SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
R-11SHEET OF
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
O & M
HOUSING DIV.
REVIEWED BY
AS SHOWN
UNITED STATES ARMY GARRISON DAEGU
ENGINEERING DIVISION, DESIGN & TECHNICAL REVIEW Br
DIRECTORATE OF PUBLIC WORK
HGFEDCBA
T I T L E S H E E T
D - 16 - 18
O, KI TAL
CHON, HYON TAE
DESIGN REVIEW SIGNATURE
ORGANIZATION
USING AGENCY
36TH SIGNAL
MASTER PLN.
ENVIRONMENTAL
NAME SIGNATURE
O&M DIV.
FIRE DEPT.
SAFETY OFFICE
DPTMS(AT/FP)
188TH MP COM.
IND. HYGENIST
HS-00517-5J
UNIT #15746, APO AP 96218-5746
C - 1
R - 1
DRAWING NO.
C - 23
CHIEF,
DESIGN & TECH. REVIEW Br.
TITLE SHEET
C - 34
PROJECT NO. HS-00517-5J, CAMP CARROLL
C - 56
E - 613
E - 714
CAMP CARROLL
MAIN DISTRIBUTION CABLE
REPLACE DAMAGED 22.9KV UNDERGROUND
MAIN DISTRIBUTION CABLE
REPLACE DAMAGED 22.9KV UNDERGROUND
E - 815
E - 916
E - 1017
E - 1118 22.9KV SWITCHING STATION NO.2 SINGLE LINE DIAGRAM
E - 1219
E - 1320
ELECTRICAL DISTRIBUTION PLAN - 5
ELECTRICAL DISTRIBUTION PLAN - 6
22.9KV SWITCHING STATION NO.1 AND PAD MTD JUNCTION DETAILS
22.9KV SWITCHING STATION NO.2
22.9KV SWITCHING STATION NO.1, INCOMING LINE STATION DRAGRAM AND LEGEND
CABLE JUNCTION PEDESTAL INSTALL DETAIL
PRIMARY DUCT & TRENCH SECTION AND INSTALLATION DETAIL
E - 512 11 OF 19 ELECTRICAL DISTRIBUTION PLAN - 4
E - 411 10 OF 19 ELECTRICAL DISTRIBUTION PLAN - 3
E - 310 ELECTRICAL DISTRIBUTION PLAN - 29 OF 19
E - 29 ELECTRICAL DISTRIBUTION PLAN - 18 OF 19
E - 1
ELECTRICAL
LEGEND, NOTES AND SCOPE OF WORK7 OF 19
CIVIL
C - 4
LOCATION PLAN
SITE LAYOUT PLAN-1
SITE LAYOUT PLAN-2
SITE LAYOUT PLAN-3
SECTION AND DETAILS
DATE: 21 SEP 16
C - 67 6 OF 19 SECTION AND DETAILS
CIVIL
AS SHOWN
HGFEDCBA
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
SHEET OF
UNITED STATES ARMY GARRISON DAEGU
DIRECTORATE OF PUBLIC WORKS
ENGINEERING DIVISION, DESIGN & TECHNICAL REVIEW Br
UNIT #15746, APO AP 96218-5746
DATE:
1 LOCATION PLAN
1 SCALE : 1 / 5000
LOCATION PLAN
C-1
N
THIS PROJECT
GRAPHIC SCALE
(IN METERS)
SCALE: 1 :5000
0 50 100 200
CAMP CARROLL
S-940 Tennis Court
S-294 Court Tennis
S-296 Court Tennis
S-165 Volleyball Court
S-980
STORY FIELD
LUTHER H.
T-646
S-671
S-672
S-673
S-674
S -644
T-780
T-508
S-86
S -7
S -7
S -7
T -6
T -5
T -7
T -5
S-961
T-533
T -5
S-714
S -8
T-377
T-584
T -3
T-3
S-531
T-417
T-863
T-765
T-368
T-507
T-772
S-967
T-924
T-575
T-696S-603
T-928
T-691
S-102
T-521
T-558
T-989
T-342
T-681
T-343
S-965
T-116
T-504
T-315
T-385
T-617
T-661
T-693
T-766
T-764
T-768
T-769
T-271
T-763
T-160
T-299
T-414
T-413
T-104
S-153
T-120
S-954
S-994
T-653
CEMETERY
S-860 Substation Electrical
S-360 Substation Electrical
S-576 Substation Electrical
S-133 bridge Foot
T-522
Footbridge
S-990 Footbridge
T-849 Footbridge
T-986 Footbridge
GATE 2
GATE 1
GATE 4
GATE 3
Gate Access
Railroad
Gate Access Farmer
Gate Access Farmer
S-118 Electronic Sign
S-952 Electronic Sign
S-781
Flag Pole
S-390
DEAD MEMORIAL
KOREAN WAR
S-741 Land Farm
T re a tm e n t
B e d
T re a tm e n t
B e d
Pond Holding
S-730
RANGE
QUALIFICATION
ZERO AND
25M RIFLE S-725
TESTING POND
BRIDGING BOAT
AMPITHEATRE
CAC
T-729 Storage Yard
Container
S-847
S-865 Bridge
Railroad
S-300 Road Bridge
S-860 Road Bridge
S-900 Road Bridge
S-500 Road Bridge
S-861 Road Bridge
A R
K A
N S
A S
N E
B R
A S
K A A
V E
N U
E
N E
W Y
O R
K A
V E
N U
E
A R
K A
N S
A S A
V E
N U
E
O H
IO
A
V E
N U
E
G E
O R
G
IA
A
V E
N U
E
T E
X A
S A
V E
N U
E
M O
N T A N
A A
V E N
U E
AVENUE
ILLINOIS AVENUE
A R
IZ
O N
A A
V E
N U
E
TENNESSEE AVENUE
N E
B R
A S
K A A
V E
N U
E
A M
E R
IC
A N A
V E N
U E
A R
K A
N S
A S A
V E
N U
E
PENN AVENUE
M
IS
S
IS
S
IP
P I
A V
E N
U E
A V
E N
U E
OHIO AVENUE
A M
E R
IC
A N A
V E N
U E
KENTUCKY AVENUE
G E
O R
G
IA
A
V E
N U
E
FLORIDA AVENUE
MISSISSIPPI
NEVADA
N E
W
N E
B R
A S
K A A
V E
N U
E
A M
E R
IC
A N A
V E N
U E
NEW YORK AVENUE
GEORGIA AVENUE
N E
B R
A S
K A A
V E
N U
E
OREGON
A V E N
U E
A V E N
U E
A V E N
U E
Y O
R K
PENN AVENUE
T-534
T-677
T-659
T-311
T-386
T-700
T-826
T-619
T-376
S-114
T-519
T-625
S-983
S-984
S-387
T-509B
T-509-2
T-578 Vehicle Scales
T-509-1
S-284
T-115
S-401
S-269
Bus Stop 10
S-383 Bus Stop 9
S-933 Bus Stop 6
S-621 Vehicle Scales
S-701
T-369
S-378
T-89
T-513
S-669 Station
Hunter Brake
S-328
S-329
T-509C
T-503 Bus Stop 1
S-622
T-624
S-639
T-416
T-827
S-350
T-415
T-979
S-667
S-705
T-926
T-577
T-720 Bus Stop 5
T-412
T-509D
T-509A
DUMP POINT
INDUSTRIAL WASTE
RECYCLING CENTER AND S-839
S-835
S-665
S-840
S-837
S-836
S-605
S-606
S-607
S-608
S-985
S-955
S-709
S-510
S-326
S-530
S-818
S-817
S-135
S-620
S-151
S-821
S-405
T-645
S-846
T -5
S-327
S -5
S-970
S-117
S-601
S-684
S-138
S-388
S-139
S-668
S-831
S-825
S-917
S-915
S -9
S-612
S -9
S-256
S-111
S-233
S-563
S-110
S-711
T-
S-231
S-396
S-230
S-100 S-235
S-375
S -9
S-136
S-403
T-565
S-253
S-250
S-977
S-676
S-254
S-573
S-946
S-998
S-203
S-841
S-123
S-938
S-657
S-914
T-516
S-341
S-911
S-113
T-520
S-913
S-141 S-143
S-142
S-264
S-731
S-101
S -309
S -2
S -7
S -9
T -9
T -9
S -9
S -9
S -2
S -9
S -6
S-675
S-320
S -8
S -8
S -9
T -5
T -9
S-9
S -9
S -3
T-318
S -4
S -6
S -3
S -8
S-9
S -6
S -8
S -8
T-126
S-121
T-125
T-127
T-207
S -1
T-236
S -9
S -6
T-206
S -3
S -9
T -3
S -3
S-154
S -9
S -8
S-974
S-321
S-
S-910S -4
S-340
S -6
S -7
S-349
S-301
S -611
T -3
S -6
S -7
S -7
S-140
S -6
S-718
S -7
S-137
S -6
S-842
S-351
S-512
S-205
S -5
S-336
S-239
S -9
S -3
S-267
S-509
T-359
S -3
S-532
S -9
S-655
S-208
T -7
S-702
S-163
S-304
T-515
S-733
S-732
S-642
S-627
T-384
S -3
T -5
T -3
S-312
S-666
S-420
S-973
T -3
T-580
S-679
T-996
S-925
T-997
S-931
T-631
T -2
S-131
S-919
T -3
T-521
S-395
S-397
S-918
S-944
T-195
T-196
T-198
T-197
T-194
T-199
S-119
S-739
S-3
S-647
T-261
S-164
S-626
S-58
T-130
S-717
S-402
T-572
T-189
T-406
T-193
T-958
S-88
S-348
T-581
S-265
S-640
S-953
S-411
S-664
S-654
S-344
S-511
S-982
S-968
S-929
T-155
S-972
T-582
S-771
S-95
T-409
S-948
S-916
S-947
S-957
T-192
S-956
S-719
T-762
S-770
S-162
S-161
T-317 Tower Cooling
T-923
S-93
S-922
T-814
T-812
T-569
T-635
S-995
T-810
T-280
T-811
T-633
T-103
T-813
T-637
T-636
S-741
TRAINING
CONFINED SPACE
BURN BUILDING AND
T-724
RESCUE
FIRE FIGHTING
S-845 Washrack
S-693 Washrack
S-404 Washrack
S-976 Washrack
S-939 Washrack
S-987 Washrack
S-316 Washrack
S-927 Washrack
T-6
S-703
PLANT
TREATMENT
SEWAGE
S-820
S-87
S-150
S-144
PLANT
TREATMENT
WATER
WETLAND
CAMP CARROLL
S-978 Substation Electrical
S-870
CLINIC
HEALTH/DENTAL
S T O
R A G E
O R
G A N
IZ
A T
IO
N A L
S
DFAC
TEMF
SEE SITE LAYOUT PLAN
1 19
21 SEP 16
HS-00517-5J
KU, HUN MO
CHI, K. K.
