Section SF 30 - BLOCK 14 CONTINUATION PAGE
a. The purpose of this amendment is to:
(1) Responses to questions received. Questions and Answers are as the following:
Question 1: The total quantities of devices and square feet of Attachment 3 are not matched with the calculated total quantities of CLINs.
Response 1: Revised Attachment 3 and CLINs. (See attached confirmed solicitation and Attachment-3-A0002)
Question 2: For the service call, PWS 5.2 states that the service call is the corrective work can be accomplished within the four (4) hours of work, and repair parts/materials are no more than KW50,000. Also, the quantities of service call on the line item is 758 each. It is unclear whether the qualities of 758 each on the line item mean 758 task orders including four (4) hours of work or the total 758 hours of service work. – Please clarify the correct quantities in accordance with PWS.
Response 2: The quantity of 758 each on the Service Call line item is 758 Task Orders including four (4) hours of work and repair parts/materials are not more than KW50,000.
(2) Added Requirements CLINs, CLIN X019 thru CLIN X026.
(3) Extended the closing date from 23 June 2016, 1300 hours to 1 July 2016, 1300 hours.
b.
All other terms and conditions remain unchanged.
NOTE
"All sources may submit a proposal or quote as applicable. However, the Republic of Korea (ROK)-United States (U.S.) Status of Forces Agreement (SOFA) does not permit the U.S. Government to grant Invited Contractor or Technical Representative Status to any offeror for this requirement. All sources submitting a proposal or quote, as applicable, including U.S. source, must already have, or obtain the requisite business licenses directly from the ROK Government, and conduct business in accordance with all applicable ROK laws, including but not limited to, rules and policies regarding labor, taxation, and immigration. Any contractor not already doing business in Korea must submit adequate verification in its initial proposal or quote that it has the requisite business licenses directly from the ROK Government to perform the contract and the capacity to conduct business in accordance with all applicable ROK laws, including but not limited to, rules and policies regarding labor, taxation, and immigration. If the initial proposal does not fully demonstrate this authorization and capacity, it will not be further considered for award. Whether an offeror demonstrates this authorization and capacity shall be determined by the Contracting Officer."
Contract Period:
Phase-In:
1 Aug 2016 - 31 Aug 2016 (CLIN 0018)
Base Year:
1 Sep 2016 - 31 Jul 2017 (CLINs 0001 - 0017)
1st Option:
1 Aug 2017 - 31 Jul 2018 (CLINs 1001 - 1017)
2nd Option:
1 Aug 2018 - 31 Jul 2019 (CLINs 2001 - 2017)
3rd Option:
1 Aug 2019 - 31 Jul 2020 (CLINs 3101 - 3017)
4th Option:
1 Aug 2020 - 31 Jul 2021 (CLINs 4001 - 4017)
a. The purpose of this amendment is to:
(1) Responses to questions received. Questions and Answers are as the following:
Question 1: "On Page 79 of the solicitation, (2) Engineering Supervisor: The Engineering Supervisor shall be the Fire Protection Specialist (FPS) who is a registered professional engineer who has passed the fire protection engineering written examination administered by the National Council of Examiners for Engineering and Surveys (NCEES) or who is certified as a Level III or above Technician by the National Institute for Certification in Engineering Technologies (NICET) in the Automatic Sprinkler System Layout/Fire Alarm and Detection System Subfield of Fire Protection Engineering Technology in accordance with NICET 1014-7 or registered Fire Protection Professional Engineer (PE) License (소방기술사) issued by ROK..
Fire Facilities Manager (소방시설관리사) is also qualified for the above requirement, "Inspection, Test, Maintenance and Repair of Fire Alarm Detection, and Suppression System" as Fire Protection Professional Engineer (소방기술사). Is Fire Facilities Manager (소방시설관리사) qualified for Engineering Supervisor?"
Response 1: Fire Facilities Manager is not qualified for Engineering Supervisor. The Government will not change the technical evaluation factors because the above sub-factor is developed based on the market research and the Government internal review.
Question 2: On 79 Page of the solicitation, it is described that "The prime Contractor shall have a Fire Protection Facilities Management Business Registration (소방시설관리 유지업 등록증)" However, we have Fire Protection Facilities Installation Business Registration (소방시설 공사업 등록증). Is it acceptable or not? Could you let us know that our registration is satisfied for the requirement?
Response 2: The solicitation stated that the prime Contractor shall have a Fire Protection Facilities Management Business Registration (소방시설관리 유지업 등록증). The Fire Protection Facilities Installation Business Registration (소방시설 공사업 등록증) is different license with the Fire Protection Facilities Management Business Registration (소방시설관리 유지업 등록증). The Government will not change the technical evaluation factors and will be evaluated in accordance with the Solicitation.
Question 3: For Local Clause 5152.204-4032 to be submitted, but could not find the clause in the solicitation.
Response 3: Inserted
(2) Changed Para 1.5.6 of the Performance Work Statement from "Safety Plan" to Safety Program".
b.
All other terms and conditions remain unchanged.
Section SF 1449 - CONTINUATION SHEET
| ITEM NO |
| SUPPLIES/SERVICES |
| QUANTITY |
| UNIT |
| UNIT PRICE |
| AMOUNT |
| 11 |
| Months |
Wet Chemical Fire Suppression System
FFP
To provide Inspection, Test and Maintenance of Wet Chemical fire suppression system (256 EA) at Camp Humphreys IAW PWS, Paragraph 5.1 See Attachment 3. Facility list and 2. UFC 3-601-2.
FOB: Destination
PURCHASE REQUEST NUMBER: 0010791261
NET AMT
| ITEM NO |
| SUPPLIES/SERVICES |
| QUANTITY |
| UNIT |
| UNIT PRICE |
| AMOUNT |
| 11 |
| Months |
Dry Chemical Fire Suppression System
To provide Inspection, Test and Maintenance of Dry chemical fire suppression system (2 EA) at Camp Humphreys IAW PWS, Paragraph 5.1. See Attachment 3. Facility list and 2. UFC 3-601-2.
NET AMT
| ITEM NO |
| SUPPLIES/SERVICES |
| QUANTITY |
| UNIT |
| UNIT PRICE |
| AMOUNT |
| 11 |
| Months |
Fire Pumps
To provide Inspection, Test and Maintenance of Fire Pumps (36 EA) at Camp Humphreys IAW PWS, Paragraph 5.1. See Attachment 3. Facility list and 2. UFC 3-601-2.
NET AMT
| ITEM NO |
| SUPPLIES/SERVICES |
| QUANTITY |
| UNIT |
| UNIT PRICE |
| AMOUNT |
| 11 |
| Months |
Wet Pipe Sprinkler Fire Suppression Syst
To provide Inspection, Test and Maintenance of Wet Pipe Sprinkler Fire Suppression System (16,819,435 SF) at Camp Humphreys IAW PWS, Paragraph 5.1. See Attachment 3. Facility list and 2. UFC 3-601-2.
NET AMT
| ITEM NO |
| SUPPLIES/SERVICES |
| QUANTITY |
| UNIT |
| UNIT PRICE |
| AMOUNT |
| 11 |
| Months |
Dry Pipe Sprinkler Fire Suppression Syst
To provide Inspection, Test and Maintenance of Dry pipe Sprinkler Fire Suppression System (891,116 SF) at Camp Humphreys IAW PWS, Paragraph 5.1. See Attachment 3. Facility list and 2. UFC 3-601-2.
NET AMT
| ITEM NO |
| SUPPLIES/SERVICES |
| QUANTITY |
| UNIT |
| UNIT PRICE |
| AMOUNT |
| 11 |
| Months |
AFFF Fire Suppression System
To provide Inspection, Test and Maintenance of AFFF Fire Suppression System (228,171 SF) at Camp Humphreys IAW PWS, Paragraph 5.1. See Attachment 3. Facility list and 2. UFC 3-601-2.
NET AMT
| ITEM NO |
| SUPPLIES/SERVICES |
| QUANTITY |
| UNIT |
| UNIT PRICE |
| AMOUNT |
| 11 |
| Months |
Standpipe Fire Suppression System
To provide Inspection, Test and Maintenance of Standpipe Fire Suppression System (62 EA) at Camp Humphreys IAW PWS, Paragraph 5.1. See Attachment 3. Facility list and 2. UFC 3-601-2.
NET AMT
| ITEM NO |
| SUPPLIES/SERVICES |
| QUANTITY |
| UNIT |
| UNIT PRICE |
| AMOUNT |
| 11 |
| Months |
Fire Alarm and Detection System
To provide Inspection, Test and Maintenance of Fire Alarm and Detection System (18,882,427 SF) at Camp Humphreys IAW PWS, Paragraph 5.1. See Attachment 3. Facility list and 2. UFC 3-601-2.
NET AMT
| ITEM NO |
| SUPPLIES/SERVICES |
| QUANTITY |
| UNIT |
| UNIT PRICE |
| AMOUNT |
| 11 |
| Months |
D500/D21 Fire Alarm Receiver
To provide Inspection, Test and Maintenance of D500/D21 Fire Alarm Receiver (4 EA) at Camp Humphreys IAW PWS, Paragraph 5.1. See Attachment 3. Facility list and 2. UFC 3-601-2.
NET AMT
| ITEM NO |
| SUPPLIES/SERVICES |
| QUANTITY |
| UNIT |
| UNIT PRICE |
| AMOUNT |
| 11 |
| Months |
Building Transceiver
To provide Inspection, Test and Maintenance of Building Transceiver (507 EA) at Camp Humphreys IAW PWS, Paragraph 5.1. See Attachment 3. Facility list and 2. UFC 3-601-2.
