Warehouse Cooler Drawings.pdf
PDF 664 KB Posted
- Attached to
- Warehouse Cooler Bid WCSO-2027-0004
- Solicitation number
- BD-27-1099-WCSO1-WCSO1-133618
- Issued by
- Worcester County, Massachusetts
About this file
This document is an architectural drawing file for a prefabricated walk-in cooler installation at Worcester Jail. The cooler specifications are 30'-9" wide by 19'-3" deep by 8'-7" tall with a 5" reinforced ceiling, featuring poured-in-place polyurethane foam insulation. The unit includes two hinged walk-in doors (one 60" x 78" right swing and one 60" x 78" left swing), embossed galvalume ceiling panels, embossed white galvanized vertical panels, and integrated electrical connections at 115V. The cooler is designed for outdoor installation and includes accessories such as a Kason 1097 door closer, locking bar with tamperproof hardware, moistureproof switchplate, rain canopy, and LED lighting. Bally Refrigerated Boxes, Inc. is responsible for furnishing the prefabricated sectional cooler panels, doors, insulation materials, structural components including double Z-purlins for ceiling support, and associated hardware, while installation of fasteners and building integration work is specified as "by others."
The refrigeration system consists of two BQZA025-H8-HT3DD condensing units (2.5 HP each) operating on 208-230/3/60 power with R448A refrigerant, and two BLP317MA-S1D-SV+ SmartVap+ evaporators operating on 115/1/60 power, requiring two separate electrical power sources. The drawing emphasizes that it is for approval only and is not to be used for construction until finalized as an "as-built" drawing. Bally panels and doors are certified compliant with federal DOE regulations, meeting minimum R-value requirements of R-25 for coolers and R-32 for freezers when tested per ASTM C518. The document includes detailed installation requirements, notes on floor reinforcement, vapor barrier specifications, caulking recommendations, air gap circulation guidelines, and disclaimers that the drawings are guide documents only and that building design compliance with local codes remains the responsibility of the project architect or engineer.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Revised Drawings.pdf | ||
| Warehouse Walk-in Cooler Bid WCSO-2027-0004.pdf | ||
| Revised Specs.pdf | ||
| Warehouse Cooler Boiler Plate.pdf | ||
| Addendum Letter.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
AutoCAD SHX Text
L.E.D. LIGHT
AutoCAD SHX Text
VAPOR-PROOF
AutoCAD SHX Text
115V SERVICE CONNECTION
AutoCAD SHX Text
- 60" X 78" SUPERDOOR -
AutoCAD SHX Text
HINGE
AutoCAD SHX Text
THIRD
AutoCAD SHX Text
DX-01
AutoCAD SHX Text
HINGE
AutoCAD SHX Text D69B
AutoCAD SHX Text
LATCH
AutoCAD SHX Text D60
AutoCAD SHX Text
36" HIGH DIAMOND TREAD
AutoCAD SHX Text
CANOPY
AutoCAD SHX Text
RAIN
AutoCAD SHX Text Kason 1097
AutoCAD SHX Text Door Closer
AutoCAD SHX Text
OFF
AutoCAD SHX Text
ON
AutoCAD SHX Text
MOISTUREPROOF
AutoCAD SHX Text
SWITCHPLATE
AutoCAD SHX Text
LOCKING BAR
AutoCAD SHX Text
COOLER
AutoCAD SHX Text
ITEM 1
AutoCAD SHX Text
COOLER
AutoCAD SHX Text
ITEM 2
AutoCAD SHX Text S
AutoCAD SHX Text 60" X 78"
AutoCAD SHX Text
SUPERDOOR
AutoCAD SHX Text S
AutoCAD SHX Text 60" X 78"
AutoCAD SHX Text
SUPERDOOR
AutoCAD SHX Text
KEA1-10FT
AutoCAD SHX Text
KEA2-10FT
AutoCAD SHX Text
KEA3-10FT
AutoCAD SHX Text
KEA4-10FT
AutoCAD SHX Text
KEA7-10FT
AutoCAD SHX Text
KEA8-10FT
AutoCAD SHX Text
KEA7A-10FT
AutoCAD SHX Text
KEA8A-10FT
AutoCAD SHX Text
KEA7-10FT
AutoCAD SHX Text
KEA8-10FT
AutoCAD SHX Text
V23B-NSF
AutoCAD SHX Text
V23B-NSF
AutoCAD SHX Text P1 (7.6")
AutoCAD SHX Text
NOTE-D
AutoCAD SHX Text
DOUBLE 'Z' PURLIN
AutoCAD SHX Text
5" X 2.5" X 14 GA.