D - 16 - 18
MAIN DISTRIBUTION CABLE
REPLACE DAMAGED 22.9KV UNDERGROUND
-3 4
SHEET OF
KU, HUN MO
CIVIL
AS SHOWN
HGFEDCBA
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
UNITED STATES ARMY GARRISON DAEGU
DIRECTORATE OF PUBLIC WORKS
ENGINEERING DIVISION, DESIGN & TECHNICAL REVIEW Br
UNIT #15746, APO AP 96218-5746
DATE:
GRAPHIC SCALE
WITHOUT ANY ADDITIONAL COST.
INCLUDING FALSEWORK SUCH AS FORMWORKS AND SHORING
10. CONTRACTOR SHOULD PROVIDE ANY NECESSARY RESOURCES
LOCAL LAWS AND REGULATIONS.
GOVERNMENT LEASED PROPERTY IN ACCORDANCE WITH
11. DISPOSAL OF WASTE MATERIALS SHOULD BE OUTSIDE U.S
GENERAL NOTES :
COR PRIOR TO COMMENCING WORK ON THE PROJECT.
INDICATED BY THE COR AND SHOULD BE APPROVED BY THE
UNDETAILED PORTION OF THE JOB INCLUDING OTHER AREAS
2. THE CONTRACTOR SHOULD SUBMIT SHOP DRAWINGS FOR ANY
PERIOD IF REQUIRED.
AND DETOUR ROAD FOR VEHICLES DURING CONSTRUCTION
6. CONTRACTOR SHOULD PROVIDE TEMPORARY ACCESS ROAD
MILLIMETERS AND STATIONS AND ELEVATIONS ARE IN METERS.
15. UNLESS OTHERWISE NOTED ALL THE DIMENSIONS ARE IN
TO SUBMISSION OF CONTRACT PROPOSAL.
AND DIMENSIONS AT THE PROJECT SITE ORIENTATION PRIOR
1. THE CONTRACTOR SHOULD VERIFY ALL EXISTING CONDITIONS
CONTRACTING OFFICER.
THE CONTRACTORS EXPENSE TO THE SATISFACTION OF THE
DAMAGED BY DISMANTLING, DEMOLISHING, OR REMOVING AT
RESTORATION TO THEIR ORIGINAL CONDITIONS OF THE ITEMS
3. THE CONTRACTOR SHOULD BE RESPONSIBLE FOR REPAIR/
SHOULD BE COVERED WITH SOLID SODDING.
4. ALL UNPAVED AREAS WITHIN THE GRADING LIMIT LINE
CONSTRUCTION OPERATIONS.
LINES, AND OTHER ITEMS WHICH WILL INTERFERE WITH THE
SUCH AS UNDER GROUND ROCK BASE, EXISTING UTILITY
AND CLEARED/REROUTED OF ALL NATURAL OBSTRUCTIONS,
5. THE SITE INDICATED ON THE DRAWING SHOULD BE GRADED
AND OTHER UTILITY MARKERS IN THE PROJECT LIMIT.
7. CONTRACTOR SHALL RESTORE/REESTABLISH SURVEY MOUMENTS
OF FROST DEPTH UNLESS OTHERWISE NOTED.
9. WATER AND SEWER LINE SHOULD HAVE A MINIMUM COVER
OPERATIONS.
SAFETY OF THE PUBLIC AND/OR MILITARY TRAFFIC AND
ALL NECESSARY PRECAUTIONS FOR THE PROTECTION AND
CONES AND OTHER PROTECTIVE FACILITIES AND SHALL TAKE
NECESSARY SIGNS, LIGHTS, FLARES, BARRICADES, MARKERS,
14. CONTRACTOR SHALL PROVIDE, INSTALL AND MAINTAIN ALL
ACCOMPLISH THE CIVIL SCOPE OF WORK.
A PART OF THIS PROJECT. THE DETAILS WILL BE UTILIZED TO
MANAGEMENT COMMAND, KOREA REGION OFFICE" FORM AS
NOVEMBER 2015, DEPARTMENT OF THE ARMY INSTALLATION
DETAIL DRAWINGS, FOR O & MA PROJECT, KOREA, 30
8. THE CIVIL STANDARD DRAWINGS SHOWN IN THE "STANDARD
#2 (REPAIR/MAINTENANCE)
LEGEND:
ITEMS TO BE REMOVED
E/P
N
C-2
HS-00517-5J
CAMP CARROLL
EXISTING ELECTRICAL POLE
CHI, K. K.
GOVERNMENT.
AREA SHALL BE PROVIDED FOR THE CONTRACTOR BY THE
BE WITHIN THE CONSTRUCTION AREA AND NO LAY DOWN
ADMINISTRATIVE FIELD OFFICES AND STORAGE AREAS SHALL
SPEC. AT THE LOCATION APPROVED/INDICATED BY C.O.R.
CONTRACTOR’S TEMPORARY FACILITIES ACCORDING TO O&MA
12. CONTRACTOR SHOULD PROVIDE AND MAINTAIN THE
APPROVAL PRIOR TO COMMENCING THE PROJECT.
TO THE DESIGN AND TECHNICAL REVIEW BRANCH FOR
13. THE CONTRACTOR SHOULD PREPARE/SUBMIT MATERIAL REVIEWS
BASE COURSE AND SUBBASE COURSE
REMOVE/REPLACE EXST. AC PAVEMENT,
MAIN DISTRIBUTION CABLE
REPLACE DAMAGED 22.9KV UNDERGROUND
SCALE : 1 / 100
SCALE: 1 : 100
2000 4000
43.
AC
43.
AC
43.
AC
42.
AC
42.
AC
42.
AC
42.
AC
42.
AC
42.
AC
42.
AC
42.
AC
43.
AC
43.
AC
43.
AC
42.
AC
42.
MH
42.
MH
42.
MH
43.
DIT
CH
42.
DIT
CH
42.
DIT
CH
E/P
E/P
M/H
M/H
SITE LAYOUT PLAN-1
SITE LAYOUT PLAN-1
CCTV
GAS
DD
D
2,5
S-622
G
EXISTING CCTV AND POLE
CCTV
(ASSUMED)
EXISTING GAS LINE
1.
REMOVE/REPLACE EXISTING DRAIN LINE WITH NEW.
CONCRETE DITCH WITH NEW.
REMOVE/REPLACE EXISTING STEEL GRATING COVERED
BASE COURSE AND SUBBASE COURSE.
REMOVE/REPLACE EXISTING ASPHALT CONCRETE PAVEMENT,
3.
2.
1.
~AC~
SEE DETAIL
SAME AS EXISTING
PAVEMENT, BASE COURSE AND SUBBASE COURSE
REMOVE/REPLACE EXISTING ASPHALT CONCRETE
(M
IN.
SEE DETAIL
FOR GAS LINE
INSTALL CONCRETE PROTECTION SLAB
COVERED CONCRETE DITCH WITH NEW
REMOVE/REPLACE EXISTING STEEL GRATING
WITH NEW (D=450, RCP)
REMOVE/REPLACE EXISTING DRAIN LINE
E
E
TYPICAL SECTION
SEE ELEC. DRAWINGS AND
AND CONCRETE PADS
NEW PRIMARY JUNCTION PEDESTALS
3. SEE THE ELECTRICAL DRAWING FOR ELECTRICAL WORKS.
WITH SOLID SODDING.
2. ALL UNPAVED AREAS WITHIN THE GRADING LIMIT LINE SHOULD BE COVERED
ARE NOT SHOWN ON THE DRAWING AND RELOCATE/ REPLACE AS REQUIRED.
COMMUNICATION LINE, ELECTRICAL LINE, GAS LINE AND WATER LINE THAT
1. CONTRACTOR SHALL VERIFY THE LOCATION OF UTILITY LINES SUCH AS
NOTES:
D - 16 - 18
2 19
21 SEP 16
INSTALL CONCRETE PROTECTION SLAB.
