M-1
A
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
MECHANICAL
MECHANICAL MATERIAL INDICATIONS &
M E C H A N I C A L M A T E R I A L I N D I C A T I O N S & S Y M B O L S
NTS
PD
Pa
OS&Y
OXY
OD
OAIL
OA
QT
PRV
PPM
POL
POC
PLMB
PH
PG
RT
RPM
RH
RDTR
RA
R12, R22
QTY
A B B R E V I A T I O N S
SBM
SAN
SA
SCH
FLOWMETER, ORIFICEBUTTERFLY
REFRIGERANT LIQUID
CHILLED WATER SUPPLY
CHILLED WATER RETURN
AIR COOLED CONDENSING UNIT
AIR CONDITION UNIT (S)
APPARATUS DEW POINT
AIR CONDITION (-ING,-ED)
CHILLED/HOT WATER RETURN
AMERICAN WIRE GAUGE
PRESSURE, BAROMETRIC
CUBIC METER PER HOUR
CHILLED/HOT WATER SUPPLY
CAPACITYCAP
CONNECTION
CONTINUE
COMPRESSOR
CUBIC METER
CPRSR
CONN
CONT
CU M
CHILLED WATER
CAST IRON PIPE
CIRCUIT
CLASSIFICATION
COOLING LOAD
COEFFICIENT
COUNTER CLOCKWISE
CLASS
CLG LOAD
COEF
CMH
CIP
CCW
CHW
CKT
ACV ALARM CHECK VALVE
AVERAGEAVG
BOILING POINT
CENTIGRADE
BAROMETER(-TRIC)
BRAKE HORSEPOWER
BP
BHP
C
BARO PR
AWG
BARO
ALUMINUM
ALTITUDE
AMBIENT
AIR HANDLING UNIT
AMPERE(AMP, AMPS)
APPROXIMATEAPPROX
ALT
AMB
AMP
AIR COND
ADP
AL
AHU
AIR COOLED
ACCU
ACLD
ACU
CHR
C/HWR
C/HWS
CHS
RL
D DRAIN
DIAMETER, INSIDE
ISOMETRIC
IRON PIPE SIZE
JOULE
THERMAL CONDUCTIVITY
KILOGRAM
KILOGRAM PER SQ. CENTIMETER (GAUGE)
KILOGRAM PER SQ. CENTIMETER
KILOGRAM PER SQ. CENTIMETER (ABSOLUTE)
KILOCALORIE PER HOUR
EXPANSION JOINT
EXPLOSION PROOF
FIRE HOSE CABINET
FULL LOAD AMPERES
ENTERING WATER TEMP
EVAPORAT (-E,-ING,-ED,-OR)
EXTERNAL STATIC PRESSURE
FACE AREA OR FRESH AIRFA
FHC
FHY
FLA
FIRE HYDRANT
ESP
EXPJT
EWT
EVAP
EP
EQPT
ENT
EFF
EQUIPMENT
ENTERING
EFFICIENCY
KG/SQ CM
KG/SQ CM A
KG/SQ CM G
KG
KCAL/HR
J
K
ID
ISO
IPS
NO
N.O.
NIC
NPT
MPS
NC
N/A
N.C.
MAX
MIN
MPH
MM
NOT IN CONTRACT
NATIONAL TAPER PIPE (THREAD)
NUMBER
NORMALLY OPEN
MINIMUM OR MINUTE
METERS PER HOUR
METERS PER SECOND
NORMALLY CLOSED
NOISE CRITERIA
NOT APPLICABLE
MAXIMUM
MILLIMETER R
FEMALE PIPE THREAD
FUEL OIL
GALVANIZED STEEL
GAGE OR GAUGE
FIXTURE
FEED WATER PUMP
FACE VELOCITY
FLUSH VALVE
FREQUENCY
FIBERGLASS REINFORCED PLASTIC
HORIZONTAL
HOT WATER HEATER
HOT WATER
HOUR(S)
HORSEPOWER
MERCURY
HEAD
HOSE BIBB
HERTZ
GRAMS
FRPCWP CIRCULATING WATER PUMP
DIRECT EXPANSION
DRY PIPE VALVE
EQUIVALENT DIRECT RADIATION
ENTERING AIR TEMPERATURE
DOUBLE POLE DOUBLE THROW
DEWPOINT TEMPERATURE
DRY BULB TEMPERATURE
DECIBEL OR DRY BULB
DIESEL OILDO
ECON
ECC
EAT
EDR
DX
DPV
DPDT
DPT
ECONOMIZER
ECCENTRIC
o
DEG or °
DIFF
DIAG
DIA or
DIV
DBT
DB
DIFFERENCE
DIAGRAM
DIAMETER
DIVISION
DEGREE
HR
HORIZ
HWH
HW
HZ
HP
HG
HD
HB
GALVS
GA
GR
FXTR
FWP
FVEL
FV
CUBIC MILLIMETER
CLOCKWISE OR COLD WATER
COEFFICIENT, VALVE FLOWCv
CU MM
CW
PLUG VALVE
THREE WAY
FPT
FO
FREQ
GATE, ANGLE
GATE, GLOBE
GLOBE
GATE
CONTROL
KJ KILOJOULE
LH
LT
LWT
LPS
M
LL
LPD
LPH
LM
LAV
LAT
LBS
LG
KW
KWH
L
LATENT HEAT
LEAVING WATER TEMPERATURE
LITERS PER HOUR
LITERS PER SECOND
LAUNDRY TRAY
METERS
LIQUID LINE
LITERS PER DAY
LINEAR METER
LEAVING AIR TEMPERATURE
LAVATORY
POUNDS
LENGTH
KILOWATT
KILOWATT HOUR
LITERS
P
FLOWMETER, VENTURI
FLOW SWITCH
PRESSURE SWITCH
PRESSURE GAUGE AND COCK
PUMP (INDICATE USE)
STRAINER
STRAINER, BLOW OFF
KG/SM
KG/SM A
KG/SM G
PS
P
OFM
FS
VFM
KILOGRAM PER SQ. METER
KILOGRAM PER SQ. METER (ABSOLUTE)
KILOGRAM PER SQ. METER (GAUGE)
JACKET WATER RETURN
MEDIUM PRESSURE STEAM
MEDIUM PRESSURE CONDENSATE
LOW PRESSURE STEAM
LOW PRESSURE CONDENSATE
BOILER BLOW DOWN
PUMPED CONDENSATE
JACKET WATER SUPPLY
VACUUM PUMP DISCHARGE
FUEL OIL TANK VENT
CONDENSATE WATER SUPPLY
CONDENSATE WATER RETURN
MEDIUM TEMPERATURE HOT WATER SUPPLY
MEDIUM TEMPERATURE HOT WATER RETURN
LOW TEMPERATURE HOT WATER SUPPLY
LOW TEMPERATURE HOT WATER RETURN
PIPE TO BE REMOVED
REFRIGERANT DISCHARGE
REFRIGERANT SUCTION
LPS
CONTROL AIR MAIN
air conditioning and refrigeration
RD
RS
(NAME)E
(NAME)
M
EXISTING PIPE
COMPRESSED AIR
VACUUM (AIR)
HWR
VAC
A
MTWS
MTWR
HWS
FOD FUEL OIL DRAIN
FOR
CS
CR
FOV
FOG
FOS FUEL OIL SUPPLY
FUEL OIL RETURN
FUEL OIL GAUGE
PC
VPD
MU
LPC
BBD
MAKE UP WATER
MPS
MPC
JWR
JWS
heating
PIPING
CHECK, SWINGSANITARY DRAIN
PITCH OR PIPE, UP(U), DOWN(D)
FLOOR SINK (200mm x 200mm)
PIPE SLEEVE WITH FIRE STOPPING
VENT THRU ROOF
BFP
60°C
82°C valves : (for selective actuators)
PLAN
HOT WATER (82°C)
HOSE BIBB
AIR LINEA
BALL
ELEV.