AutoCAD SHX Text
EXT. HEIGHT
AutoCAD SHX Text
L/FLOOR
AutoCAD SHX Text
EXT. HEIGHT
AutoCAD SHX Text
L/FLOOR
AutoCAD SHX Text
DX-01
AutoCAD SHX Text
115V SERVICE CONNECTION
AutoCAD SHX Text
115V SERVICE CONNECTION
AutoCAD SHX Text
DX-02
AutoCAD SHX Text
+ 3/8" ASSEMBLY ALLOWANCE
AutoCAD SHX Text
NOTE-A
AutoCAD SHX Text
NOTE-B
AutoCAD SHX Text
NOTE-B
AutoCAD SHX Text
NOTE-A
AutoCAD SHX Text
NOTE-C
AutoCAD SHX Text P2 (19.1")
AutoCAD SHX Text
WRENCH HOLES
AutoCAD SHX Text
DOUBLE 'Z' PURLIN
AutoCAD SHX Text
5" X 2.5" X 14 GA.
AutoCAD SHX Text
HOOKS
AutoCAD SHX Text
PINS
AutoCAD SHX Text
BLP317MA-S1D-SV+
AutoCAD SHX Text
MIN
AutoCAD SHX Text 12"
AutoCAD SHX Text
BLP317MA-S1D-SV+
AutoCAD SHX Text
MIN
AutoCAD SHX Text 12"
AutoCAD SHX Text
NOTE-D
AutoCAD SHX Text
NOTE-D
AutoCAD SHX Text
NOTE-D
AutoCAD SHX Text
NOTE-B
AutoCAD SHX Text
SLOPE
AutoCAD SHX Text
PEAK
AutoCAD SHX Text
EAVE
AutoCAD SHX Text
- TAPERED INSULATION LAYOUT -
AutoCAD SHX Text 1/2"
AutoCAD SHX Text 1-1/2"
AutoCAD SHX Text 1"
AutoCAD SHX Text 2"
AutoCAD SHX Text 2-1/2"
AutoCAD SHX Text 3"
AutoCAD SHX Text
2"FLAT(X1)
AutoCAD SHX Text 12"
AutoCAD SHX Text 1 "12"
AutoCAD SHX Text 2"
AutoCAD SHX Text 1"
AutoCAD SHX Text 58"
AutoCAD SHX Text 2 "12"
AutoCAD SHX Text 12"
AutoCAD SHX Text 1"
AutoCAD SHX Text 5/8"
AutoCAD SHX Text
QTY
AutoCAD SHX Text 1"
AutoCAD SHX Text
ROOF PIECE THICKNESS
AutoCAD SHX Text
TO
AutoCAD SHX Text 1-1/2"
AutoCAD SHX Text 1/2"
AutoCAD SHX Text
TO
AutoCAD SHX Text 1"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 1-1/2"
AutoCAD SHX Text
TO
AutoCAD SHX Text 2"
AutoCAD SHX Text 2"
AutoCAD SHX Text
TO
AutoCAD SHX Text 2-1/2"
AutoCAD SHX Text
AutoCAD SHX Text
PART# 221172 FLAT
AutoCAD SHX Text
ALL HOLES ARE 1/4" DIA. USE 12-14 X 1-1/2" TEKS TO ASSEMBLE
AutoCAD SHX Text
%%UPURLIN ASSEMBLIES TO BE ATTACHED
AutoCAD SHX Text
%%UTO END PLATES IN FIELD
AutoCAD SHX Text
PAINT ASSEMBLIES AFTER GUSSETS ARE ATTACHED AND ALL HOLES ARE DRILLED
AutoCAD SHX Text %%UDOUBLE (5" x 2-1/2") - 14GA. Z-PURLIN DETAIL
AutoCAD SHX Text
%%UASSEMBLE PURLINS AND GUSSETS INTO (1) ASSEMBLY
AutoCAD SHX Text
ZEE PURLINS
AutoCAD SHX Text
END PLATE
AutoCAD SHX Text
GUSSET PLATE (WELDED)
AutoCAD SHX Text
BETWEEN PURLINS
AutoCAD SHX Text
%%UASSEMBLY DETAIL
AutoCAD SHX Text
BROKEN OUT FOR CLARITY
AutoCAD SHX Text
GUSSETS (TYPICAL)
AutoCAD SHX Text
FRONT
AutoCAD SHX Text 12-14 x 1-1/2" TEKS (ATTACHED TO END PLATE)
AutoCAD SHX Text
GUSSET WELDED AT BALLY
AutoCAD SHX Text
SIDE
AutoCAD SHX Text IF UNDER SLAB DRAINAGE, HEAT, OR VENTILATION IS REQUIRED DO NOT FOLLOW THESE DETAILS.