SCOPE OF WORK (NEAR BLDG. #622)
#1 (CONSTRUCTION/ALTERATION)
CIVIL
AS SHOWN
HGFEDCBA
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
UNITED STATES ARMY GARRISON DAEGU
DIRECTORATE OF PUBLIC WORKS
ENGINEERING DIVISION, DESIGN & TECHNICAL REVIEW Br
UNIT #15746, APO AP 96218-5746
DATE:
GRAPHIC SCALE
LEGEND:
ITEMS TO BE REMOVED
E/P
HS-00517-5J
CAMP CARROLL
EXISTING ELECTRICAL POLE
CHI, K. K.
MAIN DISTRIBUTION CABLE
REPLACE DAMAGED 22.9KV UNDERGROUND
SCALE : 1 / 100
SCALE: 1 : 100
2000 4000
.0
A C
.9
D
IT
C H
.4
D
IT
C H
.2
D
IT
C H
.2
D
IT
C H
.4
D
IT
C H
.8
D
IT
C H
.7
D
IT
C H
.9
D
IT
C H
.7
S W
A L
K
M/H
M/H
FHT
WV
E/P
E/P
- 3
C-3
3 19
SITE LAYOUT PLAN-2
SITE LAYOUT PLAN-2
N
W W
G G
#1 (CONSTRUCTION/ALTERATION)
#2 (REPAIR/MAINTENANCE)
3.
2.
1.
(ASSUMED)
EXISTING GAS LINE
EXISTING TREES TO BE TRIMMED
COURSE AND SUBBASE COURSE
REMOVE/REPLACE EXST. AC PAVEMENT, BASE
~AC~
SEE DETAIL
SAME AS EXISTING
PAVEMENT, BASE COURSE AND SUBBASE COURSE
REMOVE/REPLACE EXISTING ASPHALT CONCRETE
SEE TYPICAL SECTION
AND HANDRAIL
CONSTRUCT CONCRETE RETAINING WALL
E
M/H
FHT
EXISTING FIRE HYDRANT
G/P
GUARD POST
INSTALL GUARD POSTS
INSTALL GUARD POSTS.
CONSTRUCT CONCRETE RETAINING WALL AND HANDRAIL.
2.
1.
(ASSUMED)
EXISTING WATER LINE2
,5
(M
IN
ACCESSORIES SAME AS EXISTING
INCLUDING NECESSARY FITTINGS AND
REMOVE/REPLACE EXISTING WATER LINE
E G/PG/PG/P
SEE ELEC. DRAWINGS
AND CONCRETE PADS
NEW PRIMARY JUNCTION PEDESTALS
THE GUIDANCE OF COR
IN ACCORDANCE WITH
TRIM EXISTNG TREES
D - 16 - 18
21 SEP 16
SCOPE OF WORK (NEAR BLDG. #676)
4. COUPLING ADAPTER SHALL BE GFM.
3. SEE THE ELECTRICAL DRAWING FOR ELECTRICAL WORKS.
WITH SOLID SODDING.
2. ALL UNPAVED AREAS WITHIN THE GRADING LIMIT LINE SHOULD BE COVERED
ARE NOT SHOWN ON THE DRAWING AND RELOCATE/ REPLACE AS REQUIRED.
COMMUNICATION LINE, ELECTRICAL LINE, GAS LINE AND WATER LINE THAT
1. CONTRACTOR SHALL VERIFY THE LOCATION OF UTILITY LINES SUCH AS
NOTES:
TRIM EXISTING TREES.
(GFM: COUPLING ADAPTER)
NECESSARY FITTINGS AND ACCESSORIES.
REMOVE/REPLACE EXISTING WATER LINE INCLUDING
BASE COURSE AND SUBBASE COURSE.
REMOVE/REPLACE EXISTING ASPHALT CONCRETE PAVEMENT,
1. COPLING ADAPTER, D=250 - 1EA, D=200 - 1EA.
*GFM(GOVERNMENT FURNISHED MATERIAL)
59.381
AC
59.555
AC
58.987
AC
60.761
AC
60.799
AC
60.867
AC
60.892
AC
60.821
AC
60.744
AC
60.697
BLDG
60.849
BLDG
60.888
BLDG
60.863
BLDG
59.189
MH
58.854
PAD
60.468
PAD
E/P
E/P
S/P
S/P
S/B
MH
MH
MH
MH
MH
MH
MH
PAD
CON
SHEET OF
KU, HUN MO
CIVIL
AS SHOWN
HGFEDCBA
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
UNITED STATES ARMY GARRISON DAEGU
DIRECTORATE OF PUBLIC WORKS
ENGINEERING DIVISION, DESIGN & TECHNICAL REVIEW Br
UNIT #15746, APO AP 96218-5746
DATE:
GRAPHIC SCALE
LEGEND:
ITEMS TO BE REMOVED
EXISTING ELECTRICAL POLE
CHI, K. K.
SCALE : 1 / 100
SCALE: 1 : 100
2000 4000
- 4
C-4
4 19
SITE LAYOUT PLAN-3
SITE LAYOUT PLAN-3
E/P
N
MH
MH
C O
M
C O
M
W
W
W
S/P
S/B
EXISTING SIGN BOARD AND POST
G
G
G
COURSE AND SUBBASE COURSE
REMOVE/REPLACE EXST. AC PAVEMENT, BASE
LINE (ASSUMED)
EXISTING GAS
(ASSUMED)
EXISTING WATER LINE
INDICATED BY COR
SIGN BOARD TO THE LOCATION
RELOCATE EXISTING MOVABLE DIGITAL
#323
BLDG.
T-376
~AC~
#1 (CONSTRUCTION/ALTERATION)
#2 (REPAIR/MAINTENANCE)
1.
3.
2.
1.
E
SEE DETAIL
SAME AS EXISTING
PAVEMENT, BASE COURSE AND SUBBASE COURSE
REMOVE/REPLACE EXISTING ASPHALT CONCRETE
MAIN DISTRIBUTION CABLE
REPLACE DAMAGED 22.9KV UNDERGROUND
CAMP CARROLL
21 SEP 16
HS-00517-5J
INSTALL CONCRETE PROTECTION SLAB.
SEE DETAIL
FOR GAS LINE
INSTALL CONCRETE PROTECTION SLAB
SAME AS EXISTING
FITTINGS AND ACCESSOIRES
LINE INCLUDING NECESSARY
REMOVE/REPLACE EXISTING WATER
EXISTING STEEL POST
TYPICAL SECTION
SEE ELEC. DRAWINGS AND
AND CONCRETE PADS
NEW PRIMARY JUNCTION PEDESTALS
D - 16 - 18
SCOPE OF WORK (NEAR BLDG. #323)
4. COPLING ADAPTER SHALL BE GFM.
3. SEE THE ELECTRICAL DRAWING FOR ELECTRICAL WORKS.
WITH SOLID SODDING.
2. ALL UNPAVED AREAS WITHIN THE GRADING LIMIT LINE SHOULD BE COVERED
ARE NOT SHOWN ON THE DRAWING AND RELOCATE/ REPLACE AS REQUIRED.
COMMUNICATION LINE, ELECTRICAL LINE, GAS LINE AND WATER LINE THAT
1. CONTRACTOR SHALL VERIFY THE LOCATION OF UTILITY LINES SUCH AS
NOTES:
RELOCATE EXISTING MOVABLE DIGITAL SIGN BOARD.
(GFM: COUPLING ADAPTER)
NECESSARY FITTINGS AND ACCESSORIES.
REMOVE/REPLACE EXISTING WATER LINE INCLUDING
BASE COURSE AND SUBBASE COURSE.
REMOVE/REPLACE EXISTING ASPHALT CONCRETE PAVEMENT,
CIVIL
AS SHOWN
HGFEDCBA
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
UNITED STATES ARMY GARRISON DAEGU
DIRECTORATE OF PUBLIC WORKS
ENGINEERING DIVISION, DESIGN & TECHNICAL REVIEW Br
UNIT #15746, APO AP 96218-5746
DATE:
CHI, K. K.
MAIN DISTRIBUTION CABLE
REPLACE DAMAGED 22.9KV UNDERGROUND
CAMP CARROLL
MORTAR
FORMED HOLE
HANDRAIL POST
HANDRAIL
AC ELEVATIONS
MATCH TO EXISTING
6001,200
(TYP.)
S=5%
EXISTING GROUND
3 NOT TO SCALE
SECTION
MATERIAL PROPERTIES:
ABBREVIATION:
2. REINFORCING STEEL YIELD STRENGTHS, fy=300 Mpa.
1. CONCRETE MINIMUM COMPRESSIVE STRENGTH AT 28 DAYS, f’c=24 Mpa.
STONE DITCH
EXISTING OPEN
D13@250 E.F
D13@250 E.F
O.C: ON CENTER
E.F: EACH FACE
T.B: TOP AND BOTTOM
E.W: EACH WAY
WALL
CONC. RETAINING
21 SEP 16
HS-00517-5J
5 19 C-5
STEEL PIPE
40mm GALVANIZED
WALL
CONC. RETAINING
SEE DETAIL ’A’
CONNECTION
WELD ALL
2,100
PAINT
HANDRAIL DETAIL
DETAIL ’A’
SECTION AND DETAILS
EARTH FILL
STRUCTUAL
2. PROVIDE PIPE SLEEVES AS REQUIRED.
1. PROVIDE SHOP DRAWING, VERIFY THE LOCATION OF WATER LINE.
NOTES:
(ASSUMED)
WATER LINE
1, (M
IN
(M
IN
2,200
(TYP.)
