This document outlines a federal contract opportunity to construct a wildlife barn. The United States Department of Agriculture Agricultural Research Service is seeking to award a firm fixed price construction contract between $500,000 to $1,000,000 to build a wildlife barn in Edinburg, Texas. Draft drawings and specifications are attached. The solicitation number is 12805B23R0023 and the North American Industry Classification System code is 236220 for commercial and institutional building construction up to $45 million. The request for proposal is anticipated to be issued on or around July 1, 2023, with a to be determined completion timeframe for the resulting contract. Offerors should monitor sam.gov for the release of the RFP package and any amendments. Registration in the System for Award Management is required.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Wildlife Barn Specifications-DRAFT.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ARCHITECTS
MEP ENGINEERS
STRUCTURAL ENGINEERS
CIVIL ENGINEERS
THESE DOCUMENTS ARE FOR INTERIM
REVIEW AND ARE "NOT FOR REGULATORY
APPROVAL, PERMITTING, OR
CONSTRUCTION."
DATE: 2022-04-13
ARCHITECT OF RECORD: Jane E Baughman
STATE: TEXAS
REGISTRATION NO.: 21091
201 West 5th St.
Suite 1100 Austin, TX 78701 512 808 1000 eypae.com
EYP, Inc.
EYP, Inc.
EYP, Inc.
04/13/2022
Wildlife Barn
Cattle Fever Tick Research Laboratory (CFTRL), Moore Field, Edinburge TX
100% CONSTRUCTION DOCUMENTS
USDA
6021060.02
/1
3/
0% C
O N
S T
R U
C T
IO
N
D O
C U
M E
N T
S W ild lif e B ar n
0.
SETTY
WALTER P MOORE
MARTINEZ MOORE
2022DRAFT
“D”
X:
\Y
\2
1\
7-
U
SD
A W et L ab a nd B ar ns
\3 -P ro du ct io n\
-S he et s\
Y0 3-
7-
-G N
.d w g Ap r 1 3,
- 1
1:
am
SAFETY & HEALTH
REAL PROPERTY
DESIGNER
CHECKED BY
PROJECT MANAGER
PPM
EPM
SETTY
DATE
A D
USDA S
U
NO. DATE BY
Service Research Agricultural
REVISIONS
DWG. NO
DRAWN BY
SOLICITATION NO.
Original drawing size is 30"x42"; Scale entities accordingly if reduced/enlarged.
1465 NORTHSIDE DRIVE, SUITE 220B
ATLANTA, GEORGIA 30318
P: 706-248-7165 www. .com
TM
PROJECT NUMBER:SIGQ212911.14
WILDLIFE BARN
02/25/2022 50% DOCUMENTS
04/13/2022
AJH
SHEET NAME
DESCRIPTION
03/18/2022 90% DOCUMENTS2
04/13/2022 100% CD FOR REVIEW3
NRS
AJH
VDA
DRAFT
X:
\Y
\2
1\
7-
U
SD
A W et L ab a nd B ar ns
\3 -P ro du ct io n\
-S he et s\
Y0 3-
7-
-G N
.d w g Ap r 1 3,
- 1
1:
am
SAFETY & HEALTH
REAL PROPERTY
DESIGNER
CHECKED BY
PROJECT MANAGER
PPM
EPM
SETTY
DATE
A D
USDA S
U
NO. DATE BY
Service Research Agricultural
REVISIONS
DWG. NO
DRAWN BY
SOLICITATION NO.
Original drawing size is 30"x42"; Scale entities accordingly if reduced/enlarged.
1465 NORTHSIDE DRIVE, SUITE 220B
ATLANTA, GEORGIA 30318
P: 706-248-7165 www. .com
TM
PROJECT NUMBER:SIGQ212911.14
WILDLIFE BARN
02/25/2022 50% DOCUMENTS
04/13/2022
AJH
SHEET NAME
DESCRIPTION
03/18/2022 90% DOCUMENTS2
04/13/2022 100% CD FOR REVIEW3
NRS
AJH
5'
20.9'
.9
12'
6'
147'
139.8'
.1
273.8'
2.
5'
342.3'
4'
X:
\Y
\2
1\
7-
U
SD
A W et L ab a nd B ar ns
\3 -P ro du ct io n\
-S he et s\
Y0 3-
7-
-D M
.d w g Ap r 1 3,
- 1
1:
am
SAFETY & HEALTH
REAL PROPERTY
DESIGNER
CHECKED BY
PROJECT MANAGER
PPM
EPM
SETTY
DATE
A D
USDA S
U
NO. DATE BY
Service Research Agricultural
REVISIONS
DWG. NO
DRAWN BY
SOLICITATION NO.
Original drawing size is 30"x42"; Scale entities accordingly if reduced/enlarged.
1465 NORTHSIDE DRIVE, SUITE 220B
ATLANTA, GEORGIA 30318
P: 706-248-7165 www. .com
TM
PROJECT NUMBER:SIGQ212911.14
WILDLIFE BARN
02/25/2022 50% DOCUMENTS
04/13/2022
AJH
SHEET NAME
DESCRIPTION
03/18/2022 90% DOCUMENTS2
04/13/2022 100% CD FOR REVIEW3
NRS
AJH
VDA
Key Notes:
Sheet Notes:
Construction Notes:
PROPOSED DEER
WORKING FACILITY
FFE-226.00
125' 17'
31.2'
.4
R5'
R5'
136.8'
6'
R8'
8'
' 17.3'
CONTRACTOR TO PROVIDE SEPARATE ESTIMATE
FOR THE DRIVEWAY AND THE STORM PIPE
X:
\Y
\2
1\
7-
U
SD
A W et L ab a nd B ar ns
\3 -P ro du ct io n\
-S he et s\
Y0 3-
7-
-L A.
dw g
Ap r 1
3,
- 1 1:
am
SAFETY & HEALTH
REAL PROPERTY
DESIGNER
CHECKED BY
PROJECT MANAGER
PPM
EPM
SETTY
DATE
A D
USDA S
U
NO. DATE BY
Service Research Agricultural
REVISIONS
DWG. NO
DRAWN BY
SOLICITATION NO.
Original drawing size is 30"x42"; Scale entities accordingly if reduced/enlarged.
1465 NORTHSIDE DRIVE, SUITE 220B
ATLANTA, GEORGIA 30318
P: 706-248-7165 www. .com
TM
PROJECT NUMBER:SIGQ212911.14
WILDLIFE BARN
02/25/2022 50% DOCUMENTS
04/13/2022
AJH
SHEET NAME
DESCRIPTION
03/18/2022 90% DOCUMENTS2
04/13/2022 100% CD FOR REVIEW3
NRS
AJH
VDA
Key Notes:
Sheet Notes:
Sheet Notes:
FFE-226.00
PROPOSED 266LF~1.5" PVC
WATER LINE
PROPOSED 78LF~18" RCP CULVERT
PIPE CLASS IV @1.00%
PROVIDE 2 SETS : 4 # 3 / 0
AWG G IN 2 1/2" C
(REF:ELEC)
PROPOSED 153LF~1.5" PVC
WATER LINE
SAFETY END TREATMENTS
SAFETY END TREATMENTS
REF: CONSTRUCTION NOTES
FOR WATER LINE DEPTH
10'
MIN
REF: CONSTRUCTION NOTES
FOR SANITARY DEPTH
PROP 81LF~3" C-900 PVC SDR26
SAN SWR @ 0.50%
PROP 33LF~3" C-900 PVC SDR26
SAN SWR @ 0.50%
5'
X:
\Y
\2
1\
7-
U
SD
A W et L ab a nd B ar ns
\3 -P ro du ct io n\
-S he et s\
Y0 3-
7-
-U
TI
L.
dw g Ap r 1 3,
- 1
1:
am
SAFETY & HEALTH
REAL PROPERTY
DESIGNER
CHECKED BY
PROJECT MANAGER
PPM
EPM
SETTY
DATE
A D
USDA S
U
NO. DATE BY
Service Research Agricultural
REVISIONS
DWG. NO
DRAWN BY
SOLICITATION NO.
Original drawing size is 30"x42"; Scale entities accordingly if reduced/enlarged.
1465 NORTHSIDE DRIVE, SUITE 220B
ATLANTA, GEORGIA 30318
P: 706-248-7165 www. .com
TM
PROJECT NUMBER:SIGQ212911.14
WILDLIFE BARN
02/25/2022 50% DOCUMENTS
04/13/2022
AJH
SHEET NAME
DESCRIPTION
03/18/2022 90% DOCUMENTS2
04/13/2022 100% CD FOR REVIEW3
NRS
AJH
VDA
Key Notes:
Sheet Notes:
General Construction Notes:
FFE-226.00
X:
\Y
\2
1\
7-
U
SD
A W et L ab a nd B ar ns
\3 -P ro du ct io n\
-S he et s\
Y0 3-
7-
-S W
PP
P.
dw g
Ap r 1
3,
- 1 1:
am
SAFETY & HEALTH
REAL PROPERTY
DESIGNER
CHECKED BY
PROJECT MANAGER
PPM
EPM
SETTY
DATE
A D
USDA S
U
NO. DATE BY
Service Research Agricultural
REVISIONS
DWG. NO
DRAWN BY
SOLICITATION NO.
Original drawing size is 30"x42"; Scale entities accordingly if reduced/enlarged.
1465 NORTHSIDE DRIVE, SUITE 220B
ATLANTA, GEORGIA 30318
P: 706-248-7165 www. .com
TM
PROJECT NUMBER:SIGQ212911.14
WILDLIFE BARN
02/25/2022 50% DOCUMENTS
04/13/2022
AJH
SHEET NAME
DESCRIPTION
03/18/2022 90% DOCUMENTS2
04/13/2022 100% CD FOR REVIEW3
NRS
AJH
VDA
LEGEND
\2
1\
7-
U
SD
A W et L ab a nd B ar ns
\3 -P ro du ct io n\
-S he et s\
Y0 3-
7-
-S W
PP
P.
dw g
Ap r 1
3,
- 1 1:
am
SAFETY & HEALTH
REAL PROPERTY
DESIGNER
CHECKED BY
PROJECT MANAGER
PPM
EPM
SETTY
DATE
A D
USDA S
U
NO. DATE BY
Service Research Agricultural
REVISIONS
DWG. NO
DRAWN BY
SOLICITATION NO.
Original drawing size is 30"x42"; Scale entities accordingly if reduced/enlarged.
1465 NORTHSIDE DRIVE, SUITE 220B
ATLANTA, GEORGIA 30318
P: 706-248-7165 www. .com
TM
PROJECT NUMBER:SIGQ212911.14
WILDLIFE BARN
02/25/2022 50% DOCUMENTS
04/13/2022
AJH
SHEET NAME
DESCRIPTION
03/18/2022 90% DOCUMENTS2
04/13/2022 100% CD FOR REVIEW3
NRS
AJH
VDA
FENCETP
CURLEX® CHANNEL
APPLICATION DETAIL
Curlex® Staple Pattern Guide For 8 ft wide Curlex Erosion Control Blankets
Adjust horizontal staple spacing for 4 ft and 16 ft wide Curlex Erosion Control Blankets
Staple Pattern
Channel Application
C
< 10.0 lb/ft² (480 Pa) Shear Stress < 17 ft/sec (5.2 m/sec) Velocity
= Staple Placement Notes:
1. Recommended staples are minimum 4 in biodegradable E-Staple®, as provided by American Excelsior Company, or 6 in wire for cohesive soils and 6 in biodegradable E-staple®, as provided by American Excelsior Company, or 8 in wire for non-cohesive soils.
