BENCHSTOCK-LIST

REPAIR PARTS LIST
NoITEMMFRMODEL#SPECIFICATIONS
1Break Rod 10EA/PKANSUL4834Break Rod.

Length : 3.1875'' / diameter : 0.135''

2 Manual Pull Station, Single Action, MFR: MONACO MONACO 708-025-01 Double Action, Break-Glass, SPST-No, Presignal 4.9''H x 3.3''W x 1.9'' D 3 Manual Pull Station, Single Action, Terminal Connection, Key Reset MFR: SILENT KNIGHT SILENT KNIGHT PS-SATK Manual Pull Station, Single Action, Terminal Connection, Key Reset.

Switch Rating : 1 amp at 125VAC, or 30VDC / Dimension : 4-3/4''H x 3-1/4''W 1-1/8''D

4Photoelectric Smoke Detector with 6.1" Senor Base, MFR: MONACOMONACO729-150-00Photoelectric Smoke Detector with 6.1" Senor Base, DETECTOR BASE, 12/24 VDC, 6.1" DIAMETER
5Heat Detector, Fixed Temperature, 135F, MFR: MONACOMONACO722-123-00Heat Detector, Fixed Temperature only, 135F,
6Heat Detector, Fixed Temperature, 190F, MFR: MONACOMONACO722-408-00Heat Detector, Fixed Temperature only, 190F,
7Two wire, Self Diagnostic,
Plugin Head/Base, Remote Test / Indicator 12/24VDC, MFR: MONACOMONACO429CTwo wire, Self Diagnostic,

Plugin Head/Base, Remote Test / Indicator 12/24VDC

8Two wire/Four wire, Plug-in Head/ Base Options 24VDC, Low Profile, MFR: MONACOMONACO449CTTwo wire/Four wire, Plug-in Head/ Base Options 24VDC, Low Profile
9Zone Expansion Module Zone Expansion Module, 24 VDC, Two Class A or Four Class B Zones (or combination), MFR: MONACOMONACO176-133-00Zone Expansion Module Zone Expansion Module, 24 VDC, Two Class A or Four Class B Zones (or combination), MFR: MONACO
10BSA-1 VHF 136-174 MHZ BSA-1 VHF 136-174 MHZ Omni Directional Antenna, MFR: MONACOMONACO190-400-00Type : 5/8 wave omnidirectional, RF Impedance :50 ohms

Forward Gain : 3 db, Ground Radials : 4 each 11 Lighting Arrestor, MFR: MONACO MONACO 198-006-00 Lighting Arrestor (Static Discharge Unit) NEMA 3R Rain tight Enclosure, 12'' x 4'' x 4''

12Motorized Vibrating Alarm Bell, MFR: MONACOMONACOMB-G6-24-RShell size : 6'' Input Voltage : 12V. Average RMS Current : 0.0060 dBA@10ft : 92
13BT-XF in a 20 inch high *12inch *4inch deep red enclosure with a narrow band (149.4125MHZ), MFR: MONACOMONACO227-600-E8BT-XF in a 20 inch high *12inch *4inch deep red enclosure with a narrow band (149.4125MHZ), MFR: MONACO
14Expansion Backplane, MFR: MONACOMONACO176-212-00Expansion Backplane, PCB : BT XZ, MTHBD, 2CD
15BT-XF Zone card, MFR: MONACOMONACO176-206-00PCB : BT-XF Zone card with Res 15K, 0.25W, 5%

TB : 4 POS, PLUG, 5.08MM

16 Addressable Heat Detector 135F, MFR: SIMPLEX SIMPLEX 4098-9733 Addressable Heat Detector 135F with Base, Voltage : 32VDC MAX, Current : 100mA Max Address Means DIP switch, 8 position 17 Addressable Heat Detector 190F, MFR: SIMPLEX SIMPLEX 4098-9734 Addressable Heat Detector 190F with Base, Voltage : 32VDC Max, Current : 100mA Max Address Means DIP switch, 8 position

18Addressable Manual Pull station, MFR: SIMPLEXSIMPLEX4099-9001Addressable Manual Pull station, Power and Communications : IDNet or MAPNET II communications, 1 address per station. Address Means : DIP switch, 8 position, UL Listed Temperature Range : 32° to 120° F (0° to 49° C) intended for indoor operation, Humidity Range : Up to 93% RH at 100° F (38° F)
19SFIO Board, MFR: SIMPLEXSIMPLEX742-367Fire Alarm Control Panel, Voltage Range : 102 to 132VAC Frequency : 60Hz, Maximum Current 2A

N2 Communications for Serial Annunciator Control up to 6 remote, 24 point I/O, Access Port : RS-232 IDNet Addressable Communications Channel : up to 250 , Four NACs : 2A@24V , Two Auxiliary Output Circuits, Battery Charger. Auxiliary Power Tap, Standard Power Supply Regulated 24 DC.