NET AMT
| ITEM NO |
| SUPPLIES/SERVICES |
| QUANTITY |
| UNIT |
| UNIT PRICE |
| AMOUNT |
| 11 |
| Months |
Fire Hydrant
To provide Inspection, Test and Maintenance of Fire Hydrant (854 EA) at Camp Humphreys IAW PWS, Paragraph 5.1. See Attachment 3. Facility list and 2. UFC 3-601-2.
NET AMT
| ITEM NO |
| SUPPLIES/SERVICES |
| QUANTITY |
| UNIT |
| UNIT PRICE |
| AMOUNT |
| 11 |
| Months |
Cleaning Agent
To provide Inspection, Test and Maintenance of Cleaning Agent (1 EA) at Camp Humphreys IAW PWS, Paragraph 5.1. See Attachment 3. Facility list and 2. UFC 3-601-2.
NET AMT
| ITEM NO |
| SUPPLIES/SERVICES |
| QUANTITY |
| UNIT |
| UNIT PRICE |
| AMOUNT |
| 11 |
| Months |
Carbon Monoxide Detector
To provide Inspection, Test and Maintenance of Carbon monoxide detector (33 EA) at Camp Humphreys IAW PWS, Paragraph 5.1. See Attachment 3. Facility list and 2. UFC 3-601-2.
NET AMT
| ITEM NO |
| SUPPLIES/SERVICES |
| ESTIMATED QUANTITY |
| UNIT |
| UNIT PRICE |
| ESTIMATED AMOUNT |
Unscheduled Repair/Restoration Work
(Requirement Item)
The contractor shall provide repair part, material, and labor cost for unscheduled repair service IAW PWS, Paragraph 5.3. of the PWS under this CLIN with the following SubCLINs. A Firm Fixed Price (FFP) Task Order will be issued after completion of negotiation for the number of labor hours and material amount for each task.
ESTIMATED
NET AMT
| ITEM NO |
| SUPPLIES/SERVICES |
| ESTIMATED QUANTITY |
| UNIT |
| UNIT PRICE |
| ESTIMATED AMOUNT |
0014AA
| 1 |
| Job |
Repair Parts and Material Cost
Repair part and material for major repair IAW PWS, Paragraph 5.4. of the PWS. Total estimated amount is W223,997,920. The Contractor is not required to submit the unit price for this CLIN. Prices will be negotiated per delivery order.
ESTIMATED
| ITEM NO |
| SUPPLIES/SERVICES |
| ESTIMATED QUANTITY |
| UNIT |
| UNIT PRICE |
| ESTIMATED AMOUNT |
0014AB
| 120 |
| Hours |
Engineering Supervisor
ESTIMATED
| ITEM NO |
| SUPPLIES/SERVICES |
| ESTIMATED QUANTITY |
| UNIT |
| UNIT PRICE |
| ESTIMATED AMOUNT |
0014AC
| 240 |
| Hours |
Electrical Fire Engineering Technician
ESTIMATED
| ITEM NO |
| SUPPLIES/SERVICES |
| ESTIMATED QUANTITY |
| UNIT |
| UNIT PRICE |
| ESTIMATED AMOUNT |
0014AD
| 240 |
| Hours |
Mechanic Fire Engineering Technician
ESTIMATED
| ITEM NO |
| SUPPLIES/SERVICES |
| ESTIMATED QUANTITY |
| UNIT |
| UNIT PRICE |
| ESTIMATED AMOUNT |
0014AE
| 480 |
| Hours |
Common Labor
ESTIMATED
| ITEM NO |
| SUPPLIES/SERVICES |
| ESTIMATED QUANTITY |
| UNIT |
| UNIT PRICE |
| ESTIMATED AMOUNT |
| 758 |
| Each |
Service Call
IAW PWS para 5.2. Requirements Item.
ESTIMATED
| ITEM NO |
| SUPPLIES/SERVICES |
| QUANTITY |
| UNIT |
| UNIT PRICE |
| AMOUNT |
| 1 |
| Each |
Accounting for Contract Services (CMR)
The Department of Army requires Contractor Manpower Reporting Application
(CMRA) to be completed by 31 October of each calendar year during the life of the contract. The Contractor shall provide all of the information requested and in the required format, using the following web address:
https://cmra.army.mil for the purpose of capturing contractor and subcontractor manpower utilized during the performance of this contract.
NET AMT
| ITEM NO |
| SUPPLIES/SERVICES |
| QUANTITY |
| UNIT |
| UNIT PRICE |
| AMOUNT |
War Hazard
Estimated cost for war hazard losses is (0)
NET AMT
| ITEM NO |
| SUPPLIES/SERVICES |
| QUANTITY |
| UNIT |
| UNIT PRICE |
| AMOUNT |
| 1 |
| Each |
Phase-in
Phase-In Period from 1 Aug 2016 thru 31 Aug 2016.
The incumbent contractor is not allowable for Phase-In cost.
NET AMT
| ITEM NO |
| SUPPLIES/SERVICES |
| ESTIMATED QUANTITY |
| UNIT |
| UNIT PRICE |
| ESTIMATED AMOUNT |
| 211 |
| Each |
Wet Chemical Fire Suppression System
To provide Inspection, Test and Maintenance of Wet Chemical fire suppression system at Camp Humphreys IAW PWS, Paragraph 5.1 See Attachment 3. Facility list and 2. UFC 3-601-2. REQUIREMENTS CLIN.
ESTIMATED
| ITEM NO |
| SUPPLIES/SERVICES |
| ESTIMATED QUANTITY |
| UNIT |
| UNIT PRICE |
| ESTIMATED AMOUNT |
| 29 |
| Each |
Fire Pumps
To provide Inspection, Test and Maintenance of Fire Pumps at Camp Humphreys IAW PWS, Paragraph 5.1. See Attachment 3. Facility list and 2. UFC 3-601-2. REQUIREMENTS CLIN.
ESTIMATED
| ITEM NO |
| SUPPLIES/SERVICES |
| ESTIMATED QUANTITY |
| UNIT |
| UNIT PRICE |
| ESTIMATED AMOUNT |
| 731,137 |
| Square Foot |
Dry Pipe Sprinkler Fire Suppression Syst
To provide Inspection, Test and Maintenance of Dry pipe Sprinkler Fire Suppression System at Camp Humphreys IAW PWS, Paragraph 5.1. See Attachment 3. Facility list and 2. UFC 3-601-2. REQUIREMENTS CLIN.
ESTIMATED
| ITEM NO |
| SUPPLIES/SERVICES |
| ESTIMATED QUANTITY |
| UNIT |
| UNIT PRICE |
| ESTIMATED AMOUNT |
| 179,845 |
| Square Foot |
AFFF Fire Suppression System
To provide Inspection, Test and Maintenance of AFFF Fire Suppression System at Camp Humphreys IAW PWS, Paragraph 5.1. See Attachment 3. Facility list and 2. UFC 3-601-2. REQUIREMENTS CLIN.
ESTIMATED
| ITEM NO |
| SUPPLIES/SERVICES |
| ESTIMATED QUANTITY |
| UNIT |
| UNIT PRICE |
| ESTIMATED AMOUNT |
| 43 |
| Each |
Standpipe Fire Suppression System
To provide Inspection, Test and Maintenance of Standpipe Fire Suppression System at Camp Humphreys IAW PWS, Paragraph 5.1. See Attachment 3. Facility list and 2. UFC 3-601-2. REQUIREMENTS CLIN.
ESTIMATED
| ITEM NO |
| SUPPLIES/SERVICES |
| ESTIMATED QUANTITY |
| UNIT |
| UNIT PRICE |
| ESTIMATED AMOUNT |
| 99 |
| Each |
Building Transceiver
To provide Inspection, Test and Maintenance of Building Transceiver at Camp Humphreys IAW PWS, Paragraph 5.1. See Attachment 3. Facility list and 2. UFC 3-601-2. REQUIREMENTS CLIN.
ESTIMATED
| ITEM NO |
| SUPPLIES/SERVICES |
| ESTIMATED QUANTITY |
| UNIT |
| UNIT PRICE |
| ESTIMATED AMOUNT |
| 7 |
| Each |
Cleaning Agent
To provide Inspection, Test and Maintenance of Cleaning Agent (1 EA) at Camp Humphreys IAW PWS, Paragraph 5.1. See Attachment 3. Facility list and 2. UFC 3-601-2. REQUIREMENTS CLIN.
ESTIMATED
| ITEM NO |
| SUPPLIES/SERVICES |
| ESTIMATED QUANTITY |
| UNIT |
| UNIT PRICE |
| ESTIMATED AMOUNT |
| 28 |
| Each |
Carbon Monoxide Detector
To provide Inspection, Test and Maintenance of Carbon monoxide detector (33 EA) at Camp Humphreys IAW PWS, Paragraph 5.1. See Attachment 3. Facility list and 2. UFC 3-601-2. REQUIREMENTS CLIN.
ESTIMATED
| ITEM NO |
| SUPPLIES/SERVICES |
| QUANTITY |
| UNIT |
| UNIT PRICE |
| AMOUNT |
| 12 |
| Months |
| OPTION |
| Wet Chemical Fire Suppression System |
FFP
To provide Inspection, Test and Maintenance of Wet Chemical fire suppression system (256 EA) at Camp Humphreys IAW PWS, Paragraph 5.1 See Attachment 3. Facility list and 2. UFC 3-601-2.
NET AMT
| ITEM NO |
| SUPPLIES/SERVICES |
| QUANTITY |
| UNIT |
| UNIT PRICE |
| AMOUNT |
| 12 |
| Months |
| OPTION |
| Dry Chemical Fire Suppression System |
FFP
To provide Inspection, Test and Maintenance of Dry chemical fire suppression system (2 EA) at Camp Humphreys IAW PWS, Paragraph 5.1. See Attachment 3. Facility list and 2. UFC 3-601-2.