2. For best results insert staples so heads are parallel to the flow of water.
3. Adjust staple pattern so staples are placed in critical channel points (e.g. slope interface, channel bottom) as illustrated below.
1.9 Staples/yd²
C
2 ft 4 ft
3 ft
4 ft
Critical channel points are circled.
\2
1\
7-
U
SD
A W et L ab a nd B ar ns
\3 -P ro du ct io n\
-S he et s\
Y0 3-
7-
-G N
.d w g Ap r 1 3,
- 1
1:
am
SAFETY & HEALTH
REAL PROPERTY
DESIGNER
CHECKED BY
PROJECT MANAGER
PPM
EPM
SETTY
DATE
A D
USDA S
U
NO. DATE BY
Service Research Agricultural
REVISIONS
DWG. NO
DRAWN BY
SOLICITATION NO.
Original drawing size is 30"x42"; Scale entities accordingly if reduced/enlarged.
1465 NORTHSIDE DRIVE, SUITE 220B
ATLANTA, GEORGIA 30318
P: 706-248-7165 www. .com
TM
PROJECT NUMBER:SIGQ212911.14
WILDLIFE BARN
02/25/2022 50% DOCUMENTS
04/13/2022
AJH
SHEET NAME
DESCRIPTION
03/18/2022 90% DOCUMENTS2
04/13/2022 100% CD FOR REVIEW3
NRS
AJH
\2
1\
7-
U
SD
A W et L ab a nd B ar ns
\3 -P ro du ct io n\
-S he et s\
Y0 3-
7-
-G N
.d w g Ap r 1 3,
- 1
1:
am
SAFETY & HEALTH
REAL PROPERTY
DESIGNER
CHECKED BY
PROJECT MANAGER
PPM
EPM
SETTY
DATE
A D
USDA S
U
NO. DATE BY
Service Research Agricultural
REVISIONS
DWG. NO
DRAWN BY
SOLICITATION NO.
Original drawing size is 30"x42"; Scale entities accordingly if reduced/enlarged.
1465 NORTHSIDE DRIVE, SUITE 220B
ATLANTA, GEORGIA 30318
P: 706-248-7165 www. .com
TM
PROJECT NUMBER:SIGQ212911.14
WILDLIFE BARN
02/25/2022 50% DOCUMENTS
04/13/2022
AJH
SHEET NAME
DESCRIPTION
03/18/2022 90% DOCUMENTS2
04/13/2022 100% CD FOR REVIEW3
NRS
AJH
TM
Original drawing size is 30"x42"; Scale entities accordingly if reduced/enlarged.
SAFETY & HEALTH
REAL PROPERTY
DESIGNER
CHECKED BY
PROJECT MANAGER
PPM
EPM
SETTY
DATE
A
D
USDA S
U
NO. DATE BY
Service Research Agricultural
REVISIONS
DWG. NO
DRAWN BY
SOLICITATION NO.
1465 NORTHSIDE DRIVE, SUITE 220B
ATLANTA, GEORGIA 30318
P: 706-248-7165 www. .com
PROJECT NUMBER: SIGQ212911.14
03/18/2022 90% DOCUMENTS
WILDLIFE BARN
SHEET NAME
DESCRIPTION
04/13/2022 100% DOCUMENTS2
JUSTIN STOLZE, P.E.
PE 130920
NOT FOR CONSTRUCTION
NOT FOR PERMIT
TA
TA
GENERAL NOTES S-001
PART I - DESIGN CRITERIA
A. GENERAL BUILDING CODE
1. THE CONSTRUCTION DOCUMENTS ARE BASED ON THE REQUIREMENTS OF THE 2015
INTERNATIONAL BUILDING CODE.
B. DEAD LOADS
1. HANGING CEILING AND MECHANICAL LOADS: AN ALLOWANCE OF 5 PSF HAS BEEN
MADE FOR HANGING CEILING AND MECHANICAL/ELECTRICAL EQUIPMENT LOADS.
C. LIVE LOADS
1. DESIGN LIVE LOADS ARE BASED ON THE MORE RESTRICTIVE OF THE
UNIFORM LOAD LISTED BELOW OR THE CONCENTRATED LOAD LISTED ACTING OVER AN
AREA 2.5 FEET SQUARE.
a. BUILDING ROOF: 20 PSF
2. REDUCTION OF LIVE LOADS: LIVE LOADS HAVE BEEN REDUCED USING THE
STANDARD PROCEDURE FROM THE BUILDING CODE.
D. WIND LOADS
1. WIND PRESSURES ARE BASED ON THE PROVISIONS OF THE FLORIDA
BUILDING CODE WHICH REFER TO THE AMERICAN SOCIETY OF CIVIL ENGINEERS,
MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER STRUCTURES, ASCE 7-10 AND
THE FOLLOWING CRITERIA:
a. ULTIMATE DESIGN WIND SPEED (VULT): 123 MPH (3 SECOND GUST)
b. NOMINAL DESIGN WIND SPEED (VASD): 108 MPH (3-SECOND GUST)
c. BUILDING RISK CATEGORY: I
d. WIND EXPOSURE CATEGORY: C
1. INTERNAL PRESSURE COEFFICIENT (GCPI): +0.55/-0.55
2. THIS STRUCTURE IS LOCATED IN A WIND-BORNE DEBRIS REGION AND IS
DESIGNED AS PARTIALLY ENCLOSED. IMPACT-RESISTANT EXTERIOR GLAZING OR
IMPACT-RESISTANT COVERING OVER EXTERIOR GLAZING IS REQUIRED FOR GLAZING
PER SECTION 1609.1.2 OF THE INTERNATIONAL BUILDING CODE, IF REQUIRED.
REFER TO THE ARCHITECTURAL DRAWINGS FOR DETAILS FOR ATTACHMENT OF THE
IMPACT-RESISTANT EXTERIOR GLAZING OR IMPACT-RESISTANT COVERING OVER
EXTERIOR GLAZING TO THE STRUCTURE.
3. WIND PRESSURES USED FOR THE DESIGN OF COMPONENTS AND CLADDING ARE
SHOWN IN THE FOLLOWING TABLE:
CLADDING LOCATION EFFECTIVE WIND LOAD
TYPE OR ZONE WIND AREA (PSF)
(SQ-FT)
WALL INTERIOR 10 +47 / -50
WALL INTERIOR 20 +46 / -49
WALL INTERIOR 50 +43 / -46
WALL INTERIOR 100 +42 / -45
WALL END ZONE 10 +47 / -59
WALL END ZONE 20 +46 / -57
WALL END ZONE 50 +43 / -52
WALL END ZONE 100 +42 / -49
ROOF INTERIOR 10 +32 / -44
ROOF INTERIOR 20 +30 / -43
ROOF INTERIOR 50 +28 / -42
ROOF INTERIOR 100 +26 / -41
ROOF EDGE 10 +32 / -68
ROOF EDGE 20 +30 / -64
ROOF EDGE 50 +28 / -58
ROOF EDGE 100 +26 / -53
ROOF CORNER 10 +32 / -95
ROOF CORNER 20 +30 / -90
ROOF CORNER 50 +28 / -83
ROOF CORNER 100 +26 / -77
OVERHANG INTERIOR 10 +17 / -83
OVERHANG INTERIOR 20 +17 / -83
OVERHANG INTERIOR 50 +17 / -83
OVERHANG INTERIOR 100 +17 / -83
OVERHANG EDGE 10 +17 / -83
OVERHANG EDGE 20 +17 / -83
OVERHANG EDGE 50 +17 / -83
OVERHANG EDGE 100 +17 / -83
OVERHANG CORNER 10 +17 / -129
OVERHANG CORNER 20 +17 / -118
OVERHANG CORNER 50 +17 / -103
OVERHANG CORNER 100 +17 / -92
NOTES:
a. WIDTH OF END ZONE/EDGE/CORNER STRIP: 5’-0” FEET
b. COMPONENT AND CLADDING PRESSURES ACT NORMAL TO THE SURFACE.
POSITIVE PRESSURES ACT TOWARDS THE SURFACE AND NEGATIVE
PRESSURES ACT AWAY FROM THE SURFACE.
c. DESIGN PRESSURE FOR COMPONENTS AND CLADDING SHALL NOT BE LESS
THAN 16 PSF ACTING IN EITHER DIRECTION NORMAL TO THE SURFACE.
d. THE EFFECTIVE WIND AREA IS THE SPAN LENGTH MULTIPLIED BY AN
EFFECTIVE WIDTH THAT NEED NOT BE LESS THAN ONE-THIRD THE SPAN
LENGTH. FOR CLADDING FASTENERS, THE EFFECTIVE WIND AREA SHALL
NOT BE GREATER THAN THE AREA THAT IS TRIBUTARY TO AN INDIVIDUAL
FASTENER.
E. BUILDING MOVEMENT AND DEFLECTIONS
1. THE BUILDING MOVEMENT SPECIFIED HEREIN IS ANTICIPATED TO OCCUR
AND SHOULD BE CONSIDERED BY THE CONTRACTOR IN THE PERFORMANCE OF THE
WORK.
2. LATERAL FRAME WIND DEFLECTION (DRIFT): THE FOLLOWING PROVISION FOR
LATERAL FRAME DEFLECTION IN THE PLANE OF THE WALL OF THE ROOF
RELATIVE TO THE SLAB-ON-GRADE SHALL BE MADE IN THE DESIGN, FABRICATION
AND INSTALLATION OF THE BUILDING CLADDING:
a. WALL HEIGHT/400
THE DEFLECTIONS LISTED ABOVE ARE BASED ON WIND LOADS WITH A 10-YEAR MEAN
RECURRENCE INTERVAL.
F. HANDRAILS AND GUARDS
1. THE HANDRAIL ASSEMBLIES AND GUARDS SHALL BE DESIGNED FOR 50 PLF OR A
CONCENTRATED LOAD OF 200 POUNDS AT ANY POINT APPLIED IN ANY
DIRECTION AT THE TOP AND TO TRANSFER THIS LOAD THROUGH THE SUPPORTS TO
THE STRUCTURE. THESE LOADS NEED NOT BE ASSUMED TO ACT CONCURRENTLY.
PART II - FOUNDATION PART V - COLD-FORMED METAL FRAMING PART VIII - MISCELLANEOUS PART IX - DRAWING INTERPRETATION
A. GEOTECHNICAL REPORT
1. FOUNDATION DESIGN IS BASED ON THE GEOTECHNICAL INVESTIGATION REPORT
AS FOLLOWS: "GEOTECHNICAL ENGINEERING STUDY FOR PROPOSED LIVESTOCK
ARTHROPOD PEST RESEARCH WET LAB AND WILDLIFE BARN EDINBURG, HILDALGO
COUNTY, TEXAS" PREPARED BY RABA KISTNER, MCALLEN, TX
2. THE GEOTECHNICAL REPORT IS AVAILABLE TO THE GENERAL CONTRACTOR
UPON REQUEST TO THE OWNER. THE INFORMATION INCLUDED THEREIN MAY BE
USED BY THE GENERAL CONTRACTOR FOR HIS GENERAL INFORMATION ONLY. THE
ARCHITECT AND ENGINEER WILL NOT BE RESPONSIBLE FOR THE ACCURACY OR
APPLICABILITY OF SUCH DATA THEREIN.