20 Sounder Base, MFR: SIMPLEX SIMPLEX 4098-9794 Analog Addressable Sounder Base fits True Alarm Photoelectric, Ionization, and Heat Sensors 21 Smoke Detector Analog Addressable Photoelectric Smoke Detector, MFR: SIMPLEX SIMPLEX 4098-9714 Smoke Detector Analog Addressable Photoelectric Smoke Detector, Mounting Requirements : 4” octagonal or 4” square box, 1-1/2” min, depth; or single gang box, 2” min. depth

22Addressable Heat Detector, MFR: SILENT KNIGHTSIRENT KNIGHTSD505-AHSAddressable Heat Detector, Operating Voltage: 17 to 41 VDC, Current Consumption: Standby: .55 mA Alarm: .55 mA Mounting: 4" SQR, 4" OCT Single gang mud ring. Detection Temperature Range: 135°F to 150°F
23Addressable Photoelectric type Smoke Detector, MFR: SILENT KNIGHTSIRENT KNIGHTSD505-APSAddressable Photoelectric type Smoke Detector, Operating Voltage: 17-41 VDC. Operating Temperature: 32°F to 120°F, Sensitivity: 0.88% - 3.56% FT. Air Velocity: 0 - 300 FPM. Relative Humidity: 85% noncondensing.
24Sounder Base, MFR: SILENT KNIGHTSIRENT KNIGHTSD505-6SB6” Sounder Base, UL Listed (meets or exceeds UL 464 requirements for evacuation signal sound level of 85 dB at 10 ft.) Aux Current Draw : Standby: 1 Ma / Alarm: 32 mA. Operating Voltage : SLC Loop: 32 VDC. Aux Input: 24 VDC
25Fire Alarm Bell with Strobe, MFR: SILENT KNIGHTSIRENT KNIGHTMB-G6-24-R/RSSP-
24MCW-FRFire Alarm Bell with Strobe, Shell Size : 6" , 24VDC, Average RMS Current : 0.030, dBA @ 10 Ft. : 92

Strobe Candela : 5/30/75/110. Average Current (AMPS) at listed VDC : .041/.063/.109/.140

26Heat Detector, 135F, MFR: SILENT KNIGHTSIRENT KNIGHTIDP-HEATHeat Detector, 135F, Addressable Thermal Detector Fixed Temp 135 (BASE NOT INCLUDED)
27Heat Detector, 190F, MFR: SILENT KNIGHTSIRENT KNIGHTIDP-HEAT-HTHeat Detector, 190F, Fixed High Temperature Thermal Detector, Operating Voltage: 15 – 32 VDC

Alarm Current: 6.5 mA @ 24 VDC max (with LED on) ,High temperature heat 135ºF – 190ºF 28 Single/Multiple Station Smoke Detector, MFR: SILENT KNIGHT SIRENT KNIGHT HD6135FB Senses and alarms at 135 degrees Fahrenheit, FIX & RATE OF RISE , Thermal Detectors, Detection Devices, Fire .

Voltage: 120 vac. Operating in temperatures from 40 degrees to 100 degrees Fahrenheit, this alarm is listed to UL 539 standards.

29Addressable Pull Station, MFR: SILENT KNIGHTSIRENT KNIGHTSD500-PSAddressable Pull Station, Operating Voltage: 24VDC, Standby Current: .55mA, Alarm Current: .55mA
30Main Board for Fire Alarm Control Panel, MFR: SILENT KNIGHTSIRENT KNIGHT5820XLBuilt-in support for up to 99 detectors and 99 modules, expandable to 396 detectors and 396 modules creating

a total point capacity of 792 points using the SK protocol. Built-in digital communicator/dialer Point status meets calibrated smoke test requirements for NFPA 72.

RS-485 SBUS provides communication to intelligent distributed system accessories

32Fire Alarm Horn with Strobe, MFR: SILENT KNIGHTSIRENT KNIGHTHRSFire Alarm Horn with Strobe, Voltage: Regulated 24DC, Candela: Selectable high-candela strobe settings of 135, 150, 177 and 185 cd.
33Fire Alarm Strobe, Model #: STR , MFR: SILENT KNIGHTSIRENT KNIGHTSTRFire Alarm Strobe, 2‐Wire Low Frequency Sounder Strobe White Operating Voltage Range :16 to 33 V (24 V nominal)

Strobe Flash Rate : 1 flash per second.