NET AMT
| ITEM NO |
| SUPPLIES/SERVICES |
| QUANTITY |
| UNIT |
| UNIT PRICE |
| AMOUNT |
| 12 |
| Months |
| OPTION |
| Fire Pumps |
FFP
To provide Inspection, Test and Maintenance of Fire Pumps (36 EA) at Camp Humphreys IAW PWS, Paragraph 5.1. See Attachment 3. Facility list and 2. UFC 3-601-2.
NET AMT
| ITEM NO |
| SUPPLIES/SERVICES |
| QUANTITY |
| UNIT |
| UNIT PRICE |
| AMOUNT |
| 12 |
| Months |
| OPTION |
| Wet Pipe Sprinkler Fire Suppression Syst |
FFP
To provide Inspection, Test and Maintenance of Wet Pipe Sprinkler Fire Suppression System (16,819,435 SF) at Camp Humphreys IAW PWS, Paragraph 5.1. See Attachment 3. Facility list and 2. UFC 3-601-2.
NET AMT
| ITEM NO |
| SUPPLIES/SERVICES |
| QUANTITY |
| UNIT |
| UNIT PRICE |
| AMOUNT |
| 12 |
| Months |
| OPTION |
| Dry Pipe Sprinkler Fire Suppression Syst |
FFP
To provide Inspection, Test and Maintenance of Dry pipe Sprinkler Fire Suppression System (891,116 SF) at Camp Humphreys IAW PWS, Paragraph 5.1. See Attachment 3. Facility list and 2. UFC 3-601-2.
NET AMT
| ITEM NO |
| SUPPLIES/SERVICES |
| QUANTITY |
| UNIT |
| UNIT PRICE |
| AMOUNT |
| 12 |
| Months |
| OPTION |
| AFFF Fire Suppression System |
FFP
To provide Inspection, Test and Maintenance of AFFF Fire Suppression System (228,171 SF) at Camp Humphreys IAW PWS, Paragraph 5.1. See Attachment 3. Facility list and 2. UFC 3-601-2.
NET AMT
| ITEM NO |
| SUPPLIES/SERVICES |
| QUANTITY |
| UNIT |
| UNIT PRICE |
| AMOUNT |
| 12 |
| Months |
| OPTION |
| Standpipe Fire Suppression System |
FFP
To provide Inspection, Test and Maintenance of Standpipe Fire Suppression System (62 EA) at Camp Humphreys IAW PWS, Paragraph 5.1. See Attachment 3. Facility list and 2. UFC 3-601-2.
NET AMT
| ITEM NO |
| SUPPLIES/SERVICES |
| QUANTITY |
| UNIT |
| UNIT PRICE |
| AMOUNT |
| 12 |
| Months |
| OPTION |
| Fire Alarm and Detection System |
FFP
To provide Inspection, Test and Maintenance of Fire Alarm and Detection System (18,882,427 SF) at Camp Humphreys IAW PWS, Paragraph 5.1. See Attachment 3. Facility list and 2. UFC 3-601-2.
NET AMT
| ITEM NO |
| SUPPLIES/SERVICES |
| QUANTITY |
| UNIT |
| UNIT PRICE |
| AMOUNT |
| 12 |
| Months |
| OPTION |
| D500/D21 Fire Alarm Receiver |
FFP
To provide Inspection, Test and Maintenance of D500/D21 Fire Alarm Receiver (4 EA) at Camp Humphreys IAW PWS, Paragraph 5.1. See Attachment 3. Facility list and 2. UFC 3-601-2.
NET AMT
| ITEM NO |
| SUPPLIES/SERVICES |
| QUANTITY |
| UNIT |
| UNIT PRICE |
| AMOUNT |
| 12 |
| Months |
| OPTION |
| Building Transceiver |
FFP
To provide Inspection, Test and Maintenance of Building Transceiver (507 EA) at Camp Humphreys IAW PWS, Paragraph 5.1. See Attachment 3. Facility list and 2. UFC 3-601-2.
NET AMT
| ITEM NO |
| SUPPLIES/SERVICES |
| QUANTITY |
| UNIT |
| UNIT PRICE |
| AMOUNT |
| 12 |
| Months |
| OPTION |
| Fire Hydrant |
FFP
To provide Inspection, Test and Maintenance of Fire Hydrant (854 EA) at Camp Humphreys IAW PWS, Paragraph 5.1. See Attachment 3. Facility list and 2. UFC 3-601-2.
NET AMT
| ITEM NO |
| SUPPLIES/SERVICES |
| QUANTITY |
| UNIT |
| UNIT PRICE |
| AMOUNT |
| 12 |
| Months |
| OPTION |
| Cleaning Agent |
FFP
To provide Inspection, Test and Maintenance of Cleaning Agent (1 EA) at Camp Humphreys IAW PWS, Paragraph 5.1. See Attachment 3. Facility list and 2. UFC 3-601-2.
NET AMT
| ITEM NO |
| SUPPLIES/SERVICES |
| QUANTITY |
| UNIT |
| UNIT PRICE |
| AMOUNT |
| 12 |
| Months |
| OPTION |
| Carbon Monoxide Detector |
FFP
To provide Inspection, Test and Maintenance of Carbon monoxide detector (33 EA) at Camp Humphreys IAW PWS, Paragraph 5.1. See Attachment 3. Facility list and 2. UFC 3-601-2.
NET AMT
| ITEM NO |
| SUPPLIES/SERVICES |
| ESTIMATED QUANTITY |
| UNIT |
| UNIT PRICE |
| ESTIMATED AMOUNT |
| OPTION |
| Unscheduled Repair/Restoration Work |
FFP
(Requirement Item)
The contractor shall provide repair part, material, and labor cost for unscheduled repair service IAW PWS, Paragraph 5.3. of the PWS under this CLIN with the following SubCLINs. A Firm Fixed Price (FFP) Task Order will be issued after completion of negotiation for the number of labor hours and material amount for each task.
ESTIMATED
| ITEM NO |
| SUPPLIES/SERVICES |
| ESTIMATED QUANTITY |
| UNIT |
| UNIT PRICE |
| ESTIMATED AMOUNT |
1014AA
| 1 |
| Job |
| OPTION |
| Repair Parts and Material Cost |
FFP
Repair part and material for major repair IAW PWS, Paragraph 5.4. of the PWS. Total estimated amount is W250,508,170. The Contractor is not required to submit the unit price for this CLIN. Prices will be negotiated per delivery order.
ESTIMATED
| ITEM NO |
| SUPPLIES/SERVICES |
| ESTIMATED QUANTITY |
| UNIT |
| UNIT PRICE |
| ESTIMATED AMOUNT |
1014AB
| 120 |
| Hours |
| OPTION |
| Engineering Supervisor |
ESTIMATED
| ITEM NO |
| SUPPLIES/SERVICES |
| ESTIMATED QUANTITY |
| UNIT |
| UNIT PRICE |
| ESTIMATED AMOUNT |
1014AC
| 240 |
| Hours |
| OPTION |
| Electrical Fire Engineering Technician |
ESTIMATED
| ITEM NO |
| SUPPLIES/SERVICES |
| ESTIMATED QUANTITY |
| UNIT |
| UNIT PRICE |
| ESTIMATED AMOUNT |
1014AD
| 240 |
| Hours |
| OPTION |
| Mechanic Fire Engineering Technician |
ESTIMATED
| ITEM NO |
| SUPPLIES/SERVICES |
| ESTIMATED QUANTITY |
| UNIT |
| UNIT PRICE |
| ESTIMATED AMOUNT |
1014AE
| 480 |
| Hours |
| OPTION |
| Common Labor |
ESTIMATED
| ITEM NO |
| SUPPLIES/SERVICES |
| ESTIMATED QUANTITY |
| UNIT |
| UNIT PRICE |
| ESTIMATED AMOUNT |
| 758 |
| Each |
| OPTION |
| Service Call |
FFP
IAW PWS para 5.2. Requirements Item.
ESTIMATED
| ITEM NO |
| SUPPLIES/SERVICES |
| QUANTITY |
| UNIT |
| UNIT PRICE |
| AMOUNT |
| 1 |
| Each |
| OPTION |
| Accounting for Contract Services (CMR) |
FFP
The Department of Army requires Contractor Manpower Reporting Application
(CMRA) to be completed by 31 October of each calendar year during the life of the contract. The Contractor shall provide all of the information requested and in the required format, using the following web address:
https://cmra.army.mil for the purpose of capturing contractor and subcontractor manpower utilized during the performance of this contract.
NET AMT
| ITEM NO |
| SUPPLIES/SERVICES |
| QUANTITY |
| UNIT |
| UNIT PRICE |
| AMOUNT |
| OPTION |
| War Hazard |
FFP
Estimated cost for war hazard losses is (0)
NET AMT
| ITEM NO |
| SUPPLIES/SERVICES |
| ESTIMATED QUANTITY |
| UNIT |
| UNIT PRICE |
| ESTIMATED AMOUNT |
| 211 |
| Each |
| OPTION |
| Wet Chemical Fire Suppression System |
FFP
To provide Inspection, Test and Maintenance of Wet Chemical fire suppression system at Camp Humphreys IAW PWS, Paragraph 5.1 See Attachment 3. Facility list and 2. UFC 3-601-2. REQUIREMENTS CLIN.
ESTIMATED
| ITEM NO |
| SUPPLIES/SERVICES |
| ESTIMATED QUANTITY |
| UNIT |
| UNIT PRICE |
| ESTIMATED AMOUNT |
| 29 |
| Each |
| OPTION |
| Fire Pumps |
FFP
To provide Inspection, Test and Maintenance of Fire Pumps at Camp Humphreys IAW PWS, Paragraph 5.1. See Attachment 3. Facility list and 2. UFC 3-601-2. REQUIREMENTS CLIN.
