SCH
SA
SAN
QTY
R12, R22
RA
RDTR
RPM
RT
PG
PH
POC
POL
PPM
PRV
QT
OA
OAIL
OD
OS&Y
Pa
NTS
BUTTERFLY
CUBIC METER PER HOUR
AIR CONDITION (-ING,-ED)
AIR CONDITION UNIT (S)
AIR COOLED CONDENSING UNIT
CHILLED/HOT WATER RETURN
CHILLED/HOT WATER SUPPLY
REFRIGERANT LIQUID
CAP CAPACITY
CUBIC METER
COMPRESSOR
CONTINUE
CONNECTION
CPRSR
CU M
CONT
CONN
COUNTER CLOCKWISE
COEFFICIENT
CIRCUIT
CAST IRON PIPE
CHILLED WATER
CKT
CMH
COEF
CHW
CCW
CIP
ALARM CHECK VALVEACV
AVG AVERAGE
BAROMETER(-TRIC)
CENTIGRADEC
BARO
AMPERE(AMP, AMPS)
ALUMINUM
APPROX
AMP
AIR COND
AHU
AL
AIR COOLED
ACU
ACLD
ACCU
CHWS
CHWR
CHR
CHS
D
RL
DRAIN
KILOCALORIE PER HOUR
KILOGRAM PER SQ. CENTIMETER
KILOGRAM
THERMAL CONDUCTIVITY
IRON PIPE SIZE
ISOMETRIC
DIAMETER, INSIDE
FACE AREA OR FRESH AIR
EXTERNAL STATIC PRESSURE
EVAPORAT (-E,-ING,-ED,-OR)
ENTERING WATER TEMP
FIRE HOSE CABINET
EXPLOSION PROOF
FHC
FA
ESP
EVAP
EWT
EFF
ENT
EQPT
EP
EFFICIENCY
ENTERING
EQUIPMENT
KG
K
IPS
ISO
ID
NIC
N.O.
NO
MPS
N.C.
N/A
MM
MPH
MIN
MAX
NOT IN CONTRACT
NORMALLY OPEN
NUMBER
NORMALLY CLOSED
METERS PER SECOND
METERS PER HOUR
MINIMUM OR MINUTE
NOT APPLICABLE
MILLIMETER
MAXIMUM
HERTZ
HOSE BIBB
HEAD
HORSEPOWER
HOUR(S)
HOT WATER
HOT WATER HEATER
HORIZONTAL
FIBERGLASS REINFORCED PLASTIC
FREQUENCY
FLUSH VALVE
FEED WATER PUMP
FIXTURE
GAGE OR GAUGE
GALVANIZED STEEL
FUEL OIL
FEMALE PIPE THREAD
CIRCULATING WATER PUMPCWP
FRP
DECIBEL OR DRY BULB
DRY BULB TEMPERATURE
ENTERING AIR TEMPERATURE
DRY PIPE VALVE
DIRECT EXPANSION
DO DIESEL OIL
EAT
DPV
DX
DIV
DIAG
DIFF
DB
DBT
DIVISION
DIAMETER
DIAGRAM
DIFFERENCE
DEGREE
HR
HZ
HW
HWH
HORIZ
HB
HD
HP
GA
GALVS
FV
FWP
FXTR
CLOCKWISE OR COLD WATERCW
PLUG VALVE
THREE WAY
FREQ
FO
FPT
GATE, GLOBE
GATE, ANGLE
GLOBE
CONTROL
GATE
M
LPS
LWT
LT
LPH
LPD
LL
LG
LBS
LAT
LAV
L
KWH
KW
LITERS PER SECOND
LITERS PER HOUR
LEAVING WATER TEMPERATURE
METERS
LAUNDRY TRAY
LITERS PER DAY
LIQUID LINE
LEAVING AIR TEMPERATURE
POUNDS
LAVATORY
LENGTH
KILOWATT HOUR
KILOWATT
LITERS
P
STRAINER, BLOW OFF
STRAINER
PUMP (INDICATE USE)
KG/ SM KILOGRAM PER SQ. METER
REFRIGERANT SUCTION
REFRIGERANT DISCHARGE
PIPE TO BE REMOVED
MEDIUM TEMPERATURE HOT WATER RETURN
MEDIUM TEMPERATURE HOT WATER SUPPLY
CONDENSER WATER RETURN
CONDENSER WATER SUPPLY
RS
RD
(NAME)
(NAME)E EXISTING PIPE
HWR
HWS
MTWR
MTWS
CR
CS
PIPING
SANITARY DRAIN
CHECK, SWING
PIPE SLEEVE WITH FIRE STOPPING
VENT THRU ROOF
BFP
PLAN
HOSE BIBB
BALL
ELEV.
PIPE SLEEVE
BACKFLOW PREVENTER
FLOOR DRAIN
FLOOR CLEANOUT
FD
FCO
FLEXIBLE CONNECTOR
ANCHOR, INTERMEDIATE
ANCHOR, MAIN
EXPANSION JOINT
EXPANSION LOOP
EJ
RELIEF
SAFETY
HOSE END DRAIN
LOCK SHIELD
NEEDLE
PRESSURE REDUCING
CONTROL, PNEUMATIC-ELECTRIC
CONTROL, ELECTRIC-PNEUMATIC
CHECK, NON-SLAM
S
R
EP
PE
COLD WATER
VENT
AD FD
QUANTITY
TEMPERATURE DIFFERENCE
TONS OF REFRIGERATION
SCHEDULE
SUPPLY AIR
SANITARY
REFRIGERANT (12, 22, ETC)
RETURN AIR
REVOLUTIONS PER MINUTE
REFRIGERATION TON
RADIATOR
TYP TYPICAL
UNIT HEATER
URINAL
UH
UR
SYMBOL
TEMPERATURE
THICKNESS
TONS
THK
TEMP
SYM
TD
OUTSIDE AIR INTAKE LOUVER
PRESSURE REDUCING VALVE
PHASE (ELECTRIC)
PETROLEUM, OIL AND LUBRICANTS
POINT OF CONNECTION
PARTS PER MILLION
PERCENT/
QUART
PRESSURE GAGE
DIAMETER, OUTSIDE
OUTSIDE SCREW & YOKE
PASCAL
POLE
SPR SPRINKLER
STAINLESS STEEL
SQUARE
STEAM
STANDARD
STEEL
ST
STD
STL
SQ
SST
SPECIFICATION
SQUARE METER
STATIC PRESSURE
SPEC
SP
SM
OUTSIDE AIR
NOT TO SCALE
SECONDSEC
VAV VARIABLE AIR VOLUME
WATER CLOSET
VENTILATION
W/
WT
WC
WD
WITH
WEIGHT
WIDTH
W
WB
VOL
VEL
VENT
VERT
WATT
WET BULB
VOLUME
VELOCITY
VERTICAL
SMOKE DAMPER (PROVIDE ACCESS DOOR)
MANUAL VOLUME DAMPER
VAC
V
VACUUM
VOLT
SPLITTER DAMPER
AD
SD
VD
TEE, SINGLE SWEEP
TEE, OUTLET DOWN
REDUCER, ECCENTRIC (STRAIGHT, DOWN)
REDUCER, ECCENTRIC (STRAIGHT, INVERT)
ELBOW, TURNED DOWN
UNION, FLANGED
UNION, SCREWED
TEE, OUTLET UP
TEE
LATERAL
ELBOW, TURNED UP
CONNECTION, TOP
CONNECTION, BOTTOM
BUSHING
CAP
FIRE DAMPER (PROVIDE ACCESS DOOR)
BDD
TURNING VANES
TRANSITION
FLEXIBLE CONNECTION
FLEXIBLE DUCT
FC
DUCT WORK
A B B R E V I A T I O N S
L E G E N D
PG
TM
AAV
FOS
3-WAY VALVE (MOTORIZED)
PRESSURE GAUGE
THERMOMETER
AUTOMATIC AIR VENT
GATE VALVE
CHECK VALVE
FUEL OIL SUPPLY
FLEXIBLE JOINTFJ
& STRAINER
M
CS
SD
SHOWER DRAIN
DEG
DIA or o
CEAT CONDENSER ENTERING AIR TEMP
LCWT LEAVING CHILLED WATER TEMP
FAIL FRESH AIR INTAKE LOUVER
EXPANSION JOINTEXPJT
EXST EXISTING
A / C AIR CONDITIONING
APPROXIMATELY
ARCH ARCHITECTURAL
BLDG BUILDING
CONC CONCRETE
DWG DRAWING
EA EACH
F.C.U. FAN COIL UNIT
MECH MECHANICAL
KCAL/ HR
KG/ SQ CM
HOT WATER SUPPLY
HOT WATER RETURN
CHILLED WATER SUPPLY
CHILLED WATER RETURN
V
DOMESTIC HOT WATER SUPPLY
DOMESTIC HOT WATER RETURN
AAV
ED EXHAUST DUCT
AUTOMATIC AIR VENT
AIR HANDLING UNIT
GROUND LEVELGL
REGISTER, SIDEWALL
SUPPLY AIR GRILLE OR
REGISTER, CEILING
SUPPLY AIR GRILLE OR
(200mm NECK DIAMETER)
CEILING DIFFUSER, ROUND TYPE
REGISTER, CEILING
EXHAUST AIR GRILLE OR
GRILLES, REGISTERS AND DIFFUSERS
SQUARE TYPE
CEILING DIFFUSER,
EG
ER
SG
SR
SG
SR
RG
RR
CD
200mm NCD
COWL, (GOOSENECK) AND FLASHING
(810mm WIDTH x 400mm DEPTH)
DUCT SIZES SHOWN810mm x 400mm
M
ELECTRIC MOTOR OPERATED DAMPER
S
MOTORIZED DAMPER
MD
SUPPLY AIR DUCT RISER
RETURN OR EXHAUST AIR DUCT RISER
SUPPLY AIR DUCT SECTION
RETURN AIR DUCT SECTION
GATE, GLOBE OR BALL VALVE
CHECK VALVE (FLOW)
ANGLE VALVE
STRAINER
DRIP CHECK VALVE
RESTRICTED ORIFICE
FILL CUP
PRESSURE GAUGE
SOLENOID VALVE
ECCENTRIC REDUCER
CONCENTRIC REDUCER
FLEXIBLE PIPE CONNECTION
RELAY
HOSE VALVE
TEST HEADER
SMOKE DAMPER
R
SD
S
: WATER MOTER ALARM GONG
SPRINKLER SYSTEM
: UP-RIGHT TYPE SPRINKLER
: PENDENT TYPE SPRINKLER
: SIDE WALL TYPE SPRINKLER
REMOVAL WORK
RELOCATED WORK
SUPPLY AIR DUCT
RETURN AIR DUCT
EXHAUST AIR DUCT
SA
RA
EA
DEMPERS
VALVES, SPECIAL DUTY
HEATING
AIR CONDITIONING & REFRIGERATION
PLUMBING
VALVES : (for selective actuators)
BACK DRAFT DAMPER
CIRCUIT SETTER
POINT OF CONNECTIONPOC
POR POINT OF REMOVAL
TcH THERMOSTAT HEATING/COOLING
THERMOSTAT OF HEATING
REGISTER, CEILING
RETURN AIR GRILLE OR
Th
REDUCER, CONCENTRIC
22 MAY 17
NAM, TAE CHIN
H
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
EDCBA
AS SHOWN
DATE:
MECHANICAL
LEGEND AND ABBREVIATIONS
M-1
YI, TONG KI
CAMP CARROLL
G
HS-00557-7J
FOR THAAD/ 2-1 ADA BATTERIES, BLDG. #998
CONVERT THE EXISTING ACS BUILDING TO COF
D - 17 - 10
20 59SHEET OF
D E S C R I P T I O N
E Q U I P M E N T S C H E D U L E
Q’ TY
NO.
