W912QR25BA018_Plans-0000.pdf
PDF 26 MB Posted
- Solicitation number
- W912QR25BA018
About this file
This file is a comprehensive set of electrical engineering design drawings and technical specifications for the Cannelton Lock and Dam Interlocks and Encoders Upgrade project for the U.S. Army Corps of Engineers Louisville District. The project involves a complete modernization of the existing lock and dam control systems, including replacing tainter gate position encoders, updating valve controls, and upgrading the lock operations interlock system to comply with current Inland Marine Transportation System Interlock Standards.
The technical scope encompasses replacing existing selsyn position indicators with new 4-20mA analog encoders across 12 tainter gates and multiple valves, retrofitting control station panels, installing new instrument junction boxes, modifying interlock wiring and logic, and upgrading proximity sensors and cable infrastructure. The project will upgrade electrical and control systems for both the main and auxiliary lock structures, ensuring improved operational reliability and standardization. The contract number is W912QR25BA018, with work scheduled for completion by May 2025, focusing on precise position sensing, lever locking mechanisms, and comprehensive system integration across multiple control stations and equipment locations.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
A
B
C
D
E
F
G
H
J
K
L
M
N
P
SU
BM
IT
TE
D B
Y:
C H
EC
KE
D B
Y:
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
IS
SU
E D
AT
E:
SI
ZE
M
AR
K
D
ES
C R
IP
TI
O N
D
AT
E
SHEET ID
LO
U
IS
VI
LL
E
D
IS
TR
IC
T
D
R . M
AR
TI
N L
U
TH
ER
K
IN
G
J R
. P
LA
C E
LO
U
IS
VI
LL
E, K Y
-M
AY
C O
N
TR
AC
T
N O
AN
SI
'D
C
AN
N
EL
TO
N
L O
C
KS
A N
D D
AM
C
AN
N
EL
TO
N
IN
TE
R
LO
C
KS
/D
AM
E
N C
O D
ER
S
U
PG
R
AD
ES
FY
4, P
C
ER
TI
FI
ED
F
IN
AL
J.
TI
M
BA
S
J.
M
O O
R E
J.
M
O O
R E
J.
TI
M
BA
S C
O
VE
R S
H
EE
T
G-001
US Army Corps of Engineers
U .S
. A R
M Y
C O
R
PS
O F
EN
G
IN
EE
R S
US Army Corps of Engineers ®
SOLICITATION NO.:
CONTRACT NO.:
ISSUE DATE:
LOUISVILLE DISTRICT
CANNELTON LOCKS AND DAM
LOCK
VOLUME #
SIGNATURES AFFIXED BELOW INDICATE
OFFICIAL RECOMMENDATION AND
APPROVAL OF ALL DRAWINGS IN THIS SET.
APPROVAL RECOMMENDED: *
*APPROVAL RECOMMENDED SIGNATURE
INDICATES DESIGN AND QUALITY CONTROL
REVIEWS ARE COMPLETE, INCLUDING ITR/ATR
CERTIFICATION.
JEFF TIMBAS, P
TECHNICAL LEAD
CHIEF, ENGINEERING DIVISION
IAN F. MITCHELL, PE
** THIS PROJECT WAS DESIGNED BY THE U.S.
ARMY CORPS OF ENGINEERS, LOUISVILLE
DISTRICT.
INDIVIDUALS WHOSE SIGNATURES AND
REGISTRATION DESIGNATIONS APPEAR ON
THESE DOCUMENTS ARE OPERATING WITHIN
THE SCOPE OF THEIR EMPLOYMENT.
SIGNATURES ARE REQUIRED BY
ER 1110-1-8152.