ESTIMATED
| ITEM NO |
| SUPPLIES/SERVICES |
| ESTIMATED QUANTITY |
| UNIT |
| UNIT PRICE |
| ESTIMATED AMOUNT |
| 731,137 |
| Square Foot |
| OPTION |
| Dry pipe sprinkler fire suppression syst |
FFP
To provide Inspection, Test and Maintenance of Dry pipe Sprinkler Fire Suppression System at Camp Humphreys IAW PWS, Paragraph 5.1. See Attachment 3. Facility list and 2. UFC 3-601-2. REQUIREMENTS CLIN.
ESTIMATED
| ITEM NO |
| SUPPLIES/SERVICES |
| ESTIMATED QUANTITY |
| UNIT |
| UNIT PRICE |
| ESTIMATED AMOUNT |
| 179,845 |
| Square Foot |
| OPTION |
| AFFF Fire Suppression System |
FFP
To provide Inspection, Test and Maintenance of AFFF Fire Suppression System at Camp Humphreys IAW PWS, Paragraph 5.1. See Attachment 3. Facility list and 2. UFC 3-601-2. REQUIREMENTS CLIN.
ESTIMATED
| ITEM NO |
| SUPPLIES/SERVICES |
| ESTIMATED QUANTITY |
| UNIT |
| UNIT PRICE |
| ESTIMATED AMOUNT |
| 43 |
| Each |
| OPTION |
| Standpipe Fire Suppression System |
FFP
To provide Inspection, Test and Maintenance of Standpipe Fire Suppression System at Camp Humphreys IAW PWS, Paragraph 5.1. See Attachment 3. Facility list and 2. UFC 3-601-2. REQUIREMENTS CLIN.
ESTIMATED
| ITEM NO |
| SUPPLIES/SERVICES |
| ESTIMATED QUANTITY |
| UNIT |
| UNIT PRICE |
| ESTIMATED AMOUNT |
| 99 |
| Each |
| OPTION |
| Building Transceiver |
FFP
To provide Inspection, Test and Maintenance of Building Transceiver at Camp Humphreys IAW PWS, Paragraph 5.1. See Attachment 3. Facility list and 2. UFC 3-601-2. REQUIREMENTS CLIN.
ESTIMATED
| ITEM NO |
| SUPPLIES/SERVICES |
| ESTIMATED QUANTITY |
| UNIT |
| UNIT PRICE |
| ESTIMATED AMOUNT |
| 7 |
| Each |
| OPTION |
| Cleaning Agent |
FFP
To provide Inspection, Test and Maintenance of Cleaning Agent (1 EA) at Camp Humphreys IAW PWS, Paragraph 5.1. See Attachment 3. Facility list and 2. UFC 3-601-2. REQUIREMENTS CLIN.
ESTIMATED
| ITEM NO |
| SUPPLIES/SERVICES |
| ESTIMATED QUANTITY |
| UNIT |
| UNIT PRICE |
| ESTIMATED AMOUNT |
| 28 |
| Each |
| OPTION |
| Carbon Monoxide Detector |
FFP
To provide Inspection, Test and Maintenance of Carbon monoxide detector (33 EA) at Camp Humphreys IAW PWS, Paragraph 5.1. See Attachment 3. Facility list and 2. UFC 3-601-2. REQUIREMENTS CLIN.
ESTIMATED
| ITEM NO |
| SUPPLIES/SERVICES |
| QUANTITY |
| UNIT |
| UNIT PRICE |
| AMOUNT |
| 12 |
| Months |
| OPTION |
| Wet Chemical Fire Suppression System |
FFP
To provide Inspection, Test and Maintenance of Wet Chemical fire suppression system (256 EA) at Camp Humphreys IAW PWS, Paragraph 5.1 See Attachment 3. Facility list and 2. UFC 3-601-2.
NET AMT
| ITEM NO |
| SUPPLIES/SERVICES |
| QUANTITY |
| UNIT |
| UNIT PRICE |
| AMOUNT |
| 12 |
| Months |
| OPTION |
| Dry Chemical Fire Suppression System |
FFP
To provide Inspection, Test and Maintenance of Dry chemical fire suppression system (2 EA) at Camp Humphreys IAW PWS, Paragraph 5.1. See Attachment 3. Facility list and 2. UFC 3-601-2.
NET AMT
| ITEM NO |
| SUPPLIES/SERVICES |
| QUANTITY |
| UNIT |
| UNIT PRICE |
| AMOUNT |
| 12 |
| Months |
| OPTION |
| Fire Pumps |
FFP
To provide Inspection, Test and Maintenance of Fire Pumps (36 EA) at Camp Humphreys IAW PWS, Paragraph 5.1. See Attachment 3. Facility list and 2. UFC 3-601-2.
NET AMT
| ITEM NO |
| SUPPLIES/SERVICES |
| QUANTITY |
| UNIT |
| UNIT PRICE |
| AMOUNT |
| 12 |
| Months |
| OPTION |
| Wet Pipe Sprinkler Fire Suppression Syst |
FFP
To provide Inspection, Test and Maintenance of Wet Pipe Sprinkler Fire Suppression System (16,819,435 SF) at Camp Humphreys IAW PWS, Paragraph 5.1. See Attachment 3. Facility list and 2. UFC 3-601-2.
NET AMT
| ITEM NO |
| SUPPLIES/SERVICES |
| QUANTITY |
| UNIT |
| UNIT PRICE |
| AMOUNT |
| 12 |
| Months |
| OPTION |
| Dry Pipe Sprinkler Fire Suppression Syst |
FFP
To provide Inspection, Test and Maintenance of Dry pipe Sprinkler Fire Suppression System (891,116 SF) at Camp Humphreys IAW PWS, Paragraph 5.1. See Attachment 3. Facility list and 2. UFC 3-601-2.
NET AMT
| ITEM NO |
| SUPPLIES/SERVICES |
| QUANTITY |
| UNIT |
| UNIT PRICE |
| AMOUNT |
| 12 |
| Months |
| OPTION |
| AFFF Fire Suppression System |
FFP
To provide Inspection, Test and Maintenance of AFFF Fire Suppression System (228,171 SF) at Camp Humphreys IAW PWS, Paragraph 5.1. See Attachment 3. Facility list and 2. UFC 3-601-2.
NET AMT
| ITEM NO |
| SUPPLIES/SERVICES |
| QUANTITY |
| UNIT |
| UNIT PRICE |
| AMOUNT |
| 12 |
| Months |
| OPTION |
| Standpipe Fire Suppression System |
FFP
To provide Inspection, Test and Maintenance of Standpipe Fire Suppression System (62 EA) at Camp Humphreys IAW PWS, Paragraph 5.1. See Attachment 3. Facility list and 2. UFC 3-601-2.
NET AMT
| ITEM NO |
| SUPPLIES/SERVICES |
| QUANTITY |
| UNIT |
| UNIT PRICE |
| AMOUNT |
| 12 |
| Months |
| OPTION |
| Fire Alarm and Detection System |
FFP
To provide Inspection, Test and Maintenance of Fire Alarm and Detection System (18,882,427 SF) at Camp Humphreys IAW PWS, Paragraph 5.1. See Attachment 3. Facility list and 2. UFC 3-601-2.
NET AMT
| ITEM NO |
| SUPPLIES/SERVICES |
| QUANTITY |
| UNIT |
| UNIT PRICE |
| AMOUNT |
| 12 |
| Months |
| OPTION |
| D500/D21 Fire Alarm Receiver |
FFP
To provide Inspection, Test and Maintenance of D500/D21 Fire Alarm Receiver (4 EA) at Camp Humphreys IAW PWS, Paragraph 5.1. See Attachment 3. Facility list and 2. UFC 3-601-2.
NET AMT
| ITEM NO |
| SUPPLIES/SERVICES |
| QUANTITY |
| UNIT |
| UNIT PRICE |
| AMOUNT |
| 12 |
| Months |
| OPTION |
| Building Transceiver |
FFP
To provide Inspection, Test and Maintenance of Building Transceiver (507 EA) at Camp Humphreys IAW PWS, Paragraph 5.1. See Attachment 3. Facility list and 2. UFC 3-601-2.
NET AMT
| ITEM NO |
| SUPPLIES/SERVICES |
| QUANTITY |
| UNIT |
| UNIT PRICE |
| AMOUNT |
| 12 |
| Months |
| OPTION |
| Fire Hydrant |
FFP
To provide Inspection, Test and Maintenance of Fire Hydrant (854 EA) at Camp Humphreys IAW PWS, Paragraph 5.1. See Attachment 3. Facility list and 2. UFC 3-601-2.
NET AMT
| ITEM NO |
| SUPPLIES/SERVICES |
| QUANTITY |
| UNIT |
| UNIT PRICE |
| AMOUNT |
| 12 |
| Months |
| OPTION |
| Cleaning Agent |
FFP
To provide Inspection, Test and Maintenance of Cleaning Agent (1 EA) at Camp Humphreys IAW PWS, Paragraph 5.1. See Attachment 3. Facility list and 2. UFC 3-601-2.
NET AMT
| ITEM NO |
| SUPPLIES/SERVICES |
| QUANTITY |
| UNIT |
| UNIT PRICE |
| AMOUNT |
| 12 |
| Months |
| OPTION |
| Carbon Monoxide Detector |
FFP
To provide Inspection, Test and Maintenance of Carbon monoxide detector (33 EA) at Camp Humphreys IAW PWS, Paragraph 5.1. See Attachment 3. Facility list and 2. UFC 3-601-2.
