W912QR25RA023_Specs_V2-0000.pdf
PDF 4 MB Posted
- Attached to
- Construction of a Microgrid System at the Conroe Army Reserve Center (ARC) in Conroe, TX
- Solicitation number
- W912QR25RA023
About this file
This document is a comprehensive set of technical specifications for a Microgrid Design project for the Conroe Army Reserve Center in Conroe, Texas. The project involves constructing a 750 kW DC microgrid system with multiple key components, including solar photovoltaic panels, a 340 kW natural gas generator, electrical distribution equipment, fire alarm systems, and associated infrastructure. The specifications detail precise technical requirements for equipment installation, including electrical systems, solar arrays, generator set, switchgear, lighting, telecommunications cabling, and grounding systems.
The project is solicited by the Department of the Army Corps of Engineers Engineering District Louisville, with a solicitation number W912QR25RA023. The specifications are dated 31 March 2025, with detailed technical requirements across multiple divisions including electrical, communications, and site preparation. Key technical specifications include requirements for solar photovoltaic modules with minimum 305-watt output, a natural gas generator with specific performance parameters, addressable fire alarm systems, and comprehensive grounding and bonding provisions. The project emphasizes cybersecurity, energy efficiency, and compliance with multiple federal standards and regulations, including NFPA, IEEE, and UL requirements.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| W912QR25RA023_Plans-0002.pdf | ||
| W912QR25RA023_Specs-0002.pdf | ||
| W912QR25RA023-0001.pdf | ||
| W912QR25RA023_Specs_V1-0000.pdf | ||
| W912QR25RA023_Plans-0000.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Solicitation For Conroe Army Reserve Center Microgrid Conroe, TX
P2: 505014
Design-Bid-Build
Specifications Vol. 2 (Div. 26-33) Certified Final Design
31 March 2025
W912QR25RA023
ARIMS: 200A
Disposition: Maintain for 15yrs after construction
W912QR25RA023_Specs_V2-0000
Signature Page
01/22/2025 01/22/2025
Pages or sheets covered by this seal:
00 10 00, 00 80 00.00 06, 01 32 01.00 06, 01 33 00, 01 35 26.00 06, 01 42 00, 01 45 00.15 10, 01 45 04.10 06, 01 50 00, 01 57 19.00 06, 01 74 19, 01 78 23
Pages or sheets covered by this seal:
01 45 35, 03 30 00, 03 62 16, 05 05 20, 05 12 00, 05 50 13, 05 51 00, 05 51 33, 05 52 00, 13 34 19, 31 63 29
01/22/2025 01/22/2025 Pages or sheets covered by this seal:
01 46 00.00 07, 25 08 20, 27 10 00.00 48, 33 82 00.00 48
Pages or sheets covered by this seal:
02 41 00, 31 00 00, 31 10 00, 31 11 00, 31 23 00.00 20, 32 11 23, 32 12 13, 32 12 16.16, 32 16 19, 32 31 13, 32 92 19, 33 11 00, 33 40 00
01/22/2025Date:
01/22/2025 01/22/2025 Pages or sheets covered by this seal:
09 90 00, 23 03 00.00 20, 23 07 00, 33 11 23
Pages or sheets covered by this seal:
25 05 11.01, 25 05 11.02, 25 05 11.03, 25 05 11.04, 25 08 10
01/22/2025 01/22/2025 Pages or sheets covered by this seal:
26 05 00.00 40, 26 05 19.00 10, 26 05 26.00 40, 26 05 71.00 40, 26 05 73 26 08 00, 26 13 14, 26 20 00, 26 23 00, 26 31 00, 26 32 15.00, 26 41 00, 26 51 00, 26 56 00, 33 71 02
Pages or sheets covered by this seal:
28 31 70
1/
/2
01/22/2025
Shaw n Olphin
Digitally signed by Shawn Olphin Date:
2025.01.21 15:40:26 -07'00'
P2: 505014, Microgrid Design 750KWDC Conroe ARC Conroe, TX
PROJECT TABLE OF CONTENTS Page 1
CERTIFIED FINAL
PROJECT TABLE OF CONTENTS
VOLUME 1
DIVISION 00 - PROCUREMENT AND CONTRACTING REQUIREMENTS
00 10 00 PRICE BREAKOUT SCHEDULE
00 80 00.00 06 04/21, CHG 1: 06/23 SPECIAL PROVISIONS
DIVISION 01 - GENERAL REQUIREMENTS
01 32 01.00 06 10/23 PROJECT SCHEDULE
01 33 00 08/18, CHG 4: 02/21 SUBMITTAL PROCEDURES
01 35 26.00 06 GOVERNMENT SAFETY REQUIREMENTS
01 42 00 02/19 SOURCES FOR REFERENCE PUBLICATIONS
01 45 00.15 10 11/16, CHG 2: 08/19 RESIDENT MANAGEMENT SYSTEM CONTRACTOR
MODE (RMS CM)
01 45 04.10 06 CONTRACTOR QUALITY CONTROL
01 45 35 11/20 SPECIAL INSPECTIONS
01 46 00.00 07 05/23 COMMISSIONING - MICROGRID
01 50 00 11/20, CHG 2: 08/22 TEMPORARY CONSTRUCTION FACILITIES AND
CONTROLS
01 57 19.00 06 04/20 TEMPORARY ENVIRONMENTAL CONTROLS AND
PERMITS
01 74 19 02/19, CHG 3: 11/21 CONSTRUCTION WASTE MANAGEMENT AND
DISPOSAL
01 78 23 08/15, CHG 2: 08/21 OPERATION AND MAINTENANCE DATA
DIVISION 02 - EXISTING CONDITIONS
02 41 00 08/22 DEMOLITION AND DECONSTRUCTION
DIVISION 03 – CONCRETE
03 30 00 02/19, CHG 4: 08/22 CAST-IN-PLACE CONCRETE
03 62 16 02/18 METALLIC NON-SHRINK GROUTING
DIVISION 05 – METALS
05 05 20 05/22 POST-INSTALLED CONCRETE AND MASONRY
ANCHORS
05 12 00 08/18, CHG 2: 05/21 STRUCTURAL STEEL
05 50 13 05/17, CHG 1: 08/18 MISCELLANEOUS METAL FABRICATIONS
05 51 00 02/17, CHG 1: 05/17 METAL STAIRS
05 51 33 02/16, CHG 2: 02/18 METAL LADDERS
05 52 00 02/18, CHG 1: 02/20 METAL RAILINGS
DIVISION 09 – FINISHES
09 90 00 02/21 PAINTS AND COATINGS
DIVISION 13 - SPECIAL CONSTRUCTION
13 34 19 08/20, CHG 1: 02/21 METAL CARPORT SYSTEMS
PROJECT TABLE OF CONTENTS Page 2
CERTIFIED FINAL
DIVISION 23 - HEATING, VENTILATING, AND AIR CONDITIONING (HVAC)
23 03 00.00 20 08/10, CHG 3: 08/18 BASIC MECHANICAL MATERIALS AND METHODS
23 07 00 02/13, CHG 7: 05/20 THERMAL INSULATION FOR MECHANICAL
SYSTEMS
DIVISION 25 - INTEGRATED AUTOMATION
25 05 11.01 05/21, CHG 1: 08/23 CYBERSECURITY FOR MICROGRID FACILITY-
RELATED CONTROL SYSTEMS
25 05 11.02 05/21, CHG 1: 08/23 CYBERSECURITY FOR EEDRS FACILITY-
RELATED CONTROL SYSTEMS
25 05 11.03 05/21, CHG 1: 08/23 CYBERSECURITY FOR FLS FACILITY-RELATED