3. REFER TO THE GEOTECHNICAL REPORT FOR INFORMATION RELATED TO SITE
AND SUBGRADE PREPARATION, INCLUDING SOIL REMOVAL AND FILL CRITERIA
AND COMPACTION REQUIREMENTS BELOW FOUNDATIONS AND SLABS-ON-GRADE.
B. SHALLOW FOUNDATIONS
1. SPREAD FOOTING:
a. MAXIMUM ALLOWABLE BEARING PRESSURE FOR CONTINUOUS FOOTINGS AND
GRADE BEAMS: 1500 PSF
b. MAXIMUM ALLOWABLE BEARING PRESSURE FOR SPREAD FOOTINGS AND
WIDENED BEAMS: 2100 PSF
c. MINIMUM DEPTH OF BEARING: 24 INCHES BELOW FINISHED EXTERIOR
GRADE
d. MINIMUM WIDTH OF BEAM FOUNDATION: 12 INCHES
2. SLAB-ON-GRADE:
a. SUBGRADE MODULUS, K: 180 PSI PER INCH
b. MODULUS VALUE REDUCED FOR LARGE, WIDE AREA LOADS
C. RETAINING WALLS
1. THE FOLLOWING CRITERIA ARE BASED ON SECTION 1610 OF THE
INTERNATIONAL BUILDING CODE:
a. ACTIVE SOIL PRESSURE: 60 PSF PER FOOT OF DEPTH.
b. AT-REST SOIL PRESSURE: 100 PSF PER FOOT OF DEPTH
c. THE DESIGN PRESSURES SPECIFIED ABOVE ARE BASED ON DRAINED
BACKFILL WITH NO BUILDUP OF WATER PRESSURE BEHIND THE WALLS.
D. CONSTRUCTION DEWATERING
1. THE CONTRACTOR SHALL DETERMINE THE EXTENT OF CONSTRUCTION
DEWATERING REQUIRED FOR THE EXCAVATION. THE CONTRACTOR SHALL SUBMIT
TO THE GEOTECHNICAL ENGINEER FOR REVIEW THE PROPOSED PLAN FOR
CONSTRUCTION DEWATERING, PRIOR TO BEGINNING THE EXCAVATION.
PART III - REINFORCED CONCRETE
PART IV - STRUCTURAL STEEL
PART VI - PRE-ENGINEERED METAL BUILDING
PART VII - SUBMITTALS
A. CLASSES OF CONCRETE
1. ALL CONCRETE SHALL CONFORM TO THE REQUIREMENTS OF THE “CLASSES OF
CONCRETE MATRIX” ON SHEET S-302 UNLESS NOTED OTHERWISE ON THE
DRAWINGS.
B. HORIZONTAL CONSTRUCTION JOINTS IN CONCRETE POURS
1. THERE SHALL BE NO HORIZONTAL CONSTRUCTION JOINTS IN ANY CONCRETE
POURS UNLESS SHOWN ON THE DRAWINGS. THE ARCHITECT/ENGINEER SHALL
APPROVE ALL DEVIATIONS OR ADDITIONAL JOINTS IN WRITING.
C. REINFORCING STEEL
1. ALL REINFORCING STEEL SHALL BE ASTM A 615 GRADE 60 UNLESS NOTED
OTHERWISE ON THE DRAWINGS OR IN THESE NOTES.
2. REINFORCING STEEL: PROVIDE REINFORCING STEEL CONFORMING TO ASTM A
706 FOR ALL REINFORCING STEEL REQUIRED TO BE WELDED AND WHERE NOTED
ON THE DRAWINGS.
3. HEADED STUD ANCHORS FOR EMBEDDED PLATES: AWS D1.1 TYPE A STUDS
MANUFACTURED IN CONFORMANCE WITH SPECIFICATION ASTM A 108 WITH A
MINIMUM TENSILE STRENGTH OF 61,000 PSI.
4. SMOOTH WELDED WIRE REINFORCEMENT: ASTM A 185, YIELD STRENGTH 65,000
PSI.
D. PLACEMENT OF WELDED WIRE REINFORCEMENT
1. WHEREVER WELDED WIRE REINFORCEMENT IS SPECIFIED AS REINFORCEMENT, IT
SHALL BE CONTINUOUS ACROSS THE ENTIRE CONCRETE SURFACE AND NOT
INTERRUPTED BY BEAMS OR GIRDERS AND PROPERLY LAPPED PER ACI 318,
12.18 AND 12.19.
E. REINFORCING STEEL COVERAGE
1. REINFORCING STEEL COVERAGE SHOULD CONFORM TO THE REQUIREMENTS
SPECIFIED IN DETAILS LABELED “TYPICAL CLEAR CONCRETE COVER” ON
SHEETS S-301 UNLESS NOTED OTHERWISE ON THE DRAWINGS. COVER
SPECIFIED SHALL BE CONSIDERED MINIMUMS THAT MAY REQUIRE INCREASING
WHERE REINFORCING STEEL INTERSECTS FOR DIFFERENT MEMBER TYPES. COVER
IN STRUCTURAL MEMBERS NOT SPECIFIED IN THE DETAILS SHALL CONFORM TO
THE REQUIREMENTS OF ACI 318 UNLESS SPECIFIED OTHERWISE ON THE
DRAWINGS. THE REINFORCING STEEL DETAILER SHALL ADJUST REINFORCING
STEEL CAGE SIZES AT INTERSECTING STRUCTURAL MEMBERS AS REQUIRED TO
ALLOW CLEARANCE FOR INTERSECTING REINFORCING BAR LAYERS WITH MINIMUM
SPECIFIED COVER.
A. MATERIAL
1. HOT ROLLED STRUCTURAL MEMBERS: ALL HOT ROLLED STEEL PLATES,
SHAPES, SHEET PILING, AND BARS SHALL BE NEW STEEL CONFORMING TO ASTM
SPECIFICATION A 6.
2. ASTM SPECIFICATION AND GRADE: CLEARLY MARK THE GRADE OF STEEL ON
EACH PIECE, WITH A DISTINGUISHING MARK VISIBLE FROM FLOOR SURFACES, FOR
THE PURPOSE OF FIELD INSPECTION OF PROPER GRADE OF STEEL. UNLESS NOTED
OTHERWISE ON THE DRAWINGS, STRUCTURAL STEEL SHALL BE AS FOLLOWS:
a. W- AND WT-SHAPES: ASTM A 992
b. L-, C-, M- AND S-SHAPES: ASTM A 36
c. RECTANGULAR HSS: ASTM A 500, GRADE B (FY=46 KSI
d. ROUND HSS: ASTM A 500, GRADE B (FY=42 KSI)
e. STEEL PIPE: ASTM A 53 (TYPE E OR S), GRADE B (FY=35 KSI)
f. BASE PLATES: ALL BASE PLATES SHALL CONFORM TO ASTM A 36 UNLESS
NOTED OTHERWISE ON THE DRAWINGS.
g. PLATES, BENT PLATES: ASTM A 36
h. CONNECTION MATERIAL: ALL CONNECTION MATERIAL, EXCEPT AS NOTED
OTHERWISE HEREIN OR ON THE DRAWINGS, INCLUDING BEARING
PLATES, GUSSET PLATES, STIFFENER PLATES, FILLER PLATES, ANGLES, ETC.
SHALL CONFORM TO ASTM A 36 UNLESS A HIGHER GRADE OF STEEL IS REQUIRED BY
STRENGTH AND PROVIDED THE RESULTING SIZES ARE COMPATIBLE WITH THE
CONNECTED MEMBERS.
i) OTHER STEEL: ANY OTHER STEEL NOT INDICATED OTHERWISE SHALL
CONFORM TO ASTM A 992 OR ASTM A 572, GRADE 50, EXCEPT PLATES AND
ANGLES THAT SHALL BE ASTM A 36.
B. STRUCTURAL BOLTS AND THREADED FASTENERS
1. THREADED ROUND STOCK: THREADED RODS SHALL CONFORM TO ASTM A 36 OR
A572, GRADE 50 AS SPECIFIED HEREIN.
C. WELDING
1. UNLESS NOTED OTHERWISE, ELECTRODES FOR WELDING SHALL CONFORM TO
E70XX (SMAW), F7XX-EXXX (SAW), ER70S-X (GMAW), OR E7XT-X (FCAW).
2. ELECTRODES FOR GRADE 60 OR GRADE 65 MATERIAL SHALL CONFORM TO E80XX
(SMAW), F8XX-EXX-XX (SAW), ER80S-X (GMAW), OR E8XT-X (FCAW).
D. ANCHOR RODS
1. UNLESS INDICATED OTHERWISE IN THE COLUMN SCHEDULE OR ON THE
DRAWINGS, ANCHOR RODS SHALL CONFORM TO ASTM F 1554 GRADE 55 (WITH
SUPPLEMENTARY REQUIREMENT S1) AND THE SIZE SHALL BE 3/4" DIAMETER AND
SHALL EMBED INTO THE CONCRETE FOUNDATION A DISTANCE OF 1’-0" WITH A
HEAVY HEX NUT AT THE EMBEDDED END. STRIKE BOLT THREADS AT THE EMBEDDED
END AT TWO PLACES BELOW THE NUT.
E. GROUT
1. GROUT BELOW STRUCTURAL STEEL BASE PLATES SHALL BE NON-METALLIC,
NON-SHRINK GROUT WITH A MINIMUM STRENGTH OF 6,000 PSI WHEN BEARING ON
3,000 PSI CONCRETE OR LESS, A STRENGTH OF 8,000 PSI WHEN BEARING ON
CONCRETE BETWEEN 3,000 AND 4,000 PSI, AND, UNLESS NOTED OTHERWISE ON THE
DRAWINGS, A STRENGTH OF 8,000 PSI WHEN BEARING ON CONCRETE GREATER THAN
4,000 PSI.
A. SUBMITTAL LIST AND SCHEDULE
1. THE GENERAL CONTRACTOR SHALL PREPARE A DETAILED LIST AND SCHEDULE
OF ALL SUBMITTAL ITEMS TO BE SENT TO THE STRUCTURAL ENGINEER PRIOR TO
THE START OF CONSTRUCTION. THIS LIST SHALL BE UPDATED AND REVISED AND
KEPT CURRENT AS THE JOB PROGRESSES. THE SUBMITTAL LIST SHALL BE
ORGANIZED AS SHOWN BELOW:
a. SHOP DRAWINGS
b. DESIGN CALCULATIONS
c. PRODUCT DATA, CERTIFICATES, REPORTS, AND OTHER LITERATURE
B. SUBMITTALS TO BE PROVIDED TO STRUCTURAL ENGINEER
1. STRUCTURAL SUBMITTALS: IN ADDITION TO THE SUBMITTALS REQUIRED BY THE
STRUCTURAL SPECIFICATIONS, THE FOLLOWING SUBMITTALS SHALL BE
PROVIDED:
a. LAYOUT OF EMBEDDED ITEMS (PLATES, ANGLES, BOLTS, ETC.) OR ITEMS
ATTACHED TO THE STRUCTURAL FRAME FOR BUILDING CLADDING
ATTACHMENT OR FOR ATTACHMENT OF OTHER ITEMS.