APPROVED: **
ELECTRICAL
DESIGNER: FIRST NAME LAST NAME
CHECKER: FIRST NAME LAST NAME
JEFF MOORE, PE
JEFF TIMBAS, PE
TIMBAS.JEFFREY.W.1
365057903
Digitally signed by
TIMBAS.JEFFREY.W.1365057903
Date: 2025.04.08 13:05:19 -04'00'
TIMBAS.JEFFREY
.W.1365057903
Digitally signed by
TIMBAS.JEFFREY.W.136505790
Date: 2025.04.08 13:04:32 -04'00'
MOORE.JEFFREY.PR
UITT.1128950466
Digitally signed by
MOORE.JEFFREY.PRUITT.1128
950466 Date: 2025.04.08 09:57:50 -04'00'
Digitally signed by
MITCHELL.IAN.F.1300565227
Date: 2025.04.18 17:16:02 -04'00'
30 June 2025
W912QR25BA018
W
2Q R
BA
8_
Pl an s-
B
C
D
E
F
G
H
J
K
L
M
N
P
SU
BM
IT
TE
D B
Y:
C H
EC
KE
D B
Y:
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
IS
SU
E D
AT
E:
SI
ZE
M
AR
K
D
ES
C R
IP
TI
O N
D
AT
E
SHEET ID
LO
U
IS
VI
LL
E
D
IS
TR
IC
T
D
R . M
AR
TI
N L
U
TH
ER
K
IN
G
J R
. P
LA
C E
LO
U
IS
VI
LL
E, K Y
-M
AY
C O
N
TR
AC
T
N O
AN
SI
'D
C
AN
N
EL
TO
N
L O
C
KS
A N
D D
AM
C
AN
N
EL
TO
N
IN
TE
R
LO
C
KS
/D
AM
E
N C
O D
ER
S
U
PG
R
AD
ES
FY
4, P
C
ER
TI
FI
ED
F
IN
AL
J.
TI
M
BA
S
J.
M
O O
R E
J.
M
O O
R E
J.
TI
M
BA
S
PR
O
PO
SE
D P
R O
JE
C
T
LA
YD
O
W N
A R
EA
G-002
US Army Corps of Engineers
U .S
. A R
M Y
C O
R
PS
O F
EN
G
IN
EE
R S
NOT TO SCALE
B2 PROPOSED LAYDOWN AREA FOR CANNELTON LOCK AND DAM CONTROLS UPDATE PROJECT
LAYDOWN AREA
1. COORDINATE FINAL LAYDOWN AREA WITH PROJECT PERSONNEL AND COR UPON
NOTICE TO PROCEED.
GENERAL NOTES
PLAN
NORTH W
2Q
R
BA
8_ Pl an s-
B
C
D
E
F
G
H
J
K
L
M
N
P
SU
BM
IT
TE
D B
Y:
C H
EC
KE
D B
Y:
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
IS
SU
E D
AT
E:
SI
ZE
M
AR
K
D
ES
C R
IP
TI
O N
D
AT
IS
VI
LL
E
D
IS
TR
IC
T
D
R . M
AR
TI
N L
U
TH
ER
K
IN
G
J R
. P
LA
C E
LO
U
IS
VI
LL
E, K Y
-M
AY
C O
N
TR
AC
T
N O
AN
SI
'D
C
AN
N
EL
TO
N
L O
C
KS
A N
D D
AM
C
AN
N
EL
TO
N
IN
TE
R
LO
C
KS
/D
AM
E
N C
O D
ER
S
U
PG
R
AD
ES
FY
4, P
C
ER
TI
FI
ED
F
IN
AL
J.
TI
M
BA
S
J.
M
O O
R E
J.
M
O O
R E
J.
TI
M
IN
ST
R U
M
EN
TA
TI
O N
L
EG
EN
D
A N
D N
O
TE
E-001 of Engineers
U .S
. A R
M Y
C O
R
PS
O F
EN
G
IN
EE
R S
PR
O D
U C
TI
O
N D
AT
A
1%
PR
O
D U
C
TI
O N
D
AT
A 2%
PR
O D
U C
TI
O
N D
AT
A
3%
PR
O
D U
C
TI
O N
D
AT
A 4%
1. FEDERAL, STATE, LOCAL, MUNICIPALITY AND UTILITY COMPANY CODES,
RULES REGULATIONS AND REQUIREMENTS APPLY UNLESS EXCEEDED BY THIS
DESIGN.
