIONS
16 E-7 CONTROL PANEL MODIFICATIONS & ELECTRICAL DETAILS
PROCESS AND INSTRUMENTATION CONTROL
17 P&ID-1
P&ID NOTES, SYMBOLS, LEGEND & ABBREVIATIONS
18 P&ID-2 P&ID BIOSOLIDS CONVEYANCE
DEFERRED SUBMITTAL LIST
ITEM: SPECIFICATION:
PREFABRICATED CROSSOVER STAIRS AND ANCHORAGE SEE SHEET M-4
PROJECT CONTACT LIST
ROLE: NAME: PHONE NUMBER:
WWTP SUPERVISOR ANDREW GRANT 541.574.3371
MURRAYSMITH PM JUSTIN MOMAN 503.225.9010
CONVEYOR MANUFACTURER DAVE MARTIN 206.624.7066
BUILDING OFFICIAL JOSEPH LEASE 541.574.0627
OWNERS CLARE PAUL 541.574.3370
CHRIS JANIGO 541.574.3376
DAVID POWELL 541.574.3369
12/31/2022RENEWS
NO. DATE BY REVISION
NOT TO SCALE
THEN DRAWING IS
NOT MEASURE 1"
IF THIS BAR DOES
NOTICE
CHECKED
DRAWN
DESIGNED
PROJECT NO.: SCALE: DATE:
C U s e r s j u s t i n m o m a n D e s k t o p P r o j e c t
F o l d e r
S h o r t c u t s N e w p o r t C A D
S h e e t s O
R G d w g
G
S T I N
M
O M s
L M
S
T e c h
SHEET
0 1
19-2673.01
G-2
AUGUST 2021
WWTP BIOSOLIDS
CONVEYOR
REPLACEMENT PROJECT
AS SHOWN
of 18
12/31/2022RENEWS
GENERAL NOTES, SYMBOLS,
AND ABBREVIATIONS
CAS
JSD
JSM
SHEET FROM
WHICH DETAIL
IS TAKEN *
SHEET WHERE
SECTION IS
SHOWN *
SECTION AND DETAIL DESIGNATIONS
SECTION DESIGNATIONS DETAIL DESIGNATIONS
2DETAIL
ASECTION
A
* NOTE: IF PLAN AND SECTION FOR DETAIL CALL-OUT AND DETAIL ARE SHOWN ON THE
SAME DRAWING, DRAWING NUMBER IS REPLACED WITH A DASH.
SECTION LETTER
DESIGNATION
SHEET FROM
WHICH SECTION
IS TAKEN *
SECTION LETTER
DESIGNATION
DETAIL
NUMBER
ABBREVIATIONSGENERAL NOTES
1. BUILDING DIMENSIONS WERE COMPILED FROM AS-BUILTS AND ARE CONSIDERED APPROXIMATE.
CONTRACTOR SHALL FIELD VERIFY ALL PERTINENT MEASUREMENTS AND NOTIFY ENGINEER OF NEED TO
ADJUST CONVEYOR LOCATION PRIOR TO STARTING CONSTRUCTION.
2. CONTRACTOR TO OBTAIN AND COMPLY WITH ALL PERMITS AND REQUIREMENTS OF LINCOLN COUNTY, CITY OF NEWPORT, AND OTHER AUTHORITY HAVING JURISDICTION.
3. ALL EXISTING FEATURES INCLUDING, BUT NOT LIMITED TO, ROADWAYS, STRUCTURES, CURBS, SIDEWALKS, FENCES, WALLS, AND PLANTINGS SHALL BE RESTORED TO EXISTING CONDITIONS UNLESS
OTHERWISE SPECIFIED.
4. PROVIDE "AS CONSTRUCTED" DRAWINGS INDICATING FINAL ALIGNMENT, LENGTHS, ANGLES, AND
MATERIALS INSTALLED. "AS CONSTRUCTED" DRAWINGS SHALL BE "RED LINES" OF THE DESIGN
DRAWINGS.
5. ALL WORK PERFORMED INSIDE PLANT BUILDING MUST BE COMPLETED DURING THE PLANNED PLANT
SHUT DOWN WINDOW AS OUTLINED IN SPEC 01 10 00.
6. CONVEYORS TO BE PROVIDED BY OWNER.
7. CONTRACTOR RESPONSIBLE FOR PROTECTION OF EQUIPMENT AND MATERIALS PROVIDED BY OTHERS.
8. CONTRACTOR SHALL PROVIDE A CONSTRUCTION STAGING AND SEQUENCING PLAN.
9. CONTRACTOR SHALL BE RESPONSIBLE FOR DISPOSAL OR SALVAGE OF EXISTING CONVEYORS.
@ AT
AB ANCHOR BOLT
ABS ACRYLONITRILE BUTADIENE
STYRENE
AC ASPHALTIC CONCRETE
ANSI AMERICAN NATIONAL STANDARDS
INSTITUTE
APPROX APPROXIMATE
APPVD APPROVED
ASSY ASSEMBLY
AWWA AMERICAN WATER WORKS
ASSOCIATION
BS BOTH SIDES
BFP BELT FILTER PRESS
BSMT BASEMENT
BTF BOTTOM FACE
BTU BRITISH THERMAL UNIT
CIP CAST-IN-PLACE
CL or C/L CENTERLINE
CLR CLEAR
CMP CORRUGATED METAL PIPE
COMM COMMUNICATION
CND CONDUIT
CONC CONCRETE
CPLG COUPLING
CR CRUSHED ROCK
DEFL DEFLECTION
DET DETAIL
DI DUCTILE IRON
DIA DIAMETER
DS DIGESTER SLUDGE
EA EACH
EL ELEVATION
ELB ELBOW
EQ EQUAL
ESC EROSION SEDIMENT CONTROL
EVG EVERGREEN
EW EACH WAY
EXIST EXISTING
FA FOUL AIR
FDN FOUNDATION
FLG FLANGE
FM FORCE MAIN
FO FIBER OPTIC
FW FINISH WATER
GBT GRAVITY BELT THICKENER
GALV GALVANIZED
GR GRADE
HDPE HIGH DENSITY POLYETHYLENE
HORIZ HORIZONTAL
ID INSIDE DIAMETER
IE INVERT ELEVATION
LB POUND
LF LINEAR FOOT
LOC LOCATION
MATL MATERIAL
MAX MAXIMUM
MFR MANUFACTURER
MH MANHOLE
MIN MINIMUM
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
OHP OVERHEAD POWER
PD PLANT DRAIN
PL PROPERTY LINE
POLY POLYETHYLENE
PVC POLYVINYL CHLORIDE
PWR POWER
RD ROAD
RDCR REDUCER
RESTR RESTRAINED
REQ'D REQUIRED
RFCA RESTRAINED FLANGED
COUPLING ADAPTER
ROW or R/W RIGHT-OF-WAY
RW RAW WATER
SAN SANITARY
SCHED SCHEDULE
SD STORM DRAIN
SHT SHEET
SLP SLOPE
SPECS SPECIFICATIONS
SPL SPOOL
SST STAINLESS STEEL
STA STATION
STD STANDARD
STL STEEL
T or TEL TELEPHONE
TB THRUST BLOCK
TDH TOTAL DYNAMIC HEAD
THK THICKNESS
TYP TYPICAL
TWAS THICKENED WASTE ACTIVATED
SLUDGE
UG UNDERGROUND
UON UNLESS OTHERWISE NOTED
VERT VERTICAL
W WATER / WEST
W/ WITH
W/O WITHOUT
WAS WASTE ACTIVATED SLUDGE
WTP WATER TREATMENT PLANT
THEN DRAWING IS
NOT MEASURE 1"
IF THIS BAR DOES
NOTICE
CHECKED
DRAWN
DESIGNED
PROJECT NO.: SCALE: DATE:
C U s e r s j u s t i n m o m a n D e s k t o p P r o j e c t
F o l d e r
S h o r t c u t s N e w p o r t C A D
S h e e t s O
R C d w g
C
S T I N
M
O M s
L M
S
T e c h
SHEET
0 1
19-2673.01
C-1
AUGUST 2021
WWTP BIOSOLIDS
CONVEYOR
REPLACEMENT PROJECT
AS SHOWN
of 18
12/31/2022RENEWS
CIVIL SITE, ACCESS
AND STAGING AREA PLAN
CAS
JSD
JSM
SCALE: 1"=40'
PLAN
SHEET NOTES:
1. CONTRACTOR TO COORDINATE STAGING WITH MAINTENANCE
AND OPERATIONS PERSONNEL AT THE PLANT.
2. CONTRACTOR TO RESTORE STAGING AREA TO ORIGINAL
CONDITIONS AFTER WORK IS COMPLETE.
O
P
E
R
A
T
I
O
N
S
B
U
I
L
D
I
N
G
M
A
I
N
T
E
N
A
N
C
E
B
U
I
L
D
I
N
G
STA
G
IN
G
AREA, S
EE
N O
TES
D
R
I V
R
O
U
G
C
E
S
S
N
S
T
R
U
C
T
I
Z
N
E
S O
LID
S
B U
IL
D
IN
G
EXIST PROPERTY FENCE LINE
EXIST EDGE OF PAVEMENT
ALL CONSTRUCTION WORK LIMITED
TO WEST SIDE OF SOLIDS BUILDING
THEN DRAWING IS
NOT MEASURE 1"
IF THIS BAR DOES
NOTICE
CHECKED
DRAWN
DESIGNED
PROJECT NO.: SCALE: DATE:
C U s e r s j u s t i n m o m a n D e s k t o p P r o j e c t
F o l d e r
S h o r t c u t s N e w p o r t C A D
S h e e t s O
R M d w g
M
S T I N
M
O M s
L M
S
T e c h
SHEET
0 1
19-2673.01
M-1
AUGUST 2021
WWTP BIOSOLIDS
CONVEYOR
REPLACEMENT PROJECT
AS SHOWN
of 18
12/31/2022RENEWS
DEMOLITION PLAN
CAS
JLC
JSM
CONTRACTOR TO PRESERVE
EXISTING SERPENTIX
SUPPORTS, TYP ALL
SEE DETAIL C FOR
UPPER SUPPORT DEMO
FLUSH CUT EXISTING DRAIN
AND PLACE PLUG IN TOP
REMOVE EXISTING BELT
CONVEYOR AND SUPPORTS
REMOVE EXISTING SERPENTIX
CONVEYOR AND HOOD (NOT
SHOWN), SEE NOTE 1 & 2
ELEV=170.33
ELEV=168.00
NOTES:
1. CONTRACTOR MAY DISASSEMBLE SERPENTIX CONVEYOR AS NECESSARY TO AID IN
REMOVAL THROUGH EXISTING CONVEYOR OPENING OUT OF THE BUILDING.
2. CONTRACTOR TO COORDINATE SHUT DOWN AND REMOVAL OF CONVEYOR WITH PLANT
OPERATION STAFF. REROUTING OF SOLIDS MUST BE COMPLETED BY PLANT OPERATION
STAFF PRIOR TO SHUT DOWN AND REMOVAL OF CONVEYOR.