CONTROL SYSTEMS
25 05 11.04 05/21, CHG 1: 08/23 CYBERSECURITY FOR HVAC DDC FACILITY-
25 08 10 05/21
25 08 20 05/21
DIVISION 26 – ELECTRICAL
26 05 00.00 40 11/20 26 05 19.00 10 11/22 26 05 26.00 40 08/19
26 05 71.00 40 02/17
26 08 00 11/22 26 13 14 11/21
RELATED CONTROL SYSTEMS
UTILITY MONITORING AND CONTROL SYSTEM
TESTING
MICROGRID CONTROL SYSTEM
COMMON WORK RESULTS FOR ELECTRICAL
INSULATED WIRE AND CABLE
GROUNDING AND BONDING FOR ELECTRICAL
SYSTEMS
LOW VOLTAGE OVERCURRENT PROTECTIVE
DEVICES
POWER SYSTEM STUDIES
APPARATUS INSPECTION AND TESTING
SWITCHGEAR HOUSE
VOLUME 2
26 20 00 08/19, CHG 3: 11/21 INTERIOR DISTRIBUTION SYSTEM
26 23 00 05/15, CHG 2: 11/19 LOW-VOLTAGE SWITCHGEAR
26 31 00 11/21 FACILITY-SCALE SOLAR PHOTOVOLTAIC (PV)
SYSTEMS
26 32 15.00 05/20 ENGINE-GENERATOR SET STATIONARY 15-2500
KW, WITH AUXILIARIES
26 41 00 11/13 LIGHTNING PROTECTION SYSTEM
26 51 00 05/20, CHG 2: 11/21 INTERIOR LIGHTING
26 56 00 08/21 EXTERIOR LIGHTING
DIVISION 27 – COMMUNICATIONS
27 10 00.00 48 10/20 BUILDING TELECOMMUNICATIONS CABLING
SYSTEM
DIVISION 28 - ELECTRONIC SAFETY AND SECURITY
28 31 70 08/20 INTERIOR FIRE ALARM SYSTEM, ADDRESSABLE
DIVISION 31 – EARTHWORK
31 00 00 08/23 EARTHWORK
31 10 00 02/21 SITE CLEARING
26 05 73 08/23
PROJECT TABLE OF CONTENTS Page 3
31 11 00 11/18 CLEARING AND GRUBBING
31 23 00.00 20 02/11, CHG 2: 08/15 EXCAVATION AND FILL
31 63 29 11/19 DRILLED CONCRETE PIERS AND SHAFTS
DIVISION 32 - EXTERIOR IMPROVEMENTS
32 11 23 05/22 AGGREGATE BASE COURSE FOR FLEXIBLE
PAVING
32 12 13 05/17 BITUMINOUS TACK AND PRIME COATS
32 12 16.16 11/20 ROAD-MIX ASPHALT PAVING
32 16 19 05/18 CONCRETE CURBS, GUTTERS AND SIDEWALKS
32 31 13 11/21 CHAIN LINK FENCES AND GATES
32 92 19 08/17, CHG 1: 08/21 SEEDING
DIVISION 33 – UTILITIES
33 11 00 02/18, CHG 1: 02/22 WATER UTILITY DISTRIBUTION PIPING
33 11 23 11/09, CHG 1: 08/17 NATURAL GAS AND LIQUID PETROLEUM PIPING
33 40 00 11/21 STORMWATER UTILITIES
33 71 02 08/21 UNDERGROUND ELECTRICAL DISTRIBUTION
33 82 00.00 48 04/20 TELECOMMUNICATIONS OUTSIDE PLANT (OSP)
APPENDIX
CONTROL CORRELATION IDENTIFIERS
-- End of Project Table of Contents --
SECTION TABLE OF CONTENTS
DIVISION 26 - ELECTRICAL
SECTION 26 20 00
INTERIOR DISTRIBUTION SYSTEM
08/19, CHG 3: 11/21
PART 1 GENERAL
1.1 REFERENCES
1.2 DEFINITIONS
1.3 SUBMITTALS
1.4 QUALITY ASSURANCE
1.4.1 Fuses
1.4.2 Regulatory Requirements
1.4.3 Standard Products
1.4.3.1 Alternative Qualifications
1.4.3.2 Material and Equipment Manufacturing Date
1.5 MAINTENANCE
1.5.1 Electrical Systems
1.6 WARRANTY
PART 2 PRODUCTS
2.1 MATERIALS AND EQUIPMENT
2.2 CONDUIT AND FITTINGS
2.2.1 Rigid Metallic Conduit
2.2.1.1 Rigid, Threaded Zinc-Coated Steel Conduit
2.2.1.2 Rigid Aluminum Conduit
2.2.2 Rigid Nonmetallic Conduit
2.2.3 Intermediate Metal Conduit (IMC)
2.2.4 Electrical, Zinc-Coated Steel Metallic Tubing (EMT)
2.2.5 Plastic-Coated Rigid Steel and IMC Conduit
2.2.6 Flexible Metal Conduit
2.2.6.1 Liquid-Tight Flexible Metal Conduit, Steel
2.2.7 Fittings for Metal Conduit, EMT, and Flexible Metal Conduit
2.2.7.1 Fittings for Rigid Metal Conduit and IMC
2.2.7.2 Fittings for EMT
2.2.8 Fittings for Rigid Nonmetallic Conduit
2.2.9 Liquid-Tight Flexible Nonmetallic Conduit
2.3 SURFACE RACEWAY
2.3.1 Surface Metal Raceway
2.3.2 Surface Nonmetallic Raceway
2.4 CABINETS, JUNCTION BOXES, AND PULL BOXES
2.5 WIRES AND CABLES
2.5.1 Conductors
2.5.1.1 Equipment Manufacturer Requirements
2.5.2 Color Coding
2.5.2.1 Ground and Neutral Conductors
2.5.2.2 Ungrounded Conductors
2.5.3 Insulation
2.5.4 Bonding Conductors
2.6 DEVICE PLATES
SECTION 26 20 00 Page 1
2.7 SWITCHES
2.7.1 Toggle Switches
2.7.2 Switch with Red Pilot Handle
2.7.3 Breakers Used as Switches
2.7.4 Disconnect Switches
2.8 FUSES
2.8.1 Fuseholders
2.8.2 Cartridge Fuses, Current Limiting Type (Class R)
2.8.3 Cartridge Fuses, High-Interrupting Capacity, Current Limiting
Type (Classes J, L, and CC)
2.8.4 Cartridge Fuses, Current Limiting Type (Class T)
2.9 RECEPTACLES
2.9.1 Weatherproof Receptacles
2.9.2 Ground-Fault Circuit Interrupter Receptacles
2.10 PANELBOARDS
2.10.1 Enclosure
2.10.2 Panelboard Buses
2.10.2.1 Panelboard Neutrals for Non-Linear Loads
2.10.3 Circuit Breakers
2.10.3.1 Multipole Breakers
2.10.3.2 Circuit Breaker With Ground-Fault Circuit Interrupter
2.11 ENCLOSED CIRCUIT BREAKERS
2.12 MOTOR SHORT-CIRCUIT PROTECTOR (MSCP)
2.13 TRANSFORMERS
2.13.1 Specified Transformer Efficiency
2.14 MOTORS
2.14.1 High Efficiency Single-Phase Motors
2.14.2 Premium Efficiency Polyphase and Single-Phase Motors
2.14.3 Motor Sizes
2.14.4 Wiring and Conduit
2.15 MOTOR CONTROLLERS
2.15.1 Control Wiring
2.15.2 Control Circuit Terminal Blocks
2.15.2.1 Types of Terminal Blocks
2.15.3 Control Circuits
2.15.4 Enclosures for Motor Controllers
2.15.5 Multiple-Speed Motor Controllers and Reversible Motor
Controllers
2.15.6 Pushbutton Stations
2.15.7 Pilot and Indicating Lights
2.16 LOCKOUT REQUIREMENTS
2.17 TELECOMMUNICATIONS SYSTEM
2.18 GROUNDING AND BONDING EQUIPMENT
2.18.1 Ground Rods
2.18.2 Ground Bus
2.18.3 Secondary Bonding Busbar
2.19 HAZARDOUS LOCATIONS
2.20 MANUFACTURER'S NAMEPLATE
2.21 FIELD FABRICATED NAMEPLATES
2.22 WARNING SIGNS
2.23 WIREWAYS
2.24 METERING
2.25 METER BASE ONLY
2.26 SURGE PROTECTIVE DEVICES
2.27 FACTORY APPLIED FINISH
2.28 SOURCE QUALITY CONTROL
2.28.1 Transformer Factory Tests
2.29 COORDINATED POWER SYSTEM PROTECTION
SECTION 26 20 00 Page 2
PART 3 EXECUTION
3.1 INSTALLATION
3.1.1 Underground Service
3.1.2 Hazardous Locations
3.1.3 Service Entrance Identification
3.1.3.1 Labels
3.1.4 Wiring Methods