ITEM
Q’ TY
NO.
ITEM
D E S C R I P T I O N Q’ TY
NO.
ITEM
D E S C R I P T I O N
1 OUTDOOR HEAT PUMP UNIT2
(CFM)
FAN CAP.
(BTUH)
HEATING CAP.
(BTUH)
COOLING CAP.
POWER SUPPLY
19,100 21,500 396
(W)
POWER INPUT
POWER SUPPLY
(W)
POWER INPUT
(CFM)
FAN CAP.
(BTUH)
HEATING CAP.
(BTUH)
COOLING CAP.
28,000 31,500
POWER SUPPLY
(W)
POWER INPUT
(CFM)
FAN CAP.
(BTUH)
HEATING CAP.
(BTUH)
COOLING CAP.
12,300 13,600 307
30 208V, 60Hz, 2Ph
ELECTRIC WALL HEATER
POWER SUPPLY: 208V, 60Hz, 2Ph
CAPACITY: 1.5 Kw
WALL EXHAUST FAN
BACK DRAFT DAMPER AND EXHAUST GRILLE.
ALUMINUM HOUSING EQUIPPED WITH DISCONNECT SWITCH, BIRD SCREEN,
WALL MOUNTED, DIRECT DRIVEN CENTRIFUGAL FAN, WEATHERPROOF,
1/ 6 115V, 60Hz, 1Ph
POWER SUPPLY19
(CFM)
CAPACITY
(HP)
FAN MOTOR
1/ 6 115V, 60Hz, 1Ph
POWER SUPPLY
(CFM)
CAPACITY
(HP)
FAN MOTOR
1/ 6 115V, 60Hz, 1Ph
POWER SUPPLY
(CFM)
CAPACITY
(HP)
FAN MOTOR
ROOF EXHAUST FAN
222 AT 1/ 8 SP (Inches wg)
279 AT 1/ 8 SP (Inches wg)
416 AT 1/ 8 SP (Inches wg)
BACK DRAFT DAMPER AND EXHAUST GRILLE.
ALUMINUM HOUSING EQUIPPED WITH DISCONNECT SWITCH, BIRD SCREEN,
ROOF MOUNTED, DIRECT OR BELT DRIVEN CENTRIFUGAL FAN, WEATHERPROOF,
116 DEHUMIDIFIER
208V, 60Hz, 2Ph
208V, 60Hz, 2Ph
DRIP OUTPUT AND DISCHARGE HOSE.
FLOOR MOUNTED, SELF-CONTAINED ELECTRIC DEHUMIDIFIER WITH CONDENSATE
POWER SUPPLY: 115V, 60Hz, 1Ph
WATTS: 420
CAPACITY: 30 PINTS / DAY
WORK CLASS: "L" (CONSTRUCTION / ALTERATION WORK)
THERMOSTAT & DISCONNECT SWITCH, RECESSED IN-WALL TYPE, UL LISTED.
HORIZONTAL DISCHARGE ELECTRIC WALL HEATER, BUILT-IN TAMPER RESISTANT
H
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
SHEET OF
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
EDCBA
AS SHOWN
DATE:
MECHANICAL
M-2
D - 17 - 10
G
WALL MOUNTED TYPE SPLIT AIR CONDITIONING UNIT (FOR COMM. ROOM)
QUALIFIED, PROVIDED ACCESS WASHABLE AIR CLEANER FILTER.
ANTI-VIBRATION DAMPER FOR MOUNTING (OUTDOOR UNIT), AHRI AND ETL
WIRED WALL MOUNTED THERMOSTAT, REMOTE ELECTRONIC CONTROLLER,
HIGH WALL DUCT FREE SPLIT COOLING SYSTEM INCLUDING AUTO OPERATION
R-410A REFRIGERANT, INDOOR/OUTDOOR AIR CONDITIONING UNIT,
CARRIER AIR CONDITIONER" MODEL NO. 40MFC012- - -3 OR APPROVED EQUAL
ELECTRICAL DATA
MOTOR RPM / CFM
COOLING CAPACITY
: 208 V, 1 PH, 60 Hz (OUTDOOR), 10 MCA
: 208 V, 1 PH, 60 Hz (INDOOR)
940 / 945 (OUTDOOR)
: 1200 / 232 (INDOOR)
: 12,000 BTUH
POWER SUPPLY: 208V, 60Hz, 3Ph
CONDENSER FAN MOTOR: 6.0A x 2EA
COMPRESSOR: 27.3A
FAN CAPACITY: 9,850 cfm
HEATING CAPACITY: 108,000 Btu/h
COOLING CAPACITY: 96,000 Btu/h
INVERTER HEAT PUMP UNIT (INDOOR UNIT)
ENERGY RECOVERY VENTILATOR
SIMILAR TO "LG ELECTRONICS." MODEL NO. ARVU063ZEA2 OR APPROVED EQUAL
208V, 60Hz, 2Ph
POWER SUPPLY
0.47
(CFM)
FAN CAPACITY
(KW)
POWER INPUT
208V, 60Hz, 2Ph
POWER SUPPLY
0.36
(CFM)
FAN CAPACITY
(KW)
POWER INPUT
5 1
6 3
7 3 ELECTRIC UNIT HEATER
BRACKET AND STANDARD ACCESSORIES.
DISCONNECT SWITCH, UNIT MOUNTED THERMOSTAT, WALL MOUNTING
MOTOR, THERMAL OVERLOAD PROTECTION, WALL MOUNTED
AND OUTLET DIFFUSER, CONSIST OF HEATING ELEMENTS, FAN AND
HORIZONTAL DISCHARGE, TOTALLY ENCLOSED, INLET LOUVER, VENTURI
POWER INPUT
FAN MOTOR
FAN CAPACITY
HEATING CAPACITY
: 3 KW
: 1/100 HP, 208V, 1 PH, 60HZ
: 350 CFM, 165.2 LPS, 1,600 RPM
: 10,000 BTU/HR
1/ 4 115V, 60Hz, 1Ph
POWER SUPPLY
(CFM)
CAPACITY
(HP)
FAN MOTOR
736 AT 3/ 8 SP (Inches wg)
12 4
111.6 1729
(W)
POWER INPUT
13 1 DOMESTIC HOT WATER HEATER
(Kcal/h)
MAX.CAPACITY
96,000
(KW)
GROSS OUTPUT
(LPH)
HEAT RECOVERY
120V, 60Hz, 1Ph
VOLT/PH/HZ
ELEC. POWER
"LG ELECTRONICS." MODEL NO. ARUN096BTE4 OR APPROVED EQUAL
"LG ELECTRONICS." MODEL NO. ARNU183TQC4 OR APPROVED EQUAL
"LG ELECTRONICS." MODEL NO. ARNU283TPC4 OR APPROVED EQUAL
"LG ELECTRONICS." MODEL NO. ARNU123TQC4 OR APPROVED EQUAL
"LG ELECTRONICS." MODEL NO. ARVU053ZEA2 OR APPROVED EQUAL
"TRANE" MODEL NO. UHAA151ATAD OR APPROVED EQUAL
"KYUNGDONG NAVIEN" MODEL NO. NPE-240S x 2 OR APPROVED EQUAL
PUMP MOTOR
PUMP CAPACITY
: 1/3 HP, 115 V, 1 PH, 60 HZ, 1,725 RPM
: 8 GPM, AT 18 FT TDH
DOMESTIC HOT WATER RE-CIRCULATION PUMP
ACROSS-THE-LINE MAGNETIC CONTROLLER IN A NEMA 250 AND NEMA MG 1.
ALL BRONZE CONSTRUCTION. MOTORS SHALL BE EQUIPPED WITH AN
IN-LINE CLOSED COUPLED CENTRIFUGAL TYPE, FLANGE CONNECTION AND
14 1
FLA 2
AHRI & CSA CERTIFY PRODUCT
SUPPLY TEMP: 60 C, TEMP RISE: 16.7 C, EFFICIENCY 90%,
MODULE TYPE, SCALE REDUCER, CONDENSING TYPE,
CONFORM TO PL 93-523 AND NSF/ANSI 61
STEEL COVER BOLTS, AIR GAP, ASSE APPROVED, AWWA STANDARD
SILICONE RUBBER DISK, REPLACEABLE POLYMER CHECK SEATS, STAINLESS
REDUCE PRESSURE ZONE BACKFLOW ASSEMBLY, LEAD FREE BRONZE BODY,
SIZE
MAX. WORKING PRESSURE
TEMP. RANGE
: 2" (50 mm)
: 175 psi (12.1 bar)
: 33 F ~ 180 F (0.5 C ~ 82 C)
WATER METER & BACKFLOW PREVENTER AND PRESSURE REDUCING STATION17 1
FUSING POINT OF 135 F, K-FACTOR OF 5.7, AND APPROVED U.L. LISTED
CONCEALED PENDENT TYPE, 1/ 2" NPT WITH 1/ 2" STANDARD ORIFICE,
QUICK RESPONSE FUSIBLE LINK SPRINKLER HEAD WITH DEFLECTOR,
SPRINKLER HEAD (RESIDENTIAL)
FUSING POINT OF 155 F, K-FACTOR OF 5.7, AND APPROVED U.L. LISTED
CONCEALED PENDENT TYPE, 1/ 2" NPT WITH 1/ 2" STANDARD ORIFICE,
STANDARD RESPONSE FUSIBLE LINK SPRINKLER HEAD WITH DEFLECTOR,
FUSING POINT OF 175 F, K-FACTOR OF 5.7, AND APPROVED U.L. LISTED
UPRIGHT TYPE, 1/ 2" NPT WITH 1/ 2" STANDARD ORIFICE,
STANDARD RESPONSE FUSIBLE LINK SPRINKLER HEAD WITH DEFLECTOR,
SPRINKLER HEAD (MECHANICAL ROOM)
SPRINKLER HEAD (LAUNDRY, STORAGE ROOM)
YI, TONG KI
NAM, TAE CHIN
22 MAY 17
CAMP CARROLL
HS-00557-7J
AND ALL ACCESSORIES & PARTS.