2. LOCATIONS, DEPTHS, MATERIAL TYPES, ELEVATIONS, ETC. OF ALL
APPURTENANCES, LINES, BUILDINGS, ETC. INDICATED ON THESE DRAWINGS
WERE TAKEN FROM VARIOUS SOURCES, ARE DIAGRAMMATIC ONLY AND ARE
SUBJECT TO VARIATION FROM EXISTING CONDITIONS, EXISTING UTILITIES
LOCATIONS MAY VARY. CONSEQUENTLY ALL CONTRACTORS MUST EXERCISE
EXTREME CARE IN THE COURSE OF THEIR WORK SO AS TO ENSURE THAT
THEY DO NOT INTERRUPT ANY EXISTING SERVICE. FOR SAFETY PURPOSES,
PAY PARTICULAR ATTENTION TO THIS PRECAUTION RELATIVE TO NATURAL
GAS AND ELECTRICAL LINES. ALL WORK MUST BE PERFORMED IN
ACCORDANCE WITH ALL FEDERAL, STATE, AND/OR LOCAL RULES,
REGULATIONS, STANDARDS AND SAFETY REQUIREMENTS.
3. BEFORE INSTALLING EQUIPMENT, MAKE FIELD MEASUREMENTS TO INSURE
THAT ALL ITEMS OF EQUIPMENT FURNISHED FIT INTO THE SPACE AS SHOWN IN
DRAWINGS. WHERE EQUIPMENT DOES NOT FIT AS SHOWN ON THE DRAWINGS,
PROVIDE A DRAWING TO THE CONTRACTING OFFICER FOR APPROVAL WITH A
PROPOSED REVISED ARRANGEMENT BEFORE INSTALLING THE EQUIPMENT.
4. NO WORK SHALL BE PERFORMED ON ENERGIZED ELECTRICAL CIRCUITS
UNLESS PROOF IS PROVIDED THAT NO OTHER MEANS EXIST. IF IT IS
DETERMINED THAT EQUIPMENT MUST BE WORKED ON IN AN ENERGIZED
CONDITION, AN ENERGIZED WORK REQUEST SHALL BE SUBMITTED TO THE
CONTRACTING OFFICER FOR ACCEPTANCE AND MUST CONTAIN INFORMATION
REQUIRED BY USACE EM 385-1-1.
5. ALL WIRING AND CABLING INDICATED IN THIS DRAWING SET WAS CREATED
BASED ON THE ASSUMPTION THAT ALL TERMINATIONS AND MARKINGS ARE
STILL PRESENT AS SHOWN IN FINAL AS-BUILT ELECTRICAL DRAWINGS (IN
REFERENCE TO DRAWING SET OC-250 AS WELL AS INTERLOCK RETROFIT
DRAWINGS) AND THAT NO MODIFICATIONS HAVE BEEN MADE SINCE
COMPLETION OF CONSTRUCTION.
6. DOCUMENTED INTERLOCK MODIFICATIONS MADE SINCE COMPLETION OF LOCK
CONSTRUCTION ARE CONSIDERED AND REPRESENTED IN THIS DRAWING SET.
ANY OTHER UNDOCUMENTED MODIFICATIONS MADE SINCE COMPLETION OF
CONSTRUCTION HAVE NOT BEEN INCLUDED.
7. REFERENCE SINGLE LINE DIAGRAM, SHOWN ON SHEET E-602, FOR OVERVIEW
OF NEW CABLING, REPAIRS, UPDATES AND CONNECTIONS BE MADE IN THIS
PROJECT. REVIEW AS-BUILT DRAWING (SINGLE LINE) OC-250.1/17 FOR OVERALL
FAMILIARIZATION WITH EXISTING SYSTEM.
8. ALL FIELD-MOUNTED SENSORS WHICH ARE LISTED IN INSTRUMENT SCHEDULE
MUST HAVE AN ENGRAVED STAINLESS STEEL TAG WHICH IS PERMANENTLY
AFFIXED TO INSTRUMENT WITH STAINLESS STEEL CABLE ROPE (FOR
IDENTIFICATION IN THE FIELD AFTER INSTALLATION).
9. ALL NEW CABLES MUST BE EITHER ROUTED WITH OTHER LOW
VOLTAGE/INSTRUMENT CABLING AND/OR SEPARATED FROM POWER CABLING
AS REQUIRED BY APPLICABLE CODES.