HOT WATER (60°C)
BACKFLOW PREVENTER
PIPE SLEEVE
(NAME)
ACID
200mm x 200mm
SURFACE CLEANOUT
FLOOR CLEANOUT
FLOOR DRAIN
CHEMICAL SUPPLY PIPES
FUNNEL DRAIN, OPEN
FCO
FD
SCO
FLOOR OR GRADE
FLOOR OR GRADE
CONDENSATE DRAIN BELOW
CONDENSATE DRAIN ABOVE
ACID WASTE
GASG
CD
CD
AIR VENT, MANUAL
AIR VENT, AUTOMATIC
W/ MEASURING TAP
EXPANSION LOOP
EXPANSION JOINT
BALL JOINT
ANCHOR, MAIN
ANCHOR, INTERMEDIATE
ALIGNMENT GUIDE
AIR SEPARATOR
FLEXIBLE CONNECTOR
SQUARE HEAD BALANCING COCK
EJ
S
MV
AVV
CHECK, NON-SLAM
CONTROL, ELECTRIC-PNEUMATIC
CONTROL, PNEUMATIC-ELECTRIC
QUICK OPENING
PRESSURE REDUCING
NEEDLE
LOCK SHIELD
HOSE END DRAIN
SAFETY
RELIEF
SQUARE HEAD BALANCING COCK
QUICK CLOSING, FUSIBLE LINK
R
S
PE
EP
plumbing
COLD WATER
HOT WATER RETURN
HOT WATER SUPPLY
VENT
MOTOR ELECTRIC
DIAPHRAGM
valves, special duty :
SOLENOIDS
valve actuators
M
FDAD
SUCTIONQUANTITY SUCT
TONS OF REFRIGERATION
TEMPERATURE DIFFERENCE
HEAT TRANSFER COEFFICIENT
SANITARY
SUBMERSIBLE
SUPPLY AIR
SCHEDULE
RADIATOR
REFRIGERATION TON
REVOLUTIONS PER MINUTE
RELATIVE HUMIDITY
RETURN AIR
THERMAL RESISTANCE
REFRIGERANT (12, 22, ETC)
TYPICALTYP
URINAL
UNIT HEATER
UR
UH
U
THERMOSTAT
THICKNESS
THERMOMETER
TEMPERATURE
SYMBOL
TSTAT
TONS
THERM
THK
TEMP
TD
SYM
SINGLE POLE DOUBLE THROW
LPH, STANDARD CONDITIONS
LPS, STANDARD CONDITIONS
LPD, STANDARD CONDITIONS
SAYBOLT SECONDS UNIVERSAL
SAYBOLT SECONDS FUROL
SENSIBLE HEATOUTSIDE AIR INTAKE LOUVER SH
PRESSURE DROP OR DIFFERENCE
PRESSURE REDUCING VALVE
PHASE (ELECTRIC)
PERCENT
PARTS PER MILLION
POINT OF CONNECTION
PLUMBING
PETROLEUM, OIL AND LUBRICANTS
QUART
OUTSIDE SCREW & YOKE
DIAMETER, OUTSIDE
PRESSURE GAGE
POLE
PASCAL
OXYGEN
SPRINKLERSPR
STEEL
STANDARD
STEAM
SQUARE
STAINLESS STEEL
STORAGESTOR
STL
STD
ST
SSU
SST
SSF
SQ
SENSIBLE LOAD
STATIC PRESSURE
SQUARE METER
SPECIFICATION
SPDT
SPEC
SM
SP
SLPH
SLPS
SLPD
SL
ALARM CHECK VALVE
SIDEWALL SPRINKLER
PENDENT SPRINKLER
UPRIGHT SPRINKLER
FIRE DEPARTMENT CONNECTION
PRE-ACTION VALVE
NOT TO SCALE
OUTSIDE AIR
(2-WAY SHOWN)
DRY-PIPE VALVE
SECOND
SAFETY FACTOR
SPECIFIC GRAVITYSG
SF
SEC
VARIABLE AIR VOLUMEVAV
VENTILATION
PRESSURE, DYNAMIC(VELOCITY)
WATER-COOLED
WATER CLOSET
WATTHOUR OR WATER HEATER
WET BULB TEMPERATURE
WATERPROOF
WSHR
WCLD
WTRPRF
WH
WT
W/
WD
WC
WBT
WEIGHT
WITH
WASHER
WIDTH
VP
VOL
WB
W
VISC
VERT
VENT
VEL
VOLUME
WET BULB
WATT
VISCOSITY
VERTICAL
VELOCITY
MANUAL VOLUME DAMPER
SMOKE DAMPER (PROVIDE ACCESS DOOR)
PNEUMATIC OPERATED DAMPER
VLV
V
VAC
M
VALVE
VOLT
VACUUM
SPLITTER DAMPER
SD
AD
VD
grilles, registers and diffusers :
SG
SR
600/300
300x150
200mm NCD
FIGURE IS ON TOP
810mm x 400mm dampers
ELBOW, TURNED DOWN
REDUCER, CONCENTRIC
REDUCER, ECCENTRIC (STRAIGHT, INVERT)
REDUCER, ECCENTRIC (STRAIGHT, DOWN)
TEE, OUTLET DOWN
TEE, SINGLE SWEEP
sprinkler
UNION, SCREWED
UNION, FLANGED
TEE, OUTLET UP
TEE
LATERAL
CONNECTION, BOTTOM
CONNECTION, TOP
ELBOW, TURNED UP
BUSHING
ELBOW, 45°
ELBOW, 90°
CAP
WELDED
FLANGED
SOLDERED
SCREWED BELL AND SPIGOT
SOLVENT CEMENT
SOUND ATTENUATOR
DETECTORS, FIRE AND/OR SMOKE
ELECTRIC MOTOR OPERATED DAMPER
FIRE DAMPER (PROVIDE ACCESS DOOR)
BACKDRAFT DAMPER
BDD
S
TRANSITION
TURNING VANES
SF
CHANGE OF ELEVATION, RISE(R), DOWN(D)
DUCT SECTION, NEGATIVE PRESS., FIRST
ACCESS DOOR, VERTICAL OR HORIZONTAL
COWL, (GOOSENECK) AND FLASHING
ACOUSTICAL LINING
FLEXIBLE DUCT
FLEXIBLE CONNECTIONFC
FIGURE IS ON TOP
R
AD
47.2
TG
94.4
UC 13mm
DG
500/300L
DUCT WORK
810mm x 400mm
810mm x 400mm
THERMOSTAT, ELECTRIC
TRAP, ELECTRIC (INDICATE TYPE)
fitting :
R
THERMOMETER
EXHAUST AIR GRILLE OR REGISTER, CEILING
DUCT SECTION, POSITIVE PRESS., FIRST
DIRECTION OF FLOW
SR
DIFFUSER, LINEAR
RETURN AIR GRILLE OR REGISTER, CEILING
CEILING DIFFUSER, SQUARE TYPE
CEILING DIFFUSER, ROUND TYPE (200mm
(600mm x 300mmH, 472 LPS)
UNDERCUT DOOR (13mm, 47.2 LPS)
DOOR GRILLE (300mmx150mmH)
NECK DIAMETER)
TRANSFER GRILLE ASSEMBLY
LOUVER, DOOR OR WALL
(500mmWx300mmH, 94.4 LPS)
RG
RR
SUPPLY AIR GRILLE OR REGISTER, SIDEWALL
EXHAUST AIR GRILLE OR REGISTER, CEILING
SUPPLY AIR GRILLE OR REGISTER, CEILING
ER
SG
EG
EXISTING WORK TO BE REMOVED.
POINT OF CONNECTION NEW TO EXISTING
OR END OF DEMOLITION WORK
EXISTING WORK TO REMAIN.(E)
REMOVE EXIST WORK.(R)
1 5
SYMBOLS AND ABBREVIATIONS
CHONG, ST
REPAIR BLDG NO. S-2369
CAMP CASEY
131607
M-2
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
MECHANICAL
GENERAL NOTES & SCOPE OF WORK
5. CONCRETE REMOVAL AND RESTORATION SHALL CONFORM TO SPECIFICATION.
NECESSARY DUCT CONNECTION(S) TO FUNCTION AS ORIGINALLY INTENDED.
12. PRIOR TO INSTALLING NEW HVAC AND PLUMBING PIPING CONTRACTOR MUST
COORDINATE WITH EXISTING DUCTWORK AND PIPING ELEVATION/LOCATION.
IF EXISTING DUCT ELEVATION IS CONFLICTED WITH NEW PIPING INSTALLATION,
REMOVE EXISTING DUCTWORK AND INSTALL NEW DUCTWORK AND MAKE ALL
CONTRACTING OFFICER FOR APPROVAL.
CONTRACTOR ACCORDING TO ACTUAL FIELD CONDITIONS AND SUBMITTED TO THE
FIELD CONDITIONS. SUCH DETAILS SHALL BE PREPARED IN THE FIELD BY THE
11. SOME DETAILS SHOWN ON THIS CONTRACT DRAWINGS MAY NOT MATCH EXACT
SUCH AS ANCHORS, HANGERS/SUPPORT, ETC.
10. ALL HVAC PIPING/DUCTWORK TO BE REMOVED SHALL INCLUDE ALL IT'S ACCESSORIES
9. ANY OPENING RESULT FROM THE REMOVAL WORK THAT'S NOT TO BE RE-USED
SHALL BE PATCHED OR RESTORED TO MATCH ADJACENT SURFACE OR AREA.
GENERAL NOTES
PER SPEC.
THIS CONTRACTOR.
AND SHALL BE VERIFIED AT THE JOB SITE.
CORRECTIONS FOR CONTRACTING OFFICER'S APPROVAL.