AutoCAD SHX Text
(IF APPLICABLE)
AutoCAD SHX Text
REINFORCED
AutoCAD SHX Text
%%UFLOOR DETAIL
AutoCAD SHX Text DIMENSIONAL AND MATERIAL DESIGN TO BE DETERMINED BY PROJECT CONSTRUCTION ENGINEER.
AutoCAD SHX Text
THEY ARE NOT INTENDED TO BE CONSTRUCTION DRAWINGS AS CONDITIONS MAY VARY WIDELY.
AutoCAD SHX Text
THESE DRAWINGS ARE INTENDED TO SERVE AS GUIDE LINE DRAWINGS ONLY.
AutoCAD SHX Text IF THIS IS NOT THE GROUND FLOOR, ENGINEERING SHOULD REVIEW FOR POSSIBLE CONDENSATION
AutoCAD SHX Text
PROBLEMS.
AutoCAD SHX Text
CONCRETE.
AutoCAD SHX Text
NOTE:
AutoCAD SHX Text
(UNLESS OTHERWISE SPECIFIED). THIS INCLUDES WALLS AND CEILING PANELS.
AutoCAD SHX Text
BALLY TO FURNISH THE PREFAB SECTIONAL WALK-IN COOLER OR FREEZER ONLY
AutoCAD SHX Text
NOTE:
AutoCAD SHX Text
NOTE:
AutoCAD SHX Text
NOTE:
AutoCAD SHX Text
LESS STEPPLATE
AutoCAD SHX Text
DUAL DUROMETER
AutoCAD SHX Text
WIPER GASKET
AutoCAD SHX Text %%uDOOR SILL
AutoCAD SHX Text
OUTER
AutoCAD SHX Text
WALL
AutoCAD SHX Text
PARTITION
AutoCAD SHX Text
WALL
AutoCAD SHX Text
OUTER
AutoCAD SHX Text
WALL
AutoCAD SHX Text
MEMBRANE ROOF
AutoCAD SHX Text
(DURO-LAST)
AutoCAD SHX Text
HOLD DOWN BUTTON
AutoCAD SHX Text
(WITH SCREW)
AutoCAD SHX Text
(BY OTHERS)
AutoCAD SHX Text
FLASHING
AutoCAD SHX Text
EXISTING
AutoCAD SHX Text
BUILDING
AutoCAD SHX Text
WALL
AutoCAD SHX Text
PANEL
AutoCAD SHX Text
VERTICAL
AutoCAD SHX Text
CEILING PANELS
AutoCAD SHX Text
VERTICAL
AutoCAD SHX Text
PANEL
AutoCAD SHX Text
BAR
AutoCAD SHX Text
TERMINATION
AutoCAD SHX Text
CEILING PANELS
AutoCAD SHX Text
TAPERED INSULATION
AutoCAD SHX Text
VAPOR BARRIER
AutoCAD SHX Text
SCREW FASTENS
AutoCAD SHX Text
TO CEILING PANEL.
AutoCAD SHX Text
FASTENER
AutoCAD SHX Text
TERMINATION BAR AND CAULKING
AutoCAD SHX Text
MEMBRANE ROOF
AutoCAD SHX Text
INSTALLATION DETAIL
AutoCAD SHX Text
(TAPERED INSULATION)
AutoCAD SHX Text
(SEE NOTIFICATION: IM-338-91 FIG.#13)
AutoCAD SHX Text %%uPANEL ATTACHMENT DETAIL (VERTICAL TO FLOOR)
AutoCAD SHX Text
PLUS CENTERLINE OF 46" VERTICAL PANELS.