3. EXISTING MECHANICAL EQUIPMENT NOT SHOWN AS DEMOLISHED ON THIS SHEET TO
REMAIN. CONTRACTOR TO PROTECT EXISTING EQUIPMENT DURING REMOVAL OF
CONVEYORS.
4. CONTRACTOR TO SAWCUT TO LIMITS SHOWN. ENSURE ALL EXPOSED REBAR IS
COATED AND CONCRETE IS RESTORED PER SPEC 03 11 00.
SCALE: NTS
MECHANICAL DEMOLITION
SCALE: NTS
STRUCTURAL DEMOLITION
A
B
SCALE: NTS
SERPENTIX UPPER SUPPORT DEMO
C
CONTRACTOR TO DEMOLISH UPPER SECTION OF
EXISTING SUPPORT AS SHOWN, REMOVE EXISTING
BOLTS CONNECTING THE UPPER AND LOWER
SECTIONS OF SUPPORT, PRESERVE AND PROTECT
LOWER SECTION OF SUPPORTS TO MODIFY AS
SHOWN ON SHT M-3
EXISTING
CONVEYOR
OPENING
EXISTING
PERSONNEL
DOOR
M-1
B
EXTEND EXISTING
OPENING TO TOP OF
CONCRETE PLATFORM,
SEE NOTE 4
3'-4"
THEN DRAWING IS
NOT MEASURE 1"
IF THIS BAR DOES
NOTICE
CHECKED
DRAWN
DESIGNED
PROJECT NO.: SCALE: DATE:
C U s e r s j u s t i n m o m a n D e s k t o p P r o j e c t
F o l d e r
S h o r t c u t s N e w p o r t C A D
S h e e t s O
R M d w g
M
S T I N
M
O M s
L M
S
T e c h
SHEET
0 1
PLAN VIEW
SCALE: 3/16" = 1'-0"
19-2673.01
M-2
AUGUST 2021
WWTP BIOSOLIDS
CONVEYOR
REPLACEMENT PROJECT
AS SHOWN
of 18
12/31/2022RENEWS
MECHANICAL PLAN
CAS
JLC
JSM
40'-1"
PASTEURIZATION CHUTE
CON-341-01
SINGLE MOTOR SHAFTLESS SCREW
CONVEYOR, PROVIDED BY OWNER
CON-351-01
REVERSIBLE SINGLE
MOTOR SHAFTLESS
SCREW CONVEYOR,
PROVIDED BY OWNER
BYPASS CHUTE
CON-341-02
SINGLE MOTOR SHAFTLESS
INCLINED SCREW CONVEYOR,
PROVIDED BY OWNER
PASTEURIZATION
ROOM
NORTH STORAGE BAY
SOUTH STORAGE BAY
D R I V E
L A N
E
FROM
CENTRIFUGES
B
M-3
M-3
A
TRENCH DRAIN
CONTROL PANEL,
SEE E SHTS
RDP DISCHARGE
TRENCH DRAIN
M-4
PREFABRICATED
CROSSOVER STAIR
THEN DRAWING IS
NOT MEASURE 1"
IF THIS BAR DOES
NOTICE
CHECKED
DRAWN
DESIGNED
PROJECT NO.: SCALE: DATE:
C U s e r s j u s t i n m o m a n D e s k t o p P r o j e c t
F o l d e r
S h o r t c u t s N e w p o r t C A D
S h e e t s O
R M d w g
M
S T I N
M
O M s
L M
S
T e c h
SHEET
0 1
19-2673.01
M-3
AUGUST 2021
WWTP BIOSOLIDS
CONVEYOR
REPLACEMENT PROJECT
AS SHOWN
of 18
12/31/2022RENEWS
MECHANICAL SECTIONS
CAS
JLC
JSM
ELEV=158.00
CL ELEV=170.25
CL ELEV=173.46
TRENCH DRAIN ELEV=156.67
PASTEURIZATION CHUTE
EL=162.08
20'-4"
CL ELEV=160.83
CON-341-01
SINGLE MOTOR SHAFTLESS SCREW
CONVEYOR, PROVIDED BY OWNER
8'-9"
CON-341-02
SINGLE MOTOR SHAFTLESS
INCLINED SCREW CONVEYOR,
PROVIDED BY OWNER
CON-351-01
REVERSIBLE, SINGLE MOTOR
SHAFTLESS SCREW CONVEYOR,
PROVIDED BY OWNER, SEE NOTE 3
2" SCH 40 PVC DRAIN FROM
INCLINE CONVEYOR TO
EXISTING TRENCH DRAIN
BYPASS CHUTE
NORTH STORAGE BAY
DRIVE LANE
PASTEURIZATION ROOM
ELEV=157.33
CON-351-01
REVERSIBLE, SINGLE MOTOR
SHAFTLESS SCREW CONVEYOR,
PROVIDED BY OWNER, SEE NOTE 3
CL ELEV=168.78
EXISTING CONCRETE PLATFORM
CON-341-02
SINGLE MOTOR SHAFTLESS INCLINED
SCREW CONVEYOR, PROVIDED BY OWNER
NORTH STORAGE BAY SOUTH STORAGE BAY
12'-4"
2'-2
" 2'-1
REMOVABLE SOFT BOOT, 1/8" NITRILE,
PROVIDED BY OWNER
SCALE: 1/4" = 1'-0"
SECTION B
M-2
SCALE: 1/4" = 1'-0"
SECTION A
M-2
M-4
STAIRS AND PLATFORM
SUPPORT MODIFICATION SCHEDULE
SUPPORT CONVEYOR APPROX. HEIGHT TO BOTTOM OF CONVEYOR AT SUPPORT CENTER
A CON-341-01 2'-2"
B CON-341-01 2'-2"
C CON-341-02 1'-11"
D CON-341-02 6'-6"
E CON-341-02
4'-1 1/2"
-SEE S SHTS FOR SUPPORT MODIFICATIONS AND ANCHORAGE
-CONTRACTOR TO ADJUST SUPPORT HEIGHTS AS NECESSARY PER FIELD MEASURMENTS
UNALTERED EXIST SUPPORT
NEW RAILING POSTS WITH BASE PLATES TO MATCH
EXISTING, CONTRACTOR TO CUT RAILING AT MINIMUM
1' AWAY FROM CONVEYOR. CONNECT NEW POSTS TO
EXISTING RAILING AND TOP OF CONCRETE, TYP BOTH
SIDES
CONTRACTOR TO INSTALL SHEET METAL
AROUND CONVEYOR TO COVER OPENING,
MATCH EXISTING MATERIAL AND INSULATION
S-2
EXIST SUPPORT D
S-2
EXIST SUPPORT C
S-2
EXISTING SUPPORT E
S-2
PROPOSED SUPPORT B
S-2
EXIST SUPPORT A
M-4
STAIRS AND PLATFORM
THEN DRAWING IS
NOT MEASURE 1"
IF THIS BAR DOES
NOTICE
CHECKED
DRAWN
DESIGNED
PROJECT NO.: SCALE: DATE:
C U s e r s j u s t i n m o m a n D e s k t o p P r o j e c t
F o l d e r
S h o r t c u t s N e w p o r t C A D
S h e e t s O
R M d w g
M
S T I N
M
O M s
L M
S
T e c h
SHEET
0 1
19-2673.01
M-4
AUGUST 2021
WWTP BIOSOLIDS
CONVEYOR
REPLACEMENT PROJECT
AS SHOWN
of 18
12/31/2022RENEWS
MECHANICAL DETAILS
CAS
JLC
JSM
SCALE: 3/4" = 1'-0"
CROSSOVER STAIRS AND PLATFORM 1
M-3
SHAFTLESS SCREW
CONVEYOR, CON-351-01
1 2
T Y P
3'-1
6'-4"
PREFABRICATED FRP
PLATFORM, HANDRAIL,
AND STAIRS, SEE NOTES
ANCHORAGE PER
CONTRACTOR
NOTES:
1. CONTRACTOR TO SUPPLY AND INSTALL FIBERGATE MODEL 866229.01 CROSSOVER
STAIR OR APPROVED EQUIVALENT.
2. CROSSOVER STAIR TO MEET REQUIREMENTS OF OSHA 1910.25 AND 1920.29.
3. CONTRACTOR TO PROVIDE ANCHORAGE, INCLUDING STRUCTURAL CALCULATIONS AS
DEFERRED SUBMITTAL, PER MANUFACTURER RECOMMENDATIONS.
M
I
19-2673.01
S-1
AUGUST 2021
WWTP BIOSOLIDS
CONVEYOR
REPLACEMENT PROJECT
AS SHOWN of 18
NO. DATE BY REVISION
NOT TO SCALE
THEN DRAWING IS
NOT MEASURE 1"
IF THIS BAR DOES
NOTICE
CHECKED
DRAWN
DESIGNED
PROJECT NO.: SCALE: DATE:X
\0 1-
PD
X \2
1-
T o
-0
5\
-0
7\
Pr oj ec t
D at a Fi le s\
_0 7_
D ra w in gs \2
1_
_2
D ra w in gs
1-
.d w g
S -1
/1
0/
0:
A M
3.
1s
LM
S T ec h)
SHEET
20 1 GENERAL STRUCTURAL
NOTES AND ELEVATION
VRV
VRV
EFL
812/31/22
19-2673.01
S-2
AUGUST 2021
WWTP BIOSOLIDS
CONVEYOR
REPLACEMENT PROJECT
AS SHOWN of 18
NO. DATE BY REVISION
NOT TO SCALE
THEN DRAWING IS
NOT MEASURE 1"
IF THIS BAR DOES
NOTICE
CHECKED
DRAWN
DESIGNED
PROJECT NO.: SCALE: DATE:X
\0 1-
PD
X \2
1-
T o
-0
5\
-0
7\
Pr oj ec t
D at a Fi le s\
_0 7_
D ra w in gs \2
1_
_2
D ra w in gs
1-
.d w g
S -2
/1
0/
0:
A M
3.
1s
LM
S T ec h)
SHEET
20 1
STRUCTURAL DETAILS
VRV
VRV
EFL
912/31/22
ASD
ABBREVIATIONS
a
A
AC
A/D
AF
AIC
ALT
A/M
ANN
AS
ASD
AT
ATS
AUTO
AWG
b
BCG
C
CAP
CB
CC
CHH
CL
CKT
CMH
CO
COMM
CON
COND
CONT
CPT
CP
CR
CS
CT
CWP
DC
DIAG
DISC
DISTR
DP
DPDT
DPST
EXST
EF
EHH
ELEM
EMERG
EFFL
EQ
EQUIP
ETM
FACP
FIN FL
FLEX
FLUOR
FO
FREQ
FU
FUT
FVNR
FVR
FWD
GA
GEN
GFI
GRS
H₂O₂
HMI
HOA
HOR
HORZ
HPS
HTR
HV
HZ
IND LT
INCAND
I/O
JB
KA
KCMIL
KV
KVA
KVAR
KVARH
KW
KWH
LCP
LP
LPS
LTG
LT(S)
(M) Ma
MCC
MCP
MOV
MS
MTD
MTG
MTS
(N)
NEC
NEMA
NEUT
NO
NTS
OVHD
OL
OT
PB
PD
PE
PEC
PF
pH
PH
PLC
PM
PNL
PNLBD
PRI
PS
PSI
PWR
(RL)
(RLD)
RCPT
RCT
RPM
RT
SCR
SD
SDBC
SEC
SECT
SF
SHH
SIG
SN
SPEC
SPD
SPDT
SS
SW
SWBD
SWGR
SYNC
TB
TC
TEMP
TP
TSP
TVSS
UH
UV
V
VA
VFD
VAR
VERT
VH
VS
W
WHM
WHDM
WP
WTRT
WTP
CIRCUIT BREAKER AUX.