7. ALL WALL/FLOOR/ROOF OPENINGS RESULTED FROM THE REMOVAL OF PIPING AND
4. ANY PIPES THAT PENETRATE FIRE RATED WALL (EXISTING/ NEW) SHALL BE SEALED
6. NO MECHANICAL WORK CAN BE STARTED WITHOUT AN APPROVED SHOP DRAWINGS.
SHOP DRAWING SHALL NOT BE THE EXACT DUPLICATION OF THE CONTRACT DRAWING.
2. LOCATION AND SIZES OF EXISTING EQUIPMENT, DUCTWORK, PIPING, ETC. APPROXIMATE
OFFICER'S REPRESENTATIVE ATTENTION WITH RECOMMENDATIONS FOR PROPER
IF ANY DISCREPANCY IS DETECTED, IT SHOULD BE BROUGHT TO THE CONTRACTING
THE EXISTING CONDITIONS, EQUIPMENT, FINISHES, ETC., PRIOR TO START OF WORK.
1. THE CONTRACTOR SHALL VISIT THE SITE AND SHALL FAMILIARIZE HIMSELF WITH
THE WORK PERFORMED UNDER THIS CONTRACT SHALL BE REPAIRED OR REPLACED BY
THE EXISTING EQUIPMENT ANY EQUIPMENT, DUCT WORK, PIPING ETC. DAMAGED DUE TO
3. CONNECT TO EXISTING SYSTEM SHALL BE DONE IN SUCH A MANNER AS NOT DAMAGE
THE REQUIREMENTS OF SEAL CLASS C.
8. ALL SUPPLY, RETURN AND EXHAUST AIR DUCTWORK SHALL BE CONSTRUCTED
ACCORDING TO SMACNA STATIC PRESSURE CALSS 500PA AND DUCTWORK SHALL MEET
DUCTWORK SHALL BE PATCHED OR RESTORED TO MATCH ADJACENT SURFACE OR AREAS.
SCOPE OF WORK
13.
CHANGES REQUIRED TO MAKE THIS
CONTRACTOR SHALL PROVIDE NECESSARY SHOP DRAWINGS FOR ANY
REQUIREMENT FOR GAS ONLY BURNERS MAY BE JUSTIFIABLE. THE
PACKAGE, PRIOR TO THE START OF CONSTRUCTION, THEREFORE THE
PROVIDE NATURAL GAS ACCESS TO THE BUILDING UNDER THIS DESIGN
CONCURRENT NATURAL GAS CONVERSION PROJECT PACKAGES MAY
HEATING SYSTEMS WITH DPW PRIOR TO THE START OF CONSTRUCTION.
AND OIL) BURNERS FOR HEATING HOT WATER AND DOMESTIC HOT WATER
THE CONTRACTOR SHALL COORDINATE THE USAGE OF DUAL FUEL (GAS
SPRINKLER WORK
HVAC SYSTEM
ALL MECHANICAL SYSTEMS SHALL BE TESTED, ADJUSTED, AND BALANCED BY THE CONTRACTOR IN STRICT ACCORDANCE WITH
APPLICABLE SECTIONS OF DIVISION 15 - MECHANICAL O&MA STANDARD TECHNICAL SPECIFICATIONS FOR MISCELLANEOUS PROJECTS, KOREA.
THE HVAC TESTING, ADJUSTING, AND BALANCING (TAB) REPORT SHALL BE SUBMITTED TO THE PROJECT COR FOR GOVERNMENT REVIEW AND
APPROVAL.
1.
2.
3.
4.
6.
WITH NEW.
REPAIR BY REPLACEMENT OF EXISTING DETERIORATED FAN COIL UNITS, OUTSIDE AIR INTAKE BOXES, CONTROLS AND ASSOCIATED PIPING
7.
8.
9.
PLUMBING WORK
1.
2.
3.
4.
5.
6. REPAIR BY REPLACEMENT EXISTING BACK FLOW PREVENTER (BFP) AND PRESSURE REDUCING VALVE (PRV) ASSEMBLY, INCLUDING PIPE
REPAIR BY REPLACEMENT OF EXISTING DETERIORATED ALL DOMESTIC HOT AND COLD WATER PIPING WITH NEW.
REPAIR BY REPLACEMENT OF EXISTING DETERIORATED ALL SEWER, VENT, FLOOR DRAIN AND CLEANOUT PIPING.
REPAIR BY REPLACEMENT OF EXISTING DETERIORATED DOMESTIC HOT WATER STORAGE TANK,DOMESTIC HOT WATER CIRCULATION PUMP, REPAIR BY REPLACEMENT OF EXISTING DETERIORATED BATHROOM PLUMBING FIXTURES AND ASSOCIATED PIPING
WITH NEW.
REPAIR BY REPLACEMENT OF EXISTING DETERIORATED ELECTRIC WATER COOLER,SINK AND VALVE BOX WITHIN THE LAUNDRY ROOM WITH NEW.
SUPPORTS AND HOSE BIBB.
PIPING INCLUDING CONTROL SYSTEM WITH NEW.
REPAIR BY REPLACEMENT OF EXISTING ALL DETERIORATED HOT/CHILLED WATER AND DRAIN PIPING INCLUDING ACCESSORIES WITH NEW.
REPAIR BY REPLACEMENT OF EXISTING DETERIORATED WALL MOUNTED FOR MECHANICAL ROOM & LAUNDRY ROOM
ROOF MOUNTED FANS FOR BATHROOM, CONTROL SYSTEM AND ASSOCIATED DUCT WITH NEW.
REPAIR BY REPLACEMENT OF EXISTING DETERIORATED CEILING MOUNTED ELECTRIC HEATER, ELEC. UNIT HEATER AND THERMOSTAT WITH NEW.
5. REPAIR BY REPLACEMENT OF EXISTING DETERIORATED EXHAUST AIR DUCTWORK DRYER VENT, REGISTER, MOTORIZED OUTSIDE AIR INTAKE LOUVER DAMPER WITH NEW.
1. INSTALL FIRE PROTECTION SYSTEM WITH NEW WET TYPE SPRINKLER SYSTEM AND ASSOCIATED PIPING.
A. WORK CLASS "K" (REPAIR / MAINTENANCE WORK)
B. WORK CLASS "L" (CONSTRUCTION WORK)
DOMESTIC HOT WATER RE-CIRCULATION PUMP, THERMOSTATIC MIXING VALVE, CONC. PAD AND ASSOCIATED ACCESSORIES WITH NEW.
REPAIR BY REPLACEMENT OF EXISTING DETERIORATED CHILLED/HOT WATER CIRCULATION PUMP, CONC. PAD AND ASSOCIATED
REPAIR BY REPLACEMENT OF EXISTING DETERIORATED EXPANSION TANK, AIR SEPARATOR, CONC. PADS AND ASSOCIATED
PIPING WITH NEW.
REPAIR BY REPLACEMENT OF EXISTING DETERIORATED RANGE HOOD AND 100MM DRYER CONNECT TO DRYER WITH NEW.
CHONG, ST
REPAIR BLDG NO. S-2369
M-3
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
MECHANICAL
(PSI)
MAX. WORKING
PRESSURE
MAX. WORKING
CEMENT LINED
REMARKS
(PSI)PRESSURE
REMARKS
RPM
1,750
MOTOR
VOLT/PH/HZHP
HEADCAPACITY
TYPESERVICE
BASE MOUNTED END SUCTION
CENTRIFUGAL TYPE
Q'TY
P
P
ITEM NO
PUMPS
REMARKS
TANK SIZE
ACCEPTANCE VOLUME TANK SIZE
TYPE
BLADDER TYPE
TANK
SERVICE
TYPE
CAPACITY
ET
ITEM NO
Q'TY
DT
ITEM NO
Q'TY
EXPANSION TANK
HOT WATER SYSTEM
DOMESTIC HOT
WATER SYSTEM
SERVICE
DOMESTIC HOT WATER STORAGE TANK
P
16"DIA x 45" LONG
(INCH x INCH)
15022
(GALLONS)
PIPE SIZE(DIA)
PIPE MOUNTED
REMARKS
WITH STRAINER
AIR SEPARATOR
INLET
TYPEQ'TY
AS
ITEM NO SERVICE
HOT WATER SYSTEM
OUTLET
50 50
HOT / CHILLED WATER CIRC. PUMP
(GPM)
36 28
(FT TDH)
3/4 208/3/60
DOMESTIC HOT WATER
CIRC. PUMP
115/1/60
CENTRIFUGAL TYPE
PIPE MOUNTED IN-LINE 7.4 8 1/12 1,750
PIPE MOUNTED IN-LINE
CENTRIFUGAL TYPERECIRC. PUMP
DOMESTIC HOT WATER 5.3 25 1/3 115/1/60 1,750
VERTICAL MOUNTED TYPE
(GAL'S)
480 42" x 84"
(" DIA x " LONG)