AutoCAD SHX Text
AND WA-1 USED AT ALL OTHER VERTICAL JOINTS
AutoCAD SHX Text
NOTE:
AutoCAD SHX Text
SLEEVE ANCHOR
AutoCAD SHX Text 5/16" X 1-1/2"
AutoCAD SHX Text
VERTICAL PANEL
AutoCAD SHX Text
%%UFINISH FLOOR
AutoCAD SHX Text
TEKS-SCREW
AutoCAD SHX Text
#12-14 HEX HEAD
AutoCAD SHX Text
WALL ANCHORS
AutoCAD SHX Text
WA-1 & WA-2
AutoCAD SHX Text 1/4"%%c
AutoCAD SHX Text 3/8"%%c
AutoCAD SHX Text
1-5/8" X 2-1/2" X 6"-LONG
AutoCAD SHX Text
WA-2
AutoCAD SHX Text 1/4"%%c
AutoCAD SHX Text 3/8"%%c
AutoCAD SHX Text
1-5/8" X 2-1/2" X 4"-LONG
AutoCAD SHX Text
WA-1
AutoCAD SHX Text
WA-2 WALL ANCHOR USED AT CORNER JOINTS
AutoCAD SHX Text
(SEE INSTRUCTION #IM-265-88)
AutoCAD SHX Text
RE-INFORCEMENT
AutoCAD SHX Text
PLATE
AutoCAD SHX Text
EXTERIOR
AutoCAD SHX Text
FLASHING
AutoCAD SHX Text
4X2 EXTERIOR
AutoCAD SHX Text
(OUTDOOR FLASHING)
AutoCAD SHX Text %%uSECTION VIEW%%u
AutoCAD SHX Text
FINISHED FLOOR
AutoCAD SHX Text
INTERIOR
AutoCAD SHX Text 4" X 2"
AutoCAD SHX Text
TEK SCREW
AutoCAD SHX Text
VERTICAL PANEL
AutoCAD SHX Text
OUTDOOR FLASHING
AutoCAD SHX Text
CAULK
AutoCAD SHX Text
CAULK
AutoCAD SHX Text
BY
AutoCAD SHX Text
CHK'D
AutoCAD SHX Text
LBL'D
AutoCAD SHX Text
DATE
AutoCAD SHX Text
BY
AutoCAD SHX Text
LBL'D
AutoCAD SHX Text
DATE
AutoCAD SHX Text
SIGNED
AutoCAD SHX Text
SIGNED APPROVAL
AutoCAD SHX Text
DRAWN BY
AutoCAD SHX Text
DATE
AutoCAD SHX Text
DATE
AutoCAD SHX Text
BY
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
REV
AutoCAD SHX Text
NUMBER
AutoCAD SHX Text
ORDER
AutoCAD SHX Text
NUMBER
AutoCAD SHX Text
DRAWING
AutoCAD SHX Text
FOR
AutoCAD SHX Text
OR THE INFORMATION SHOWN HEREON WILL BE
AutoCAD SHX Text
MADE TO A THIRD PARTY WITHOUT PRIOR
AutoCAD SHX Text
WRITTEN CONSENT FROM BALLY REFRIGERATED
AutoCAD SHX Text
BOXES, INC.
AutoCAD SHX Text
RESTRICTED, CONFIDENTIAL DOCUMENT.
AutoCAD SHX Text
THIS DRAWING AND ALL INFORMATION SHOWN
AutoCAD SHX Text
HEREON ARE THE EXCLUSIVE PROPERTY OF
AutoCAD SHX Text
BALLY REFRIGERATED BOXES, INC., AND ARE
AutoCAD SHX Text
SUBMITTED ONLY ON A CONFIDENTIAL BASIS.
AutoCAD SHX Text
THE RECIPIENT AGREES NOT TO REPRODUCE
AutoCAD SHX Text
THE DRAWING, TO RETURN IT UPON REQUEST,
AutoCAD SHX Text
AND THAT NO DISCLOSURE OF THE DRAWING
AutoCAD SHX Text
THIS DRAWING HAS BEEN CAREFULLY CHECKED BY OUR DRAFTING
AutoCAD SHX Text
DEPARTMENT. HOWEVER, ERRORS OF INTERPRETATION CAN
AutoCAD SHX Text
OCCUR. THEREFORE, BEFORE YOU RETURN DRAWING MARKED
AutoCAD SHX Text
"APPROVED", BE CERTAIN THAT YOU CHECK THEM CAREFULLY.
AutoCAD SHX Text
NOTE - THIS ORDER WILL NOT BE SCHEDULED FOR PRODUCTION
AutoCAD SHX Text
UNTIL RECEIPT OF APPROVED DRAWINGS BY BALLY.