1. REMOVE ALL HVAC SYSTEM, PLUMBING SYSTEM, SEWER SYSTEM, SPRINKLER PIPING
4. INSTALL NEW ELECTRIC UNIT HEATER AS INDICATED IN PLANS.
ALL NECESSARY ACCESSORIES & PARTS. ,
DUCTWORK, TRANSFER DUCTS, DAMPERS, SECURITY BARS, INSULATION, DEHUMIDIFIER AND
3. INSTALL NEW ROOF EXHAUST FANS, WALL MOUNTED EXHAUST FANS WITH ASSOCIATED
& PARTS.
CONCRETE PAD, INSULATION, DRAIN PIPING AND ALL NECESSARY ACCESSORIES
5. INSTALL NEW WALL MOUNTED TYPE SPLIT A/C UNIT (FOR COMM. RM) INCLUDING
DISTRIBUTING OPERATION SYSTEM.
REFRIGERANT LIQUID, FOUR SEASONAL HERMETIC SAFETY COVER, MULTI
PROPELLER TYPE BLOW-THRU OUTDOOR FAN, ACCUMULATOR, R410A
BRIDGE CIRCUIT AIR-COOLED COIL WITH CORROSION RESISTANT COATING,
TYPE COMPRESSOR WITH MULTI POWER SYSTEM, SUB COOL INTERCHANGER
DIGITAL CONTROLLED INVERTER COMPRESSOR AND CONSTANT VELOCITY
CONDENSING UNIT SYSTEM FOR ABOVE-GROUND INSTALLATION. BUILT IN
OUTDOOR MOUNTED SEASONAL HEATING AND COOLING MULTI OUTDOOR
AIR CLEANER FILTER, HIGH EFFICIENCY INVERTER MOTOR.
WASHABLE
MOTORIZED DISCHARGE VANES, CONDENSATE WATER LIFT PUMP, EASY ACCESS
CONTROLLER AND COOLING INVERTER SYSTEM EQUIPPED WITH INDEPENDENT
INDOOR CEILING MOUNTED CASSETTE TYPE UNIT FOR HEATING,TEMPERATURE
AND CONTROLLER.
TEMPERATURE CONTROLLER AND MOTOR INTEGRATION SYSTEM,
MODE FOR MALFUNCTION AND ERROR, WASHABLE AIR FILTER, TIMER, FAN
FUNCTION, SUPPLY AIR AND RETURN AIR VOLUME CONTROL, SELF ALARM
TRANSFER HEAT AIR AND NORMAL AIR CHANGE, THREE SPEED AIR CONTROL
AIR UNIT, RUST PROOF CASING, AUTOMATIC MODE CHANGER BETWEEN
INDOOR ABOVE CEILING MOUNTED TYPE HEAT RECOVERY MAKE-UP FRESH
FOR THAAD/ 2-1 ADA BATTERIES, BLDG. #998
CONVERT THE EXISTING ACS BUILDING TO COF
SCOPE OF WORK
SCOPE OF WORK
EQUIPMENT SCHEDULE,
PERFORM THE WORK AS GAS DISTRIBUTION GENERAL NOTES.
VALVES AND ALL NECESSARY ACCESSORIES & PARTS ALSO CONTRACTOR SHALL
VALVE TO WATER HEATER INCLUDING GAS TRAIN ASSEMBLY, GAS PIPES, FITTINGS,
9. CONNECT EXISTING GAS DISTRIBUTION SYSTEM FROM EMERGENCY AUTO SHUT-OFF
VALVES, WIND GUIDE, ACCESS DOORS AND ALL NECESSARY ACCESSORIES & PARTS.
ROOM CONTROLS AND CONCRETE PAD WITH ASSOCIATED DUCTWORK, PIPING, FITTINGS, INSULATION,
2. INSTALL NEW HEAT PUMP UNITS, ENERGY RECOVERY MAKE UP AIR UNITS, CENTRAL CONTROL, ACCESSORIES & PARTS.
PIPING, INSULATION, VALVES, ELECTRIC WALL HEATERS(BATHROOM) AND ALL NECESSARY
6. INSTALL NEW PLUMBING SYSTEM, SEWER & VENT SYSTEM, DOMESTIC WATER
PERFORM THE WORK AS NOTES FOR FIRE SPRINKLER SYSTEM AT THE DWG NO. M-3.
AND ALL NECESSARY ACCESSORIES AND PARTS ALSO CONTRACTOR SHALL
8. INSTALL NEW WET TYPE FIRE SPRINKLER PIPING INCLUDING SPRINKLER HEAD, ALL TEST
HOSE BIBB, VALVES, GAUGES AND ALL NECESSARY ACCESSORIES & PARTS WITH NEW ONES.
PREVENTER & PRESSURE REDUCING STATION, WATER PIPING, ALL GAS PIPING & EQUIPMENTS,
7. INSTALL NEW DOMESTIC HOT WATER HEATER, RE-CIRCULATION PUMP, WATER METER, BACKFLOW
10. CONTRACTOR SHALL REMOVE ALL DDC SYSTEM OF JOHNSON CONTROL.
COSTS WITH EXISTING (OR NEW) DDC SYSTEM INSTALLED BY JOHNSON CONTROL.
11. CONTRACTOR SHALL BE RESPONSIBLE FOR REMOVAL & REINSTALLATION AND ALL ASSOCIATED
21 59
7. THE CONTRACTOR SHALL PERFORM THE TRAINING ABOUT GAS SUPPLY SYSTEM TO O&M DIVISION.
AND GAS PIPING LINES TO DESIGN & TECHNICAL REVIEW BRANCH FOR APPROVAL PRIOR TO CONSTRUCTION.
5. THE CONTRACTOR SHALL SUBMIT THE DETAILED SHOP DRAWING OF GAS DISTRIBUTION SYSTEM
GENERAL NOTES
DUCTWORK SHALL BE PATCHED OR RESTORED TO MATCH THE ADJACENT SURFACE OR AREA.
4. ALL WALL / FLOOR / ROOF OPENINGS RESULTING FROM THE REMOVAL OF PIPING AND
AS DIRECTED BY THE CONTRACTING OFFICER.
EXISTING AREAS CAUSED BY THIS PROJECT AND TO MATCH CONDITION TO ADJACENT AREAS
5. THE CONTRACTOR SHALL BE RESPONSIBLE TO CONSTRUCT OR REPAIR ALL DAMAGES TO
CEILING, ROOF, EQUIPMENT, PIPE, DUCT AND ELECTRICAL ITEMS.
PREVENTION SYSTEM WITH NO ADDITIONAL COST TO THE GOVERNMENT SUCH AS WALLS,
ITEMS TO MAKE WAY FOR THE INSTALLATION AND REPLACEMENT OF MECHANICAL AND FIRE
18. THE CONTRACTOR SHALL BE RESPONSIBLE TO REMOVE AND REINSTALL THE OBSTRUCTED
SPECIFICATIONS.
CONTRACT DRAWINGS SHALL BE SUBMITTED FOR APPROVAL AS REQUIRED BY THE CONTRACT
OF THE ACTUAL PROPOSED CONTROL SYSTEM WHICH MAY DEVIATE FROM THAT SHOWN ON
SYSTEM TO SATISFY ALL FUNCTIONAL REQUIREMENTS SHOWN ON DRAWING. SHOP DRAWINGS
17. THE CONTRACTOR IS RESPONSIBLE FOR PROVIDING A COMPLETE AND WORKABLE CONTROL
9. ANY PIPES THAT PENETRATE FIRE RATED WALLS (EXISTING/ NEW) SHALL BE SEALED PER SPEC.
TO ENSURE PROPER OPERATION, AS ORIGINALLY INTENDED.
EQUIPMENT. THE CONTRACTOR SHALL TEST, ADJUST AND BALANCE EQUIPMENT AS REQUIRED
14. THE CONTRACTOR SHALL PROVIDE ALL NECESSARY START-UP AND TESTING OF THE NEW
AND SHALL BE VERIFIED AT THE JOB SITE.
2. LOCATION AND SIZES OF EXISTING EQUIPMENT, DUCTWORK, PIPING, ETC, ARE APPROXIMATE
PRIOR TO COMMENCING CONSTRUCTION FOR APPROVAL.
ACCORDING TO ACTUAL FIELD CONDITIONS AND SUBMITTED TO THE CONTRACTING OFFICER
FIELD CONDITIONS. SUCH DETAILS SHALL BE PREPARED IN THE FIELD BY THE CONTRACTOR
3. SOME DETAILS SHOWN ON THIS CONTRACT DRAWINGS MAY NOT MATCH EXACTLY TO THE
CONTRACTING OFFICER’S APPROVAL.
REPRESENTATIVE ATTENTION WITH RECOMMENDATIONS FOR PROPER CORRECTIONS FOR
IF ANY DISCREPANCY IS DETECTED, IT SHOULD BE BROUGHT TO THE CONTRACTING OFFICER’S
PRIOR TO COMMENCING ANY CONSTRUCTION OR REPAIR.
EQUIPMENT, DUCTWORK, PIPING, DIMENSIONS AND ETC. UNDER THE SUPERVISION OF C.O.R
1. THE CONTRACTOR SHALL BE RESPONSIBLE IN VERIFYING ALL EXISTING CONDITION,
A SHOP DRAWING SHALL NOT BE THE EXACT DUPLICATION OF THE CONTRACT DRAWING.
10. NO MECHANICAL WORK CAN BE STARTED WITHOUT AN APPROVED SHOP DRAWING.
THE REQUIREMENTS OF SEAL CLASS C.
TO SMACNA STATIC PRESSURE CONSTRUCTION CLASS 500PA AND DUCTWORK SHALL MEET
7. THE SUPPLY, RETURN AND EXHAUST AIR DUCTWORK SHALL BE CONSTRUCTED ACCORDING
START OF CONSTRUCTION.
PLAN SHALL BE SUBMITTED TO AND APPROVED BY DPW AND THE USER, PRIOR TO THE
USER TO FULLY UTILIZE THE FACILITY DURING THE CONSTRUCTION PERIOD. THIS PHASING
SHALL PROVIDE A PHASING PLAN FOR CONSTRUCTION COMPLETION ALLOWING FOR THE
FACILITY BE FULLY OPERATIONAL DURING THE CONSTRUCTION PERIOD, THE CONTRACTOR
19. DUE TO THE CRITICAL NATURE OF THE FACILITY FUNCTION, IF IT IS REQUIRED THAT THE
CONTRACTOR.
