W912SV18B5001 RFI Log

30 August 2018

1. The Equipment Manufacturer has requested wiring diagrams of the actuators. Is this information available and can it be provided for their reference?

ANSWER – See file drawing [A01 AXQD102073 SHEET E109.pdf]

2. The solicitation listed part numbers for breakers, however the SOW does not clearly state that breakers are to be replaced. Are the breakers to be replaced?

ANSWER -- Yes, breakers replaced.

3. Can the existing wiring be re-used, or does the wiring need to be replaced for both power and controls?

ANSWER -- Wiring can be reused.

4. What is our responsibility regarding the existing floats. Is there any work related to the floats?

ANSWER -- No work required on floats

5. The specifications reference excavation several times. Please confirm there is no excavation required.

ANSWER -- No excavation is contemplated by the Government.

6. The solicitation references testing of the actuators. Is this testing requirement include third party testing, or simply testing and confirming operation?

ANSWER -- Just confirmation of operations.