AutoCAD SHX Text
PLEASE READ
AutoCAD SHX Text THESE DRAWINGS ARE NOT TO BE CONSIDERED AS APPROVED BY LOCAL OR STATE BUILDING AUTHORITIES.
AutoCAD SHX Text THEY HAVE BEEN PREPARED SOLELY FOR THE GUIDANCE OF REGISTERED ARCHITECTS AND ENGINEERS AND FOR THE ASSISTANCE OF
AutoCAD SHX Text LOCAL INSTALLERS. IT IS THE RESPONSIBILITY OF THE PROJECT ARCHITECT OR ENGINEER TO ASSURE THE BUILDING DESIGN MEETS
AutoCAD SHX Text LOCAL CODE REQUIREMENTS. THIS INCLUDES STRUCTURAL DESIGN AS WELL AS ANY WORK PERFORMED BY THE GENERAL CONTRACTOR.
AutoCAD SHX Text BALLY REFRIGERATED BOXES, INC., IN PREPARING THESE DRAWINGS AND SPECIFICATIONS, DOES NOT ASSUME ANY RESPONSIBILITY
AutoCAD SHX Text THE DRAWINGS AND SPECIFICATIONS DESCRIBE A BUILDING ASSEMBLED FROM BALLY PANELS INSULATED WITH URETHANE
AutoCAD SHX Text "FOAMED-IN-PLACE". THE SIZE AND SHAPE IS THAT WHICH MOST CLEARLY MEETS DIMENSIONS SUBMITTED BY THE USER.
AutoCAD SHX Text BALLY REFRIGERATED BOXES, INC., PROVIDES PANELS FREQUENTLY SPECIFIED BY OTHERS, AND IS NOT RESPONSIBLE FOR THE
AutoCAD SHX Text SELECTION OR RECOMMENDATION BY OTHERS OF THE PANEL FINISH FOR ANY BUILDING OR WALK-IN APPLICATION.
AutoCAD SHX Text
FOR THE SUCCESSFUL COMPLETION OR USAGE OF THE STRUCTURE DESCRIBED.
AutoCAD SHX Text
IMPORTANT - PLEASE READ
AutoCAD SHX Text
REFRIGERATED BOXES, INC.
AutoCAD SHX Text
TM
AutoCAD SHX Text
MOREHEAD CITY, NC 28557
AutoCAD SHX Text
135 LITTLE NINE DRIVE
AutoCAD SHX Text
FAX:
AutoCAD SHX Text
PHONE: (252) 240-2829
AutoCAD SHX Text
PHONE: (610) 702-2210
AutoCAD SHX Text
FAX:
AutoCAD SHX Text
BALLY, PA 19503
AutoCAD SHX Text
20 NORTH FRONT ST. (SUITE 8)
AutoCAD SHX Text
BALLY (NC OFFICE)
AutoCAD SHX Text
BALLY (PA OFFICE)
AutoCAD SHX Text
(252) 240-0384
AutoCAD SHX Text
(610) 702-2211
AutoCAD SHX Text
SHEET 1 OF 1
AutoCAD SHX Text
WORCESTER JAIL
AutoCAD SHX Text
COOLER/COOLER
AutoCAD SHX Text
76734AE
AutoCAD SHX Text
RJC
AutoCAD SHX Text 09/14/26
AutoCAD SHX Text 76734
AutoCAD SHX Text
SCALE: 1/2" = 1' - 0"
AutoCAD SHX Text
THRU ENTRANCE DOOR
AutoCAD SHX Text
%%USECTION VIEW%%U
AutoCAD SHX Text
SCALE: 1/2" = 1' - 0"
AutoCAD SHX Text
%%UPLAN VIEW-A%%U
AutoCAD SHX Text
SPECIFICATIONS
AutoCAD SHX Text
30'-9" X 19'-3" X 8'-7" W/ 5" REINFORCED CEILING
AutoCAD SHX Text
INSTALLATION
AutoCAD SHX Text
- OUTDOOR
AutoCAD SHX Text
- LOADING HEIGHT - AT LEAST 18" OF OPEN SPACE MUST BE
AutoCAD SHX Text
MAINTAINED BETWEEN TOP OF PRODUCT AND CEILING PANELS
AutoCAD SHX Text
- INTERIOR ACCESS SPEED-LOK HOLES ARE FURNISHED
AutoCAD SHX Text
STANDARD ON ALL MULTI-SPAN CEILING PANELS
AutoCAD SHX Text
IF EXTERIOR ACCESS IS REQUIRED, PLEASE CHECK BOX.