THE WORK PERFORMED UNDER THIS CONTRACT SHALL BE REPAIRED OR REPLACED BY THIS
THE EXISTING EQUIPMENT, NEW EQUIPMENT, DUCT WORK, PIPING AND ETC. DAMAGES DUE TO
11. CONNECTIONS TO EXISTING SYSTEM SHALL BE DONE IN SUCH A MANNER AS NOT DAMAGE
FOR APPROVAL.
DESIGN & TECHNICAL REVIEW BRANCH VIA C.O.R. PRIOR TO COMMENCING CONSTRUCTION
12. THE CONTRACTOR SHALL SUBMIT MANUFACTURER’S INSTALLATION SHOP DRAWINGS TO THE
US ORIGIN MATERIALS:
AS INDICATED ON THE DRAWINGS.
INTERNET SITE HTTP:// WWW.CCKBID.COM). ALL NON-GENERIC US ORIGIN MATERIALS SHALL BE
DATED FEBRUARY 2, 2004 (ELECTRONIC VERSION OF THIS DOCUMENT CAN BE FOUND AT
REGISTER OF IMA-KORO PAMPHLET 420-1 "INSPECTION OF CONSTRUCTION CONTRACTS",
ALL GENERIC US ORIGIN MATERIALS SHALL BE AS OFF-SHORE IN THE GENERIC SUBMITTAL
SPECIFICATIONS FOR O & MA PROJECTS, KOREA (REVISION 1 - 20151030)".
15. ALL EQUIPMENT AND MATERIALS SHALL MEET THE REQUIREMENTS OF "STANDARD TECHNICAL
ADDITIONAL COST TO THE PROJECT CONTRACT.
THE DETAILS WILL BE UTILIZED TO ACCOMPLISH THE MECHANICAL SCOPE OF WORK AT NO
O & MA PROJECTS, KOREA (NOVEMBER 30, 2015)" FORM AS A PART OF THIS PROJECT.
16. THE MECHANICAL STANDARD DRAWINGS SHOWN IN THE "STANDARD DETAIL DRAWINGS FOR
NATURAL-GAS / LIQUID PETROLEUM GAS DISTRIBUTION.
TECHNICAL SPECIFICATIONS FOR O & MA PROJECTS, KOREA (REVISION 1 - 20151030)" SECTION 33 51 15,
1. GAS DISTRIBUTION SYSTEM SHALL CONFORM TO KOREA GAS SAFETY CODE AS WELL AS "STANDARD
20151030)" SECTION 33 51 15, PART 2 PRODUCTS.
AS WELL AS "STANDARD TECHNICAL SPECIFICATIONS FOR O & MA PROJECTS, KOREA (REVISION 1 -
2. ALL MATERIALS OF GAS DISTRIBUTION SYSTEM SHALL CONFORM TO KOREA GAS SAFETY CODE
THE DESIGN & TECHNICAL REVIEW BRANCH FOR APPROVAL PRIOR TO CONSTRUCTION.
6. THE CONTRACTOR SHALL SUBMIT ALL MATERIAL INFORMATION OF GAS DISTRIBUTION SYSTEM TO
REVIEW BRANCH FOR APPROVAL BEFORE COMMENCING THE WORK.
13. THE CONTRACTOR SHALL SUBMIT ALL MATERIAL INFORMATION TO THE DESIGN & TECHNICAL
GAS DISTRIBUTION GENERAL NOTES
4. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE CONTRIBUTION OF GAS INFRASTRUCTURE.
ADJUSTMENTS, RELOCATIONS AND/ OR REPAIRS WILL BE MADE AT THE CONTRACTOR’S COST.
AS A RESULT OF THE CONTRACTOR’S CONSTRUCTION. ALL DAMAGE TO GAS FACILITIES REQUIRING
3. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL DAMAGES TO GAS FACILITIES DURING OR
SUCH AS ANCHORS, HANGERS, SUPPORTS, ETC.
8. ALL PIPES, DRAINS AND DUCTWORK TO BE REMOVED SHALL INCLUDE ALL ITS ACCESSORIES
ACCESSORIES.
8. THE CONTRACTOR SHALL CONSULT GAS SUPPLIER FOR THE INSTALLATIONS OF GAS PIPING AND
9. THE CONTRACTOR SHALL CONSULT GAS SUPPLIER FOR GAS PIPING SIZE.
TO D&TR BRANCH THROUGH THE COR.
10. THE CONTRACTOR SHALL PERFORM A GAS LEAKING TEST AND SUBMIT THE GAS LEAKING TEST REPORT
22 59
AS ORIGINALLY INTENDED.
AND INSTALL NEW DUCTWORK AND MAKE ALL NECESSARY DUCT CONNECTION TO FUNCTION
ELEVATION IS CONFLICTED WITH NEW PIPING INSTALLATION, REMOVE THE EXISTING DUCTWORK
& LOCATION PRIOR TO INSTALL NEW HVAC AND PLUMBING PIPING. IF THE EXISTING DUCT
6. THE CONTRACTOR SHALL COORDINATE WITH THE EXISTING DUCTWORK AND PIPING ELEVATION
GENERAL NOTES AND SCOPE OF WORK
H
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
SHEET OF
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
EDCBA
AS SHOWN
DATE:
MECHANICAL
M-3
D - 17 - 10
G
CAMP CARROLL
YI, TONG KI
NAM, TAE CHIN
22 MAY 17
HS-00557-7J
5. FIRE PROTECTION SYSTEM SHALL COMPLY WITH UFC 3-600-1.
NFPA 13 AND 13R.
6. AUTO SPRINKLER SYSTEM SHALL BE DESIGNED AND INSTALLED IN ACCORDANCE WITH
PREVENTION OFFICE TO COORDINATE INSPECTION OF MATERIAL.
PRIOR TO INSTALLATION TO VERIFY COMPLIANCE WITH STANDARDS. CONTACT FIRE
12. ALL EQUIPMENT AND PIPING MUST BE INSPECTED BY THE FIRE PREVENTION OFFICE
NEEDED LOCATIONS.
14. ENSURE TO INSTALL LABELED ACCESS DOORS FOR ALL THE TEST AND MAINTENANCE
NFPA 13 AND 13R.
11. SWAY BRACING FOR SPRINKLER PIPING SHALL BE PROVIDED IN ACCORDANCE WITH
NOTES FOR FIRE SPRINKLER SYSTEM:
OFFICE FOR APPROVAL PRIOR TO CONSTRUCTION.
DESIGN ANALYSIS TO DESIGN & TECHNICAL REVIEW BRANCH AND FIRE PREVENTION
CONSTRUCTION. THE CONTRACTOR SHALL SUBMIT DETAILED SHOP DRAWINGS AND
MEET WITH APPLICABLE CODES AND REGULATIONS TO COMPLETE SUBJECT PROJECT
COST CAUSED FROM NOT SHOWN OR/AND INDICATED IN THE CONCEPTUAL DRAWINGS TO
IGCE PURPOSE ONLY. THE CONTRACTOR IS RESPONSIBLE FOR ALL OTHER ADDITIONAL
1. THE FIRE SPRINKLER SYSTEM ROUTING AND PIPE SIZES SHOWN ARE CONCEPTUAL FOR
AND EQUIPMENT LISTS.
SHALL BE IN ACCORDANCE WITH APPLICABLE CODES, MANUFACTURER’S RECOMMENDATIONS
2. ALL EQUIPMENT SHOWN IN SUGGESTED LOCATIONS, FINAL QUANTITY AND LAYOUT
3. COORDINATE EQUIPMENT LOCATIONS WITH LIGHTING AND HVAC SYSTEMS.
USED PROVIDED IT MEETS UL OR/AND FM REQUIREMENTS).
4. ALL EQUIPMENT TO BE UL LISTED OR FM APPROVED (LOCAL EQUIPMENT MAYBE
FIRE PREVENTION OFFICE PRIOR TO IMPLEMENTATION.
PLAN, THE CHANGE SHALL BE APPROVED TO DESIGN & TECHNICAL REVIEW BRANCH AND
7. IF FIELD CONDITIONS NECESSITATE SIGNIFICANT CHANGE FROM APPROVED
VERIFICATION.
FAILURE TO DO THIS WILL REQUIRE THE CONTRACTOR TO RE-EXPOSE THE PIPING FOR
PIPE THAT SUPPLIES THE AUTOMATIC FIRE EXTINGUISHING SYSTEM / STANDPIPE SYSTEM.
8. THE FIRE INSPECTOR SHALL PERFORM A VISUAL INSPECTION OF ALL UNDERGROUND
SPRINKLER HEAD IN THE SYSTEM.
RISER WILL RESULT IN FLUSHING THE ABOVEGROUND SPRINKLER SYSTEM THROUGH EVERY
SYSTEM. FAILURE TO FLUSH UNDERGROUND FIRE LINE PRIOR TO "STACKING" THE SPRINKLER
GROUND PIPES WHICH SUPPLY THE AUTOMATIC FIRE-EXTINGUISHING SYSTEM/ STANDPIPE
9. THE FIRE INSPECTOR MUST WITNESS A HYDROSTATIC TEST AND FLUSH OF ALL UNDER-
POSITION.
INSPECTOR TEST VALVES AND/OR MAIN DRAIN. FULLY LABEL ALL VALVES AND NORMAL
13. ENSURE ALL PIPING IS SLOPED TO ALLOW 100 PERCENT DRAINING OF SYSTEM FROM
FOR THAAD/ 2-1 ADA BATTERIES, BLDG. #998
CONVERT THE EXISTING ACS BUILDING TO COF
ETC. FAILURE TO INSPECTION WILL RESULT IN RESCHEDULING INSPECTION.