1 3
1 2 3
W/BACKDRAFT DAMPER BIRD SCREENW/DISCONNECT SWITCH
FAN MOTOR
VOLT/PH/HZ
AIR CAP
ESP
HP REMARKS
CEILING GRILLE
115/1/60
TYPE
SERVICE
EF
EF
EF
Q'TYITEM NO
EXHAUST AIR FAN FOR MECH ROOM
FANS
EXHAUST AIR FAN FOR LAUNDRY ROOM
DIRECT DRIVEN, CENTRIFUGAL FAN
115/1/60
5 PREFABRICATED ROOF CURB.
WALL MOUNTED TYPE,
(CFM)
440 1/4" 1/22
DIRECT DRIVEN, CENTRIFUGAL FAN
WALL MOUNTED TYPE,
300 1/4" 1/22
ROOF MOUNTED TYPE,
DIRECT DRIVEN, CENTRIFUGAL FAN
321115/1/60EXHAUST AIR FAN FOR BATH ROOM3 320 1/4" 1/12
AIR
CAPACITY
(CFM)
Q'TY SERVICE
CSP
ITEM NO
INCH)
TOTAL
(BTU/HR)
COOLING
EAT(F)
GPM
-300
BED ROOMS
201,202,203,204,205,206)
(101,102,103,104,105,106
TYPE
VERTICAL CABINET
FLOOR MTD. TYPE
CHILLED / HOT WATER COIL
ROW
SENSIBLE
(BTU/HR) DB WB
EWT
( F)
MAX
WPD
(INCH)
HEAT CAP
(BTU/HR)
EAT
( F)
EWT
( F)
HEATING
SUPPLY FAN OUTSIDE AIR
HP VOLT/PH/HZ CFM LOUVER SIZE
9,500
44 69 1402.82.1 16,100 115/1/600.08 12"X2"30
1 600 3 18,600 13,700
44 694.1 2.7 29,700 115/1/60
MOTORIZED O.A INTAKE DAMPER.7,000
VERTICAL CABINET
FLOOR MTD. TYPE -
12"X2"300.08TV/DAY RM(207)
NOTE
-. UNIT SHALL BE PROVIDED WITH OA WALLBOX WITH
-. UNIT SHALL BE PROVIDED WITH SUB-BASE
-. CENTURY ACE MODEL #CAF-300 OR APPROVED EQUAL
-. CENTURY ACE MODEL #CAF-600 OR APPROVED EQUAL
-. FAN MOTOR UL LISTED: FILE NO. E235242
REMARKS
4&2 3
HOOD SIZE
(INCH)POWER VOLT/PH/HZ
12.5AMPS
SERVICE TYPE
(CFM)
CAPACITY
FAN FAN MOTOR
ITEM NO Q'TY
RH
RANGE HOOD
INCLUDE4 FE3 BUILT-IN CONTROL SWITCH21 WASHABLE FILTER LIGHTING(75W)
RANGE HOOD 115/1/60 30"x18"LOUNGE ROOM1
R E M A R KD E S C R I P T I O NITEM NO QTY.
EWC
ELECTRIC WATER COOLER
MOTOR : 1/5 HP, 115 V, 1 PH, 60 HZ.
FLOOR MOUNTED TYPE, MECHANICALLY
CAPACITY : 8.0 GPH, 80 DEG.F. TO 50 DEG.F.
AIR COOLED WITH AIR COOLED CONDENSER
& COMPRESSOR SHALL CONFORM TO ARI
STANDARD 1010.
DAMPER SIZE
MOTOR POWER 24W, 115V, 60HZ, 1PH.
16" X 12"
PLATE, ALUMINUM LOUVER, ACTUATOR, LINKAGE AND TRANSFORMER.
MOTRORIZED, OPPOSED DAMPER BLADES, GALVANIZED STEEL FRAME MOUNTING
R E M A R KD E S C R I P T I O NITEM NO QTY.
MOTORIZED OUTSIDE AIR INTAKE LOUVED DAMPER
FCU
FCU
FAN COIL UNITS
120/1/60
(KW)
HEATING
CAPACITY
VOLT/PH/HZ
TYPEQ'TY
NO
SERVICE
ITEM
UH
CEILING MTD
RECESSED TYPE
FOR CORRIDOR 120/1/601.0
REMARKS
(KW)
HEATING
CAPACITY
VOLT/PH/HZ
TYPEQ'TY
NO
ELECTRIC HEATER
SERVICE
ITEM
2 SIMILAR TO "QMARK" MODEL NO QCH1101 OR APPROVAL EQUAL.
ELECTRIC UNIT HEATER
FOR MECH ROOM
HORIZONTAL
DISCHARGE TYPE
2.0 3.8
LPM
82.1
EWT
( C)
15.5
EAT
( C)
FAN CAPACITY
LPS
256.7
RPM
1,550
HP
1/20
MDCEH
M E C H A N I C A L E Q U I P M E N T S C H E D U L E
MECHANICAL EQUIPMENT SCHEDULE
CHONG, ST
REPAIR BLDG NO. S-2369
M-4
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
MECHANICAL
HWR/CHWR
HWS/CHWS
- SCALE : 1 / 100
M4
FIRST FLOOR
NEW HVAC FLOOR PLAN
SECOND FLOOR
HWS/CHWS
HWR/CHWR
3/4" DRAIN TO 1st FOOR (TYP)
3/4" DRAIN (TYP)
HWS/CHWS
HWR/CHWR
SEE MECH. ROOM
PARTIAL PLAN
EXPANSION LOOP
AND PIPE GUARD (TYP)
PIPE ANCHOR
(TYP)
DF
TT T T T T T
FEC
W
RH
SIZE 350 x 175
WITH BIRDSCREEN
M5-
FCU
FCU
E A
FCU
300x50 OA INTAKE
LOUVER W/WALL BOX (TYP)
D D D D D
300x50 OA INTAKE
LOUVER W/WALL BOX (TYP)
T T T T T T
FCU
20 40
FCU
FCU
FCU
FCU
32 32
32 40
E A
E A
E A
E A
EF
EF
EF
E A
E A
E A
C /H
W S
C /H
W R
C /H
W R
C /H
W S
C /H
W S
C /H
W R
D
C /H
W R
C /H
W S
C /H
W R
C /H
W S
C /H
W R
C /H
W S
C /H
W S
C /H
W R
D
32 40
D
C /H
W R
C /H
W S
3/4" DRAIN (TYP)
C /H
W S
C /H
W R
C /H
W S
C /H
W R
C /H
W S
C /H
W R
40 40
C /H
W R
C /H
W S
C /H
W S
C /H
W R
25 40
C /H
W S
C /H
W R
C /H
W R
C /H
W S
C /H
W S
C /H
W R
D
3/4" DRAIN (TYP)
C /H
W R
C /H
W S
C /H
W S
C /H
W R
C /H
W R
C /H
W S
C /H
W S
D D
C /H
W S
C /H
W R
C /H
W R
C /H
W R
C /H
W S
D
C /H
W R
C /H
W S
C /H
W R
C /H
W S
D C /H
W S
C /H
W R
D
C /H
W R
C /H
W S
C /H
W R
C /H
W S
D
C /H
W S
C /H
W R
FCU
FCU
FCU
FCU
FCU
EXHAUST
DUCT RISER
FCU
FCU
FCU
FCU
FCU
(TYP.)
EXHAUST
DUCT RISER
(TYP.)
300x50 OA INTAKE
LOUVER W/WALL BOX (TYP)
20 20 20 20 20 20
15 15 15 15 15 15
32 32
EF
EF
E A
M5-
CEH
CEH
T T
150x100(TYP)
120x100
ROOF GOOSENECK
SEE DETAIL
DN
1.
NOTES:
CONTRACTOR SHALL VERIFY EXACT LOCATION, SIZE AND DIRECTION
OF HVAC PIPING AND DUCTS IN FIELD(TYP)
2. CONTRACTOR SHALL SUBMIT SHOP DRAWING FOR HVAC PIPING SYSTEM.
UP
W W D D
LS
LS
SS
UP
BED ROOM
BED ROOM
BED ROOM
BED ROOM BED ROOM
BED ROOM
STAIR-2
JANITOR
LAUNDRY RM
STAIR-1
RM
BULK STORAGE
SPRINKLER &
DN
DF
FEC
BED ROOM
BED ROOM
BED ROOM
BED ROOM
BED ROOM
BED ROOM
DAY ROOM
CORRIDOR
STAIR-1
JANITOR
UP
STAIR-2
FCU
FCU
FCU
FCU
FCU
FCU
FCU
MECH ROOM
G
G
M
EXISTING GAS PIPING SYSTEM
TO BE REMAINED
3.
4.
EXISTING GAS PIPING SYSTEM BE REMAINED.
REMOVE AND REINSTALL EXISTING GAS TYPE BOILER & DOMESTIC HOT WATER HEATER.
