This is a project specifications document for the Wacousta Building located at 9135 Herbison Road in Eagle, Michigan, involving the removal and replacement of an existing fire alarm system. The project scope includes fire alarm system design and engineering, plan review submittals to the Michigan Bureau of Fire Services and Bureau of Construction Codes, electrical permitting, demolition of the existing system, installation of field devices and conduit, control panel and NAC Booster installation and wiring, device and system programming, acceptance testing and certification, and owner training. The system will be designed to comply with the Michigan Building Code (2021) and NFPA 72 National Fire Alarm Signaling Code (2019). The equipment specification includes a Siemens FV922 Cerberus Pro Voice Fire Alarm Control Panel as the primary control unit, along with 25 dual action manual pull stations, 29 optical smoke detectors, heat detectors, multi-criteria smoke/heat/CO detectors, 10 duct smoke detector housings, 47 ceiling mount and 9 wall mount addressable speaker/strobes, 10 ceiling mount and 11 wall mount strobes, 11 addressable relay modules, monitor modules, remote test switches, surge protection devices, and four sealed lead-acid backup batteries.

The specifications include an allowance of $10,000 at the owner's discretion for contingencies or changes. Bidders are required to submit a complete set of fire alarm shop drawings and supporting documentation electronically through the Accela system using project number PR2026BFS-000075, with explicit instructions not to create a new BFS report number for plan submittals. No specific pricing terms, response deadlines, or award dates are outlined in this specifications document, which focuses primarily on the technical requirements and equipment specifications for the fire alarm system replacement project.

View the file

Other files

File Type Posted
Wacousta - Voice Evacuation Fire Alarm System RFP.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Wacousta Building (9135 Herbison Road, Eagle, MI) Voice Evacuation Fire Alarm System

Project Specifications

Remove existing fire alarm panel and system devices and design and install a replacement system to meet current code and standards. The system will be designed based on your architectural drawings, the Michigan Building Code (2021), and NFPA 72 National Fire Alarm Signaling Code (2019).

Scope of Work

1. Fire alarm system design and engineering.

2. Plan review submittals. (Bureau of Fire Services & Bureau of Construction Codes).

3. Electrical permit (Michigan Bureau of Construction Codes).

4. Demolition of existing fire alarm system.

5. Installation and termination of field devices.

6. Conduit, cable, and device boxes.

7. Installation and wiring of control panel and NAC Booster.

8. Device and system programming.

9. Acceptance testing and certification of system.

10. Owner training.

11. Allowance of $10,000 at owners discretion.

Equipment 1 - Siemens FV922 Cerberus Pro Voice Fire Alarm Control Panel (Black) 25 - Siemens XMS-D Dual Action Manual Pull Station 29 - Siemens OP-921 Optical Smoke Detector 1 - Siemens OOHC941 Multi-criteria Smoke/Heat/CO Detector 2 - Siemens Hl-921 Heat Detector 31 - Siemens DB-11 Standard Detector Base 1 - Siemens ABHW-4B Audible Detector Base 1 - Siemens ABHW-4B Audible Detector Base 10 - Siemens FDBZ492 Duct Smoke Detector Housing w/Sample Tube & Detector 10 - Siemens TSM-1X Remote Test Switch with Indicator LED 11 - Siemens XTRI-R Addressable Relay Module 1 - Siemens XTRI-S Addressable Single Monitor Module 1 - Siemens XTRI-D Addressable Dual Monitor Module 47 - Siemens SC-SS-CR-F ACEND Ceiling Mount Speaker/Strobe (Red) 9 - Siemens SC-SS-WR-F ACEND Wall Mount Speaker/Strobe (Red) 10 - Siemens SC-ST-CR-F ACEND Ceiling Mount Strobe (Red) 11 - Siemens SC-ST-WR-F ACEND Wall Mount Strobe (Red) 1 - Space Age Electronics SPD Surge Protection Device 1 - Space Age Electronics SDB System Document Box 4 - Power Patrol Sealed Lead-Acid Batteries

Note – A completed set of fire alarm shop drawings and supporting documentation shall be submitted for review. Fire alarm shop drawing shall be submitted electronically to the Accela system, using project number PR2026BFS-000075. Please do not create a new BFS report number for the submittal of the plans.