SPRINKLER PIPE, NAIL PLATES IF REQUIRED, LOCATION OF FIRE DEPARTMENT CONNECTIONS, CLIPS IF REQUIRED, PLACEMENT & TYPE OF SPRINKLER HEADS, FIRE CAULKING AROUND
10. AT THE TIME OF THE TEST, THE INSPECTOR SHALL CHECK PIPE SIZE, PIPE HANGERS, SURGE
- M-4
P-1
SCALE : 1 / 100
HGF
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
EDCBA
AS SHOWN
DATE:
MECHANICAL
M-4
D - 17 - 10
SHEET OF
N
CAMP CARROLL
YI, TONG KI
NAM, TAE CHIN
22 MAY 17
HS-00557-7J
REMOVAL HVAC DUCT PLAN
REMOVAL HVAC DUCT PLAN
FOR THAAD/ 2-1 ADA BATTERIES, BLDG. #998
CONVERT THE EXISTING ACS BUILDING TO COF
23 59
C/HWR
C/HWS
T T SW T SW SWT
H
S W
T
C/HWS
C/HWR
D
SWTT SW
SW
C/HWR
C
H W
R C
H W
S
DC
H W
S C
H W
R
D
S W
T
C
H W
R C
H W
S D
D
D
HGF
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
EDCBA
AS SHOWN
DATE:
MECHANICAL
M-5
D - 17 - 10
SHEET OF
N
CAMP CARROLL
YI, TONG KI
NAM, TAE CHIN
22 MAY 17
HS-00557-7J
- M-5
P-1
SCALE : 1 / 100
REMOVAL HVAC PIPING PLAN
REMOVAL HVAC PIPING PLAN
FOR THAAD/ 2-1 ADA BATTERIES, BLDG. #998
24 59
25 59
HGF
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
EDCBA
AS SHOWN
DATE:
MECHANICAL
REMOVAL PLUMBING & SEWER PLAN
M-6
D - 17 - 10
SHEET OF
N
S
S
S
S
S
S
S
V
S
CANOPY
MECH
150 FCO
,5
DF
40 150
40 32
40 25
100 FCO
S
V
S
S
V
S
V
V
S
S
S
V
V
V
V S
V
S
SV
GS
S
CAMP CARROLL
YI, TONG KI
NAM, TAE CHIN
22 MAY 17
HS-00557-7J
- M-6
P-1
SCALE : 1 / 100
REMOVAL PLUMBING & SEWER PLAN
FOR THAAD/ 2-1 ADA BATTERIES, BLDG. #998
26 59
HGF
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
EDCBA
AS SHOWN
DATE:
MECHANICAL
M-7
D - 17 - 10
SHEET OF
N
CAMP CARROLL
YI, TONG KI
NAM, TAE CHIN
22 MAY 17
HS-00557-7J
- M-7
P-1
SCALE : 1 / 100
WET TYPE FIRE SPRINKLER PIPING PLAN
WET TYPE FIRE SPRINKLER PIPING PLAN
N
- M-8
P-2
SCALE : 1 / 50
27 59
HGF
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
EDCBA
AS SHOWN
DATE:
MECHANICAL
M-8
D - 17 - 10
SHEET OF
C/HWR
C/HWS
CHR
CHS
C/HWR
C/HWS
E
HWS
HWR
H
E
80 80
MECH
20 20
SP
1,500
CAMP CARROLL
YI, TONG KI
NAM, TAE CHIN
22 MAY 17
HS-00557-7J
REMAIN 150 ALARM CHECK VALVE
REMAIN OS & Y GATE VALVE W/TAMPER SWITCH(TYP)
REMAIN BACKFLOW PREVENTER W/ASSEMBLY
REMAIN TEST VALVE W/OS & Y GATE VALVE AND TAMPER SWITCH
REMAIN ALARM GONG
(SIZE=100x65x65)
REMAIN FIRE SIAMESE CONN
REMAIN & REMOVAL MECH. RM. PLAN
REMAIN WET TYPE FIRE SPRINKLER SYSTEM
REMAIN EXISTING UNDERGROUND CHILLED WATER PIPING
REMOVE EXISTING CHILLER WITH ABOVEGROUND PIPING
CUT & CAP EXISTING UNDERGROUND CHILLED WATER PIPING
REMAIN & REMOVAL MECH. RM. PLAN
N
- M-9
P-1
SCALE : 1 / 100
28 59
HGF
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
EDCBA
AS SHOWN
DATE:
MECHANICAL
M-9
D - 17 - 10
SHEET OF
QTY REMARKS
12-32
P.D.I
SYMBOL
FU
RATING
WATER HAMMER ARRESTER SCHEDULE
2P-11
SYMBOL DESCRIPTION QTY. REMARKS
P-1
P-5
C.W.
LAVATORY
H.W. WASTE
VENT
WATER CLOSET
15 15 50 40
PLUMBING FIXTURE SCHEDULE
15 15 40
P-4 3505020
SHOWER 100
6 (NOT EXCEED 3.5 LITERS PER FLUSH /
FLUSH TANK TYPE
WATER EFFICIENT TOILET)
PDI-WH 201 AND MANUFACTURER’S INSTRUCTIONS.
SIZE AND LOCATE WATER HAMMER ARRESTORS PER
1. PROVIDE 300 x 300 ACCESS DOOR TO ALL WATER HAMMER ARRESTER.
2. ALL DOMESTIC PIPING SHALL BE INSULATED.
EXPOSED TYPE
COUNTER TOP TYPE
FLOOR MOUNTED TYPEURINAL
Male
Female
JAN
Corridor
SS
- M-9
P-1
SCALE : 1 / 50
JAN
SS
20, 20
MECH RM
TO / FROM MECH. ROOM
DOMESTIC WATER PIPES
Male
Female
- M-9
I-1
B , 20, 25, 20
NEW DOMESTIC WATER PIPING PARTIAL PLAN
20, 25, 25
20, 25, 32
20, 25, 25
20, 25, 25
20, 25, 32
20, 25, 32
20, 25, 32
20, 25, 32
20, 25, 32
20, 25, 32
20, 25, 32
, 2 5, , 2 5, , 2 5, , 2 5, 25, 20
20, 20
20, 25, 32
15 20 , 2 5, , 2 5, 20, 20
A X 2
B X
P-1
P-1
P-1
P-1
P-1
P-1
P-4
P-4
P-4
P-11P-11
P-5 P-5
P-5 P-5
P-
P-
P-
P-
P-
P-
P-
P-
P-
P-
P-
P-
P-
P-
P-
NOT TO SCALE
P-10 15 15 50 40 1SERVICE SINK
P-10
CAMP CARROLL
YI, TONG KI
NAM, TAE CHIN
22 MAY 17
HS-00557-7J
NEW DOMESTIC WATER PIPING PLAN
NEW DOMESTIC WATER PIPING ISOMETRIC DIAGRAM
SPECIFIC NOTES
SPECIFIC NOTES
NEW DOMESTIC WATER PIPING PLAN,
(SIZE : 600 X 600)
CEILING ACCESS DOOR
29 59
HGF
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
EDCBA
AS SHOWN
DATE:
MECHANICAL
M-10
D - 17 - 10
SHEET OF
N
Male
Female
JAN
Corridor
SS
MECH RM
- M-10
P-1
SCALE : 1 / 50
- M-10
P-1
SCALE : 1 / 100
100 VTR
Male
Female
JAN
SS
5050 FD
50 FD
50 FD50 FD
100 FCO
100 FCO
100 FCO
100 FCO
100 FCO
100 FCO
100 VTR
NEW SEWER & VENT PIPING PLAN
NEW SEWER & VENT PIPING PARTIAL PLAN
1,500
50 FD50 FD
50 FD
50 FD
100 (TYP.)
50 (TYP.)
75 FD75 FD
50 50 FD
100 FCO
CONNENT TO EXISTING SEWER LINE
CAMP CARROLL
YI, TONG KI
NAM, TAE CHIN
22 MAY 17
HS-00557-7J
NEW SEWER & VENT PIPING PLAN
50 FD
DRAIN LINE
CONNECT TO EXISTING
- M-11
SCALE : 1 / 100
30 59
HGF
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
EDCBA
AS SHOWN
DATE:
MECHANICAL
M-11
D - 17 - 10
SHEET OF
Y1
Y2
Y1
Y2Y1Y1Y1
2 4
2 4
2 4
1 3
1 3
Ø150
1 3
1 3
2 4 2 4 2 5
2 4
1 3
2 6
25A
25A
25A
25A32A
25A
32A
25A
32A
25A
32A
25A
32A
25A
32A
25A
Tch
Tch
Tch Tch
Tch
Tch
Tch
Tch
SS
1 3
D
D
D
D
REFRIGERANT PIPE DIAMETER FROM BRANCH TO BRANCH
CONNECTING PIPES [mm(INCH)]INDEX
6.35 (1/4)
9.52 (3/8)
12.7 (1/2)
15.88 (5/8)
19.05 (3/4)
22.2 (7/8)
25.4 (1)
28.58 (1 1/8)
31.8 (1 1/4)
34.9 (1 3/8)
38.1 (1 1/2)
41.3 (1 5/8)
44.5 (1 3/4)
50.8 (2)
53.98 (2 1/8)15
RL
RS
D
D cT
FOR A/C UNIT DRAIN
40 mm PVC PIPE IN THE WALL
32A
2 4
Tch
2 2
OUTDOOR HPU (TYP. OF 2EA)1
2 3 4
M-15 M-15
SEE DETAIL DWG
WITH CONC. PAD
FOR HEAT PUMP UNIT (TYP. OF 10EA)
TEMPERATURE CONTROLLER W/ SHUT OFF SW
INDOOR HPU (TYP. OF 10EA)
M-17 M-17
WITH CONC. PAD SEE DETAIL DWG
AIR CONDITIONING UNIT
WALL MOUNTED TYPE
Tch
CAMP CARROLL
YI, TONG KI
NAM, TAE CHIN
22 MAY 17
HS-00557-7J
NEW HAVC & PIPING PLAN
NEW HAVC & PIPING PLAN
L E G E N D
(SIZE : MANUFACTURER’S RECOMMENDATION)
CEILING ACCESS DOOR X 2EATEMPERATURE CONTROLLER
FOR THAAD/ 2-1 ADA BATTERIES, BLDG. #998
CONVERT THE EXISTING ACS BUILDING TO COF
Cc
FOR ALL HEAT PUMP SYSTEM
CENTRAL CONTROLLER
Ø150
Ø150
Ø250
Ø250
Ø250
Ø250
Ø150
Ø250
Ø150 Ø150
Ø200Ø200
Ø150
Ø250
Ø250
Ø250
Ø250
Ø200
Ø250
Ø250
Ø150
Ø150
Ø250
Ø250
- M-12
P-1
SCALE : 1 / 100
31 59
HGF
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
EDCBA
AS SHOWN
DATE:
MECHANICAL
M-12
D - 17 - 10
SHEET OF
RA
SA
OA
EA
SA
RA
EA
OA
R A
S A
E A
O A
R A
S A
E A
O A
Ø150
Ø150
Ø150
Ø150
Ø250 Ø150
Ø250
Ø150
Ø150
SS
5 ENERGY RECOVERY VENTILATOR
(TYP. OF 3EA)
ENERGY RECOVERY VENTILATOR
ACCESS DOOR (TYP. OF 4EA)
INDICATE THE ROOM NO. FOR EACH CONTROLLER
FOR ENERGY RECOVERY VENTILATOR (TYP. OF 4EA)
VENTILATION CONTROLLER W/ SHUT-OFF SW
MANUFACTURER’S RECOMMENDATION AND SITE CONDITIONS.
