A2_Drawing_files___58479___ELEC.pdf

PDF 3 MB Posted

Attached to
Repair Bldg 2308, Camp Casey
Solicitation number
W91QVN-17-R-0065
Issued by

About this file

Electrical Drawings

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

GENERAL NOTES

1.

2.MOUNTING HEIGHTS ABOVE FLOOR SHALL BE AS FOLLOW UNLESS OTHERWISE

NOTED ON THE DRAWING.

LIGHTING FIXTURE SEE LIGHTING FIXTURE SCHEDULE

PANELBOARD SEE SPECIFICATION

SAFETY SWITCH 1524mm TO CENTER OF THE ENCL

RECEPTACLE,TELEPHONE OUTLET 305mm TO CENTER OF THE ENCL

MOTOR CONTROLLER 1524mm TO CENTER OF THE ENCL

1676mm TO CENTER OF THE ENCL

2286mm TO CENTER OF BELL

3.

4.

6.THE SOIL RESISTANCE TO GROUND FOR THE ELECTRICAL AND COMMMUNICATION

SYSTEMS SHALL BE 25 OHMS OR LESS. THE SOIL RESISTANCE TEST SHALL BE

7.

COORDINATED WITH THE CENTRAL FIRE DEPARTMENT SO THAT

THE EQUIPMENT SHOULD BE COMPATIBLE WITH THE MAIN EXISTING

ON CEILINGDETECTOR

1372mm TO CENTER OF STATIONMANUAL PULL STATION

5.

CONDUCTED BY THE CONTRACTOR TO OBTAIN THE REQUIRED SOIL RESISTANCE.

INDICATEDS 2 #12AWG IN 16C

INDICATEDS 3 #12AWG IN 16C

INDICATEDS 4 #12AWG IN 16C

A GREATER NUMBER OF WIRES ARE INDICATED AS FOLLOWS;

1219mm TO CENTER OF THE ENCLWALL SWTICH

CONDUIT UNLESS OTHERWISE INDICATED.

ALL EQUIPMENT CONTROL WIRING SHALL BE #14 AWG. "TW" IN 16C

AND LOCATION OF THE F/A ANTENNA WITH THE CENTRAL FIRE DEPARTMENT

THE CONTRACTOR SHALL SUBMIT THE SHOP DRAWING FOR THE MOUNTING

TO TRANSMIT THE ALARM RADIO SIGNAL WAVE WITHOUT ANY OBSTRUCTION.

DETAIL OF THE F/A ANTENNA, AND COORDINATE THE MOUNTING HEIGHT

F/A EQUIPMENT IN THE CENTRAL FIRE DEPARTMENT.

THE EQUIPMENT SHOULD BE COMPATIBLE WITH THE MAIN EXISTING

A

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

ELECTRICAL

SCOPE OF WORKS

LEGEND, GENERAL NOTES AND

E-1

1.

SCOPE OF WORK

F/A & MNS EQUIPMENT IN THE CENTRAL FIRE DEPARTMENT.

THE MANUFACTURER AND MODEL OF NEW F/A& MNS EQUIPMENT SHALL BE

F/A &MNS CONTROL

COMBO. SPEAKER & STROBE

3.

2.

6.

12.

13.

14.

5.

4.

A. REPAIR/MAINTENANCE ( K )

10.

11.

8.

9.

15.

SINGLE POLE TOGGLE SWITCH, 15A-125V

L E G E N D

FLEXIBLE CONDUIT W/CONNECTORS

LIGHTING

WIRING

POWER

INTERIOR

S

SYMBOL DESCRIPTION

DESCRIPTION

DESCRIPTION

T

J

THERMOSTAT (UNDER MECH. ITEM)

JUNCTION BOX

SYMBOL

SYMBOL

F FAN MOTOR (UNDER MECH. ITEM)

SAFETY SWITCH

C CONTROL CIRCUIT

3-WAY SWITCH, 15A-125V

AND GOVERNMENT INSTALLED

GOVERNMENT FURNISHED

GFGI

WEATHERPROOFWP

LA LIGHTNING ARRESTER

EXPLOSIONPROOFEP

DISTRIBUTIONDIST

GROUND FAULT PROTECTIONGFP

A AMPERE

AC ALTERNATING CURRENT

AF/AT AMPERE FRAME/AMPERE TRIP

AWG AMERICAN WIRE GAUGE

BC BARE COPPER

BLDG BUILDING

BRKR BREAKER

C CONDUIT

CB CIRCUIT BREAKER

CKT CIRCUIT

CONN CONNECTION

CT CURRENT TRANSFORMER

DET(S) DETAIL(S)

DIAG DIAGRAM

DISC DISCONNECT

DWG(S) DRAWING(S)

EA EACH

EM EMERGENCY

ENCL ENCLOSURE

EXST EXISTING

F/A FIRE ALARM

FL FLOOR

FLUOR FLUORESCENT

FXTR FIXTURE

GEN GENERATOR

GND GROUND

HP HORSE POWER

HZ HERTZ

INCAND INCANDESCENT

INSTL INSTALLATION

J-BOX JUNCTION BOX

K KILO

KV KILO VOLT

KVA KILO VOLT AMPERE

LTG LIGHTING

MAG MAGNETIC

MAX MAXIMUM

MIN MINIMUM OR MINUTE

MTG MOUNTING

NO NUMBER

O/H OVER HEAD

PH PHASE

PNLBD PANELBOARD

PRIM PRIMARY

PWR POWER

Q'TY QUANTITY

RCPT RECEPTACLE

REQ'D REQUIRED

SCHED SCHEDULE

SEC SECONDARY

SPEC SPECIFICATION

STD STANDARD

SW SWITCH

TEL TELEPHONE

TYP TYPICAL

U/G UNDERGROUND

V VOLT

VA VOLT AMPERE

W WATT

W/ WITH

XFMR TRANSFORMER

& AND

CABNET TYPE, RATED WATT ON LTG SCHEDULE

LED LIGHTING FIXTURE, WALL MOUNTED OR UNDER

ON LTG SCHEDULE, WET LOCATION

LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG

FAULT PROTECTED TYPE

DUPLEX RECEPTACLE, 2P-3W-20A-125V, GROUNDED

PANELBOARD

3S

HOMERUN CIRCUIT TO PANELBOARD

TYPE OF MTG ON LTG SCHEDULE

EXTERIOR LED LIGHTING FIXTURE, RATED WATT &

TYPE

DUPLEX RECEPTACLE, 2P-3W-20A-125V, GROUNDING

ABBREVIATION

THE COTNRACTOR SHALL SUBMIT A SHOP DRAWING OF HVAC SYSTEM

IN ACCORDANCE WITH SEQUENCE OF OPERATION INDICATED ON THE

MECHANICAL DRAWINGS.

ANY CIRCUIT WITHOUT FURTHER DESIGNATION INDICATES 2-#12AWG

WIRES IN 16C CONDUIT UNLESS OTHERWISE INDICATED.

THE GROUNDING CONDUCTORS SHALL BE SEPARATELY PROVIDED FOR

ELECTRICAL EQUIPMENT UNLESS OTHERWISE INDICATED ON THE DRAWING.

NEW.

W/COVER PLATES AND ASSOCIATED WIRING & CONDUIT WITH

REPLACE EXISTING CATV CABINETS & PULLBOXES, OUTLETS

CEILING.

ALL WIRING SHALL BE CONCEALED ABOVE CEILING WHEN THE ROOM HAS

CATV BEFORE CONSTRUCTION.

CONTRACTOR SHALL COORDINATE WITH AREA MP, DO IMO, SIGNAL BRIGADE,

AND GOVERNMENT ACCEPTANCE.

PANELBOARD DOOR, REQUIRED BEFORE FINAL BUILDING INSPECTION

CONTRACTOR SHALL MAKE CIRCUIT CHARTS AND ATTACH THEM TO

FIRE CODE AND SPECIFICATIONS.

OF THE NATIONAL ELECTRICAL CODE, NATIONAL ELECTRICAL SAFETY CODE,

ALL ELECTRICAL WORK SHALL CONFORM TO THE CURRENT REQUIREMENTS

OR RENOVATION.

CONDITION AND DIMENSIONS PRIOR TO COMMENCING ANY CONSTRUCTION

THE CONTRACTOR SHALL BE RESPONSIBLE IN VERIFING ALL EXISTING

FIXTURE A MINIMUM DISTANCE OF 458mm.

FIRE ALARM DETECTORS SHALL BE LOCATED TO CLEAR ANY LIGHTING

7.

FMCP

FTR

ANTENNA

AUXILIARY

DESCRIPTION

F

TELEPHONE OUTLET

SYMBOL

CTC CATV SYSTEM CABINET

CATV OUTLET

ADDRESSABLE FA MANUAL PULL STATION

WP

F M

TTB

FIRE ALARM/MASS NOTIFICATION CONTROL PANEL

TELEPHONE TERMINAL BOARD

TV

MOUNTED TYPE

F/A & MASS NOTIFICATION SPEAKER "WP" WALL

STROBES

WALL MOUNTED SPEAKER /COMBO. (FA+MNS)VISUAL

CONNECTION

BUILDING TRANSMITTER UNIT FOR FIRE ALARM

SYSTEM

F FIRE ALARM SYSTEM CIRCUIT

WIRING FOR TELEPHONE LINET

BRANCH CIRCUIT, EXPOSED ON CEILING OR WALL

WIRING CONCEALED IN THE CEILING AND WALL

F/M

8.

L

PHOTOCELL

WP

FAULT PROTECTED TYPE, WEATHER PROOF

DUPLEX RECEPTACLE, 2P-3W-20A-125V, GROUNDED

TYPE

SINGLE RECEPTACLE, 2P-3W-20A-125V, GROUNDING

TYPE WITH PLUG

SINGLE RECEPTACLE, 3P-4W-30A-125/250V, GROUNDING

TYPE WITH PLUG

SINGLE RECEPTACLE, 3P-4W-50A-125/250V, GROUNDING

L

L

ON LTG SCHEDULE

LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG

ON LTG SCHEDULE

LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG

W/EMERGENCY BATTERY UNIT

L

W/EMERGENCY UNIT

WIRING TO UPSTAIR OR DOWNSTAIR

TYPE

QUADPLEX RECEPTACLE, 2P-3W-20A-125V, GROUNDING

ON LTG SCHEDULE

LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG

ON LTG SCHEDULE

LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG

L

L

SYSTEM WITH ASSOCIATED ACCESSORIES.

REMOVE AND REINSTALL EXISTING CCTV CAMERAS & MONITORING

9.

REMOVE EXISTING PUBLIC ADDRESS SYSTEM INCLUDING SPEAKERS.

UNITS.