1,000
1,000
NOT TO SCALE5
SECTION (TYP.)2
S=0.5%
(MIN.)
S=0.5%
(MIN.)
2 4
AND GEOTEXTILE
GRAVEL POCKET(300x300x300)
PVC PIPE(D=50)@2,000
D13@250 E.F.T.B
1. PAINT HANDRAIL SURFACES IN ACCORDANCE WITH COLOR CODE GUIDANCE OF COR.
NOTE:
(MAX.)
SEE ELEC. DRAWINGS
AND CONCRETE PAD
PRIMARY JUNCTION PEDESTAL
SEE ELEC. DRAWINGS
AND CONCRETE PAD
PRIMARY JUNCTION PEDESTAL
D - 16 - 18
CIVIL
AS SHOWN
HGFEDCBA
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
UNITED STATES ARMY GARRISON DAEGU
DIRECTORATE OF PUBLIC WORKS
ENGINEERING DIVISION, DESIGN & TECHNICAL REVIEW Br
UNIT #15746, APO AP 96218-5746
DATE:
CHI, K. K.
MAIN DISTRIBUTION CABLE
REPLACE DAMAGED 22.9KV UNDERGROUND
CAMP CARROLL
HS-00517-5J
6 19 C-6
1 1
MIN
NEW AC SURFACE
NEW PRIME COAT
NEW BASE COURSE
NEW SUBBASE COURSE
COAT
APPLY TACK
SAW CUT AND
PAVEMENT
EXISTING AC
COURSE
EXISTING BASE
COURSE
EXISTING SUBBASE
COMPACTED SUBGRADE
WARNING TAPE
SATISFACTORY BACKFILL
INDICATED ON ELEC. PLANS
DUCT, NUMBER AS
CONCRETE ENCASED
DUCT
WIDTH
NOT TO SCALE6
MIN
DUCT & TRENCH SECTION (TYP)
SECTION AND DETAILS
SLAB
PROTECTION
ASPHALT SURFACE
BASE COUSRE
SUBBASE COURSE
GAS LINE
NOT TO SCALE6
(SQ)
BLACK
YELLOW
150 150 150
D13
F.E.L
CONCRETE FOUNDATION
POST FILLED WITH CONCRETE
150 mm DIA. STEEL PIPE GUARD
WELDED TO STEEL PIPE
NOT TO SCALE6
GUARD POST DETAIL (TYP)
PROTECTION SLAB DETAIL (TYP)
PROFESSIONAL ENGINEER, DESCRIBING THE METHODS FOR SHORING.
2. PROVIDE DRAWING AND CALCULATIONS, CERTIFIED BY A REGISTERED
OF LABORATORY MAX. DENSITY.
1. BASE AND SUBBASE COURSE SHALL BE COMPACTED AT LEAST 100 %
NOTES:
E.F.T.B D13@150
1,800
21 SEP 16
ENGINEERING DIVISION, DESIGN & TECHNICAL REVIEW Br
ELECTRICAL
AS SHOWN
HGFEDCBA
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
UNITED STATES ARMY GARRISION DAEGU
DIRECTORATE OF PUBLIC WORK
UNIT #15746, APO AP 96218-5746
DATE:
LEGEND, NOTES AND SCOPE OF WORK
5.
6.
E-1
D - 16 - 18HS-00517-5J
SHEET OF
SIN, YS
KIM, CK
1.
N O T E S
3.
2.
4. MOUNTING HEIGHTS ARE AS BELOW. MEASUREMENT IS TO CENTER OF OUTLET.
WIRES IS INDICATED AS FOLLOW;
AND ONE (1)-#12AWG GROUND WIRE IN 16mm CONDUIT. A GREATER NUMBER OF
ANY CIRCUIT WITHOUT FURTHER DESIGNATION INDICATES TWO (2)-#12AWG WIRES
3-#12AWG WIRES AND 1-#12AWG GROUND WIRE IN 16mm CONDUIT.
4-#12AWG WIRES AND 1-#12AWG GROUND WIRE IN 16mm CONDUIT.
FIRE ALARM CONTROL PANEL----------------------------5’-0" ABOVE FLOOR
MANUAL PULL STATION----------------------------------4’-6" ABOVE FLOOR
FIRE ALARM BELL---------------------------------------7’-0" ABOVE FLOOR
LIGHTING FIXTURE--------------------SEE LIGHTING FIXTURE SCHEDULE
TOGGLE SWITCH-----------------------1220mm TO CENTER OF THE OUTLET
RECEPTACLE---------------------------460mm TO CENTER OUTLET
PANELBOARD, CIRCUIT BREAKER------------------------SEE SPECIFICATION
CAULKING MATERIAL SHALL BE VERIFIED BY F&ES OFFICE PRIOR TO CONSTRUCTION.
BOTH SIDE OF FIRE WALLS, FIRE-PARTITIONS AND FIRE-RATED PIPE CHASE WALLS.
ALL PIPE PENETRATIONS SHALL BE SEALED WITH FIRE RATED CAULKING MATERIAL ON
1.
SPECIFICATIONS FOR O&MA PROJECTS, AND SPECIFICATIONS.
ELECTRICAL CODE, NATIONAL ELECTRICAL SAFETY CODE, FIRE CODE, TECHNICAL STANDARD
ALL ELECTRICAL WORK SHALL CONFORM TO THE LATEST REQUIREMENTS OF THE NATIONAL
CONDUIT WHICH IS TO BE BONDED TO THE MAIN GROUNDING SYSTEM AT BOTH ENDS.
GROUNDING WIRE SHALL BE GREEN INSULATED COPPER WIRE IN RIGID GALVANIZED STEEL
ALL WIRING SHALL BE CONCEALED ABOVE THE CEILING WHEN THE ROOM HAS A CEILING.
L E G E N D
NEWEXSTREMOVE
SCOPE OF WORK
CAMP CARROLL
MAIN DISTRIBUTION CABLE
REPLACE DAMAGED 22.9KV UNDERGROUND
7.
STORAGE AREA.
THE CONTRACTOR SHALL TURN OVER ALL SALVAGED MATERIAL TO THE DPW DESIGNATED
M M M
H H H
PMJ PRIMARY PAD MTD JUNCTION BOX
MANHOLE
HANDHOLE
PMJPMJ
UNDERGROUND DISTRIBUTION LINE+ + +
OROROR
A
A
AS
VS
AS
VS
AS
VS
A
GROUND ROD
POWER CIRCUIT BREAKER
DRAW-OUT TYPE DEVICE CONNECTION
FUSE
AMMETER SWITCH
VOLTMETER SWITCH
INVERSE TIME OVERCURRENT RELAY, NO.
DESIGNATES RELAY TYPE
27 = UNDERVOLTAGE RELAY
50 = INSTANTANEOUS OVERCURRENT RELAY
51N = RESIDUAL NEUTRAL INVERSE TIME OVERCURRENT RELAY
67 = DIRECTIONAL OVERCURRENT RELAY
67N = DIRECTIONAL NEUTRAL OVERCURRENT RELAY
SWITCH
FUSED SWITCH OR FUSED CUTOUT
CURRENT TRANSFORMER
POTENTIAL (VOLTAGE) TRANSFORMER
TRANSFORMER
AMMETER LETTER DESIGNATES METER TYPE
V = VOLT METER
W = WATT METER
PF = POWER FACTOR METER
VAR = KILO-VAR METER
WHM = KILOWATT-HOUR METER
LIGHTNING ARRESTER/SURGE ARRESTER
8.
ELECTRICAL LINES AND ANY NEW ELECTRICAL EQUIPMENT AND CABLING.
AND ELECTRICAL SHOP FOR ANY REMOVAL OR REPAIR OF EXISTING EQUIPMENT OR UNDERGROUND
THE CONTRACTOR SHALL COORDINATE WITH THE BASE ENGINEER (DPW). ELECTRICAL ENGINEER
B. REPAIR/MAINTENANCE
1.
2.
3.
SWITCHGEARS, VCBS, DISTRIBUTION LINES, EQUIPMENTS AND HIGH VOLTAGE ACCESSORIES.
PROVIDE OPERATION TEST & ADJUST, REPAIR AT EACH SWITCHING STATIONS INCLUDING MOF, CONTROL WIRES, DOORS, SPACE HEATERS AND ASSOCIATED ACCESSORIES AT EACH SWITCH STATION.
REPLACE DETERIORATED EXISTING PROTECTION & MONITORING EQUIPMENT INCLUDING RELAYS, A. CONSTRUCTION
INCLUDING DUCT & MANHOLE CLEANING AND ASSOCIATED ACCESSORIES.
REPLACE EXISTING DETERIORATED 22.9KV UNDERGROUND MAIN DISTRIBUTION LINE WITH NEW
US ORIGIN MATERIAL:
INDICATED ON THE DRAWINGS.
INTERNET SITE (http//www.cckbid.com). ALL NON-GENERIC US ORIGIN MATERIALS SHALL BE AS
DATED REVISION 1 - 20151030 (ELECTRONIC VERSION OF THIS DOCUMENT CAN BE FOUND AT
REGISTER OF IMA-KORO PAMPHLET 420-1 "INSPECTION OF CONSTRUCTION CONTRACTS
ALL GENERIC US ORIGIN MATERIALS SHALL BE AS OFF-SHORE IN THE GENERIC SUBMITTAL
7 19
DUCT, SPLICE KIT AND NECESSARY ASSOCIATED ACCESSORIES.