1. SIZES AND LAYOUTS OF DUCTWORK MAY CHANGE DEPENDING ON
SPECIFIC NOTES
CAMP CARROLL
YI, TONG KI
NAM, TAE CHIN
22 MAY 17
HS-00557-7J
NEW ERV & DUCT PLAN
NEW ERV & DUCT PLAN
L E G E N D
(SIZE : MANUFACTURER’S RECOMMENDATION)
CEILING ACCESS DOOR X 4EA
VCVC VC VC
- M-13
SCALE : 1 / 100
32 59
HGF
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
EDCBA
AS SHOWN
DATE:
MECHANICAL
EXISTING / REMOVAL HVAC PLAN
M-13
D - 17 - 10
SHEET OF
SS
V .D
V.D
250 x 200
R-1
200 x 100
R-4
300 x 250
R-4 SECURITY BAR
V.D
M-19G-3
SECURITY BAR
300 x 300 V.D
V.D V.D
200 x 100
R-1
300 x 300
V.D
250 x 150
300 x 250
R-3
300 x 300
R-3
R-3 R-1
AIR DEVICE SCHEDULE
UNIT NO.
R-3
R-4
G-1
TYPE
EXHAUST
FUNCTION
EXHAUST
EXHAUST
REGISTER
REGISTER
REGISTER
SIZE
150 x 150
300 x 300
250 x 250
SUPPLY T. GRILLE 350 x 350
R-1
T. GRILLESUPPLYG-3 450 x 450
250 x 200
300 x 250
R-4
R-1
8 ELECTRIC WALL HEATER(TYP. OF 2EA) 8
300 x 300
R-3 R-3
300 x 250
300 x 300
300 x 250
350 x 250
300 x 200
300 x 200
G-1
G-1 G-1
G-1
G-3
G-3
G-3G-3
G-1
G-1
300 x 200
G-3
G-3350 x 250
SPECIFIC NOTES
2. INSTALL VOLUME DAMPER AT EACH BRANCH DUCT CONNECTION.
3. FIRE DAMPER SHALL BE PROVIDED IN ACCORDANCE WITH NFPA 90A.
SITE CONDITIONS.
1. SIZES AND LAYOUTS OF DUCTWORK MAY CHANGE DEPENDING ON
DRAINAGE.
THE FLOOR DRAIN IN THE ARMS ROOM FOR THE CONTINUOUS GRAVITY
4. THE DRAIN PIPE FOR THE DEHUMIDIFIER SHALL BE CONNECTED TO
BE PROVIDED IN CEILING FOR DUCT ACCESS DOORS, DAMPERS, ETC.
5. WHERE DUCTS ARE INSTALLED ABOVE CEILING, ACCESS PANELS SHALL
DIMENSION AT THE ELBOW EQUALS OR EXCEEDS 300MM.
VANES SHALL ALSO BE INSTALLED AT ROUND ELBOWS WHEN A DUCT
6. TURNING VANES SHALL BE INSTALLED IN ALL SQUARE ELBOWS. TURNING
BY ASHRAE HANDBOOKS, AND NFPA 90-A.
DUCT CONSTRUCTION STANDARDS BY SMACNA, INDUSTRIAL VENTILATION
7. OTHER DUCT WORK DETAILS NOT SHOWN SHALL CONFORM TO HVAC
7 ELECTRIC UNIT HEATER (TYP. OF 3EA)
WALL EXHAUST FAN
WALL EXHAUST FAN
WALL EXHAUST FAN
DEHUMIDIFIER
CAMP CARROLL
YI, TONG KI
NAM, TAE CHIN
22 MAY 17
HS-00557-7J
NEW HVAC DUCT PLAN
SEE DETAIL DWG.
SECURITY BAR
cT cT cT cT cT cT
FOR THAAD/ 2-1 ADA BATTERIES, BLDG. #998
CONVERT THE EXISTING ACS BUILDING TO COF
300 x 300
R-4
200 x 150
SEE O&MA STANDARD DETAIL DWG NO. M-328.
ROOF EXHAUST FAN (TYP. OF 4EA)
SEE O&MA STANDARD DETAIL DWG NO. M-328.
ROOF EXHAUST FAN (TYP. OF 4EA)
HOSE BIBB
AUTOMATIC SHUT-OFF VALVE
EXISTING MAIN GAS PIPE &
NEW MECH. ROOM PIPING PARTIAL PLAN
NEW GAS PIPE & ALL TRAIN ASSEMBLY
P-1 M-14
SCALE : 1 / 50
AND PRESSURE REDUCING STATION (TYP.)
WATER METER & BACKFLOW PREVENTER
HGF
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
EDCBA
AS SHOWN
DATE:
MECHANICAL
M-14
D - 17 - 10
SHEET OF
203225
THERMOSTATIC MIXING VALVE
HOT WATER SENSOR
RE-CIRCULATION PUMP
DOMESTIC HOT WATER
EXISTING MAIN WATER LINE
HOT WATER HEATER W/ CONC. PAD 13
14 RE
-C
IRCULA
TIO
N
PUMP
DOMES
TIC
H
OT
WAT
ER
HOT WATER SENSOR
TH
ER
MOST
AT
IC
MI
XIN
G
VAL
VE
I-1
NOT TO SCALE
M-14
NEW MECH. ROOM PIPING ISOMETRIC DIAGRAM
F
ROM
/ T O
MEC
H.
ROOM
DOMES
TIC
WAT
ER
P
IPE
S
17 AND
PR
ES
SURE
R
EDUCIN
G
ST
AT
IO
N
(TY
P.)
WAT
ER
M
ET
ER
B
ACKF
LO
W
PR
EVE
NTE
R
SPECIFIC NOTES
KEY PLAN
FOLLOW THE MANUFACTURER’S INSTALLATION GUIDE.
1. THIS DRAWING SHOWS SUGGESTED PIPING CONFIGURATION. CONTRACTORS SHALL
GAS PIPING AND ACCESSORIES.
3. THE CONTRACTOR SHALL CONSULT GAS SUPPLIER FOR THE INSTALLATIONS OF
4. THE CONTRACTOR SHALL CONSULT GAS SUPPLIER FOR GAS PIPE SIZING.
2. THE CONTRACTOR SHALL INSTALL GAUGES WHERE NECESSARY.
BETWEEN THE RPZ RELIEF VALVE OPENING AND ANY DISCHARGE PIPING.
AN AIR GAP NOT LESS THAN TWICE THE DIAMETER OF THE RELIEF PORT OPENING
5. THE REDUCED PRESSURE BACKFLOW PREVENTER SHALL BE PROVIDED WITH
EXISTING MAIN WATER LINE
NEW
SMOKE
S
TA
CK
SS
MODULE
HOT
WAT
ER
H
EAT
ER
CONC.
PAD
SPECIFIC NOTES
MANUFACTURER’S RECOMMENDATION AND SITE CONDITIONS.
1. LAYOUTS OF HOT WATER HEATER MAY CHANGE DEPENDING ON
CAMP CARROLL
YI, TONG KI
NAM, TAE CHIN
22 MAY 17
HS-00557-7J
NEW MECH. ROOM PIPING PARTIAL PLAN
FOR THAAD/ 2-1 ADA BATTERIES, BLDG. #998
33 59
34 59
HGF
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
EDCBA
AS SHOWN
DATE:
MECHANICAL
M-15
D - 17 - 10
SHEET OF
SS
SP
EXISTING SPRINKLER SYSTEM
P-1 M-15
SCALE : 1 / 100
25 25
25 25
25 25
25 25
40 50 50
40 50 50
NEW WET TYPE FIRE SPRINKLER PIPING PLAN
CONSTRUCTION.
MEET WITH APPLICABLE CODES AND REGULATIONS TO COMPLETE SUBJECT PROJECT
COST CAUSED FROM NOT SHOWN OR/AND INDICATED IN THE CONCEPTUAL DRAWINGS TO
IGCE PURPOSE ONLY. THE CONTRACTOR IS RESPONSIBLE FOR ALL OTHER ADDITIONAL
1. THE FIRE SPRINKLER SYSTEM ROUTING AND PIPE SIZES SHOWN ARE CONCEPTUAL FOR
SPECIFIC NOTES
RESIDENTIAL RECESSED TYPE SPRINKLER HEAD (TYP.) : 31 EA
UPRIGHT FUSIBLE TYPE SPRINKLER HEAD (TYP.) : 6 EA
STANDARD RECESSED TYPE SPRINKLER HEAD (TYP.) : 20 EA
SPRINKLER HEAD (UPRIGHT FUSIBLE)
SPRINKLER HEAD (STANDARD RECESSED TYPE)
SPRINKLER HEAD (RESIDENTIAL RECESSED TYPE)
CAMP CARROLL
YI, TONG KI
NAM, TAE CHIN
22 MAY 17
HS-00557-7J
NEW WET TYPE FIRE SPRINKLER PIPING PLAN
DUCT GRADIENT :
MORE THAN 1/30 (WALL LAYER)
ENSURING THE RIGHT DISTANCE
(PREVENTION OF THE RAINWATER INTRUSION)
SET ANCHOR BOLT
DUCT
ERV
THE CONTROL BOX
SPIRAL DUCT
INSPECTION HOLE SIZE
600x600
RASA
EA
OA
POSITION CONFIRMATION OF
25 (32) 30 (38) 40 (48) 50 (60) 65 (76)
8 20 40 60 100
DRAIN PIPE SUPPORT HANGER SPACING (RIGID TUBES CHLORIDE)
DRAIN PIPE DIAMETER PIPE
DRAIN PIPE - MATERIAL : PVC
RIGHT CONSTRUCTION METHOD
HORIZONTAL DRAIN PIPE
GRADIENT 1/50~1/100 SHOULD GIVE UP
INDOOR PLUMBING PIPE BRANCHES
NOMINAL
(EXTERIOR LIGHT)
INDOOR CONNECTION
CAPACITY (HP)
DRAIN PIPE, A TRAP VALUE.