AutoCAD SHX Text
INSULATION
AutoCAD SHX Text
EXTERIOR FINISH
AutoCAD SHX Text
- EMBOSSED GALVALUME CEILING
AutoCAD SHX Text
- EMBOSSED WHITE GALVANIZED VERTICALS
AutoCAD SHX Text
INTERIOR FINISH
AutoCAD SHX Text
- EMBOSSED WHITE GALVANIZED
AutoCAD SHX Text
DOORS/ACCESSORIES
AutoCAD SHX Text
- (1) 60" X 78" RIGHT SWING HINGED WALK-IN DOOR
AutoCAD SHX Text
- (1) 60" X 78" LEFT SWING HINGED WALK-IN DOOR
AutoCAD SHX Text R
AutoCAD SHX Text
LOCKING DIRECTION
AutoCAD SHX Text
HOOK EDGE (TYP)
AutoCAD SHX Text
GASKET SEAL
AutoCAD SHX Text
TURN CLOCKWISE
AutoCAD SHX Text
INTERIOR
AutoCAD SHX Text
SPEED-LOC (TYP)
AutoCAD SHX Text
HOOK
AutoCAD SHX Text
EDGE
AutoCAD SHX Text
EXTERIOR
AutoCAD SHX Text
WALL
AutoCAD SHX Text
PARTITION WALL CAULKING DETAIL
AutoCAD SHX Text
BREAKER PANELS
AutoCAD SHX Text
PARTITION
AutoCAD SHX Text
(LOOKING DOWN)
AutoCAD SHX Text
VERTICAL PANELS
AutoCAD SHX Text
ADDED PRECAUTION AGAINST VAPOR LEAKS,
AutoCAD SHX Text
BALLY RECOMMENDS THAT ALL PARTITION WALL
AutoCAD SHX Text PANELS: "%%uJOINTS BE CAULKED DURING ASSEMBLY%%u".
AutoCAD SHX Text
PANELS TO (VERTICAL, CEILING, FLOOR) BREAKER
AutoCAD SHX Text
PIN
AutoCAD SHX Text
EDGE
AutoCAD SHX Text
AutoCAD SHX Text
VERTICAL, CEILING, FLOOR
AutoCAD SHX Text
BETWEEN PANELS
AutoCAD SHX Text
CAULK BEAD
AutoCAD SHX Text
WARM SIDE OF PARTITION
AutoCAD SHX Text
- ELECTRICAL CONNECTION
AutoCAD SHX Text
AIR GAP/CIRCULATION RECOMMENDATION
AutoCAD SHX Text
BALLY RECOMMENDS A 2" GAP BETWEEN WALK-IN
AutoCAD SHX Text
VERTICAL PANELS AND EXISTING BUILDING WALLS FOR
AutoCAD SHX Text
PROPER AIR CIRCULATION. IT IS ALSO RECOMMENDED
AutoCAD SHX Text
THAT AIR EXCHANGE/CIRCULATION BE PROVIDED FOR
AutoCAD SHX Text
WALK-INS THAT ARE WITHIN AN ENCLOSED AREA.
AutoCAD SHX Text
%%USTATIONARY LOAD%%U:
AutoCAD SHX Text
%%UMOBILE EQUIPMENT%%U (DOLLIES OR CARTS):
AutoCAD SHX Text
(ALUMINUM DIAMOND TREAD OVERLAY IS ALSO AN OPTION).
AutoCAD SHX Text
%%UFORK-LIFT USE%%U:
AutoCAD SHX Text
A MINIMUM OF 4" REINFORCED CONCRETE
AutoCAD SHX Text
BALLY FLOOR PANEL GUIDELINES
AutoCAD SHX Text
LIMIT 700 LBS. SQ. FT. (UNIFORMLY DISTRIBUTED)
AutoCAD SHX Text
BALLY FLOOR PANELS MUST BE REINFORCED
AutoCAD SHX Text
WITH FOAMED PLYWOOD UNDER INTERIOR FLOOR SKIN.
AutoCAD SHX Text
MUST BE POURED OVER BALLY FLOOR PANELS.