CERTIFICATE FROM MANUFACTURER FOR LED LIGHTING FIXTURES AND POWER

CONTRACTOR SHALL BE RESPONSIBLE TO PROVIDE 10YEARS WARRANTY

ASSOCIATED WIRING & CONDUIT WITH NEW.

RECEPTACLES AND COVER PLATES, CIRCUIT BREAKER, AND

REPLACE EXISTING PANELBOARDS, PANELBOARD FRONT COVERS,

CONDUITS WITH NEW.

SWITCHES, PHOTOCELL, LIGHTING CONTACTOR, WIRES AND

LIGHTS, EXTERIOR LIGHTS, TOGGLE SWITCHES, 3-WAY

REPLACE DETERIORATED EXISTING LIGHTING FIXTURES, EXIT

AND ASSOCIATED WIRING AND CONDUIT WITH NEW.

EQUIPMENT RACK AND ACCESSORIES, OUTLETS W/ COVER PLATES

REPLACE DETERIORATED EXISTING TELEPHONE TERMINAL BOARD,

16.

THE GRADING LINE OF NEW DUCTS WILL BE LIMITED TO THE

WIDTH OF DUCT EXCAVATION.

AND AFTER INSTALLATION OF ELECTRICAL SYSTEM.

TO THEIR ORIGINAL CONDITION AND OPERATION DURING

ALL DAMAGED AREA INCLUDING SODDING, UTILITIES, STRUCTURES

THE CONTRACTOR SHALL BE RESPONSIBLE FOR RESTORING

LIGHTING CONTACTOR, SEL SW (H-O-A)

REPAIR BLDG S-2308

CAMP CASEYTAK, YS

58479

LINE, HANDHOLE AND ACCESSORIES WITH NEW.

REPLACE EXISTING EXTERIOR UNDERGROUND TELECOMMUNICATION

WITH NEW.

CONTROL SYSTEM, WIRES AND CONDUITS FOR HVAC SYSTEM

MOTOR STARTERS, MANUAL MOTOR STARTERS, JUNCTION BOXES,

CONTROL PANEL, COMBINATION MOTOR STARTERS, MAGNETIC

REPLACE DETERIORATED EXISTING SAFETY SWITCHES, MASTER

WIRING AND CONDUIT.

REQ'D) DEVICE, LOCAL OPERATING CONSOLE AND ASSOCIATED

VISUAL SIGNAL STROBES, MICROPHONE, SPEAKER (WATTAGE AS

DETECTOR & RELAY MODULE, BUILDING TRANSMITTER, ANTENNA,

NOTIFICATION SYSTEM PANEL, MANUAL PULL STATION, SMOKE

NEW ADDRESSABLE FIRE ALARM CONTROL AND MASS

REPLACE DETERIORATED FIRE ALARM CONTROL SYSTEM WITH

MH1-1A

MH2

MH1-A

MH1

1'

B

B

MH2-1

A

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

ELECTRICAL

EXIST TELECOMM LINE

(TYPICAL)

IN EXIST TELECOMM MANHOLE

C C

C

SCALE :

1/300

(1-96 CORE, SINGLE MODE FIBER OPTIC CABLE)

SEE NOTE 2 BELOW

IN EXIST TELE MANHOLE

NEW SPLICE KIT

FOR ABBREVIATION, LEGEND, AND GENERAL NOTES1.

NOTES

2.

SHALL BE INSTALLED ON THE EXISTING MANHOLE

AND TYPE OF SPLICE KITS SHALL BE COORDINATED

THE CONTRACTOR SHALL VERIFY EXISTING3.

UNDERGROUND TELECOMM LINE'S ACTUAL

CONDITION PRIOR TO WORK.

SEE SHEET NO. E-1.

WITH BASE SIGNAL COMPANY.

EXIST COMM MANHOLE

(TYPICAL)

C

C

IN 2-4" FABRIC INNER DUCT IN EXISTNG U/G CONDUIT

NEW 1-94 CORE, SINGLE MODE FIBER OPTIC CABLE

FROM MANHOLE "MH1-1A" TO "MH2-2"

NEW 1-96 CORE, SINGLE MODE FIBER OPTIC CABLE

NEW 1-100 PAIR AWG#24 TELEPHONE CABLE

M A

T C

H

L

IN

E

S

D W

G

E

T

N O

EXIST/NEW EXTERIOR TELECOMM DISTRIBUTION PLAN-1

EXISTNG U/G CONDUIT

NEW 1-100 PAIR AWG#24 TELEPHONE CABLE IN

NEW 1-94 CORE, SINGLE MODE FIBER OPTIC CABLE &

DISTRIBUTION PLAN-1

EXIST/NEW EXTERIOR TELECOMM

E-2

REPAIR BLDG S-2308

CAMP CASEYTAK, YS

58479

(1-100 PAIR AWG#24)

NEW TELEPHONE CABLE SPLICING KIT

HOUSE

GUARD

GUARD TOWER

A

B

MH2-2

MH2-3

A

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

ELECTRICAL

C

C

C

SCALE :

1/300

FOR ABBREVIATION, LEGEND, AND GENERAL NOTES1.

NOTES

2.

SHALL BE INSTALLED ON THE EXISTING MANHOLE

AND TYPE OF SPLICE KITS SHALL BE COORDINATED

THE CONTRACTOR SHALL VERIFY EXISTING3.

UNDERGROUND TELECOMM LINE'S ACTUAL

CONDITION PRIOR TO WORK.

SEE SHEET NO. E-1.

WITH BASE SIGNAL COMPANY.

NEW 1-12 CORE, SINGLE MODE FIBER OPTIC CABLE

1WAY: 1-12 CORE, SINGLE MODE FIBER OPTIC CABLE IN 3-4" FABRIC INNER DUCT

NEW U/G COMM LINE 2WAY OF 103C

NEW COMM HANDHOLE,

M A

T

L

IN

D W

G

E

N O

1WAY: 1-100 PAIR, AWG#24 TELEPHONE CABLE IN 3-4" FABRIC INNER DUCT

NEW 1-12 CORE, SINGLE MODE FIBER OPTIC CABLE

FABRIC INNER DUCT IN EXIST U/G CONDUIT

& 1-100 PAIR, AWG#24 TELEPHONE CABLE W/3-4"

(TYPICAL)

EXIST COMM MANHOLE

NEW SPLICE KIT

(1-12CORE, SINGLE MODE FIBER OPTIC CABLE)

SEE NOTE 2 BELOW

IN EXIST TELE MANHOLE

EXIST/NEW EXTERIOR TELECOMM DISTRIBUTION PLAN-2

SEE OMA STANDARD DETAIL DRAWING

RM

COMM.

1WAY: 1-12 CORE, SINGLE MODE FIBER OPTIC CABLE IN 3-4" FABRIC INNER DUCT

1WAY: 1-100 PAIR, AWG#24 TELEPHONE CABLE IN 3-4" FABRIC INNER DUCT

NEW U/G COMM LINE 2WAY OF 103C

DISTRIBUTION PLAN-2

EXIST/NEW EXTERIOR TELECOMM

E-3

REPAIR BLDG S-2308

SCALE: 1/100

EWC

E W

C

FEC

UP

UP

S/S

STORAGE

VEST

ROOM

ADMIN OFFICE

R.O

106B

T.O

106A

WAIT AREA

STORAGE

106C

STAIR-2

119B

CO

XO

COMM

COMMO SHOP

113A 113B

JAN

MULTI-PURPOSE RM

STORAGE

115MECH ROOM

C.Q

VEST

STAIR-1

119A LAUNDRY

JAN

CORRIDOR

105A

COMMUNITY

FEC

D

W

W

D

W/D

W/D

OFFICE

NBC ROOM

ARMS ROOM

COMM RM

LATRINE

MALE

LATRINE

FEMALE

E W

C

FECFEC

UPDN

UPDN

REF

STAIR-1

218A

219CORRIDOR

BED ROOM

201A

BED ROOM

201B

BED ROOM

202A

BED ROOM

202B

BED ROOM

203A

BED ROOM

203B

BED ROOM

204A

BED ROOM

204B

BED ROOM

205A

BED ROOM

205B

BED ROOM

206A

BED ROOM

206B

BED ROOM

207A

BED ROOM

207B

BED ROOM

208A

BED ROOM

208B

STAIR-2

218B

LAUNDRY

BED ROOM

214A

BED ROOM

214B

BED ROOM

213A

BED ROOM

213B

BED ROOM

212A

BED ROOM

212B

BED ROOM

211A

BED ROOM

211B

BED ROOM

210A

BED ROOM

210B

BED ROOM

209A

BED ROOM

209B

JAN

S/S

D

W

W

318A

301A 301B 302A 302B 303A 303B 304A 304B 305A 305B 306A 306B 307A 307B 308A 308B

314A 314B 313A 313B 312A 312B 311A 311B 310A 310B 309A 309B

318B

401A 401B 402A 402B 403A 403B 404A 404B 405A 405B 406A 406B 407A 407B 408A 408B

414A 414B 413A 413B 412A 412B 411A 411B 410A 410B 409A 409B

D

W/D

W/D

418B

418A

319 419

DAY RM

SCALE: 1/100

A

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

ELECTRICAL

E-4

J

J

J

J

J

J J

J

J J J J

J J J

J J

J

J

J

J

J

J

J

J

J

J

J

J

J

J

J

J

J

J

J

J J J

JJ

J

J J

J J

J

J

J

J

J

J J

J

J

J

J

J

J J

J

J J

J

J

J

J

J J J J J

J

J

J

J

J

J

J

S

S

S

S

S

S S

S

S

3S 3S

S

S

S

S

S

J

J J

J

J

J

J

J

J

J

J

JJ

J

J

S

S

SSS

S

S

3 3 3

S

L

L

L L L

L L

LL

L

L

L

L

L

L L L L L

L

L L L

LL

LL

LLL

L L

L

LL

L

LL

L

L

LL

L

L

L L

L LLLL L

L

L L L L L L L L L L L L L L L

L L

L

L

L

L

L L

L

L L L

L

L L

L L

L

LL

L L

L L

L

L

L

L L L L L L L L L L L L L L L L

L

L

L

SS S

S

S

S

S3

S3

SSSS

S

S

S

S

S

S

3S3S

S

S

L

L

J

LIGHTING CIRCUIT

PARKING AREA

RECONNECT EXIST

ORIENTED FACING NORTH

600W, 120V, 1PH

PHOTOELECTRIC

FOR ARMS ROOM

REPLACE W/ NEW WALL MOUNTED LED LIGHT

1ST FLOOR LIGHTING PLAN

2ND, 3RD AND 4TH FLOOR LIGHTING PLAN

PLAN

1ST, 2ND, 3RD AND 4TH FLOOR LIGHTING

MODULE PLAN ON E-9

SEE TYPICAL BEDROOM ELECTRICAL

L

L

L

OFFICE

OFFICE

ADMIN OFFICEADMIN OFFICE

L L

LL

L

L

L

L

L L

LL

LL

SS

CONTACTOR

CONNECT TO LIGHTING

2ND FL ONLY

EXTERIOR LIGHT, TYPE "NS-12"

CIRCUIT BREAKERS

CONN. TO EXIST

CONTACTOR AND WIRING DIAGRAM FOR APPROVAL

CONTRACTOR SHALL PROVIDE SHOP DRAWING FOR LIGHTING

1EA-(H-O-A) SELECTOR SWITCH, NEMA 4X ENCL.