2. DEFERRED SUBMITTALS:
a. THE FOLLOWING ITEMS ARE CONSIDERED DEFERRED SUBMITTALS BY THE
REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE:
1. COLD-FORMED METAL FRAMING (S&S, REC)
2. EXTERIOR WALL SYSTEM (S&S, REC)
3. METAL BUILDING (S&S)
4. STRUCTURAL STEEL CONNECTIONS (S&S) NOTES:
(S&S) ITEMS MARKED THUS SHALL HAVE THE SHOP DRAWINGS AND DELEGATED
DESIGN SUBMITTALS (INCLUDING CALCULATIONS) SEALED PER THE PROJECT
SPECIFICATIONS BY AN ENGINEER REGISTERED IN THE STATE WHERE THE PROJECT
IS LOCATED.
(REC) ITEMS MARKED THUS SHALL BE SUBMITTED TO ENGINEER FOR RECORD
ONLY AND WILL NOT HAVE THE ENGINEER’S SHOP DRAWING STAMP AFFIXED.
1) ALL SHOP DRAWINGS MUST BE REVIEWED AND ELECTRONICALLY STAMPED BY THE
GENERAL CONTRACTOR PRIOR TO SUBMITTAL.
3. SUBMITTAL REQUIREMENTS:
a. CONTRACTOR SHALL PROVIDE THE SUBMITTAL IN ELECTRONIC PORTABLE
DOCUMENT FORMAT (PDF) PER THE SPECIFICATIONS.
b. THE OMISSION FROM THE SHOP DRAWINGS OF ANY MATERIALS REQUIRED
BY THE CONTRACT DOCUMENTS TO BE FURNISHED SHALL NOT RELIEVE THE
CONTRACTOR OF THE RESPONSIBILITY OF FURNISHING AND INSTALLING SUCH
MATERIALS, REGARDLESS OF WHETHER THE SHOP DRAWINGS HAVE BEEN REVIEWED
AND APPROVED.
C. REPRODUCTION
1. THE USE OF ELECTRONIC FILES OR REPRODUCTIONS OF THESE CONTRACT
DOCUMENTS BY ANY CONTRACTOR, SUBCONTRACTOR, ERECTOR, FABRICATOR, OR
MATERIAL SUPPLIER IN LIEU OF PREPARATION OF SHOP DRAWINGS SIGNIFIES
THEIR ACCEPTANCE OF ALL INFORMATION SHOWN HEREON AS CORRECT, AND
OBLIGATES THEMSELVES TO ANY JOB EXPENSE, REAL OR IMPLIED, ARISING
DUE TO ANY ERRORS THAT MAY OCCUR HEREON.
A. DESIGN RESPONSIBILITY
1. THE DESIGN AND DETAILING OF ALL COLD-FORMED METAL FRAMING
COMPONENTS AND THEIR CONNECTION TO THE SUPPORTING STRUCTURE SHALL BE
DELEGATED TO AND THE RESPONSIBILITY OF A SPECIALTY ENGINEER. REFER TO
SPECIALTY ENGINEER REQUIREMENTS PARAGRAPH IN PART <> - MISCELLANEOUS OF
THESE GENERAL NOTES.
2. COLD-FORMED METAL FRAMING IS NOT SHOWN ON THE STRUCTURAL PLANS OR
DETAILS. REFER TO THE ARCHITECTURAL DRAWINGS FOR SCOPE. REFER TO PART I
FOR LOAD REQUIREMENTS.
B. MATERIALS
1. STUD AND TRACK PROFILES SHALL BE STANDARD SECTIONS USED BY
MEMBERS OF THE STEEL STUD MANUFACTURERS ASSOCIATION (SSMA). SSMA MEMBER
DESIGNATIONS AS SHOWN ON THE FOLLOWING EXAMPLE:
600 S 162-43 REPRESENTS A 6.00” DEEP, STUD SECTION, 1.625” WIDE FLANGE,
0.043” (43 MILS) MINIMUM STEEL THICKNESS.
NOTES:
S = STUD SECTION T = TRACK SECTION
U = CHANNEL SECTION F = FURRING CHANNEL
2. UNLESS NOTED OTHERWISE ON THE DRAWINGS, MEMBERS SHALL HAVE THE
FOLLOWING YIELD STRENGTHS:
a. STUDS: 33, 43 MIL THICKNESS FY = 33 KSI
b. STUDS: 54, 68, 97 MIL THICKNESS FY = 50 KSI c. TRACKS: 33, 43, 54, 68, 97 MIL FY = 33 KSI
d. U-CHANNELS, FURRING CHANNELS: FY = 33 KSI
3. ALL COLD-FORMED STEEL FRAMING MATERIALS SHALL HAVE A MINIMUM G60
GALVANIZED COATING.
A. THE PRE-ENGINEERED METAL BUILDING SYSTEM SHALL BE DESIGNED BY THE
METAL BUILDING MANUFACTURER IN CONFORMANCE TO THE INTERNATIONAL BUILDING
CODE AND THE “LOW-RISE BUILDING SYSTEMS MANUAL” AS PUBLISHED BY THE METAL
BUILDING MANUFACTURERS’ ASSOCIATION. WHERE THESE CRITERIA CONFLICT, THE MORE
STRINGENT CRITERIA SHALL APPLY.
B. IT IS THE PRE-ENGINEERED METAL BUILDING MANUFACTURER’S RESPONSIBILITY
TO DESIGN THE COMPLETE BUILDING SYSTEM (STEEL FRAMING, ANCHOR RODS, PURLINS,
GIRTS, BRACINGS, CONNECTIONS, ROOFING, WALL PANELS, COMPONENTS, ATTACHMENTS,
ETC.). THE MANUFACTURER SHALL SUBMIT A CERTIFICATION LETTER BEARING THE SEAL
OF A PROFESSIONAL ENGINEER REGISTERED IN TEXAS STATING THAT THE BUILDING
SYSTEM DESIGN MEETS THE INDICATED CODE, PERFORMANCE, AND LOADING
REQUIREMENTS.
C. THE PRE-ENGINEERED METAL BUILDING MANUFACTURER SHALL BE CERTIFIED BY
AMERICAN INSTITUTE OF STEEL CONSTRUCTION CATEGORY MB.
D. CALCULATIONS FOR FRAME DEFLECTIONS SHALL BE DONE USING ONLY THE BARE
FRAME METHOD. REDUCTIONS BASED ON ENGINEERING JUDGMENT USING THE ASSUMED
COMPOSITE STIFFNESS OF THE BUILDING ENVELOPE SHALL NOT BE PERMITTED.
CALCULATIONS SHALL BE SUBMITTED VERIFYING THAT THE ACTUAL DRIFT UNDER CODE-
REQUIRED LOADINGS DOES NOT EXCEED THE ALLOWABLE.
E. THE PRE-ENGINEERED MANUFACTURER SHALL PROVIDE ALL GIRTS, PURLINS, AND
OTHER COMPONENTS REQUIRED FOR A COMPLETE SYSTEM. ALL WALL SYSTEMS, SUCH AS
METAL STUDS, STOREFRONTS, ETC., SHALL BE PROPERLY SUPPORTED BY THE METAL
BUILDING SYSTEM. ALLOWABLE DEFLECTIONS OF COMPONENTS SHALL BE IN ACCORDANCE
WITH THE INTERNATIONAL BUILDING CODE, SECTION 1604.3.
F. THE FOUNDATION DESIGN IS BASED UPON THE SCHEMATIC METAL BUILDING FRAME
SHOWN IN THE CONTRACT DOCUMENTS. THE CONTRACTOR SHALL BE RESPONSIBLE FOR
COORDINATION OF ANY REVISIONS REQUIRED AS A RESULT OF A CHANGE IN THE METAL
BUILDING SCHEME, INCLUDING THE REDESIGN OF FOUNDATIONS.
G. THE SIZE, NUMBER, AND PLACEMENT PATTERN OF ALL ANCHOR RODS SHALL BE
DETERMINED BY THE PRE-ENGINEERED BUILDING MANUFACTURER. ANCHOR ROD EMBEDMENT
LIMITS ARE INDICATED ON THE DRAWINGS.
H. USE PINNED COLUMN BASES THROUGHOUT THE METAL BUILDING SYSTEM EXCEPT
WHERE CANTILEVERED WIND COLUMNS ARE SPECIFIED, WHICH ARE FIXED COLUMNS
BASES.
I. THE PRE-ENGINEERED METAL BUILDING SHALL BE DESIGNED BY THE
MANUFACTURER TO RESIST LATERAL LOADS VIA THE MOMENT FRAMES AND CABLE BRACED
FRAMES INDICATED.
J. UNLESS OTHERWISE NOTED OR SPECIFIED, ALL STEEL MEMBERS SHALL BE
HOT DIPPED GALVANIZED.
K. THE METAL BUILDING ERECTOR SHALL PROVIDE ALL TEMPORARY GUYING AND
BRACING.
A. CONTRACT DOCUMENTS
1. IT IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR TO OBTAIN ALL
CONTRACT DOCUMENTS AND LATEST ADDENDA AND TO SUBMIT SUCH DOCUMENTS
TO ALL SUBCONTRACTORS AND MATERIAL SUPPLIERS PRIOR TO THE SUBMITTAL
OF SHOP DRAWINGS, FABRICATION OF ANY STRUCTURAL MEMBERS, AND
ERECTION IN THE FIELD.
2. THE CONTRACT STRUCTURAL DRAWINGS AND SPECIFICATIONS REPRESENT THE
FINISHED STRUCTURE, AND, EXCEPT WHERE SPECIFICALLY SHOWN, DO NOT
INDICATE THE METHOD OR MEANS OF CONSTRUCTION. THE CONTRACTOR SHALL
SUPERVISE AND DIRECT THE WORK AND SHALL BE SOLELY RESPONSIBLE FOR ALL
CONSTRUCTION MEANS, METHODS, PROCEDURES, TECHNIQUES, AND SEQUENCE.
3. OPENINGS THROUGH FLOORS, ROOFS, AND WALLS FOR DUCTS, PIPING,
AND/OR CONDUIT SHALL BE COORDINATED BY THE CONTRACTOR. CONTRACTOR SHALL
VERIFY SIZES AND LOCATIONS OF HOLES AND OPENINGS WITH THE MECHANICAL,
ELECTRICAL, PLUMBING, AND FIRE PROTECTION DRAWINGS AND THE RESPECTIVE
SUBCONTRACTORS.
4. REFER TO DRAWINGS OTHER THAN STRUCTURAL FOR COMPLETE INFORMATION
INCLUDING: TYPES OF FLOOR SLAB FINISHES AND THEIR LOCATIONS, FLOOR SLAB
DEPRESSIONS AND CURBS, OPENINGS IN STRUCTURAL WALLS, ROOFS AND FLOORS
REQUIRED BY ARCHITECTURAL AND MEP FEATURES, STAIRS, RAMPS, ETC.
5. WHERE MEMBER LOCATIONS ARE NOT SPECIFICALLY DIMENSIONED, MEMBERS ARE
EITHER LOCATED ON COLUMNS LINES OR ARE EQUALLY SPACED BETWEEN LOCATED
MEMBERS.
6. IF CERTAIN FEATURES ARE NOT FULLY SHOWN OR SPECIFIED ON THE
DRAWINGS OR IN THE SPECIFICATIONS, THEIR CONSTRUCTION SHALL BE OF THE
SAME CHARACTER AS SHOWN OR SPECIFIED IN SIMILAR CONDITIONS.