INSTALL NEW CABLE JUNCTION PEDESTAL(GFM) INCLUDING 25KV DISTRIBUTION CABLE, CONCRETE ENCASEMENT
N
ELECTRICAL
AS SHOWN
HGFEDCBA
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
UNITED STATES ARMY GARRISION DAEGU
DIRECTORATE OF PUBLIC WORK
UNIT #15746, APO AP 96218-5746
DATE:
E-2
D - 16 - 18
SHEET OF
SIN, YS
KIM, CK
21 SEP 16
MAIN DISTRIBUTION CABLE
REPLACE DAMAGED 22.9KV UNDERGROUND
CAMP CARROLL
HS-00517-5J
0 120003000 6000
SCALE: 1:300
x x x x x x x xxxx x x x
KEY PLAN
- E2
P-1 ELECTRICAL DISTRIBUTION PLAN - 1
T-377
T-619
S -9
T-813
S T O
R A G E
O R
G A N
IZ
A T
IO
N A L
S
D
T-569
T-565
T
T-575
S-574
S
S u b s ta ti o n
E le c tr ic a l
S-573
T-578 Vehicle Scales
S-640
GATE 2
EMHM-01
DHM-01
M
H
EMHM-02
DHM-02
H
M
D
/D /D
D
/D
/D
/D
SCALE : 1 / 300
(REUSE EXISTING DUCT)
IN 155mmC DUCT WITH DUCT CLEANING
& 1-750KCMIL, 600V, POWER CABLE
REPLACE 2SET OF 3-750KVMIL, 25KV "XLP"
MATCH LINE SEE SHEET E-3
SEE
ENLARGED PLAN
- E8
P-1
22.9KV PRI-5.7/ 3.3KV SEC
EXISTING KEPCO SUBSTATION
PLAN REFER DWG SH E-8
22.9KV SWITCHGEAR ENLARGED
SWITCHING STATION NO.1
CLEAN EXISTING ELECTRICAL MANHOLE
CLEAN EXISTING ELECTRICAL MANHOLE
8 19
ELECTRICAL DISTRIBUTION PLAN - 1
AS SHOWN
HGFEDCBA
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
UNITED STATES ARMY GARRISION DAEGU
DIRECTORATE OF PUBLIC WORK
UNIT #15746, APO AP 96218-5746
DATE:
E-3
SHEET OF
SIN, YS
KIM, CK
MAIN DISTRIBUTION CABLE
REPLACE DAMAGED 22.9KV UNDERGROUND
CAMP CARROLL
HS-00517-5J
0 120003000 6000
SCALE: 1:300
- E3
P-1 ELECTRICAL DISTRIBUTION PLAN - 2
S-657
T
T-561
T 3 T
N E
B R
A S
K A
V E
N U
E
T-580
S-563
S-622
T-572
T-582
T-581
P M J
EMHM-03
DHM-03
M H
DHM-04
EMHM-04
M H
/D
D D
/D
/D
D D
SCALE : 1 / 300
KEY PLAN
T-377
T-619
S -9
T-813
S T O
R A G E
O R
G A N
IZ
A T
IO
N A L
S
MATCH LINE. SEE SHEET E-2
MATCH LINE. SEE SHEET E-4
(REUSE EXISTING DUCT)
IN 155mmC DUCT WITH DUCT CLEANING
& 1-750KCMIL, 600V, POWER CABLE
REPLACE 2SET OF 3-750KVMIL, 25KV "XLP"
CLEAN EXISTING ELECTRICAL MANHOLE
CLEAN EXISTING ELECTRICAL MANHOLE
DUCT WITH PULL WIRE
IN 155mmC DUCT AND 4-155mmC SPARE
& 1-750KCMIL, 600V, POWER CABLE
PROVIDE 4SET OF 3-750KVMIL, 25KV "XLP"
21 SEP 16
D - 16 - 18
ELECTRICAL DISTRIBUTION PLAN - 2
9 19
INSTALL DETAIL SHEET NO. E-12
600A, 25KV, 2WAY JUNCTION(GFM) SEE
NEW 2EA PRIMARY JUNCTION PEDESTAL
AS SHOWN
HGFEDCBA
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
UNITED STATES ARMY GARRISION DAEGU
DIRECTORATE OF PUBLIC WORK
UNIT #15746, APO AP 96218-5746
DATE:
E-4
D - 16 - 18
SHEET OF
SIN, YS
KIM, CK
21 SEP 16
MAIN DISTRIBUTION CABLE
REPLACE DAMAGED 22.9KV UNDERGROUND
CAMP CARROLL
HS-00517-5J
0 120003000 6000
SCALE: 1:300
- E4
P-1 ELECTRICAL DISTRIBUTION PLAN - 3
S-530
S-668
T-661
S-675
S-693 Washrack
T-693
T-584
DHM-05 EMHM-05 M
H
/D
D
D
/D
/D
SCALE : 1 / 300
KEY PLAN
T-377
T-619
S -9
T-813
S T O
R A G E
O R
G A N
IZ
A T
IO
N A L
S
MATCH LINE. SEE SHEET E-3
MATCH LINE. SEE SHEET E-5
(REUSE EXISTING DUCT)
IN 155mmC DUCT WITH DUCT CLEANING
& 1-750KCMIL, 600V, POWER CABLE
REPLACE 2SET OF 3-750KVMIL, 25KV "XLP"
CLEAN EXISTING ELECTRICAL MANHOLE
ELECTRICAL DISTRIBUTION PLAN - 3
10 19
AS SHOWN
HGFEDCBA
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
UNITED STATES ARMY GARRISION DAEGU
DIRECTORATE OF PUBLIC WORK
UNIT #15746, APO AP 96218-5746
DATE:
E-5
SHEET OF
SIN, YS
KIM, CK
11 19
MAIN DISTRIBUTION CABLE
REPLACE DAMAGED 22.9KV UNDERGROUND
CAMP CARROLL
HS-00517-5J
0 120003000 6000
SCALE: 1:300
- E5
P-1 ELECTRICAL DISTRIBUTION PLAN - 4
D
S-532
N E
B R
A S
E
N U
E
S-842
S-676
T
DHM-06 H
M
EMHM-06
M
H DHM-07
EMHM-07
D
/D
/D
D D
SCALE : 1 / 300
KEY PLAN
T-377
T-619
S -9
T-813
S T O
R A G E
O R
G A N
IZ
A T
IO
N A L
S
MATCH LINE. SEE SHEET E-4
MATCH LINE. SEE SHEET E-6
P M J
(REUSE EXISTING DUCT)
IN 155mmC DUCT WITH DUCT CLEANING
& 1-750KCMIL, 600V, POWER CABLE
REPLACE 2SET OF 3-750KVMIL, 25KV "XLP"
CLEAN EXISTING ELECTRICAL MANHOLE
CLEAN EXISTING ELECTRICAL MANHOLE
DUCT WITH PULL WIRE
IN 155mmC DUCT AND 4-155mmC SPARE
& 1-750KCMIL, 600V, POWER CABLE
PROVIDE 4SET OF 3-750KVMIL, 25KV "XLP"
21 SEP 16
D - 16 - 18
ELECTRICAL DISTRIBUTION PLAN - 4
INSTALL DETAIL SHEET NO. E-12
600A, 25KV, 2WAY JUNCTION(GFM) SEE
AS SHOWN
HGFEDCBA
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
UNITED STATES ARMY GARRISION DAEGU
DIRECTORATE OF PUBLIC WORK
UNIT #15746, APO AP 96218-5746
DATE:
E-6
SHEET OF
SIN, YS
KIM, CK
12 19
MAIN DISTRIBUTION CABLE
REPLACE DAMAGED 22.9KV UNDERGROUND
CAMP CARROLL
HS-00517-5J
0 120003000 6000
SCALE: 1:300
- E6
P-1 ELECTRICAL DISTRIBUTION PLAN - 5
S -3
S-3
T-369
S -3
S-840
S
S-
S-5
T-503 Bus Stop 1
DHM-08
EMHM-08 HM
D
D
/D
/D
/D
D
SCALE : 1 / 300
KEY PLAN
T-377
T-619
S -9
T-813
S T O
R A G E
O R
G A N
IZ
A T
IO
N A L
S
MATCH LINE. SEE SHEET E-5
MATCH LINE. SEE SHEET E-7
P M J
CLEAN EXISTING ELECTRICAL MANHOLE
(REUSE EXISTING DUCT)
IN 155mmC DUCT WITH DUCT CLEANING
& 1-750KCMIL, 600V, POWER CABLE
REPLACE 2SET OF 3-750KVMIL, 25KV "XLP"
DUCT WITH PULL WIRE
IN 155mmC DUCT AND 2-155mmC SPARE
& 1-750KCMIL, 600V, POWER CABLE
PROVIDE 4SET OF 3-750KVMIL, 25KV "XLP"
21 SEP 16
D - 16 - 18
ELECTRICAL DISTRIBUTION PLAN - 5
INSTALL DETAIL SHEET NO. E-12
600A, 25KV, 2 WAY JUNCTION(GFM) SEE
AS SHOWN
HGFEDCBA
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
UNITED STATES ARMY GARRISION DAEGU
DIRECTORATE OF PUBLIC WORK