CONTACTS(NO), MECHANICALLY HELD LIGHTING CONTACTOR,

: LIGHTING CONTACTOR, 120V, 60HZ COIL W/2EA-20A,

J

J

CONNECT TO EXISTING LIGHT CIRCUIT (TYPICAL)

LL

REPAIR BLDG S-2308

A

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

ELECTRICAL

E-5

DIODE(LED) EXIT LIGHT FIXTURE 1PH, 120V, 4.99W

WALL SURFACE MOUNTED LIGHT EMITTING

NS-7

NS-4a & 4b NS-6a & 6b

WALL MOUNTED FLUORESCENT LIGHT FIXTURE,

1PH, 120V, 1/32W TRIPLE TWIN-TUBE LAMP,

NS-8

100 WALL

NS-9

245mm

254mm

NS-5a & 5b

NS-10

CEILING RECESSED MOUNTED LIGHT EMITTING DIODE (LED)

CEILING RECESSED MOUNTED LIGHT EMITTING DIODE (LED)

FIXTURE, 1PH, 120V, 18W, WITH CONVERTER & ACCESSORIES,

CEILING SURFACE MOUNTED LIGHT EMITTING DIODE (LED) FIXTURE, 1PH, 120V, 18W, WITH CONVERTER & ACCESSORIES

WALL SURFACE MOUNTED LIGHT EMITTING DIODE (LED)

WET LOCATION SHOWER LIGHT TRIM, UL LISTED POWER UNIT

AS REQUIRED, UL LISTED POWER UNIT

W/BUILT-IN PHOTOCELL, WET LOCATION TYPE, UL LISTED

CEILING SURFACE/PENDANT MOUNTED LIGHT EMITTING DIODE (LED)

FIXTURE, 1PH, 120V, 45W, UL LISTED, WITH CONVERTER &

CEILING RECESSED MOUNTED LIGHT EMITTING DIODE (LED)

NS-11a & NS-11b NS-12

WALL MOUNTED LIGHT EMITTING DIODE(LED) LIGHT

FIXTURE, 1PH, 120V, 60 WATT, CONVERTER AND ACCESSORIES

UNDERCABINET LED LIGHT FIXTURE

1PH, 120V, 17W, CONVERTER AND ACCESSORIES,

WET LOCATIONS TYPE(IP66), UL LISTED POWER,

MANUFACTURED BY "SKC LIGHTING" OR APPROVED EQUAL.

NS-3a & NS-3b

(MAX. INPUT), BATTERY BACK-UP WITH BATTERY CHARGER,

SINGLE FACE(NS-3a) & DOUBLE FACE(NS-3b)

LIGHTING FIXTURE DETAILS

FIXTURE, 1PH, 120V, 45W, UL LISTED, WITH CONVERTER &

ACCESSORIES AS REQUIRED, (NS-4a) & WITH EM UNIT (NS-4b) FIXTURE, 1PH, 120V, 50W, UL LISTED, WITH CONVERTER &

ACCESSORIES, (NS-5a) & WITH EM UNIT (NS-5b) AS REQUIRED

FIXTURE, 1PH, 120V, 45W, UL LISTED, WITH CONVERTER AND

ACCESSORIES AS REQUIRED, (NS-6a) & EM UNIT(NS-6b)

UL LISTED POWER UNIT

ACCESSORIES AS REQUIRED, (NS-11a) & WITH EM UNIT (NS-11b)