FROM THE WELDING DIFFICULT OR INDOOR
LIKELY TO BE INTRODUCED, SUCH AS ODOR
IF THE GRADIENT IS SUFFICIENT, WHICH IS
NOTE
DIAMETER (A) 16 Below
0.75 Within 1.0 Within 1.2 Within 1.5 Within 2.0 Within
150 More than20~40 40~50 65~125
300mm
FLEXIBLE HOSE
R.L/R.G
HANGER
CEILING TEX
DRAIN
MAXIMUM
F. L
THERE WILL BE A GAP AND CEILING FINISHES
1. CAPACITY DEGRADATION DUE TO THE CEILING IN THE AIR INTAKE.
2. THROUGH A FILTER NOT SPILL THE PRODUCT CONCERNED.
3. TEMPERATURE SENSING A BAD COLD REFLUX.
1M
REFRIGERANT PIPING
COMPUTATIONAL BOLT
DRAIN PIPING
CONNECTED TO THE MAIN PIPE
POWER LINE
COMMUNICATION LINES
WASHERS
NUT
3/8" COMPUTATIONAL BOLT
HANGER BRACKETS
TAPPED MECHANICAL ANCHORS
COMPUTATIONAL BOLT (3/8")
EXCEPT DUCT INSTALLATION EQUIPMENT
* DRAIN PIPE INSTALLATION STANDARDS
1. AFTER THE VERTICAL UPWARD DOWNWARD GRADIENT (1/50~1/100) AND SHOULD AVOID BENDING INSTALLED.
2. DRAIN PUMP HEAD HAS BEEN INSTALLED AS A STANDARD 450MM BELOW THE DRAIN PORT.
3. HANGERS FOR PLUMBING FIXTURE DRAIN INTERVALS ARE ALSO WITHIN 1.2M~1.5M.
4. IT WILL USE A FLEXIBLE HOSE OR FLEXIBLE HOSE FLEXIBLE.
AIR CONDITIONERS
CEILING CASSETTE
MAXIMUM 450mm
NOTE
S = 1/100
"B"
"A"
"A"
"B"
- NOT TO SCALE
M-16
PLUMBING DRAIN CAUTION
- NOT TO SCALE
M-16
"ERV" INSTALLATION SECTION VIEW
- NOT TO SCALE
M-16
4-WAY FLEXIBLE HOSES USED IN THE INSTALLATION
- NOT TO SCALE
M-16
INDOOR FIXED DETAIL4-WAY INSTALLING THE INDOOR CROSS-SECTION
HGF
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
EDCBA
AS SHOWN
DATE:
MECHANICAL
DETAIL DRAWINGS
M-16
D - 17 - 10
SHEET OF
CAMP CARROLL
YI, TONG KI
NAM, TAE CHIN
22 MAY 17
HS-00557-7J
FOR THAAD/ 2-1 ADA BATTERIES, BLDG. #998
CONVERT THE EXISTING ACS BUILDING TO COF
* CEILING FINISHES AND IN CASE OF A NICHE
MAXIMUM INTERVAL (M)
OF THE INDOOR UNIT AND DRAIN HORIZONTAL TUBE.
INDOOR UNITS SHOULD HAVE THE HEIGHT (FALL)
THE SIMULTANEOUS INSTALLATION OF MULTIPLE
DRAIN PIPE TO THE DRAIN PIPE JOINT JOINING
TABLE.
DIAMETER : DRAIN PIPE DIAMETER SEE
35 59
NOT TO SCALE
OUTDOOR HPU CONCRETE PAD
CAMP CARROLL
36 59
NOT TO SCALE-
PIPE HANGER DETAIL
NOT TO SCALE-
PIPE INSULATION DETAIL DETAIL DRAWINGS
M-17
3 4
"H" BEAM
(150MM HEIGHT)
RUBBER PAD
PAD 12T
CONCRETE PAD
RUBBER PAD
CONC. PAD
NOT TO SCALE-
2 CONCRETE PAD DETAILS
2. CHAMFER ALL EXPOSED EDGES OF CAST-IN-PLACE CONCRETE 19mm UNLESS OTHERWISE NOTED.
1. PAD SIZE SHALL BE COORDINATED WITH THE EQUIPMENT UNIT MANUFACTURER.
16 GAGE SHEET METAL
16 GAGE SHEET METAL
HGF
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
SHEET OF
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
EDCBA
AS SHOWN
DATE:
MECHANICAL
M-17
D - 17 - 10
M-17
M-17M-17
LONGITUDINAL JOINTS
YI, TONG KI
NAM, TAE CHIN
22 MAY 17
HS-00557-7J
FIN GRADE
19 CHAMFER
150 MIN 150 MIN
E.W.T.B
D16 @200 OC
200 150
MECHANICAL EQUIPMENT
CONCRETE PAD
100% COMPACTED BASE COURSE
NOTE :
ABBREVIATION:
T.B: TOP AND BOTTOM
E.W: EACH WAY
MATERIAL PROPERTIES:
2. REINFORCING STEEL YIELD STRENGTHS, fy=300 Mpa.
1. CONCRETE MINIMUM COMPRESSIVE STRENGTH AT 28 DAYS, f’c=24 Mpa.
FD ECA BG HF
HOT PIPE LINE
HGD FECBG H A
CG
MF
EXPOSED
CLINCHING STAPLE @ 100 O.C.
CG OR
MF
EXPOSED
WEATHER
A
C
D
B
CLASS II ADHESIVE
OVERLAP (40)
VAPOR-BARRIER JACKET
2. HOT WATER HEATING
3. HEATED OIL PIPE LINE
1. STEAM & CONDENSATE
5. REFRIGERATION SUCTION
4. A/C CONDENSATE DRAIN
COLD WATER PIPE LINE
3. DUAL TEMP. WATER
2. CHILLED WATER
1. MAKE-UP WATER
DOWN TO SHED WATER
SHALL BE OVERLAPPED
ALUMINUM JACKET
H
G
NOTE :
BAPIPING
COLD PIPE LINE
HOT PIPE LINE
D EC
INSULATION
PIPE
AREA
ITEM
80 JACKET STRIPE
F
CONCEALED
VAPOR-BARRIER JACKET
(MIN. 40 JACKET OVERLAP)
VAPOR-BARRIER COATING
10 W x 0.5 THK @300 O.C.
ALUMINUM LOCK-TYPE BANDS
80 JACKET STRIP OR
MF - MINERAL FIBER SHALL BE USED FOR HOT PIPES
CG - CELLULAR GLASS SHALL BE USED FOR COLD PIPES
SEE SPECIFICATION FOR INSULATION THICKNESS
PIPE SADDLE
PIPE SADDLE
65 THRU 80
UP TO 50
PIPE SIZE
15 DIA
100 THRU 12510 DIA
PIPE SIZEROD SIZE
CLEVIS HANGER
(NOT VAPOR BARRIER)
3,600
ROLLER
STAND
PIPE
LENGTH AS REQ’D
LOCKING
CONC BEAM
TRAPEZE HANGER
PL 15 X 200 X 200
BOLT PIPE ROLLERS TO ANGLE (TYP)
ANCH BOLT.
HANGER ROD (TYP)
NO INSULATION
16 GAGE STEEL
654032 5025
HANGER ROD SPACING
PIPE SIZE
3,3002,7002,400 3,0002,100
OF SMALLEST PIPE ON TRAPEZE.
MAX. ALLOWABLE
SPACING
NOTE : FOR TRAPEZE HANGER TAKE SPACING
ANGLE
SUPPORT NUT
PIPE SADDLE AT
LEAST 300 LONG
WELD
10080
3,900
(TYP)
INSULATION (TYP)
CONNECTION TO CONCRETE FLOOR W/CONCRETE ANCHORS OR TO
ROOF STRUCTURE MEMBER FOR TOP FLOOR
MIN. 600VAPOR BARRIER
INSULATION
NOTE
ANCHOR
ANGLE
CROSS BRACING
SLAB OR BEAM
AT LEAST 300 LONG
100 THRU 125
HANGER ROD SCHEDULE
15 DIA.65 THRU 80
10 DIA.UP TO 50
PIPE SIZEROD SIZEPIPE SIZE
16 DIA
ROD SIZE
CROSS BRACE : REFER TO SMACNA’S SEISMIC RESTRAINT MANUAL CHAPTER 5.
AT LEAST 300 LONG
LOCKING NUT
SUPPORT NUT
INSULATION
VAPOR BARRIER
16 DIA
ROD SIZE
HANGER ROD
HANGER ROD SCHEDULE
PIPE
HEAVY DUTY
CLEVIS HANGER
CAMP CARROLL
NOT TO SCALE-
PIPE SLEEVE-THRU INTERIOR WALL
NOT TO SCALE-
PIPE SLEEVE-THRU FLOOR
NOT TO SCALE-
WATER METER AND BACKFLOW PREVENTER & PRESSURE REDUCING STATION
NOT TO SCALE-
WATER HAMMER ARRESTOR
DETAIL DRAWINGS
M-18
1 2
NOT TO SCALE-
TYPICAL IN LINE PUMP PIPING DETAIL
37 59
HGF
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
SHEET OF
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
EDCBA
AS SHOWN
DATE:
MECHANICAL
M-18
D - 17 - 10
M-18 M-18
M-18 M-18
YI, TONG KI
NAM, TAE CHIN
22 MAY 17
HS-00557-7J
ORIFICE
FLOW CONTROL
STAINLESS STEEL
SHELL
THREADED PLUG
H E
IG
H T
NOTE ; SUPPORT PIPE BOTH SIDE OF WALL SO THAT NO
INTERIOR WALL
SLEEVE
PLASTIC)
SEALANT #2
METAL BAND
(TYP)
(CLOSED CELL
FLEXIBLE FOAM
RUBBER OR
MATERIAL
BACK UP
INSULATION
INSULATION
INSULATION
SEALANT #2
MIN 6.5 CLEARANCE
BACK UP MATERIAL
ALL AROUND
PIPE WITHOUT
METAL JACKET
WEIGHT RESTS AT POINT OF SLEEVE
PIPE
CEILING
LC
PIPE WITH
SLEEVE
METAL JACKET
METAL BAND (TYP)
RUBBER OR PLASTIC)
FLEXIBLE FOAM
(CLOSED CELL
BACK UP MATERIAL
SLEEVE
PIPE WITH INSULATIONPIPE WITHOUT INSULATION
P
IP
E
MATERIAL
BACK UP
FIN. FLOOR
CEMENT
SLEEVE
SPRING CLIP TYPE
ESCUTCHEON
NOTE :
m m m m
64mm
INSULATION
CLEARANCE
MIN. 6.4mm
SEALANT
SEALANT
1. ESCUTCHEONS SHALL BE PROVIDED AT ALL FINISHED SURFACES WHERE
EXPOSED PIPING, BARE OR INSULATED PASSES THROUGH FLOORS OR
CEILINGS, EXCEPT IN BOILER, UTILITY OR EQUIPMENT ROOMS.
2. USE FIRE STOPPING MATERIAL (SEE SPEC. 07840) AT FLOOR.
(TYPICAL)
PRESSURE GAUGE
SHUT-OFF COCK SUCTION
PROVIDE CHECK VALVE
WATER PUMP
AND DOMESTIC
IN DISCHARGES
DISCHARGE
SHUT-OFF VALVE
BALANCING VALVE
"C"
"A"
"B"
TYPE
33-60128 125
94 81
115 81
HEIGHT DIAMETER
1-11
12-32
CAPACITY
FIXTURE UNIT
FIXTURE
TO LAST
FROM BRANCH
SUPPLY
AND SIZE
20 OR 25 SEE
DWGS FOR LOCATION
PRESSURE PNEUMATIC
STAINLESS STEEL
DISPLACEMENT
ADAPTER
FLUID
BELLOWS
HYDRAULIC
CUSHION
DISPLACEMENT
DIAMETER
PIPE HANGER
STRAINER
(TYP OF 3)
GATE VALVE
GLOBE VALVE
UNION (TYP)
PET COCK (TYP OF 2)
REDUCING TEE (TYP)
REDUCER
BACKFLOW PREVENTER
REDUCED PRESSURE
(TYP OF 2)
PRESSURE GAUGE
MAX 30 PSIG
VENTED STATIC PRESSURE
SET @ 5 PSI ABOVE SYSTEM
PRESSURE REDUCING VALVE
(TYP OF 2)
GAUGE TAPPING
SAFETY VALVE
CONTROL PIPE
PRESSURE
M
WATER METER
SYSTEM
TO
CW
STAPLE
OVERLAP
E
D
F
ADHESIVE
INSULATION
FASTENER
DUCT
C
B
A
DUCT CONSTRUCTION STANDARDS METAL AND FLEXIBLE TABLE 1-2.
