SYMBOL BY CHK.ZONE DATE APVD.

R E V I S I O N S

DESCRIPTION

R-11SHEET OF

DESIGNED BY

CHECKED BY

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. REF NO.

SCALE :SAFETY REP

SIGNAL REP

FES

FORCE PROTECTION

O & M

HOUSING DIV.

REVIEWED BY

AS SHOWN

UNITED STATES ARMY GARRISON DAEGU

ENGINEERING DIVISION, DESIGN & TECHNICAL REVIEW Br

DIRECTORATE OF PUBLIC WORK

HGFEDCBA

T I T L E S H E E T

D - 16 - 18

O, KI TAL

CHON, HYON TAE

DESIGN REVIEW SIGNATURE

ORGANIZATION

USING AGENCY

36TH SIGNAL

MASTER PLN.

ENVIRONMENTAL

NAME SIGNATURE

O&M DIV.

FIRE DEPT.

SAFETY OFFICE

DPTMS(AT/FP)

188TH MP COM.

IND. HYGENIST

HS-00517-5J

UNIT #15746, APO AP 96218-5746

C - 1

R - 1

DRAWING NO.

C - 23

CHIEF,

DESIGN & TECH. REVIEW Br.

TITLE SHEET

C - 34

PROJECT NO. HS-00517-5J, CAMP CARROLL

C - 56

E - 613

E - 714

CAMP CARROLL

MAIN DISTRIBUTION CABLE

REPLACE DAMAGED 22.9KV UNDERGROUND

MAIN DISTRIBUTION CABLE

REPLACE DAMAGED 22.9KV UNDERGROUND

E - 815

E - 916

E - 1017

E - 1118 22.9KV SWITCHING STATION NO.2 SINGLE LINE DIAGRAM

E - 1219

E - 1320

ELECTRICAL DISTRIBUTION PLAN - 5

ELECTRICAL DISTRIBUTION PLAN - 6

22.9KV SWITCHING STATION NO.1 AND PAD MTD JUNCTION DETAILS

22.9KV SWITCHING STATION NO.2

22.9KV SWITCHING STATION NO.1, INCOMING LINE STATION DRAGRAM AND LEGEND

CABLE JUNCTION PEDESTAL INSTALL DETAIL

PRIMARY DUCT & TRENCH SECTION AND INSTALLATION DETAIL

E - 512 11 OF 19 ELECTRICAL DISTRIBUTION PLAN - 4

E - 411 10 OF 19 ELECTRICAL DISTRIBUTION PLAN - 3

E - 310 ELECTRICAL DISTRIBUTION PLAN - 29 OF 19

E - 29 ELECTRICAL DISTRIBUTION PLAN - 18 OF 19

E - 1

ELECTRICAL

LEGEND, NOTES AND SCOPE OF WORK7 OF 19

CIVIL

C - 4

LOCATION PLAN

SITE LAYOUT PLAN-1

SITE LAYOUT PLAN-2

SITE LAYOUT PLAN-3

SECTION AND DETAILS

DATE: 21 SEP 16

C - 67 6 OF 19 SECTION AND DETAILS

CIVIL

AS SHOWN

HGFEDCBA

DESIGNED BY

CHECKED BY

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :SAFETY REP

SIGNAL REP

FES

FORCE PROTECTION

CHIEF,

DESIGN & TECH. REVIEW Br.

O & M

HOUSING DIV.

REVIEWED BY

SYMBOL BY CHK.ZONE DATE APVD.

R E V I S I O N S

DESCRIPTION

SHEET OF

UNITED STATES ARMY GARRISON DAEGU

DIRECTORATE OF PUBLIC WORKS

ENGINEERING DIVISION, DESIGN & TECHNICAL REVIEW Br

UNIT #15746, APO AP 96218-5746

DATE:

1 LOCATION PLAN

1 SCALE : 1 / 5000

LOCATION PLAN

C-1

N

THIS PROJECT

GRAPHIC SCALE

(IN METERS)

SCALE: 1 :5000

0 50 100 200

CAMP CARROLL

S-940 Tennis Court

S-294 Court Tennis

S-296 Court Tennis

S-165 Volleyball Court

S-980

STORY FIELD

LUTHER H.

T-646

S-671

S-672

S-673

S-674

S -644

T-780

T-508

S-86

S -7

S -7

S -7

T -6

T -5

T -7

T -5

S-961

T-533

T -5

S-714

S -8

T-377

T-584

T -3

T-3

S-531

T-417

T-863

T-765

T-368

T-507

T-772

S-967

T-924

T-575

T-696S-603

T-928

T-691

S-102

T-521

T-558

T-989

T-342

T-681

T-343

S-965

T-116

T-504

T-315

T-385

T-617

T-661

T-693

T-766

T-764

T-768

T-769

T-271

T-763

T-160

T-299

T-414

T-413

T-104

S-153

T-120

S-954

S-994

T-653

CEMETERY

S-860 Substation Electrical

S-360 Substation Electrical

S-576 Substation Electrical

S-133 bridge Foot

T-522

Footbridge

S-990 Footbridge

T-849 Footbridge

T-986 Footbridge

GATE 2

GATE 1

GATE 4

GATE 3

Gate Access

Railroad

Gate Access Farmer

Gate Access Farmer

S-118 Electronic Sign

S-952 Electronic Sign

S-781

Flag Pole

S-390

DEAD MEMORIAL

KOREAN WAR

S-741 Land Farm

T re a tm e n t

B e d

T re a tm e n t

B e d

Pond Holding

S-730

RANGE

QUALIFICATION

ZERO AND

25M RIFLE S-725

TESTING POND

BRIDGING BOAT

AMPITHEATRE

CAC

T-729 Storage Yard

Container

S-847

S-865 Bridge

Railroad

S-300 Road Bridge

S-860 Road Bridge

S-900 Road Bridge

S-500 Road Bridge

S-861 Road Bridge

A R

K A

N S

A S

N E

B R

A S

K A A

V E

N U

E

N E

W Y

O R

K A

V E

N U

E

A R

K A

N S

A S A

V E

N U

E

O H

IO

A

V E

N U

E

G E

O R

G

IA

A

V E

N U

E

T E

X A

S A

V E

N U

E

M O

N T A N

A A

V E N

U E

AVENUE

ILLINOIS AVENUE

A R

IZ

O N

A A

V E

N U

E

TENNESSEE AVENUE

N E

B R

A S

K A A

V E

N U

E

A M

E R

IC

A N A

V E N

U E

A R

K A

N S

A S A

V E

N U

E

PENN AVENUE

M

IS

S

IS

S

IP

P I

A V

E N

U E

A V

E N

U E

OHIO AVENUE

A M

E R

IC

A N A

V E N

U E

KENTUCKY AVENUE

G E

O R

G

IA

A

V E

N U

E

FLORIDA AVENUE

MISSISSIPPI

NEVADA

N E

W

N E

B R

A S

K A A

V E

N U

E

A M

E R

IC

A N A

V E N

U E

NEW YORK AVENUE

GEORGIA AVENUE

N E

B R

A S

K A A

V E

N U

E

OREGON

A V E N

U E

A V E N

U E

A V E N

U E

Y O

R K

PENN AVENUE

T-534

T-677

T-659

T-311

T-386

T-700

T-826

T-619

T-376

S-114

T-519

T-625

S-983

S-984

S-387

T-509B

T-509-2

T-578 Vehicle Scales

T-509-1

S-284

T-115

S-401

S-269

Bus Stop 10

S-383 Bus Stop 9

S-933 Bus Stop 6

S-621 Vehicle Scales

S-701

T-369

S-378

T-89

T-513

S-669 Station

Hunter Brake

S-328

S-329

T-509C

T-503 Bus Stop 1

S-622

T-624

S-639

T-416

T-827

S-350

T-415

T-979

S-667

S-705

T-926

T-577

T-720 Bus Stop 5

T-412

T-509D

T-509A

DUMP POINT

INDUSTRIAL WASTE

RECYCLING CENTER AND S-839

S-835

S-665

S-840

S-837

S-836

S-605

S-606

S-607

S-608

S-985

S-955

S-709

S-510

S-326

S-530

S-818

S-817

S-135

S-620

S-151

S-821

S-405

T-645

S-846

T -5

S-327

S -5

S-970

S-117

S-601

S-684

S-138

S-388

S-139

S-668

S-831

S-825

S-917

S-915

S -9

S-612

S -9

S-256

S-111

S-233

S-563

S-110

S-711

T-

S-231

S-396

S-230

S-100 S-235

S-375

S -9

S-136

S-403

T-565

S-253

S-250

S-977

S-676

S-254

S-573

S-946

S-998

S-203

S-841

S-123

S-938

S-657

S-914

T-516

S-341

S-911

S-113

T-520

S-913

S-141 S-143

S-142

S-264

S-731

S-101

S -309

S -2

S -7

S -9

T -9

T -9

S -9

S -9

S -2

S -9

S -6

S-675

S-320

S -8

S -8

S -9

T -5

T -9

S-9

S -9

S -3

T-318

S -4

S -6

S -3

S -8

S-9

S -6

S -8

S -8

T-126

S-121

T-125

T-127

T-207

S -1

T-236

S -9

S -6

T-206

S -3

S -9

T -3

S -3

S-154

S -9

S -8

S-974

S-321

S-

S-910S -4

S-340

S -6

S -7

S-349

S-301

S -611

T -3

S -6

S -7

S -7

S-140

S -6

S-718

S -7

S-137

S -6

S-842

S-351

S-512

S-205

S -5

S-336

S-239

S -9

S -3

S-267

S-509

T-359

S -3

S-532

S -9

S-655

S-208

T -7

S-702

S-163

S-304

T-515

S-733

S-732

S-642

S-627

T-384

S -3

T -5

T -3

S-312

S-666

S-420

S-973

T -3

T-580

S-679

T-996

S-925

T-997

S-931

T-631

T -2

S-131

S-919

T -3

T-521

S-395

S-397

S-918

S-944

T-195

T-196

T-198

T-197

T-194

T-199

S-119

S-739

S-3

S-647

T-261

S-164

S-626

S-58

T-130

S-717

S-402

T-572

T-189

T-406

T-193

T-958

S-88

S-348

T-581

S-265

S-640

S-953

S-411

S-664

S-654

S-344

S-511

S-982

S-968

S-929

T-155

S-972

T-582

S-771

S-95

T-409

S-948

S-916

S-947

S-957

T-192

S-956

S-719

T-762

S-770

S-162

S-161

T-317 Tower Cooling

T-923

S-93

S-922

T-814

T-812

T-569

T-635

S-995

T-810

T-280

T-811

T-633

T-103

T-813

T-637

T-636

S-741

TRAINING

CONFINED SPACE

BURN BUILDING AND

T-724

RESCUE

FIRE FIGHTING

S-845 Washrack

S-693 Washrack

S-404 Washrack

S-976 Washrack

S-939 Washrack

S-987 Washrack

S-316 Washrack

S-927 Washrack

T-6

S-703

PLANT

TREATMENT

SEWAGE

S-820

S-87

S-150

S-144

PLANT

TREATMENT

WATER

WETLAND

CAMP CARROLL

S-978 Substation Electrical

S-870

CLINIC

HEALTH/DENTAL

S T O

R A G E

O R

G A N

IZ

A T

IO

N A L

S

DFAC

TEMF

SEE SITE LAYOUT PLAN

1 19

21 SEP 16

HS-00517-5J

KU, HUN MO

CHI, K. K.