NET AMT
| ITEM NO |
| SUPPLIES/SERVICES |
| ESTIMATED QUANTITY |
| UNIT |
| UNIT PRICE |
| ESTIMATED AMOUNT |
| OPTION |
| Unscheduled Repair/Restoration Work |
FFP
(Requirement Item)
The contractor shall provide repair part, material, and labor cost for unscheduled repair service IAW PWS, Paragraph 5.3. of the PWS under this CLIN with the following SubCLINs. A Firm Fixed Price (FFP) Task Order will be issued after completion of negotiation for the number of labor hours and material amount for each task.
ESTIMATED
| ITEM NO |
| SUPPLIES/SERVICES |
| ESTIMATED QUANTITY |
| UNIT |
| UNIT PRICE |
| ESTIMATED AMOUNT |
2014AA
| 1 |
| Job |
| OPTION |
| Repair Parts and Material Cost |
FFP
Repair part and material for major repair IAW PWS, Paragraph 5.4. of the PWS. Total estimated amount is W252,433,650. The Contractor is not required to submit the unit price for this CLIN. Prices will be negotiated per delivery order.
ESTIMATED
| ITEM NO |
| SUPPLIES/SERVICES |
| ESTIMATED QUANTITY |
| UNIT |
| UNIT PRICE |
| ESTIMATED AMOUNT |
2014AB
| 120 |
| Hours |
| OPTION |
| Engineering Supervisor |
ESTIMATED
| ITEM NO |
| SUPPLIES/SERVICES |
| ESTIMATED QUANTITY |
| UNIT |
| UNIT PRICE |
| ESTIMATED AMOUNT |
2014AC
| 240 |
| Hours |
| OPTION |
| Electrical Fire Engineering Technician |
ESTIMATED
| ITEM NO |
| SUPPLIES/SERVICES |
| ESTIMATED QUANTITY |
| UNIT |
| UNIT PRICE |
| ESTIMATED AMOUNT |
2014AD
| 240 |
| Hours |
| OPTION |
| Mechanic Fire Engineering Technician |
ESTIMATED
| ITEM NO |
| SUPPLIES/SERVICES |
| ESTIMATED QUANTITY |
| UNIT |
| UNIT PRICE |
| ESTIMATED AMOUNT |
2014AE
| 480 |
| Hours |
| OPTION |
| Common Labor |
ESTIMATED
| ITEM NO |
| SUPPLIES/SERVICES |
| ESTIMATED QUANTITY |
| UNIT |
| UNIT PRICE |
| ESTIMATED AMOUNT |
| 758 |
| Each |
| OPTION |
| Service Call |
FFP
ESTIMATED
| ITEM NO |
| SUPPLIES/SERVICES |
| QUANTITY |
| UNIT |
| UNIT PRICE |
| AMOUNT |
| 1 |
| Each |
| OPTION |
| Accounting for Contract Services (CMR) |
FFP
The Department of Army requires Contractor Manpower Reporting Application
(CMRA) to be completed by 31 October of each calendar year during the life of the contract. The Contractor shall provide all of the information requested and in the required format, using the following web address:
https://cmra.army.mil for the purpose of capturing contractor and
NET AMT
| ITEM NO |
| SUPPLIES/SERVICES |
| QUANTITY |
| UNIT |
| UNIT PRICE |
| AMOUNT |
| OPTION |
| War Hazard |
FFP
NET AMT
| ITEM NO |
| SUPPLIES/SERVICES |
| ESTIMATED QUANTITY |
| UNIT |
| UNIT PRICE |
| ESTIMATED AMOUNT |
| 211 |
| Each |
| OPTION |
| Wet Chemical Fire Suppression System |
FFP
To provide Inspection, Test and Maintenance of Wet Chemical fire suppression system at Camp Humphreys IAW PWS, Paragraph 5.1 See Attachment 3. Facility list and 2. UFC 3-601-2. REQUIREMENTS CLIN.
ESTIMATED
| ITEM NO |
| SUPPLIES/SERVICES |
| ESTIMATED QUANTITY |
| UNIT |
| UNIT PRICE |
| ESTIMATED AMOUNT |
| 29 |
| Each |
| OPTION |
| Fire Pumps |
FFP
To provide Inspection, Test and Maintenance of Fire Pumps at Camp Humphreys IAW PWS, Paragraph 5.1. See Attachment 3. Facility list and 2. UFC 3-601-2. REQUIREMENTS CLIN.
ESTIMATED
| ITEM NO |
| SUPPLIES/SERVICES |
| ESTIMATED QUANTITY |
| UNIT |
| UNIT PRICE |
| ESTIMATED AMOUNT |
| 731,137 |
| Square Foot |
| OPTION |
| Dry pipe sprinkler fire suppression syst |
FFP
To provide Inspection, Test and Maintenance of Dry pipe Sprinkler Fire Suppression System at Camp Humphreys IAW PWS, Paragraph 5.1. See Attachment 3. Facility list and 2. UFC 3-601-2. REQUIREMENTS CLIN.
ESTIMATED
| ITEM NO |
| SUPPLIES/SERVICES |
| ESTIMATED QUANTITY |
| UNIT |
| UNIT PRICE |
| ESTIMATED AMOUNT |
| 179,845 |
| Square Foot |
| OPTION |
| AFFF Fire Suppression System |
FFP
To provide Inspection, Test and Maintenance of AFFF Fire Suppression System at Camp Humphreys IAW PWS, Paragraph 5.1. See Attachment 3. Facility list and 2. UFC 3-601-2. REQUIREMENTS CLIN.
ESTIMATED
| ITEM NO |
| SUPPLIES/SERVICES |
| ESTIMATED QUANTITY |
| UNIT |
| UNIT PRICE |
| ESTIMATED AMOUNT |
| 43 |
| Each |
| OPTION |
| Standpipe Fire Suppression System |
FFP
To provide Inspection, Test and Maintenance of Standpipe Fire Suppression System at Camp Humphreys IAW PWS, Paragraph 5.1. See Attachment 3. Facility list and 2. UFC 3-601-2. REQUIREMENTS CLIN.
ESTIMATED
| ITEM NO |
| SUPPLIES/SERVICES |
| ESTIMATED QUANTITY |
| UNIT |
| UNIT PRICE |
| ESTIMATED AMOUNT |
| 99 |
| Each |
| OPTION |
| Building Transceiver |
FFP
To provide Inspection, Test and Maintenance of Building Transceiver at Camp Humphreys IAW PWS, Paragraph 5.1. See Attachment 3. Facility list and 2. UFC 3-601-2. REQUIREMENTS CLIN.
ESTIMATED
| ITEM NO |
| SUPPLIES/SERVICES |
| ESTIMATED QUANTITY |
| UNIT |
| UNIT PRICE |
| ESTIMATED AMOUNT |
| 7 |
| Each |
| OPTION |
| Cleaning Agent |
FFP
To provide Inspection, Test and Maintenance of Cleaning Agent (1 EA) at Camp Humphreys IAW PWS, Paragraph 5.1. See Attachment 3. Facility list and 2. UFC 3-601-2. REQUIREMENTS CLIN.
ESTIMATED
| ITEM NO |
| SUPPLIES/SERVICES |
| ESTIMATED QUANTITY |
| UNIT |
| UNIT PRICE |
| ESTIMATED AMOUNT |
| 28 |
| Each |
| OPTION |
| Carbon Monoxide Detector |
FFP
To provide Inspection, Test and Maintenance of Carbon monoxide detector (33 EA) at Camp Humphreys IAW PWS, Paragraph 5.1. See Attachment 3. Facility list and 2. UFC 3-601-2. REQUIREMENTS CLIN.
ESTIMATED
| ITEM NO |
| SUPPLIES/SERVICES |
| QUANTITY |
| UNIT |
| UNIT PRICE |
| AMOUNT |
| 12 |
| Months |
| OPTION |
| Wet Chemical Fire Suppression System |
FFP
To provide Inspection, Test and Maintenance of Wet Chemical fire suppression system (256 EA) at Camp Humphreys IAW PWS, Paragraph 5.1 See Attachment 3. Facility list and 2. UFC 3-601-2.
NET AMT
| ITEM NO |
| SUPPLIES/SERVICES |
| QUANTITY |
| UNIT |
| UNIT PRICE |
| AMOUNT |
| 12 |
| Months |
| OPTION |
| Dry Chemical Fire Suppression System |
FFP
To provide Inspection, Test and Maintenance of Dry chemical fire suppression system (2 EA) at Camp Humphreys IAW PWS, Paragraph 5.1. See Attachment 3. Facility list and 2. UFC 3-601-2.
NET AMT
| ITEM NO |
| SUPPLIES/SERVICES |
| QUANTITY |
| UNIT |
| UNIT PRICE |
| AMOUNT |
| 12 |
| Months |
| OPTION |
| Fire Pumps |
FFP
To provide Inspection, Test and Maintenance of Fire Pumps (36 EA) at Camp Humphreys IAW PWS, Paragraph 5.1. See Attachment 3. Facility list and 2. UFC 3-601-2.
NET AMT
| ITEM NO |
| SUPPLIES/SERVICES |
| QUANTITY |
| UNIT |
| UNIT PRICE |
| AMOUNT |
| 12 |
| Months |
| OPTION |
| Wet Pipe Sprinkler Fire Suppression Syst |
FFP
To provide Inspection, Test and Maintenance of Wet Pipe Sprinkler Fire Suppression System (16,819,435 SF) at Camp Humphreys IAW PWS, Paragraph 5.1. See Attachment 3. Facility list and 2. UFC 3-601-2.