CONTACT, CLOSED WHEN
BREAKER IS CLOSED
AMMETER, AMPERES
ALTERNATING CURRENT
ANALOG TO DIGITAL
AMPERE FRAME
AMPERES INTERRUPTING
CAPACITY
ALTERNATOR
AUTO/MANUAL
CONTROLLER
ANNUNCIATOR
AMMETER SWITCH
ADJUSTABLE SPEED DRIVE
AMPERE TRIP
AUTOMATIC TRANSFER
SWITCH
AUTOMATIC
AMERICAN WIRE GAGE
CIRCUIT BREAKER AUX.
CONTACT, CLOSED WHEN
BREAKER IS OPEN
BARE COPPER GROUND
CONDUIT, CONTACTOR
CAPACITOR
CIRCUIT BREAKER
CONTROL CABLE, CLOSING
COIL
COMMUNICATION
HANDHOLE
CHLORINE
CIRCUIT
COMMUNICATION MANHOLE
CONDUIT ONLY
COMMUNICATION
CONTACTOR
CONDUCTOR
CONTINUED,
CONTINUATION
CONTROL POWER
TRANSFORMER
CONTROL PANEL
CONTROL RELAY
CONTROL SWITCH
CURRENT TRANSFORMER
COLD WATER PIPE
DIRECT CURRENT
DIAGRAM
DISCONNECT
DISTRIBUTION
DISTRIBUTION PANEL
DOUBLE POLE, DOUBLE
THROW
DOUBLE POLE, SINGLE
THROW
EXISTING
EXHAUST FAN
ELECTRICAL HANDHOLE
ELEMENTARY
EMERGENCY
EFFLUENT
EQUAL
EQUIPMENT
ELAPSED TIME METER
FIRE ALARM CONTROL
PANEL
FINISHED FLOOR
FLEXIBLE
FLUORESCENT
FIBER OPTIC
FREQUENCY
FUSE
FUTURE
FULL VOLTAGE, NON
REVERSING
FULL VOLTAGE, REVERSING
FORWARD
GAUGE
GENERATOR
GROUND FAULT
INTERRUPTER
GALVANIZED RIGID STEEL
HYDROGEN PEROXIDE
HUMAN MACHINE
INTERFACE
HAND-OFF-AUTOMATIC
HAND-OFF-REMOTE
HORIZONTAL
HIGH PRESSURE SODIUM
HEATER
HIGH VOLTAGE
HERTZ (CYCLES PER
SECOND)
INDICATING LIGHT
INCANDESCENT
INPUT/OUTPUT
JUNCTION BOX
KILOAMPERES
THOUSANDS OF CIRCULAR
MILS
KILOVOLTS
KILOVOLT AMPERES
KILOVOLT AMPERES
REACTIVE
KILOVOLT AMPERES
REACTIVE HOURS
KILOWATTS
KILOWATT HOURS
LIGHTING CONTROL PANEL
LIGHTING PANEL
LOW PRESSURE SODIUM
LIGHTING
LIGHT(S)
MODIFIED
MILLIAMPERES
MOTOR CONTROL CENTER
MOTOR CIRCUIT
PROTECTOR
MOTOR OPERATED VALVE
MOTOR STARTER
MOUNTED
MOUNTING
MANUAL TRANSFER
SWITCH
NEW
NATIONAL ELECTRICAL
CODE
NATIONAL ELECTRICAL
MANUFACTURER'S ASSOC.
NEUTRAL
NORMALLY OPEN, NUMBER
NOT TO SCALE
OVERHEAD
THERMAL OVERLOAD
RELAY
OVER TEMPERATURE
PULLBOX, PUSHBUTTON
POSITIVE DISPLACEMENT
PHOTOELECTRIC
PHOTOELECTRIC CELL
POWER FACTOR
MEASURE OF ACIDITY OR
ALKALINITY
PHASE
PROGRAMMABLE LOGIC
CONTROLLER
POWER MONITOR
PANEL
PANELBOARD
PRIMARY
PRESSURE SWITCH
POUNDS PER SQUARE INCH
POWER
RELOCATE
RELOCATED
RECEPTACLE
REPEAT CYCLE TIMER
REVOLUTIONS PER MINUTE
RESET TIMER
SILICON CONTROLLED
RECTIFIER
SMOKE DETECTOR
SOFT-DRAWN BARE
COPPER
SECONDS, SECONDARY
SECTION
SUPPLY FAN
SIGNAL HANDHOLE
SIGNAL
SOLID NEUTRAL
SPECIFICATIONS
SURGE PROTECTIVE
DEVICE
SINGLE POLE, DOUBLE
THROW
STAINLESS STEEL, SOLID
STATE SWITCH
SWITCHBOARD
SWITCHGEAR
SYNCHRONIZING TERMINAL
BOX, TERMINAL BOARD
TELEPHONE CABINET
TEMPERATURE
TWISTED PAIR UNSHIELDED
TWISTED SHIELDED PAIR
TRANSIENT VOLTAGE
SURGE SUPPRESSOR
UNIT HEATER
ULTRA VIOLET
VOLTS
VOLT-AMPERES
VARIABLE FREQUENCY
DRIVE
VOLT AMPERES REACTIVE
VERTICAL
VAR-HOUR
VOLTMETER SWITCH
WIRE, WATTS
WATTHOUR METER
WATTHOUR DEMAND
METER
WEATHERPROOF
WATERTIGHT
WATER TREATMENT PLANT
SPECIAL EQUIPMENT CONNECTION
AS SHOWN
MOTOR CONNECTION,
HORSEPOWER INDICATED
TRANSFORMER
LINE OR LOAD REACTOR, IMPEDENCE
SHOWN
CURRENT TRANSFORMER
DISCONNECT SWITCH,
AMPERAGE RATING SHOWN
THERMAL MAGNETIC CIRCUIT BREAKER
MAGNETIC ONLY CIRCUIT BREAKER (MOTOR
CIRCUITS ONLY) CONTINUOUS CURRENT
RATING AND TRIP SETTINGS SHOWN
MOTOR STARTER, SIZE SHOWN
FUSE, SIZE SHOWN
ADJUSTABLE SPEED DRIVE
JJ
CONDUIT UP
CONDUIT DOWN
CONDUIT UP FROM UNDERGROUND RACEWAY
30A
FUSED DISCONNECT SWITCH, SWITCH
AND FUSE RATING SHOWN
60/40 = 60A SWITCH WITH 40A FUSE
F
JUNCTION BOX
GROUND CONNECTION PER
NEC ARTICLE 250
CONDUIT SEAL-OFF
CONDUIT CONCEALED
UNDERFLOOR OR UNDERGROUND
CONDUIT CONCEALED IN WALL
OR ABOVE CEILING IN FINISHED
AREAS, EXPOSED IN PROCESS
AND EQUIPMENT AREAS.
CONDUIT STUB
FLEXIBLE CONDUIT OR MFR CABLE
T
LOCAL TERMINAL OR LUG CONNECTION
A C
0A
T
NEW ELECTRICAL EQUIPMENT
GENERAL NOTES
1. ALL MATERIALS AND INSTALLATIONS SHALL BE IN ACCORDANCE WITH THE LATEST NATIONAL ELECTRICAL CODE.
INSTALLATION DRAWINGS, CONSTRUCTION SPECIFICATIONS AND LOCAL CODES. ALL MATERIALS SHALL BE NEW AND LISTED BY THE UNDERWRITERS' LABORATORY INC. (UL). ALL ELECTRICAL WORK SHALL BE INSTALLED IN A GOOD AND
WORKMANLIKE MANNER.
2. REFER TO THE ELECTRICAL CIRCUIT SCHEDULE FOR CIRCUIT IDENTIFICATIONS, ROUTING, CONDUCTOR SIZES, ETC.
3. ELECTRICAL CONTRACTOR SHALL COORDINATE WITH OTHER DISCIPLINES AS REQUIRED TO MITIGATE INTERFERENCES.
4. CONDUIT MATERIAL SHOWN ON ELECTRICAL PLANS ARE SPECIFIC FOR THE LOCATION WHERE THE CONDUIT STARTS.
CONTRACTOR IS RESPONSIBLE FOR TRANSITIONING TO APPROVED CONDUIT MATERIAL BASED ON LOCATION AND IN
ACCORDANCE TO ELECTRICAL SPECIFICATIONS.
SYMBOLS
AUTOMATIC TRANSFER SWITCH
R
FIELD TERMINAL
FUSED TERMINAL, SIZE SHOWN
SPEED POTENTIOMETER
120V CONTROL RELAY, DPDT MINIMUM
24VDC CONTROL RELAY, DPDT MINIMUM
RELAY CONTACT - NO, NC
PUSHBUTTON OR
SWITCH CONTACT BLOCK - NO, NC
R PUSH-TO-TEST LED PILOT LIGHT
HAND
OFF
AUTO
THREE POSITION SWITCH
20A
60/40
SURFACE MOUNTED LED LUMINAIRE *
RECESSED MOUNTED LED LUMINAIRE *
WALL MOUNTED LED LUMINAIRE *
* SHADED LUMINAIRE INDICATES BATTERY
BACKED UNIT
DUPLEX, QUADPLEX RECEPTACLE,
W/DESIGNATOR
GFI = GROUND FAULT INTERRUPTING
WP = WEATHERPROOF
+48 = HEIGHT AFF.
WALL SWITCH STANDARD TOGGLE,
DESIGNATOR
3 = 3-WAY
D = DIMMER
T = TIMER
METERBASE W/UTILITY METER
GFI
M
DISCONNECT RECEPTACLE AND PLUG
GROUND ROD
GROUND ROD TEST WELL
FLOAT SWITCH - NO, NC
TEMPERATURE SWITCH - NO, NC
ETM ELAPSED TIME METER
CNT COUNTER
LIMIT SWITCH - NO, NC
TIME DELAY CONTACTS,
NORMALLY OPEN TIMED CLOSED
NORMALLY CLOSED TIMED OPEN
S SMOKE/HEAT DETECTOR
I INTRUSION SWITCH
T THERMOSTAT/TEMPERATURE
TRANSMITTER
5A
F1 1A
EXISTING ELECTRICAL EQUIPMENT
EQUIPMENT TO BE DEMO'D OR REMOVED
ELECTRICAL CIRCUIT
IDENTIFICATION
MULTIPLE ELECTRICAL CIRCUITS,
SEPARATE CONDUITS
MULTIPLE ELECTRICAL CIRCUITS,
COMMON CONDUIT (SIZE SHOWN)
1"C
P1
P1 C1
P2 C2
P1 P3
P2 P4
XXX
HOME RUN, ELECTRICAL PANEL DESTINATION SHOWN.