D - 16 - 18

MAIN DISTRIBUTION CABLE

REPLACE DAMAGED 22.9KV UNDERGROUND

-3 4

SHEET OF

KU, HUN MO

CIVIL

AS SHOWN

HGFEDCBA

DESIGNED BY

CHECKED BY

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :SAFETY REP

SIGNAL REP

FES

FORCE PROTECTION

CHIEF,

DESIGN & TECH. REVIEW Br.

O & M

HOUSING DIV.

REVIEWED BY

SYMBOL BY CHK.ZONE DATE APVD.

R E V I S I O N S

DESCRIPTION

UNITED STATES ARMY GARRISON DAEGU

DIRECTORATE OF PUBLIC WORKS

ENGINEERING DIVISION, DESIGN & TECHNICAL REVIEW Br

UNIT #15746, APO AP 96218-5746

DATE:

GRAPHIC SCALE

WITHOUT ANY ADDITIONAL COST.

INCLUDING FALSEWORK SUCH AS FORMWORKS AND SHORING

10. CONTRACTOR SHOULD PROVIDE ANY NECESSARY RESOURCES

LOCAL LAWS AND REGULATIONS.

GOVERNMENT LEASED PROPERTY IN ACCORDANCE WITH

11. DISPOSAL OF WASTE MATERIALS SHOULD BE OUTSIDE U.S

GENERAL NOTES :

COR PRIOR TO COMMENCING WORK ON THE PROJECT.

INDICATED BY THE COR AND SHOULD BE APPROVED BY THE

UNDETAILED PORTION OF THE JOB INCLUDING OTHER AREAS

2. THE CONTRACTOR SHOULD SUBMIT SHOP DRAWINGS FOR ANY

PERIOD IF REQUIRED.

AND DETOUR ROAD FOR VEHICLES DURING CONSTRUCTION

6. CONTRACTOR SHOULD PROVIDE TEMPORARY ACCESS ROAD

MILLIMETERS AND STATIONS AND ELEVATIONS ARE IN METERS.

15. UNLESS OTHERWISE NOTED ALL THE DIMENSIONS ARE IN

TO SUBMISSION OF CONTRACT PROPOSAL.

AND DIMENSIONS AT THE PROJECT SITE ORIENTATION PRIOR

1. THE CONTRACTOR SHOULD VERIFY ALL EXISTING CONDITIONS

CONTRACTING OFFICER.

THE CONTRACTORS EXPENSE TO THE SATISFACTION OF THE

DAMAGED BY DISMANTLING, DEMOLISHING, OR REMOVING AT

RESTORATION TO THEIR ORIGINAL CONDITIONS OF THE ITEMS

3. THE CONTRACTOR SHOULD BE RESPONSIBLE FOR REPAIR/

SHOULD BE COVERED WITH SOLID SODDING.

4. ALL UNPAVED AREAS WITHIN THE GRADING LIMIT LINE

CONSTRUCTION OPERATIONS.

LINES, AND OTHER ITEMS WHICH WILL INTERFERE WITH THE

SUCH AS UNDER GROUND ROCK BASE, EXISTING UTILITY

AND CLEARED/REROUTED OF ALL NATURAL OBSTRUCTIONS,

5. THE SITE INDICATED ON THE DRAWING SHOULD BE GRADED

AND OTHER UTILITY MARKERS IN THE PROJECT LIMIT.

7. CONTRACTOR SHALL RESTORE/REESTABLISH SURVEY MOUMENTS

OF FROST DEPTH UNLESS OTHERWISE NOTED.

9. WATER AND SEWER LINE SHOULD HAVE A MINIMUM COVER

OPERATIONS.

SAFETY OF THE PUBLIC AND/OR MILITARY TRAFFIC AND

ALL NECESSARY PRECAUTIONS FOR THE PROTECTION AND

CONES AND OTHER PROTECTIVE FACILITIES AND SHALL TAKE

NECESSARY SIGNS, LIGHTS, FLARES, BARRICADES, MARKERS,

14. CONTRACTOR SHALL PROVIDE, INSTALL AND MAINTAIN ALL

ACCOMPLISH THE CIVIL SCOPE OF WORK.

A PART OF THIS PROJECT. THE DETAILS WILL BE UTILIZED TO

MANAGEMENT COMMAND, KOREA REGION OFFICE" FORM AS

NOVEMBER 2015, DEPARTMENT OF THE ARMY INSTALLATION

DETAIL DRAWINGS, FOR O & MA PROJECT, KOREA, 30

8. THE CIVIL STANDARD DRAWINGS SHOWN IN THE "STANDARD

#2 (REPAIR/MAINTENANCE)

LEGEND:

ITEMS TO BE REMOVED

E/P

N

C-2

HS-00517-5J

CAMP CARROLL

EXISTING ELECTRICAL POLE

CHI, K. K.

GOVERNMENT.

AREA SHALL BE PROVIDED FOR THE CONTRACTOR BY THE

BE WITHIN THE CONSTRUCTION AREA AND NO LAY DOWN

ADMINISTRATIVE FIELD OFFICES AND STORAGE AREAS SHALL

SPEC. AT THE LOCATION APPROVED/INDICATED BY C.O.R.

CONTRACTOR’S TEMPORARY FACILITIES ACCORDING TO O&MA

12. CONTRACTOR SHOULD PROVIDE AND MAINTAIN THE

APPROVAL PRIOR TO COMMENCING THE PROJECT.

TO THE DESIGN AND TECHNICAL REVIEW BRANCH FOR

13. THE CONTRACTOR SHOULD PREPARE/SUBMIT MATERIAL REVIEWS

BASE COURSE AND SUBBASE COURSE

REMOVE/REPLACE EXST. AC PAVEMENT,

MAIN DISTRIBUTION CABLE

REPLACE DAMAGED 22.9KV UNDERGROUND

SCALE : 1 / 100

SCALE: 1 : 100

2000 4000

43.

AC

43.

AC

43.

AC

42.

AC

42.

AC

42.

AC

42.

AC

42.

AC

42.

AC

42.

AC

42.

AC

43.

AC

43.

AC

43.

AC

42.

AC

42.

MH

42.

MH

42.

MH

43.

DIT

CH

42.

DIT

CH

42.

DIT

CH

E/P

E/P

M/H

M/H

SITE LAYOUT PLAN-1

SITE LAYOUT PLAN-1

CCTV

GAS

DD

D

2,5

S-622

G

EXISTING CCTV AND POLE

CCTV

(ASSUMED)

EXISTING GAS LINE

1.

REMOVE/REPLACE EXISTING DRAIN LINE WITH NEW.

CONCRETE DITCH WITH NEW.

REMOVE/REPLACE EXISTING STEEL GRATING COVERED

BASE COURSE AND SUBBASE COURSE.

REMOVE/REPLACE EXISTING ASPHALT CONCRETE PAVEMENT,

3.

2.

1.

~AC~

SEE DETAIL

SAME AS EXISTING

PAVEMENT, BASE COURSE AND SUBBASE COURSE

REMOVE/REPLACE EXISTING ASPHALT CONCRETE

(M

IN.

SEE DETAIL

FOR GAS LINE

INSTALL CONCRETE PROTECTION SLAB

COVERED CONCRETE DITCH WITH NEW

REMOVE/REPLACE EXISTING STEEL GRATING

WITH NEW (D=450, RCP)

REMOVE/REPLACE EXISTING DRAIN LINE

E

E

TYPICAL SECTION

SEE ELEC. DRAWINGS AND

AND CONCRETE PADS

NEW PRIMARY JUNCTION PEDESTALS

3. SEE THE ELECTRICAL DRAWING FOR ELECTRICAL WORKS.

WITH SOLID SODDING.

2. ALL UNPAVED AREAS WITHIN THE GRADING LIMIT LINE SHOULD BE COVERED

ARE NOT SHOWN ON THE DRAWING AND RELOCATE/ REPLACE AS REQUIRED.

COMMUNICATION LINE, ELECTRICAL LINE, GAS LINE AND WATER LINE THAT

1. CONTRACTOR SHALL VERIFY THE LOCATION OF UTILITY LINES SUCH AS

NOTES:

D - 16 - 18

2 19

21 SEP 16

INSTALL CONCRETE PROTECTION SLAB.

SCOPE OF WORK (NEAR BLDG. #622)

#1 (CONSTRUCTION/ALTERATION)

CIVIL

AS SHOWN

HGFEDCBA

DESIGNED BY

CHECKED BY

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :SAFETY REP

SIGNAL REP

FES

FORCE PROTECTION

CHIEF,

DESIGN & TECH. REVIEW Br.

O & M

HOUSING DIV.

REVIEWED BY

SYMBOL BY CHK.ZONE DATE APVD.

R E V I S I O N S

DESCRIPTION

UNITED STATES ARMY GARRISON DAEGU

DIRECTORATE OF PUBLIC WORKS

ENGINEERING DIVISION, DESIGN & TECHNICAL REVIEW Br

UNIT #15746, APO AP 96218-5746

DATE:

GRAPHIC SCALE

LEGEND:

ITEMS TO BE REMOVED

E/P

HS-00517-5J

CAMP CARROLL

EXISTING ELECTRICAL POLE

CHI, K. K.