3.1.4.1 Pull Wire
3.1.5 Conduit Installation
3.1.5.1 Restrictions Applicable to Aluminum Conduit
3.1.5.2 Restrictions Applicable to EMT
3.1.5.3 Restrictions Applicable to Nonmetallic Conduit
3.1.5.4 Underground Conduit
3.1.6 Watthour Meters
3.1.7 Surge Protective Devices
3.2 FIELD FABRICATED NAMEPLATE MOUNTING
3.3 WARNING SIGN MOUNTING
3.4 FIELD APPLIED PAINTING
3.5 FIELD QUALITY CONTROL
3.5.1 Devices Subject to Manual Operation
3.5.2 600-Volt Wiring Test
3.5.3 Transformer Tests
3.5.4 Ground-Fault Receptacle Test
3.5.5 Arc-Fault Receptacle Test
3.5.6 Grounding System Test
3.5.7 Watthour Meter
3.5.8 Phase Rotation Test
-- End of Section Table of Contents --
SECTION 26 20 00 Page 3
SECTION 26 20 00
INTERIOR DISTRIBUTION SYSTEM
08/19, CHG 3: 11/21
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI)
ANSI C12.1 (2014; Errata 2016) Electric Meters - Code for Electricity Metering
ASTM INTERNATIONAL (ASTM)
ASTM B1 (2013) Standard Specification for Hard-Drawn Copper Wire
ASTM B8 (2011; R 2017) Standard Specification for Concentric-Lay-Stranded Copper Conductors, Hard, Medium-Hard, or Soft
ASTM D709 (2017) Standard Specification for Laminated Thermosetting Materials
INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)
IEEE 100 (2000; Archived) The Authoritative Dictionary of IEEE Standards Terms
IEEE C2 (2023) National Electrical Safety Code
INTERNATIONAL ELECTRICAL TESTING ASSOCIATION (NETA)
NETA ATS (2021) Standard for Acceptance Testing Specifications for Electrical Power Equipment and Systems
NATIONAL ELECTRICAL CONTRACTORS ASSOCIATION (NECA)
NECA NEIS 1 (2015) Standard for Good Workmanship in Electrical Construction
NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)
ANSI C12.7 (2014) Requirements for Watthour Meter Sockets
ANSI C80.1 (2020) American National Standard for Electrical Rigid Steel Conduit (ERSC)
ANSI C80.3 (2020) American National Standard for
SECTION 26 20 00 Page 4
Electrical Metallic Tubing (EMT)
ANSI C80.5 (2020) American National Standard for Electrical Rigid Aluminum Conduit
NEMA 250 (2020) Enclosures for Electrical Equipment (1000 Volts Maximum)
NEMA FU 1 (2012) Low Voltage Cartridge Fuses
NEMA ICS 1 (2022) Standard for Industrial Control and Systems: General Requirements
NEMA ICS 2 (2000; R 2020) Industrial Control and Systems Controllers, Contactors, and Overload Relays Rated 600 V
NEMA ICS 4 (2015) Application Guideline for Terminal Blocks
NEMA ICS 6 (1993; R 2016) Industrial Control and Systems: Enclosures
NEMA KS 1 (2013) Enclosed and Miscellaneous Distribution Equipment Switches (600 V Maximum)
NEMA MG 1 (2021) Motors and Generators
NEMA MG 10 (2017) Energy Management Guide for Selection and Use of Fixed Frequency Medium AC Squirrel-Cage Polyphase Induction Motors
NEMA MG 11 (1977; R 2012) Energy Management Guide for Selection and Use of Single Phase Motors
NEMA RN 1 (2005; R 2013) Polyvinyl-Chloride (PVC) Externally Coated Galvanized Rigid Steel Conduit and Intermediate Metal Conduit
NEMA ST 20 (2014) Dry-Type Transformers for General Applications
NEMA TC 2 (2020) Standard for Electrical Polyvinyl Chloride (PVC) Conduit
NEMA TC 3 (2021) Polyvinyl Chloride (PVC) Fittings for Use With Rigid PVC Conduit and Tubing
NEMA WD 1 (1999; R 2020) Standard for General Color Requirements for Wiring Devices
NEMA WD 6 (2021) Wiring Devices Dimensions Specifications
NEMA Z535.4 (2011; R 2017) Product Safety Signs and Labels
SECTION 26 20 00 Page 5
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 70 (2023) National Electrical Code
NFPA 70E (2021) Standard for Electrical Safety in the Workplace
TELECOMMUNICATIONS INDUSTRY ASSOCIATION (TIA)
TIA-569 (2019e; Add 1 2022) Telecommunications Pathways and Spaces
TIA-607 (2019d) Generic Telecommunications Bonding and Grounding (Earthing) for Customer Premises
U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)
10 CFR 431 Energy Efficiency Program for Certain Commercial and Industrial Equipment
29 CFR 1910.147 The Control of Hazardous Energy (Lock Out/Tag Out)
29 CFR 1910.303 Electrical, General
UNDERWRITERS LABORATORIES (UL)
UL 1 (2005; Reprint Jan 2022) UL Standard for Safety Flexible Metal Conduit
UL 5 (2016; Reprint Jul 2022) UL Standard for Safety Surface Metal Raceways and Fittings
UL 5A (2015; Reprint Aug 2020) Nonmetallic Surface Raceways and Fittings
UL 6 (2022) UL Standard for Safety Electrical Rigid Metal Conduit-Steel
UL 6A (2008; Reprint Mar 2021) UL Standard for Safety Electrical Rigid Metal Conduit - Aluminum, Red Brass, and Stainless Steel
UL 20 (2018; Reprint Jan 2021) UL Standard for Safety General-Use Snap Switches
UL 44 (2018; Reprint May 2021) UL Standard for Safety Thermoset-Insulated Wires and Cables
UL 50 (2015) UL Standard for Safety Enclosures for Electrical Equipment, Non-Environmental Considerations
UL 67 (2018; Reprint Jul 2020) UL Standard for Safety Panelboards
UL 83 (2017; Reprint Mar 2020) UL Standard for Safety Thermoplastic-Insulated Wires and
SECTION 26 20 00 Page 6
Cables
UL 248-4 (2010; Reprint Apr 2019) Low-Voltage Fuses
- Part 4: Class CC Fuses
UL 248-8 (2011; Reprint Aug 2020) Low-Voltage Fuses
- Part 8: Class J Fuses
UL 248-10 (2011; Reprint Aug 2020) Low-Voltage Fuses
- Part 10: Class L Fuses
UL 248-12 (2011; Reprint Aug 2020) Low Voltage Fuses
- Part 12: Class R Fuses
UL 248-15 (2018) Low-Voltage Fuses - Part 15: Class T Fuses
UL 360 (2013; Reprint Aug 2021) UL Standard for Safety Liquid-Tight Flexible Metal Conduit
UL 467 (2022) UL Standard for Safety Grounding and Bonding Equipment