UNIT #15746, APO AP 96218-5746
DATE:
E-7
SHEET OF
SIN, YS
KIM, CK
13 19
MAIN DISTRIBUTION CABLE
REPLACE DAMAGED 22.9KV UNDERGROUND
CAMP CARROLL
HS-00517-5J
0 120003000 6000
SCALE: 1:300
EMHM-09
- E7
P-1 ELECTRICAL DISTRIBUTION PLAN - 6
S
N E B
R A S
E
N U
E
S-860 Substation Electrical x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x
BANK
CAP
BANK
CAP
T
T
S-349
T -3
S-320
S -3
S-328
S-321
++ M
H
S-340
DHM-10
DHM-09
/D
D
D
/D
D
D
H
/D
SCALE : 1 / 300
KEY PLAN
T-377
T-619
S -9
T-813
S T O
R A G E
O R
G A N
IZ
A T
IO
N A L
S
MATCH LINE. SEE SHEET E-6
SEE
ENLARGED PLAN
- E9
P-1
CLEAN EXISTING ELECTRICAL MANHOLE
(REUSE EXISTING DUCT)
IN 155mmC DUCT WITH DUCT CLEANING
& 1-750KCMIL, 600V, POWER CABLE
REPLACE 2SET OF 3-750KVMIL, 25KV "XLP"
21 SEP 16
ELECTRICAL DISTRIBUTION PLAN - 6
AS SHOWN
HGFEDCBA
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
UNITED STATES ARMY GARRISION DAEGU
DIRECTORATE OF PUBLIC WORK
UNIT #15746, APO AP 96218-5746
DATE:
E-8
SHEET OF
SIN, YS
KIM, CK
14 19
MAIN DISTRIBUTION CABLE
REPLACE DAMAGED 22.9KV UNDERGROUND
CAMP CARROLL
HS-00517-5J
N x x x x x x x x xx x x x x
(NOTE 1)
TO KEPCO 22.9KV BUS
1500 914.6 914.6 1220
1200 1220 1220 1500
XFMR
SERVICE
STATION
M1
VCB
M2
VCB
MOF
KEPCO
MOF
KEPCO
NFSM
SLOPE
1500 914.6 914.6
1220 1200 1220 1220 1500
- E8
P-1
- E8
P-2
SCALE: 1:50
500 1000 2000
SCALE : 1 / 50
FRONT ELEVATION
SEE SH. "E-2"
TO EMHM-01
(TO BE REMAIN)
600V CABLE IN 155mmDBPVC
3-#750 KCMIL, 25KV & 1-750KCMIL,
22.9KV SWITCHING STATION NO.1
SCALE : 1 / 50
INSTALLED BY KEPCO
ENCLOSURE(WP) SUPPLIED &
REPAIR EXISTING METERING &
& 1-750KCMIL, 600V CABLE WITH NEW
REPLACE EXISTING 3-#750 KCMIL, 25KV
SERVICE TRANSFORMER(SEE NOTES)
PANELBOARDS AND STATION
REPAIR AUXILLIARY SECTION FOR
NOTES)
CIRCUIT BREAKER, 22.9KV(SEE
REPAIR EXISTING VACUUM TYPE
- E8
D-1
NOT TO SCALE
PAD MTD JUNCTION DETAILS
PAD MTD JUNCTION DETAILS
22.9KV SWITCHING STATION NO.1 AND
(REUSE EXISTING DUCT)
1-750KCMIL, 600V CABLE IN 155mmPVC
REPLACE 3-#750 KCMIL, 25KV &
WIRE MESH
WITH 6"X6" - W2.9 X 2.9
CONC. PAD REINFORCED
#1/0 AWG DAWG "BC"
GROUND WIRE,
WIRE MESH
WITH 6"X6 - W2.9XW2.9
CONC. PAD REINFORCED
WITH MASONRY GROUT FILL
RECTANGULAR HOLE
DESCRIPTIONSITEM
600A 15/25KV CLASS 2-WAY DEADBREAK JUNCTION
ADJUSTABLE LOCATION STAINLESS STEEL PARKING STAND
600A 15KV/25KV CLASS STANDOFF BUSHING FOR PARKING
316 STAINLESS STL MOUNTING BAR & PARKING
CLIP MOUNTING RAILS
GROUND BAR, #2AWG SOLID COPPER
FOR SPARE BUSING ON JUNCTIONS
600A 15/25KV CLASS INSULATED PROTECTIVE CAP
GROUND ROD, COPPER CLAD STEEL,
19mmDIA X 3m LG WITH
WELDING CONNECTION
GRAVEL SUB-BASE
6" 100% WELL COMPACTED
100% COMPACTION
BEYOND PAD ON ALL AROUND
A MINIMUM OF 1 FOOT
EXTEND GRAVELFILL
600A 15/25KV CLASS DEADBREAK CONNECTOR FOR 750KCMIL
DANGER
PMJ
NOTE :
W/ ASSIGNMENT NUMBER
PROVIDE EACH PMJ
+176°F, ROUND CORNERS, 3/16" HOLES
POLISH VINYL PLASTIC, -40°F,
SETON M2325 HPP 60MIL
10"
(254)
(1
MASONRY GROUT, 76mm THK
NOTES:
B.
A. CABLE JUNCTION PEDESTAL SHALL BE MANUFACTURED BY
SHALL BE PROTECTED BY THE INSULATED PROTECTIVE CAPS
ALL SPARE BUSHINGS ON THE JUNCTIONS AND STANDOFF BUSHING
NTS
PMJ ASSIGNMENT SIGN
INCLUDE SS LOUVERS
FIBERGLASS ENCLOSURE, NOMINAL THICKNESS 1/ 4 NOMINAL THICKNESS
15641264
"POWER DESIGN INC." OR APPROVED EQUAL.
AS SHOWN
HGFEDCBA
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
UNITED STATES ARMY GARRISION DAEGU
DIRECTORATE OF PUBLIC WORK
UNIT #15746, APO AP 96218-5746
DATE:
E-9
SHEET OF
SIN, YS
KIM, CK
15 19
MAIN DISTRIBUTION CABLE
REPLACE DAMAGED 22.9KV UNDERGROUND
CAMP CARROLL
HS-00517-5J
N x x x x x x x x x x x x x x x x x x x x x x x x x x x xx xx xx xx xx x
X X X X X
BANK
CAP
BANK
CAP
3200 2000 3200
18000
914.61200914.6914.6914.6914.6 914.6 914.6 914.6 914.6 914.6 914.6 914.6
FRONT
11 9 3 2 1A
- E9
P-1
- E9
P-2
22.9KV SWITCHING STATION NO.2
FRONT ELEVATION
SCALE : 1 / 50
SCALE: 1:50
500 1000 2000
SCALE : 1 / 50
SEE SHT "E-7"
FROM EMHM-09
NO.
ITEM
EQUIPMENT DESCRIPTION
FEEDER NO. 1 CIRCUIT BREAKER COMPARTMENT
FEEDER NO. 3 CIRCUIT BREAKER COMPARTMENT(SPARE)
TIE-IN BREAKER COMPARTMENT, NORMALLY OPEN
FEEDER NO. 2 CIRCUIT BREAKER COMPARTMENT
FEEDER NO. 4 CIRCUIT BREAKER COMPARTMENT(SPARE)
TRANSITION FOR TIE-IN BREAKER COMPARTMENT
22.9KV SWITCHING STATION N0.2
MAIN BREAKER "A" COMPARTMENT
MAIN BREAKER "B" COMPARTMENT
FEEDER NO. C1 CIRCUIT BREAKER COMPARTMENT FOR CAPACITOR BANK BUS "A"
FEEDER NO. C2 CIRCUIT BREAKER COMPARTMENT FOR CAPACITOR BANK BUS "B"
11A
SPACE FOR FEEDER BREAKER
SPACE FOR FEEDER BREAKER
1A
11A
11 8 7 6 5 4
13 12
(TO BE REMAIN)
1-155mm PVC SPARE DUCT
(TO BE REMAIN)
1-155mm PVC SPARE DUCT
(TO BE REMAIN)
& 1-500KCMIL, 600V IN 155mmPVC
FEEDER NO.2: 3-#500KCMIL, 25KV
(TO BE REMAIN)
& 1-500KCMIL, 600V, IN 155mmPVC
FEEDER NO.1: 3-#500KCMIL, 25KV
SPACE
SPACE
(EMPTY) (TO BE REMAIN)
EXISTING 2-27mm EACH PVC 103mmPVC(TO BE REMAIN)
1-#2 AWG(G) 600V IN
3-#4/0 AWG 25KV XLPE &
(TO BE REMAIN)
INNER DUCT(SPARE)
2-78mmPVC W/2-27mm
22.9KV SWITCHING STATION NO.2
DC PANEL AND CHARGER AND REMOTE CONTROL UNIT(RTU)
PROTECTIONS, STATION SERVICE PANEL "MDP", 48 V BATTERIES,
STATION SERVICE TRANSFORMER COMPLETE W/ OVERCURRENT
CAPACITOR BANK "A", 600 KVAR W/BLOCK SHORTING SWITCH
CAPACITOR BANK "B", 1800 KVAR W/BLOCK SHORTING SWITCH
FUTURE
SPACE
FUTURE
SPACE
NFSM 15
18000
914.6 914.6 914.6 914.6 1200 914.6914.6914.6914.6914.6914.6914.6914.6