MAIN DISTRIBUTION CABLE

REPLACE DAMAGED 22.9KV UNDERGROUND

SCALE : 1 / 100

SCALE: 1 : 100

2000 4000

.0

A C

.9

D

IT

C H

.4

D

IT

C H

.2

D

IT

C H

.2

D

IT

C H

.4

D

IT

C H

.8

D

IT

C H

.7

D

IT

C H

.9

D

IT

C H

.7

S W

A L

K

M/H

M/H

FHT

WV

E/P

E/P

- 3

C-3

3 19

SITE LAYOUT PLAN-2

SITE LAYOUT PLAN-2

N

W W

G G

#1 (CONSTRUCTION/ALTERATION)

#2 (REPAIR/MAINTENANCE)

3.

2.

1.

(ASSUMED)

EXISTING GAS LINE

EXISTING TREES TO BE TRIMMED

COURSE AND SUBBASE COURSE

REMOVE/REPLACE EXST. AC PAVEMENT, BASE

~AC~

SEE DETAIL

SAME AS EXISTING

PAVEMENT, BASE COURSE AND SUBBASE COURSE

REMOVE/REPLACE EXISTING ASPHALT CONCRETE

SEE TYPICAL SECTION

AND HANDRAIL

CONSTRUCT CONCRETE RETAINING WALL

E

M/H

FHT

EXISTING FIRE HYDRANT

G/P

GUARD POST

INSTALL GUARD POSTS

INSTALL GUARD POSTS.

CONSTRUCT CONCRETE RETAINING WALL AND HANDRAIL.

2.

1.

(ASSUMED)

EXISTING WATER LINE2

,5

(M

IN

ACCESSORIES SAME AS EXISTING

INCLUDING NECESSARY FITTINGS AND

REMOVE/REPLACE EXISTING WATER LINE

E G/PG/PG/P

SEE ELEC. DRAWINGS

AND CONCRETE PADS

NEW PRIMARY JUNCTION PEDESTALS

THE GUIDANCE OF COR

IN ACCORDANCE WITH

TRIM EXISTNG TREES

D - 16 - 18

21 SEP 16

SCOPE OF WORK (NEAR BLDG. #676)

4. COUPLING ADAPTER SHALL BE GFM.

3. SEE THE ELECTRICAL DRAWING FOR ELECTRICAL WORKS.

WITH SOLID SODDING.

2. ALL UNPAVED AREAS WITHIN THE GRADING LIMIT LINE SHOULD BE COVERED

ARE NOT SHOWN ON THE DRAWING AND RELOCATE/ REPLACE AS REQUIRED.

COMMUNICATION LINE, ELECTRICAL LINE, GAS LINE AND WATER LINE THAT

1. CONTRACTOR SHALL VERIFY THE LOCATION OF UTILITY LINES SUCH AS

NOTES:

TRIM EXISTING TREES.

(GFM: COUPLING ADAPTER)

NECESSARY FITTINGS AND ACCESSORIES.

REMOVE/REPLACE EXISTING WATER LINE INCLUDING

BASE COURSE AND SUBBASE COURSE.

REMOVE/REPLACE EXISTING ASPHALT CONCRETE PAVEMENT,

1. COPLING ADAPTER, D=250 - 1EA, D=200 - 1EA.

*GFM(GOVERNMENT FURNISHED MATERIAL)

59.381

AC

59.555

AC

58.987

AC

60.761

AC

60.799

AC

60.867

AC

60.892

AC

60.821

AC

60.744

AC

60.697

BLDG

60.849

BLDG

60.888

BLDG

60.863

BLDG

59.189

MH

58.854

PAD

60.468

PAD

E/P

E/P

S/P

S/P

S/B

MH

MH

MH

MH

MH

MH

MH

PAD

CON

SHEET OF

KU, HUN MO

CIVIL

AS SHOWN

HGFEDCBA

DESIGNED BY

CHECKED BY

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :SAFETY REP

SIGNAL REP

FES

FORCE PROTECTION

CHIEF,

DESIGN & TECH. REVIEW Br.

O & M

HOUSING DIV.

REVIEWED BY

SYMBOL BY CHK.ZONE DATE APVD.

R E V I S I O N S

DESCRIPTION

UNITED STATES ARMY GARRISON DAEGU

DIRECTORATE OF PUBLIC WORKS

ENGINEERING DIVISION, DESIGN & TECHNICAL REVIEW Br

UNIT #15746, APO AP 96218-5746

DATE:

GRAPHIC SCALE

LEGEND:

ITEMS TO BE REMOVED

EXISTING ELECTRICAL POLE

CHI, K. K.

SCALE : 1 / 100

SCALE: 1 : 100

2000 4000

- 4

C-4

4 19

SITE LAYOUT PLAN-3

SITE LAYOUT PLAN-3

E/P

N

MH

MH

C O

M

C O

M

W

W

W

S/P

S/B

EXISTING SIGN BOARD AND POST

G

G

G

COURSE AND SUBBASE COURSE

REMOVE/REPLACE EXST. AC PAVEMENT, BASE

LINE (ASSUMED)

EXISTING GAS

(ASSUMED)

EXISTING WATER LINE

INDICATED BY COR

SIGN BOARD TO THE LOCATION

RELOCATE EXISTING MOVABLE DIGITAL

#323

BLDG.

T-376

~AC~

#1 (CONSTRUCTION/ALTERATION)

#2 (REPAIR/MAINTENANCE)

1.

3.

2.

1.

E

SEE DETAIL

SAME AS EXISTING

PAVEMENT, BASE COURSE AND SUBBASE COURSE

REMOVE/REPLACE EXISTING ASPHALT CONCRETE

MAIN DISTRIBUTION CABLE

REPLACE DAMAGED 22.9KV UNDERGROUND

CAMP CARROLL

21 SEP 16

HS-00517-5J

INSTALL CONCRETE PROTECTION SLAB.

SEE DETAIL

FOR GAS LINE

INSTALL CONCRETE PROTECTION SLAB

SAME AS EXISTING

FITTINGS AND ACCESSOIRES

LINE INCLUDING NECESSARY

REMOVE/REPLACE EXISTING WATER

EXISTING STEEL POST

TYPICAL SECTION

SEE ELEC. DRAWINGS AND

AND CONCRETE PADS

NEW PRIMARY JUNCTION PEDESTALS

D - 16 - 18

SCOPE OF WORK (NEAR BLDG. #323)

4. COPLING ADAPTER SHALL BE GFM.

3. SEE THE ELECTRICAL DRAWING FOR ELECTRICAL WORKS.

WITH SOLID SODDING.

2. ALL UNPAVED AREAS WITHIN THE GRADING LIMIT LINE SHOULD BE COVERED

ARE NOT SHOWN ON THE DRAWING AND RELOCATE/ REPLACE AS REQUIRED.

COMMUNICATION LINE, ELECTRICAL LINE, GAS LINE AND WATER LINE THAT

1. CONTRACTOR SHALL VERIFY THE LOCATION OF UTILITY LINES SUCH AS

NOTES:

RELOCATE EXISTING MOVABLE DIGITAL SIGN BOARD.

(GFM: COUPLING ADAPTER)

NECESSARY FITTINGS AND ACCESSORIES.

REMOVE/REPLACE EXISTING WATER LINE INCLUDING

BASE COURSE AND SUBBASE COURSE.

REMOVE/REPLACE EXISTING ASPHALT CONCRETE PAVEMENT,

CIVIL

AS SHOWN

HGFEDCBA

DESIGNED BY

CHECKED BY

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :SAFETY REP

SIGNAL REP

FES

FORCE PROTECTION

CHIEF,

DESIGN & TECH. REVIEW Br.

O & M

HOUSING DIV.

REVIEWED BY

SYMBOL BY CHK.ZONE DATE APVD.

R E V I S I O N S

DESCRIPTION

UNITED STATES ARMY GARRISON DAEGU

DIRECTORATE OF PUBLIC WORKS

ENGINEERING DIVISION, DESIGN & TECHNICAL REVIEW Br

UNIT #15746, APO AP 96218-5746

DATE:

CHI, K. K.

MAIN DISTRIBUTION CABLE

REPLACE DAMAGED 22.9KV UNDERGROUND

CAMP CARROLL

MORTAR

FORMED HOLE

HANDRAIL POST

HANDRAIL

AC ELEVATIONS

MATCH TO EXISTING

6001,200

(TYP.)

S=5%

EXISTING GROUND

3 NOT TO SCALE

SECTION

MATERIAL PROPERTIES:

ABBREVIATION:

2. REINFORCING STEEL YIELD STRENGTHS, fy=300 Mpa.

1. CONCRETE MINIMUM COMPRESSIVE STRENGTH AT 28 DAYS, f’c=24 Mpa.

STONE DITCH

EXISTING OPEN

D13@250 E.F

D13@250 E.F

O.C: ON CENTER

E.F: EACH FACE

T.B: TOP AND BOTTOM

E.W: EACH WAY

WALL

CONC. RETAINING

21 SEP 16

HS-00517-5J

5 19 C-5

STEEL PIPE

40mm GALVANIZED

WALL

CONC. RETAINING

SEE DETAIL ’A’

CONNECTION

WELD ALL

2,100

PAINT

HANDRAIL DETAIL

DETAIL ’A’

SECTION AND DETAILS

EARTH FILL

STRUCTUAL

2. PROVIDE PIPE SLEEVES AS REQUIRED.

1. PROVIDE SHOP DRAWING, VERIFY THE LOCATION OF WATER LINE.

NOTES:

(ASSUMED)

WATER LINE

1, (M

IN

(M

IN

2,200

(TYP.)

1,000

1,000

NOT TO SCALE5

SECTION (TYP.)2

S=0.5%

(MIN.)

S=0.5%

(MIN.)

2 4

AND GEOTEXTILE

GRAVEL POCKET(300x300x300)

PVC PIPE(D=50)@2,000

D13@250 E.F.T.B

1. PAINT HANDRAIL SURFACES IN ACCORDANCE WITH COLOR CODE GUIDANCE OF COR.

NOTE:

(MAX.)