NET AMT
| ITEM NO |
| SUPPLIES/SERVICES |
| QUANTITY |
| UNIT |
| UNIT PRICE |
| AMOUNT |
| 12 |
| Months |
| OPTION |
| Dry Pipe Sprinkler Fire Suppression Syst |
FFP
To provide Inspection, Test and Maintenance of Dry pipe Sprinkler Fire Suppression System (891,116 SF) at Camp Humphreys IAW PWS, Paragraph 5.1. See Attachment 3. Facility list and 2. UFC 3-601-2.
NET AMT
| ITEM NO |
| SUPPLIES/SERVICES |
| QUANTITY |
| UNIT |
| UNIT PRICE |
| AMOUNT |
| 12 |
| Months |
| OPTION |
| AFFF Fire Suppression System |
FFP
To provide Inspection, Test and Maintenance of AFFF Fire Suppression System (228,171 SF) at Camp Humphreys IAW PWS, Paragraph 5.1. See Attachment 3. Facility list and 2. UFC 3-601-2.
NET AMT
| ITEM NO |
| SUPPLIES/SERVICES |
| QUANTITY |
| UNIT |
| UNIT PRICE |
| AMOUNT |
| 12 |
| Months |
| OPTION |
| Standpipe Fire Suppression System |
FFP
To provide Inspection, Test and Maintenance of Standpipe Fire Suppression System (62 EA) at Camp Humphreys IAW PWS, Paragraph 5.1. See Attachment 3. Facility list and 2. UFC 3-601-2.
NET AMT
| ITEM NO |
| SUPPLIES/SERVICES |
| QUANTITY |
| UNIT |
| UNIT PRICE |
| AMOUNT |
| 12 |
| Months |
| OPTION |
| Fire Alarm and Detection System |
FFP
To provide Inspection, Test and Maintenance of Fire Alarm and Detection System (18,882,427 SF) at Camp Humphreys IAW PWS, Paragraph 5.1. See Attachment 3. Facility list and 2. UFC 3-601-2.
NET AMT
| ITEM NO |
| SUPPLIES/SERVICES |
| QUANTITY |
| UNIT |
| UNIT PRICE |
| AMOUNT |
| 12 |
| Months |
| OPTION |
| D500/D21 Fire Alarm Receiver |
FFP
To provide Inspection, Test and Maintenance of D500/D21 Fire Alarm Receiver (4 EA) at Camp Humphreys IAW PWS, Paragraph 5.1. See Attachment 3. Facility list and 2. UFC 3-601-2.
NET AMT
| ITEM NO |
| SUPPLIES/SERVICES |
| QUANTITY |
| UNIT |
| UNIT PRICE |
| AMOUNT |
| 12 |
| Months |
| OPTION |
| Building Transceiver |
FFP
To provide Inspection, Test and Maintenance of Building Transceiver (507 EA) at Camp Humphreys IAW PWS, Paragraph 5.1. See Attachment 3. Facility list and 2. UFC 3-601-2.
NET AMT
| ITEM NO |
| SUPPLIES/SERVICES |
| QUANTITY |
| UNIT |
| UNIT PRICE |
| AMOUNT |
| 12 |
| Months |
| OPTION |
| Fire Hydrant |
FFP
To provide Inspection, Test and Maintenance of Fire Hydrant (854 EA) at Camp Humphreys IAW PWS, Paragraph 5.1. See Attachment 3. Facility list and 2. UFC 3-601-2.
NET AMT
| ITEM NO |
| SUPPLIES/SERVICES |
| QUANTITY |
| UNIT |
| UNIT PRICE |
| AMOUNT |
| 12 |
| Months |
| OPTION |
| Cleaning Agent |
FFP
To provide Inspection, Test and Maintenance of Cleaning Agent (1 EA) at Camp Humphreys IAW PWS, Paragraph 5.1. See Attachment 3. Facility list and 2. UFC 3-601-2.
NET AMT
| ITEM NO |
| SUPPLIES/SERVICES |
| QUANTITY |
| UNIT |
| UNIT PRICE |
| AMOUNT |
| 12 |
| Months |
| OPTION |
| Carbon Monoxide Detector |
FFP
To provide Inspection, Test and Maintenance of Carbon monoxide detector (33 EA) at Camp Humphreys IAW PWS, Paragraph 5.1. See Attachment 3. Facility list and 2. UFC 3-601-2.
NET AMT
| ITEM NO |
| SUPPLIES/SERVICES |
| ESTIMATED QUANTITY |
| UNIT |
| UNIT PRICE |
| ESTIMATED AMOUNT |
| OPTION |
| Unscheduled Repair/Restoration Work |
FFP
(Requirement Item)
The contractor shall provide repair part, material, and labor cost for unscheduled repair service IAW PWS, Paragraph 5.3. of the PWS under this CLIN with the following SubCLINs. A Firm Fixed Price (FFP) Task Order will be issued after completion of negotiation for the number of labor hours and material amount for each task.
ESTIMATED
| ITEM NO |
| SUPPLIES/SERVICES |
| ESTIMATED QUANTITY |
| UNIT |
| UNIT PRICE |
| ESTIMATED AMOUNT |
3014AA
| 1 |
| Job |
| OPTION |
| Repair Parts and Material Cost |
FFP
Repair part and material for major repair IAW PWS, Paragraph 5.4. of the PWS. Total estimated amount is W254,222,104. The Contractor is not required to submit the unit price for this CLIN. Prices will be negotiated per delivery order.
ESTIMATED
| ITEM NO |
| SUPPLIES/SERVICES |
| ESTIMATED QUANTITY |
| UNIT |
| UNIT PRICE |
| ESTIMATED AMOUNT |
3014AB
| 120 |
| Hours |
| OPTION |
| Engineering Supervisor |
ESTIMATED
| ITEM NO |
| SUPPLIES/SERVICES |
| ESTIMATED QUANTITY |
| UNIT |
| UNIT PRICE |
| ESTIMATED AMOUNT |
3014AC
| 240 |
| Hours |
| OPTION |
| Electrical Fire Engineering Technician |
ESTIMATED
| ITEM NO |
| SUPPLIES/SERVICES |
| ESTIMATED QUANTITY |
| UNIT |
| UNIT PRICE |
| ESTIMATED AMOUNT |
3014AD
| 240 |
| Hours |
| OPTION |
| Mechanic Fire Engineering Technician |
ESTIMATED
| ITEM NO |
| SUPPLIES/SERVICES |
| ESTIMATED QUANTITY |
| UNIT |
| UNIT PRICE |
| ESTIMATED AMOUNT |
3014AE
| 480 |
| Hours |
| OPTION |
| Common Labor |
ESTIMATED
| ITEM NO |
| SUPPLIES/SERVICES |
| ESTIMATED QUANTITY |
| UNIT |
| UNIT PRICE |
| ESTIMATED AMOUNT |
| 758 |
| Each |
| OPTION |
| Service Call |
FFP
ESTIMATED
| ITEM NO |
| SUPPLIES/SERVICES |
| QUANTITY |
| UNIT |
| UNIT PRICE |
| AMOUNT |
| 1 |
| Each |
| OPTION |
| Accounting for Contract Services (CMR) |
FFP
The Department of Army requires Contractor Manpower Reporting Application
(CMRA) to be completed by 31 October of each calendar year during the life of the contract. The Contractor shall provide all of the information requested and in the required format, using the following web address:
https://cmra.army.mil for the purpose of capturing contractor and
NET AMT
| ITEM NO |
| SUPPLIES/SERVICES |
| QUANTITY |
| UNIT |
| UNIT PRICE |
| AMOUNT |
| OPTION |
| War Hazard |
FFP
NET AMT
| ITEM NO |
| SUPPLIES/SERVICES |
| ESTIMATED QUANTITY |
| UNIT |
| UNIT PRICE |
| ESTIMATED AMOUNT |
| 211 |
| Each |
| OPTION |
| Wet Chemical Fire Suppression System |
FFP
To provide Inspection, Test and Maintenance of Wet Chemical fire suppression system at Camp Humphreys IAW PWS, Paragraph 5.1 See Attachment 3. Facility list and 2. UFC 3-601-2. REQUIREMENTS CLIN.
ESTIMATED
| ITEM NO |
| SUPPLIES/SERVICES |
| ESTIMATED QUANTITY |
| UNIT |
| UNIT PRICE |
| ESTIMATED AMOUNT |
| 29 |
| Each |
| OPTION |
| Fire Pumps |
FFP
To provide Inspection, Test and Maintenance of Fire Pumps at Camp Humphreys IAW PWS, Paragraph 5.1. See Attachment 3. Facility list and 2. UFC 3-601-2. REQUIREMENTS CLIN.
ESTIMATED
| ITEM NO |
| SUPPLIES/SERVICES |
| ESTIMATED QUANTITY |
| UNIT |
| UNIT PRICE |
| ESTIMATED AMOUNT |
| 731,137 |
| Square Foot |
| OPTION |
| Dry pipe sprinkler fire suppression syst |
FFP
To provide Inspection, Test and Maintenance of Dry pipe Sprinkler Fire Suppression System at Camp Humphreys IAW PWS, Paragraph 5.1. See Attachment 3. Facility list and 2. UFC 3-601-2. REQUIREMENTS CLIN.
ESTIMATED
| ITEM NO |
| SUPPLIES/SERVICES |
| ESTIMATED QUANTITY |
| UNIT |
| UNIT PRICE |
| ESTIMATED AMOUNT |
| 179,845 |
| Square Foot |
| OPTION |
| AFFF Fire Suppression System |
FFP
To provide Inspection, Test and Maintenance of AFFF Fire Suppression System at Camp Humphreys IAW PWS, Paragraph 5.1. See Attachment 3. Facility list and 2. UFC 3-601-2. REQUIREMENTS CLIN.