UL 489 (2016; Rev 2019) UL Standard for Safety Molded-Case Circuit Breakers, Molded-Case Switches and Circuit-Breaker Enclosures
UL 498 (2017) UL Standard for Safety Attachment Plugs and Receptacles
UL 506 (2017; Reprint Jan 2022) UL Standard for Safety Specialty Transformers
UL 508 (2018; Reprint Jul 2021) UL Standard for Safety Industrial Control Equipment
UL 514B (2012; Reprint May 2020) Conduit, Tubing and Cable Fittings
UL 651 (2011; Reprint May 2022) UL Standard for Safety Schedule 40, 80, Type EB and A Rigid PVC Conduit and Fittings
UL 674 (2022) UL Standard for Safety Electric Motors and Generators for Use in Hazardous (Classified) Locations
UL 797 (2007; Reprint Mar 2021) UL Standard for Safety Electrical Metallic Tubing -- Steel
UL 869A (2006; Reprint Jun 2020) Reference Standard for Service Equipment
UL 870 (2016; Reprint Mar 2019) UL Standard for Safety Wireways, Auxiliary Gutters, and Associated Fittings
UL 943 (2016; Reprint Feb 2018) UL Standard for Safety Ground-Fault Circuit-Interrupters
SECTION 26 20 00 Page 7
UL 984 (1996; Reprint Sep 2005) Hermetic Refrigerant Motor-Compressors
UL 1063 (2017; Reprint Jun 2022) UL Standard for Safety Machine-Tool Wires and Cables
UL 1203 (2013; Reprint Apr 2022) UL Standard for Safety Explosion-Proof and Dust-Ignition-Proof Electrical Equipment for Use in Hazardous (Classified) Locations
UL 1242 (2006; Reprint Apr 2022) UL Standard for Safety Electrical Intermediate Metal Conduit -- Steel
UL 1449 (2021; Reprint Dec 2022) UL Standard for Safety Surge Protective Devices
UL 1660 (2019; Reprint Jan 2022) Liquid-Tight Flexible Nonmetallic Conduit
UL 1699 (2017; Reprint Feb 2022) UL Standard for Safety Arc-Fault Circuit-Interrupters
UL 4248-1 (2022) UL Standard for Safety Fuseholders
- Part 1: General Requirements
UL 4248-12 (2018; Reprint Feb 2022) UL Standard for Safety Fuseholders - Part 12: Class R
1.2 DEFINITIONS
Unless otherwise specified or indicated, electrical and electronics terms used in these specifications, and on the drawings, are as defined in
IEEE 100 .
1.3 SUBMITTALS
Government approval is required for submittals with a "G" or "S" classification. Submittals not having a "G" or "S" classification are for information only. When used, a code following the "G" classification identifies the office that will review the submittal for the Government.
Submit the following in accordance with Section 01 33 00 SUBMITTAL
PROCEDURES:
SD-02 Shop Drawings
Panelboards; G
Transformers; G
Wireways; G
SD-03 Product Data
Receptacles; G
Circuit Breakers; G
SECTION 26 20 00 Page 8
Switches; G
Transformers; G
Enclosed Circuit Breakers; G
Motor Controllers; G
Metering; G
Meter Base Only; G
Secondary Bonding Busbar; G
Surge Protective Devices; G
SD-06 Test Reports
600-volt Wiring Test; G
Grounding System Test; G
Transformer Tests; G
Ground-fault Receptacle Test; G
Arc-fault Receptacle Test; G
SD-07 Certificates
Fuses; G
SD-09 Manufacturer's Field Reports
Transformer Factory Tests
SD-10 Operation and Maintenance Data
Electrical Systems, Data Package 5; G
Metering, Data Package 5; G
1.4 QUALITY ASSURANCE
1.4.1 Fuses
Submit coordination data as specified in paragraph, FUSES of this section.
1.4.2 Regulatory Requirements
In each of the publications referred to herein, consider the advisory provisions to be mandatory, as though the word, "must" had been substituted for "should" wherever it appears. Interpret references in these publications to the "authority having jurisdiction," or words of similar meaning, to mean the Contracting Officer. Provide equipment, materials, installation, and workmanship in accordance with NFPA 70 unless more stringent requirements are specified or indicated. NECA NEIS 1 shall be considered the minimum standard for workmanship.
SECTION 26 20 00 Page 9
1.4.3 Standard Products
Provide materials and equipment that are products of manufacturers regularly engaged in the production of such products which are of equal material, design and workmanship and:
a. Have been in satisfactory commercial or industrial use for 2 years prior to bid opening including applications of equipment and materials under similar circumstances and of similar size.
b. Have been on sale on the commercial market through advertisements, manufacturers' catalogs, or brochures during the 2-year period.
c. Where two or more items of the same class of equipment are required, provide products of a single manufacturer; however, the component parts of the item need not be the products of the same manufacturer unless stated in this section.
1.4.3.1 Alternative Qualifications
Products having less than a 2-year field service record will be acceptable if a certified record of satisfactory field operation for not less than 6000 hours, exclusive of the manufacturers' factory or laboratory tests, is furnished.
1.4.3.2 Material and Equipment Manufacturing Date
Products manufactured more than 3 years prior to date of delivery to site are not acceptable.
1.5 MAINTENANCE
1.5.1 Electrical Systems
Submit operation and maintenance data in accordance with Section 01 78 23, OPERATION AND MAINTENANCE DATA and as specified herein. Submit operation and maintenance manuals for electrical systems that provide basic data relating to the design, operation, and maintenance of the electrical distribution system for the building. Include the following:
a. Single line diagram of the "as-built" building electrical system.
b. Schematic diagram of electrical control system (other than HVAC, covered elsewhere).
c. Manufacturers' operating and maintenance manuals on active electrical equipment.