SEE ELEC. DRAWINGS

AND CONCRETE PAD

PRIMARY JUNCTION PEDESTAL

SEE ELEC. DRAWINGS

AND CONCRETE PAD

PRIMARY JUNCTION PEDESTAL

D - 16 - 18

CIVIL

AS SHOWN

HGFEDCBA

DESIGNED BY

CHECKED BY

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :SAFETY REP

SIGNAL REP

FES

FORCE PROTECTION

CHIEF,

DESIGN & TECH. REVIEW Br.

O & M

HOUSING DIV.

REVIEWED BY

SYMBOL BY CHK.ZONE DATE APVD.

R E V I S I O N S

DESCRIPTION

UNITED STATES ARMY GARRISON DAEGU

DIRECTORATE OF PUBLIC WORKS

ENGINEERING DIVISION, DESIGN & TECHNICAL REVIEW Br

UNIT #15746, APO AP 96218-5746

DATE:

CHI, K. K.

MAIN DISTRIBUTION CABLE

REPLACE DAMAGED 22.9KV UNDERGROUND

CAMP CARROLL

HS-00517-5J

6 19 C-6

1 1

MIN

NEW AC SURFACE

NEW PRIME COAT

NEW BASE COURSE

NEW SUBBASE COURSE

COAT

APPLY TACK

SAW CUT AND

PAVEMENT

EXISTING AC

COURSE

EXISTING BASE

COURSE

EXISTING SUBBASE

COMPACTED SUBGRADE

WARNING TAPE

SATISFACTORY BACKFILL

INDICATED ON ELEC. PLANS

DUCT, NUMBER AS

CONCRETE ENCASED

DUCT

WIDTH

NOT TO SCALE6

MIN

DUCT & TRENCH SECTION (TYP)

SECTION AND DETAILS

SLAB

PROTECTION

ASPHALT SURFACE

BASE COUSRE

SUBBASE COURSE

GAS LINE

NOT TO SCALE6

(SQ)

BLACK

YELLOW

150 150 150

D13

F.E.L

CONCRETE FOUNDATION

POST FILLED WITH CONCRETE

150 mm DIA. STEEL PIPE GUARD

WELDED TO STEEL PIPE

NOT TO SCALE6

GUARD POST DETAIL (TYP)

PROTECTION SLAB DETAIL (TYP)

PROFESSIONAL ENGINEER, DESCRIBING THE METHODS FOR SHORING.

2. PROVIDE DRAWING AND CALCULATIONS, CERTIFIED BY A REGISTERED

OF LABORATORY MAX. DENSITY.

1. BASE AND SUBBASE COURSE SHALL BE COMPACTED AT LEAST 100 %

NOTES:

E.F.T.B D13@150

1,800

21 SEP 16

ENGINEERING DIVISION, DESIGN & TECHNICAL REVIEW Br

ELECTRICAL

AS SHOWN

HGFEDCBA

DESIGNED BY

CHECKED BY

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :SAFETY REP

SIGNAL REP

FES

FORCE PROTECTION

CHIEF,

DESIGN & TECH. REVIEW Br.

O & M

HOUSING DIV.

REVIEWED BY

SYMBOL BY CHK.ZONE DATE APVD.

R E V I S I O N S

DESCRIPTION

UNITED STATES ARMY GARRISION DAEGU

DIRECTORATE OF PUBLIC WORK

UNIT #15746, APO AP 96218-5746

DATE:

LEGEND, NOTES AND SCOPE OF WORK

5.

6.

E-1

D - 16 - 18HS-00517-5J

SHEET OF

SIN, YS

KIM, CK

1.

N O T E S

3.

2.

4. MOUNTING HEIGHTS ARE AS BELOW. MEASUREMENT IS TO CENTER OF OUTLET.

WIRES IS INDICATED AS FOLLOW;

AND ONE (1)-#12AWG GROUND WIRE IN 16mm CONDUIT. A GREATER NUMBER OF

ANY CIRCUIT WITHOUT FURTHER DESIGNATION INDICATES TWO (2)-#12AWG WIRES

3-#12AWG WIRES AND 1-#12AWG GROUND WIRE IN 16mm CONDUIT.

4-#12AWG WIRES AND 1-#12AWG GROUND WIRE IN 16mm CONDUIT.

FIRE ALARM CONTROL PANEL----------------------------5’-0" ABOVE FLOOR

MANUAL PULL STATION----------------------------------4’-6" ABOVE FLOOR

FIRE ALARM BELL---------------------------------------7’-0" ABOVE FLOOR

LIGHTING FIXTURE--------------------SEE LIGHTING FIXTURE SCHEDULE

TOGGLE SWITCH-----------------------1220mm TO CENTER OF THE OUTLET

RECEPTACLE---------------------------460mm TO CENTER OUTLET

PANELBOARD, CIRCUIT BREAKER------------------------SEE SPECIFICATION

CAULKING MATERIAL SHALL BE VERIFIED BY F&ES OFFICE PRIOR TO CONSTRUCTION.

BOTH SIDE OF FIRE WALLS, FIRE-PARTITIONS AND FIRE-RATED PIPE CHASE WALLS.

ALL PIPE PENETRATIONS SHALL BE SEALED WITH FIRE RATED CAULKING MATERIAL ON

1.

SPECIFICATIONS FOR O&MA PROJECTS, AND SPECIFICATIONS.

ELECTRICAL CODE, NATIONAL ELECTRICAL SAFETY CODE, FIRE CODE, TECHNICAL STANDARD

ALL ELECTRICAL WORK SHALL CONFORM TO THE LATEST REQUIREMENTS OF THE NATIONAL

CONDUIT WHICH IS TO BE BONDED TO THE MAIN GROUNDING SYSTEM AT BOTH ENDS.

GROUNDING WIRE SHALL BE GREEN INSULATED COPPER WIRE IN RIGID GALVANIZED STEEL

ALL WIRING SHALL BE CONCEALED ABOVE THE CEILING WHEN THE ROOM HAS A CEILING.

L E G E N D

NEWEXSTREMOVE

SCOPE OF WORK

CAMP CARROLL

MAIN DISTRIBUTION CABLE

REPLACE DAMAGED 22.9KV UNDERGROUND

7.

STORAGE AREA.

THE CONTRACTOR SHALL TURN OVER ALL SALVAGED MATERIAL TO THE DPW DESIGNATED

M M M

H H H

PMJ PRIMARY PAD MTD JUNCTION BOX

MANHOLE

HANDHOLE

PMJPMJ

UNDERGROUND DISTRIBUTION LINE+ + +

OROROR

A

A

AS

VS

AS

VS

AS

VS

A

GROUND ROD

POWER CIRCUIT BREAKER

DRAW-OUT TYPE DEVICE CONNECTION

FUSE

AMMETER SWITCH

VOLTMETER SWITCH

INVERSE TIME OVERCURRENT RELAY, NO.

DESIGNATES RELAY TYPE

27 = UNDERVOLTAGE RELAY

50 = INSTANTANEOUS OVERCURRENT RELAY

51N = RESIDUAL NEUTRAL INVERSE TIME OVERCURRENT RELAY

67 = DIRECTIONAL OVERCURRENT RELAY

67N = DIRECTIONAL NEUTRAL OVERCURRENT RELAY

SWITCH

FUSED SWITCH OR FUSED CUTOUT

CURRENT TRANSFORMER

POTENTIAL (VOLTAGE) TRANSFORMER

TRANSFORMER

AMMETER LETTER DESIGNATES METER TYPE

V = VOLT METER

W = WATT METER

PF = POWER FACTOR METER

VAR = KILO-VAR METER

WHM = KILOWATT-HOUR METER

LIGHTNING ARRESTER/SURGE ARRESTER

8.

ELECTRICAL LINES AND ANY NEW ELECTRICAL EQUIPMENT AND CABLING.

AND ELECTRICAL SHOP FOR ANY REMOVAL OR REPAIR OF EXISTING EQUIPMENT OR UNDERGROUND

THE CONTRACTOR SHALL COORDINATE WITH THE BASE ENGINEER (DPW). ELECTRICAL ENGINEER

B. REPAIR/MAINTENANCE

1.

2.

3.

SWITCHGEARS, VCBS, DISTRIBUTION LINES, EQUIPMENTS AND HIGH VOLTAGE ACCESSORIES.

PROVIDE OPERATION TEST & ADJUST, REPAIR AT EACH SWITCHING STATIONS INCLUDING MOF, CONTROL WIRES, DOORS, SPACE HEATERS AND ASSOCIATED ACCESSORIES AT EACH SWITCH STATION.

REPLACE DETERIORATED EXISTING PROTECTION & MONITORING EQUIPMENT INCLUDING RELAYS, A. CONSTRUCTION

INCLUDING DUCT & MANHOLE CLEANING AND ASSOCIATED ACCESSORIES.

REPLACE EXISTING DETERIORATED 22.9KV UNDERGROUND MAIN DISTRIBUTION LINE WITH NEW

US ORIGIN MATERIAL:

INDICATED ON THE DRAWINGS.

INTERNET SITE (http//www.cckbid.com). ALL NON-GENERIC US ORIGIN MATERIALS SHALL BE AS

DATED REVISION 1 - 20151030 (ELECTRONIC VERSION OF THIS DOCUMENT CAN BE FOUND AT

REGISTER OF IMA-KORO PAMPHLET 420-1 "INSPECTION OF CONSTRUCTION CONTRACTS

ALL GENERIC US ORIGIN MATERIALS SHALL BE AS OFF-SHORE IN THE GENERIC SUBMITTAL

7 19

DUCT, SPLICE KIT AND NECESSARY ASSOCIATED ACCESSORIES.

INSTALL NEW CABLE JUNCTION PEDESTAL(GFM) INCLUDING 25KV DISTRIBUTION CABLE, CONCRETE ENCASEMENT

N

ELECTRICAL

AS SHOWN

HGFEDCBA

DESIGNED BY

CHECKED BY

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :SAFETY REP

SIGNAL REP

FES

FORCE PROTECTION

CHIEF,

DESIGN & TECH. REVIEW Br.

O & M

HOUSING DIV.

REVIEWED BY

SYMBOL BY CHK.ZONE DATE APVD.