1. RUNS MARKED WITH CROSS-HATCHES INDICATE
NUMBER OF NO.12 WIRE. LARGER GAUGES ARE
SHOWN OR NOTED ELSEWHERE. LONG CROSS HATCH
INDICATES NEUTRAL, SHORT INDICATES PHASE
CONDUCTOR, SLANT INDICATES GROUND WIRE PER
NEC ARTICLE 250.
2. FOR UNMARKED CONDUIT RUNS, CONTRACTOR
SHALL INSTALL REQUIRED NUMBER OF WIRES FOR
POWER AND/OR CONTROL OF ELEMENTS IN
CIRCUIT(S) SHOWN. SIZE OF WIRE SHALL BE NO.
12, UNLESS OTHERWISE NOTED OR REQUIRED BY
CODE.
3. SIZE CONDUIT ACCORDING TO SPECIFICATIONS AND
APPLICABLE CODE.
4. DASHED LINE INDICATE CONDUITS CONCEALED
UNDERGROUND OR UNDERFLOOR.
5. SOLID HOME RUN INDICATES CONDUIT ABOVE
CEILING IN FINISHED AREA, CONCEALED IN WALL
OR EXPOSED IN PROCESS AND EQUIPMENT AREAS.
XXX
CR
CR
NO. DATE BY REVISION
NOT TO SCALE
THEN DRAWING IS
NOT MEASURE 1"
IF THIS BAR DOES
NOTICE
CHECKED
DRAWN
DESIGNED
PROJECT NO.: SCALE: DATE:P:
\P ro je ct s\
.9
1.
_M S A _N ew po rt _S ol id s_ C on ve ya nc e\
D W
G \1
9-
-O
R -E
-1 .d w g
E-
8/ 2/
:4
PM
R O
B
ER
TC
3.
1s
LM
S T ec h)
SHEET
20 1
OR CCB #196597 WA #INDUSSI880K9
Industrial Systems INC
(360) 952-8958
Vancouver, Washington 98682
Fax:
Phone:
12119 NE 99th Street e-mail: is@industrialsystems-inc.com
Suite #2090
(360) 718-7267
AK #1018436
PROJECT#:20.91.01
19-2673
E-1
AUGUST 2021
WWTP BIOSOLIDS
CONVEYOR
REPLACEMENT PROJECT
AS SHOWN of 18
ELECTRICAL LEGEND, SYMBOLS
AND ABBREVIATIONS
RSC
RSC
TBC
DocuSign Envelope ID: 5AAD073C-6307-40C8-B506-024E498122D1
8/10/2021
60MCC3
CABLE
TRAY
CONTROL
PANEL
CP2
SWITCHGEAR
60SWGR1
XFMR
60TX3
JBOX 25TJB4
@ WALKWAY
M J
JBOX 25JB1
(BELOW STAIRWAY)
M M
25M351
TRUCK LOADING
CONV.
25M341B
PRODUCT
CONV.
25HS351A,B
PULL CORD
SWITCHES
25SSL351
SPEED SWITCH
25FP341A
PRODUCT CONV.
FLEX CONTROL
PANEL
25M341A
PRODUCT
CONV.
ACTUATOR
25HS341A,B
PULL CORD
SWITCHES
25FV341
SPRAY
WASH
25SSL351
SPEED
SWITCH
EXISTING
PRODUCT CONV.
TO BE DEMO'D
SEE MECH. SHEETS
EXISTING
TRUCK LOAD BELT CONV.
TO BE DEMO'D
SEE MECH. SHEETS
PASTEURIZATION
CONTROL
PANEL 25FP900
NO. DATE BY REVISION
NOT TO SCALE
THEN DRAWING IS
NOT MEASURE 1"
IF THIS BAR DOES
NOTICE
CHECKED
DRAWN
DESIGNED
PROJECT NO.: SCALE: DATE:P:
\P ro je ct s\
.9
1.
_M S A _N ew po rt _S ol id s_ C on ve ya nc e\
D W
G \1
9-
-O
R -E
-2 .d w g
E-
8/ 2/
:4
PM
R O
B
ER
TC
3.
1s
LM
S T ec h)
SHEET
20 1
OR CCB #196597 WA #INDUSSI880K9
Industrial Systems INC
(360) 952-8958
Vancouver, Washington 98682
Fax:
Phone:
12119 NE 99th Street e-mail: is@industrialsystems-inc.com
Suite #2090
(360) 718-7267
AK #1018436
PROJECT#:20.91.01
19-2673
E-2
AUGUST 2021
WWTP BIOSOLIDS
CONVEYOR
REPLACEMENT PROJECT
AS SHOWN of 18
ELECTRICAL PARTIAL
BUILDING PLAN - DEMO
RSC
RSC
TBC
KEY NOTES
EXISTING CONDUIT AND UNLABELED JUNCTION
BOX TO BE PROTECTED AND REMAIN INTACT
DURING CONVEYOR REPLACEMENT.
GENERAL NOTES
1. NOT ALL EQUIPMENT SHOWN IN ELECTRICAL ROOM
FOR CLARITY.
2. SEE SHEET E-7 FOR RISER DIAGRAM.
SCALE: 3/16" = 1'-0"
ELECTRICAL DEMO PLAN
PASTEURIZATION
ROOM
NORTH STORAGE BAY
SOUTH STORAGE BAY
D R
IV
E LA
N
E
CONTROL
ROOM
ELECTRICAL ROOM
60MCC3
CABLE
TRAY
CONTROL
PANEL
CP2
SWITCHGEAR
60SWGR1
XFMR
60TX3
JBOX 25TJB4
@ WALKWAY
M
M M J
JBOX 25JB1
(BELOW
STAIRWAY)
CON-351-01
BIOSOLIDS
REVERSIBLE
SCREW CONV.
CON-341-02
BIOSOLIDS
INCLINE SCREW
CONV.
CON-351-01
PULL CORD
SWITCHES
CON-351-01
SPEED
SWITCH
CS-351
REVERSIBLE SCREW
CONV. DIRECTION
CONTROL STATION
CON-341-02
PULL CORD
SWITCHES
CON-341-01
PULL CORD
SWITCHES
CON-341-01
BIOSOLIDS
SCREW CONV.
CON-341-01
SPEED
SWITCH
CON-341-02
SPEED
SWITCH
PASTEURIZATION
CONTROL
PANEL 25FP900
P3
P2
P1 C10 C11 C12
1"C
C22
P13
C21 C32 C33 C34
C201"C
60MCC3
C30 C31
ASD
NO. DATE BY REVISION
NOT TO SCALE
THEN DRAWING IS
NOT MEASURE 1"
IF THIS BAR DOES
NOTICE
CHECKED
DRAWN
DESIGNED
PROJECT NO.: SCALE: DATE:P:
\P ro je ct s\
.9
1.
_M S A _N ew po rt _S ol id s_ C on ve ya nc e\
D W
G \1
9-
-O
R -E
-3 .d w g
E-
8/ 2/
:4
PM
R O
B
ER
TC
3.
1s
LM
S T ec h)
SHEET
20 1
OR CCB #196597 WA #INDUSSI880K9
Industrial Systems INC
(360) 952-8958
Vancouver, Washington 98682
Fax:
Phone:
12119 NE 99th Street e-mail: is@industrialsystems-inc.com
Suite #2090
(360) 718-7267
AK #1018436
PROJECT#:20.91.01
19-2673
E-3
AUGUST 2021
WWTP BIOSOLIDS
CONVEYOR
REPLACEMENT PROJECT
AS SHOWN of 18
ELECTRICAL PARTIAL
BUILDING PLAN
RSC
RSC
TBC
KEY NOTES
SEE SHEET E-4 FOR MODIFICATIONS TO EXISTING MCC.
SEE SHEET E-7 FOR CONTROL STATION DETAIL.
ROUTE CONDUCTORS FOR CONV-341-01 MOTOR IN EXISTING
CONDUIT FROM JBOX 25TJB4 IF CONDUIT FILL ALLOWS.
OTHERWISE ROUTE NEW 3/4" CONDUIT WITH CONDUCTORS
ALONG EXISTING CONDUIT ROUTE.
GENERAL NOTES
1. NOT ALL EQUIPMENT SHOWN IN ELECTRICAL ROOM FOR CLARITY.
2. SEE SHEET E-7 FOR RISER DIAGRAM.
3. ALL NEW CONDUITS AND FITTINGS USED IN THE PASTEURIZATION
ROOM AND STORAGE BAY AREAS TO BE PVC COATED RIGID.
4. ANY NEW JUNCTION BOX USED IN THE PASTEURIZATION ROOM AND
STORAGE BAY AREAS TO BE NEMA 4X STAINLESS STEEL OR
NON-METALLIC.
5. PULL CORD, AND SPEED SWITCHES ARE VENDOR PROVIDED,
CONTRACTOR INSTALLED ON PROVIDED BRACKETING. COORDINATE
SPECIFICS WITH VENDOR.
SCALE: 3/16" = 1'-0"
ELECTRICAL PLAN
PASTEURIZATION
ROOM
NORTH STORAGE BAY
SOUTH STORAGE BAY
D R
IV
E LA
N
E
CONTROL
ROOM
ELECTRICAL ROOM
SCALE: 3/16" = 1'-0"
CIRCUIT SCHEDULE
EXISTING MCC 60MCC3, 480V, 3Ø, 3W, 1200A, 42,000AIC
50A
R A S P
U M
P
P1
ASD
7AC
77AT
1.5 B
IN
A C
TI
V A
TI
O N
M
1200:5
(3)
TO 60SWGR-1
BUSS A VIA KEY
INTERLOCK
BREAKER
POWER
MONITOR
(3) 30A
A S D
FP
C H
LO
R
IN
E
IN
D U
C
TI
O N
M
IX
ER
M
CTRL
PNL
20A
KEY NOTES
GENERAL NOTES
1. ALL EQUIPMENT IS EXISTING UNLESS OTHERWISE
SHOWN AS BOLDED EQUIPMENT.
2. SEE SHEET E-3 FOR CIRCUIT SCHEDULE.
1 REPLACE EXISTING CUTLER HAMMER OVERLOAD
MODEL H2007B WITH UNIT SIZED FOR NEW MOTOR.
VERIFY EXISTING CUTLER HAMMER OVERLOAD UNIT
SIZE WITH NEW MOTOR. PROVIDE NEW OVERLOADS
IF NEEDED OR RE-ADJUST EXISTING SETTINGS.
EXISTING CONDUIT AND CONDUCTORS TO BE
RE-USED AND EXTENDED WHERE REQUIRED.
REMOVE EXISTING STARTER BUCKET AND RETURN
TO OWNER.
PROVIDE AND INSTALL NEW BUCKET WITH CIRCUIT
BREAKER AND ADJUSTABLE SPEED DRIVE FOR NEW
CONVEYOR. SEE SHEET E-5.