FOR STANDARD SEALING REQUIREMENTS, REFER TO SMACNA HVAC
ON 300mm ON CENTER ENTIRE PERIMETER OF THE DUCT IN 150mm WIDTH STRIPS CLASS II ADHESIVE (LESS THAN 600mm DUCT) AROUND
FLEXIBLE TYPE
50mm OVERLAP
CLASS II ADHESIVE UNDER THE
VAPOR-BARRIER JACKET
100mm OVERLAP
CLASS II ADHESIVE UNDER THE
RIGID TYPE
EXPOSEDCONCEALEDAREA
DUCT IN
ITEM
A
B
C
D
E
F
COATS
GLASS CLOTH EMBEDDED BETWEEN
OF VAPOR-BARRIER COATING WITH
JACKET IS USED, APPLY TWO COATS
WHEN FIELD APPLY VAPOR-BARRIER
100mm O.C. WITH TYPE II VAPOR-BARRIER COATING
DUCT CORNER
NOT MORE THAN 400mm FROM SIDES 400mm O.C. AND 600mm LARGER DUCT BOTTOM/
INSULATION JOINT
80mm FROM THE EDGES OF THE
APART AND NOT MORE THAN
ALL FOUR SIDE OF DUCT 300mm
VAPOR-BARRIER JACKET
NOT TO SCALE
EXTERIOR DUCT INSULATION DETAIL
NOTE :
CAMP CARROLL
38 59
ALL TRANSVERSE EDGES
DIMENSIONS
TO BE COATED WITH ADHESIVE
CB
E
FOLDED CORNER
PIN AND WASHER
ALTERNATE
(FASTENER)
12.71 TO 30.5 MPS
DUCT SECTION
UP TO 12.7 MPS
VELOCITY
(TYPICAL 1,200 OR 1,500mm)
A
E
B
LINING
C
B
C
B
C
A
E
2.
1.NOTE :
ATTACHED BY SCREWS, RIVETS OR WELDS.)
BE FORMED ON DUCT OR BE CHANNEL OR ZEE
NOSING ON EVERY LEADING EDGE. (NOSING MAY
WHEN VELOCITY ABOVE 20.3 MPS USE METAL
MAXIMUM SPACING FOR FASTENERS ACTUAL
INTERVALS ARE APPROXIMATE.
LAPPED AND BUTTED CORNER
GASKET
DUCT
TYPE1
TYPE 2
(REQ’D 2)
DOOR
DUCT
GASKET
DOOR
FASTENER
APPROVED
FASTENER
BACK
24 26
2-S
2-S
1-S
FRAME DOOR
METAL GAGE
FASTENER
HINGE POS.3HINGE POS.2
BUTT HINGE OR
PIANO HINGE
NO.
HINGES
DOOR
SIZE
AND LESS
498 Pa.
STATIC 400 X 500
600 X 600
300 X 300
NOTE: S = SIDE OPPOSITE HINGES
LOCKS
NO.
NOT TO SCALE
DUCT ACCESS DOOR
NOT TO SCALE
DUCT LINING DETAIL
NOT TO SCALE
TYPICAL SECURITY BARS INSTALLATION
NOT TO SCALE
DUCT HANGER
STRAP HANGER TRAPEZE HANGERS
SEE NOTE 1
INSULATION
RIGID
SCREWS
HANGER LOOPS
OMITTED IF
SCREWS MAY BE
FOR LOAD
SIZE BOLT(S)
ROD
ANGLE
STRAPS OR
STRAPS
HANGER
ANGLES
NUTS
ROD
25mm MIN.
3.
2.
1.
LIMITS.
DO NOT EXCEED ALLOWABLE LOAD
BOTH DUTIES.
ATTACHMENT IF IT QUALIFIES FOR
REINFORCEMENT MAY BE USED FOR
UNDER A BOTTOM OF REINFORCEMENT.
UNLESS FOOT OF STRAP IS PLACED
DISTANCE IS NOT TO EXCEED 1500mm
DETAIL DRAWINGS
6 " O.C.3-3/8 "
MAX
1-1/2 "
3/16 " SLEEVE
AND VERTICAL
HORIZONTAL
3/4 " DIA BARS TYP
2 PLACES
ANGLE FRAME
1-1/2" x 1-1/2" x 3/16 "
SEE NOTE 2
LOAD CAPACITY)
(VERIFY UPPER TRAPEZE
ALTERNATIVE LOCATION
M-19
HGF
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
EDCBA
AS SHOWN
DATE:
MECHANICAL
M-19
D - 17 - 10
M-19
M-19 M-19 M-19
YI, TONG KI
NAM, TAE CHIN
22 MAY 17
HS-00557-7J
HANGER SIZES FOR RECTANGULAR DUCT
SHELF ANGLES
TRAPEZE
UP THRU 450 - 25x22 GA.
475 THRU 750 - 25x22 GA.
25x18 GA.
25x18 GA.
25x16 GA.
25x16 GA.
40x16 GA.
50x50x6
50x50x7
50x50x8
25x25x6
25x25x6
OF DUCT(mm)
DIMENSION
LONGEST
775 THRU 1025
1050 THRU 1500
1525 THRU 2150
2160 THRU 2450
OVER 2475
RODS(mm)
HANGER
HANGER(mm)
STRAP
40x40x6
40x40x6
SPACING(m)
MAXIMUM
3.00
3.00
3.00
3.00
2.40
2.40
2.40
10mm
10mm
10mm
10mm
15mm
NOTES
FOR THAAD/ 2-1 ADA BATTERIES, BLDG. #998
SHEET OF
CAMP CARROLL
39 59
NOT TO SCALE- NOT TO SCALE-
FLOOR CLEANOUTFLOOR DRAIN
DETAIL DRAWINGS
M-20
1 2
DRAINS SHALL BE CONNECTED TO CAST IRON P-TRAP.
A CHROMIUM PLATED BRONZE, NICKEL BRONZE OR NICKEL BRASS STRAINER.
NOTES:
M-20
2.CHROMIUM-PLATED BRONZE, NICKEL BRONZE, NICKEL BRASS OR
HGF
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
EDCBA
AS SHOWN
DATE:
MECHANICAL
M-20
D - 17 - 10
SHEET OF
YI, TONG KI
NAM, TAE CHIN
22 MAY 17
HS-00557-7J
AREA/PIT DRAIN
CEMENT
WATER-PROOF MEMBRANE
A
FINISH/TILE FLOOR
SEE NOTE-2
AOUTLET SIZE
WATER-PROOF MEMBRANE
SEE NOTE-1
75 200
100 250
50 125
FILL/BED
SLAB
STRUCTURAL
CEMENT
DRAIN AND BACKWATER VALVE
SEE NOTE-2
SEE NOTE-2
SEE NOTE-1
WATER-PROOF MEMBRANE
FLOOR/SHOWER DRAIN
SEE NOTE-1
STRUCTURAL
SLAB
FILL/BED
STRUCTURAL
SLAB
FILL/BED
CEMENT
FINISH/TILE FLOOR
4. DRAINS SHALL HAVE A CAST IRON BODY AND SEEPAGE PAN AND
2. NEOPRENE RUBBER GASKET COMPRESSION TYPE JOINT.
1. WATER-PROOF MEMBRANE ARE NOT REQUIRED IN SLAB ON GRADE.
3.
FINISH/TILE FLOORA A
TARRED JUTE PACKING(OAKUM)
STAINLESS STEEL FLUSH TYPE ACCESS COVER PLATE
NOTES : 1.WATER-PROOF MEMBRANE ARE NOT REQUIRED IN SLAB ON GRADE.
CAST IRON
PIPE
Y-BRANCH
WHEN NOT THRU RUN
PLUG Y-BRANCH
1/8 BEND
WATER-PROOF MEMBRANE
TWO PIECE THREADED
ADJUSTABLE HOUSING
LEAD CAULKING
SCORIATED COVER
SEE NOTE-2
NEOPRENE GASKET
FINISH FLOOR
| HS-00557-7J_T1 |
| HS-00557-7J_AE01 |
| HS-00557-7J_AE02 |
| HS-00557-7J_AE03 |
| HS-00557-7J_AE04 |
| HS-00557-7J_AE05 |
| HS-00557-7J_AE06 |
| HS-00557-7J_AE07 |
| HS-00557-7J_AE08 |
| HS-00557-7J_AE09 |
| HS-00557-7J_AE10 |
| HS-00557-7J_AE11 |
| HS-00557-7J_AE12 |
| HS-00557-7J_AE13 |
| HS-00557-7J_AE14 |
| HS-00557-7J_AE15 |
| HS-00557-7J_AE16 |
| HS-00557-7J_AE17 |
| HS-00557-7J_AE18 |
| HS-00557-7J_AE19 |
| HS-00557-7J_M01 |
| HS-00557-7J_M02 |
| HS-00557-7J_M03 |
| HS-00557-7J_M04 |
| HS-00557-7J_M05 |
| HS-00557-7J_M06 |
| HS-00557-7J_M07 |
| HS-00557-7J_M08 |
| HS-00557-7J_M09 |
| HS-00557-7J_M10 |
| HS-00557-7J_M11 |
| HS-00557-7J_M12 |
| HS-00557-7J_M13 |
| HS-00557-7J_M14 |
| HS-00557-7J_M15 |
| HS-00557-7J_M16 |
| HS-00557-7J_M17 |
| HS-00557-7J_M18 |
| HS-00557-7J_M19 |
| HS-00557-7J_M20 |
| HS-00557-7J_E01 |
| HS-00557-7J_E02 |
| HS-00557-7J_E03 |
| HS-00557-7J_E04 |
| HS-00557-7J_E05 |
| HS-00557-7J_E06 |
| HS-00557-7J_E07 |
| HS-00557-7J_E08 |
| HS-00557-7J_E09 |
| HS-00557-7J_E10 |
| HS-00557-7J_E11 |
| HS-00557-7J_E12 |
| HS-00557-7J_E13 |
| HS-00557-7J_E14 |
| HS-00557-7J_E15 |
| HS-00557-7J_E16 |
| HS-00557-7J_E17 |
| HS-00557-7J_E18 |
| HS-00557-7J_E19 |
| HS-00557-7J_E20 |
File details come from the government source that posted it. Updated .