R E V I S I O N S

DESCRIPTION

UNITED STATES ARMY GARRISION DAEGU

DIRECTORATE OF PUBLIC WORK

UNIT #15746, APO AP 96218-5746

DATE:

E-2

D - 16 - 18

SHEET OF

SIN, YS

KIM, CK

21 SEP 16

MAIN DISTRIBUTION CABLE

REPLACE DAMAGED 22.9KV UNDERGROUND

CAMP CARROLL

HS-00517-5J

0 120003000 6000

SCALE: 1:300

x x x x x x x xxxx x x x

KEY PLAN

- E2

P-1 ELECTRICAL DISTRIBUTION PLAN - 1

T-377

T-619

S -9

T-813

S T O

R A G E

O R

G A N

IZ

A T

IO

N A L

S

D

T-569

T-565

T

T-575

S-574

S

S u b s ta ti o n

E le c tr ic a l

S-573

T-578 Vehicle Scales

S-640

GATE 2

EMHM-01

DHM-01

M

H

EMHM-02

DHM-02

H

M

D

/D /D

D

/D

/D

/D

SCALE : 1 / 300

(REUSE EXISTING DUCT)

IN 155mmC DUCT WITH DUCT CLEANING

& 1-750KCMIL, 600V, POWER CABLE

REPLACE 2SET OF 3-750KVMIL, 25KV "XLP"

MATCH LINE SEE SHEET E-3

SEE

ENLARGED PLAN

- E8

P-1

22.9KV PRI-5.7/ 3.3KV SEC

EXISTING KEPCO SUBSTATION

PLAN REFER DWG SH E-8

22.9KV SWITCHGEAR ENLARGED

SWITCHING STATION NO.1

CLEAN EXISTING ELECTRICAL MANHOLE

CLEAN EXISTING ELECTRICAL MANHOLE

8 19

ELECTRICAL DISTRIBUTION PLAN - 1

AS SHOWN

HGFEDCBA

DESIGNED BY

CHECKED BY

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :SAFETY REP

SIGNAL REP

FES

FORCE PROTECTION

CHIEF,

DESIGN & TECH. REVIEW Br.

O & M

HOUSING DIV.

REVIEWED BY

SYMBOL BY CHK.ZONE DATE APVD.

R E V I S I O N S

DESCRIPTION

UNITED STATES ARMY GARRISION DAEGU

DIRECTORATE OF PUBLIC WORK

UNIT #15746, APO AP 96218-5746

DATE:

E-3

SHEET OF

SIN, YS

KIM, CK

MAIN DISTRIBUTION CABLE

REPLACE DAMAGED 22.9KV UNDERGROUND

CAMP CARROLL

HS-00517-5J

0 120003000 6000

SCALE: 1:300

- E3

P-1 ELECTRICAL DISTRIBUTION PLAN - 2

S-657

T

T-561

T 3 T

N E

B R

A S

K A

V E

N U

E

T-580

S-563

S-622

T-572

T-582

T-581

P M J

EMHM-03

DHM-03

M H

DHM-04

EMHM-04

M H

/D

D D

/D

/D

D D

SCALE : 1 / 300

KEY PLAN

T-377

T-619

S -9

T-813

S T O

R A G E

O R

G A N

IZ

A T

IO

N A L

S

MATCH LINE. SEE SHEET E-2

MATCH LINE. SEE SHEET E-4

(REUSE EXISTING DUCT)

IN 155mmC DUCT WITH DUCT CLEANING

& 1-750KCMIL, 600V, POWER CABLE

REPLACE 2SET OF 3-750KVMIL, 25KV "XLP"

CLEAN EXISTING ELECTRICAL MANHOLE

CLEAN EXISTING ELECTRICAL MANHOLE

DUCT WITH PULL WIRE

IN 155mmC DUCT AND 4-155mmC SPARE

& 1-750KCMIL, 600V, POWER CABLE

PROVIDE 4SET OF 3-750KVMIL, 25KV "XLP"

21 SEP 16

D - 16 - 18

ELECTRICAL DISTRIBUTION PLAN - 2

9 19

INSTALL DETAIL SHEET NO. E-12

600A, 25KV, 2WAY JUNCTION(GFM) SEE

NEW 2EA PRIMARY JUNCTION PEDESTAL

AS SHOWN

HGFEDCBA

DESIGNED BY

CHECKED BY

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :SAFETY REP

SIGNAL REP

FES

FORCE PROTECTION

CHIEF,

DESIGN & TECH. REVIEW Br.

O & M

HOUSING DIV.

REVIEWED BY

SYMBOL BY CHK.ZONE DATE APVD.

R E V I S I O N S

DESCRIPTION

UNITED STATES ARMY GARRISION DAEGU

DIRECTORATE OF PUBLIC WORK

UNIT #15746, APO AP 96218-5746

DATE:

E-4

D - 16 - 18

SHEET OF

SIN, YS

KIM, CK

21 SEP 16

MAIN DISTRIBUTION CABLE

REPLACE DAMAGED 22.9KV UNDERGROUND

CAMP CARROLL

HS-00517-5J

0 120003000 6000

SCALE: 1:300

- E4

P-1 ELECTRICAL DISTRIBUTION PLAN - 3

S-530

S-668

T-661

S-675

S-693 Washrack

T-693

T-584

DHM-05 EMHM-05 M

H

/D

D

D

/D

/D

SCALE : 1 / 300

KEY PLAN

T-377

T-619

S -9

T-813

S T O

R A G E

O R

G A N

IZ

A T

IO

N A L

S

MATCH LINE. SEE SHEET E-3

MATCH LINE. SEE SHEET E-5

(REUSE EXISTING DUCT)

IN 155mmC DUCT WITH DUCT CLEANING

& 1-750KCMIL, 600V, POWER CABLE

REPLACE 2SET OF 3-750KVMIL, 25KV "XLP"

CLEAN EXISTING ELECTRICAL MANHOLE

ELECTRICAL DISTRIBUTION PLAN - 3

10 19

AS SHOWN

HGFEDCBA

DESIGNED BY

CHECKED BY

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :SAFETY REP

SIGNAL REP

FES

FORCE PROTECTION

CHIEF,

DESIGN & TECH. REVIEW Br.

O & M

HOUSING DIV.

REVIEWED BY

SYMBOL BY CHK.ZONE DATE APVD.

R E V I S I O N S

DESCRIPTION

UNITED STATES ARMY GARRISION DAEGU

DIRECTORATE OF PUBLIC WORK

UNIT #15746, APO AP 96218-5746

DATE:

E-5

SHEET OF

SIN, YS

KIM, CK

11 19

MAIN DISTRIBUTION CABLE

REPLACE DAMAGED 22.9KV UNDERGROUND

CAMP CARROLL

HS-00517-5J

0 120003000 6000

SCALE: 1:300

- E5

P-1 ELECTRICAL DISTRIBUTION PLAN - 4

D

S-532

N E

B R

A S

E

N U

E

S-842

S-676

T

DHM-06 H

M

EMHM-06

M

H DHM-07

EMHM-07

D

/D

/D

D D

SCALE : 1 / 300

KEY PLAN

T-377

T-619

S -9

T-813

S T O

R A G E

O R

G A N

IZ

A T

IO

N A L

S

MATCH LINE. SEE SHEET E-4

MATCH LINE. SEE SHEET E-6

P M J

(REUSE EXISTING DUCT)

IN 155mmC DUCT WITH DUCT CLEANING

& 1-750KCMIL, 600V, POWER CABLE

REPLACE 2SET OF 3-750KVMIL, 25KV "XLP"

CLEAN EXISTING ELECTRICAL MANHOLE

CLEAN EXISTING ELECTRICAL MANHOLE

DUCT WITH PULL WIRE

IN 155mmC DUCT AND 4-155mmC SPARE

& 1-750KCMIL, 600V, POWER CABLE

PROVIDE 4SET OF 3-750KVMIL, 25KV "XLP"

21 SEP 16

D - 16 - 18

ELECTRICAL DISTRIBUTION PLAN - 4

INSTALL DETAIL SHEET NO. E-12

600A, 25KV, 2WAY JUNCTION(GFM) SEE

AS SHOWN

HGFEDCBA

DESIGNED BY

CHECKED BY

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :SAFETY REP

SIGNAL REP

FES

FORCE PROTECTION

CHIEF,

DESIGN & TECH. REVIEW Br.

O & M

HOUSING DIV.

REVIEWED BY

SYMBOL BY CHK.ZONE DATE APVD.

R E V I S I O N S

DESCRIPTION

UNITED STATES ARMY GARRISION DAEGU

DIRECTORATE OF PUBLIC WORK

UNIT #15746, APO AP 96218-5746

DATE:

E-6

SHEET OF

SIN, YS

KIM, CK

12 19

MAIN DISTRIBUTION CABLE

REPLACE DAMAGED 22.9KV UNDERGROUND

CAMP CARROLL

HS-00517-5J

0 120003000 6000

SCALE: 1:300

- E6

P-1 ELECTRICAL DISTRIBUTION PLAN - 5

S -3

S-3

T-369

S -3

S-840

S

S-

S-5

T-503 Bus Stop 1

DHM-08

EMHM-08 HM

D

D

/D

/D

/D

D

SCALE : 1 / 300

KEY PLAN

T-377

T-619

S -9

T-813

S T O

R A G E

O R

G A N

IZ

A T

IO

N A L

S

MATCH LINE. SEE SHEET E-5

MATCH LINE. SEE SHEET E-7

P M J

CLEAN EXISTING ELECTRICAL MANHOLE

(REUSE EXISTING DUCT)

IN 155mmC DUCT WITH DUCT CLEANING

& 1-750KCMIL, 600V, POWER CABLE

REPLACE 2SET OF 3-750KVMIL, 25KV "XLP"

DUCT WITH PULL WIRE

IN 155mmC DUCT AND 2-155mmC SPARE

& 1-750KCMIL, 600V, POWER CABLE

PROVIDE 4SET OF 3-750KVMIL, 25KV "XLP"

21 SEP 16

D - 16 - 18

ELECTRICAL DISTRIBUTION PLAN - 5

INSTALL DETAIL SHEET NO. E-12

600A, 25KV, 2 WAY JUNCTION(GFM) SEE

AS SHOWN

HGFEDCBA

DESIGNED BY

CHECKED BY

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :SAFETY REP

SIGNAL REP

FES

FORCE PROTECTION

CHIEF,

DESIGN & TECH. REVIEW Br.