NEW HVAC FLOOR PLAN AND NOTES
FCU
FCU
T
T
CHONG, ST
REPAIR BLDG NO. S-2369
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
MECHANICAL
T
CS
WALL VENTILATOR
DOMESTIC HOT WATER CIRCULATION PUMP
EXPANSION TANK
AIR SEPARATOR
PRESSURE REDUCING VALVE
PRESSURE PRINCIPLE TYPE
BACKFLOW PREVENTOR
CIRCULATION PUMP
HOT/CHILLED WATER
H W
S / C
H W
S
H W
R / C
H W
R
2",1",21/2".2",2".
TH O
DM
300 CFM
16" X 12" OAIL
DOMESTIC HOT WATER RE-CIRCULATION PUMP
DOMESTIC HOT WATER STORAGE TANK
MOTORIZED OUTSIDE AIR INTAKE LOUVED DAMPER
EXISTING DOMESTIC HOT WATER HEATER
2"
2"
3/4"
- M5 SCALE : 1 / 50
1 MECHANICAL ROOM PARTIAL PLAN
- M5
NOT TO SCALE
MECHANICAL ROOM FAN CONTROL DIAGRAM
T
SWITCH
"HAND-OFF-AUTO" SELECTOR
1.
3.
2.
"HAND-OFF-AUTO" SELECTOR SWITCH TO "AUTO" POSITION OPERATES THE ROOF VENTILATOR
AUTOMATICALLY BY THE ROOM THERMOSTAT T .
THERMOSTAT T OPERATES THE VENTILATOR IN "ON-OFF" SEQUENCE TO MAINTAIN ROOM
TEMPERATURE BELOW 95 F.
SEQUENCE OF OPERATION
SET @ 95 F
ROOM THERMOSTAT
H-O-A
340 CFM
18" X 12" OAIL
DM
VENTILATOR UNTILL MANUALLY STOP.
"HAND-OFF-AUTO" SELECTOR SWITCH TO "HAND" POSITION OPERATES CONTINUOUSLY THE ROOF
INTAKE LOUVERD DAMPER
MOTORIZED OUTSIDE AIR
4. THE WALL VENTILATOR ELECTRICALLY INTERLOCKED WITH MOTORIZED OUTSIDE AIR INTAKE LOUVERED DAMPER.
M
P
P
P
EF
AS
ET
DT
MD
HT
UH
UNIT HEATER
R
METAL SCREEN FRAME
BOLT & NUT
ANGLE IRON REINFORCING
WHERE REQUIRED
SCREEN
AS REQUIRED
TACK WELDED
ANGLE RIVETED OR
WATERPROOF
SEAMS AND JOINTS
15 SCREEN
R= W
D U C
T SIZE +
25%
MESH SCREEN
450 MIN.
(HEAVY
SNOW AREA)
ROOF
M
IN
M
IN
FLASHING
- M5 NOT TO SCALE
ROOF GOOSENECK(RECTANGULAR DUCT)
EXISTING AIR-COOLED CHILLER
TO BE REMAINED
POC
EXISTING HOT WATER HEATING BOILER
TO BE REMOVED AND REINSTALLED
TO BE REMOVED AND REINSTALLED
2 1/2" COLD WATER SUPPLY LINE
1.
NOTES:
CONTRACTOR SHALL VERIFY EXACT LOCATION, SIZE AND DIRECTION
2. CONTRACTOR SHALL SUBMIT SHOP DRAWING FOR HVAC PIPING SYSTEM.
3.
4.
CONTRACTOR SHALL REMOVE AND REINSTALL THE EXISTING GAS FIRED
CONC. PAD
CONC. PAD
CONC. PAD
CONC. PAD
CONC. PAD
OF HVAC PIPING IN MECH ROOM.
HOT WATER BOILER AND DOMESTIC HOT WATER HEATER ASSOCIATED FLUE AND GAS PIPING.
CONTRACTOR SHALL REMAIN GAS PIPING SYSTEM IN MECH ROOM.
MECHANICAL RM PARTIAL PLAN, CONTROL
DIAGRAM, ROOF GOOSENECK AND
NOTES
M-5
CHONG, ST
REPAIR BLDG NO. S-2369
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
MECHANICAL
G
M mm
MAI
N
GAS
P
IPI
NG
(E
G
GAS
T
RAI
N
AS
SE
MBL
Y
(TY
P.
AUTO
MAT
IC
GAS
L
EAK
DET
EC
TIO
N
GAS
L
EAK
DET
EC
TO
R
MOUNTE
D
ON
CEIL
IN
G mm
SHUT
OFF
V
AL
VE
E)
SHUT
OFF
V
AL
VE
(E
GAS
F
IR
ED
HOT
W
AT
ER
B
OI
LE
R
TO
B
E
RE
MOVE
D
RE
IN
ST
AL
LE
D
GAS
F
IR
ED
DOMES
TIC
H
OT
W
AT
ER
HEAT
ER
T
O
BE
R
EMOVE
D
RE
IN
ST
AL
LE
D
CONTR
OL
PANEL
(E
GAS
A
LA
RM
GONG(
E)
SHUT
OFF
V
AL
VE
E)
GAS
M
ET
ER
(E
GAS
R
EGULA
TO
R( E)
FIL
TE
R( E)
EXIS
TIN
G
CONC.
P
AD
TO
B
E
RE
PL
ACED
TO
B
E
RE
PL
ACED
EXIS
TIN
G
CONC.
P
AD
NOT TO SCALE
MECH RM GAS PIPING ISOMETRIC DIAGRAM
NOTES:
CONTRACTOR SHALL REMOVE AND REINSTALL THE EXISTING GAS FIRED
HOT WATER BOILER AND DOMESTIC HOT WATER HEATER ASSOCIATED FLUE AND GAS PIPING.
CONTRACTOR SHALL REMAIN GAS PIPING SYSTEM IN MECH ROOM.
DIAGRAM AND NOTES
MECH RM GAS PIPING ISOMETRIC
M-6
M6
CHONG, ST
REPAIR BLDG NO. S-2369
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
MECHANICAL
- NOT TO SCALE
SUNSHIELD
(W/REMOTE BULB)
OUTDOOR AIR THERMOSTAT
T O
E
HWR
HWS
HWR
HWS
HEATING SYSTEM
FROM/TO BLDG.
PRESSURE REDUCING
BACK FLOW PREVENTER
MAKE UP COLD WATER
PCONTROL PANEL
H W
R
H W
S
EXPANSION
CHEMICAL FEEDER
G
DOMESTIC HOT WATER
THEMOSTATIC
VALVE
ASSEMBLY
TANK MOTOR STARTER1
ET
P
HOT/CHILLED CIRC. PUMP
SENSOR
AS
SEPERATOR
AIR
EXISTING GAS FIRED HOT WATER
BOILER TO BE REMOVED & REINSTALLED
MECH RM HVAC PIPING AND CONTROL ISOMETRIC DIAGRAM
GAS FIRED DOMESTIC HOT WATER
HEATER TO BE REMOVED & REINSTALLED
MIXING VALVE
REPLACE EXISTING HOT
WATER PIPING WITH NEW.
WATER PIPING WITH NEW.
REPLACE EXISTING HOT
CIRC. PUMP
NOT TO SCALE
MECH RM HOT WATER PIPING AND CONTROL ISOMETRIC DIAGRAM
P
REPLACE EXISTING CONC. PAD.
REPLACE EXISTING CONC. PAD.
RESET SCHEDULE AS INDICATED.
SUPPLY TEMPERATURE SETPOINT SHALL BE DETERMINED FROM A LINEAR
MAINTAIN HOT WATER SUPPLY TEMPERATURE AT SETPOINT. THE HOT WATER
THE BOILER BUILT-IN CONTROL SHALL MODULATE THE BOILER CONTROL TO
2. HOT WATER TEMPERATURE RESET CONTROL
1.1
1.
SET BOILER B-1 "HAND-AUTO" SWITCH TO AUTO POSITION, BOILER STARTS WHEN
WINTER SEASON
POSITION, PUMP STARTS AND RUNS CONTINOUSLY WHEN O.A. THERMOSTAT
SET EXISTING HOT WATER CIRC PUMP "HAND-OFF-AUTO" SWITCH TO "AUTO"
DROPS BELOW IT'S SETPOINT OF 15.6 DEG.C.
EXISTING HOT WATER CIRC PUMP IS ENERGIZED. BOILER PACKAGE CONTROL SHALL
MAINTAIN BOILER HOT WATER SUPPLY TEMPERATURE AT 82.2 DEG. C.
SEQUENCE OF OPERATION
1.3
BOILER SYSTEM CONTROL EQUIPMENT SCHEDULE
1. O.A. THERMOSTAT:
SPDT SWTCH WHICH MAKES CIRCUIT ON TEMPERATURE FALL,
RDMOTE BULB ELECTRIC TYPE THERMOSTAT, STANDARD RESPONSE
CONTROL RANGE 0-100 DEG F, 5 FEET COPPER CAPILLARY TUVBING,
DIFF= 1.0 DEG.F. ADJ. AND 8 AMPS AT 120VAC.