REPAIR BLDG S-2308

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

E-6

MOUNTING METHOD

LIGHTING FIXTURE SCHEDULE

LAMP

TYPENO

ROOM

NAME WATTS

COE STD DET 40-06-04

TYPE

NO

SHT

Q'TY REMARKS MOUNTING METHOD

LIGHTING FIXTURE SCHEDULE

LAMP

TYPENO

ROOM

NAME WATTS

COE STD DET 40-06-04

TYPE

NO

SHT

Q'TY REMARKS

CEILING RECESSED5-

CEILING RECESSED1-

- EXIT LIGHT WALL MOUNTED5NS-3a -

CEILING SURFACE1NS-3b -

DOUBLE FACE

1/4.99

SINGLE FACE,

ABOVE DOOR TOP

WITH ARROW

- EXTERIOR WALL MOUNTED3-1/35

CEILING SURFACE6NS-3a -1/4.99

SINGLE FACE

WITH ARROW

1-

5-

STORAGE103 CEILING RECESSED

COMMUNITY ROOM104 CEILING RECESSED5-

CEILING RECESSED1- W/EM UNIT

ADMIN OFFICE105 CEILING RECESSED7-

CEILING RECESSED1- W/EM UNIT

COMM RM105A CEILING SURFACE1-

WAIT AREA106 CEILING RECESSED1- W/EM UNIT

T.O106A CEILING RECESSED1-

CEILING RECESSED1- W/EM UNIT

R.O106B CEILING RECESSED1-

CEILING RECESSED1- W/EM UNIT

STORAGE106C CEILING SURFACE1-

C.O107 CEILING RECESSED2-

CEILING RECESSED1- W/EM UNIT

X.O108 CEILING RECESSED2-

CEILING RECESSED1- W/EM UNIT

COMM109 CEILING RECESSED2-

CEILING RECESSED1- W/EM UNIT

SUPPLY ROOM110 CEILING RECESSED3-

CEILING RECESSED1-

NBC ROOM111 CEILING RECESSED5-

CEILING RECESSED1-

W/EM UNIT

W/EM UNIT

COMMO SHOP112 CEILING RECESSED2-

MALE113A CEILING RECESSED1-

WALL MOUNTED1-

FEMALE113B CEILING RECESSED1-

WALL MOUNTED1-

JANITOR113 CEILING SURFACE1-

MUIL-PURPOSE114A CEILING RECESSED8-

CEILING RECESSED2-

ROOM

W/EM UNIT

CEILING RECESSED1-

CEILING RECESSED1- W/EM UNIT

STORAGE115

CEILING RECESSED1-C.O116

CEILING RECESSED1-VEST117

CEILING RECESSED1-

W/EM UNIT

LAUNDRY118

1-

1- W/EM UNIT

STAIR-1119A

11-

STAIR-2119B

6- W/EM UNIT

CORRIDOR120

1-

1-

W/EM UNIT

MECH ROOM124 CEILING SURFACE4-

CEILING SURFACE1- W/EM UNIT

BEDROOM201A,B~

DAY RM215 CEILING RECESSED3-

214A,B

CEILING RECESSED1- W/EM UNIT

UNDER CABINET MTD1-

JANITOR216 CEILING SURFACE1-

LAUNDRY217 CEILING RECESSED1-

CEILING RECESSED1- W/EM UNIT

STAIR-1218A CEILING SURFACE2-

STAIR-2218B CEILING SURFACE2-

W/EM UNIT

W/EM UNIT

CORRIDOR219 CEILING RECESSED12-

CEILING RECESSED5- W/EM UNIT

CEILING RECESSED2-

CEILING RECESSED1-DRESS ROOM

BATH ROOM CEILING RECESSED2-

WALL MOUNTED1-

BEDROOM301A,B~

315 CEILING RECESSED3-

314A,B

CEILING RECESSED1- W/EM UNIT

JANITOR316 CEILING SURFACE1-

LAUNDRY317 CEILING RECESSED1-

CEILING RECESSED1- W/EM UNIT

STAIR-1318A CEILING SURFACE2-

STAIR-2318B CEILING SURFACE2-

W/EM UNIT

W/EM UNIT

CORRIDOR319 CEILING RECESSED12-

CEILING RECESSED5- W/EM UNIT

CEILING RECESSED2-

CEILING RECESSED1-DRESS ROOM

BATH ROOM CEILING RECESSED2-

WALL MOUNTED1-

BEDROOM401A,B~

MULTI-PURPOSE415 CEILING RECESSED3-

414A,B

CEILING RECESSED1- W/EM UNIT

JANITOR416 CEILING SURFACE1-

LAUNDRY417 CEILING RECESSED1-

CEILING RECESSED1- W/EM UNIT

STAIR-1418A CEILING SURFACE2-

STAIR-2418B CEILING SURFACE2-

W/EM UNIT

W/EM UNIT

CORRIDOR419 CEILING RECESSED12-

CEILING RECESSED5- W/EM UNIT

CEILING RECESSED2-

CEILING RECESSED1-DRESS ROOM

BATH ROOM CEILING RECESSED2-

WALL MOUNTED1-

ROOM

VEST121

JANITOR122 CEILING SURFACE

CEILING RECESSED1-

W/EM UNIT

WALL MOUNTED7NS-12 -

W/EM UNIT

W/EM UNIT

LED 50

NS-5a

NS-5b

W/EM UNIT

W/EM UNIT

NS-4b 45 1-

NS-4a 45 - 1

CEILING RECESSED

NS-5a

NS-5b

NS-5a

NS-5b 50

NS-6a 45

NS-5b 50

NS-5a

NS-5b 50

NS-5a

NS-5b 50

NS-6a 45

NS-5a

NS-5b 50

NS-5a

NS-5b 50

NS-5a

NS-5b 50

NS-4a

NS-4b 45

NS-4a

NS-4b 45

NS-4a 45

NS-4b 45 - 1 CEILING RECESSED W/EM UNIT

NS-7 18 -

NS-4a 45

45NS-4b

NS-7 18

NS-4b

NS-7 18

NS-5a

NS-5b 50

NS-4a

NS-4b 45

W/EM UNIT50NS-5b

NS-5b 50

NS-4a

NS-4b 45

- 1 CEILING RECESSED

NS-6b 45

NS-6b 45

W/EM UNIT

NS-11a

NS-11b

CEILING SURFACE

CEILING SURFACE

CEILING RECESSED

CEILING RECESSED

CEILING RECESSED

NS-4a

NS-4b 45

NS-4a

NS-4b

NS-8 17

NS-7 18

NS-5a

NS-5b 50

17NS-10

NS-7 18

NS-4a 45

45NS-4b

W/EM UNIT

NS-6b

NS-6b 45

NS-11a

NS-11b 25

NS-5b 50

NS-7 18

NS-4a 45

45NS-4b

NS-8 17

18NS-7

W/EM UNIT

DAY RM NS-5a

NS-5b 50

17NS-10

NS-7 18

NS-4a 45

45NS-4b

NS-6b

NS-6b 45

NS-11a

NS-11b 25

NS-4a 45

45NS-4b

NS-8 17

18NS-7

NS-5a

NS-5b 50

17NS-10

NS-7 18

NS-4a 45

45NS-4b

NS-6b

NS-6b 45

NS-11a

NS-11b 25

NS-9

1/4.99

- 1

UNDER CABINET MTD

UNDER CABINET MTD

ELECTRICAL

LIGHTING FIXTURE SCHEDULE

LED

FLUOR

101 ADMIN OFFICE

ADMIN OFFICE NS-5a

NS-5b CEILING RECESSED

CEILING RECESSED

W/EM UNIT

3-

LED NS-5a 50123

NS-5b 50 1- W/EM UNIT

OFFICE CEILING RECESSED

CEILING RECESSED

REPAIR BLDG S-2308

UP

UP

S/S

STORAGE

VEST

ROOM

ADMIN OFFICE

R.O

106B

T.O

106A

WAIT AREA

STORAGE

106C

STAIR-2

119B

CO

XO

COMM

109110

COMMO SHOP

113A

113B

JAN

MULTI-PURPOSE RM

114STORAGE

MECH ROOM

C.Q

VEST

STAIR-1

119A

LAUNDRY

JAN

CORRIDOR

105A

COMMUNITY

D

W

W

D

W/D

W/D

OFFICE

NBC ROOM

ARMS ROOM

COMM RM

LATRINE

MALE

LATRINE

FEMALE

UPDN

REF

STAIR-1

218A

219CORRIDOR

BED ROOM

201A

BED ROOM

201B

BED ROOM

202A

BED ROOM

202B

BED ROOM

203A

BED ROOM

203B

BED ROOM

204A

BED ROOM

204B

BED ROOM

205A

BED ROOM

205B

BED ROOM

206A

BED ROOM

206B

BED ROOM

207A

BED ROOM

207B

BED ROOM

208A

BED ROOM

208B

STAIR-2

218B

LAUNDRY

BED ROOM

214A

BED ROOM

214B

BED ROOM

213A

BED ROOM

213B

BED ROOM

212A

BED ROOM

212B

BED ROOM

211A

BED ROOM

211B

BED ROOM

210A

BED ROOM

210B

BED ROOM

209A

BED ROOM

209B

JAN

S/S

W

318A

301A 301B 302A 302B 303A 303B 304A 304B 305A 305B 306A 306B 307A 307B 308A 308B

314A 314B 313A 313B 312A 312B 311A 311B 310A 310B 309A 309B 318B

401A 401B 402A 402B 403A 403B 404A 404B 405A 405B 406A 406B 407A 407B 408A 408B

414A 414B 413A 413B 412A 412B 411A 411B 410A 410B 409A 409B

418B

418A

319 419

DAY RM

SCALE: 1/100

A

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

ELECTRICAL

E-7

J

J

J

+1800

EWC

EWC

F

FCU

FF

FCU

F

FCU

F

FCU

F

FCU

F

FCU

F

FCU

F C

U

TV

TV

S

S

S

F

FCU

F

FCU

J

J

J

EWC

ER

R

RH

FF

FCU

F

TV

TV

S

S

EWC

TV

TV

J J J J JJJ

SS

2ND, 3RD & 4TH FLOOR POWER PLAN

1ST FLOOR POWER PLAN

TT

T

RH

"P1A"

"P1B"

"P2A" "P3A" "P4A"

"P2B" "P3B" "P4B"

P4B-38

T

M D

P

J

"L1"

"L2" "L3" "L4"

A/C

+1800

J

JF

L1-4

L1-5

L1-6

L1-7

L2,3,4-7

L2,3,4-6 L2,3,4-3

L2,3,4-2

L2,3,4-4

L2,3,4-5

L2,3,4-1

"P"

TO P4B-40

FROM PANELBOARD "P"

TO LOADCENTER "L1","L2"&"L3"

TO P-5

1/10HP (MECH ITEM)

EXHAUST FAN, 1PH,115V,

ADDITIONAL LEGEND (THIS SHEET ONLY)

GROUNDING TYPE AND COVER FACE PLATE FOR CATV 208VAC SERVICE

2P-3W-20A-250V, GROUNDING TYPE

(LOCATED IN CATV DIST. CABINET)

D

REPLACE EXIST RECEPTACLE20

W/NEW SINGLE RECPTACLE, 2P-3W-20A-125V,

GROUNDING TYPE, PLUG AND COVER FACE

REPLACE EXIST SINGLE RECEPTACLE

W/NEW SINGLE RECPTACLE,

PLATE FOR DRYER, 1PH-120/208V-5KW

FOR ELECTRIC WATER COOLER, 1PH-115V-1/5HP

GROUNDING TYPE AND COVER FACE PLATE

REPLACE EXIST RECEPTACLE

EWC

W/NEW SINGLE RECPTACLE, 2P-3W-20A-125V,

(TYPICAL)

(TYPICAL)

REPLACE NEW SINGLE RECEPTACLE,

FOR CATV 120VAC SERVICE

2P-3W-20A-125V, SURGE SUPPRESSION TYPE

(LOCATED IN CATV DIST. CABINET)

REPLACE NEW DUPLEX RECEPTACLE,

TV

3P-4W-30A-125/250V, TV

S MANUAL MOTOR STARTER

1PH-115V-1HP (MAX.)

(2P-100AF-20AT, 10000AIC)

W/O.L RELAYS, 3-POSITION SEL.

SWITCH (A-O-H) & PILOT LAMPS, NEMA 1 ENCL.

D D

D D

2#12 & 1#12(G) IN 16C

PROVIDE NEW WIRING

(TYPICAL)

SAFETY SWITCH, 2PST-240V-30A

A

B

1PH, 120V, 1/2HP

AIR HANDLING UNIT,

LOADCENTER "L2","L3","L4"

TO PANELBOARD "P" FROM

M

MAG.MOTOR STARTER, 2P-120V,

NEMA SIZE "00",

ER

GROUNDING TYPE, PLUG AND COVER FACE

REPLACE EXIST SINGLE RECEPTACLE

W/NEW SINGLE RECPTACLE,

(TYPICAL)

3P-4W-50A-125/250V, PLATE FOR ELECTRIC RANGE

RECONNECT TO EXIST

WIRING(TYPICAL)

FOR WASHER, REF., FAN COIL UNIT, MICROWAVE

M

1PH,115V,1.7FLA (MECH ITEM)

CONDENSATE DRAIN LIFT PUMP,

B

SAFETY SWITCH, 2PST-240V-30A

A

NON-FUSIBLE. NEMA 3R ENCL

NON-FUSIBLE. NEMA 1 ENCL

TO P-6

RECONNECT TO EXIST

WIRING(TYPICAL)

MDP-10

FLOOR ONLY (MECH ITEM)(TYPICAL)

ROOF FAN, 1PH, 120V, 1/15HP @ 4TH

115V, 1.5KW (MECH ITEM)

SPLIT AIR CONDITIONING UNIT, 1PH,

J

1PH,115V, 1/12HP (MECH ITEM)

EXHAUST FAN FOR TOILET,

EF5

EF4EF4EF4EF4EF4EF4EF4

EF3

EF3

EF1

EF1

"MDP" FOR PANELBOARD "P"

WITH NEW CIRCUIT BREAKER (3P-225AF-225AT) IN

EXIST MAIN DIST. PANELBOARD "MDP"/ REPLACE

"P2A", "P2B", "P3A", "P3B","P4A" & "P4B")

WITH NEW (TYPICAL FOR PANELBOARD "P1A", "P1B",

REPLACE EXIST FRONT COVER OF PANELBOARD

1ST, 2ND, 3RD & 4TH FLOOR POWER PLAN

MODULE PLAN ON E-9

SEE TYPICAL BEDROOM ELECTRICAL

70mm dia C.

4-3/0 & 1#4(G) IN

IN 36mm C.

3#4& 1#8(G)

IN 22mm C.

3#10& 1#10(G)

W,R,F,M,RH

OVEN, RANGE HOOD

W W

T

T

ALARM SWITCH

FLOOR MOUNTED LATCHING

NEW JUNCTION BOX FOR

( 15 cm ABOVE DOOR )

BALANCED MAGNETIC SWITCH

NEW JUNCTION BOX FOR

J

J

J

J

FOR CONTROL UNIT

NEW JUNCTION BOX

SIGNAL PROCESSOR

ULTRASONIC MOTION SENSOR

NEW JUNCTION BOX FOR

J

SENSOR TRANSCEIVER

ULTRASONIC MOTION

NEW JUNCTION BOX FOR

W/PULLING WIRE (TYPICAL)

EMPTY COPNDUIT 22mm C

TO PNLBD "P1B"

IN 16mmC

1-4PAIR CAT6

NOTE

1.

CONDITION.

FOR J-SIID SYSTEM WIRING TO MEET SITE

RELOCATE WIRING AND JUNCTION BOXES

CONTRACTOR IS RESPONSIBLE TO

OA(��)

EA(��)

RA(��)

SA(��)

F

FCU

F

FCU

F

FCU

F

FCU

F

FCUFCU

F

FCU

F

F

FCU

T

T T

T

T T TT

C

C

C

C

C

C

J

J

J

SPARE OF "P2B, P3B,P4B"OR "L2","L3","L4"

SPARE OF "P1B OR "L1"

J

OFFICE

OFFICE

FF

TT

FF

C

C

C

C

J

L2,4-8 J

L1,3-8

FLOOR)

(TYP OF 4EA@2ND&4TH

HEATER,1PH, 208V, 2KW

ELEC. CABINET UNIT

PLATE WITH NEW (TYPICAL)

REPLACE EXIST RECEPTACLE AND COVER

(TYPICAL)

THERMOSTAT (MECH ITEM)

(TYPICAL OF 8EA)

208V, 1PH,360W(MECH ITEM)

ENERGY RECOVERY UNIT,

"L2","L3","L4"

SPARE OF "P2B, P3B, P4B OR

TO SPARE OF "L1"

L1-1

NEW TVSS

SURGE SUPPRESSOR)

TVSS(TRANSIENT VOLTAGE

REPAIR BLDG S-2308

CAMP CASEYTAK, YS

58479

T

C

T

C

C

F

FCU

C

C

F

C

C

C C C

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

ELECTRICAL

E-8

1 20 2#12&1#12(G)

13115LOAD CENTER, "L1"

LOAD CENTER, "L2"

LOAD CENTER, "L3"

LOAD CENTER, "L4"

5 6

3PHASE ,4WIRE, 120/208V,

MTD TYPE, NEMA 1 ENCL.

100 100002

18630

REMARK

GNA CB

AICAF

SIZE

ATC PBA

PHASE LOAD

CIRCUIT BREAKER

CONNECTION

DIAGRAM

S/N

GND

CKT

NO.