O & M

HOUSING DIV.

REVIEWED BY

SYMBOL BY CHK.ZONE DATE APVD.

R E V I S I O N S

DESCRIPTION

UNITED STATES ARMY GARRISION DAEGU

DIRECTORATE OF PUBLIC WORK

UNIT #15746, APO AP 96218-5746

DATE:

E-7

SHEET OF

SIN, YS

KIM, CK

13 19

MAIN DISTRIBUTION CABLE

REPLACE DAMAGED 22.9KV UNDERGROUND

CAMP CARROLL

HS-00517-5J

0 120003000 6000

SCALE: 1:300

EMHM-09

- E7

P-1 ELECTRICAL DISTRIBUTION PLAN - 6

S

N E B

R A S

E

N U

E

S-860 Substation Electrical x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x

BANK

CAP

BANK

CAP

T

T

S-349

T -3

S-320

S -3

S-328

S-321

++ M

H

S-340

DHM-10

DHM-09

/D

D

D

/D

D

D

H

/D

SCALE : 1 / 300

KEY PLAN

T-377

T-619

S -9

T-813

S T O

R A G E

O R

G A N

IZ

A T

IO

N A L

S

MATCH LINE. SEE SHEET E-6

SEE

ENLARGED PLAN

- E9

P-1

CLEAN EXISTING ELECTRICAL MANHOLE

(REUSE EXISTING DUCT)

IN 155mmC DUCT WITH DUCT CLEANING

& 1-750KCMIL, 600V, POWER CABLE

REPLACE 2SET OF 3-750KVMIL, 25KV "XLP"

21 SEP 16

ELECTRICAL DISTRIBUTION PLAN - 6

AS SHOWN

HGFEDCBA

DESIGNED BY

CHECKED BY

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :SAFETY REP

SIGNAL REP

FES

FORCE PROTECTION

CHIEF,

DESIGN & TECH. REVIEW Br.

O & M

HOUSING DIV.

REVIEWED BY

SYMBOL BY CHK.ZONE DATE APVD.

R E V I S I O N S

DESCRIPTION

UNITED STATES ARMY GARRISION DAEGU

DIRECTORATE OF PUBLIC WORK

UNIT #15746, APO AP 96218-5746

DATE:

E-8

SHEET OF

SIN, YS

KIM, CK

14 19

MAIN DISTRIBUTION CABLE

REPLACE DAMAGED 22.9KV UNDERGROUND

CAMP CARROLL

HS-00517-5J

N x x x x x x x x xx x x x x

(NOTE 1)

TO KEPCO 22.9KV BUS

1500 914.6 914.6 1220

1200 1220 1220 1500

XFMR

SERVICE

STATION

M1

VCB

M2

VCB

MOF

KEPCO

MOF

KEPCO

NFSM

SLOPE

1500 914.6 914.6

1220 1200 1220 1220 1500

- E8

P-1

- E8

P-2

SCALE: 1:50

500 1000 2000

SCALE : 1 / 50

FRONT ELEVATION

SEE SH. "E-2"

TO EMHM-01

(TO BE REMAIN)

600V CABLE IN 155mmDBPVC

3-#750 KCMIL, 25KV & 1-750KCMIL,

22.9KV SWITCHING STATION NO.1

SCALE : 1 / 50

INSTALLED BY KEPCO

ENCLOSURE(WP) SUPPLIED &

REPAIR EXISTING METERING &

& 1-750KCMIL, 600V CABLE WITH NEW

REPLACE EXISTING 3-#750 KCMIL, 25KV

SERVICE TRANSFORMER(SEE NOTES)

PANELBOARDS AND STATION

REPAIR AUXILLIARY SECTION FOR

NOTES)

CIRCUIT BREAKER, 22.9KV(SEE

REPAIR EXISTING VACUUM TYPE

- E8

D-1

NOT TO SCALE

PAD MTD JUNCTION DETAILS

PAD MTD JUNCTION DETAILS

22.9KV SWITCHING STATION NO.1 AND

(REUSE EXISTING DUCT)

1-750KCMIL, 600V CABLE IN 155mmPVC

REPLACE 3-#750 KCMIL, 25KV &

WIRE MESH

WITH 6"X6" - W2.9 X 2.9

CONC. PAD REINFORCED

#1/0 AWG DAWG "BC"

GROUND WIRE,

WIRE MESH

WITH 6"X6 - W2.9XW2.9

CONC. PAD REINFORCED

WITH MASONRY GROUT FILL

RECTANGULAR HOLE

DESCRIPTIONSITEM

600A 15/25KV CLASS 2-WAY DEADBREAK JUNCTION

ADJUSTABLE LOCATION STAINLESS STEEL PARKING STAND

600A 15KV/25KV CLASS STANDOFF BUSHING FOR PARKING

316 STAINLESS STL MOUNTING BAR & PARKING

CLIP MOUNTING RAILS

GROUND BAR, #2AWG SOLID COPPER

FOR SPARE BUSING ON JUNCTIONS

600A 15/25KV CLASS INSULATED PROTECTIVE CAP

GROUND ROD, COPPER CLAD STEEL,

19mmDIA X 3m LG WITH

WELDING CONNECTION

GRAVEL SUB-BASE

6" 100% WELL COMPACTED

100% COMPACTION

BEYOND PAD ON ALL AROUND

A MINIMUM OF 1 FOOT

EXTEND GRAVELFILL

600A 15/25KV CLASS DEADBREAK CONNECTOR FOR 750KCMIL

DANGER

PMJ

NOTE :

W/ ASSIGNMENT NUMBER

PROVIDE EACH PMJ

+176°F, ROUND CORNERS, 3/16" HOLES

POLISH VINYL PLASTIC, -40°F,

SETON M2325 HPP 60MIL

10"

(254)

(1

MASONRY GROUT, 76mm THK

NOTES:

B.

A. CABLE JUNCTION PEDESTAL SHALL BE MANUFACTURED BY

SHALL BE PROTECTED BY THE INSULATED PROTECTIVE CAPS

ALL SPARE BUSHINGS ON THE JUNCTIONS AND STANDOFF BUSHING

NTS

PMJ ASSIGNMENT SIGN

INCLUDE SS LOUVERS

FIBERGLASS ENCLOSURE, NOMINAL THICKNESS 1/ 4 NOMINAL THICKNESS

15641264

"POWER DESIGN INC." OR APPROVED EQUAL.

AS SHOWN

HGFEDCBA

DESIGNED BY

CHECKED BY

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :SAFETY REP

SIGNAL REP

FES

FORCE PROTECTION

CHIEF,

DESIGN & TECH. REVIEW Br.

O & M

HOUSING DIV.

REVIEWED BY

SYMBOL BY CHK.ZONE DATE APVD.

R E V I S I O N S

DESCRIPTION

UNITED STATES ARMY GARRISION DAEGU

DIRECTORATE OF PUBLIC WORK

UNIT #15746, APO AP 96218-5746

DATE:

E-9

SHEET OF

SIN, YS

KIM, CK

15 19

MAIN DISTRIBUTION CABLE

REPLACE DAMAGED 22.9KV UNDERGROUND

CAMP CARROLL

HS-00517-5J

N x x x x x x x x x x x x x x x x x x x x x x x x x x x xx xx xx xx xx x

X X X X X

BANK

CAP

BANK

CAP

3200 2000 3200

18000

914.61200914.6914.6914.6914.6 914.6 914.6 914.6 914.6 914.6 914.6 914.6

FRONT

11 9 3 2 1A

- E9

P-1

- E9

P-2

22.9KV SWITCHING STATION NO.2

FRONT ELEVATION

SCALE : 1 / 50

SCALE: 1:50

500 1000 2000

SCALE : 1 / 50

SEE SHT "E-7"

FROM EMHM-09

NO.

ITEM

EQUIPMENT DESCRIPTION

FEEDER NO. 1 CIRCUIT BREAKER COMPARTMENT

FEEDER NO. 3 CIRCUIT BREAKER COMPARTMENT(SPARE)

TIE-IN BREAKER COMPARTMENT, NORMALLY OPEN

FEEDER NO. 2 CIRCUIT BREAKER COMPARTMENT

FEEDER NO. 4 CIRCUIT BREAKER COMPARTMENT(SPARE)

TRANSITION FOR TIE-IN BREAKER COMPARTMENT

22.9KV SWITCHING STATION N0.2

MAIN BREAKER "A" COMPARTMENT

MAIN BREAKER "B" COMPARTMENT

FEEDER NO. C1 CIRCUIT BREAKER COMPARTMENT FOR CAPACITOR BANK BUS "A"

FEEDER NO. C2 CIRCUIT BREAKER COMPARTMENT FOR CAPACITOR BANK BUS "B"

11A

SPACE FOR FEEDER BREAKER

SPACE FOR FEEDER BREAKER

1A

11A

11 8 7 6 5 4

13 12

(TO BE REMAIN)

1-155mm PVC SPARE DUCT

(TO BE REMAIN)

1-155mm PVC SPARE DUCT

(TO BE REMAIN)

& 1-500KCMIL, 600V IN 155mmPVC

FEEDER NO.2: 3-#500KCMIL, 25KV

(TO BE REMAIN)

& 1-500KCMIL, 600V, IN 155mmPVC

FEEDER NO.1: 3-#500KCMIL, 25KV

SPACE

SPACE

(EMPTY) (TO BE REMAIN)

EXISTING 2-27mm EACH PVC 103mmPVC(TO BE REMAIN)

1-#2 AWG(G) 600V IN

3-#4/0 AWG 25KV XLPE &

(TO BE REMAIN)

INNER DUCT(SPARE)

2-78mmPVC W/2-27mm

22.9KV SWITCHING STATION NO.2

DC PANEL AND CHARGER AND REMOTE CONTROL UNIT(RTU)

PROTECTIONS, STATION SERVICE PANEL "MDP", 48 V BATTERIES,

STATION SERVICE TRANSFORMER COMPLETE W/ OVERCURRENT

CAPACITOR BANK "A", 600 KVAR W/BLOCK SHORTING SWITCH

CAPACITOR BANK "B", 1800 KVAR W/BLOCK SHORTING SWITCH

FUTURE

SPACE

FUTURE

SPACE

NFSM 15

18000

914.6 914.6 914.6 914.6 1200 914.6914.6914.6914.6914.6914.6914.6914.6

2-155C SPARE(REUSE EXISTING DUCT)

1-750KCMIL, 600V IN 155mmPVC)

REPLACE 2(3-#750KCMIL, 25KV &

AS SHOWN

HGFEDCBA

DESIGNED BY

CHECKED BY

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :SAFETY REP

SIGNAL REP

FES

FORCE PROTECTION

CHIEF,

DESIGN & TECH. REVIEW Br.