10.UNLESS SPECIFIED OTHERWISE IN THIS DRAWING, ALL FLOOR MOUNTED
EQUIPMENT OR ENCLOSURE PEDESTAL MOUNTS MUST BE PLACED UPON A
CONCRETE HOUSEKEEPING PAD. PAD SHALL EXTEND 2" BEYOND EQUIPMENT
DIMENSIONS ON ALL SIDES, HAVE A 1" CHAMFER, AND BE MINIMUM 4" IN
HEIGHT. ALL WALL MOUNT EQUIPMENT MUST BE SECURED WITH 316 SERIES
STAINLESS STEEL STRUT CHANNEL WITH FASTENERS RATED FOR USE WITH
STRUT CHANNEL.
11. A SOLID FIXED BARRIER SHALL BE REQUIRED IN CABLE TRAYS WHERE LOW
VOLTAGE DC CIRCUITS AND COMMUNICATIONS CABLES AND HIGHER VOLTAGE
AC CABLES CO-EXIST IN THE SAME CABLE TRAY SECTION. BARRIERS SHOULD
FORM A MINIMUM OF A 4” SPACING BETWEEN THESE DIFFERENT TYPES OF
CABLES.
12.CABLE TRAY AND CONDUIT OPENINGS INTO BUILDINGS SHALL BE SEALED
WATERTIGHT. ALL OPENINGS IN JUNCTION BOXES OR CONTROL PANELS SHALL
BE COVERED OR PLUGGED. REPAIRS TO THIS EQUIPMENT SHALL MAINTAIN
THE NEMA RATING OF THE ENCLOSURE.
13.PENETRATIONS MADE THROUGH FIRE RATED FLOORS, WALLS, OR PARTITIONS
FOR THE PURPOSE OF INSTALLING RACEWAY CARRYING ELECTRICAL,
TELEPHONE, TELEVISION, COMMUNICATION, OR SIGNAL CIRCUITS SHALL BE
FIRE STOPPED PER ALL APPLICABLE BUILDING CODES.
14. ALL CONTROL PANELS (JUNCTION BOXES) TO BE BUILT BY A UL LISTED
508/508A CERTIFIED PANEL FABRICATION SHOP.
15. ALL CONTROL PANELS MUST BE PROVIDED WITH A COMPLETE PRINTED SET
OF THE APPROVED WIRING SCHEMATICS AND DIAGRAMS (AS DEFINED IN
SPECIFICATION DOCUMENTS).
16. ALL EXISTING SELSYN VALVE POSITION SENSORS (VPS) MUST REMAIN
PROPERTY OF GOVERNMENT DURING DEMO. COORDINATE RETURN OF THESE
ITEMS WITH COR.
GENERAL NOTES
XX
XXX
FIELD-MOUNTED INSTRUMENT TAG - FOLLOWING ISA TAGGING
CONVENTIONS
ABBREVIATIONS LEGEND
TYPE TC SHIELDED INSTRUMENTATION CABLE - NEW CABLE
FROM (CURRENT SOURCE) - TO (CONTROL STATION) - #PAIRS
OR #TRIPLES ('T' SUFFIX INDICATES TRIPLE)
FROM-TO-#PR
VERTICAL TRANSITION THROUGH CONDUIT SLEEVE / RECESS
BETWEEN CROSSOVER AND GALLERY
CABLE OR WIRE TERMINATION POINT
IJB - INSTRUMENT JUNCTION BOX
CM - CURRENT MIRROR/SIGNAL RELAY
CS - CONTROL STATION
MCT - MULTIPLE CABLE TRANSIT
PE - POTENTIAL EARTH / GROUND, INDICATED BY GRN OR GRN/YELLOW (PER NEC)
TB - TERMINAL BLOCK, GROUP OR STRIP
TC - TRAY CABLE, AS DEFINED BY NATIONAL ELECTRICAL CODE
TC/ER - TRAY CABLE, EXPOSED RUN
TSP - TWISTED SHIELDED PAIR, INSTRUMENT CABLE
TRI - TRIAD, 3 WIRE SHIELDED INSTRUMENT CABLE
RELEVANT INSTRUMENT SOCIETY OF AMERICA (ISA) STANDARD TAGGING:
FIRST LETTER:
' Z ' INDICATES A POSITION SENSING ELEMENT OR INSTRUMENT