1.6 WARRANTY
Provide equipment items supported by service organizations that are reasonably convenient to the equipment installation in order to render satisfactory service to the equipment on a regular and emergency basis during the warranty period of the contract.
SECTION 26 20 00 Page 10
PART 2 PRODUCTS
2.1 MATERIALS AND EQUIPMENT
As a minimum, meet requirements of UL, where UL standards are established for those items, and requirements of NFPA 70 for all materials, equipment, and devices.
2.2 CONDUIT AND FITTINGS
Conform to the following:
2.2.1 Rigid Metallic Conduit
2.2.1.1 Rigid, Threaded Zinc-Coated Steel Conduit
ANSI C80.1 , UL 6 .
2.2.1.2 Rigid Aluminum Conduit
ANSI C80.5 , UL 6A .
2.2.2 Rigid Nonmetallic Conduit
PVC Type EPC-40 in accordance with NEMA TC 2, UL 651 .
2.2.3 Intermediate Metal Conduit (IMC)
UL 1242 , zinc-coated steel only.
2.2.4 Electrical, Zinc-Coated Steel Metallic Tubing (EMT)
UL 797 , ANSI C80.3 .
2.2.5 Plastic-Coated Rigid Steel and IMC Conduit
NEMA RN 1, Type 40( 40 mils thick).
2.2.6 Flexible Metal Conduit
UL 1 , limited to 6 feet.
2.2.6.1 Liquid-Tight Flexible Metal Conduit, Steel
UL 360 , limited to 6 feet.
2.2.7 Fittings for Metal Conduit, EMT, and Flexible Metal Conduit
UL 514B . Ferrous fittings: cadmium- or zinc-coated in accordance with
UL 514B .
2.2.7.1 Fittings for Rigid Metal Conduit and IMC
Threaded-type. Split couplings unacceptable.
2.2.7.2 Fittings for EMT
Die Cast compression type.
SECTION 26 20 00 Page 11
2.2.8 Fittings for Rigid Nonmetallic Conduit
NEMA TC 3 for PVC, and UL 514B .
2.2.9 Liquid-Tight Flexible Nonmetallic Conduit
UL 1660 .
2.3 SURFACE RACEWAY
2.3.1 Surface Metal Raceway
UL 5 , two-piece painted steel, totally enclosed, snap-cover type. Provide multiple outlet-type raceway with grounding-type receptacle where indicated. Provide receptacles as specified herein, spaced a minimum of one every 18 inches.
2.3.2 Surface Nonmetallic Raceway
UL 5A , nonmetallic totally enclosed, snap-cover type.
2.4 CABINETS, JUNCTION BOXES, AND PULL BOXES
UL 50 ; volume greater than 100 cubic inches, NEMA Type 1 enclosure; sheet steel, hot-dip, zinc-coated. Where exposed to wet, damp, or corrosive environments, NEMA Type 3R.
2.5 WIRES AND CABLES
Provide wires and cables in accordance applicable requirements of NFPA 70 and UL for type of insulation, jacket, and conductor specified or indicated. Do not use wires and cables manufactured more than 12 months prior to date of delivery to site.
2.5.1 Conductors
Provide the following:
a. Conductor sizes and capacities shown are based on copper, unless indicated otherwise.
b. Conductors No. 8 AWG and larger diameter: stranded.
c. Conductors No. 10 AWG and smaller diameter: solid.
d. Conductors for remote control, alarm, and signal circuits, classes 1, 2, and 3: stranded unless specifically indicated otherwise.
e. All conductors: copper, unless type of conductor material is specifically indicated, or specified, or required by equipment manufacturer.
2.5.1.1 Equipment Manufacturer Requirements
When manufacturer's equipment requires copper conductors at the terminations or requires copper conductors to be provided between components of equipment, provide copper conductors or splices, splice boxes, and other work required to satisfy manufacturer's requirements.
SECTION 26 20 00 Page 12
2.5.2 Color Coding
Provide color coding for service, feeder, branch, control, and signaling circuit conductors.
2.5.2.1 Ground and Neutral Conductors
Provide color coding of ground and neutral conductors as follows:
a. Grounding conductors: Green.
b. Neutral conductors: White.
c. Exception, where neutrals of more than one system are installed in same raceway or box, other neutrals color coding: white with a different colored (not green) stripe for each.
2.5.2.2 Ungrounded Conductors
Provide color coding of ungrounded conductors in different voltage systems as follows:
a. 208/120 volt, three-phase
(1) Phase A - black
(2) Phase B - red
(3) Phase C - blue
b. 480/277 volt, three-phase
(1) Phase A - brown
(2) Phase B - orange
(3) Phase C - yellow
c. 120/240 volt, single phase: Black and red
2.5.3 Insulation
Unless specified or indicated otherwise or required by NFPA 70 , provide power and lighting wires rated for 600-volts, Type THWN/THHN conforming to UL 83 or Type XHHW or RHW conforming to UL 44 , except that grounding wire may be type TW conforming to UL 83 ; remote-control and signal circuits:
Type TW or TF, conforming to UL 83 . Where equipment or devices require 90-degree Centigrade (C) conductors, provide only conductors with 90-degree C insulation or better.
2.5.4 Bonding Conductors
ASTM B1, solid bare copper wire for sizes No. 8 AWG and smaller diameter;
ASTM B8, Class B, stranded bare copper wire for sizes No. 6 AWG and larger diameter.
2.6 DEVICE PLATES
Provide the following:
SECTION 26 20 00 Page 13
a. UL listed, one-piece device plates for outlets to suit the devices installed.
b. For metal outlet boxes, plates on unfinished walls: zinc-coated sheet steel or cast metal having round or beveled edges.
c. For nonmetallic boxes and fittings, other suitable plates may be provided.
d. Plates on finished walls: satin finish stainless steel or brushed-finish aluminum, minimum 0.03 inch thick.
e. Screws: machine-type with countersunk heads in color to match finish of plate.
f. Sectional type device plates are not be permitted.
g. Plates installed in wet locations: gasketed and UL listed for "wet locations."
2.7 SWITCHES
2.7.1 Toggle Switches
NEMA WD 1, UL 20 , single pole, double pole, and three-way, totally enclosed with bodies of thermoplastic or thermoset plastic and mounting strap with grounding screw. Include the following:
a. Handles: ivory thermoplastic.
b. Wiring terminals: screw-type, side-wired.
c. Contacts: silver-cadmium and contact arm - one-piece copper alloy.
d. Switches: rated quiet-type ac only, 120/277 volts, with current rating and number of poles indicated.
2.7.2 Switch with Red Pilot Handle
NEMA WD 1. Provide the following:
a. Pilot lights that are integrally constructed as a part of the switch's handle.
b. Pilot light color: red and illuminate whenever the switch is closed or "on".
c. Pilot lighted switch: rated 20 amps and 120 volts or 277 volts as indicated.
d. The circuit's neutral conductor to each switch with a pilot light.
2.7.3 Breakers Used as Switches
For 120- and 277-Volt fluorescent fixtures, mark breakers "SWD" in accordance with UL 489 .