O & M

HOUSING DIV.

REVIEWED BY

SYMBOL BY CHK.ZONE DATE APVD.

R E V I S I O N S

DESCRIPTION

UNITED STATES ARMY GARRISION DAEGU

DIRECTORATE OF PUBLIC WORK

UNIT #15746, APO AP 96218-5746

DATE:

E-10

SHEET OF

SIN, YS

KIM, CK

16 19

MAIN DISTRIBUTION CABLE

REPLACE DAMAGED 22.9KV UNDERGROUND

CAMP CARROLL

HS-00517-5J

LEGEND:

POTENTIAL TRANSFORMER

CURRENT TRANSFORMER

KILOWATT HOUR METER

PHASE OVERCURRENT RELAY,

TIME INVERSE

GROUND OVERCURRENT RELAY,

INSTANTANEOUS

WHM

51N

PT

CT

PHASE OVERCURRENT RELAY,

INSTANTANEOUS

52-X

KEY INTERLOCK

CLF CURRENT LIMITING FUSE

SURGE ARRESTER STATION

CLASS 18KV

MOF METERING OUTFIT

K

27 UNDERVOLTAGE RELAY

AMMETER SWITCH

AMMETER

POWER FACTOR METER

VOLTMETER

VOLTMETER SWITCH

VARMETER

67N

DIRECTIONAL OVERCURRENT RELAY,

GROUND

DIRECTIONAL OVERCURRENT RELAY,

PHASE

STATION SERVICE

PANEL "DP"

48 V BATTERIES

DC PANEL AND

CHARGER

30A, 2P, 240V MTS

IN NEMA 1 ENCL

30 A, 2P

(TYP)

TO PT 52-M2 TO PT 52-M1

SSM

86 51N51TYPICAL

TYPICAL

THROUGH 86 50/51

86 51 51N

67N 27

86 51N51

86 LOCKOUT RELAY

BUS DIFFERENTIAL

SD CAPACITOR BANK SWITCHING DEVICE

ACD AUTOMATIC CONTROL DEVICE

RTU

SCADA

SOLID STATE MICROPROCESSOR

67N

86 50/51 50/51N

VACUUM BREAKER, DRAW OUT TYPE,

1200A OR 600A, 27KV

KILOWATT DEMAND METER

REMOTE TERMINAL UNIT

(FUTURE - PHASE 2)

SUPERVISORY CONTROL AND

DATA ACQUISITION (FUTURE - PHASE 2)

50/51

PHASE AND GROUND

OVERCURRENT RELAY

50GS ZERO SEQUENCE GROUND SENSOR

50GS

SUBSTATION ND PRIMARY LINE (BY KEPCO)

WHM

D

KILOWATT HOUR METER W/ DEMAND REGISTER

SSM-C2

SSM-C1

SSM-T

SSM-4

SSM-1

SSM-B

SSM-A

SSM-M2

SSM-M1

W

VS

VAR

V

PF

AS

A

CLF

PT

22.9KV/120V

CLF

PT

22.9KV/120V

SWITCHING STATION "NO. 1"

KILOWATT HOUR METER KILOWATT HOUR METER

LA

3-18KV

CLF CLF

PT PT

TO "DP"

#2/0 AWG BC

IN 21mm PVC

LA

3-18KV

#2/0 AWG BC

IN 21mm PVC

22.9KV/

120/240V, 5KVA

SERVICE XFMR

VCB

1200A

25KA

VCB

1200A

25KA

#6 AWG BC

IN 16mm PVC

TO RTU

TO SWITCHING STATION NO. 2,

FOR CONT. SEE SHT "E-2"

22.9KV BUS

3-CTS

1200/5A

3-CTS

1200/5A

3-CTS

1200/5A

3-CTS

1200/5A

3-CTS

1200/5A

3-CTS

1200/5A

#6 AWG BC

IN 16mm PVC (TYP)

22.9KV LINE

(BY KEPCO)

3-750KCMIL, 25KV &

1-750KCMIL, 600V

IN 155mm PVC DB

3-750 KCMIL, 25KV XLPE &

1-750 KCMIL, 600 V

IN 155mm PVC

EXISTING KEPCO

SUBSTATION BETWEEN

GATE #1 AND #2 OF

D

PT

10/12 MVA 10/12 MVA

WHM VS VWHMVSV

D

WHM WHM

52-M2 52-M1

AS

A

SSM-M1

AS

A

SSM-M2

PF PF

22.9KV SWITCHING STATION NO.1 - SINGLE LINE DIAGRAM

SERVICE PANEL BLOCK DIAGRAM

INCOMING LINE STATION

NOT TO SCALE

NOT TO SCALE

EXISTING 5.7/3.3KV

CAMP CARROLL.

LINE STATION DRAGRAM AND LEGEND

22.9KV SWITCHING STATION NO.1, INCOMING

REPAIR DAMAGED MOF REPAIR DAMAGED MOF

OR APPROVED EQUAL

BASED PROTECTIVE RELAYS "GIPAM-2000F1"

(TYP OF 2EA)

& MONITORING EQUIPMENT

DIGITAL INTEGRATED PROTECTION

REPLACE EXISTING WITH NEW

- E10

D-1

- E10

D-2

- KEPSCO CERTIFICATION TEST

ACCESSORIES ON EACH PANEL

- CLEAN VCB, PT, SWITCH AND ASSOCIATED

- PT OPERATION TEST ON EACH PANEL

- ALL VCB OPERATION/FUNCTION TEST

- RELAY OPERATION TEST ON EACH PANEL

- REPLACE RELAY WITH DOOR ON EACH PANEL

- REPLACE CONTROL WIRES ON EACH PANEL

- PROVIDE FAN WITH COVER TO PROTECT INCOMING DUST

- PROVIDE THERMOSTAT TO CONTROL HEATER

- REPLACE 2EA SPACE HEATER ON EACH PANEL

DETAIL SCOPE OF WORK

AS SHOWN

HGFEDCBA

DESIGNED BY

CHECKED BY

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :SAFETY REP

SIGNAL REP

FES

FORCE PROTECTION

CHIEF,

DESIGN & TECH. REVIEW Br.

O & M

HOUSING DIV.

REVIEWED BY

SYMBOL BY CHK.ZONE DATE APVD.

R E V I S I O N S

DESCRIPTION

UNITED STATES ARMY GARRISION DAEGU

DIRECTORATE OF PUBLIC WORK

UNIT #15746, APO AP 96218-5746

DATE:

E-11

SHEET OF

SIN, YS

KIM, CK

17 19

MAIN DISTRIBUTION CABLE

REPLACE DAMAGED 22.9KV UNDERGROUND

CAMP CARROLL

HS-00517-5J

3-CTS

600/5A

VCB

TIE N.O.

1200A

SWITCHING STATION "NO. 2" (25KV)

RTU

3-LA

18KV

3-CTS

600/5A

CLFCLF

PT’S

22.9KV/120V

SPARE

VCB

600A

16KA

1200A

16KA

MAIN VCB

1200A

16KA

155mm DIA.

EMPTY DUCT

155mm DIA.

EMPTY DUCT

EMH2-01 EMH1-01

#2/0 AWG BC

IN 21mm PVC

CLF CLF

3-CTS

600/5A

3-CTS

600/5A

VCB

600A

16KA

3-CTS

600/5A

3-CTS

600/5A

VCB

600A

16KA

3-CTS

600/5A

3-CTS

600/5A

VCB

600A

16KA

G

CLF

FUSE 2A

#6 AWG BC

IN 16mm PVC

#1/0 AWG BC

IN 21mm PVC

(TYP)

15KVA, 1PH STATION

3-CTS

600/5A

3-CTS

600/5A

87A 3-CTS

600/5A

3-CTS

600/5A

87B

3-CTS

600/5A

SD

PT

#6 AWG

GND WIRE

VCB

600A

16KA

3-CTS

600/5A

3-CTS

600/5A

SD

PT

#2 AWG

GND WIRE

#6 AWG

GND WIRE

VCB

600A

16KA

SPARE FEEDER NO.2

TO SWITCHING STATION NO. 1,

FDR NO. 1

3LAS

18KV

(TYP)

3-CTS

600/5A

CT

50/5A

CT

50/5A

CT

50/5A

CT

50/5A

CT

50/5A

CT

50/5A

3-CTS

1200/5A

3-CTS

1200/5A

3-CTS

1200/5A

3-CTS

1200/5A

3-CTS

1200/5A

3-CTS

1200/5A

3-CTS

1200/5A

3-#4/0 AWG,

25KV XLPE,

1-#2 AWG (G),

600V IN 103mm DIA. DUCT

87A 87B

CAP BANK

1800 KVAR

CAP BANK

600 KVAR

(NOTE 6)

22.9KV BUS "B" 1200A CU, 4W + N + 25% G, 16KA MIN 22.9KV BUS "A" 1200A CU, 4W + N + 25% G, 16KA MIN

3-500 KCMIL, 25KV XLPE &

1-500 KCMIL

600V IN 155mm DIA. DUCT

3-500 KCMIL, 25KV XLPE &

1-500 KCMIL

600V IN 155mm DIA. DUCT

3-750 KCMIL, 25KV XLPE &

1-750 KCMIL, 600V IN 155C PVC

3-CTS

1200/5A

3-CTS

1200/5A

87A 87B

K

VVS

AS

A

VAR PFW

AS

A

W PF

52-B 52-A

52-352-4 52-2 52-1

52-T

SSM-A

V VS

AS

A

VARPF W

SSM-1

AS

A

W PF

SSM-3

AS

A

W PF

SSM-2

AS

A

W PF

SSM-4

SSM-T

SSM-B

86B

87B

86A

87A

AS

A

PF

ACD

52-C2 SSM-C2

AS

A

PF

ACD

52-C1 SSM-C1

27 27

#2 AWG

GND WIRE

PROVISION FOR

FUTURE EXPANSION

3-#4/0 AWG,

25KV XLPE,

1-#2 AWG (G), 600V

POWER CABLE IN

103mm DUCT DUCT

3-LA

18KV

PT’S

22.9KV/120V

22.9KV SWITCHING STATION NO.2 - SINGLE LINE DIAGRAM

NOT TO SCALE

SINGLE LINE DIAGRAM

22.9KV SWITCHING STATION NO.2

FOR CONT. SEE SHT "E-7"