S
EP
TA
G
E S C R
EE
N
IN
G U
N
IT
M
15AC
165AT
S
PA
R E
7AC
77AT
LI
M
E
TR
A N
S
FE
R S C R
EW
C O
N V
M
7AC
77AT
LI
M
E A D
D
IT
IO
N
S C R
EW
C O
N V
M
7AC
77AT
D
EW
A
TE
R
IN
G B
EL
T
C O
N V
M
7AC
77AT
D
EW
A
TE
R
IN
G B
EL
T
C O
N V
M
30A
ASD
A S D
TH
ER
M O
B
LE
N D
ER
M
1A
TH
ER
M O
B
LE
N D
ER
M
1B
3AC
33AT
PA
S
TE
U R
IZ
A
TI
O N
V
ES
S
EL
M
15AC
165AT
PR
O
D U
C T
C O
N V
M
1B
C
EN
TR
IF
U G
E S C R
EW
C O
N V
M
7AC
77AT
C
EN
TR
IF
U G
E S C R
EW
C O
N V
M
7AC
77AT
200A
FP
1 CTRL
PNL
H
EA
T S
YS
TE
M
P O
W
ER
C O
N
TR
O L
PA
N
EL
FP
TR
U
C K L
O A D
IN
G
B
EL
T C O
N V
M
7AC
77AT
3AC
33AT
S
PA
R E
3AC
33AT
S
PA
R E
30A
FP
1 CTRL
PNL
LI
M
E
TR
U C K
U N
LO
A D
IN
G
P A N
EL
FP
P1
200A
DIST.
PNL
60DP1
250A
TO
70MCC1
(MAINT.
BLDG)
600AF
600AS
TO
80MCC1
(OPS
BLDG)
60TX1
45KVA,
480- 208Y/120V, 3PH, 4W
LTG.
PNL
60LP1
60TX2
75KVA,
480- 208Y/120V, 3PH, 4W
LTG.
PNL
60LP2
60TX3
ISOLATION
15KVA,
480- 208Y/120V, 3PH, 4W
LTG.
PNL
60IP1
B
IO
S O
LI
D
S S
C R
EW
C O
N V
C O
N -3
-0
B
IO
S O
LI
D
S I
N C
LI
N E
S C R
EW
C O
N V
C O
N -3
-0
TO 60SWGR-1
BUSS B VIA KEY
INTERLOCK
BREAKER
P2
4 4
15A
ASD
SCALE: NONE
60MCC3 - ONE-LINE DIAGRAM
B
IO
S O
LI
D
S R
EV
ER
S
IN
G S C R
EW
C O
N V
C O
N -3
-0
P3
5%
NO. DATE BY REVISION
NOT TO SCALE
THEN DRAWING IS
NOT MEASURE 1"
IF THIS BAR DOES
NOTICE
CHECKED
DRAWN
DESIGNED
PROJECT NO.: SCALE: DATE:P:
\P ro je ct s\
.9
1.
_M S A _N ew po rt _S ol id s_ C on ve ya nc e\
D W
G \1
9-
-O
R -E
-4 .d w g
E-
8/ 2/
:4
PM
R O
B
ER
TC
3.
1s
LM
S T ec h)
SHEET
20 1
OR CCB #196597 WA #INDUSSI880K9
Industrial Systems INC
(360) 952-8958
Vancouver, Washington 98682
Fax:
Phone:
12119 NE 99th Street e-mail: is@industrialsystems-inc.com
Suite #2090
(360) 718-7267
AK #1018436
PROJECT#:20.91.01
19-2673
E-4
AUGUST 2021
WWTP BIOSOLIDS
CONVEYOR
REPLACEMENT PROJECT
AS SHOWN of 18
ELECTRICAL MCC ONE-LINE
AND ELEVATIONS
RSC
RSC
TBC
SCALE: NONE
60MCC3 - PARTIAL ELEV.
SCALE: NONE
STARTER SCHEMATICS
480V, 3Ø, 60HZ BUSS
M
R
ON
CPT
480V-120V
7AC
77AT
OL
M
M
OL'S
M M
SPARE
ETM
BIOSOLIDS SCREW CONV.
CON-341-01
15A 3P
480V, 3Ø, 60HZ BUSS
U V W
ADJUSTABLE SPEED
DRIVE (ASD)
CR1
CR4
21 PLC CALL
CPT
480V-120V
"FWD RUN"
DISCRETE SIGNALS TO PLC
AT PASTEURIZATION
CONTROL PANEL
25FP900
(TYP)
L1 L2 L3
5%
R
FWD
SCALE: NONE
VFD SCHEMATIC
L CR6
KEY NOTES
GENERAL NOTES
1. STARTER SCHEMATIC PROVIDED FOR REFERENCE
AND TO BE RE-USED FOR NEW CONSTANT SPEED
CONVEYORS.
2. THE BASIS OF DESIGN SHOWN FOR THE ASD IS FOR
THE ACS800 MANUFACTURED BY ABB. ADDITIONAL
MANUFACTURER'S PER THE SPECIFICATIONS ARE
ACCEPTABLE, AND IF ACCEPTED, THE WIRING
DIAGRAM SHALL BE UPDATED PER THE SPECIFIC
MANUFACTURER.
1 FUSING AND CPT SIZING PER MANUFACTURER'S
RECOMMENDATION.
PROVIDE ASD WITH OPTIONAL RELAY OUTPUT
BOARD IF REQUIRED.
RELAY CHANGES STATE WHEN POWER IS
APPLIED. RELAY RETURNS TO NORMAL STATE
WHEN POWER IS REMOVED OR A FAULT OCCURS.
PLC CALL
"REV RUN"
CR5
X2
"RUNNING
FORWARD"
CR1
"RUNNING
REVERSE"
CR2
"FAULT"
CR3
1ESR2
PASTEURIZATON
CONTROL PANEL
25FP900
PASTEURIZATON
CONTROL PANEL
25FP900
3-1
"MTR CALL"
PASTEURIZATON
CONTROL PANEL
25FP900
CR1 3-2
480V, 3Ø, 60HZ BUSS
M
R
ON
CPT
480V-120V
15AC
165AT
OL
M
M
OL'S
ETM
3-5
"MTR CALL"
PASTEURIZATON
CONTROL PANEL
25FP900
CR2 3-6
BIOSOLIDS INCLINE SCREW CONV.
CON-341-02
3-3
PASTEURIZATON
CONTROL PANEL
25FP900
3-4
M M
SPARE
3-7
PASTEURIZATON
CONTROL PANEL
25FP900
3-8
KEYPAD
TO BE MOUNTED
IN MCC DOOR
RELAY OUT
"RUNNING
FORWARD"
XR01
CR3
R
FAULT
CR2
ETM
R
REV
XR02
RELAY OUT
"RUNNING
REVERSE"
RELAY OUT
"VFD OK"
NOT FAULTED
XR03
CR2
CR1
(AI1) BOTTOM = 0/2-10V
(AI2) TOP = 0/4-20MA
A I1
A I2
J1 J2
"RUN ENABLE" (DIIL)
"START" (DI6)
"REVERSE" (DI5)
(+24VD)
XD24
CR4
CR5
CR6
SPEED SIGNAL FROM PLC
AT PASTEURIZATION
CONTROL PANEL
25FP900
4-20MA
AI+
AI-
SHLD
ANALOG IN
"SPEED
SETPOINT"
(AI2+)
(AI2-)
XAI
BIOSOLIDS REVERSING SCREW CONV.
CON-351-01
NO. DATE BY REVISION
NOT TO SCALE
THEN DRAWING IS
NOT MEASURE 1"
IF THIS BAR DOES
NOTICE
CHECKED
DRAWN
DESIGNED
PROJECT NO.: SCALE: DATE:P:
\P ro je ct s\
.9
1.
_M S A _N ew po rt _S ol id s_ C on ve ya nc e\
D W
G \1
9-
-O
R -E
-5 .d w g
E-
8/ 4/
:4
PM
R O
B
ER
TC
3.
1s
LM
S T ec h)
SHEET
20 1
OR CCB #196597 WA #INDUSSI880K9
Industrial Systems INC
(360) 952-8958
Vancouver, Washington 98682
Fax:
Phone:
12119 NE 99th Street e-mail: is@industrialsystems-inc.com
Suite #2090
(360) 718-7267
AK #1018436
PROJECT#:20.91.01
19-2673
E-5
AUGUST 2021
WWTP BIOSOLIDS
CONVEYOR
REPLACEMENT PROJECT
AS SHOWN of 18
ELECTRICAL CONTROL
DIAGRAMS
RSC
RSC
TBC
PASTEURIZATION CONTROL PANEL 25FP90060MCC3 - CON-351-01
6 3725FP900-3-37
1B
8 38
RUN FWD
RUN REV
1B
120VAC
CR1
CR2
10 39
FAULT
9 CR3
16 PT. DISCRETE
120VAC INPUT MODULE
RACK 1 / SLOT 4
1746-IA16
IN-11
BIO REV SCREW CONV
CON-351-01
RUNNING FORWARD
IN-12
IN-13
16 PT. DISCRETE
RELAY OUT MODULE
RACK 1 / SLOT 9
1746-OW16
OUT 12
CR4
CR5
BIO REV SCREW CONV
CON-351-01
RUNNING FORWARD
BIO REV SCREW CONV
CON-351-01
VFD FAULT
X2
120VAC CONTROL
POWER
X2
OUT 13
SCALE: NONE
VFD INTERCONNECT WIRING
BIO REV SCREW CONV
CON-351-01
RUN CALL FORWARD
BIO REV SCREW CONV
CON-351-01
RUN CALL REVERSE
ADJUSTABLE
SPEED DRIVE (ASD)
AI+
AI-
SHLD
MOTOR SPEED
SETPOINT
ANALOG IN
6 6+
6-
SHLD
4 PT. ANALOG
OUT MODULE
RACK 1 / SLOT 11
1746sc-INO4i 8-6+
BIO REV SCREW CONV
CON-351-01
MOTOR SPEED SETPOINT
(0-100%)
I OUT 0+
8-6- COM 0-
TB-8
C
PU
S
LC
/0
0 1 2 3
PO
W
ER
S
U
PP
LY
-P
4 5
P
T.
I
N
PU
T
-I
A
P
T.
I
N
PU
T
-I
A
P
T.
I
N
PU
T
-I
A
P
T.
I
N
PU
T
-I
A
P
T.
I
N
PU
T
-I
A
P
T.
R
LY
O
U
TP
U T
-O W
P
T.
R
LY
O
U
TP
U T
-O W
P
T.
R
LY
O
U
TP
U T
-O W
P
T.
R
LY
O
U
TP
U T
-O W
PT
A N
LG
I
N
PU
T
-N
I4
PT
A N
LG
O
U
TP
U T sc -I
N O
4i
OFF ON/AUTO
XO
362 IN-14
BIO REV SCREW CONV
CON-351-01
MODE SELECT
TB-7
TB-3
PASTEURIZATION
CONTROL PANEL 25FP900FIELD
PULL CORD
PULL CORD
BIOSOLIDS
SCREW CONV.
CONV-341-01
PULL CORDBIOSOLIDS
INCLINE
SCREW CONV.
CONV-341-02
PULL CORD
PULL CORDEXISTING
PASTEURIZATION
VESSEL
25M331
PULL CORD
PULL CORD
PULL CORD
PULL CORD
PULL CORD
40 4
E-STOP
ER1
SCALE: NONE
WIRING MODIFICATIONS
KEY NOTES
1 NEW SIGNALS TO BE WIRED TO EXISTING SPARE
INPUTS OR OUTPUTS.