2-155C SPARE(REUSE EXISTING DUCT)
1-750KCMIL, 600V IN 155mmPVC)
REPLACE 2(3-#750KCMIL, 25KV &
AS SHOWN
HGFEDCBA
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
UNITED STATES ARMY GARRISION DAEGU
DIRECTORATE OF PUBLIC WORK
UNIT #15746, APO AP 96218-5746
DATE:
E-10
SHEET OF
SIN, YS
KIM, CK
16 19
MAIN DISTRIBUTION CABLE
REPLACE DAMAGED 22.9KV UNDERGROUND
CAMP CARROLL
HS-00517-5J
LEGEND:
POTENTIAL TRANSFORMER
CURRENT TRANSFORMER
KILOWATT HOUR METER
PHASE OVERCURRENT RELAY,
TIME INVERSE
GROUND OVERCURRENT RELAY,
INSTANTANEOUS
WHM
51N
PT
CT
PHASE OVERCURRENT RELAY,
INSTANTANEOUS
52-X
KEY INTERLOCK
CLF CURRENT LIMITING FUSE
SURGE ARRESTER STATION
CLASS 18KV
MOF METERING OUTFIT
K
27 UNDERVOLTAGE RELAY
AMMETER SWITCH
AMMETER
POWER FACTOR METER
VOLTMETER
VOLTMETER SWITCH
VARMETER
67N
DIRECTIONAL OVERCURRENT RELAY,
GROUND
DIRECTIONAL OVERCURRENT RELAY,
PHASE
STATION SERVICE
PANEL "DP"
48 V BATTERIES
DC PANEL AND
CHARGER
30A, 2P, 240V MTS
IN NEMA 1 ENCL
30 A, 2P
(TYP)
TO PT 52-M2 TO PT 52-M1
SSM
86 51N51TYPICAL
TYPICAL
THROUGH 86 50/51
86 51 51N
67N 27
86 51N51
86 LOCKOUT RELAY
BUS DIFFERENTIAL
SD CAPACITOR BANK SWITCHING DEVICE
ACD AUTOMATIC CONTROL DEVICE
RTU
SCADA
SOLID STATE MICROPROCESSOR
67N
86 50/51 50/51N
VACUUM BREAKER, DRAW OUT TYPE,
1200A OR 600A, 27KV
KILOWATT DEMAND METER
REMOTE TERMINAL UNIT
(FUTURE - PHASE 2)
SUPERVISORY CONTROL AND
DATA ACQUISITION (FUTURE - PHASE 2)
50/51
PHASE AND GROUND
OVERCURRENT RELAY
50GS ZERO SEQUENCE GROUND SENSOR
50GS
SUBSTATION ND PRIMARY LINE (BY KEPCO)
WHM
D
KILOWATT HOUR METER W/ DEMAND REGISTER
SSM-C2
SSM-C1
SSM-T
SSM-4
SSM-1
SSM-B
SSM-A
SSM-M2
SSM-M1
W
VS
VAR
V
PF
AS
A
CLF
PT
22.9KV/120V
CLF
PT
22.9KV/120V
SWITCHING STATION "NO. 1"
KILOWATT HOUR METER KILOWATT HOUR METER
LA
3-18KV
CLF CLF
PT PT
TO "DP"
#2/0 AWG BC
IN 21mm PVC
LA
3-18KV
#2/0 AWG BC
IN 21mm PVC
22.9KV/
120/240V, 5KVA
SERVICE XFMR
VCB
1200A
25KA
VCB
1200A
25KA
#6 AWG BC
IN 16mm PVC
TO RTU
TO SWITCHING STATION NO. 2,
FOR CONT. SEE SHT "E-2"
22.9KV BUS
3-CTS
1200/5A
3-CTS
1200/5A
3-CTS
1200/5A
3-CTS
1200/5A
3-CTS
1200/5A
3-CTS
1200/5A
#6 AWG BC
IN 16mm PVC (TYP)
22.9KV LINE
(BY KEPCO)
3-750KCMIL, 25KV &
1-750KCMIL, 600V
IN 155mm PVC DB
3-750 KCMIL, 25KV XLPE &
1-750 KCMIL, 600 V
IN 155mm PVC
EXISTING KEPCO
SUBSTATION BETWEEN
GATE #1 AND #2 OF
D
PT
10/12 MVA 10/12 MVA
WHM VS VWHMVSV
D
WHM WHM
52-M2 52-M1
AS
A
SSM-M1
AS
A
SSM-M2
PF PF
22.9KV SWITCHING STATION NO.1 - SINGLE LINE DIAGRAM
SERVICE PANEL BLOCK DIAGRAM
INCOMING LINE STATION
NOT TO SCALE
NOT TO SCALE
EXISTING 5.7/3.3KV
CAMP CARROLL.
LINE STATION DRAGRAM AND LEGEND
22.9KV SWITCHING STATION NO.1, INCOMING
REPAIR DAMAGED MOF REPAIR DAMAGED MOF
OR APPROVED EQUAL
BASED PROTECTIVE RELAYS "GIPAM-2000F1"
(TYP OF 2EA)
& MONITORING EQUIPMENT
DIGITAL INTEGRATED PROTECTION
REPLACE EXISTING WITH NEW
- E10
D-1
- E10
D-2
- KEPSCO CERTIFICATION TEST
ACCESSORIES ON EACH PANEL
- CLEAN VCB, PT, SWITCH AND ASSOCIATED
- PT OPERATION TEST ON EACH PANEL
- ALL VCB OPERATION/FUNCTION TEST
- RELAY OPERATION TEST ON EACH PANEL
- REPLACE RELAY WITH DOOR ON EACH PANEL
- REPLACE CONTROL WIRES ON EACH PANEL
- PROVIDE FAN WITH COVER TO PROTECT INCOMING DUST
- PROVIDE THERMOSTAT TO CONTROL HEATER
- REPLACE 2EA SPACE HEATER ON EACH PANEL
DETAIL SCOPE OF WORK
AS SHOWN
HGFEDCBA
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
UNITED STATES ARMY GARRISION DAEGU
DIRECTORATE OF PUBLIC WORK
UNIT #15746, APO AP 96218-5746
DATE:
E-11
SHEET OF
SIN, YS
KIM, CK
17 19
MAIN DISTRIBUTION CABLE
REPLACE DAMAGED 22.9KV UNDERGROUND
CAMP CARROLL
HS-00517-5J
3-CTS
600/5A
VCB
TIE N.O.
1200A
SWITCHING STATION "NO. 2" (25KV)
RTU
3-LA
18KV
3-CTS
600/5A
CLFCLF
PT’S
22.9KV/120V
SPARE
VCB
600A
16KA
1200A
16KA
MAIN VCB
1200A
16KA
155mm DIA.
EMPTY DUCT
155mm DIA.
EMPTY DUCT
EMH2-01 EMH1-01
#2/0 AWG BC
IN 21mm PVC
CLF CLF
3-CTS
600/5A
3-CTS
600/5A
VCB
600A
16KA
3-CTS
600/5A
3-CTS
600/5A
VCB
600A
16KA
3-CTS
600/5A
3-CTS
600/5A
VCB
600A
16KA
G
CLF
FUSE 2A
#6 AWG BC
IN 16mm PVC
#1/0 AWG BC
IN 21mm PVC
(TYP)
15KVA, 1PH STATION
3-CTS
600/5A
3-CTS
600/5A
87A 3-CTS
600/5A
3-CTS
600/5A
87B
3-CTS
600/5A
SD
PT
#6 AWG
GND WIRE
VCB
600A
16KA
3-CTS
600/5A
3-CTS
600/5A
SD
PT
#2 AWG
GND WIRE
#6 AWG
GND WIRE
VCB
600A
16KA
SPARE FEEDER NO.2
TO SWITCHING STATION NO. 1,
FDR NO. 1
3LAS
18KV
(TYP)
3-CTS
600/5A
CT
50/5A
CT
50/5A
CT
50/5A
CT
50/5A
CT
50/5A
CT
50/5A
3-CTS
1200/5A
3-CTS
1200/5A
3-CTS
1200/5A
3-CTS
1200/5A
3-CTS
1200/5A
3-CTS
1200/5A
3-CTS
1200/5A
3-#4/0 AWG,
25KV XLPE,
1-#2 AWG (G),
600V IN 103mm DIA. DUCT
87A 87B
CAP BANK
1800 KVAR
CAP BANK
600 KVAR
(NOTE 6)
22.9KV BUS "B" 1200A CU, 4W + N + 25% G, 16KA MIN 22.9KV BUS "A" 1200A CU, 4W + N + 25% G, 16KA MIN
3-500 KCMIL, 25KV XLPE &
1-500 KCMIL
600V IN 155mm DIA. DUCT
3-500 KCMIL, 25KV XLPE &
1-500 KCMIL
600V IN 155mm DIA. DUCT
3-750 KCMIL, 25KV XLPE &
1-750 KCMIL, 600V IN 155C PVC
3-CTS
1200/5A
3-CTS
1200/5A
87A 87B
K
VVS
AS
A
VAR PFW
AS
A
W PF
52-B 52-A
52-352-4 52-2 52-1
52-T
SSM-A
V VS
AS
A
VARPF W
SSM-1
AS
A
W PF
SSM-3
AS
A
W PF
SSM-2
AS
A
W PF
SSM-4
SSM-T
SSM-B
86B
87B
86A
87A
AS
A
PF
ACD
52-C2 SSM-C2
AS
A
PF
ACD
52-C1 SSM-C1
27 27
#2 AWG
GND WIRE
PROVISION FOR
FUTURE EXPANSION
3-#4/0 AWG,
25KV XLPE,
1-#2 AWG (G), 600V
POWER CABLE IN
103mm DUCT DUCT
3-LA
18KV
PT’S
22.9KV/120V
22.9KV SWITCHING STATION NO.2 - SINGLE LINE DIAGRAM