B. DRAWING CONFLICTS
1. THE GENERAL CONTRACTOR SHALL COMPARE THE ARCHITECTURAL AND
STRUCTURAL DRAWINGS AND REPORT ANY DISCREPANCY BETWEEN EACH SET OF
DRAWINGS AND WITHIN EACH SET OF DRAWINGS TO THE ARCHITECT AND ENGINEER
PRIOR TO THE FABRICATION AND INSTALLATION OF ANY STRUCTURAL MEMBERS.
C. CONFLICTS IN STRUCTURAL REQUIREMENTS
1. WHERE CONFLICT EXISTS AMONG THE VARIOUS PARTS OF THE STRUCTURAL
CONTRACT DOCUMENTS, STRUCTURAL DRAWINGS, GENERAL NOTES, AND
SPECIFICATIONS, THE STRICTEST REQUIREMENTS, AS INDICATED BY THE
ENGINEER, SHALL GOVERN.
D. ADJACENT BUILDINGS AND PROPERTY
1. THE GENERAL CONTRACTOR SHALL ENSURE THAT ALL CONSTRUCTION METHODS
USED WILL NOT CAUSE DAMAGE TO THE ADJACENT BUILDINGS AND PROPERTY. THIS
SHALL INCLUDE ALL FOUNDATION INSTALLATION.
E. RESPONSIBILITY OF THE CONTRACTOR FOR STABILITY OF THE STRUCTURE DURING
CONSTRUCTION
1. ALL STRUCTURAL ELEMENTS OF THE PROJECT HAVE BEEN DESIGNED BY THE
STRUCTURAL ENGINEER TO RESIST THE REQUIRED CODE VERTICAL AND LATERAL
FORCES THAT COULD OCCUR IN THE FINAL COMPLETED STRUCTURE ONLY. THE
ABILITY OF THE STRUCTURAL FRAME TO RESIST THE REQUIRED CODE FORCES
DERIVES FROM THE COMPLETE INSTALLATION OF THE LATERAL FORCE
RESISTING SYSTEMS AND DIAPHRAGMS DESCRIBED BELOW. IT IS THE
RESPONSIBILITY OF THE CONTRACTOR TO DESIGN AND PROVIDE ALL REQUIRED
BRACING DURING CONSTRUCTION TO MAINTAIN THE STABILITY AND SAFETY OF
ALL STRUCTURAL ELEMENTS DURING THE CONSTRUCTION PROCESS UNTIL THE
LATERAL-LOAD RESISTING OR STABILITY-PROVIDING SYSTEM IS COMPLETELY
INSTALLED AND ALL DESIGNATED CONCRETE ELEMENTS (IF ANY) HAVE REACHED
A MINIMUM OF 75% OF THEIR DESIGN STRENGTH. THIS INCLUDES DESIGNING
FOR ALL APPLICABLE TEMPORARY, CONSTRUCTION AND ENVIRONMENTAL FORCES
PER ASCE 37 INCLUDING BUT NOT LIMITED TO WIND AND SEISMIC ON THE
STRUCTURE DURING CONSTRUCTION. THE REQUIRED STRUCTURAL ELEMENTS ARE:
a. STEEL FRAMES:
1. LATERAL-FORCE RESISTING SYSTEM
a. DUAL SYSTEM, INDICATED ON THE DRAWINGS AS A COMBINATION
OF MOMENT FRAMES AND BRACED FRAMES.
F. RESPONSIBILITY OF THE CONTRACTOR FOR CONSTRUCTION LOADS
1. THE STRUCTURE HAS BEEN DESIGNED FOR THE LOADS IDENTIFIED WITHIN
THESE STRUCTURAL DRAWINGS THAT ARE ANTICIPATED TO BE APPLIED TO THE
FINAL STRUCTURE ONCE COMPLETED AND OCCUPIED. THE CONTRACTOR SHALL NOT
OVERLOAD THE STRUCTURE DURING CONSTRUCTION. THE CONTRACTOR SHALL BE
RESPONSIBLE FOR CHECKING THE ADEQUACY OF THE STRUCTURE TO SUPPORT ANY
APPLIED CONSTRUCTION LOADS, INCLUDING THOSE DUE TO CONSTRUCTION VEHICLES
OR EQUIPMENT, MATERIAL HANDLING OR STORAGE, SHORING OR RESHORING, OR ANY
OTHER CONSTRUCTION ACTIVITY. THE CONTRACTOR SHALL SUBMIT CALCULATIONS
SIGNED AND SEALED BY AN ENGINEER LICENSED IN THE STATE WHERE THE PROJECT
IS LOCATED VERIFYING THE ADEQUACY OF THE STRUCTURE FOR ANY PROPOSED
CONSTRUCTION LOADS THAT ARE IN EXCESS OF THE STATED DESIGN LOADS. THE
STRUCTURAL ENGINEER IS NOT RESPONSIBLE TO DESIGN OR CHECK THE STRUCTURE
FOR LOADS APPLIED TO THE STRUCTURE FOR ANY CONSTRUCTION ACTIVITY.
G. CONTRACTOR SUBSTITUTIONS
1. ANY MATERIALS OR PRODUCTS SUBMITTED FOR APPROVAL THAT ARE
DIFFERENT FROM THE MATERIAL OR PRODUCTS SPECIFIED IN THE STRUCTURAL
CONTRACT DOCUMENTS WILL BE APPROVED ONLY IF THE FOLLOWING CRITERIA ARE
SATISFIED:
a. A COST SAVINGS TO THE OWNER IS DOCUMENTED AND SUBMITTED WITH
THE REQUEST.
b. THE MATERIAL OR PRODUCT HAS BEEN APPROVED BY THE
INTERNATIONAL CODE COUNCIL (ICC) AND THE ICC REPORT IS SUBMITTED WITH
THE REQUEST.
1. THE ICC ESR THAT IS SUBMITTED MUST REFERENCE THE BUILDING
CODE UNDER WHICH THE PROJECT IS PERMITTED.
2. ICC REPORTS THAT HAVE BEEN DISCONTINUED AT THE TIME OF
PRODUCT INSTALLATION WILL NOT BE ACCEPTED.
2. SUBMITTALS NOT SATISFYING THE ABOVE CRITERIA WILL NOT BE CONSIDERED.
H. MECHANICAL EQUIPMENT WEIGHTS
1. THE GENERAL CONTRACTOR SHALL SUBMIT ACTUAL WEIGHTS OF EQUIPMENT
TO BE USED IN THE PROJECT TO THE STRUCTURAL ENGINEER FOR VERIFICATION OF
LOADS USED IN THE DESIGN AT LEAST THREE WEEKS PRIOR TO FABRICATION AND
CONSTRUCTION OF THE SUPPORTING STRUCTURE.
I. THE STRUCTURAL ENGINEER’S ROLE DURING CONSTRUCTION
1. THE ENGINEER SHALL NOT HAVE CONTROL NOR CHARGE OF, AND SHALL NOT
BE RESPONSIBLE FOR, CONSTRUCTION MEANS, METHODS, TECHNIQUES, SEQUENCES,
OR PROCEDURES, FOR SAFETY PRECAUTIONS AND PROGRAMS IN CONNECTION WITH
THE WORK, FOR THE ACTS OR OMISSION OF THE CONTRACTOR, SUBCONTRACTOR, OR
ANY OTHER PERSONS PERFORMING ANY OF THE WORK, OR FOR THE FAILURE OF ANY
OF THEM TO CARRY OUT THE WORK IN ACCORDANCE WITH THE CONTRACT DOCUMENTS.
2. PERIODIC SITE OBSERVATION BY FIELD REPRESENTATIVES OF WALTER P.
MOORE AND ASSOCIATES IS SOLELY FOR THE PURPOSE OF BECOMING GENERALLY
FAMILIAR WITH THE PROGRESS AND QUALITY OF THE WORK COMPLETED AND
DETERMINING, IN GENERAL, IF THE WORK OBSERVED IS BEING PERFORMED IN A
MANNER INDICATING THAT THE WORK, WHEN FULLY COMPLETED, WILL BE IN
ACCORDANCE WITH THE STRUCTURAL CONTRACT DOCUMENTS. THIS LIMITED SITE
OBSERVATION SHOULD NOT BE CONSTRUED AS EXHAUSTIVE OR CONTINUOUS TO CHECK
THE QUALITY OR QUANTITY OF THE WORK, BUT RATHER PERIODIC IN AN EFFORT TO
KEEP THE OWNER REASONABLY INFORMED ABOUT THE PROGRESS AND QUALITY OF THE
PORTION OF THE STRUCTURE COMPLETED.
J. MAINTENANCE STATEMENT
1. ALL STRUCTURES REQUIRE PERIODIC MAINTENANCE TO EXTEND LIFESPAN
AND TO ENSURE STRUCTURAL INTEGRITY FROM EXPOSURE TO THE ENVIRONMENT. A
PLANNED PROGRAM OF MAINTENANCE SHALL BE ESTABLISHED BY THE BUILDING
OWNER. THIS PROGRAM SHALL INCLUDE SUCH ITEMS SUCH AS BUT NOT LIMITED TO
PAINTING OF STRUCTURAL STEEL, PROTECTIVE COATING FOR CONCRETE, SEALANTS,
CAULKED JOINTS, EXPANSION JOINTS, CONTROL JOINTS, SPALLS AND CRACKS IN
CONCRETE, AND PRESSURE WASHING OF EXPOSED STRUCTURAL ELEMENTS EXPOSED TO
A SALT ENVIRONMENT OR OTHER HARSH CHEMICALS.
A. DRAWING VIEWS LABELED AS “TYPICAL”
1. PARTIAL PLANS, ELEVATIONS, SECTIONS, DETAILS, OR SCHEDULES
LABELED WITH “TYPICAL” AT THE BEGINNING OF THEIR TITLE SHALL APPLY TO
ALL SITUATIONS OCCURRING ON THE PROJECT THAT ARE THE SAME OR SIMILAR TO
THOSE SPECIFICALLY SHOWN. THE APPLICABILITY OF THE CONTENT OF THESE
VIEWS TO LOCATIONS ON THE PLAN CAN BE DETERMINED FROM THE TITLE OF THE
VIEWS. SUCH VIEWS SHALL APPLY WHETHER OR NOT THEY ARE KEYED IN AT EACH
LOCATION. DECISIONS REGARDING APPLICABILITY OF THESE “TYPICAL” VIEWS
SHALL BE DETERMINED BY THE STRUCTURAL ENGINEER.
B. STRUCTURAL ABBREVIATIONS, SYMBOLS, AND NOTATIONS
1. REFER TO SHEET S-002 FOR ABBREVIATIONS, SYMBOLS, AND NOTATIONS USED
ON THE STRUCTURAL DRAWINGS.