NEW PULL CORD AND ZERO SPEED SWITCHES TO
BE CONNECTED TO EXISTING WIRING FROM
REPLACED CONVEYOR SWITCHES.
INSTALL OR USE EXISTING SPARE TERMINALS
FOR CONNECTION OF REVERSING CONVEYOR
PULL CORD SWITCHES IN E-STOP WIRING CHAIN.
RECONNECT PANEL E-STOP AS SHOWN.
INSTALL NEW TERMINAL BLOCKS OR USE SPARES
WHERE AVAILABLE. DO NOT USE SPARE ANALOG
TERMINALS FOR DISCRETE CONNECTIONS.
INSTALL NEW RELAYS IN CONTROL PANEL FOR
CONTROL OF NEW REVERSING CONVEYOR.
NEW MODULE AND TERMINAL BLOCKS TO BE
INSTALLED IN EXISTING PLC RACK FOR SPEED
CONTROL OF NEW REVERSING CONVEYOR.
PBL33
N
FIELD
120VAC
120VAC
CB3
3A
GENERAL NOTES
1. EXISTING WIRING SHOWN IS BASED OFF RECORD
DRAWINGS PROVIDED BY THE OWNER.
CONTRACTOR TO VERIFY AND MODIFY/UPDATE AS
NEEDED TO PERFORM THE FUNCTIONS AS SHOWN.
PASTEURIZATION
CONTROL PANEL 25FP900
TB-2
EXISTING
DEWATERING
BELT CONV.
25M311
BIOSOLIDS
REVERSING
SCREW CONV.
CON-351-01
114BIOSOLIDS
SCREW CONV.
CONV-341-01
ZERO SPEED
TB-1
L1 1-1
1-2
PULL CORD/ESTOP
SCALE: NONE
WIRING MODIFICATIONS
SPEED SWITCH
L2/N
16 PT. DISCRETE
120VAC INPUT MODULE
RACK 1 / SLOT 4
1746-IA16
IN-0348
31-3
41-4
N 1B
120VAC
1B
BIOSOLIDS
INCLINE
SCREW CONV.
CONV-341-02
ZERO SPEED
L1 1-5
1-6L2/N 71-7 81-8
N
IN-1349
BIOSOLIDS
REVERSING
SCREW CONV.
CONV-351-01
ZERO SPEED
45A
L1 25FP900-1-45A
L2/N N
IN-15363
1B
1B
45B
45C
45D
ER114 6
E-STOPCENTRIFUGE
CONTROL
PANEL 1
E-STOPCENTRIFUGE
CONTROL
PANEL 2 17 7
ESR1
ESR18
ESR2
ESR3
RESET
PB1
25FP900-3-38
25FP900-3-39
ESR241 25FP900-1-45B
25FP900-1-45C
25FP900-1-45D
CR
BRSF
CR
BRSR
N1
BRSF44
4325FP900-2-43
25FP900-2-44
BRSR4525FP900-2-45
25FP900-2-40
25FP900-2-39
25FP900-2-41
25FP900-2-42
TB-2
SCALE: NONE
EXIST. PLC RACK UPDATE
SHD 0/1
L
25FP900-8-6+
25FP900-8-6-
CR6
CR6
"RUN ENABLE" (DIIL)
(+24VD)
XAI
XD24
NO. DATE BY REVISION
NOT TO SCALE
THEN DRAWING IS
NOT MEASURE 1"
IF THIS BAR DOES
NOTICE
CHECKED
DRAWN
DESIGNED
PROJECT NO.: SCALE: DATE:P:
\P ro je ct s\
.9
1.
_M S A _N ew po rt _S ol id s_ C on ve ya nc e\
D W
G \1
9-
-O
R -E
-6 .d w g
E-
8/
/2
:2
PM
R
O B
ER
TC
3.
1s
LM
S T ec h)
SHEET
20 1
OR CCB #196597 WA #INDUSSI880K9
Industrial Systems INC
(360) 952-8958
Vancouver, Washington 98682
Fax:
Phone:
12119 NE 99th Street e-mail: is@industrialsystems-inc.com
Suite #2090
(360) 718-7267
AK #1018436
PROJECT#:20.91.01
19-2673
E-6
AUGUST 2021
WWTP BIOSOLIDS
CONVEYOR
REPLACEMENT PROJECT
AS SHOWN of 18
CONTROL PANEL MODIFICATIONS
RSC
RSC
TBC
NORTH
CSXXX
NEMA 4
STAINLESS
STEEL
PUSHBUTTON
ENCLOSURE
30MM, NEMA 4
RED PILOT
INDICATOR
W/ NAMEPLATE
SOUTH
NORTH SOUTH
30MM, NEMA 4
PUSHBUTTON.
W/ NAMEPLATE
J
PRODUCT CONV.
SCALE: NONE
RISER DIAGRAMS
25SSL341
SPEED
SENSOR
25HS341B
PULL CORD
25FV341
SPRAY
WASH
TRUCK LOAD BELT CONV.
25HS341A
PULL CORD
M M
J
M
25HS351A
PULL CORD
25TJB4
J-BOX
25M341B
25FP341A
PRODUCT CONV. FLEX
CONTROL PANEL
25HS351B
PULL CORD
25SSL351
SPEED
SENSOR
25M341A
J
25M351
EXISTING
J
BIOSOLIDS CONV.
CON-341-01
CON-341-01
SPEED SENSOR
CON-341-01
PULL CORD B
M
25TJB4
J-BOX
MODIFIED
UNLABELED
J-BOX
BIOSOLIDS INCLINE CONV.
CON-341-02
CON-341-02
SPEED SENSOR
CON-341-01
PULL CORD A
M
M
60MCC3
ASD
CON-351-01
PULL CORD B
CON-351-01
PULL CORD A
CON-351-01
SPEED SENSOR
CS-351
REVERSIBLE CONV.
DIRECTION
CONTROL STATION
BIOSOLIDS
REVERSING CONV.
CON-351-01
KEY NOTES
1 EQUIPMENT TO BE REMOVED AND CONDUCTORS
TO BE PULLED BACK TO UNLABELED J-BOX,
COILED AND "SAFED-OFF". SOME CONDUCTORS
TO BE RE-USED FOR NEW REVERSIBLE
CONVEYOR CONTROL STATION.
EQUIPMENT TO BE REMOVED AND CONDUCTORS
TO BE PULLED BACK TO J-BOX 25TJB4, COILED
AND "SAFED-OFF".
EQUIPMENT, CONDUIT, AND CONDUCTORS TO BE
REMOVED.
EQUIPMENT AND CONDUIT TO BE REMOVED.
MOTOR CONDUCTORS TO BE EXTENDED FROM
J-BOX 25TJB4 FOR CONNECTION TO NEW
CONVEYOR MOTOR CON-341-01.
EQUIPMENT AND CONDUIT TO BE REMOVED.
MOTOR CONDUCTORS TO BE PULLED BACK TO
25TJB4 AND RE-USED FOR CONNECTION TO NEW
CONVEYOR MOTOR CON-341-02.
EQUIPMENT AND CONDUIT TO BE REMOVED.
CONTROL CONDUCTORS TO BE PULLED BACK TO
LOWER UNLABELED J-BOX AND RE-USED FOR
CONNECTION TO NEW CONVEYOR CON-341-02
SENSORS.
EQUIPMENT AND CONDUIT TO BE REMOVED.
CONTROL CONDUCTORS TO BE PULLED BACK TO
LOWER UNLABELED J-BOX AND RE-USED FOR
CONNECTION TO NEW CONVEYOR CON-341-01
SENSORS.
CONTROL STATION TO OPERATE IN PARALLEL
WITH SCADA. SCADA TO SELECT REVERSING
CONVEYOR DESTINATION AND THE CONTROL
STATION SHALL ALLOW THE OPERATOR TO
CHANGE THE DESTINATION LOCALLY VIA A
MOMENTARY INPUT TO THE PLC.
INSTALL NEW TERMINAL BLOCKS OR USE SPARES
WHERE AVAILABLE. DO NOT USE SPARE ANALOG
TERMINALS FOR DISCRETE CONNECTIONS.
EXISTING CONTROL PANEL LIGHTS (PRODUCT
CONVEYOR LEFT AND RIGHT) TO BE RE-LABELED
FOR NEW BIOSOLIDS REVERSING CONVEYOR.
SWAP OUT EXISTING GREEN LENS WITH RED.
SEE DRAWING E-6.
EXISTING CONTROL PANEL LIGHT (PRODUCT
CONVEYOR TRUCK LOADING POSITION) TO BE
RE-LABELED FOR NEW BIOSOLIDS REVERSING
CONVEYOR. SWAP OUT EXISTING GREEN LENS
WITH AMBER. SEE DRAWING E-6.
REPLACE EXISTING SPRAY WASH ON/OFF/AUTO
SELECTOR SWITCH WITH NEW OFF - ON/AUTO
2-POSITION SELECTOR FOR BIOSOLIDS
REVERSING CONVEYOR. WIRE TO SPARE INPUT.
SEE DRAWING E-6.
REPLACE EXISTING NAMEPLATES WITH
NAMEPLATES FOR NEW EQUIPMENT.
SCALE: NONE
CONSOLE INTERCONNECT WIRING
BIO REV SCREW CONV
CON-351-01
RUN NORTH
BIO REV SCREW CONV
CON-351-01
RUN SOUTH
1B
120VAC
TB-2
NORTH
SOUTH
1746-IA16
IN-4368
IN-5
16 PT. DISCRETE
120VAC INPUT MODULE
RACK 1 / SLOT 4
PASTEURIZATION
CONTROL PANEL 25FP900CS-351
369RUN SOUTH
16 PT. DISCRETE
RELAY OUT MODULE
RACK 1 / SLOT 8
1746-OW16
OUT 2
OUT 3
BIO REV SCREW CONV
CON-351-01
RUNNING NORTH
BIO REV SCREW CONV
CON-351-01
RUNNING SOUTH
XX
N1 1
2-32
2-33
2-34
G
NORTH
R
NORTH
G
SOUTH
R
SOUTH
XX
RUN NORTH
OUT 4416
1A
FAULT
GENERAL NOTES
1. EXISTING WIRING SHOWN IS BASED OFF RECORD
DRAWINGS PROVIDED BY THE OWNER.
CONTRACTOR TO VERIFY AND MODIFY/UPDATE AS
NEEDED TO PERFORM THE FUNCTIONS AS SHOWN.
BIO REV SCREW CONV
CON-351-01
FAULT
25FP900-N1
25FP900-N1
25FP900-N1
25JB1
J-BOX
25FP900
CONTROL
PANEL
CON-341-02
PULL CORD A
CON-341-02
PULL CORD B
60MCC3
60MCC3
25JB1
J-BOX
25FP900
CONTROL
PANEL
POWER ON
SYSTEM CONTROLS
EMERGENCY
STOP
AUTO START AUTO STOP
W R G
HORN
SILENCE
RESET
R
OFF
MAN AUTO
PAST/BYPASS
EURIZE
A
A
A
R
R
A
WARNING!