ESTIMATED
| ITEM NO |
| SUPPLIES/SERVICES |
| ESTIMATED QUANTITY |
| UNIT |
| UNIT PRICE |
| ESTIMATED AMOUNT |
| 43 |
| Each |
| OPTION |
| Standpipe Fire Suppression System |
FFP
To provide Inspection, Test and Maintenance of Standpipe Fire Suppression System at Camp Humphreys IAW PWS, Paragraph 5.1. See Attachment 3. Facility list and 2. UFC 3-601-2. REQUIREMENTS CLIN.
ESTIMATED
| ITEM NO |
| SUPPLIES/SERVICES |
| ESTIMATED QUANTITY |
| UNIT |
| UNIT PRICE |
| ESTIMATED AMOUNT |
| 99 |
| Each |
| OPTION |
| Building Transceiver |
FFP
To provide Inspection, Test and Maintenance of Building Transceiver at Camp Humphreys IAW PWS, Paragraph 5.1. See Attachment 3. Facility list and 2. UFC 3-601-2. REQUIREMENTS CLIN.
ESTIMATED
| ITEM NO |
| SUPPLIES/SERVICES |
| ESTIMATED QUANTITY |
| UNIT |
| UNIT PRICE |
| ESTIMATED AMOUNT |
| 7 |
| Each |
| OPTION |
| Cleaning Agent |
FFP
To provide Inspection, Test and Maintenance of Cleaning Agent (1 EA) at Camp Humphreys IAW PWS, Paragraph 5.1. See Attachment 3. Facility list and 2. UFC 3-601-2. REQUIREMENTS CLIN.
ESTIMATED
| ITEM NO |
| SUPPLIES/SERVICES |
| ESTIMATED QUANTITY |
| UNIT |
| UNIT PRICE |
| ESTIMATED AMOUNT |
| 28 |
| Each |
| OPTION |
| Carbon Monoxide Detector |
FFP
To provide Inspection, Test and Maintenance of Carbon monoxide detector (33 EA) at Camp Humphreys IAW PWS, Paragraph 5.1. See Attachment 3. Facility list and 2. UFC 3-601-2. REQUIREMENTS CLIN.
ESTIMATED
| ITEM NO |
| SUPPLIES/SERVICES |
| QUANTITY |
| UNIT |
| UNIT PRICE |
| AMOUNT |
| 12 |
| Months |
| OPTION |
| Wet Chemical Fire Suppression System |
FFP
To provide Inspection, Test and Maintenance of Wet Chemical fire suppression system (256 EA) at Camp Humphreys IAW PWS, Paragraph 5.1 See Attachment 3. Facility list and 2. UFC 3-601-2.
NET AMT
| ITEM NO |
| SUPPLIES/SERVICES |
| QUANTITY |
| UNIT |
| UNIT PRICE |
| AMOUNT |
| 12 |
| Months |
| OPTION |
| Dry Chemical Fire Suppression System |
FFP
To provide Inspection, Test and Maintenance of Dry chemical fire suppression system (2 EA) at Camp Humphreys IAW PWS, Paragraph 5.1. See Attachment 3. Facility list and 2. UFC 3-601-2.
NET AMT
| ITEM NO |
| SUPPLIES/SERVICES |
| QUANTITY |
| UNIT |
| UNIT PRICE |
| AMOUNT |
| 12 |
| Months |
| OPTION |
| Fire Pumps |
FFP
To provide Inspection, Test and Maintenance of Fire Pumps (36 EA) at Camp Humphreys IAW PWS, Paragraph 5.1. See Attachment 3. Facility list and 2. UFC 3-601-2.
NET AMT
| ITEM NO |
| SUPPLIES/SERVICES |
| QUANTITY |
| UNIT |
| UNIT PRICE |
| AMOUNT |
| 12 |
| Months |
| OPTION |
| Wet Pipe Sprinkler Fire Suppression Syst |
FFP
To provide Inspection, Test and Maintenance of Wet Pipe Sprinkler Fire Suppression System (16,819,435 SF) at Camp Humphreys IAW PWS, Paragraph 5.1. See Attachment 3. Facility list and 2. UFC 3-601-2.
NET AMT
| ITEM NO |
| SUPPLIES/SERVICES |
| QUANTITY |
| UNIT |
| UNIT PRICE |
| AMOUNT |
| 12 |
| Months |
| OPTION |
| Dry Pipe Sprinkler Fire Suppression Syst |
FFP
To provide Inspection, Test and Maintenance of Dry pipe Sprinkler Fire Suppression System (891,116 SF) at Camp Humphreys IAW PWS, Paragraph 5.1. See Attachment 3. Facility list and 2. UFC 3-601-2.
NET AMT
| ITEM NO |
| SUPPLIES/SERVICES |
| QUANTITY |
| UNIT |
| UNIT PRICE |
| AMOUNT |
| 12 |
| Months |
| OPTION |
| AFFF Fire Suppression System |
FFP
To provide Inspection, Test and Maintenance of AFFF Fire Suppression System (228,171 SF) at Camp Humphreys IAW PWS, Paragraph 5.1. See Attachment 3. Facility list and 2. UFC 3-601-2.
NET AMT
| ITEM NO |
| SUPPLIES/SERVICES |
| QUANTITY |
| UNIT |
| UNIT PRICE |
| AMOUNT |
| 12 |
| Months |
| OPTION |
| Standpipe Fire Suppression System |
FFP
To provide Inspection, Test and Maintenance of Standpipe Fire Suppression System (62 EA) at Camp Humphreys IAW PWS, Paragraph 5.1. See Attachment 3. Facility list and 2. UFC 3-601-2.
NET AMT
| ITEM NO |
| SUPPLIES/SERVICES |
| QUANTITY |
| UNIT |
| UNIT PRICE |
| AMOUNT |
| 12 |
| Months |
| OPTION |
| Fire Alarm and Detection System |
FFP
To provide Inspection, Test and Maintenance of Fire Alarm and Detection System (18,882,427 SF) at Camp Humphreys IAW PWS, Paragraph 5.1. See Attachment 3. Facility list and 2. UFC 3-601-2.
NET AMT
| ITEM NO |
| SUPPLIES/SERVICES |
| QUANTITY |
| UNIT |
| UNIT PRICE |
| AMOUNT |
| 12 |
| Months |
| OPTION |
| D500/D21 Fire Alarm Receiver |
FFP
To provide Inspection, Test and Maintenance of D500/D21 Fire Alarm Receiver (4 EA) at Camp Humphreys IAW PWS, Paragraph 5.1. See Attachment 3. Facility list and 2. UFC 3-601-2.
NET AMT
| ITEM NO |
| SUPPLIES/SERVICES |
| QUANTITY |
| UNIT |
| UNIT PRICE |
| AMOUNT |
| 12 |
| Months |
| OPTION |
| Building Transceiver |
FFP
To provide Inspection, Test and Maintenance of Building Transceiver (507 EA) at Camp Humphreys IAW PWS, Paragraph 5.1. See Attachment 3. Facility list and 2. UFC 3-601-2.
NET AMT
| ITEM NO |
| SUPPLIES/SERVICES |
| QUANTITY |
| UNIT |
| UNIT PRICE |
| AMOUNT |
| 12 |
| Months |
| OPTION |
| Fire Hydrant |
FFP
To provide Inspection, Test and Maintenance of Fire Hydrant (854 EA) at Camp Humphreys IAW PWS, Paragraph 5.1. See Attachment 3. Facility list and 2. UFC 3-601-2.
NET AMT
| ITEM NO |
| SUPPLIES/SERVICES |
| QUANTITY |
| UNIT |
| UNIT PRICE |
| AMOUNT |
| 12 |
| Months |
| OPTION |
| Cleaning Agent |
FFP
To provide Inspection, Test and Maintenance of Cleaning Agent (1 EA) at Camp Humphreys IAW PWS, Paragraph 5.1. See Attachment 3. Facility list and 2. UFC 3-601-2.
NET AMT
| ITEM NO |
| SUPPLIES/SERVICES |
| QUANTITY |
| UNIT |
| UNIT PRICE |
| AMOUNT |
| 12 |
| Months |
| OPTION |
| Carbon Monoxide Detector |
FFP
To provide Inspection, Test and Maintenance of Carbon monoxide detector (33 EA) at Camp Humphreys IAW PWS, Paragraph 5.1. See Attachment 3. Facility list and 2. UFC 3-601-2.
NET AMT
| ITEM NO |
| SUPPLIES/SERVICES |
| ESTIMATED QUANTITY |
| UNIT |
| UNIT PRICE |
| ESTIMATED AMOUNT |
| OPTION |
| Unscheduled Repair/Restoration Work |
FFP
(Requirement Item)
The contractor shall provide repair part, material, and labor cost for unscheduled repair service IAW PWS, Paragraph 5.3. of the PWS under this CLIN with the following SubCLINs. A Firm Fixed Price (FFP) Task Order will be issued after completion of negotiation for the number of labor hours and material amount for each task.
ESTIMATED
| ITEM NO |
| SUPPLIES/SERVICES |
| ESTIMATED QUANTITY |
| UNIT |
| UNIT PRICE |
| ESTIMATED AMOUNT |
4014AA
| 1 |
| Job |
| OPTION |
| Repair Parts and Material Cost |
FFP
Repair part and material for major repair IAW PWS, Paragraph 5.4. of the PWS. Total estimated amount is W256,299,944. The Contractor is not required to submit the unit price for this CLIN. Prices will be negotiated per delivery order.