LOAD DESCRIPTION

TOTAL

LOAD

186302520062460TOTAL LOAD

13 15

1000 1000

SPARE 1000 1000

3 30

SPACE

SPACE

SPACE

PANELBOARD "P" LOAD SCHEDULE 60HZ, SN & GND, FLUSH

6300 6815

13115 6300 6815

13115 6300 6815

13115 6300 6815

UNIT

SPLIT AIR CONDITIONING

PUMP

CONDENSATE DRAIN LIFT

EQUIPMENT RACK(LAN)

TELEPHONE TERMINAL BOARD

FMCP

FMBP#1

FMBP#2

FMBP#3

TVSS

1000 1000

2#12&1#12(G)

SPARE

SPACE

SPACE

SPACESPACE

SPACE

SPACE

SPACE

SPACE

SPACE

SPACE

TOTAL DEMAND LOAD ; 50522 (VA)

4-3/0 & 1#4(G) IN

70mm dia C.

3#4&1#8(G)

"L3 &"L4" LOAD SCHEDULE

PANELBOARD "P" & LOAD CENTER "L1","L2",

SPACE

4#10&1#10(G)

MAIN 3P-225AF-225A MAIN

W/LOCK

SPACE SPACE

TOTAL LOAD 13115

LOAD

TOTAL

LOAD DESCRIPTION

NO.

CKT

GND

S/N

DIAGRAM

CONNECTION

CIRCUIT BREAKER

PHASE LOAD

A B P AT

SIZE

AF AIC

BA N G

REMARK

360 360

1 10000100 2#12&1#12(G)20

EXH FAN-5, 83W

MTD TYPE, NEMA 1 ENCL.

60HZ, SN & GND, FLUSH

1PHASE ,3WIRE, 120/240V,

1 20

503235

3#10&1#10(G)

RCPTS 180VAx2

COMBINATION WASHER/DRYER

COMBINATION WASHER/DRYER

CATV RCPTS 180VA

CATV RCPTS 360VA 360

180 180

360 360

500 500SPARE

SPARE

SPARE

2#12&1#12(G)

6300 6815

3#4& 1#8(G) IN 36mm C.

TOTAL DEMAND LOAD ; 10784 (VA)

MAIN LUG 100A

ELECTRIC UNIT HEATER 1000 2#12&1#12(G)

1000 1000

12 13

SPARE

SPARE

1000 1000

500 500

TOTAL LOAD 13115

LOAD

TOTAL

LOAD DESCRIPTION

NO.

CKT

GND

S/N

DIAGRAM

CONNECTION

CIRCUIT BREAKER

PHASE LOAD

A B P AT

SIZE

AF AIC

BA N G

REMARK

360 360

1 10000100 2#12&1#12(G)20

EXH FAN-5, 83W

MTD TYPE, NEMA 1 ENCL.

60HZ, SN & GND, FLUSH

1PHASE ,3WIRE, 120/240V,

ELEC RANGE, 6470W

1 20

3#8&1#10(G)

SHUNT-TRIP

3#10&1#10(G)

HOOD FAN 2.0A & REF, 1/4HP

LOADCENTER "L2-L4" LOAD SCHEDULE

RCPTS 180VAx2

COMBINATION WASHER/DRYER

COMBINATION WASHER/DRYER

CATV RCPTS 180VA

CATV RCPTS 360VA 360

180 180

360 360

500 500SPARE

SPARE

SPARE

2#12&1#12(G)

6300 6815

3#4& 1#8(G) IN 36mm C.

TOTAL DEMAND LOAD ; 10784 (VA)

MAIN LUG 100A

ELECTRIC UNIT HEATER 1000 2#12&1#12(G)

1000 1000

12 13

SPARE

SPARE

1000 1000

500 500

LOADCENTER "L1" LOAD SCHEDULE

SPARE

SPARE -

REPAIR BLDG S-2308

UH

J

MJS

MJ M J

MJ

J

J

EFJ

M D

P

ADDITIONAL LEGEND (THIS SHEET ONLY)

PILOT LAMPS, NEMA 1 ENCL.

W/O.L RELAYS, 3-POSITION SEL. SW (A-O-H) &

MAGNETIC MOTOR STARTER, 2P-120V, NEMA SIZE "00",A

CONTROL TRANSFORMER & PILOT LAMPS,

W/O.L RELAYS, 3-POSITION SEL. SW (A-O-H),

MAGNETIC MOTOR STARTER, 3P-208V, NEMA SIZE "1",

NEMA 1 ENCL.

C

(UNDER MECH. ITEM)

3PH-200V-5HP

H.W.CIRC.PUMP

(UNDER MECH. ITEM)

3PH-200V-7 /2HP

CH.W.CIRC.PUMP

(UNDER MECH. ITEM)

1PH-115V-1/20HP

UNIT HEATER

M-19

(UNDER MECH. ITEM)

1PH-115V-1/4HP

D.H.W.CIRC.PUMP

(UNDER MECH. ITEM)

A

DC

CONTROL TRANSFORMER & PILOT LAMPS,

W/O.L RELAYS, 3-POSITION SEL. SW (A-O-H),

MAGNETIC MOTOR STARTER, 3P-208V, NEMA SIZE "2",

NEMA 1 ENCL.

D

B

3#8 & 1#8(G) IN 27C

3#12 & 1#12(G) IN 21C

(TYPICAL)

(TYPICAL)

CONTROL TRANSFORMER & PILOT LAMPS,

W/O.L RELAYS, 3-POSITION SEL. SW (A-O-H),

NEMA 1 ENCL.

B

(TYPICAL)

1P-115V-1HP (MAX.),

MANUAL MOTOR STARTER,S

NEMA 1 ENCL.

3-POSITION SEL. SW (H-O-A), W/PILOT LAMP (GREEN),

MANUAL MOTOR STARTER, 1P-115V-1HP (MAX.),

S

1/50SCALE:

3#10 & 1#10(G) IN 21C

A

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

ELECTRICAL

E-9

1/50SCALE:

D.H.W RECIR. PUMP

3PH-200V-1-1/2HP

EXIST H.W. BOILER

EXIST D.H.W. HEATER

TYPICAL BEDROOM ELECTRICAL MODULE PLAN

MDP-8

MDP-19

MDP-6

MDP-12

MDP-3

MDP-8

MECH. RM PARTIAL POWER PLAN

PLAN & MECH. RM PARTIAL POWER PLAN

TYPICAL BEDROOM ELECTRICAL MODULE

MDP-5

MDP-7

MCP

M C

B

EXIST MAIN DIST. PANELBOARD "NMDP"

EXIST PANELBOARD "MDP"

MAG. MOTOR STARTER, 3P-208V, NEMA SIZE "0",

W

P

WHM

EXIST WATT HOUR METER

EXIST REMOTE CHILLER CONTROL SYSTEM

NEW SAFETY SWITCH 3PST-600A, 240VAC

NON-FUSIBLE, NEMA 3R ENCL.

EXIST CT'S

CT'SNMDP

EXIST MAIN CIRCUIT BREAKER "MCB"

S

T

T THERMOSTAT (MECH ITEM)

REPAIR BLDG S-2308

CAMP CASEYTAK, YS

58479

MCP

PANEL FOR GOVERNMENT APPROVAL PRIOR TO CONSTRUCTION.

WIRING DIAGRAN INCLUDING OARC(MECH ITEM) OF MASTER CONTROL

MASTER CONTROL PANEL, CONTRACTOR SHALL SUBMIT SPEC. AND

BED ROOM A BED ROOM B

F

SB

L L

3S

S

S S

S

3S

3S

S

SJ

L

L

L L L

L

J

J J a

J b b b b b b a a a a a

SB

FCUFCU

PLATE W/NEW (TYPICAL)

TV

TV

CATV OUTLET W/"0"dB LOSS FACE

PLATE AND F-81 BARREL TYPE

CONNECTOR (M.H: +300mm AFF)

(TYPICAL)

REPLACE EXIST WALL MTD TYPE LIGHTING

(TYPICAL)

FIXTURE W/ NEW LED LIGHT, TYP "NS-8"

REPLACE EXIST GFCI RECEPTACLE & COVER

PLATE W/NEW (TYPICAL)

L L

REPLACW WITH NEW WALL MTD TYPE

REPLACE EXIST CEILING RECESSED MTD TYPE LIGHTING

(TYPICAL)

FIXTURE W/ NEW LED LIGHT, TYP "NS-4b"

REPLACE EXIST CEILING RECESSED MTD TYPE LIGHTING

(TYPICAL)

FIXTURE W/ NEW LED LIGHT, TYP "NS-4a"

FAN COIL UNIT/1PH, 115V, 1/30HP,

(TYPICAL)

& THERMOSTAT (UNDER MECH. ITEM)

JUCTION BOX

W/NEW (TYPICAL)

REPLACE EXIST 3-WAY LIGHT SWITCH & COVER PLATE

REPLACE EXIST TOGGLE SWITCH & COVER PALTE

W/NEW (TYPICAL)

(TYPICAL)

FIXTURE W/ NEW LED LIGHT, TYP "NS-7"

REPLACE EXIST CEILING SURFACE MTD TYPE LIGHTING

REPLACE SINGLE RECEPTACLE & COVER

REPLACE EXIST DUPLEX RECEPTACLE & COVER

PLATE W/NEW FOR FAN COIL UNIT (TYPICAL)

REPLACE EXIST SINGLE MODULAR JACK AND

& COVER PALTE W/NEW (TYPICAL)

REPLACE EXIST SMOKE DETECTOR WITH

W/ SOUNDER BASE (TYPICAL)

NEW ADDRESSABLE SMOKE DETECTOR

EXHAUST FAN FOR BATH RM, 1PH, 115V-45W

(UNDER MECH. ITEM)

VISUAL STROBE(FA+MNS) (TYPICAL)

REPLACE EXIST WALL MOUNTED SPEAKER,

T T

THERMOSTAT(MECH ITEM)

TV TV

BED ROOM A BED ROOM B

F

SB

L L

3S

S

S S

S

3S

3S

S

SJ

L

L

L L L

L

J

J J a

J b b b b b b a a a a a

SB

FCUFCU

TV

TV

L L

T T

TV TV

S b 3 Sb3

3S3S

MODULE-A MODULE-B

REPLACE SINGLE RECEPTACLE & COVER

PLATE W/NEW FOR FAN COIL UNIT (TYPICAL)

W/NEW (TYPICAL)

REPLACE EXIST 3-WAY LIGHT SWITCH & COVER PLATE

PLATE W/NEW (TYPICAL)

RECEPTACLE & COVER

REPLACE EXIST DUPLEX

REPLACW WITH NEW WALL

MTD TYPE CATV OUTLET W/

"0"dB LOSS FACE PLATE

AND F-81 BARREL TYPE

CONNECTOR (M.H: +300mm

AFF) (TYPICAL)

REPLACE EXIST SINGLE

PALTE W/NEW (TYPICAL)

MODULAR JACK AND COVER

JUCTION BOX

REPLACE EXIST SMOKE DETECTOR WITH

W/ SOUNDER BASE (TYPICAL)

NEW ADDRESSABLE SMOKE DETECTOR

VISUAL STROBE(FA+MNS) (TYPICAL)

REPLACE EXIST WALL MOUNTED SPEAKER,

THERMOSTAT(MECH ITEM)

NOTE

CONTRACTUAL WORK TO MEET SITE CONDITION.