NOTES:
1.WIRING INDICATED IS SCHEMATIC. THE CONTRACTOR SHALL
PROVIDE ALL WIRING REQUIRED TO IMPLEMENT THE SEQUENCE
OF OPERATION.
2.PROVIDE SUITABLE ENCLOSURES OR WEATHERPROOF METAL
COVERS FOR ALL INSTRUMENTS, MOTORS, WIRING, AND TUBING
INSTALLED LUTSIDE THE BUILDING
3.ALL WIRING SHALL BE IN ACCDRDANCE WITH DIVISION
16 SPECIFICATION PROVISIONS.
4.PROVIDE AN AUTOMATIC TEMPERATURE CONTROL PANEL WHERE
INDICATED ON THE DRAWINGS. PANEL SHALL BE ENAMEL
FINISHED 14 GAUGE STEEL, NEMA 12 CONSTRUCTION.
15.6
OA-T
82.1
HWS-T-SP
-6.7
DEGREES C
RESET SCHEDULE
HOT WATER SUPPLY TEMPERATURE
MECH RM HVAC PIPING AND CONTROL
AND NOTES
ISOMETRIC DIAGRAM, MECH RM HOT WATER
PIPING AND CONTROL ISOMETRIC DIAGRAM,
M-7
M7
M7
CHONG, ST
REPAIR BLDG NO. S-2369
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
MECHANICAL
UP
40 25
DN
40 25
UP
UP
UP
DN
DN DN
32 32
SECOND FLOOR
- SCALE : 1 / 100
FIRST FLOOR
50,25,65.
50,32,20. 50,40,20. 50,32,20.
15 15
40 25 40 25
40 25
40 25
POC
40 25
40 25
MECHANICAL
B A B A
DN
B A
AB AB AB
UP
B
A
A
B
1.
NOTES:
CONTRACTOR SHALL VERIFY EXACT LOCATION, SIZE AND DIRECTION
2. CONTRACTOR SHALL SUBMIT SHOP DRAWING FOR PLUMBING PIPING SYSTEM.
Q' TY
WATER HAMMER ARRESTER SCHEDULE
FIXTURE
UNIT RATING
CONN.
SIZE
P.D.I
SYMBOL
REMARK
1 - 11A
( TYPICAL )
12 - 32B
15 mm
20 mm COMPRESSION CHAMBER WITH EXPANSION
STAINLESS STEEL CONSTRUCTION PRESSURIZED
EWC
OF HOT WATER, COLD WATER, SEWER AND VENT PIPING IN FIELD(TYP)
NEW HOT & COLD WATER PIPING PLAN
DN
SEE MECH. ROOM
PARTIAL PLANM5-
DN
DF
FEC
BED ROOM
BED ROOM
BED ROOM
BED ROOM
BED ROOM
BED ROOM
DAY ROOM
CORRIDOR
STAIR-1
JANITOR
UP
STAIR-2
UP
W WD D
LS
LS
SS
UP
STAIR-1
BED ROOM
BED ROOM
BED ROOM
BED ROOM
LAUNDRY RM
JANITOR
BED ROOM
BED ROOM
RM
BULK STORAGE
SPRINKLER &
STAIR-2
MECH ROOM
RESPONSIBLE FOR VERIFYING ACTUAL QUANTITIES BASED ON THE CONTRACT DOCUMENTS
1. QUANTITIES ARE SHOWN FOR ESTIMATION PURPOSE ONLY, THE CONTRACTOR SHALL BENOTES :
REQUIREMENTS.
SEE EQUIPMENT SCHEDULE
50 O.S.D
40-
WASTE
PIPE CONNECTION
H.W. VENT
BACK
SINGLE BOWL
STAINLESS STEEL TYPE
R E M A R K S
PLUMBING FIXTURE SCHEDULE
C.W.
EWC
P-13
ELECTRIC
WATER COOLER
SHOWER
WASHER
QTY.
P-8
P-12
P-7
P-1
SYMBOL
SERVICE SINK
LAUNDRY SINK
KITCHEN SINK
SINGLE BOWL
F I X T U R E
LAVATORY
WATER CLOSET
15 FLUSH TANKE MOUNTED TYPE
COUNTER TOP TYPE
W/ AERATOR SHALL BE KOSDO INC
MODEL KSAJ-515-24 OR APPROVED EQUAL.
SHALL BE KOSDO INC
MODEL KSAJ-100 OR APPROVED EQUAL.
P-1 P-1 P-1 P-1
P-5
P-5 P-5 P-5 P-5
P-7P-7 P-7P-7
P-8
P-12
P-12
P-13P-13 P-13P-13
P-7
P-1
P-5
P-13 P-13
P-1
P-5
P-7 P-7
P-1
P-5
P-13 P-13
P-1
P-5
P-7 P-7
P-1
P-5
P-13 P-13
P-1
P-5
P-7 P-7
P-1
P-5
P-13 P-13
P-1
P-5
P-7 P-7
P-8
M8
NEW HOT & COLD WATER PIPING PLAN,
PLUMBING FIXTURE SCHEDULE, WATER
HAMMER ARRESTER SCHEDULE AND NOTES
M-8
CHONG, ST
REPAIR BLDG NO. S-2369
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
MECHANICAL
SECOND FLOOR
4"FCO
4"FD
4"FCO
3"FD
2" OPEN SIGHT DRAIN
3"FCO
CONN. TO EXST. SEWER LINE
4"
4"
4" 4" 4"
3"
11/2"
11/2"
11/4"
2"
2" VENT PIPE LINE
TO 2ND FLOOR
3" SEWER LINE
TO 1ST FLOOR
- SCALE : 1 / 100
FIRST FLOOR
1.
NOTES:
CONTRACTOR SHALL VERIFY EXACT LOCATION, SIZE AND DIRECTION
2. CONTRACTOR SHALL SUBMIT SHOP DRAWING FOR PLUMBING PIPING SYSTEM.
OF HOT WATER, COLD WATER, SEWER AND VENT PIPING IN FIELD(TYP)
DF
REF
11/4"
2"
4" SEWER LINE
TO 1st FLOOR
4"FCO
2"SD 2"SD
11/4"
2"
4" SEWER LINE
TO 1st FLOOR
4"FCO
2"SD 2"SD
2"
4" SEWER LINE
TO 1st FLOOR
4"FCO
2"SD 2"SD
FROM 2nd FLOOR (TYP)
4" SEWER PIPE LINE
11/4"
4"
2"SD2"SD
11/2" VENT PIPE
TO 2nd FLOOR
FROM 2nd FLOOR (TYP)
4" SEWER PIPE LINE
11/4"
4"
2"SD2"SD
11/2" VENT PIPE
TO 2nd FLOOR
FROM 2nd FLOOR (TYP)
4" SEWER PIPE LINE
11/4"
4"
2"SD2"SD
11/2" VENT PIPE
TO 2nd FLOOR
NEW SEWER AND VENT PIPING PLAN
3"X2" REDUCER
3"VTR
3"X2" REDUCER
3"VTR
3"X2" REDUCER
3"VTR
4"VTR
4"X3" REDUCER
DN
4"FCO
4"FCO
4"FCO
DN
DF
FEC
BED ROOM
BED ROOM
BED ROOM
BED ROOM
BED ROOM
BED ROOM
DAY ROOM
CORRIDOR
STAIR-1
JANITOR
UP
STAIR-2
UP
W WD D
LS
LS
SS
UP
STAIR-1
BED ROOM
BED ROOM
BED ROOM
BED ROOM
LAUNDRY RM
JANITOR
BED ROOM
BED ROOM
RM
BULK STORAGE
SPRINKLER &
STAIR-2
MECH ROOM
P-1
P-5
P-13 P-13
P-1
P-5
P-7 P-7
P-1
P-5
P-13 P-13
P-1
P-5
P-7 P-7
P-1
P-5
P-13 P-13
P-1
P-5
P-7 P-7
P-1
P-5
P-13 P-13
P-1
P-5
P-7 P-7
P-1
P-5
P-13 P-13
P-1
P-5
P-7 P-7
P-1
P-5
P-13 P-13
P-1
P-5
P-7 P-7
POC
NEW SEWER AND VENT PIPING PLAN
AND NOTES
M-9
M9
CHONG, ST
REPAIR BLDG NO. S-2369
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
MECHANICAL
SP
D
FIRE PROTECTION LEGEND & ABBREVIATION
INDICATING BUTTERFLY
OS & Y
KEY OPERATED
SPRINKLER
MAIN SUPPLY SPRINKLER
PENDENT SPRINKLER
UPRIGHT SPRINKLER(K=5.6)
CUTTING POINT
CAP
FIRE DEPARTMENT CONNECTION
(2-WAY SHOWN)
NON-RISING STEM
VALVES
TAMPER DETECTION SWITCH
CHECK
FITTING
WALL MOUNTED TEST HEADER
CONNECTION, TOP
ELBOW, 90
ELBOW, 45
ELBOW, TURNED UP
ELBOW, TURNED DOWN
TEE
TEE, OUTLET UP
TEE, OUTLET DOWN
CONNECTION, BOTTOM
RISER REDUCER, ECCENTRIC (STRAIGHT, INVERT)
REDUCER, ECCENTRIC (STRAIGHT, DOWN)
TEE, SINGLE SWEEP
UNION, SCREWED
UNION, FLANGED
REDUCER, CONCENTRIC
GATE, NORMALLY CLOSED
GLOBE
DIAPHRAGM
GATE
GATE, NORMALLY OPEN
SWING GATE CHECK TYPICALTYP.