SECTION 26 20 00 Page 14
2.7.4 Disconnect Switches
NEMA KS 1. Provide heavy duty-type switches where indicated, where switches are rated higher than 240 volts, and for double-throw switches.
Utilize Class R fuseholders and fuses for fused switches, unless indicated otherwise. Provide horsepower rated for switches serving as the motor-disconnect means. Provide switches in NEMA 1 3R, enclosure.
2.8 FUSES
NEMA FU 1. Provide complete set of fuses for each fusible switch panel and control center. Coordinate time-current characteristics curves of fuses serving motors or connected in series with circuit breakers or other circuit protective devices for proper operation. Submit coordination data for approval. Provide fuses with a voltage rating not less than circuit voltage.
2.8.1 Fuseholders
Provide in accordance with UL 4248-1 .
2.8.2 Cartridge Fuses, Current Limiting Type (Class R)
UL 248-12 , Class RK-1 RK-5 time-delay type. Provide only Class R associated fuseholders in accordance with UL 4248-12 .
2.8.3 Cartridge Fuses, High-Interrupting Capacity, Current Limiting Type (Classes J, L, and CC)
UL 248-8 , UL 248-10 , UL 248-4 , Class J for zero to 600 amperes, Class L for 601 to 6,000 amperes, and Class CC for zero to 30 amperes.
2.8.4 Cartridge Fuses, Current Limiting Type (Class T)
UL 248-15 , Class T for zero to 1,200 amperes, 300 volts; and zero to 800 amperes, 600 volts.
2.9 RECEPTACLES
Provide the following:
a. UL 498 , general purpose specification grade. Residential grade receptacles are not acceptable.
b. Ratings and configurations: as indicated.
c. Bodies: ivory as per NEMA WD 1.
d. Face and body: thermoplastic supported on a metal mounting strap.
e. Dimensional requirements: per NEMA WD 6.
f. Screw-type, side-wired wiring terminals or of the solderless pressure type having suitable conductor-release arrangement.
g. Grounding pole connected to mounting strap.
h. The receptacle: containing triple-wipe power contacts and double or triple-wipe ground contacts.
SECTION 26 20 00 Page 15
2.9.1 Weatherproof Receptacles
Provide receptacles, UL listed for use in "wet locations" with integral GFCI protection. Include cast metal box with gasketed, hinged, lockable and weatherproof while-in-use, polycarbonate, UV resistant/stabilized cover plate.
2.9.2 Ground-Fault Circuit Interrupter Receptacles
UL 943 , duplex type for mounting in standard outlet box. Provide device capable of detecting current leak when the current to ground is 6 milliamperes or higher, and tripping per requirements of UL 943 for Class A ground-fault circuit interrupter devices. Provide screw-type, side-wired wiring terminals or pre-wired (pigtail) leads.
2.10 PANELBOARDS
Provide panelboards in accordance with the following:
a. UL 67 and UL 50 .
b. Panelboards for use as service disconnecting: additionally conform to
UL 869A .
c. Panelboards: circuit breaker-equipped.
d. Designed such that individual breakers can be removed without disturbing adjacent units or without loosening or removing supplemental insulation supplied as means of obtaining clearances as required by UL.
e. Where "space only" is indicated, make provisions for future installation of breaker sized as indicated.
f. Directories: indicate load served by each circuit of panelboard.
g. Directories: indicate source of service (e.g. upstream panel, switchboard, motor control center) to panelboard.
h. Type directories and mount in holder behind transparent protective covering.
i. Panelboard nameplates: provided in accordance with paragraph FIELD
FABRICATED NAMEPLATES.
2.10.1 Enclosure
Provide panelboard enclosure in accordance with the following:
a. UL 50 .
b. Cabinets mounted outdoors or flush-mounted: hot-dipped galvanized after fabrication.
c. Cabinets: painted in accordance with paragraph PAINTING.
d. Outdoor cabinets: NEMA 4x with conduit hubs welded to the cabinet a removable steel plate 1/4 inch thick in the bottom for field drilling
SECTION 26 20 00 Page 16 for conduit connections.
e. Front edges of cabinets: form-flanged or fitted with structural shapes welded or riveted to the sheet steel, for supporting the panelboard front.
f. All cabinets: fabricated such that no part of any surface on the finished cabinet deviates from a true plane by more than 1/8 inch.
g. Holes: provided in the back of indoor surface-mounted cabinets, with outside spacers and inside stiffeners, for mounting the cabinets with a 1/2 inch clear space between the back of the cabinet and the wall surface.
h. Flush doors: mounted on hinges that expose only the hinge roll to view when the door is closed.
i. Each door: fitted with a combined catch and lock latch.
j. Keys: two provided with each lock, with all locks keyed alike.
k. Finished-head cap screws: provided for mounting the panelboard fronts on the cabinets.
2.10.2 Panelboard Buses
Support bus bars on bases independent of circuit breakers. Design main buses and back pans so that breakers may be changed without machining, drilling, or tapping. Provide isolated neutral bus in each panel for connection of circuit neutral conductors. Provide separate ground bus identified as equipment grounding bus per UL 67 for connecting grounding conductors; bond to steel cabinet. In addition to equipment grounding bus, provide second "isolated" ground bus, where indicated.
2.10.2.1 Panelboard Neutrals for Non-Linear Loads
Provide in accordance with the following:.
a. UL listed, with panelboard type specifically UL heat rise tested for use on non-linear loads.
b. Panelboard: heat rise tested in accordance with UL 67 , except with the neutral assembly installed and carrying 200 percent of the phase bus current during testing.
c. Verification of the testing procedure: provided upon request.
d. Two neutral assemblies paralleled together with cable is not acceptable.
e. Nameplates for panelboard rated for use on non-linear loads: marked "SUITABLE FOR NON-LINEAR LOADS" and in accordance with paragraph FIELD
FABRICATED NAMEPLATES.
f. Provide a neutral label with instructions for wiring the neutral of panelboards rated for use on non-linear loads.
SECTION 26 20 00 Page 17
2.10.3 Circuit Breakers
UL 489 , thermal magnetic-type having a minimum short-circuit current rating equal to the short-circuit current rating of the panelboard in which the circuit breaker will be mounted. Breaker terminals: UL listed as suitable for type of conductor provided. Where indicated on the drawings, provide circuit breakers with shunt trip devices. Series rated circuit breakers and plug-in circuit breakers are unacceptable.
2.10.3.1 Multipole Breakers
Provide common trip-type with single operating handle. Design breaker such that overload in one pole automatically causes all poles to open.
Maintain phase sequence throughout each panel so that any three adjacent breaker poles are connected to Phases A, B, and C, respectively.
2.10.3.2 Circuit Breaker With Ground-Fault Circuit Interrupter
UL 943 and NFPA 70 . Provide with auto-monitoring (self-test) and lockout features, "push-to-test" button, visible indication of tripped condition, and ability to detect and trip when current imbalance is 6 milliamperes or higher per requirements of UL 943 for Class A ground-fault circuit interrupter devices.
2.11 ENCLOSED CIRCUIT BREAKERS
UL 489 . Individual molded case circuit breakers with voltage and continuous current ratings, number of poles, overload trip setting, and short circuit current interrupting rating as indicated. Enclosure type as indicated.
