WJ Hooper AGS Tank Addendum No_1.docx

DOCX document 403 KB Posted

Attached to
W. J. Hooper WPP Above-Ground Storage Tank Reconditioning
Solicitation number
PE-63125-NONST-2024-000000019
Issued by
Clayton County, Georgia

About this file

This document is an addendum to a state and local contract opportunity issued by the Clayton County Water Authority for the W. J. Hooper WPP Above-Ground Storage Tank Reconditioning project. The addendum revises the painting specifications in Division 2 Section 4, with the changes highlighted in yellow. Bidders must acknowledge receipt of this addendum and include it in their bid responses. The project scope involves the reconditioning of the above-ground storage tank at the W.J. Hooper Water Production Plant. Bids are due by July 2, 2024, with a non-mandatory pre-bid virtual meeting on June 20, 2024 and a mandatory site visit on the same date. The contract will be awarded to the successful bidder following the bid opening.

The addendum provides detailed paint system requirements, including surface preparation, paint types, and minimum dry film thicknesses for the exterior and interior tank and piping surfaces. The paint system options and associated product information are provided for Tnemec, Induron, and Sherwin-Williams paint products. The total dry film thickness requirement ranges from 10.0 to 15.5 mils depending on the selected paint system.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Clayton County Water Authority May 2024 W. J. Hooper WPP Above-Ground Storage Tank Reconditioning

Division 4 Specifications Section 2: Painting

REVISIONS:

1. Please revise Division 2 Section 4 Painting, page 4-2.8 with the revised version provided with this addendum. Revisions are highlighted in yellow.

Acknowledgment of receipt of this addendum must be signed and included in your bid response.

COMPANY NAME

SIGNATURE

DATE

1600 Battle Creek Road, Morrow, GA 30260 W. J. Hooper WPP Above-Ground Storage Tank Reconditioning

ADDENDUM #

DATE
Tuesday, June 18, 2024
BID NUMBER
2024-WP-18
BID OPENING DATE
July 2, 2024
PRE-BID MEETING DATE
Thursday, June 20, 2024

ADDENDUM MUST BE SIGNED AND INCLUDED IN YOUR RESPONSE TO THE RFB.

2.010 Paint Types

A. The following surfaces shall have the types of paints scheduled below applied at the dry film thickness (DFT) in mils per coat noted in the paint schedule below:

Surface Preparation: SSPC-SP6 Type: Epoxy/Polyurethane Use: Exterior Tank and Piping Overcoat, except Ductile Iron Pipe

Coat Minimum Dry Film Thickness ‘DFT’ (Mils)

Tnemec

Induron

Sherwin-Williams

Prime (spot repair)

Manufacturer specific
Series 135 Chembuild

(3.0 to 4.0 mils) Induramastic 85 (3.0 to 5.0 mils) Macropoxy

646 FC

(3.0-4.0 mils)

Intermediate
Manufacturer specific
Series 135 Chembuild

(3.0 to 4.0 mils) Induramastic 85 (3.0 to 5.0 mils) Macropoxy

646 FC

(3.0-4.0 mils)

Finish
Manufacturer specific
21074U Endura-Shield II

(2.0 to 3.0 mils) 6600 Indurethane Plus (2.0 to 3.0 mils) Acrolon Ultra (2.0 to 3.0 mils)

System

Surface Preparation: SSPC-SP10
Type: Zinc/EpoxySurface Profile: 2.0 to 3.0 mils

Use: Interior Tank and Piping, except Ductile Iron Pipe

Coat Minimum Dry Film Thickness ‘DFT’ (Mils)

Tnemec

Induron

Sherwin-Williams

Prime
Manufacturer specific
Series 91-H2O

(2.5 to 3.5 mils) Indurazinc MC67 (2.5 to 3.5 mils) Corothane I Galvapac 2K (2.0 to 3.0 mils)

Stripe
Manufacturer specific
1N140Pota-Pox Plus

(2.0 to 3.0 mils)

3PE-70/RC-70

(2.0 to 3.0 mils) Macropoxy 5500LT (2.0 to 3.0 mils)

Intermediate
Manufacturer specific
1N140Pota-Pox Plus

(4.0 to 6.0 mils)

3PE-70/RC-70

(4.0 to 6.0 mils) Macropoxy 5500LT (4.0 to 6.0 mils)

Finish
Manufacturer specific
1N140Pota-Pox Plus

(4.0 to 6.0 mils)

3PE-70/RC-70

(4.0 to 6.0 mils) Macropoxy 5500LT (4.0 to 6.0 mils)

System
Total DFT
10.5 to 15.5 mils
10.5 to 15.5 mils
10.0 to 15.0 mils
1Add Series 44-700 Epoxy Accelerator when the surface temperature is below 50F.
2Add Series 44-710 Urethane Accelerator when the surface temperature is below 50F.

4-.2.8R image1.jpeg

File details come from the government source that posted it. Updated .