CONTRACTOR SHALL VERIFY EXIST TYPE OF MODULES AND PROVIDE 1.

F FF F

J JJJ

JJ

WITH NEW IN THE WALL OR ABOVE CEILING (TYPICAL)

FOR FANCOIL UNIT POWER AND THERMOSTAT

REPLACE EXISTING CONDUIT AND JUNCTION BOX

WITH NEW IN THE WALL OR ABOVE CEILING (TYPICAL)

FOR FANCOIL UNIT POWER AND THERMOSTAT

REPLACE EXISTING CONDUIT AND JUNCTION BOX

J J

EWC

E W

C

UP

UP

S/S

STORAGE

VEST

ROOM

ADMIN OFFICE

105 R.O

106B

T.O

106A

WAIT AREA

STORAGE

106C

STAIR-2

119B

CO

XO

COMM

COMMO SHOP

113A 113B

JAN

MULTI-PURPOSE RM

STORAGE

MECH ROOM

C.Q

VEST

STAIR-1

119A

LAUNDRY

JAN

CORRIDOR

105A

COMMUNITY

D

W

W

D

W/D

W/D

OFFICE

NBC ROOM

ARMS ROOM

COMM RM

LATRINE

MALE

LATRINE

FEMALE

E W

C

FECFEC

UPDN

UPDN

REF

STAIR-1

218A

219CORRIDOR

BED ROOM

201A

BED ROOM

201B

BED ROOM

202A

BED ROOM

202B

BED ROOM

203A

BED ROOM

203B

BED ROOM

204A

BED ROOM

204B

BED ROOM

205A

BED ROOM

205B

BED ROOM

206A

BED ROOM

206B

BED ROOM

207A

BED ROOM

207B

BED ROOM

208A

BED ROOM

208B

STAIR-2

218B

LAUNDRY

BED ROOM

214A

BED ROOM

214B

BED ROOM

213A

BED ROOM

213B

BED ROOM

212A

BED ROOM

212B

BED ROOM

211A

BED ROOM

211B

BED ROOM

210A

BED ROOM

210B

BED ROOM

209A

BED ROOM

209B

JAN

S/S

D

W

W

318A

301A 301B 302A 302B 303A 303B 304A 304B 305A 305B 306A 306B 307A 307B 308A 308B

314A 314B 313A 313B 312A 312B 311A 311B 310A 310B 309A 309B

318B

401A 401B 402A 402B 403A 403B 404A 404B 405A 405B 406A 406B 407A 407B 408A 408B

414A 414B 413A 413B 412A 412B 411A 411B 410A 410B 409A 409B

D

W/D

W/D

418B

418A

319 419

DAY RM

SCALE: 1/100

A

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

ELECTRICAL

E-10

LAN

TTB

DUAL MODULAR JACK

CAT-6, 8-PIN (RJ45 TYPE) OUTLET

FOR "TEL/DATA" (TYPICAL)

W/COVER PLATE & LUG FOR TEL

CAT-6, 8-PIN (RJ45 TYPE) OUTLET

(TYPICAL)

SOLID BOTTOM TYPE CABLE TRAY

ABOVE THE CEILING

(STEEL, 300mmW x 150mm H x LENGTH

AS REQ'D) W/O COVER

WITH SUPPORTER EVERY 3000mm

TO BE TERMINATED AT PATCH

TEL/DATA WIRE IN 27C

2-4PAIR, #24AWG, CAT-6

PANEL VIA CABLE TRAY

(TYPICAL)

REPLACE W/ NEW SINGLE MODULAR JACK

(TYPICAL)

TO BE TERMINATED AT MAIN

REPLACE EXISTING SINGLE MODULAR JACK

AND COVER PLATE WITH NEW

P-8

1ST FLOOR LAN/TEL PLAN

2ND, 3RD & 4TH FLOOR TEL PLAN

1ST, 2ND, 3RD & 4TH FLOOR LAN/TEL PLAN

T T C

W/FABRIC INNER DUCT IN 54C

1-50PAIR, #24AWG, TEL WIRE

OFFICE

OFFICE

DIAGRAM ON E-10)

AT MECH RM (SEE TEL SYSTEM

110 TERMINAL BLOCK IN TTC

DIAGRAM ON E-10)

RACK(SEE TEL SYSTEM

BOARD, EQUIPMENT

TELEPHONE TERMINAL

P EXIST PULL BOX

CABLE IN NEW 103 diaC.

EXIST 1-12CORE FIBER OPTIC

TO NEW PATCH PANEL IN EQUIPMENT RACK

TERMINATE EXIST 1-12 FIBER OPTIC CABLE

CORRIDOR

REPAIR BLDG S-2308

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

ELECTRICAL

E-11

(TYPICAL)

CABLE SUPPORT

EXOTHERMIC WELDING, LISTED COMPRESSION TWO-

1. THE CONNECTIONS OF THE BONDING CONDUCTOR FOR

TELECOMMUNITIONS TO THE TMGB SHALL UTILIZE

HOLE LUGS, SUITABLE AND EQUIVALENT TWO-HOLE

FINISHED FLOOR AND SHALL BE PLACED WITHIN 75mm

3. ENTRANCE CONDUITS SHALL EXTEND 150mm ABOVE

NOTES:

CROSS CONNECTING

PATCH CORD AS REQ'D

(1-100PAIR) (TYPICAL)

110 TYPE TERMINAL BLOCK

G

G

NEW TELEPHONE TERMINAL BOARD (TTB)

G

GROUNDING BUSBAR (TMGB)

(100mm(W) x6.4mm(D) x450mmLG)

GROUND WIRE

NEW TELECOMMUNICATION MAIN

CONDUCTOR #6AWG

NOT TO SCALE

RACK TYPE 1-48 PORT

PATCH PANEL "DATA"

STAMP FACING OUT" TO ENSURE THAT THEY CAN BE

"PLYWOOD WILL BE INSTALLED WITH FIRE RATED

4. TEST RESULTS WILL BE PROVIDED IAW THE MOST RECENT

REVISION OF THE ANSI/TIA/EIA-568.

5. LABEL ALL DROPS IAW TIA/EIA-606-A.

6. LABEL ALL GROUNDS IAW I3A.

LUGS ARE PREFERRED.

FIELD VERIFIED.

OF A WALL.

NEW GROUND BONDING

RACK TYPE 1-48 PORT

(TYPICAL)

RACK TYPE 1-48 PORT

PATCH PANEL TEL"

PATCH PANEL "DATA"

6 METER (20FEET) SLACK

W/"SC" TYPE CONNECTIONS

HUB (N.I.C)

MODE FIBER OPTIC CABLE

(TYPICAL)

SEE NOTE 2 BELOW.

NEW 2WAY OF 103dia CONDUIT

52-4PAIR, CAT-6, #24AWG FOR TEL

1WAY: 52-4PAIR, CAT-6, #24AWG FOR DATA &

1WAY: SPARE W/PULL WIRE

(TYPICAL)

END BLANKS

D

T

SURGE SUPPRESSION TYPE

QUAD-PLEX RECEPTACLE

2P-3W-125V-20A

GROUNDING TYPE WITH

DEDICATED CIRCUIT

D

T

D

T

D

T

D

T

D

T

D

T

105123123 104 105 105 105

ROOM NUMBER

WHICH DEVICE IS LOCATED

(TYPICAL)

1-4PAIR, #24AWG, CAT-6

FOR TEL IN 27C

CONN TO NEW PATCH PANEL

VIA CABLE TRAY

SOLID BOTTOM TYPE CABLE TRAY

ABOVE THE CEILING

(STEEL, 300mmW x 150mm H x LENGTH

AS REQ'D) W/O COVER

WITH SUPPORTER EVERY 3000mm

TO BE TERMINATED AT PATCH

TEL/DATA WIRE IN 27C

2-4PAIR, #24AWG, CAT-6

PANEL VIA CABLE TRAY

(TYPICAL)

1500mmx2400mmx19mmTHK PLYWOODx1EA

D

T

106B

D

T

106B

D

T

D

T

D

T

D

T

D

T

D

T

114 110

D

T

D

T

109 107 107 107 107

DUAL MODULAR JACK

CAT-6, 8-PIN (RJ45 TYPE) OUTLET

FOR "TEL/DATA" (TYPICAL)

CONDUIT COUPLING

(TYPICAL)

NEW CONDUIT STUB-UP W/SEALING

(150mm AFF) (TYPICAL)

G

COMM RM 105A

2. PLYWOOD SHALL BE FIRE-RATED.

84.58"(H)"x24"(W)x34.67"(D)

(100mm(W) x6.4mm(D) x300mmLG)

NEW TELECOMMUNICATION

GROUNDING BUSBAR (TGB)

D

T

D

T

106A

D

T

D

T

D

T

D

T

D

T

D

T

D

T

105 105

D

T

106B

D

T

106A

D

T

106A

109 109

D

T

D

T

D

T

108 108 108 108

G

D

T

D

T

(TYPE NEMA 5-20R)

POWER RECEPTACLES

P-7

P-8

(TYPICAL)

TELECOMMUNICATION SYSTEM DIAGRAM

TELECOMMUNICATION SYSTEM DIAGRAM

7. CONTRACTOR SHALL SUBMIT SHOP DRAWING FOR DETAIL

EQUIPMENT RACK AND TELEPHONE TERMINAL BOARD FOR

GOVENRMENT APPROVAL PRIOR TO CONSTRUCTION.

RACK TYPE 1-48 PORT

RACK TYPE 1-12 PORT

D

T

D

T

102101

D

T

D

T

D

T

102102

D

T

D

T

D

T

D

T

D

T

D

T

D

T

D

T

D

T

PATCH PANEL "TEL"

WIRING TO REMAIN

EXISTING TERMINAL BLOCKS AND

MECH RM 123

CABINET

EXIST TELEPHONE TERMINAL

CONN TO NEW MAIN PANEL

GROUNDING SYSTEM

1#6 "BC" IN 27C

PTB

G

G

G

G

SEE SITE PLAN

CONDUIT COUPLING

(TYPICAL)

NEW CONDUIT STUB-UP W/SEALING

(150mm AFF) (TYPICAL)

PROTECTED TERMINAL BLOCK

(ENTRANCE) (1-100PAIR)

WALL MOUNTED TYPE

1-100PAIR, #24AWG TEL CABLE

IN MECH RM (123)

TEMINATE TO MAIN TERMINAL BLOCK AT TTC

1-50PAIR, #24AWG TEL CABLE, 54mm C.