34 Photoelectric Smoke Detector, MFR: SILENT KNIGHT SIRENT KNIGHT IDP-PHOTO Operating Voltage: 15–32 VDC, SLC Standby and Alarm Current: 300 Μa Operating Temperature : 32º – 120ºF (0ºC – 49ºC). Humidity: 10% – 93% non-condensing 35 Photoelectric Smoke Detector w/Thermal, MFR: SILENT KNIGHT SIRENT KNIGHT IDP-PHOTO-T Photoelectric Smoke Detector w/Thermal, MFR: SILENT KNIGHT, Operating Voltage: 15–32 VDC SLC Standby and Alarm Current: 300 μA, IDP-Photo-T: 32º – 100ºF (0ºC – 38ºC), IDP-Photo-T Thermal: Fixed temperature set point 135ºF (57ºC)

36Thermal Sounder Base, MFR; SILENT KNIGHTSIRENT KNIGHTSSB501BHTThermal Sounder Base, Operating Voltage: 15 – 32 VDC, Alarm Current: 15 mA max, Sound Output: Greater than 90 dBA
37Manual Single Station, MFR: SILENT KNIGHTSIRENT KNIGHTIDP-PULL-SAManual Single Station, Operating Voltage: 15–32 VDC, Operating Current (LED flashing): 300 Μa

Switch: Single pole, single throw (SPST) normally open (N/O) switch which closes upon activation of the pull station.

38 Expellant Gas Cartage (LT-30-R), MFR: ANSUL ANSUL #423435 Expellant Gas Cartage (LT-30-R), LT-30-R Nitrogen Cartridge, For use with 3 gallon cylinder, •DOT/TC, •RHT Available in boxes of 16 39 Expellant Gas Cartage (101-20), MFR: ANSUL ANSUL #423441 Expellant Gas Cartage (101-20), DOT/TC, For use with 3 gallon cylinder, Available in boxes of 16

40Fusible Link, 360F (25/package), K-Type , MFR: ANSULANSUL#415745Fusible Link, 360F (25/package), K-Type
41Link, Fusible (GAS) 212F, MFR: GUARDIAN / 25/PACKAGEGUARDIAN323013Link, Fusible (GAS) 212F, 25ea/PACKAGE
42Wire Rope 500ft(152m), MFR: ANSULANSUL#79653Wire Rope, Stainless Steel, 1/16 in. Diameter 500ft.
43Nozzle, 1W, MFR: ANSULANSUL#419336Single Nozzle, Perimeter : 67cm, Diameter : 22cm

Nozzle Tip Stamping-Flow No. 1W 44 Nozzle, 1N, MFR: ANSUL ANSUL #419335 Horizontal Protection, Length : 2.4m Filter Height : 51cm Nozzle Tip Stamping-Flow No. 1N 45 Swivel Adaptor, MFR: ANSUL ANSUL #418569 Nozzle Swivel Adapter for Kitchen Knight II Nozzle Assy.

to allow precise directional aiming of PYRO-CHEM Nozzles on Appliance Protection.

Restaurant Fire Suppression Systems, Restaurant System Nozzle Adaptor

46Metal Blow-Off Cap (10/Packages), Model #: 433208, MFR: ANSULANSUL#433208Metal Blow-Off Cap (10/Packages)
47ANSUL Tank Adaptor Bursting Discs 10/pac, Model #: 417911, MFR: ANSULANSUL#417911Tank Adaptor Bursting Discs. (10/Packages)
48Tamper Switch, Model #: OSYSU-2, MFR: VIKINGVIKINGOSYSU-2Tamper Switch, OSYSU-2: Two Sets of SPDT (Form C) -40º F to 140ºF (-40ºC to 60ºC)

10.0 Amps at 125/250 VAC 2.0 Amps at 30VDC Resistive10 mAmps minimum at 24 VDC.

49Water Motor Alarm Assembly, MFR: VIKINGVIKING7862Water Motor Alarm Assembly, Water working pressure: Rated to 175 PSI (12 bar)
50Alarm pressure Switch, Dual SPDT, MFR: VIKINGVIKING9471Alarm pressure Switch, Dual SPDT.
51Pressure Supervisory Switch, Dual SPDTMFR; VIKINGVIKING9473Pressure Supervisory Switch, Dual SPDT.
52Upright Sprinkler Head Upright Sprinkler Head, 135F, 1/2" NPT, K=5.6, MFR: VIKINGVIKING10138FBUpright Sprinkler Head Upright Sprinkler Head, 135F, 1/2" NPT, K=5.6
53Pendent Sprinkler Head, 135F, 1/2" NPT, K=5.6 with Escutcheon, MFR: VIKINGVIKING10139FAPendent Sprinkler Head, 135F, 1/2" NPT, K=5.6 with Escutcheon. Finish : Chrome
54Water Pressure Gauge, MFR: VIKINGVIKINGVWATERSF300 PSI (20.7 bar) Water Pressure Gauge
55Air Pressure Gauge, MFR: VIKINGVIKINGVAIRSFConnection: 1/4” NPT Working Pressure : Water Gauge: 300 psi (20.7 bar). Air Gauge: 80 PSI (5.5 bar)
56Identification Sign,Identification Sign, acrylic, 5mm THK, 2" Dia
57Multiful Station Smoke Alarm Model : 5919TH, MFR : BRK ElectronicBRK Electronic5919THAlarm Dimensions : 5.5" diameter, 2.5" height. Operating : 40°F(4.4°C) to 100°F(38°C)