B
SLOPE
DOWN
8" 6"
STRUCTURAL SYMBOLS AND NOTATIONS
THE FOLLOWING MATERIAL IDENTIFICATION SYMBOLS MAY BE USED IN THE SECTIONS AND
DETAILS:
THE FOLLOWING MATERIAL IDENTIFICATION SYMBOLS MAY BE USED IN THE PLANS:
STEEL
COLUMN
CONCRETE
COLUMN
CONCRETE
WALL
LOADBEARING
MASONRY WALL
NON-LOADBEARING
MASONRY WALL
BOUNDARY OF CONCRETE
TOPPING SLAB POURED ON
SUBSTRUCTURE
REFERENCE GRID LINE SYMBOL
THE FOLLOWING SYMBOLIC LINEWORK MAY BE USED THROUGHOUT THE DRAWINGS:
THESE FOLLOWING SYMBOLS MAY BE USED THROUGHOUT THE DRAWINGS TO REFER TO
OTHER VIEWS:
THESE FOLLOWING SYMBOLS MAY BE USED THROUGHOUT THE
DRAWINGS:
DETAIL
NUMBER OR
LETTER
SHEET NUMBER
REFERENCE
OBJECT
OVERALL
SECTION SYMBOL
DETAIL NUMBER
OR LETTER
SHEET NUMBER
REFERENCE
OBJECT
PARTIAL
SECTION SYMBOL
ELEVATION OF REFERENCE
OBJECT OR LOCATION
REFERENCE OBJECT
OR LOCATION
REFERENCE
OBJECT
FRAMING
ELEVATION SYMBOL
DETAIL
REFERENCE
SYMBOL
REVISION CLOUD
SYMBOL
ELEVATION
DESIGNATION SYMBOL
REFERENCE GRID
INDICATOR SYMBOL
GRID LABEL
WORK POINT
SYMBOL
REVISION NUMBER
OR LETTER
AREA OR ITEM
BEING REVISED
WP
DETAIL
NUMBER OR
LETTER
SHEET NUMBER
AREA OR
ITEM BEING
DETAILED
FLAT FACE
BREAK MARK
CURVED FACE
BREAK MARK
LINE
BREAK MARK
A
S-302
A
S-302
A
S-302
A
S-302
TOP OF SLAB
10'-4"
THE FOLLOWING SYMBOLS MAY BE USED THROUGHOUT THE PLANS.
RIDGE
INDICATOR
SYMBOL
STEP TO SLOPE
INDICATOR
SYMBOL
SLOPE TRANSITION
INDICATOR
SYMBOL
STEP
INDICATOR
SYMBOL
RAMP SLOPE
INDICATOR
SYMBOL
KEYNOTE INDICATOR
SYMBOL
PROJECT NORTH
ARROW SYMBOL
SIZE OF
STEP (IF
PROVIDED)
SIZE OF
STEP (IF
PROVIDED)
SLOPE PITCH
INDICATOR
SYMBOL
HORIZONTAL
DIMENSION
VERTICAL
DIMENSION
LARGE OPENING IN
STRUCTURAL SLAB OR DECK
SMALL OPENINGS IN
STRUCTURAL SLAB OR DECK
FPx
REINFORCING STEEL
WITH 90° HOOK
REINFORCING STEEL
WITH 180° HOOK
CONCRETE FRAMING
PENETRATION
N
OPE
N
MOMENT CONNECTION
(NON-SEISMIC)
CONNECTION WITH
PASS THROUGH FORCE
MOMENT
CONNECTION
(SEISMIC)
CONNECTION WITH
DOUBLE SHEAR PLATE
CONNECTION WITH TWO
COLUMNS OF BOLTS
CONNECTION WITH FULL-
DEPTH SHEAR PLATE
CONNECTION WITH
GUSSET
CONNECTION WITH
GUSSET AND WELDED
FLANGES
SPECIAL
CONNECTION
(TYPE X)
BEAM SPLICE CONNECTION
(SHEAR ONLY)
CONNECTION WITH
WELDED TOP FLANGE
CONNECTION TO
CONCRETE WITH
EMBEDDED PLATE
X
X
EPx
EPx
FPx
FORCE
(KIPS)
STEEL FRAMING
PENETRATION
MECHANICAL UNIT OR
OTHER EQUIPMENT
XXX-x 3,500#
BELOW
ROUGH OUTLINE OF
UNIT
UNIT NAME (IF PROVIDED)
MAXIMUM TOTAL ALLOWABLE
WEIGHT OF UNIT OR
EQUIPMENT INCLUDING
WEIGHT OF CURB
IF PROVIDED, INDICATES
UNIT IS HANGING BELOW
FLOOR OR ROOF
PASS-THROUGH
FORCE SYMBOL
BRACE/KICKER
DIRECTION
INDICATOR SYMBOL
Bxx DENOTES SLAB BOTTOM REINFORCEMENT TYPE "xx"
BMxx DENOTES CONCRETE BEAM TYPE "xx"
BPxx DENOTES BASE PLATE TYPE "xx"
Cxx DENOTES COLUMN TYPE "xx"
CFxx DENOTES CONTINUOUS FOOTING TYPE "xx"
DPxx DENOTES DRILLED PIER TYPE "xx"
EPxx DENOTES EMBEDDED PLATE TYPE "xx"
Fxx DENOTES SPREAD FOOTING TYPE "xx"
FPxx DENOTES FRAMING PENETRATION TYPE "xx"
GBxx DENOTES GRADE BEAM TYPE "xx"
MWxx DENOTES CMU WALL TYPE "xx"
Pxx DENOTES PIER TYPE "xx"
PCxx DENOTES PILE OR PIER CAP TYPE "xx"
Sxx DENOTES ONE-WAY SLAB TYPE "xx"
SRxx DENOTES HEADED SHEAR STUD REINFORCEMENT TYPE "xx"
SFxx DENOTES STRIP FOOTING TYPE "xx"
Txx DENOTES SLAB TOP REINFORCEMENT TYPE "xx"
WFxx DENOTES WALL FOOTING TYPE "xx"
THE FOLLOWING STRUCTURAL ELEMENT TAGS, USED IN CONJUNCTION WITH
SCHEDULES, MAY APPEAR ON THE DRAWINGS:
Ø
ADDL
AESS
AFF
AHR
AHU
ALT
APPROX
AR
ARCH
BC
BF
BLDG
BM
BO
BOD
BOT
BRDG
BRG
BTWN
C
CANTIL
CFSF
CG
CIP
CJ
CJP
CL
CMU
COL
CONC
CONN
CONSTR
CONT
COORD
COV
CPRS
CTRS
db
DBA
DCW
DET
DIA
DIM
DWA
DWG
EA
EF
EJ
EL
ELEV
EMBED
ENGR
EQ
EQUIP
EQUIV
EW
EXIST
EXP
EXT
FAB
f'c f'm
FD
FDTN
FF
FIN
FLR
FS
FTG
FUT
FV
Fy
GA
GALV
GEN
GR
H
HGR
HORIZ
HSA
HSS
ID
INFO
INT
JT
K
KSF
KSI
LBS
Ld
LLBB
AT
AND
NUMBER
ROUND, DIAMETER
ADDITIONAL
ARCHITECTURAL EXPOSED
STRUCTURAL STEEL
ABOVE FINISHED FLOOR
ANCHOR
AIR HANDLING UNIT
ALTERNATE
APPROXIMATE
ANCHOR ROD
ARCHITECTURAL
BOTTOM OF COLUMN
BRACED FRAME
BUILDING
BEAM
BOTTOM OF
BOTTOM OF DECK
BOTTOM
BRIDGING
BEARING
BETWEEN
CAMBER
CANTILEVER
COLD-FORMED STEEL FRAMING
CENTER OF GRAVITY
CAST-IN-PLACE
CONSTRUCTION/CONTROL JOINT
COMPLETE JOINT PENETRATION
CENTERLINE
CONCRETE MASONRY UNIT
COLUMN
CONCRETE
CONNECTION
CONSTRUCTION
CONTINUOUS
COORDINATE
COVER
COMPRESSIBLE
CENTERS
BAR DIAMETER
DEFORMED BAR ANCHOR
DEMAND CRITICAL WELD
DETAIL
DIAMETER
DIMENSION
DEFORMED WIRE ANCHOR
DRAWING
EACH
EACH FACE
EXPANSION JOINT
ELEVATION
ELEVATOR
EMBEDMENT, EMBEDDED
ENGINEER
EQUAL
EQUIPMENT
EQUIVALENT
EACH WAY
EXISTING
EXPANSION
EXTERIOR
FABRICATE
28 DAY CONCRETE STRENGTH
28 DAY MASONRY STRENGTH
FLOOR DRAIN
FOUNDATION
FAR FACE
FINISH(ED)
FLOOR
FAR SIDE
FOOTING
FUTURE
FIELD VERIFY
YIELD STRENGTH
GAGE, GAUGE
GALVANIZE(D)
GENERAL
GRADE
HORIZONTAL REACTION
HANGER
HORIZONTAL
HEADED STUD ANCHOR
HOLLOW STRUCTURAL SECTION
INSIDE DIAMETER
INFORMATION
INTERIOR
JOINT
KIPS (1000 LBS)
KIPS PER SQUARE FOOT
KIPS PER SQUARE INCH
POUNDS
DEVELOPMENT LENGTH
LONG LEG BACK TO BACK
LLH
LLV
LONG
LSH
LSLP
LSLT
LSV
LWC
M
MAS
MAX
MC
MECH
MEZZ
MFR
MH
MIN
MISC
MTL
NF
NIC
NS
NTS
NWC
OC
OD
OPH
OPNG
OPP
OVS
P
PAF
PAR
PCC
PCF
PCY
PERP
PL
PLF
PJP
PRELIM
PROP
PSF
PSI
PT
QTY
R
RAD
REF
REINF
REM
REQD
REV
RS
RTU
SC
SCHED
SDS
SECT
SHT
SIM
SLBB
SLRS
SOG
SPA
SPEC
SPRT
SQ
SS
SSLP
SSLT
STD
STIF
STIR
STL
STRUCT
SW
SYMM
T
TC
THD
TO
TOC
TOM
TOS
TRANS
TYP
UNO
VERT
WF
WP
WS
WT
WWR
XS
XXS
LONG LEG HORIZONTAL
LONG LEG VERTICAL
LONGITUDINAL
LONG SIDE HORIZONTAL
LONG-SLOTTED HOLE PARALLEL
LONG-SLOTTED HOLE TRANSVERSE
LONG SIDE VERTICAL
LIGHTWEIGHT CONCRETE
MOMENT
MASONRY
MAXIMUM
MOMENT CONNECTION
MECHANICAL
MEZZANINE
MANUFACTURER
HORIZONTAL MOMENT
MINIMUM
MISCELLANEOUS
METAL
NEAR FACE
NOT IN CONTRACT
NEAR SIDE
NOT TO SCALE
NORMALWEIGHT CONCRETE
ON CENTER
OUTSIDE DIAMETER
OPPOSITE HAND
OPENING
OPPOSITE
OVERSIZED HOLE
AXIAL LOAD
POWDER ACTUATED FASTENER
PARALLEL
PRECAST CONCRETE
POUNDS PER CUBIC FOOT
POUNDS PER CUBIC YARD
PERPENDICULAR
PLATE
POUNDS PER LINEAR FOOT
PARTIAL JOINT PENETRATION
PRELIMINARY
PROPERTY
POUNDS PER SQUARE FOOT
POUNDS PER SQUARE INCH
POST-TENSION(ED)
QUANTITY
REACTION
RADIUS
REFERENCE
REINFORCEMENT
REMAINDER
REQUIRED
REVISION
ROCK SOCKET
ROOF TOP UNIT
SLIP CRITICAL
SCHEDULE(D)
SELF-DRILLING SCREW
SECTION
SHEET
SIMILAR
SHORT LEG BACK TO BACK
SEISMIC LOAD RESISTING SYSTEM
SLAB-ON-GRADE
SPACING
SPECIFICATION
SUPPORT
SQUARE
STAINLESS STEEL
SHORT-SLOTTED HOLE PARALLEL
SHORT-SLOTTED HOLE TRANSVERSE
STANDARD
STIFFENER
STIRRUP
STEEL
STRUCTURE, STRUCTURAL
SHEAR WALL
SYMMETRIC, SYMMETRICAL
TORSION
TOP OF COLUMN
THREADED
TOP OF
TOP OF CONCRETE
TOP OF MASONRY
TOP OF STEEL, TOP OF SLAB
TRANSVERSE
TYPICAL
UNLESS NOTED OTHERWISE
VERTICAL
WALL FOOTING
WORK POINT
WATERSTOP
WEIGHT
WELDED WIRE REINFORCEMENT
EXTRA STRONG
DOUBLE EXTRA STRONG
THE FOLLOWING ABBREVIATIONS MAY BE USED IN THE DRAWINGS:
THE FOLLOWING STRUCTURAL ANNOTATIONS MAY APPEAR ON THE FOUNDATION
PLANS:
F7.0 C12 +640'-0"
SPREAD, STRIP, OR COMBINED FOOTING MARK
P2 C12 +640'-0" ~600'-0"
20'-0" RS
1200K
PIER MARK
COLUMN MARK (IF PROVIDED)
TOP OF PIER ELEVATION (IF PROVIDED)
ESTIMATED PIER TIP ELEVATION (IF PROVIDED)
REQUIRED ROCK SOCKET (IF PROVIDED)
COLUMN UNFACTORED REACTION IN KIPS (IF PROVIDED)
WF5.0 WALL FOOTING MARK
STEP IN
FOOTING
TOP OF FOOTING ELEVATION (IF PROVIDED)
COLUMN MARK (IF PROVIDED)
MW2 WALL MARK (IF PROVIDED)
ALL STEPS WILL BE NOTED
Tx
#4x20'-0" BOTTOM
BARS @12"
4-#4x5'-0" TOP
REINFORCING STEEL NOTED IN PLAN SHALL BE
LOCATED ACCORDING TO PLAN NOTES, TYPICAL
VIEWS, AND SCHEDULES. HOOKS ARE INDICATED IN
PLAN WHERE REQUIRED FOR NON-SCHEDULED
REINFORCING STEEL. WHERE HOOKS ARE SHOWN,
LENGTHS PROVIDED DO NOT INCLUDE HOOK.