AutoCAD SHX Text
CAULK BOTH SIDES OF HANGERS
AutoCAD SHX Text
(#004671) PC-A
AutoCAD SHX Text
PANEL JOINT HANGER CLIP
AutoCAD SHX Text 2"
AutoCAD SHX Text 2"
AutoCAD SHX Text
SURFACE
AutoCAD SHX Text
PANEL
AutoCAD SHX Text
EXTERIOR
AutoCAD SHX Text %%uREQUIRED WHEN (3 OR 4) JOINT INTERSECTIONS OCCUR
AutoCAD SHX Text
PREVENTING VAPOR LEAKS
AutoCAD SHX Text
CAULKING GUN;
AutoCAD SHX Text
CAULK AT PANEL INTERSECTIONS
AutoCAD SHX Text
AND 2" ALONG PANEL JOINTS.
AutoCAD SHX Text
THIS DRAWING IS TO BE USED FOR
AutoCAD SHX Text
FOR INSTALLATION!
AutoCAD SHX Text
EVERY SHIPPED ORDER WILL HAVE
AutoCAD SHX Text "%%uAPPROVAL ONLY%%u".
AutoCAD SHX Text
-> DO NOT USE THIS DRAWING
AutoCAD SHX Text
A FINALIZED "AS-BUILT" DRAWING.
AutoCAD SHX Text
- POURED IN-PLACE POLYURETHANE FOAM
AutoCAD SHX Text
- BALLY PANELS AND DOORS ARE CERTIFIED COMPLIANT WITH CURRENT FEDERAL DOE REGULATIONS FOR WALK IN COOLERS & FREEZERS
AutoCAD SHX Text
- BALLY PANELS AND DOORS EXCEED MINIMUM R-VALUES* FOR COOLERS (MINIMUM R-25, EXCLUDING FLOORS), AND FREEZERS (MIN. R-32, EXCEPT FLOORS, WHICH ARE MIN. R-28) *WHEN TESTED PER ASTM C518 TO FEDERAL REG. 431.304
AutoCAD SHX Text
- SUPERDOOR: 3RD HINGE, DT INT & EXT 36"H
AutoCAD SHX Text
- LOCKING BAR (TAMPERPROOF HARDWARE)
AutoCAD SHX Text
- MOISTUREPROOF SWITCHPLATE
AutoCAD SHX Text
- K1097 DOOR CLOSER
AutoCAD SHX Text
- RAIN CANOPY (SHIPPED LOOSE)
AutoCAD SHX Text
TOTAL WATTS
AutoCAD SHX Text
DEFROST
AutoCAD SHX Text
REFRIGERATION
AutoCAD SHX Text
MODEL NUMBER
AutoCAD SHX Text
QTY
AutoCAD SHX Text
RFGT
AutoCAD SHX Text H/P
AutoCAD SHX Text
COMPRESSOR
AutoCAD SHX Text
- BY BALLY
AutoCAD SHX Text
POWER
AutoCAD SHX Text
SUPPLY
AutoCAD SHX Text
FAN MTRS
AutoCAD SHX Text
HP
AutoCAD SHX Text
LRA
AutoCAD SHX Text
RLA
AutoCAD SHX Text
QTY
AutoCAD SHX Text
FLA
AutoCAD SHX Text
FUSE
AutoCAD SHX Text
AMPS
AutoCAD SHX Text
MCA
AutoCAD SHX Text
CMPT
AutoCAD SHX Text
MAX
AutoCAD SHX Text
TYPE
AutoCAD SHX Text
(CONDENSING UNIT MOUNTED
AutoCAD SHX Text
OUTDOORS)
AutoCAD SHX Text
ALL CONDENSATION DRAIN LINES MUST BE SLOPED AT LEAST 1:12.
AutoCAD SHX Text FREEZER CONDENSATION DRAIN LINES MUST BE HEATED, INSULATED AND TRAPPED INDIVIDUALLY.
AutoCAD SHX Text
INSTALLATION
AutoCAD SHX Text
BY OTHERS
AutoCAD SHX Text 1"
AutoCAD SHX Text 12"
AutoCAD SHX Text
ALL SPECIFICATIONS LISTED ABOVE ARE FOR %%UINDIVIDUAL UNITS ONLY.
AutoCAD SHX Text
AND ONE TO THE SMARTVAP+ EVAPORATOR.