OPERATING HEAT SYSTEM WITHOUT
PROCESSING SLUDGE
WILL DAMAGE EQUIPMENT
LIME
SILO
HIGH LEVEL
REORDER
LEVEL
LOW LEVEL
BIOSOLIDS
REVERSING
CONV.
RUNNING
SOUTH
FAULT
RUNNING
NORTH
A
FAULT
R
ON
OFF ON/
AUTO
A
FAULT
R
ON
OFF ON/
AUTO
A
FAULT
R
ON
OFF ON/
AUTO
A
FAULT
R
ON
OFF ON/
AUTO
A
FAULT
R
ON
OFF ON/
AUTO
BIOSOLIDS
INCLINE
CONV.
PASTUERI
ZATION
VESSEL
THERMO
BLENDER
DEWATER
BELT
CONV.
LOWER CONTROL SWITCH AREACONTROL PANEL 25PF900
SIDE ELEVATION
BIOSOLIDS
CONV.
OFF ON/
AUTO
BIOSOLIDS
REVERSING
CONV.
UPPER CONTROL SWITCH AREA
NO. DATE BY REVISION
NOT TO SCALE
THEN DRAWING IS
NOT MEASURE 1"
IF THIS BAR DOES
NOTICE
CHECKED
DRAWN
DESIGNED
PROJECT NO.: SCALE: DATE:P:
\P ro je ct s\
.9
1.
_M S A _N ew po rt _S ol id s_ C on ve ya nc e\
D W
G \1
9-
-O
R -E
-7 .d w g
E-
8/ 2/
:4
PM
R O
B
ER
TC
3.
1s
LM
S T ec h)
SHEET
20 1
OR CCB #196597 WA #INDUSSI880K9
Industrial Systems INC
(360) 952-8958
Vancouver, Washington 98682
Fax:
Phone:
12119 NE 99th Street e-mail: is@industrialsystems-inc.com
Suite #2090
(360) 718-7267
AK #1018436
PROJECT#:20.91.01
19-2673
E-7
AUGUST 2021
WWTP BIOSOLIDS
CONVEYOR
REPLACEMENT PROJECT
AS SHOWN of 18
CONTROL PANEL MODIFICATIONS
& ELECTRICAL DETAILS
RSC
RSC
TBC
SCALE: NTS
CONTROL STATION DETAIL
SCALE: NTS
SWITCH & INDICATOR MODIFICATIONS
CONTROL PANEL 25FP900
LOCATION/ACCESSIBILITY
FIELD MOUNTED
1.
2.
FIELD OR LOCALLY MOUNTED.
1.
2.
3.
4.
MOUNTED.
VISIBLE ON VIDEO DISPLAY.
CENTRAL OR MAIN CONTROL ROOM.
DEVICE.
ACCESSIBLE TO AN OPERATOR AT
DEVICE OR CONSOLE.
CENTRAL OR MAIN CONTROL ROOM.
REAR OF PANEL OR CABINET
MOUNTED.
1.
2.
3. NOT VISIBLE ON VIDEO DISPLAY.
OPERATOR AT DEVICE OR CONSOLE.
NOT NORMALLY ACCESSIBLE TO AN4.
FIELD OR LOCAL CONTROL PANEL.
1.
2.
3. FRONT OF SECONDARY OR LOCAL
PANEL MOUNTED.
4. VISIBLE ON VIDEO DISPLAY.
ACCESSIBLE TO AN OPERATOR AT5.
DEVICE OR CONSOLE.
FIELD OR LOCAL CONTROL PANEL.2.
3.
4.
5.
REAR OF SECONDARY OR LOCAL
NOT VISIBLE ON VIDEO DISPLAY.
NOT NORMALLY ACCESSIBLE TO AN
OPERATOR AT DEVICE OR CONSOLE.
PANEL OR CABINET MOUNTED.
SECONDARY OR LOCAL CONTROL ROOM.
SECONDARY OR LOCAL CONTROL ROOM.
FRONT OF MAIN PANEL OR CONSOLE
PRIMARY LOCATION NORMALLY
ACCESSIBLE TO AN OPERATOR
PRIMARY LOCATION NORMALLY
INACCESSIBLE TO AN OPERATOR
AUXILIARY LOCATION NORMALLY
ACCESSIBLE TO AN OPERATOR
AUXILIARY LOCATION NORMALLY
INACCESSIBLE TO AN OPERATOR
ACCESSIBLE TO AN OPERATOR AT
GENERAL INSTRUMENT SYMBOLS
DISCRETE
INSTRUMENTS
SHARED
DISPLAY AND
CONTROL
(DCS)
PLC
DISCRETE
HARDWARE
INTERLOCK
INSTRUMENT IDENTIFICATION LETTERS
A
MEASURED OR
INITIATING VARIABLE
FIRST LETTER
MODIFIER
SUCCEEDING LETTERS
READOUT OR
PASSIVE FUNCTION
OUTPUT
FUNCTION MODIFIER
ALARM
B BURNER, FLAME, COMBUSTION USER'S CHOICE USER'S CHOICE USER'S CHOICE
ANALYSIS
C CONTROL,
D DIFFERENTIAL
E
F
VOLTAGE SENSOR (PRIMARY ELEMENT)
FLOW RATE
G GLASS,
VIEWING DEVICE
H HAND HIGH
I CURRENT (ELECTRICAL) INDICATE
J POWER SCAN
K TIME, TIME SCHEDULE CONTROL
L LOWLIGHTLEVEL
M USER'S CHOICE (TYPICALLY MOMENTARY MIDDLE,
INTERMEDIATE
N USER'S CHOICE USER'S CHOICE USER'S CHOICE USER'S CHOICE
O
P
Q
R
USER'S CHOICE ORIFICE, RESTRICTION
PRESSURE, VACUUM POINT (TEST) CONNECTION
QUANTITY OR HEAT DUTY
RADIATION RECORD
S
T
V
W
X
SPEED, FREQUENCY SAFETY SWITCH
TEMPERATURE TRANSMIT
VIBRATION, MECHANICAL ANALYSIS
WEIGHT, FORCE, TORQUE WELL
UNCLASSIFIED UNCLASSIFIED UNCLASSIFIED UNCLASSIFIEDX AXIS
Y Y AXISEVENT, STATE OR PRESENCE
Z Z AXISPOSITION, DIMENSION
RATIO
(FRACTION)
TIME RATE
INTEGRATE,
TOTALIZE
VALVE, DAMPER,
LOUVER
CONVERT
RELAY,
COMPUTE,
DRIVER,
ACTUATOR,
UNCLASSIFIED
FINAL CONTROL
ELEMENT
CLOSED
OPEN
USER'S CHOICE (TYPICALLY
CONDUCTIVITY - ELECTRICAL)
USER'S CHOICE (TYPICALLY
USER'S CHOICE OR GAUGING
DIVERT
MOISTURE OR HUMIDITY)
THROUGH
DENSITY OR SPECIFIC GRAVITY)
(DIMENSIONAL)
STATIONOF CHANGE
U MULTIVARIABLE MULTIFUNCTION MULTIFUNCTION MULTIFUNCTION
COMMAND
PRIMARY (AG & UG)
SECONDARY / UTILITY (AG & UG)
FUTURE OR EXISTING ON NEW P&IDs
JACKETED OR DOUBLE CONTAINMENT
INSTRUMENT LINE SYMBOLS
PIPING LINE SYMBOLS
INSTRUMENT SUPPLY OR
CONNECTION TO PROCESS
PNEUMATIC SIGNAL
ELECTRIC SIGNAL (ANALOG)
HYDRAULIC SIGNAL
CAPILLARY TUBE
ELECTROMAGNETIC, SONIC,
OPTICAL, OR NUCLEAR SIGNAL
SOFTWARE OR DATA LINK
MECHANICAL LINK
ELECTRIC SIGNAL (DISCRETE)
ABBREVIATIONS
AG ABOVE GROUND
ATM ATMOSPHERE
BYP BYPASS
CC CHEMICAL CLEANOUT
CL CENTERLINE
CO CLEANOUT
CONN CONNECTION
CSC CAR SEAL CLOSED
CSO CAR SEAL OPEN
CTR CENTER
DCS DISTRIBUTED CONTROL SYSTEM
DES DESIGN
DIA DIAMETER
DP DESIGN PRESSURE
D/P DIFFERENTIAL PRESSURE
DRN DRAIN
DT DESIGN TEMPERATURE
DWG DRAWING
(E) EXISTING
EL ELEVATION
ESD EMERGENCY SHUTDOWN
FOF FACE OF FLANGE
(F) FURNISHED
FC FAIL CLOSED
FI FAIL INDETERMINATE
FL FAIL LOCKED (LAST POSITION)
FLG FLANGE
FO FAIL OPEN
FP FULL PORT
FV FULL VACUUM
GO GEAR OPERATED
GR GRADE
HC HOSE CONNECTION
HDR HEADER
HH HAND HOLE
HOA HAND/OFF/AUTOMATIC
HP HIGH PRESSURE
HPT HIGH POINT
IAS INSTRUMENT AIR SUPPLY
LC LOCKED CLOSED
LCP LOCAL CONTROL PANEL
LO LOCKED OPEN
LP LOW PRESSURE
LPT LOW POINT
MTL MATERIAL
MAX MAXIMUM
MCC MOTOR CONTROL CENTER
MCP MAIN CONTROL PANEL
MIN MINIMUM
MOV MOTOR OPERATED VALVE
MW MANWAY
NC NORMALLY CLOSED
NNF NORMALLY NO FLOW
NO NORMALLY OPEN
NOZ NOZZLE
O/C OPEN/CLOSE
O/O ON/OFF
OIT OPERATOR INTERFACE TERMINAL
OP OUTPUT
OVHD OVERHEAD
PLC PROGRAMMABLE LOGIC CONTROLLER
PRESS PRESSURE
PV PROCESS VARIABLE
(R) RELOCATED
REQD REQUIRED
RIO REMOTE I/O PANEL
RTD RESISTANCE TEMPERATURE DETECTOR
SC SAMPLE CONNECTION
SCADA SUPERVISORY CONTROL AND
DATA ACQUISITION
SCH SCHEDULE
SD SHUTDOWN
SG SPECIFIC GRAVITY
SIS SAFETY INSTRUMENTED SYSTEM
SO STEAM OUT
SP SET POINT
SS STAINLESS STEEL S/S or START/STOP
STD STANDARD
T/C THERMOCOUPLE
TDH TOTAL DIFFERENTIAL HEAD
TEMP TEMPERATURE
THRD THREADED
TSO TIGHT SHUT-OFF
TYP TYPICAL
UG UNDERGROUND
VNT VENT
VAC VACUUM
VB VORTEX BREAKER
VFD VARIABLE FREQUENCY DRIVE
W/ WITH
W/O WITHOUT
HS
ID
HOA
1A
TYPICAL INSTRUMENT TAG NUMBERS & DESIGNATION
INSTRUMENT TYPE
SEE 'INSTRUMENT IDENTIFICATION LETTERS'
ADDITIONAL INSTRUMENT IDENTIFICATION
SEE 'HAND SWITCH ABBREVIATIONS'
INSTRUMENT IDENTIFICATION
(DIGITS DENOTE ASSOCIATED AREA)
WHEN USED, LETTER DISTINGUISHES BETWEEN
MULTIPLE SIMILAR DEVICES
USED WHEN MULTIPLE TRAINS ARE USED AND
REPRESENTS THE TRAIN NUMBER
HAND SWITCH ABBREVIATIONS
TYPICAL EQUIPMENT TAG NUMBERS & DESIGNATION
FLOW STREAM IDENTIFIERS
B.