2.12 MOTOR SHORT-CIRCUIT PROTECTOR (MSCP)
Motor short-circuit protectors, also called motor circuit protectors (MCPs): UL 508 and UL 489 , and provided as shown. Provide MSCPs that consist of an adjustable instantaneous trip circuit breaker used only in conjunction with a combination motor controller which provides coordinated motor branch-circuit overload and short-circuit protection. Rate MSCPs in accordance with the requirements of NFPA 70 .
2.13 TRANSFORMERS
Provide transformers in accordance with the following:
a. NEMA ST 20 , general purpose, dry-type, self-cooled, ventilated.
b. Provide transformers in NEMA 1 enclosure.
c. Taps for transformers 15 kVA and larger: Two 2.5 percent taps Full Capacity Above Nominal (FCAN) and four 2.5 percent taps Full Capacity Below Nominal (FCBN).
d. Transformer insulation system:
(1) 220 degrees C insulation system for transformers 15 kVA and greater, with temperature rise not exceeding 115 degrees C under full-rated load in maximum ambient of 40 degrees C.
(2) 180 degrees C insulation for transformers rated 10 kVA and less, SECTION 26 20 00 Page 18 with temperature rise not exceeding 80 degrees C under full-rated load in maximum ambient of 40 degrees C.
e. Transformer of 150 degrees C temperature rise is not acceptable.
f. Transformer of 115 degrees C temperature rise: capable of carrying continuously 115 percent of nameplate kVA without exceeding insulation rating.
g. Transformer of 80 degrees C temperature rise: capable of carrying continuously 130 percent of nameplate kVA without exceeding insulation rating.
h. Transformers: quiet type with maximum sound level at least 3 decibels less than NEMA standard level for transformer ratings indicated.
2.13.1 Specified Transformer Efficiency
Transformers, indicated and specified with: 480V primary, 80 degrees C or 115 degrees C temperature rise, kVA ratings of 37.5 to 100 for single phase or 30 to 500 for three phase, energy efficient type. The transformer is not acceptable if the calculated transformer efficiency is less than the efficiency indicated in 10 CFR 431 , Subpart K.
2.14 MOTORS
Provide motors in accordance with the following:
a. NEMA MG 1.
b. Hermetic-type sealed motor compressors: Also comply with UL 984 .
c. Provide the size in terms of HP, or kVA, or full-load current, or a combination of these characteristics, and other characteristics, of each motor as indicated or specified.
d. Determine specific motor characteristics to ensure provision of correctly sized starters and overload heaters.
e. Rate motors for operation on 208-volt, 3-phase circuits with a terminal voltage rating of 200 volts, and those for operation on 480-volt, 3-phase circuits with a terminal voltage rating of 460 volts.
f. Use motors designed to operate at full capacity with voltage variation of plus or minus 10 percent of motor voltage rating.
g. Unless otherwise indicated, use continuous duty type motors if rated 1 HP and above.
h. Where fuse protection is specifically recommended by the equipment manufacturer, provide fused switches in lieu of non-fused switches indicated.
i. Use Inverter-Rated motors designed to operate with adjustable speed drive (ASD).
SECTION 26 20 00 Page 19
2.14.1 High Efficiency Single-Phase Motors
Single-phase fractional-horsepower alternating-current motors: high efficiency types are not acceptable. In exception, for special purpose motors and motor-driven equipment with a minimum seasonal or overall efficiency rating, such as a SEER rating, provide equipment with motor to meet the overall system rating indicated.
2.14.2 Premium Efficiency Polyphase and Single-Phase Motors
Select polyphase and continuous-duty single phase motors based on high efficiency characteristics relative to typical characteristics and applications as listed in NEMA MG 10 and NEMA MG 11. In addition, continuous rated, polyphase squirrel-cage medium induction motors must meet the requirements for premium efficiency electric motors in accordance with NEMA MG 1, including the NEMA full load efficiency ratings. In exception, for motor-driven equipment with a minimum seasonal or overall efficiency rating, such as a SEER rating, provide equipment with motor to meet the overall system rating indicated.
2.14.3 Motor Sizes
Provide size for duty to be performed, not exceeding the full-load nameplate current rating when driven equipment is operated at specified capacity under most severe conditions likely to be encountered. When motor size provided differs from size indicated or specified, make adjustments to wiring, disconnect devices, and branch circuit protection to accommodate equipment actually provided. Provide controllers for motors rated 1-hp and above with electronic phase-voltage monitors designed to protect motors from phase-loss, undervoltage, and overvoltage. Provide protection for motors from immediate restart by a time adjustable restart relay.
2.14.4 Wiring and Conduit
Provide internal wiring for components of packaged equipment as an integral part of the equipment. Provide power wiring and conduit for field-installed equipment using adjustable speed drive (ASD) manufacturer required wiring type and length, and motor control equipment forming part of motor control centers or switchgear assemblies, the conduit and wiring connecting such centers, assemblies, or other power sources to equipment as specified herein. Power wiring and conduit: conform to the requirements specified herein. Control wiring: provided under, and conform to, the requirements of the section specifying the associated equipment.
2.15 MOTOR CONTROLLERS
Provide motor controllers in accordance with the following:
a. UL 508 , NEMA ICS 1 , and NEMA ICS 2 .
b. Provide controllers with thermal overload protection in each phase, and one spare normally open auxiliary contact, and one spare normally closed auxiliary contact.
c. Provide controllers for motors rated 1-hp and above with electronic phase-voltage monitors designed to protect motors from phase-loss, undervoltage, and overvoltage.
SECTION 26 20 00 Page 20
d. Provide protection for motors from immediate restart by a time adjustable restart relay.
e. When used with pressure, float, or similar automatic-type or maintained-contact switch, provide a hand/off/automatic selector switch with the controller.
f. Connections to selector switch: wired such that only normal automatic regulatory control devices are bypassed when switch is in "hand" position.
g. Safety control devices, such as low and high pressure cutouts, high temperature cutouts, and motor overload protective devices: connected in motor control circuit in "hand" and "automatic" positions.
h. Control circuit connections to hand/off/automatic selector switch or to more than one automatic regulatory control device: made in accordance with indicated or manufacturer's approved wiring diagram.
i. Provide selector switch with the means for locking in any position.
j. Provide a disconnecting means, capable of being locked in the open position, for the motor that is located in sight from the motor location and the driven machinery location. As an alternative, provide a motor controller disconnect, capable of being locked in the open position, to serve as the disconnecting means for the motor if it is in sight from the motor location and the driven machinery location.
k. Overload protective devices: provide adequate protection to motor windings; be thermal inverse-time-limit type; and include manual reset-type pushbutton on outside of motor controller case.
l. Cover of combination motor controller and manual switch or circuit breaker: interlocked with operating handle of switch or circuit breaker so that cover cannot be opened unless handle of switch or circuit breaker is in "off" position.
2.15.1 Control Wiring
Provide control wiring in accordance with the following:
a. All control wire: stranded tinned copper switchboard wire with 600-volt flame-retardant insulation Type SIS meeting UL 44 , or Type MTW meeting UL 1063 , and passing the VW-1 flame tests included in those standards.
b. Hinge wire: Class K stranding.
c. Current transformer secondary leads: not smaller than No. 10 AWG.
d. Control wire minimum size: No. 14 AWG.
e. Power wiring for 480-volt circuits and below: the same type as control wiring with No. 12 AWG minimum size.
f. Provide wiring and terminal arrangement on the terminal blocks to permit the individual conductors of each external cable to be terminated on adjacent terminal points.