NO
EXST EXISTING
ABBREVIATIONS
MAX MAXIMUM
MIN MINIMUM
DRAIN PIPE
NUMBER
PIPE HANGER
DRAWINGDWG
CONN
CONT CONTINUE/CONTINUATION
CONNECTION
RM ROOM
W/ WITH
W/O WITHOUT
SCH SCHEDULE
BRANCH LINE RESTRAINTS
RESIDENTIAL PENDENT SPRINKLER
DRY SIDEWALL SPRINKLER
UPRIGHT SPRINKLER(K=8.0)
SPRINKLER Q'TY LIST
SPRINKLER HEAD TYPE
US/(METRIC)
"K" FACTOR
SIZE
A R E ASYMBOL
BED ROOM
THREAD
SPRINKLER Q'TY LIST
RESIDENTIAL PENDENT TYPE SPRINKLER HEAD 4.9/(68)1/2" NPT
TOTAL
MECH ROOMQUICK RESPONSE UPRIGHT TYPE SPRINKLER HEAD 8.0/(115)3/4" NPT
55.6/(80)1/2" NPT
QUICK RESPONSE PENDENT TYPE SPRINKLER HEAD
TOTAL NUMBER OF SPRINKLER OF SYSTEM 96
TV/DAY RM, LAUNDRY, JANITOR
95.6/(80)1/2" NPT
QUICK RESPONSE DRY SIDEWALL TYPE SPRINKLER HEAD CORRIDOR
BULK STORAGEQUICK RESPONSE UPRIGHT TYPE SPRINKLER HEAD 5.6/(80)1/2" NPT
9. ELEVATOR FIRE SPRINKLER SHALL BE IN ACCORDANCE WITH UFC 3-600-01, PAR 6-30.
AUTOMATIC FIRE SUPPRESSION(S) GENERAL NOTES:
1. THE CONTRACTOR SHALL PROVIDE AND INSTALL AN AUTOMATIC WET PIPE SPRINKLER SYSTEM
TO FULLY PROTECT THIS FACILITY. THE FIRE SPRINKLER SYSTEM SHOWN THESE DRAWING IS
PERFORMANCE BASED WHICH MEANS CONCEPTUAL REQUIREMENT ONLY. THE SPRINKLER
CONTRACTOR SHALL SUBMIT A COMPLETE FIRE SPRINKLER SYSTEM SHOPDRAWINGS BASED ON
NFPA 13 AND SPECIFICATION REQUIREMENTS AND SUBMIT FOR APPROVAL PRIOR TO
INSTALLATION. THE EQUIPMENT SHOWN ARE SUGGESTED LOCATIONS HOWEVER FINAL LAYOUT
SHALL BE IN ACCORDANCE WITH APPLICABLE CODES, MANUFACTURER'S RECOMMENDATIONS, AND
EQUIPMENT LISTINGS. CONTRACTOR SHALL COORDINATE SPRINKLER HEADS LOCATIONS WITH,
CEILING PANELS, LIGHTING FIXTURES, AND HVAC AIR DEVICES. ALL EQUIPMENT SHALL BE UL
LISTED AND FM APPROVED IN ACCORDANCE WITH NFPA 13 AND THE PROJECT SPECIFICATION.
2. THE CONTRACTOR SHALL CONDUCT WATER SUPPLY HYDRANT TEST FOR THIS PROJECT BASED
ON NFPA 291 REQUIREMENTS AND UTILIZE THIS DATA TO DESIGN THE SPRINKLER SYSTEM.
THE HYDRANT LOCATIONS, FLOW TESTS, AND DATE SHALL BE INDICATED ON THE
SHOPDRAWINGS. AUTOMATIC SPRINKLER PROTECTION SYSTEM IS REQUIRED TO PROTECT THIS
ENTIRE FACILITY. A MINIMUM 10% SAFETY FACTOR IS REQUIRED BETWEEN THE AVAILABLE
WATER SUPPLY AND THE SPRINKLER SYSTEM DEMAND.
INSTALLED IN THE HORIZONTAL POSITION.
7. ALL AUTOMATIC SPRINKLER DRAIN VALVES FOR FIRE DEPARTMENT CONNECTIONS SHALL BE
BE INSTALLED ON THE EXTERIOR.
DRAINS, BUT MUST TERMINATE TO THE BUILDING EXTERIOR. SPRINKLER RISERS SHALL NOT
AND MAINTENANCE. TEST DRAINS ARE NOT TO BE TERMINATED AT WALL SINKS OR FLOOR
6. PROVIDE MINIMUM 1M X 2M SPACE FOR EACH FIRE SPRINKLER RISER FOR INSTALLATION
AS-BUILT DRAWINGS FOR THIS PROJECT.
CONTRACTOR SHALL CONFORM TO THE SYMBOLS INDICATED IN NFPA 170 TO DEVELOP THE
22-"PLANS AND CALCULATIONS" PRIOR TO SPRINKLER PIPING INSTALLATION. THE
5. CONTRACTOR SHALL SUBMIT HYDRAULIC CALCULATIONS AS REQUIRED BY NFPA 13 CHAPTER
4. FIRE PROTECTION PLANS SHOWN ARE USED FOR COST ESTIMATE PURPOSE ONLY.
WITH O-RINGS ARE NOT PERMITTED.
BRACING CALCULATION IN ACCORDANCE WITH NFPA 13 REQUIREMENTS; SPRINKLERS
3. PROVIDE EARTHQUAKE PROTECTION (SWAY BRACING), END OF BRANCH LINE AND SEISMIC
8. FLEXIBLE COUPLINGS SHALL BE INSTALLED IN ACCORDANCE WITH NFPA 13, PAR 9.3.2.
10. ALL PIPING, SANITARY, VENT, WASTE, PLUMBING, OTHER PIPING, POWER OR CONTROL CIRCUTS, OR DUCT SHALL PENETRATE ANY STAIR OR EXIT PASSAGEWAY ENCLOSURE UNLESS IT SERVES
AN APPLIANCE WITHIN THE ENCLOSURE AND DEAD ENDS IN THE ENCLOSURE.
VERIFYING ACTUAL QUANTITIES BASED ON THE CONTRACT DOCUMENT REQUIRMENTS.
1. QUANTITIES ARE SHOWN FOR ESTIMATING PURPOSE ONLY, THE CONTRACTOR SHALL BE RESPONSIBLE FOR
NOTE
FIRE PROTECTION LEGEND & ABBREVIATION,
AUTOMATIC FIRE SUPPRESSION GENERAL
NOTES, SPRINKLER Q'TY LIST AND NOTE
M-10
CHONG, ST
REPAIR BLDG NO. S-2369
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
MECHANICAL
DN
FIRST FLOOR
SECOND FLOOR
25 25
100 100 100 100 100 100
100 100 100 100 100 100
S P (W
SP
(W
PENDENT TYPE SPRINKLER HEAD
15mm QUICK RESPONSE
UPRIGHT TYPE SPRINKLER HEAD
20mm QUICK RESPONSE
UPRIGHT TYPE SPRINKLER HEAD
15mm QUICK RESPONSE
SCALE : 1/100
PENDENT TYPE SPRINKLER HEAD
15mm RESIDENTIAL
PENDENT TYPE SPRINKLER HEAD
15mm QUICK RESPONSE
PENDENT TYPE SPRINKLER HEAD
15mm RESIDENTIAL
D D
DRY SIDEWALL TYPE SPRINKLER HEAD
15mm QUICK RESPONSE
SYSTEM TEST CONNECTION
100 10
100mm X 65mm X 65mm
FIRE DEPARTMENT SIAMESE CONNECTION
W/20mm BALL DRIP VALVE
100 mm CHECK VALVE
PIPING PARTIAL PLANM5-
1 SEE MECH. ROOM FIRE PROTECTION
UP
W WD D
LS
LS
SS
UP
STAIR-1
BED ROOM
BED ROOM
BED ROOM
BED ROOM
LAUNDRY RM
JANITOR
BED ROOM
BED ROOM
RM
BULK STORAGE
SPRINKLER &
STAIR-2
MECH ROOM
DN
DF
FEC
BED ROOM
BED ROOM
BED ROOM
BED ROOM
BED ROOM
BED ROOM
DAY ROOM
CORRIDOR
STAIR-1
JANITOR
UP
STAIR-2
FIRE PROTECTION PIPING PLAN
FIRE PROTECTION PIPING PLAN
M-11
M11 CHONG, ST
REPAIR BLDG NO. S-2369
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
MECHANICAL
140 SM (1500 SF)
TV/DAY RM, LAUNDRY,
INTERMEDIATE TEMPERATURE RATING
140 SM (1500 SF)
ORDINARY TEMPERATURE RATING
HC-1 HAZARD HC-2 HAZARD
OCCUPANCY
BULK STORAGEBED ROOM
4.9M X 4.9M
(16FT X 16FT)
MAX. 4.9 M (16 FT)
MIN. 2.4 M (8 FT)
JANITOR, CORRIDOR
SPRINKLER NOZZLE
K-FACTOR OF
(8.0)
(5.6)
(4.9)
(5.6)
WET SPRINKLER
4.1 LPM/SM (0.10 GPM/SF)
QUICK RESPONSE
20.9 SM (225 SF)
950 LPM (250 GPM)
MAX. 4.6 M (15 FT)
MIN. 1.8 M (6 FT)
