BLDG 436
TYPE OF TOWER: Self Support
TOWER HEIGHT: 160'
2.3.4 Furnish and install RF signage.
Entrance and Compound
Bent/Rusty/Damaged Diagonal
2.3.1 Repair or replace all damaged/missing tower structural member(s) to include legs and braces.
2.3.5 Properly install structural bolts such that the bolt head is on the underside and the nut screws in topside.
2.3.6 Furnish and install Waveguide Ice Bridge to properly support and protect coax (Not to exceed 10'x10'x24').
2.3.13 Wire Brush and Cold Galvanize rusted Brackets and/or mounting hardware.
2.3.10 Furnish and install lightning rod: 4' copper clad air terminal with threaded end for mounting at the top of the tower as recommended by EIA/TIA (Electronic Industries Alliance/Telecommunications Industry Association).
2.3.12 Remove all unused hardware, antenna(s), lines, equipment from tower and provide proper disposal.
2.3.12 Tower has unused hardware, lines/antennas and/or equipment, remove all unused equipment from the tower.
2.3 Remove (1) 4' Dish.
2.3.2 Replace broken/damaged beacon/sidelight lenses. Dispose of any broken/damaged hardware.
2.3.3 Troubleshoot light system and repair or replace. Contractor will evaluate and report to ATC POC for decision on repair versus replacement.
2.3.8 Furnish light monitoring equipment: ITL Mon-930 unit Manufactured by International Tower Lighting or equivalent.
2.3.9 Furnish and install FAA alarmed controller or alarm contacts on tower: ITL RLC-201 Alarmed Controller, Manufactured by International Tower Lighting or equivalent.
View down
H-FIELD
TOWER HEIGHT: 160’
2.5.7 Remove all unused hardware, antenna(s), lines, equipment from tower and provide proper disposal.
2.5.6 Properly secure coaxial jumper(s).
2.5.3 Furnish and install W/G Bridge to properly support and protect coax.(Not to exceed 10x10x24)
2.5.2 Furnish and install RF radiation signage.
2.5.1 Furnish and install ASTM 325 structural bolts.
2.5.1 Furnish and install ASTM 325 structural bolts.
2.5.5 Furnish and install (1) Max 12" Ground bus bar with insulators and brackets.
2.5.4 Properly secure feed lines.
2.5.4 Properly secure feed lines.
Howell Point
TOWER HEIGHT: 65'
2.2.1 Furnish and install RF radiation signage
2.2.2 Furnish and install (2) Max 12" Ground bus bar with insulators and brackets.
2.2.2 Furnish and install (2) Max 12" Ground bus bar with insulators and brackets.
2.2.3 Remove all unused hardware, antenna(s), lines, equipment from tower and
Munson Test Course
TOWER HEIGHT: 150'
2.4.1 Furnish and install RF radiation signage.
2.4.2 Furnish and install (1) Max 12” Ground bus bar with insulators and brackets.
2.4.2 Properly secure feed lines.
2.4.2 Properly secure feed lines.
Perryman
TOWER HEIGHT: 120’
2.6.6 Remove all unused hardware, antenna(s), lines, equipment from tower and provide proper disposal.
2.6.1 Furnish and install RF radiation signage.
2.6.2 Furnish and install waveguide/ ice bridge to properly support and protect coax
Entry port and waveguide ice bridge.
2.6.3 Properly secure feed lines
2.6.4 Furnish and install (1) Max 12" Ground bus bar with insulators and brackets.
2.6.5 Properly secure coaxial jumper(s).
2.6.5 Properly secure coaxial jumper(s).
2.6.3 Properly secure feed lines.
2.6.3 Properly secure feed lines.
Worton Point
TOWER HEIGHT: 65'
2.1.1 Furnish and install radio frequency (RF) radiation signage
2.1.2 Wire brush and cold galvanize the rusting safety rail. Paint the repaired rail white. Paint will be supplied by contractor.
2.1.2 Wire brush and cold galvanize the rusting safety rail. Paint the repaired rail white.
Paint will be supplied by contractor.
2.1.3 Remove all unused hardware, antenna(s), lines, equipment from tower and