A SINGLE ARROWED LINE INDICATES THE EXTENT
OVER WHICH THE REINFORCING STEEL IS TO BE
DISTRIBUTED WITH AN EQUAL SPACING BETWEEN
BARS.
A DOUBLE ARROWED LINE INDICATES THAT THE
REINFORCING STEEL IS TO BE PROVIDED IN EACH
DIRECTION UNTIL ONE OF THE FOLLOWING OCCURS:
1. AN EDGE OF SLAB
2. A SIGNIFICANT CHANGE IN THE SLAB
GEOMETRY
3. OTHER REINFORCING STEEL OF A SIMILAR
NATURE IS SHOWN
SW3
SHEAR WALL
DESIGNATION
OPENING IN WALL
BM4 <-1'-0">
COLUMN MARK (IF PROVIDED)
HEADED SHEAR STUD REINFORCEMENT
MARK (IF PROVIDED)
BEAM MARK
TOP OF CONCRETE BEAM ELEVATION
RELATIVE TO TYPICAL TOP OF
CONCRETE ELEVATION. A POSITIVE
VALUE INDICATES THE CONCRETE
BEAM IS ABOVE THE TYPICAL
ELEVATION.
C4
SR8
THE FOLLOWING STRUCTURAL ANNOTATIONS MAY APPEAR ON THE CONCRETE
FRAMING PLANS
REFERENCE LINE OR OBJECT WHERE
REINFORCING STOPS
THE FOLLOWING STRUCTURAL ANNOTATIONS MAY APPEAR ON THE STEEL FRAMING
PLANS. ALL LOADS INDICATED ARE FACTORED:
W16x26 C=1.25
(18)
TOP OF STEEL ELEVATION RELATIVE
TO TYPICAL TOP OF STEEL
ELEVATION. A POSITIVE VALUE
INDICATES THE STEEL BEAM IS
ABOVE THE TYPICAL ELEVATION.
BRACED FRAME DESIGNATION
BRACES CONTINUING ABOVE
ARE INDICATED BY HIDDEN
LINES ABOVE BEAM
BRACES CONTINUING BELOW
ARE INDICATED BY HIDDEN
LINES BELOW BEAM
BRACED FRAME BF-1
THE FOLLOWING DIAGRAM PROVIDES INFORMATION REGARDING THE ORIENTATION OF THE
REACTIONS PROVIDED. THE DIAGRAM BELOW APPLIES TO ALL NON-SLOPING MEMBERS
REGARDLESS OF THE INDIVIDUAL MEMBER ORIENTATION (FOR EXAMPLE, AN HSS ORIENTED
LONG-SIDE HORIZONTAL). REFER TO DETAILS FOR ADDITIONAL INFORMATION ON LOADING
OF SLOPED MEMBERS.
FOR ALL LOADING, REACTIONS ARE TO BE APPLIED AT THE CENTERLINE OF THE MEMBER AT
THE WORK POINT, UNLESS NOTED OTHERWISE. IF ONLY A SINGLE VALUE IS SHOWN, THE
LOAD SHALL BE ASSUMED TO ACT IN BOTH DIRECTIONS WITH EQUAL MAGNITUDE. FOR
AXIAL LOAD REACTIONS, A POSITIVE VALUE INDICATES TENSION. FOR VERTICAL
MOMENTS, A POSITIVE VALUE WILL CAUSE COMPRESSION IN THE TOP OF THE BEAM AND
TENSION IN THE BOTTOM.
VERTICAL AXIS
BEAM
HORIZONTAL MOMENT REACTION (MH)
OCCURS ABOUT VERTICAL AXIS
VERTICAL MOMENT REACTION (M)
VERTICAL SHEAR REACTION (R)
OCCURS ALONG VERTICAL AXIS
AXIAL REACTION (P) ALONG MEMBER
BEAM
HORIZONTAL SHEAR
REACTION (H)
TORSION
REACTION (T)
SECTION ELEVATION
COLUMN SIZE OR MARK (IF PROVIDED)
BASE PLATE MARK (IF PROVIDED)
W14x90
BP3
SLOPE EDGE
A
S-302
DETAIL
NUMBER OR
LETTER
SHEET NUMBER
ALUMINUM CAST-IN-PLACE
CONCRETE
EARTH EARTH
(UNDISTURBED)
EXISTING
CONSTRUCTION
GRAVEL GROUT
MASONRY STEEL
MATERIAL IDENTIFICATION SYMBOLS
SYMBOLIC LINEWORK
VIEW REFERENCE SYMBOLS
UNIVERSAL SYMBOLS
STRUCTURAL ELEMENTS TAGSPLAN SYMBOLS FOUNDATION ANNOTATION STYLES STEEL ANNOTATION STYLES
ABBREVIATIONS
CONCRETE ANNOTATION STYLES
W16x26 C=1.25
P160/-100 R30 H15
BEAM SIZE
BEAM CAMBER
LEFT END VERTICAL SHEAR
REACTION (IN KIPS)
RIGHT END VERTICAL SHEAR
REACTION (IN KIPS)
W16x26 C=1.25
(18)
NUMBER OF SHEAR
STUDS AT UNIFORM
SPACING
(8) (5) (10) (5)
ALTERNATE SHEAR STUD
CALLOUT FOR NON-
UNIFORM SPACING
AXIAL LOAD REACTION (IN KIPS)
VERTICAL SHEAR REACTION
(IN KIPS)
HORIZONTAL SHEAR REACTION
(IN KIPS)
VERTICAL MOMENT REACTION
(IN KIP-FEET)
HORIZONTAL MOMENT REACTION
(IN KIP-FEET)
TORSION REACTION (IN KIP-FEET)
M260/-150
MH100
T30
W16x26 C=1.25
(18)
R25
NON-COMPOSITE BEAM
COMPOSITE BEAM
R25 R30
R25 R30
BEAM SIZE
BEAM CAMBER
LEFT END VERTICAL SHEAR
REACTION (IN KIPS)
RIGHT END VERTICAL SHEAR
REACTION (IN KIPS)
R25 R30W16x26 C=1.25
ADDITIONAL INFORMATION MAY BE SPECIFIED ON STEEL BEAMS FOR THE PURPOSES
OF DELEGATED CONNECTION DESIGN. IN THOSE CASES, FORCES AND MOMENTS WILL
BE PROVIDED AS APPROPRIATE AT THE ENDS OF THE BEAMS AS INDICATED BELOW.
R25 R30
<+2 1/2>
CENTERLINE SYMBOL
PLAN MATCHLINE SYMBOL
NON-STRUCTURAL LINE SYMBOL
WELDED WIRE REINFORCEMENT
SYMBOL
STEEL JOIST LINE SYMBOL
OPENING LINE SYMBOL
TM
Original drawing size is 30"x42"; Scale entities accordingly if reduced/enlarged.
SAFETY & HEALTH
REAL PROPERTY
DESIGNER
CHECKED BY
PROJECT MANAGER
PPM
EPM
SETTY
DATE
A
D
USDA S
U
NO. DATE BY
Service Research Agricultural
REVISIONS
DWG. NO
DRAWN BY
SOLICITATION NO.
1465 NORTHSIDE DRIVE, SUITE 220B
ATLANTA, GEORGIA 30318
P: 706-248-7165 www. .com
PROJECT NUMBER: SIGQ212911.14
03/18/2022 90% DOCUMENTS
WILDLIFE BARN
SHEET NAME
DESCRIPTION
04/13/2022 100% DOCUMENTS2
JUSTIN STOLZE, P.E.