60 MIN.
(57°C-77°C / 135°F-170°F)
ORDINARY TEMPERATURE RATING
TYPE OF SYSTEM
SPRINKLER
SPRINKLER TYPE
MAX. COVERAGE PER
BETWEEN SPRINKLERS
MAX. & MIN. SPACE OF
RATING*
SPRINKLER TEMPERATURE
DESCRIPTION
HAZARD
FIRE PROTECTION REQUIREMENTS
DESIGN DENSITY
DURATION OF SUPPLY
HOSE STREAM
DESIGN AREA
APPLICATION AREA
WET SPRINKLER
8.2 LPM/SM (0.20 GPM/SF)
QUICK RESPONSE
12.1 SM (130 SF)
950 LPM (250 GPM)
MAX. 4.6 M (15 FT)
230 SM (2500 SF)
MIN. 1.8 M (6 FT)
60 MIN.
(79°C-107°C / 175°F-220°F)
WET SPRINKLER
8.2 LPM/SM (0.20 GPM/SF)
QUICK RESPONSE
12.1 SM (130 SF)
950 LPM (250 GPM)
MAX. 4.6 M (15 FT)
MIN. 1.8 M (6 FT)
60 MIN.
(57°C-77°C / 135°F-170°F)
WET SPRINKLER
2.1 LPM/SM (0.05 GPM/SF)
RESIDENTIAL
950 LPM (250 GPM)
MAX. 4 HEADS
60 MIN.
RESIDENTIAL
OCCUPANCY
(57°C-77°C / 135°F-170°F)
ORDINARY TEMPERATURE RATING
OCCUPANCY
ORDINARY HAZARD
GROUP-II OCCUPANCY
- M12
SCALE : 1/50
MECH ROOM FIRE PROTECTION PIPING PARTIAL PLAN
100mm ALARM CHECK VALVE
100mm BACKFLOW PREVENTER
UL/FM APPROVED ASSEMBLY
W/2-65mm HOSE VALVE
100mm X 2-65mm TEST HOSE HEADER
W/20mm BALL DRIP VALVE
FOR BACKFLOW PREVENTER FLOW TEST
100mm X 65mm X 65mm
FIRE DEPARTMENT SIAMESE CONNECTION
W/20mm BALL DRIP VALVE
CONCRETE SPLASH BLOCK
WATER MOTOR ALARM GONG
MECH ROOM
WWDD
N .O
N .O
T S
N.O.
T S
N.C.
OS & Y GATE VALVE
W/ TAMPER SWITCH
SEE M-3 FIRST FLOOR PLAN
SEE CIVIL DWG
RM
BULK STORAGE
SPRINKLER &
MECH ROOM FIRE PROTECTION PIPING
PLAN AND FIRE PROTECTION REQUIREMENTS
M-12
CHONG, ST
REPAIR BLDG NO. S-2369
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
MECHANICAL
MAIN RISER CONNECTION(TYPICAL)
AND SPIGOT PIECE
DUCTILE IRON FLANGE
AND SPIGOT PIIPE
RODS NOT LESS
THAN 20Ø
DUCTILE IRON BELL
SERVICE
FROM FIRE
MAIN
G.L
GENERAL NOTE :
OR LEAVING THE SUBJECT BUILDINGS.
THIS DETAIL SHALL BE UTILIZED WHERE
.FIRE MAIN SERVICE LINES ARE ENTERINE
STEEL PIPE
THRUST BLOCK
CONC.
FL
BITUMASTIC COATED
BITUMASTIC COATED
SWAY BRACING
SEE
FX501
PIPE
O N
I C T
E N
D
E
PI
POT
SP O
U F
IR
E
A
DEPT C
KR
STA
N
N
CONNECTION
FIRE DEPT
CLAPPER
SWIVEL
2-1/2" NS OR BS
EASE - OFF
HOSE COUPLING
PLUG
THREAD
- M13
- M13
SYSTEM TEST CONNECTION ON WET PIPE SYSTEM
PIPE EXTENDS THROUGH WALL TO OUTSIDE.
2. THE TEST VALVE SHOULD BE LOCATED AT AN
ACCESSIBLE POINT AND PREFERABLY NOT
OVER 7FT (2.1M) ABOVE THE FLOOR.
OUTLET GIVING FLOW
TO ONE SPRINKLER
EQUIVALENT
PIPE IN WARM ROOM BEYOND VALVE WHERE
1. NOT LESS THAN 4FT (1.2M) OF EXPOSED TEST
NOTES :
ACCESSIBLE LOCATION
TEST VALVE IN READILY
CORROSION-RESISTANT
SMOOTH BORE
45° ELL
SEE NOTE
BRANCH LINE
P.G.
- M13
SPRINKLER ALARM CHECK VALVE & MAIN RISER1
- M13
CONC
SLAB
SWAY BRACE
FITTINGS
SCHEDULE 40
PIPE *
PIPE
CLAMP
SPRINKLER
CROSSMAIN
EXPANSION BOLT
(TYP)
CONC
SLAB
SWAY BRACE
FITTINGS
SCHEDULE 40
PIPE *
SPRINKLER
CROSS
MAIN
EXPANSION
BOLT
PIPE
CLAMP
* PIPE SIZE SHALL BE DETERMINED BY CALCULATIONS
FIRE DEPT SIAMESE CONNECTION5
M13
W/TAMPER SWITCH
GATE VALVE
OS & Y
FIRST
PIPE SUPPORT
1 3
SEE
FX501
FIRE DEPT CONNECTION
VALVE
BALL DROP
2 TAMPER SWITCH
BACKFLOW PREVENTER
TEST VALVE HEADER
TEST VALVE
OS & Y GATE VALVE
DESCRIPTION
ITEM
PER NFPA 13
FLEXIBLE COUPLING
FOR EARTH QUAKE
(WITH TAMPER SWITCH)
SUPERVISORY VALVE
WATER MOTOR ALARM DRAIN
PRESSURE SWITCH
PIPE SUPPORT
RISER TO SPRINKLER SYSTEM
FIRST SUPPORT W/CROSS BRACING
RETARDING CHAMBER
WATER MOTOR ALARM GONG
MAIN DRAIN VALVE
SWAY BRACING PER NFPA 13 FOR
FLEXIBLE COUPLERS PER NFPA 13
DESCRIPTION
ALARM CHECK VALVE
(2-REQUIRED)
PRESSURE GAGE
ZONE 1 EARTHQUAKE
ITEM
FOR EARTH QUAKE
VALVE
BALL DROP
MAIN DRAIN AND TEST VALVE
(WITH TAMPER SWITCH)
OS & Y GATE VALVE
DETAILS
M-13
CHONG, ST
REPAIR BLDG NO. S-2369
| Repair Bldg# S-2369, Cp Casey_M1 |
| Repair Bldg# S-2369, Cp Casey_M2 |
| Repair Bldg# S-2369, Cp Casey_M3 |
| Repair Bldg# S-2369, Cp Casey_M4 |
| Repair Bldg# S-2369, Cp Casey_M5 |
| Repair Bldg# S-2369, Cp Casey_M6 |
| Repair Bldg# S-2369, Cp Casey_M7 |
| Repair Bldg# S-2369, Cp Casey_M8 |
| Repair Bldg# S-2369, Cp Casey_M9 |
| Repair Bldg# S-2369, Cp Casey_M10 |
| Repair Bldg# S-2369, Cp Casey_M11 |
| Repair Bldg# S-2369, Cp Casey_M12 |
| Repair Bldg# S-2369, Cp Casey_M13 |
File details come from the government source that posted it. Updated .