REMOVE EXIST TEL LINE

1-50PAIR, #24AWG TEL CABLE, 54mm C. FROM TTB AT COMM RM(105A)

EXIST TEL LINE

EXIST MAIN 110 TERMINAL BLOCK

110 TEMINAL BLOCK IN EXIST TTC

NEW 1-50 PAIR AWG#24/ CONNECT TO MAIN

EQUIPMENT RACK

D

T

D

T

101101

D

T

D

T

NEW 1-12 STRAND SINGLE

REPAIR BLDG S-2308

EWC

W

C

UP

UP

S/S

STORAGE

VEST

ROOM

ADMIN OFFICE

R.O

106B

T.O

106A

WAIT AREA

STORAGE

106C

STAIR-2

119B

CO

XO

COMM

109110111

COMMO SHOP

113A 113B

JAN

MULTI-PURPOSE RM

STORAGE

MECH ROOM

C.Q

VEST

STAIR-1

119A

LAUNDRY

JAN

CORRIDOR

105A

COMMUNITY

D

W

W

D

W/D

W/D

OFFICE

NBC ROOMARMS ROOM

COMM RM

LATRINE

MALE LATRINE

FEMALE

UPDN

UPDN

STAIR-1

218A

219CORRIDOR

BED ROOM

201A

BED ROOM

201B

BED ROOM

202A

BED ROOM

202B

BED ROOM

203A

BED ROOM

203B

BED ROOM

204A

BED ROOM

204B

BED ROOM

205A

BED ROOM

205B

BED ROOM

206A

BED ROOM

206B

BED ROOM

207A

BED ROOM

207B

BED ROOM

208A

BED ROOM

208B

STAIR-2

218B

LAUNDRY

BED ROOM

214A

BED ROOM

214B

BED ROOM

213A

BED ROOM

213B

BED ROOM

212A

BED ROOM

212B

BED ROOM

211A

BED ROOM

211B

BED ROOM

210A

BED ROOM

210B

BED ROOM

209A

BED ROOM

209B

JAN

S/S

D

W

W

318A

301A 301B 302A 302B 303A 303B 304A 304B 305A 305B 306A 306B 307A 307B 308A 308B

314A 314B 313A 313B 312A 312B 311A 311B 310A 310B 309A 309B

318B

401A 401B 402A 402B 403A 403B 404A 404B 405A 405B 406A 406B 407A 407B 408A 408B

414A 414B 413A 413B 412A 412B 411A 411B 410A 410B 409A 409B

D

W/D

W/D

418B

418A

319 419

DAY RM

A

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

ELECTRICAL

E-12

TV TV TV

TV

TV

TV

TV

T V

T V

T V

T V

T V

C T

C

TV TV

SCALE 1/100

1-RG 11/U IN 21C

COAXIAL CABLE

(TYPICAL)

W/8-WAY TAP-OFF AND

PULL BOX (300x300x200D)

LOCKING DEVICE ABOVE CEILING

CATV OUTLET W/"0"dB LOSS FACE

PLATE AND F-81 BARREL TYPE

CONNECTOR (M.H: +300mm AFF)

(TYPICAL)

1-RG 6/U IN 16C

COAXIAL CABLE

(TYPICAL)

W/6-WAY TAP-OFF AND

PULL BOX (300x300x200D)

LOCKING DEVICE ABOVE CEILINGSEE DIAGRAM

PROVIDE NEW CATV DIST. CABINET (CTC-1)

NEW WALL MTD TYPE

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV TV

T V

T V

T V

T V

T V

T V

T V

T V

T V

T V

T V

T V

T V

T V

T V

T V

T V

T V

T V

T V

T V

T V

T V

T V

T V

T V

T V

T V

T V

T V

T V

T V

T V

T V

T V

T V

T V

T V

T V

T V

T V

T V

T V

T V

T V

T V

C T

C

6TV 4

8 8

T V

T V

T V

T V

T V

T V

T V

T V

T V

T V

T V

P

T V

TV

TV TV

TV

TV

TV

W/4-WAY TAP-OFF AND

PULL BOX (300x300x200D)

LOCKING DEVICE ABOVE CEILING

W/6-WAY TAP-OFF AND

PULL BOX (300x300x200D)

LOCKING DEVICE ABOVE CEILING

W/8-WAY TAP-OFF AND

PULL BOX (300x300x200D)

LOCKING DEVICE ABOVE CEILING

(TYPICAL OF 6)

CATV OUTLET W/"0"dB LOSS FACE

NEW WALL MTD TYPE

PLATE AND F-81 BARREL TYPE

CONNECTOR (M.H: +300mm AFF)

(TYPICAL)

1-RG 6/U IN 16C

COAXIAL CABLE

(TYPICAL)

SCALE 1/100

1-RG 11/U IN 21C

COAXIAL CABLE

(TYPICAL)

27C EMPTY CONDUIT

TO " " IN RM. 215CTC

W/PULL WIRE

TO REMAIN

EXIST ENTRANCE CAP & SEC.RACK

T V

TV

REPLACE W/ NEW CATV DIST.

CABINET (CTC-2) SEE DIAGRAM

1ST FL CATV PLAN

2ND ,3RD AND 4TH FL CATV PLAN

1ST, 2ND ,3RD AND 4TH FLOOR CATV PLAN

OFFICE

OFFICE

REPAIR BLDG S-2308

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

ELECTRICAL

E-13

3F

4F

2F

1F

AMP

ROOF

2AMP

AMP

AMP

TV

106B

TV

TV TV

TV

TV

TV TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV TV

TV

211 210

TV

TV

TV

TV

TV

TV TV

TV

TV

TV

TV

TV

TV

TV TV

TV

202 203

TV

TV

TV

TV

TV

TV TV

TV

204 205

TV

TV

TV

TV

TV

TV TV

TV

206 207

TV

TV

TV

TV

TV

TV TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV TV

TV

311 310

TV

TV

TV

TV

TV

TV TV

TV

TV

TV

TV

TV

TV

TV TV

TV

302 303

TV

TV

TV

TV

TV

TV TV

TV

304 305

TV

TV

TV

TV

TV

TV TV

TV

306 307

TV

TV

TV

TV

TV

TV TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV

TV TV

TV

411 410

TV

TV

TV

TV

TV

TV TV

TV

TV

TV

TV

TV

TV

TV TV

TV

402 403

TV

TV

TV

TV

TV

TV TV

TV

404 405

TV

TV

TV

TV

TV

TV TV

TV

406 407

TV

TV

TV

TV

TV

TV TV

TV

G

G G

G G

RG 6/U IN 16C

COAXIAL CABLE

(TYPICAL)

DEVICE IS LOCATED

ROOM NUMBER WHICH

(TYPICAL)

CATV OUTLET W/"0"dB LOSS FACE

NEW WALL MTD TYPE

PLATE AND F-81 BARREL TYPE

CONNECTOR (M.H: +300mm AFF)

(TYPICAL)

SURGE SUPPRESSION TYPE

DUPLEX RECEPTACLE

(2P-3W-15A-125V)

FOR AMPLIFIER

(TYPICAL)

(TYPICAL)

1#6 "BC" IN 21C

(TYPICAL)

GROUNDING TERMINAL BLOCK

W/8-WAY TAP-OFF AND

PULL BOX (300x300x200D)

LOCKING DEVICE ABOVE CEILING

(TYPICAL)

W/4-WAY TAP-OFF AND

PULL BOX (300x300x200D)

LOCKING DEVICE ABOVE CEILING

(TYPICAL)

W/6-WAY TAP-OFF AND

PULL BOX (300x300x200D)

LOCKING DEVICE ABOVE CEILING

(TYPICAL)

2#12 & 1#12(G) IN 16C

RG 11/U IN 21C

COAXIAL CABLE

(TYPICAL)

GROUND ROD, COPPER CLAD STEEL,

19mm dia x 3000mm LONG

WITH WELDING CONNECTION AND

CONN. TO BLDG ELECTRODE

GROUNDING SYSTEM

#6 "BC"

EXIST ENTRANCE CAP & SEC. RACK

TO REMAIN

PROVIDE NEW 27C EMPTY CONDUIT

W/PULL WIRE

TV

TV

TV

TV TV

TV

TV

TV

TV TV

TV

2#12 & 1#12(G) IN 16C

2#12 & 1#12(G) IN 16C

1PH-208V

2#12 & 1#12(G) IN 16C

CATV DISTRIBUTION CABINET (CTC-2)

(762mm(W)x610mm(H)x254mm(D), BACKBOARD LINE EXTENDER

WITH 610x610 W/19THK PLYWOOD

AMPLIFIERS, 4-WAY SPLITTER-1EA,

RECEPTACLE, AIR VENTS AND

LOCKING DEVICE NEMA 1 ENCL

2-WAY SPLITTER-1EA,

CATV DISTRIBUTION CABINET (CTC-1)

(762mm(W)x610mm(H)x254mm(D), BACKBOARD LINE EXTENDER

WITH 610x610 W/19THK PLYWOOD

AMPLIFIERS, 2-WAY SPLITTER-1EA,

RECEPTACLE, AIR VENTS AND

LOCKING DEVICE NEMA 1 ENCL

CATV DISTRIBUTION CABINET (CTC-3)

(762mm(W)x610mm(H)x254mm(D), BACKBOARD LINE EXTENDER

WITH 610x610 W/19THK PLYWOOD

AMPLIFIERS, 2-WAY SPLITTER-1EA,

RECEPTACLE, AIR VENTS AND

LOCKING DEVICE NEMA 1 ENCL

CATV DISTRIBUTION CABINET (CTC-4)

(762mm(W)x610mm(H)x254mm(D), BACKBOARD LINE EXTENDER

WITH 610x610 W/19THK PLYWOOD

AMPLIFIERS, 2-WAY SPLITTER-1EA,

RECEPTACLE, AIR VENTS AND

LOCKING DEVICE NEMA 1 ENCL

CATV SYSTEM DIAGRAM

NOT TO SCALE

TO LOADCENTER "L1", CKT NO. "L1-5"

1PH-208V

2#12 & 1#12(G) IN 16C

TO LOADCENTER "L1", CKT NO. "L1-4"

TO LOADCENTER "L2", CKT NO. "L2-4"

TO LOADCENTER "L2", CKT

NO. "L2-5" 1PH-208V

TO LOADCENTER "L3", CKT NO. "L3-4"

