Ques # RFP Ref Question Answer Change made to Synopsis/Solicitation?
Section L- 4.1.2
This section reads "Include a fully completed “Small Business Program Representations” as found in section K of the solicitation and FAR 52.219-1, if applicable." Can you please post section K?
52.219-9, Small Business Program Representations was inadvertenly not included in the Solicitation.
Yes, 52.19-9 was included.
2 PWS
What is the ceiling height throughout all facilities? Will a lift be provided?
Lift will not be provided. B700-8ft, B699-10ft, E1430-10ft, B688/690-10ft. Water tank sheds have 15ft ceilings. No
3 PWS
On the sample drawing provided in SOW, it appears there are wet pipe sprinkler systems as well. Are the facilities equipped with any other suppression system? Is the inspection, testing and maintenance of any other systems outside of the deluge systems part of this project?
The deluge piping has heat activated fire sprinklers installed in various locations throughout but is not a fully separate monitored system. ITM of other fire alarms is not part of this contract.
No
4 PWS
Can you please provide model and manufacture for fire alarm/releasing panels associated with the systems?
Permanent systems:
Pilotex High Speed Deluge Control Panels Det Tronics C7050 Detectors Det Tronics R7404 Controllers Pilotex HSM-D High Speed Control Modules ASCO 8210 solenoid valves Automatic Sprinkler nozzles
Portable Systems:
1ea Pyrotech LFM-7489 1 ea CVD Equipment Corporation system that is charged with a nitrogen tank and has 1ea R7404, 4 UV Detectors and 4 Nozzles. No
5 PWS How are the deluge systems actuated?
Det Tronics C7050 Ultraviolet Flame Detectors with manual pull stations as backups. No