NOT TO SCALE
SINGLE LINE DIAGRAM
22.9KV SWITCHING STATION NO.2
FOR CONT. SEE SHT "E-7"
SERVICE XFMR
(TYP OF 9EA)
& MONITORING EQUIPMENT
DIGITAL INTEGRATED PROTECTION
REPLACE EXISTING WITH NEW
- E11
D-1 DETAIL SCOPE OF WORK
21 SEP 16
D - 16 - 18
22.9 KV TO 120/240V
REPLACE EXISTING
TRANSFORMER 22.9KV TO 120/ 240V 15KVA
- REPLACE EXISTING STATION SERVICE
- KEPSCO CERTIFICATION TEST
ACCESSORIES ON EACH PANEL
- CLEAN VCB, PT, SWITCH AND ASSOCIATED
INCLUDE REPLACE BROKEN FUSES
- PT OPERATION TEST ON EACH PANEL
- ALL VCB OPERATION/FUNCTION TEST
- RELAY OPERATION TEST ON EACH PANEL
- REPLACE RELAY WITH DOOR ON EACH PANEL
- REPLACE CONTROL WIRES ON EACH PANEL
- PROVIDE FAN WITH COVER TO PROTECT INCOMING DUST
- PROVIDE THERMOSTAT TO CONTROL HEATER
- REPLACE 2EA SPACE HEATER ON EACH PANEL
AS SHOWN
HGFEDCBA
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
UNITED STATES ARMY GARRISION DAEGU
DIRECTORATE OF PUBLIC WORK
UNIT #15746, APO AP 96218-5746
DATE:
E-12
SHEET OF
SIN, YS
KIM, CK
18 19
MAIN DISTRIBUTION CABLE
REPLACE DAMAGED 22.9KV UNDERGROUND
CAMP CARROLL
HS-00517-5J
NOT TO SCALE- E12
D-1
G R
O U
N D
L
IN
E
THRU HOLE FOR
PADLOCKING
CAST BRONZE
HASP BLOCK
CAPTIVE RECESSED
SS 1/2 13 NC PENTA
HEAD BOLT
PEBESTAL LID
EXTERIOR
PLASTIC WIRE
STOP LID LINER
DF3 HASP
ITEM
SS ADJUSTABLE PARKING CLIP (6X)
SPM-540 UNIV. SS JUNCTION MOUNTING BAR
PNL-1/0 BOLTED GROUND CONNECTOR
GAS SPRING LID SUPPORT 60 #-15 (2X)
NOTES:
B. MOUNTING BAR WILL WITHSTAND A MINIMUM 400-LB
LOADING TO INSTALL OR REMOVE ELBOWS
CONCRETE PAD REINFORCED
GRAVEL SUB-BASE
300GL
G
NFSM
G
NFSM
COPPER CLAD STEEL
19diax3000mmLG WITH
GROUND ROD
GROUNDING WIRE
DESCRIPTIONS
A. CABLE JUNCTION PEDESTAL SHALL BE MANUFACTURED BY
CHAMFER
316 STAINLESS STL SLIDING PARKING CLIP MOUNTING BARS
3000PSI-28DAYS
100% WELL COMPACTED
DETAIL "A"
9 MOUNT "DANGER HIGH VOLTAGE" SIGN
CABLE JUNCTION PEDESTAL INSTALL DETAIL
TYP.
ANCHOR LEDGES,
3/16" THK 316 S/S
TYP.
CHAMFER EDGES SLACK
5M (15’) GENEROUS
LENGTH AS REQUIRED
ACCESS
FRONT
AS REQ’D
BOLTS & NUTS
3/6 S/S
(TYPICAL)
NUTS, 316 S/S, TYP.
316" LEDGE, BOLTS,
-40OF, +1760F, ROUND CORNERS
60MIL PRESS POLISH VINYL PLASTIC
SETON: (HHP) M2404
VOLTAGE
HIGH
M2404
10"
DANGER
END SECTIONFRONT SECTON
SCHEMATIC CONNECTORS
TOP VIEW
DETAIL ’A’DF3 HASP DETAIL
SIGN
(254)
(1
PHASE "A" PHASE "B" PHASE "C"
NOTE : PROVIDE SIGNS AS NOTED.
NTS
FDR C
KCMIL
SETON M4860
-40°F, +185°F 8"L
NYLON TIE/LOCK
M4500
19 GAUGE, 3/16" HOLE, M4500
BRASS TAGS, 1/4" LETTERING, 1/2H NUMBERS
SETON:
CABLE TAG
(5)
2" OCTAGON
NTS
PROVIDE CABLE ASSIGNMENT TAGS.
NOTE :
CABLE LOADBREAK CONNECTORS, 600A(FOR 750KCMIL), 25KV
C. MINIMUM MATERIAL THICKNESS - 4.76mm(3/16")
MODEL NO. CJP-40-56-L2-WG-6225-GB2 FIBERGLASS PEDESTAL
"POWER DESIGN INC." OR APPROVED EQUAL.
0dia.WIRE MESH
WITH 150x150x-4.0dia.x4.
#2/0 "BC",
WELDING CONNECTION
CABLE JUNCTION PEDESTAL INSTALL DETAIL(TYPICAL)
RTE 25 KV, 600 AMP 2-WAY JUNCTIONS (4X)
AS SHOWN
HGFEDCBA
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
UNITED STATES ARMY GARRISION DAEGU
DIRECTORATE OF PUBLIC WORK
UNIT #15746, APO AP 96218-5746
DATE:
E-13
SHEET OF
SIN, YS
KIM, CK
19 19
MAIN DISTRIBUTION CABLE
REPLACE DAMAGED 22.9KV UNDERGROUND
CAMP CARROLL
HS-00517-5J
NOT TO SCALE- E13
D-4
NOTES:
8 WAY
1. PROVIDE ENOUGH CLEARANCE ON BOTH SIDES
OF TRENCH TO FACILITATE INSTALLATION
& REMOVAL OF FORMS ON SIDES OF CONCRETE
ENCASED DUCTS.
2. INSTALL ONE 13mm DOUBLE BRAID HIGH STRENGTH
76 50
(WIDTH OF CUT VARIES)
1 1
SAW CUT
& APPLY TACK
COAT
EXST AC
PAVEMENT
EXST
BASE
EXST
SUB BASE
NEW AC PAVEMENT
NEW ASPHALT
SURFACE COAT
NEW PRIME COAT
WARNING TAPE
COMPACT THE TOP 6" (152)
OF ALL SUBGRADE CUTS TO A MIN.
OF 90% MAX. DENSITY FOR COHESIVE
MATERIAL & 95% MAX. DENSITY FOR
COHESION LESS MATERIAL
AGGREGATE BASE
COURSE COMPACTED
TO A MIN OF 100%
MAX. DENSITY
WIDTH
DUCT
DUCT
THICKNESS
WARNING TAPE
COMPACTED
BACKFILL
M
IN
EXST FIN
GRADE (WIDTH OF CUT VARIES)
RESTORE GRADE TO EXST CONDITION
COMPACTED BACKFILL
SUB BASE
COMPACTED
TO 100% MAX
DENSITY
CONCRETE ENCASED
DUCT, NUMBER AS
INDICATED ON PLANS.
CONCRETE ENCASED DUCT
6 WAY AS INDICATED IN PLAN
229 229
MIN
MIN
229 229
DUCT THICKNESS
INITIAL BACKFILL
MATERIAL
(M
IN
(M
IN
INITIAL
BACKFILL
MATERIAL
(MIN. 8500 LB TENSILE STRENGTH) POLYESTER
PULL ROPE IN EACH SPARE CONDUIT WITH A MIN
600mm SPARE CORD PROTRUDING FROM EACH END.
BASE SPACERS
INTERMEDIATE
SPACERS
PVC CONDUIT
INTERMEDIATE
SPACERS
BASE
SPACER
76 76
152 7676
BASE SPACER
NOT TO SCALE
(NON TRAFFIC AREA)
NOT TO SCALE (TRAFFIC AREA)
INTERMEDIATE SPACER
- E13
D-3
- E13
D-1
- E13
D-2
- E13
P-1
INSTALLATION DETAIL
PRIMARY DUCT & TRENCH SECTION AND
168 168
PRIMARY DUCT & TRENCH SECTION - AC PAVEMENT(TYPICAL)
PRIMARY DUCT & TRENCH SECTION(TYPICAL)
SPACER POSITIONING(TYPICAL)
PRIMARY DUCT SECTION DETAIL(TYPICAL)
SPACER DETAIL(TYPICAL)
CONC ENCASEMENT
2500 PSI
INTERMEDIATE SPACER
(TYPICAL)
(TYPICAL)
BASE SPACER
168 16850
| HS-00517-5J_T01 |
| HS-00517-5J_C01 |
| HS-00517-5J_C02 |
| HS-00517-5J_C03 |
| HS-00517-5J_C04 |
| HS-00517-5J_C05 |
| HS-00517-5J_C06 |
| HS-00517-5J_E01 |
| HS-00517-5J_E02 |
| HS-00517-5J_E03 |
| HS-00517-5J_E04 |
| HS-00517-5J_E05 |
| HS-00517-5J_E06 |
| HS-00517-5J_E07 |
| HS-00517-5J_E08 |
| HS-00517-5J_E09 |
| HS-00517-5J_E10 |
| HS-00517-5J_E11 |
| HS-00517-5J_E12 |
| HS-00517-5J_E13 |