ESTIMATED
| ITEM NO |
| SUPPLIES/SERVICES |
| ESTIMATED QUANTITY |
| UNIT |
| UNIT PRICE |
| ESTIMATED AMOUNT |
4014AB
| 120 |
| Hours |
| OPTION |
| Engineering Supervisor |
ESTIMATED
| ITEM NO |
| SUPPLIES/SERVICES |
| ESTIMATED QUANTITY |
| UNIT |
| UNIT PRICE |
| ESTIMATED AMOUNT |
4014AC
| 240 |
| Hours |
| OPTION |
| Electrical Fire Engineering Technician |
ESTIMATED
| ITEM NO |
| SUPPLIES/SERVICES |
| ESTIMATED QUANTITY |
| UNIT |
| UNIT PRICE |
| ESTIMATED AMOUNT |
4014AD
| 240 |
| Hours |
| OPTION |
| Mechanic Fire Engineering Technician |
ESTIMATED
| ITEM NO |
| SUPPLIES/SERVICES |
| ESTIMATED QUANTITY |
| UNIT |
| UNIT PRICE |
| ESTIMATED AMOUNT |
4014AE
| 480 |
| Hours |
| OPTION |
| Common Labor |
ESTIMATED
| ITEM NO |
| SUPPLIES/SERVICES |
| ESTIMATED QUANTITY |
| UNIT |
| UNIT PRICE |
| ESTIMATED AMOUNT |
| 758 |
| Each |
| OPTION |
| Service Call |
FFP
ESTIMATED
| ITEM NO |
| SUPPLIES/SERVICES |
| QUANTITY |
| UNIT |
| UNIT PRICE |
| AMOUNT |
| 1 |
| Each |
| OPTION |
| Accounting for Contract Services (CMR) |
FFP
The Department of Army requires Contractor Manpower Reporting Application
(CMRA) to be completed by 31 October of each calendar year during the life of the contract. The Contractor shall provide all of the information requested and in the required format, using the following web address:
https://cmra.army.mil for the purpose of capturing contractor and
NET AMT
| ITEM NO |
| SUPPLIES/SERVICES |
| QUANTITY |
| UNIT |
| UNIT PRICE |
| AMOUNT |
| OPTION |
| War Hazard |
FFP
NET AMT
| ITEM NO |
| SUPPLIES/SERVICES |
| ESTIMATED QUANTITY |
| UNIT |
| UNIT PRICE |
| ESTIMATED AMOUNT |
| 211 |
| Each |
| OPTION |
| Wet Chemical Fire Suppression System |
FFP
To provide Inspection, Test and Maintenance of Wet Chemical fire suppression system at Camp Humphreys IAW PWS, Paragraph 5.1 See Attachment 3. Facility list and 2. UFC 3-601-2. REQUIREMENTS CLIN.
ESTIMATED
| ITEM NO |
| SUPPLIES/SERVICES |
| ESTIMATED QUANTITY |
| UNIT |
| UNIT PRICE |
| ESTIMATED AMOUNT |
| 29 |
| Each |
| OPTION |
| Fire Pumps |
FFP
To provide Inspection, Test and Maintenance of Fire Pumps at Camp Humphreys IAW PWS, Paragraph 5.1. See Attachment 3. Facility list and 2. UFC 3-601-2. REQUIREMENTS CLIN.
ESTIMATED
| ITEM NO |
| SUPPLIES/SERVICES |
| ESTIMATED QUANTITY |
| UNIT |
| UNIT PRICE |
| ESTIMATED AMOUNT |
| 731,137 |
| Square Foot |
| OPTION |
| Dry pipe sprinkler fire suppression syst |
FFP
To provide Inspection, Test and Maintenance of Dry pipe Sprinkler Fire Suppression System at Camp Humphreys IAW PWS, Paragraph 5.1. See Attachment 3. Facility list and 2. UFC 3-601-2. REQUIREMENTS CLIN.
ESTIMATED
| ITEM NO |
| SUPPLIES/SERVICES |
| ESTIMATED QUANTITY |
| UNIT |
| UNIT PRICE |
| ESTIMATED AMOUNT |
| 179,845 |
| Square Foot |
| OPTION |
| AFFF Fire Suppression System |
FFP
To provide Inspection, Test and Maintenance of AFFF Fire Suppression System at Camp Humphreys IAW PWS, Paragraph 5.1. See Attachment 3. Facility list and 2. UFC 3-601-2. REQUIREMENTS CLIN.
ESTIMATED
| ITEM NO |
| SUPPLIES/SERVICES |
| ESTIMATED QUANTITY |
| UNIT |
| UNIT PRICE |
| ESTIMATED AMOUNT |
| 43 |
| Each |
| OPTION |
| Standpipe Fire Suppression System |
FFP
To provide Inspection, Test and Maintenance of Standpipe Fire Suppression System at Camp Humphreys IAW PWS, Paragraph 5.1. See Attachment 3. Facility list and 2. UFC 3-601-2. REQUIREMENTS CLIN.
ESTIMATED
| ITEM NO |
| SUPPLIES/SERVICES |
| ESTIMATED QUANTITY |
| UNIT |
| UNIT PRICE |
| ESTIMATED AMOUNT |
| 99 |
| Each |
| OPTION |
| Building Transceiver |
FFP
To provide Inspection, Test and Maintenance of Building Transceiver at Camp Humphreys IAW PWS, Paragraph 5.1. See Attachment 3. Facility list and 2. UFC 3-601-2. REQUIREMENTS CLIN.
ESTIMATED
| ITEM NO |
| SUPPLIES/SERVICES |
| ESTIMATED QUANTITY |
| UNIT |
| UNIT PRICE |
| ESTIMATED AMOUNT |
| 7 |
| Each |
| OPTION |
| Cleaning Agent |
FFP
To provide Inspection, Test and Maintenance of Cleaning Agent (1 EA) at Camp Humphreys IAW PWS, Paragraph 5.1. See Attachment 3. Facility list and 2. UFC 3-601-2. REQUIREMENTS CLIN.
ESTIMATED
| ITEM NO |
| SUPPLIES/SERVICES |
| ESTIMATED QUANTITY |
| UNIT |
| UNIT PRICE |
| ESTIMATED AMOUNT |
| 28 |
| Each |
| OPTION |
| Carbon Monoxide Detector |
FFP
To provide Inspection, Test and Maintenance of Carbon monoxide detector (33 EA) at Camp Humphreys IAW PWS, Paragraph 5.1. See Attachment 3. Facility list and 2. UFC 3-601-2. REQUIREMENTS CLIN.
ESTIMATED
PWS
PERFORMANCE WORK STATEMENT (PWS)
Inspection, Test, Maintenance and Repair of
Fire Alarm Detection, and Suppression System
1. General: This is a non-personal services contract to provide the service of inspection, test, maintenance and repair of Fire Alarm Detection and Suppression System at Area III. The Government shall not exercise any supervision or control over the contract service providers performing the services herein. Such contract service providers shall be accountable solely to the Contractor who, in turn is responsible to the Government.
1.1 Description of Services/Introduction: USAG Humphreys is facing a multi-billion dollar transformation program that will add 400 plus new facilities to the inventory. This brings a major challenge that other garrisons are not experiencing. DPW’s plan is to keep and improve the sustainability of the existing facilities as well as the ones associated with the transformation infrastructure.
1.2 Background: This service will be performed in various facilities, which shall include officer quarters, enlisted quarters, retail outlets, recreation facilities, offices, warehouses, and aircraft shelters, or any other facility at Area III in the Republic of Korea (ROK). All services shall be provided in accordance with established standards, principles, and ethics of the profession and applicable professional specialty organizations, National Fire Protection Association (NFPA) standards, and Unified Facilities Criteria (UFC) 3-601-02, latest edition.
1.3 Objectives: The objective of this contract is to provide inspection, testing, preventive maintenance and repair on wet chemical system, dry chemical system, fire pump system, wet pipe sprinkler system, dry pipe sprinkler system, foam spray and sprinkler system, stand pipe system fire alarm and detection system, D-21 fire alarm receiver, building transceivers, in the various facilities at Area III.
1.4 Period of Performance: The period of performance shall be for one (1) Base Year and four (4) 12 month option years. The Period of Performance reads as follows:
Phase-In:
1 Aug 2016 - 31 Aug 2016 (CLIN 0018)
Base Year:
1 Sep 2016 - 31 Jul 2017 (CLINs 0001 - 0017)
1st Option:
1 Aug 2016 - 31 Jul 2017 (CLINs 1001 - 1017)
2nd Option:
1 Aug 2017 - 31 Jul 2018 (CLINs 2001 - 2017)
3rd Option:
1 Aug 2018 - 31 Jul 2019 (CLINs 3101 - 3117)
4th Option:
1 Aug 2019 - 31 Jul 2020 (CLINs 4001 - 4017)
1.5 General Information
1.5.1 Holidays:
1.5.1.1 U.S. Federal holidays are as follows:
1 January (New Year's Day) 3rd Monday, January (Dr. King’s Birthday) 3rd Monday, February (President’s Birthday) Last Monday, May (Memorial Day) 4 July (Independence Day)
1st Monday September (Labor Day)
2nd Monday, October (Columbus Day) 11 November (Veterans' Day)
4th Thursday, November (Thanksgiving Day) 25 December (Christmas Day)
1.5.1.2. ROK legal holidays are as follows:
1 and 2 January (New Year)
Lunar New Year (On the Lunar Calendar)
1 March (Independence Movement Day) 1 May (Labor Day) 5 May (Children's Day) Buddha's Birthday (On Lunar calendar) 6 June (Memorial Day)
17 July (Constitution Day) 15 August (Liberation Day) Chu-Sok (On the Lunar Calendar)
3 October (National Foundation Day)
25 December (Christmas Day)
1.5.2 Hours of Operation: The contractor is responsible for conducting business, between the hours of 0800 and 1700 hrs Monday through Friday except Korean holidays or when the Government facility is closed due to local or national emergencies, administrative closings, or similar Government directed facility closings.