This document is a tank inspection and maintenance assessment report for a 501,000-gallon bolted GST (ground storage tank). The report identifies current conditions and provides specific recommendations for repairs and upgrades across multiple tank components.
Exterior and Structural Components: The tank's exterior coating is in good condition but requires cleaning via pressure washing with an antifungal solution. The shell ladder lacks a compliant cable-type safety climb device and requires installation of fall protection signage at its base. The primary roof hatch needs a Confined Space Entry sign and a locking device (to be provided by owner). The primary shell manway bolts show rust and require replacement with maintenance-free galvanized steel bolts. Foundation anchor bolts and nuts exhibit rust and require cleaning, tightening, tack welding, and repainting. The exposed concrete foundation shows cracking and spalling requiring cleaning, sealing or painting, and repair with commercial non-shrinking grout.
Interior Systems and Accessories: The tank contains excessive sediment buildup requiring emergency dry interior cleanout. Interior wet conditions and lack of heating necessitate installation of two open coil element (OCE) heaters with electrical work by others. The tank requires an anti-vortex plate on the suction line and sacrificial anodes for passive cathodic protection. Shell accessories need attention: the liquid level gauge requires adjustment, calibration, and lubrication; a thermometer must be installed; the PVC overflow pipe in poor condition must be replaced with a steel overflow system complete with standoffs, flapper valve, and screen; and a frost-proof drain valve with locking device (lock provided by owner) must be installed.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| SOW.pdf | ||
| SF1449 - 15B21326Q00000003.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Recommendations :
● Pressure wash the tank exterior with an antifungal solution.
Current Conditions :
● The tank's exterior coating is in good condition; however, it needs to be cleaned.
Coatings
Exterior
501,000 Gallon Bolted GST
Exterior
● Perform a dry interior cleanout to remove sediment. *WORK SHOULD BE PERFORMED ON AN
EMERGENCY BASIS.*
Current Conditions :
● The tank has excessive sediment buildup.
Coatings
Sediment
Sediment
Interior Wet
● Install a cable-type safety climb device on the shell ladder.
● Install a Fall Protection Required sign near the base of the shell ladder.
Current Conditions :
● The shell ladder is not in compliance for the following reason: Does not have a compliant cable-type safety climb device.
● There is currently no signage at the base of the shell ladder.
Ladders/Platforms
Shell Ladder
Shell Ladder
● Adjust, calibrate, and lubricate the existing liquid level gauge.
Current Conditions :
● The liquid level gauge needs to be adjusted and calibrated.
Shell Accessories
Liquid Level Gauge
Liquid Level Gauge
● Install a thermometer on the tank.
Current Conditions :
● The tank is not equipped with a thermometer.
Shell Accessories
Thermometer
● Replace the PVC overflow pipe with a steel overflow system, complete with standoffs, flapper valve, and screen.
Current Conditions :
● The tank is equipped with a PVC overflow pipe which appears to be in poor condition.
Shell Accessories
Overflow
Overflow
● Install a frost-proof drain valve complete with a locking device. *Lock to be provided by owner.*
Current Conditions :
● The tank is not equipped with a drain valve.
Shell Accessories
Drain
● Install two open coil element (OCE) heaters. *Electrical work by others.*
Current Conditions :
● The tank does not appear to have heaters.
Interior
Heating System
● Install an anti-vortex plate on the suction line.
Current Conditions :
● The tank is not equipped with an anti-vortex plate.
Interior
Anti-Vortex
● Install sacrificial anodes on the interior shell.
Current Conditions :
● The tank does not appear to be equipped with a passive cathodic protection system.
Interior
Cathodic Protection
● Post a Confined Space Entry sign at the primary roof hatch.
● Install a lock on the primary roof hatch. *Owner to provide a lock.*
Current Conditions :
● The primary roof hatch does not have a Confined Space Entry sign.
● The primary roof hatch does not have a locking device.
Access Points
Primary Roof Hatch
Primary Roof Hatch
● Replace the bolts on the primary shell manway with maintenance-free galvanized steel bolts.
Current Conditions :
● The bolts on the primary shell manway are showing signs of rust.
Access Points
Primary Shell Manway
Primary Shell Manway
● Clean the area around the anchor bolts, tighten the anchor nuts and tack weld the nuts to the bolts, then repaint.
Current Conditions :
● The anchor bolts and nuts are showing signs of rusting.
Foundation & Grade
Anchor Bolts
● Clean the exposed foundation and seal or paint to protect the concrete.
● Repair cracks and spalling with a commercial non-shrinking grout.
Current Conditions :
● The foundation does not appear to be sealed.
● The foundation is experiencing cracking and spalling.
Foundation & Grade