SERVICE XFMR

(TYP OF 9EA)

& MONITORING EQUIPMENT

DIGITAL INTEGRATED PROTECTION

REPLACE EXISTING WITH NEW

- E11

D-1 DETAIL SCOPE OF WORK

21 SEP 16

D - 16 - 18

22.9 KV TO 120/240V

REPLACE EXISTING

TRANSFORMER 22.9KV TO 120/ 240V 15KVA

- REPLACE EXISTING STATION SERVICE

- KEPSCO CERTIFICATION TEST

ACCESSORIES ON EACH PANEL

- CLEAN VCB, PT, SWITCH AND ASSOCIATED

INCLUDE REPLACE BROKEN FUSES

- PT OPERATION TEST ON EACH PANEL

- ALL VCB OPERATION/FUNCTION TEST

- RELAY OPERATION TEST ON EACH PANEL

- REPLACE RELAY WITH DOOR ON EACH PANEL

- REPLACE CONTROL WIRES ON EACH PANEL

- PROVIDE FAN WITH COVER TO PROTECT INCOMING DUST

- PROVIDE THERMOSTAT TO CONTROL HEATER

- REPLACE 2EA SPACE HEATER ON EACH PANEL

AS SHOWN

HGFEDCBA

DESIGNED BY

CHECKED BY

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :SAFETY REP

SIGNAL REP

FES

FORCE PROTECTION

CHIEF,

DESIGN & TECH. REVIEW Br.

O & M

HOUSING DIV.

REVIEWED BY

SYMBOL BY CHK.ZONE DATE APVD.

R E V I S I O N S

DESCRIPTION

UNITED STATES ARMY GARRISION DAEGU

DIRECTORATE OF PUBLIC WORK

UNIT #15746, APO AP 96218-5746

DATE:

E-12

SHEET OF

SIN, YS

KIM, CK

18 19

MAIN DISTRIBUTION CABLE

REPLACE DAMAGED 22.9KV UNDERGROUND

CAMP CARROLL

HS-00517-5J

NOT TO SCALE- E12

D-1

G R

O U

N D

L

IN

E

THRU HOLE FOR

PADLOCKING

CAST BRONZE

HASP BLOCK

CAPTIVE RECESSED

SS 1/2 13 NC PENTA

HEAD BOLT

PEBESTAL LID

EXTERIOR

PLASTIC WIRE

STOP LID LINER

DF3 HASP

ITEM

SS ADJUSTABLE PARKING CLIP (6X)

SPM-540 UNIV. SS JUNCTION MOUNTING BAR

PNL-1/0 BOLTED GROUND CONNECTOR

GAS SPRING LID SUPPORT 60 #-15 (2X)

NOTES:

B. MOUNTING BAR WILL WITHSTAND A MINIMUM 400-LB

LOADING TO INSTALL OR REMOVE ELBOWS

CONCRETE PAD REINFORCED

GRAVEL SUB-BASE

300GL

G

NFSM

G

NFSM

COPPER CLAD STEEL

19diax3000mmLG WITH

GROUND ROD

GROUNDING WIRE

DESCRIPTIONS

A. CABLE JUNCTION PEDESTAL SHALL BE MANUFACTURED BY

CHAMFER

316 STAINLESS STL SLIDING PARKING CLIP MOUNTING BARS

3000PSI-28DAYS

100% WELL COMPACTED

DETAIL "A"

9 MOUNT "DANGER HIGH VOLTAGE" SIGN

CABLE JUNCTION PEDESTAL INSTALL DETAIL

TYP.

ANCHOR LEDGES,

3/16" THK 316 S/S

TYP.

CHAMFER EDGES SLACK

5M (15’) GENEROUS

LENGTH AS REQUIRED

ACCESS

FRONT

AS REQ’D

BOLTS & NUTS

3/6 S/S

(TYPICAL)

NUTS, 316 S/S, TYP.

316" LEDGE, BOLTS,

-40OF, +1760F, ROUND CORNERS

60MIL PRESS POLISH VINYL PLASTIC

SETON: (HHP) M2404

VOLTAGE

HIGH

M2404

10"

DANGER

END SECTIONFRONT SECTON

SCHEMATIC CONNECTORS

TOP VIEW

DETAIL ’A’DF3 HASP DETAIL

SIGN

(254)

(1

PHASE "A" PHASE "B" PHASE "C"

NOTE : PROVIDE SIGNS AS NOTED.

NTS

FDR C

KCMIL

SETON M4860

-40°F, +185°F 8"L

NYLON TIE/LOCK

M4500

19 GAUGE, 3/16" HOLE, M4500

BRASS TAGS, 1/4" LETTERING, 1/2H NUMBERS

SETON:

CABLE TAG

(5)

2" OCTAGON

NTS

PROVIDE CABLE ASSIGNMENT TAGS.

NOTE :

CABLE LOADBREAK CONNECTORS, 600A(FOR 750KCMIL), 25KV

C. MINIMUM MATERIAL THICKNESS - 4.76mm(3/16")

MODEL NO. CJP-40-56-L2-WG-6225-GB2 FIBERGLASS PEDESTAL

"POWER DESIGN INC." OR APPROVED EQUAL.

0dia.WIRE MESH

WITH 150x150x-4.0dia.x4.

#2/0 "BC",

WELDING CONNECTION

CABLE JUNCTION PEDESTAL INSTALL DETAIL(TYPICAL)

RTE 25 KV, 600 AMP 2-WAY JUNCTIONS (4X)

AS SHOWN

HGFEDCBA

DESIGNED BY

CHECKED BY

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :SAFETY REP

SIGNAL REP

FES

FORCE PROTECTION

CHIEF,

DESIGN & TECH. REVIEW Br.

O & M

HOUSING DIV.

REVIEWED BY

SYMBOL BY CHK.ZONE DATE APVD.

R E V I S I O N S

DESCRIPTION

UNITED STATES ARMY GARRISION DAEGU

DIRECTORATE OF PUBLIC WORK

UNIT #15746, APO AP 96218-5746

DATE:

E-13

SHEET OF

SIN, YS

KIM, CK

19 19

MAIN DISTRIBUTION CABLE

REPLACE DAMAGED 22.9KV UNDERGROUND

CAMP CARROLL

HS-00517-5J

NOT TO SCALE- E13

D-4

NOTES:

8 WAY

1. PROVIDE ENOUGH CLEARANCE ON BOTH SIDES

OF TRENCH TO FACILITATE INSTALLATION

& REMOVAL OF FORMS ON SIDES OF CONCRETE

ENCASED DUCTS.

2. INSTALL ONE 13mm DOUBLE BRAID HIGH STRENGTH

76 50

(WIDTH OF CUT VARIES)

1 1

SAW CUT

& APPLY TACK

COAT

EXST AC

PAVEMENT

EXST

BASE

EXST

SUB BASE

NEW AC PAVEMENT

NEW ASPHALT

SURFACE COAT

NEW PRIME COAT

WARNING TAPE

COMPACT THE TOP 6" (152)

OF ALL SUBGRADE CUTS TO A MIN.

OF 90% MAX. DENSITY FOR COHESIVE

MATERIAL & 95% MAX. DENSITY FOR

COHESION LESS MATERIAL

AGGREGATE BASE

COURSE COMPACTED

TO A MIN OF 100%

MAX. DENSITY

WIDTH

DUCT

DUCT

THICKNESS

WARNING TAPE

COMPACTED

BACKFILL

M

IN

EXST FIN

GRADE (WIDTH OF CUT VARIES)

RESTORE GRADE TO EXST CONDITION

COMPACTED BACKFILL

SUB BASE

COMPACTED

TO 100% MAX

DENSITY

CONCRETE ENCASED

DUCT, NUMBER AS

INDICATED ON PLANS.

CONCRETE ENCASED DUCT

6 WAY AS INDICATED IN PLAN

229 229

MIN

MIN

229 229

DUCT THICKNESS

INITIAL BACKFILL

MATERIAL

(M

IN

(M

IN

INITIAL

BACKFILL

MATERIAL

(MIN. 8500 LB TENSILE STRENGTH) POLYESTER

PULL ROPE IN EACH SPARE CONDUIT WITH A MIN

600mm SPARE CORD PROTRUDING FROM EACH END.

BASE SPACERS

INTERMEDIATE

SPACERS

PVC CONDUIT

INTERMEDIATE

SPACERS

BASE

SPACER

76 76

152 7676

BASE SPACER

NOT TO SCALE

(NON TRAFFIC AREA)

NOT TO SCALE (TRAFFIC AREA)

INTERMEDIATE SPACER

- E13

D-3

- E13

D-1

- E13

D-2

- E13

P-1

INSTALLATION DETAIL

PRIMARY DUCT & TRENCH SECTION AND

168 168

PRIMARY DUCT & TRENCH SECTION - AC PAVEMENT(TYPICAL)

PRIMARY DUCT & TRENCH SECTION(TYPICAL)

SPACER POSITIONING(TYPICAL)

PRIMARY DUCT SECTION DETAIL(TYPICAL)

SPACER DETAIL(TYPICAL)

CONC ENCASEMENT

2500 PSI

INTERMEDIATE SPACER

(TYPICAL)

(TYPICAL)

BASE SPACER

168 16850

HS-00517-5J_T01
HS-00517-5J_C01
HS-00517-5J_C02
HS-00517-5J_C03
HS-00517-5J_C04
HS-00517-5J_C05
HS-00517-5J_C06
HS-00517-5J_E01
HS-00517-5J_E02
HS-00517-5J_E03
HS-00517-5J_E04
HS-00517-5J_E05
HS-00517-5J_E06
HS-00517-5J_E07
HS-00517-5J_E08
HS-00517-5J_E09
HS-00517-5J_E10
HS-00517-5J_E11
HS-00517-5J_E12
HS-00517-5J_E13