PE 130920
NOT FOR CONSTRUCTION
NOT FOR PERMIT
TA
TA
SYMBOLS AND
ANNOTATIONS S-002
1 2 3 4 5 6
A
D
S-201
S-201
G B x
20'-10" 20'-10" 20'-10" 20'-10" 20'-10"
/2
/2
S -2
S
-2
CROSS-BRACING ASSUMED
IN BAY, TO BE DESIGNED
AND CONFIRMED BY PRE-
ENGINEERED METAL
BUILDING MANUFACTURER
F5 F5 F7 F7 F5 F5 F5
F5 F5 F7
F7 F5 F5 F5 CE24x24
CE24x24
CE24x24
CE24x24
CE24x24
CE24x24
CE24x24
CE24x24
CE24x24
CE24x24
CE24x24
CE24x24
CE24x24
CE24x24
WF18x18 TYP, CENTER
UNDER PRE-
FABRICATED PEN
STRUCTURE
TOF: -0'-6" UNO
PRE-FABRICATED
STRUCTURE AND
ANCHORAGE BY
MANUFACTURER
WIDEN GRADE BEAM AS
SHOWN FOR PEN WALL
SUPPORTS
PRE-FABRICATED
PEN STRUCTURE BY
OTHERS
PRE-FABRICATED
PEN STRUCTURE BY
OTHERS
G B x
G B x
G B x
G B x
G B x
G B x
GB20x20
GB20x20
WF18x18 TYP, CENTER
UNDER PRE-FABRICATED
PEN STRUCTURE
TOF: -0'-6" UNO
C E
N T
E R
E D
O N
C O
L U
M N
T
Y P
F O
U N
D A
T
IO
N A
N D
E N
C A
S E
M E
N T
S-302
TYP
S-302
TYP
S-302
TYP
CROSS-BRACING ASSUMED
IN BAY, TO BE DESIGNED
AND CONFIRMED BY PRE-
ENGINEERED METAL
BUILDING MANUFACTURER
TYPICAL PERIMETER
FENCING TO BE SELF
SUPPORTED FROM GRADE,
BY OTHERS, 80% MINIMUM
OPENNESS
HSS TRELLIS POSTS, REFER
TO TRELLIS PLAN, PROVIDE
4" THICK UNREINFORCED
CONCRETE ENCASEMENT
BLOW GRADE TO PROTECT
STEEL AND BASEPLATE, TYP
REVOLVING DOOR
SUPPORT BY PEN
MANUFACTURER, BRACE
TO PEN STRUCTURE
MAXIMUM LOADING CONSIDERED FOR TYPICAL BRACED BAY FOUNDATION DESIGN:
GRAVITY: 140 KIP FACTORED LRFD, 74 KIP SERVICE ASD
UPLIFT: 30 KIP FACTORED LRFD, 17 KIP SERVICE ASD
LATERAL: 18 KIP FACTORED (SHORT), 8 KIP FACTORED (LONG)
MAXIMUM LOADING CONSIDERED
FOR TYPICAL FOUNDATION DESIGN:
GRAVITY: 50 KIP FACTORED LRFD, 35 KIP SERVICE ASD
UPLIFT: 18 KIP FACTORED LRFD, 11 KIP SERVICE ASD
LATERAL: 18 KIP FACTORED (SHORT)
WF18x18
WF18x18
B
C
T Y
P
T O
F -2
T O
F -2
T O
F -2
T O
F -2
T O
F -2
T O
F -2
T O
F -2
TOF: -2'-0"
TOF: -2'-0"
TOF: -2'-0" TOF: -2'-0" TOF: -2'-0" TOF: -2'-0" TOF: -2'-0" TOF: -2'-0" TOF: -2'-0"
TOF: -2'-0"TOF: -2'-0"TOF: -2'-0"TOF: -2'-0"
TOF: -2'-0"
TOF: -2'-0"TOF: -2'-0"
S-302
TYP
T Y
P
"1'-0"
ENLARGE GRADE BEAM BELOW
TRELLIS POST AS SHOWN
1 2 3 4 5 6
S-201
S-201
HSS6x6x1/4 BEAM, TYP
TOP OF STEEL = 10'-0"
HSS6x6x1/4 COLUMN REFER
TO ARCH FOR FINAL HSS POST
LOCATIONS, TYP
UTILITY ATTACHMENT TO TRELLIS
BY OTHERS, REFER TO MEP
B
C
4'-8" 9'-9" 6'-5"7'-2" 13'-8"9'-8" 11'-2"8'-0" 4'-3" 8'-7"11'-8" 9'-2"16'-5" 4'-5"
S-302
TYP
P E
R A
R C
H M
A X
GC TO COORDINATE PEN AROUND
TRELLIS POST IN PEN WALL WITH
PEN MANUFACTURER, TYP
TM
Original drawing size is 30"x42"; Scale entities accordingly if reduced/enlarged.
SAFETY & HEALTH
REAL PROPERTY
DESIGNER
CHECKED BY
PROJECT MANAGER
PPM
EPM
SETTY
DATE
A
D
USDA S
U
NO. DATE BY
Service Research Agricultural
REVISIONS
DWG. NO
DRAWN BY
SOLICITATION NO.
1465 NORTHSIDE DRIVE, SUITE 220B
ATLANTA, GEORGIA 30318
P: 706-248-7165 www. .com
PROJECT NUMBER: SIGQ212911.14
03/18/2022 90% DOCUMENTS
WILDLIFE BARN
SHEET NAME
DESCRIPTION
04/13/2022 100% DOCUMENTS2
JUSTIN STOLZE, P.E.
PE 130920
NOT FOR CONSTRUCTION
NOT FOR PERMIT
TA
TA
CONSTRUCTION PLAN -
FOUNDATION AND TRELLIS S-101
1/8" = 1'-0"1
CONSTRUCTION PLAN - FOUNDATION
1/8" = 1'-0"2
CONSTRUCTION PLAN - TRELLIS
0'-0"
LEVEL 01
16'-0"
LEVEL 02
A D
-2'-0"
FOUNDATION
19'-10 1/2" 10'-0" 20'-1 1/2"
PRE-ENGINEERED METAL
BUILDING STRUCTURE BY
MANUFACTURER
PRE-ENGINEERED PEN
STRUCTURE BY OTHERS
WALL ENCLOSURE, REFER
TO ELEVATIONS FOR MAX
EXTENTS
ROOFING
10'-0"
TRELLIS TOS
HSS TRELLIS STRUCTURE
FOR MEP SUPPORT
B C
A D
50'-0"
/4
M A
X
B C
0'-0"
LEVEL 01
16'-0"
LEVEL 02
1 2 3 4 5 6
-2'-0"
FOUNDATION
20'-10"20'-10"20'-10"20'-10"20'-10"
10'-0"
TRELLIS TOS
0'-0"
LEVEL 01
16'-0"
LEVEL 02
123456
-2'-0"
FOUNDATION
20'-10" 20'-10" 20'-10" 20'-10" 20'-10"
10'-0"
TRELLIS TOS
AD
50'-0"
BC
TM
Original drawing size is 30"x42"; Scale entities accordingly if reduced/enlarged.
SAFETY & HEALTH
REAL PROPERTY
DESIGNER
CHECKED BY
PROJECT MANAGER
PPM
EPM
SETTY
DATE
A
D
USDA S
U
NO. DATE BY
Service Research Agricultural
REVISIONS
DWG. NO
DRAWN BY
SOLICITATION NO.
1465 NORTHSIDE DRIVE, SUITE 220B
ATLANTA, GEORGIA 30318
P: 706-248-7165 www. .com
PROJECT NUMBER: SIGQ212911.14
03/18/2022 90% DOCUMENTS
WILDLIFE BARN
SHEET NAME
DESCRIPTION
04/13/2022 100% DOCUMENTS2
JUSTIN STOLZE, P.E.
PE 130920
NOT FOR CONSTRUCTION
NOT FOR PERMIT
TA
TA
ELEVATIONS AND
SECTIONS S-201
1/8" = 1'-0"10
BUILDING SECTION - TYPICAL INTERIOR MOMENT FRAME
1/8" = 1'-0"3
WEST BUILDING ELEVATION
1/8" = 1'-0"8
SOUTH FRAMING ELEVATION
1/8" = 1'-0"15
NORTH FRAMING ELEVATION
1/8" = 1'-0"5
EAST BUILDING ELEVATION
AND ASSOCIATES, INC.
© COPYRIGHT WALTER P. MOORE
03200-GN-COVER-01
NOTES:
1. CONCRETE PROFILES AND REINFORCING STEEL CONFIGURATIONS ARE SCHEMATIC AND
ARE PROVIDED FOR ESTABLISHING TYPICAL CLEAR CONCRETE COVERS ONLY. REFER
TO STRUCTURAL PLANS AND DETAILS FOR ALL OTHER INFORMATION.
2. ALL COVERS SHOWN ARE CLEAR FROM THE OUTERMOST SURFACE OF REINFORCING
STEEL TO THE CLOSEST OUTER SURFACE OF THE CONCRETE, INCLUDING REVEALS,
DRIP GROOVES, OR RUSTICATIONS.
3. WHERE COVERS ARE DIFFERENT AS A FUNCTION OF BAR SIZE, DETAILER SHALL ADJUST
LOCATION OF TRANSVERSE REINFORCING STEEL AS REQUIRED SUCH THAT CLEAR
COVERS ARE MET FOR BOTH TRANSVERSE AND LONGITUDINAL STEEL.
4. C0, C1, AND C2 REFER TO THE CORROSION EXPOSURE CLASS OF THE CONCRETE
ELEMENT. REFER TO THE CLASSES OF CONCRETE MATRIX AND GENERAL NOTES FOR
ADDITIONAL INFORMATION.
AND ASSOCIATES, INC.
© COPYRIGHT WALTER P. MOORE
03200-FN-COVER-14A
NOTES:
1. REFER TO "NOTES FOR TYPICAL CLEAR CONCRETE COVER
FOR REINFORCING STEEL" FOR ADDITIONAL INFORMATION.
2 1/2" TOP
3" EARTH-FORMED
SIDES/ENDS
3" BOTTOM
2 1/2" BOARD-FORMED
SIDES/ENDS
AND ASSOCIATES, INC.
© COPYRIGHT WALTER P. MOORE
03200-FN-COVER-16A
NOTES:
1. REFER TO "NOTES FOR TYPICAL CLEAR CONCRETE COVER
FOR REINFORCING STEEL" FOR ADDITIONAL INFORMATION.
2" SIDES/ENDS
EACH FACE
2" TOP
WALL HORIZONTAL BAR
TENSION DEVELOPMENT AND LAP SPLICE LENGTHS
GRADE 60 REINFORCEMENT, NORMALWEIGHT CONCRETE
BAR
SIZE
LAP
CLASS
f'c = 3000 PSI f'c = 4000 PSI f'c = 5000 PSI f'c = 6000 PSI f'c = 7000 PSI f'c = 8000 PSI
#3 A
B
#4 A
B
#5 A
B
#6 A
B
#7 A
B
#8 A
B
#9 A
B
#10 A
B
#11 A
B
NOTES:
1. ALL SPLICE LENGTHS ARE IN INCHES.
2. THIS TABLE SHALL BE USED FOR WALL HORIZONTAL
BARS ONLY. REFER TO OTHER DEVELOPMENT
LENGTH TABLES FOR WALL VERTICAL BARS AND
OTHER MEMBERS.
3. THE TENSION DEVELOPMENT LENGTH (Ld) IS EQUAL
TO THE SCHEDULED "CLASS A" LAP SPLICE LENGTH.
4. FOR EPOXY-COATED BARS, MULTIPLY THE
TABULATED SPLICE LENGTHS BY 1.3.
5. WHEN LAP SPLICING BARS OF DIFFERENT SIZES,
THE LAP LENGTH IS DETERMINED BY THE SMALLER
BAR BUT MAY NOT BE LESS THAN THE "CLASS A"
SPLICE LENGTH OF THE LARGER BAR.
6. FOR CONCRETE STRENGTHS IN BETWEEN THOSE
TABULATED HERE, USE DEVELOPMENT AND LAP
SPLICE LENGTHS OF LOWER CONCRETE STRENGTH.
AND ASSOCIATES, INC.
© COPYRIGHT WALTER P. MOORE
00860-WL-DELSP-01
BAR
SIZE
LAP
CLASS
f'c = 3000 PSI f'c = 4000 PSI f'c = 5000 PSI f'c = 6000 PSI f'c = 7000 PSI f'c = 8000 PSI
CATEGORY
CATEGORY
CATEGORY
CATEGORY
CATEGORY
CATEGORY
CATEGORY
CATEGORY
CATEGORY
CATEGORY
CATEGORY
CATEGORY
#5
#6
#7
#8
#9
#10
#11
A
B
A
B
A
B
A
B
A
B
A
B
A
B
WALL VERTICAL BAR TENSION DEVELOPMENT AND LAP SPLICE LENGTHS
GRADE 60 REINFORCEMENT, NORMALWEIGHT CONCRETE
NOTES:
1. ALL SPLICE LENGTHS ARE IN INCHES.
2. THIS TABLE SHALL BE USED FOR WALL VERTICAL
BARS ONLY. REFER TO OTHER…