TO LOADCENTER "L3", CKT

NO. "L3-5" 1PH-208V

TO LOADCENTER "L4", CKT

NO. "L4-5" 1PH-208V

TO LOADCENTER "L4", CKT NO. "L4-4"

CATV SYSTEM DIAGRAM

REPAIR BLDG S-2308

EWC

FEC

UP

UP

S/S

STORAGE

VEST

121 ROOM

ADMIN OFFICE

R.O

106B

T.O

106A

WAIT AREA

STORAGE

106C

STAIR-2

119B

CO

XO

COMM

109110111

COMMO SHOP

113A 113B

JAN

MULTI-PURPOSE RM

STORAGE

MECH ROOM

C.Q

VEST

STAIR-1

119A

LAUNDRY

JAN

CORRIDOR

105A

COMMUNITY

D

W

W

D

W/D

W/D

OFFICE

NBC ROOMARMS ROOM

COMM RM

LATRINE

MALE

LATRINE

FEMALE

E W

C

FECFEC

UPDN

UPDN

STAIR-1

218A

CORRIDOR

BED ROOM

201A

BED ROOM

201B

BED ROOM

202A

BED ROOM

202B

BED ROOM

203A

BED ROOM

203B

BED ROOM

204A

BED ROOM

204B

BED ROOM

205A

BED ROOM

205B

BED ROOM

206A

BED ROOM

206B

BED ROOM

207A

BED ROOM

207B

BED ROOM

208A

BED ROOM

208B

STAIR-2

218B

LAUNDRY

BED ROOM

214A

BED ROOM

214B

BED ROOM

213A

BED ROOM

213B

BED ROOM

212A

BED ROOM

212B

BED ROOM

211A 211B 210A

210B

BED ROOM

209A

BED ROOM

209B

JAN

S/S

D

W

W

318A

301A 301B 302A 302B 303A 303B 304A 304B 305A 305B 306A 306B 307A 307B 308A 308B

314A

314B 313A 313B 312A 312B 311A 311B 310A

310B 309A 309B

318B

401A 401B 402A 402B 403A 403B 404A 404B 405A 405B 406A 406B 407A 407B 408A 408B

414A

414B 413A 413B 412A 412B 411A 411B 410A

410B 409A 409B

D

W/D

W/D

418B

418A

319 419

DAY RM

A

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

ELECTRICAL

E-14

ADDRESSABLE FIRE ALARM

F M

C P

F T

R

F F

F

F

F F

F

F

F

F F

F

F

F

F

FF

FF

F

F

F

F

AS REQ'D. PROGRAMMABLE MODULE

RELAYS, POWER MODULE AS REQ'D,

LCD ANNUNCIATOR, SYNCHRONIZATION

CONTROL MODULE, BATTERY,

BATTERY CHARGER, NEMA 1 ENCL

SURFACE MOUNTED BUILDING TRANSMITTER

W/BATTERY & BATTERY CHARGER

NEMA 1ENCL

1/100SCALE:

ADDRESSABLE FIRE ALARM

MANUAL PULL STATION

(TYPICAL)

SMOKE DETECTOR

(TYPICAL)

S P

R

J J

C

F

F

F F

F F

F

F

F

F F

F

F F F F F F F F F F F F

F F

F

FF

F

FF

F

F

FF

FF

F

F

F

F

F

F

F

SB

SHSH

F

F

SBSB SB

F F

SB SB

F

SB SB

F

SB SB

F

SB SH

F

SB SB

F

SB SB

F F F F F F

F

SHSH

F

SHSH

F

SBSH

F

SBSB

F

SBSB

1/100SCALE:

SURFACE MOUNTED BOOSTER PANEL

1PH, 120VAC INPUT, 5A(MAX)@24VDC, OUTPUT

W/CLASS "A" AS REQ'D W/SLC MODULE

AS REQ'D POWER MODULE AS REQ'D

CONFIGURATION PROGRAMMABLE RELAYS.

GROUND LOOP ISOLATION ANS TRANSIENT

PROTECTION etc. NEMA 1 ENCL

CONN TO SHUNT TRIP CIRCUIT

RELAY W/ADDRESSABLE MODULE

FIRE SUPPRESSION PANEL

W/ADDRESSABLE MODULE

(UNDER MECH. ITEM)

FOR ELEC RANGE

ADDRESSABLE FIRE ALARM

MANUAL PULL STATION

(TYPICAL)

FFF

F M

B P

J

PSTS

J

TS

J

TS

J

TS

J

LOC

LOC

J

FS

WALL MOUNTED SPEAKER (WATTAGE AS REQ'D)

/COMBO. (FA+MNS) VISUAL STROBES

(CANDELA AS REQ'D) (TYPICAL)

WALL MOUNTED SPEAKER (WATTAGE AS REQ'D)

/COMBO. (FA+MNS) VISUAL STROBES

(CANDELA AS REQ'D) (TYPICAL)

LOCAL OPERATING CONSOLE

SURFACE MOUNTED ADDRESSABLE COMBINED FIRE ALARM

CONTROL AND MASS NOTIFICATION SYSTEM PANEL, W/24VDC

BULIT-IN ADDRESSABLE POINTS MODULES

BED ROOM BED ROOM

BED ROOM

(TYPICAL)

LOCAL OPERATING CONSOLE

(TYPICAL)

D

J

DS

R

J

CO

W P

F M

W P

F M

WP

F M

F

TS

J J

FS

WALL MOUNTED SPEAKER (WATTAGE AS REQ'D)

,COMBO. (FA+MNS), "WP" (TYPICAL)

1ST FL FIRE ALARM AND MASS NOTIFICATION SYSTEM PLAN

2ND, 3RD & 4TH FL FIRE AND MASS NOTIFICATION SYSTEM PLAN

AND MASS NOTIFICATION SYSTEM PLAN

1ST, 2ND, 3RD & 4TH FLOOR FIRE ALARM

LOADCENTER "L2","L3" &"L4"

BREAKER L2-3,L3-3 & L4-3 IN

SMOKE W/SOUNDER BASE (TYPICAL)

ADDRESSABLE COMBINED PHOTOELECTRIC

OFFICE

OFFICE

FF

F

F

FF

REPAIR BLDG S-2308

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

2#12 IN 16C(FOR POWER)

12#14 IN 21C(FOR SIGNAL)

(TYPICAL)

SEE NOTE 2. BELOW

FOR NO & SIZE OF WIRE

WHICH DEVICE IS LOCATED

(TYPICAL)

ROOM NUMBER

SG

6#14 IN 16C

BOOSTER PANEL#1 (FMBP)

BATTERY CHARGER, POWER MODULE PANEL(AS REQ'D)

SYNCHRONIZATION CONTROL MODULE, DIGITAL VOICE

FIRE ALARM/MASS NOTIFICATION CONTROL PANEL,

24VDC, BUILT-IN ADDRESSABLE POINTS MODULES

AS REQUIRED, PROGRAMMABLE MODULE & RELAYS,

POWER MODULE AS REQ.D LCD ANNUNCIATOR,

123120101 117

EXT 120120 109 110 113B

NOT TO SCALE

(TYPICAL)

BATTERY & BATTERY CHARGER, etc. NEMA 1 ENCL

GROUND LOOP ISOLATION AND TRANSIENT PROTECTION

BOOSTER PANEL, 1PH, 120VAC INPUT, 6A(MAX)

@24VDC OUTPUT W/CLASS"A" AS REQ'D WITH

SLC MODULE AS REQ'D, POWER MODULE PANEL (AS REQ'D)

AMPLIFIER(AS REQ'D) CONFIGURATION PROGRAMMABLE RELAYS,

MANUAL PULL STATION

(TYPICAL)

W/MOUNTING BRACKET

LIGHTNING ARRESTER

OMNI-DIRECTION TYPE

W/CONNECTORS IN 16C

COAXIAL CABLE

GROUND CONDUCTOR

#6 "BC" IN 21C

W/WEATHER-PROOF ENCLOSURE

WITH WELDING CONNECTION

GROUND ROD, COPPER CLAD

STEEL, 19mmdia x 3000mmLG

BUILDING

TRANSMITTER

G ~

GROUND ROD, COPPER CLAD

#6, "BC" IN 21C

GROUNDING SYSTEM

CONN TO BLDG ELECTRODE

STEEL, 19mmdiax3000mmLG

WITH WELDING CONNECTION AND

2#12 & 1#12(G) IN 16C

G

SG

CONTROL PANEL (FMCP)

COMBINED FIRE ALARM/

ROOF

3rd FLOOR

1st FLOOR

EXT

113A

111107

120 106104

SURFACE MOUNTED COMBINED ADDRESSABLE

MODULE, POWER SUPPLY, MICROPHONE, BATTERY,

AND AMPLIFIER(AS REQ'D), NEMA 1 ENCL

MASS NOTIFICATION

FIRE ALARM/MASS NOTIFICATION

15.

"FIRE" AND W/CLEAR LENS.

1.

"ALERT" IN RED LETTER AND W/AMBER LENS.

SAFE PATH FACILITY COMMUNICATIONS OR APPROVED EQUAL.

STROBES FOR FIRE ALARM SHALL BE MARKED

STROBES FOR MASS NOTIFICATION SHALL BE MARKED

FOR ABBREVIATION, LEGEND, AND GENERAL NOTES

MASS NOTIFICATION SYSTEM SHALL BE SIMILAR TO WHEELOCK10.

5) EMERGENCY WEATHER CONDITIONS APPROPRIATE FOR THE LOCAL AREA

4) EVACUATION OF THE BUILDING USING EXITS OTHER THAN THE NORMAL MAIN ENTRANCE/EXIT

2) INTRUDER/HOSTILE PERSON SIGHTED WITHIN/AROUND THE BUILDING

1) BOMB THREAT OR ACTUAL BOMB WITHIN/AROUND THE BUILDING

ARE IN ENGLISH AND HANGUL AT LEAST FOR THE FOLLOWING ITEMS.

THE MASS NOTIFICATION SYSTEM SHALL BE ENSURED THAT PRERECORDED MESSAGES

WITH THE MANUFACTURER'S LISTED INSTALLATION REQUIREMENTS AND WIRE COUNT.

SHOP SUBMITTAL TO SHOW DETAILED INSTALLATION DEVICE LOCATIONS IN ACCORDANCE

THE APPLICABLE CODE, SPECIFICATIONS AND MANUFACTURER'S EQUIPMENT LISTING.

IS THE MINIMUM REQUIRED AND THE FINAL QUANTITY SHALL BE IN ACCORDANCE WITH

THE MASS NOTIFICATION SYSTEM IS CONCEPTUAL. THE NUMBER OF DEVICES SHOWN19.

3) OCCUPANTS DIRECTED TO TAKE COVER WITHIN THE BUILDING

6) "ALL CLEAR" MESSAGE

PER…

This is the start of the file's text. The full file is on GovTribe.