SECTION 26 20 00 Page 21
2.15.2 Control Circuit Terminal Blocks
Provide control circuit terminal blocks in accordance with the following:
a. NEMA ICS 4 .
b. Control circuit terminal blocks for control wiring: molded or fabricated type with barriers, rated not less than 600 volts.
c. Provide terminals with removable binding, fillister or washer head screw type, or of the stud type with contact and locking nuts.
d. Terminals: not less than No. 10 in size with sufficient length and space for connecting at least two indented terminals for 10 AWG conductors to each terminal.
e. Terminal arrangement: subject to the approval of the Contracting Officer with not less than four spare terminals or 10 percent, whichever is greater, provided on each block or group of blocks.
f. Modular, pull apart, terminal blocks are acceptable provided they are of the channel or rail-mounted type.
g. Submit data showing that any proposed alternate will accommodate the specified number of wires, are of adequate current-carrying capacity, and are constructed to assure positive contact between current-carrying parts.
2.15.2.1 Types of Terminal Blocks
a. Short-Circuiting Type: Short-circuiting type terminal blocks:
furnished for all current transformer secondary leads with provision for shorting together all leads from each current transformer without first opening any circuit. Terminal blocks: comply with the requirements of paragraph CONTROL CIRCUIT TERMINAL BLOCKS above.
b. Load Type: Load terminal blocks rated not less than 600 volts and of adequate capacity: provided for the conductors for NEMA Size 3 and smaller motor controllers and for other power circuits, except those for feeder tap units. Provide terminals of either the stud type with contact nuts and locking nuts or of the removable screw type, having length and space for at least two indented terminals of the size required on the conductors to be terminated. For conductors rated more than 50 amperes, provide screws with hexagonal heads. Conducting parts between connected terminals must have adequate contact surface and cross-section to operate without overheating. Provide each connected terminal with the circuit designation or wire number placed on or near the terminal in permanent contrasting color.
2.15.3 Control Circuits
Control circuits: maximum voltage of 120 volts derived from control transformer in same enclosure. Transformers: conform to UL 506 , as applicable. Transformers, other than transformers in bridge circuits:
provide primaries wound for voltage available and secondaries wound for correct control circuit voltage. Size transformers so that 80 percent of rated capacity equals connected load. Provide disconnect switch on primary side. Provide one fused secondary lead with the other lead
SECTION 26 20 00 Page 22 grounded. For designated systems, as indicated, provide backup power supply, including transformers connected to emergency power source.
Provide for automatic switchover and alarm upon failure of primary control circuit.
2.15.4 Enclosures for Motor Controllers
NEMA ICS 6 .
2.15.5 Multiple-Speed Motor Controllers and Reversible Motor Controllers
Across-the-line-type, electrically and mechanically interlocked.
Multiple-speed controllers: include compelling relays and multiple-button, station-type with pilot lights for each speed.
2.15.6 Pushbutton Stations
Provide with "start/stop" momentary contacts having one normally open and one normally closed set of contacts, and red lights to indicate when motor is running. Stations: heavy duty, oil-tight design.
2.15.7 Pilot and Indicating Lights
Provide LED cluster lamps.
2.16 LOCKOUT REQUIREMENTS
Provide circuit breakers, disconnecting means, and other devices that are electrical energy-isolating capable of being locked out for machines and other equipment to prevent unexpected startup or release of stored energy in accordance with 29 CFR 1910.147 , NFPA 70E and 29 CFR 1910.303 . Comply with requirements of Division 23, "Mechanical" for mechanical isolation of machines and other equipment.
2.17 TELECOMMUNICATIONS SYSTEM
Provide system of telecommunications wire-supporting structures (pathway), including: outlet boxes, conduits with pull wires wireways, cable trays, and other accessories for telecommunications outlets and pathway in accordance with TIA-569 and as specified herein. Additional telecommunications requirements are specified in Section 27 10 00.00 48
BUILDING TELECOMMUNICATIONS CABLING SYSTEM.
2.18 GROUNDING AND BONDING EQUIPMENT
2.18.1 Ground Rods
UL 467 . Ground rods: cone pointed copper-clad steel, with minimum diameter of 3/4 inch and minimum length 10 feet. Sectional type rods may be used for rods 20 feet or longer.
2.18.2 Ground Bus
Copper ground bus: provided in the electrical equipment rooms as indicated.
2.18.3 Secondary Bonding Busbar
Provide corrosion-resistant grounding busbar suitable for indoor
SECTION 26 20 00 Page 23 installation in accordance with TIA-607 . Busbars: plated for reduced contact resistance. If not plated, clean the busbar prior to fastening the conductors to the busbar and apply an anti-oxidant to the contact area to control corrosion and reduce contact resistance. Provide a Primary bonding busbar (PBB) in the telecommunications entrance facility. The Primary bonding busbar (PBB): sized in accordance with the immediate application requirements and with consideration of future growth. Provide Secondary bonding busbars with the following:
a. Predrilled copper busbar provided with holes for use with standard sized lugs,
b. Minimum dimensions of 0.25 in thick by 4 in wide for the PBB with length as indicated;
c. Listed by a nationally recognized testing laboratory.
2.19 HAZARDOUS LOCATIONS
Electrical materials, equipment, and devices for installation in hazardous locations, as defined by NFPA 70 : specifically approved by Underwriters' Laboratories, Inc., or Factory Mutual for particular "Class," "Division," and "Group" of hazardous locations involved. Boundaries and classifications of hazardous locations: as indicated. Equipment in hazardous locations: comply with UL 1203 for electrical equipment and industrial controls and UL 674 for motors.
2.20 MANUFACTURER'S NAMEPLATE
Provide on each item of equipment a nameplate bearing the manufacturer's name, address, model number, and serial number securely affixed in a conspicuous place; the nameplate of the distributing agent will not be acceptable.
2.21 FIELD FABRICATED NAMEPLATES
Provide field fabricated nameplates in accordance with the following:
a. ASTM D709.
b. Provide laminated plastic nameplates for each equipment enclosure, relay, switch, and device; as specified or as indicated on the drawings.
c. Each nameplate inscription: identify the function and, when applicable, the position.
d. Nameplates: melamine plastic, 0.125 inch thick, white with black center core.
e. Provide red laminated plastic label with white center core where indicated.
f. Surface: matte finish. Corners: square. Accurately align lettering and engrave into the core.
g. Minimum size of nameplates: one by 2.5 inches.
h. Lettering size and style: a minimum of 0.25 inch high normal block
SECTION 26 20 00 Page 24 style.
2.22 WARNING SIGNS
Provide warning signs for flash protection in accordance with NFPA 70E and NEMA Z535.4 for switchboards, panelboards, industrial control panels, and motor control centers that are in other than dwelling occupancies and are likely to require examination, adjustment, servicing, or maintenance while energized. Provide field installed signs to warn qualified persons of potential electric arc flash hazards when warning signs are not provided by the manufacturer.
This is the start of the file's text. The full file is on GovTribe.