CONNECTOR NUMBER
CONNECTOR NUMBER
C. UTILITY CONNECTOR
PRIMARY/SECONDARY LINES AND INSTRUMENT SIGNAL CONNECTOR
A.
CONNECTOR NUMBER
OFF-PLOT CONNECTOR
D. TIE-IN SYMBOL
TIE-IN NUMBER
T
XXX
XX
P&ID No
OFF-PAGE CONNECTORS AND TIE-IN SYMBOL
SERVICE DESCRIPTION
ORIGIN /DESTINATION
XX P&ID No
XX P&ID No
SERVICE DESCRIPTION
ORIGIN/DESTINATION
INPUT / OUTPUT SIGNALS
ANALOG INPUT (AI)
DISCRETE INPUT (DI)
ANALOG OUTPUT (AO)
DISCRETE OUTPUT (DO)
MEASURED VARIABLE OR OUTPUT FUNCTION FROM 'INSTRUMENT
IDENTIFICATION LETTERS' TABLE
AO = AUTO/OFF
AM = AUTO/MANUAL
CM = COMPUTER/MANUAL
CL = COMPUTER LOCAL
ES = EMERGENCY STOP
FR = FORWARD/REVERSE
FOR = FORWARD/OFF/REVERSE
FS = FAST/SLOW
FOS = FAST/OFF/SLOW
HA = HAND/AUTO
HIM = HUMAN INTERFACE MODULE
HOA = HAND/OFF/AUTOMATIC
LLS = LEAD/LAG/STANDBY
LOC = LOCAL/OFF/COMPUTER
LOR = LOCAL/OFF/REMOTE
LOS = LOCKOUT/STOP
LA = LOCAL/AUTO
LR = LOCAL/REMOTE
OC = OPEN/CLOSE
OCA = OPEN/CLOSE/AUTO
OO = ON/OFF
OOA = ON/OFF/AUTO
OSC = OPEN/STOP/CLOSE
RES = RESET
RF = RUN/FAULT
RSL = RAISE/STOP/LOWER
SS = START/STOP
SOR = START/OFF/RESET
V/B = VFD/BYPASS
AER = AERATOR
BIN = BIN
BL = BLOWER
CEL = CELL
CLA = CLARIFIER
CLS = CLASSIFIER
CND = CONDENSATE TRAP
CON = CONVEYOR
CMP = COMPRESSOR
DIF = DIFFUSER
DIG = DIGESTER
DIS = DISINFECTION UNIT
FED = FEEDER
FLT = FILTER
HEX = HEAT EXCHANGER
MIX = MIXER
PMP = PUMP
PRS = PRESS
SCN = SCREEN
SDG = SLIDE GATE
SL = SLUICE GATE
SMP = SUMP
THK = THICKENER
TNK = TANK
WEL = WET WELL
ABE = AERATION BASIN EFFLUENT
BD = BASIN DRAIN
CS = COMBINED SLUDGE
CAS = CAUSTIC SODA
DR = DRAIN
DS = DEWATERED SLUDGE
FBW = FILTER BACKWASH
FE = FINAL EFFLUENT
GR = GRIT
ICE = INTERMEDIATE CLARIFIER
EFFLUENT
LPA = LOW PRESSURE AIR
ML = MIXED LIQUOR
NPW = NON POTABLE WATER
PE = PRIMARY EFFLUENT
PI = PRIMARY INFLUENT
PLE = PLANT EFFLUENT
PS = PRIMARY SLUDGE
RAS = RETURN ACTIVATED SLUDGE
RS = RAW SEWAGE
SSL = SECONDARY SLUDGE
SCM = SCUM
SSCM = SECONDARY SCUM
SCRN = SCREENINGS
SE = SECONDARY EFFLUENT
TE = TERTIARY EFFLUENT
TWAS = THICKENED WASTE
ACTIVATED SLUDGE
UW = UTILITY WATER
WAS = WASTE ACTIVATED SLUDGE
BL-110-01
EQUIPMENT TYPE
(SEE CHART ABOVE)
EQUIPMENT ID
UNIQUE IDENTIFIER
PROCESS EQUIPMENT
SCREW CONVEYOR
NO. DATE BY REVISION
NOT TO SCALE
THEN DRAWING IS
NOT MEASURE 1"
IF THIS BAR DOES
NOTICE
CHECKED
DRAWN
DESIGNED
PROJECT NO.: SCALE: DATE:P:
\P ro je ct s\
.9
1.
_M S A _N ew po rt _S ol id s_ C on ve ya nc e\
D W
G \1
9-
-O
R -P
ID
1.
dw g P&
ID
-1
/2
/2
1:
P
M R
O B
ER
TC
3.
1s
LM
S T ec h)
SHEET
20 1
OR CCB #196597 WA #INDUSSI880K9
Industrial Systems INC
(360) 952-8958
Vancouver, Washington 98682
Fax:
Phone:
12119 NE 99th Street e-mail: is@industrialsystems-inc.com
Suite #2090
(360) 718-7267
AK #1018436
PROJECT#:20.91.01
19-2673
P&ID-1
AUGUST 2021
WWTP BIOSOLIDS
CONVEYOR
REPLACEMENT PROJECT
AS SHOWN of 18
P&ID NOTES, SYMBOLS,
LEGEND AND ABBREVIATIONS
RSC
RSC
TBC
PLC 25PLC1
(PASTEURIZATION SYSTEM
CONTROL PANEL 25FP900)
SCADA
60MCC3
FIELD
XA
351-1H
FAULT
SC
351-1
SPD
CTRL
XA
351-1H
SC
351-1
VFD
351-1
NORTH STORAGE BAY SOUTH STORAGE BAY
TO TRENCH DRAIN
CON-341-01
BIOSOLIDS SCREW
CONVEYOR
CON-341-02
BIOSOLIDS INCLINED
SCREW CONVEYOR
CON-351-01
BIOSOLIDS REVERSIBLE
SCREW CONVEYOR
PASTEURIZATION ROOM
- EXIST
DS
FROM PASTEURIZATION VESSEL
YI
341-1
R
ON
START
CMD FAULTRUN'G
RUNTIME
TOTAL
STARTS
XA
341-1
QI
341-1
KI
341-1
YI
341-1
YC
341-1
YI
341-1
YC
341-1
MS
341-1
- EXIST
DS
FROM CENTRIFUGE
HS
341-1A
ES
SSL
341-1
SSL
341-1
SSL
341-2
ZERO
SPEED
SIL
341-1
YI
341-2
R
ONMS
341-2
HS
341-2A
ES
PULL
CORD
PULL
CORD
PULL
CORD
25FP900
PASTEURIZATION SYSTEM
CONTROL CONSOLE
HS
341-1B
ES
HS
351-1A
ES
HS
351-1B
ES
HS
341-2B
ES
KEYED NOTES
PULL CORDS WITH E-STOP
SWITCH LOCATED ON BOTH
SIDES OF CONVEYOR.
EXISTING INDICATOR TO
BE RE-USED. COLOR OF
LENSES TO BE CHANGED.
EXISTING SPRAY WASH
HAND SWITCH TO BE
REPLACED AND WIRED TO
SPARE INPUT.
VENDOR PROVIDED
EQUIPMENT.
SSL
351-1
YI
351-1C
R
NORTH YI
351-1D
R
SOUTH
HS
351-1C
NORTH HS
351-1D
SOUTH
CS-351
SSL
351-1
ZERO
SPEED
SIL
351-1
RUN'G
FWD
RUNTIME
QI
351-1
KI
351-1
YI
351-1A
YI
351-1A
TOTAL
STARTS
YC
351-1A
YC
351-1A
START
FWD
CMD
NORTH
SELECT
HS
351-1C
HS
351-1C
SOUTH
SELECT
HS
351-1D
HS
351-1D
RUN'G
NORTH
YI
351-1C
YI
351-1C
RUN'G
SOUTH
YI
351-1D
YI
351-1D
RUN'G
REV
YI
351-1B
YI
351-1B
YI
351-1A
R
FWD YI
351-1B
R
REV
YI
351-1H
R
FAULT
HS
341-1
O/OA
HS
341-1
HS
341-1
YI
341-1
A
FAULTYI
341-1
R
ON
XA
341-1
YI
341-1
SSL
341-1
ZERO
SPEED
SIL
341-1
START
CMD RUN'G
RUNTIME
TOTAL
STARTS
QI
341-2
KI
341-2
YI
341-2
YC
341-2
YI
341-2
YC
341-2
FAULT
XA
341-2
HS
341-2
O/OA
OFF-
ON/AUTO
HS
341-2
HS
341-2
YI
341-2
A
FAULTYI
341-2
R
ON
XA
341-2
YI
341-2
OFF-
ON/AUTO
HS
351-1E
O/OA
OFF-
ON/AUTO
HS
351-1E
HS
351-1E
YC
351-1B
YC
351-1B
START
REV
CMD FAULT
XA
351-1G
YI
351-1G
A
FAULT
XA
351-1G
YI
351-1F
R
RUN
NORTH
YI
351-1F
YI
351-1E
R
RUN
SOUTH
YI
351-1E
2 2 2
NO. DATE BY REVISION
NOT TO SCALE
THEN DRAWING IS
NOT MEASURE 1"
IF THIS BAR DOES
NOTICE
CHECKED
DRAWN
DESIGNED
PROJECT NO.: SCALE: DATE:P:
\P ro je ct s\
.9
1.
_M S A _N ew po rt _S ol id s_ C on ve ya nc e\
D W
G \1
9-
-O
R -P
ID
2.
dw g P&
ID
-2
/2
/2
1:
P
M R
O B
ER
TC
3.
1s
LM
S T ec h)
SHEET
20 1
OR CCB #196597 WA #INDUSSI880K9
Industrial Systems INC
(360) 952-8958
Vancouver, Washington 98682
Fax:
Phone:
12119 NE 99th Street e-mail: is@industrialsystems-inc.com
Suite #2090
(360) 718-7267
AK #1018436
PROJECT#:20.91.01
19-2673
P&ID-2
AUGUST 2021
WWTP BIOSOLIDS
CONVEYOR
REPLACEMENT PROJECT
AS SHOWN of 18
P&ID
BIOSOLIDS CONVEYANCE
RSC
RSC
TBC
| 19-2673-OR-G-G-1 |
| G-1 |
| 19-2673-OR-G-G-2 |
| G-2 |
| 19-2673-OR-C-C-1 |
| C-1 |
| 19-2673-OR-M-1-M-1 |
| M-1 |
| 19-2673-OR-M-2-M-2 |
| M-2 |
| 19-2673-OR-M-3-4-M-3 |
| M-3 |
| 19-2673-OR-M-3-4-M-4 |
| M-4 |