AutoCAD SHX Text
POWER SOURCES; ONE TO THE CONDENSING UNIT
AutoCAD SHX Text
SMARTVAP+ REFRIGERATION REQUIRES TWO SEPARATE
AutoCAD SHX Text
NOTE
AutoCAD SHX Text
- (2) BQ WIND GUARDS FOR CONDENSING UNITS
AutoCAD SHX Text 208-230/3/60
AutoCAD SHX Text R448A
AutoCAD SHX Text
AutoCAD SHX Text 2.5
AutoCAD SHX Text
BQZA025-H8-HT3DD
AutoCAD SHX Text 13.7
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 1.7
AutoCAD SHX Text 18.8
AutoCAD SHX Text C
AutoCAD SHX Text
AutoCAD SHX Text 15.4
AutoCAD SHX Text 115/1/60
AutoCAD SHX Text
BLP317MA-S1D-SV+
AutoCAD SHX Text
AutoCAD SHX Text .07
AutoCAD SHX Text
AutoCAD SHX Text 3.0
AutoCAD SHX Text
AutoCAD SHX Text 3.3
AutoCAD SHX Text C
AutoCAD SHX Text 3.0
AutoCAD SHX Text
- DOUBLE 'Z' PURLINS 5" X 2.5" X 14GA.
AutoCAD SHX Text
CEILING SUPPORT
AutoCAD SHX Text
- PURLINS BY BALLY
AutoCAD SHX Text
GENERAL NOTES
AutoCAD SHX Text
- NOTE D:
AutoCAD SHX Text BALLY TO FURNISH 14GA. GALVANIZED STEEL FOAMED IN PLACE AGAINST INTERIOR SKIN OF VERTICAL AS SHOWN. STEEL BEGINS 12" FROM TOP OF VERTICAL AND EXTENDS TO TOP OF PANEL.
AutoCAD SHX Text
- NOTE A:
AutoCAD SHX Text BALLY TO FURNISH 1/8" ALUMINUM DIAMOND TREAD 48"H WAINSCOT TO COVER EXPOSED EXTERIOR AS SHOWN.
AutoCAD SHX Text 1/8"
AutoCAD SHX Text 12"
AutoCAD SHX Text BALLY TO FURNISH TAPERED INSULATION. SLOPE: BALLY TO FURNISH (#000330) 4 MIL. VAPOR BARRIER (10FT WIDE) FOR INSTALLATION BETWEEN MEMBRANE ROOF AND TAPERED INSULATION.
AutoCAD SHX Text
- NOTE:
AutoCAD SHX Text
- NOTE:
AutoCAD SHX Text BALLY TO FURNISH LESS FLOOR OUTDOOR FLASHING. ALL FASTENERS AND INSTALLATION BY OTHERS.
AutoCAD SHX Text BALLY ADVISES AGAINST OUTDOOR INSTALLATION OF WAINSCOT DUE TO RISK OF EXPOSURE TO MOISTURE BETWEEN EXTERIOR WALK-IN METAL SKIN AND WAINSCOT. ALL SEAMS MUST BE PROPERLY SEALED AND MAINTAINED TO AVOID POTENTIAL DAMAGE. INSTALLATION AND WATERTIGHT SEALING OF SEAMS IS BY OTHERS.
AutoCAD SHX Text
WAINSCOT FOR OUTDOOR APPLICATIONS
AutoCAD SHX Text
- NOTE:
AutoCAD SHX Text
ADDITIONAL LIGHTING & STRIP CURTAINS TO BE FURNISHED BY OTHERS
AutoCAD SHX Text
- NOTE:
AutoCAD SHX Text BALLY TO FURNISH EW CLOSURE TRIM. PLEASE ADVISE SIZE AND QUANTITY. FASTENERS AND INSTALLATION BY OTHERS.
AutoCAD SHX Text
(L/FLOOR, EXTENDED HEIGHT)
AutoCAD SHX Text
- NOTE C:
AutoCAD SHX Text
MEMBRANE ROOF FLANGED UP ALONG THIS EDGE, FLASHING TO BUILDING WALL BY OTHERS.
AutoCAD SHX Text
- NOTE B:
AutoCAD SHX Text BALLY TO FURNISH WA-1 AND WA-2 WALL ANCHORS AND R.E.B. (REINFORCED, EXTERIOR, BOTTOM) FOR VERTICAL PANEL BASE ATTACHMENT ALONG (3) WALLS AS SHOWN.
| Sheets and Views |
| Layout1 |
File details come from the government source that posted it. Updated .