Audio Alarm : 85dB at 10ft Power Consumption : .025 Amps typical in standby .025 Amps in alarm Ratings: 3A @ 125V AC @ 30V DC 58 GENTEX Horn & Strobe (GEC24-15/75WR), Model : 904-1127-002, MFR :GENTEX GENTEX 904-1127-002 Nominal Voltage : 24VDC Strobe Candela : 15 (ANSI/UL 1971) / 75 (ANSI/UL1638).

In Anechoic Room dBA @ 10ft. : 100.

59 Fire Alarm Control Panel, Model : 4010, MFR : Simplex SIMPLEX 742-267 Fire Alarm Control Panel, Voltage Range : 102 to 132VAC Frequency : 60Hz, Maximum Current 2A N2 Communications for Serial Annunciator Control up to 6 remote, 24 point I/O, Access Port : RS-232 IDNet Addressable Communications Channel : up to 250 , Four NACs : 2A@24V , Two Auxiliary Output Circuits, Battery Charger. Auxiliary Power Tap, Standard Power Supply Regulated 24 DC.

60 Fire Alarm Control Panel, Model : 5820XL, MFR : Silent Knight SIRENT KNIGHT 5820XL Fire Alarm Control Panel, 127 point, expandable to 792 points, multi-loop addressable fire alarm control/ communicator system. Powerful features such as drift compensation, maintenance alert, built-in digital communicator, and distributed intelligent power. Point status meets calibrated smoke test requirements for NFPA 72

61Fire Alarm Control Panel, Model : IFP-100, MFR : Silent KnightSIRENT KNIGHTIFP-100Fire Alarm Control Panel Flush Mount Dimensions: 14.5”W x 24.75”H x 3.5”D . Color: Red Primary AC: 120 VRMS @ 50/60 Hz, 2.5A Alarm Current: 325 mA Approvals NFPA 13, NFPA 15, NFPA 16, NFPA 70, & NFPA 72.
62B Fusible Link, Model : 323013, MFR: Globe technologiesGlobe technologies323013Maximum Load = 40 lbs. (18.14 kg.) Minimum Load = 10 lbs. (4.54 kg.). 360 Degree F Model ML
63Self Smoke Detector,BRK ELECT2002Photoelectronic Smoke Alarm with Battery Back-Up, 120V AC, 60Hz, 9Volt Battery Included,

UL Listed.

64 Battery 12V, 7AH solite SLD 7-12 Sealed Lead-ACD Battery / Voltage : 12V / AMP : 7AH L : 151mm W : 65mm H : 94mm 65 Battery, 12V, 12AH solite SLD12-12 Sealed Lead-ACD Battery / Voltage : 12V / AMP : 12AH L : 151mm W : 98mm H : 94mm 66 Battery 12V, 18AH solite SLD-18-12 Sealed Lead-ACD Battery / Voltage : 12V / AMP : 18AH L : 181mm W : 76mm H : 167mm 67 Battery 12V, 31AH solite SLD 31-12 Sealed Lead-ACD Battery / Voltage : 12V / AMP : 31AH L : 196mm W : 131mm H : 167mm 68 Battery 12V, 40AH solite SLD 40-12 Sealed Lead-ACD Battery / Voltage : 12V / AMP : 40AH L : 197mm W : 168mm H : 175mm

69Battery 9V, Dry Batteryrocket6F22Dry Battery 9V
70Battery 12V, 150AHaltlasBX-150LBattery 12V, 150AH

L : 506mm W : 212mm H : 210mm 71 Vulcan I FACP MONACO 176-129-00 Vulcan I FACP, 24Vdc, 1 Class A or 2 Class B Zones, 24'' x 14'' x 3.5'' Surface Mount Enclosure, for three Zone Expansion Module.

72 ZONE CARD MONACO 176-133-00 Zone Expansion Module Zone Expansion Module, 24 VDC, 2 Class A or 4 Class B Zones.

73 Wet chemical agent, 3 gallons ANSUL #79372 Low pH Liquid Wet Chemical Agent, 3 gal.

Restaurant Fire Suppression Systems 74 Battery 12V, 1.2AH power ps sonic PS-1212 Rechargeable Sealed Lead Acid Battery / 12V, 1.2AH L : 96mm W : 43mm H : 52mm