' P ' INDICATES PRESSURE ELEMENT OR INSTRUMENT
SECOND LETTER:
' S ' SWITCH
' T ' TRANSMITTER (4-20MA) INDICATING CONTINUOUS POSITION
' I ' METER/INDICATOR DEVICE - FIELD OR PANEL MOUNT
THIRD LETTER:
'O' OPEN STATE OF PROCESS/VALVE/MECHANICAL COMPONENT
'C' CLOSED STATE OF PROCESS/VALVE/MECHANICAL COMPONENT
' XZ ' TOGETHER INDICATES AN ACTUATOR/DRIVE
SIGNAL FLOW DIRECTION
R
5A
5A
CR
XX
CR
M
LED PANEL LIGHT / INDICATOR
R - RED, B - BLUE, W - WHITE, G - GREEN, Y - YELLOW, A - AMBER
X = 'AC' FOR 85-264 VAC / X = BLANK FOR 12-30 VDC (DEFAULT)
CONTROL FUSE WITH RATING
(BLADE TYPE ATC "AUTOMOTIVE" FUSE)
CONTROL BREAKER
SPST SWITCH (NORMALLY OPEN)
NO AND NC RELAY CONTACTS
CONTACTOR OR RELAY COIL, MOTOR RELAY COIL
(TD, IF PRESENT, INDICATES TIME-ON DELAY FUNCTION)
PUSHBUTTON (NO/NC)
CENTER OFF MOMENTARY KNOB ACTUATED SWITCH
(CONTACT TYPES / FUNCTIONS INDICATED IN WIRING
DIAGRAMS)
PANEL MOUNT ALARM
SOCKET / PIN CONNECTION (DISCONNECT)
OUTAGE GUIDANCE
PROJECT TO REMAIN ACTIVE DURING CONSTRUCTION WITH ONLY ONE LOCK
STRUCTURE BEING DOWN AT A TIME. THIS MUST BE COORDINATED WITH
OPERATIONS.
XX
XXX
CENTRAL CONTROL ROOM PANEL-MOUNT DEVICE INSTRUMENT
TAG - FOLLOWING ISA TAGGING CONVENTIONS
X
DUAL-LEVEL TERMINAL BLOCK, BRIDGEABLE, DIN RAIL MOUNT,
GRAY, RATED AT 28A AND SUITABLE FOR USE WITH 24-10 AWG
WIRE, TOP TERMINAL (#1) AND BOTTOM TERMINAL (#2)
ARRANGED AS SHOWN (SCREW TYPE OR SPRING CAGE)
DUAL-LEVEL TERMINAL BLOCK, BRIDGED PE GROUNDING TO DIN
RAIL (THROUGH METAL CLAMPS), GREEN/YELLOW, SUITABLE
FOR USE WITH 24-10 AWG WIRE (SCREW TYPE OR SPRING
CAGE)
TB#
PE
ELECTRICAL BUS CONTINUATION TO/FROM OTHER SHEET
CHASSIS/ENCLOSURE/EARTH GROUND (PE) CONNECTION
(NOT A POWER SUPPLY GROUND)
WIRING AND CABLE NOTES
ALL NEW INSTRUMENT CABLE ROUTED IN GALLERIES MUST BE TRAY-RATED AND
COMPLY WITH TC/TC-ER REQUIREMENTS (PER NEC ARTICLE 336) IN ADDITION TO
MEETING IEEE-1580 REQUIREMENTS. ALUMINUM/POLYESTER TAPE SHIELD MUST
OVERLAP, PROVIDING 100% COVERAGE WITH TINNED-COPPER SHIELD DRAIN.
UTILIZE COMMON/COLLECTIVE SHIELD DRAIN FOR MULTIPLE PAIR CABLES.
REFERENCE SPECIFICATIONS AND SCHEDULES WITHIN THIS DRAWING SET FOR
FURTHER CONSTRUCTION, MATERIAL AND WIRE SIZING REQUIREMENTS. CABLE
DIAMETERS LISTED IN THIS DRAWING PACKAGE ARE ESTIMATES ONLY.
ALL NEW INTERIOR HOOKUP WIRING FOR ALL INSTRUMENT JUNCTION BOXES AND
CONTROL STATIONS (IJB-1, AT CS-1,2,3,4 AND CS-S) MUST BE XLPE INSULATED AND
MEET UL3173 REQUIREMENTS (600V, 125 DEG C).
ALL NEW INTERIOR HOOKUP WIRING WITHIN MOTOR CONTROL CENTERS MUST BE
BLACK XHHW-2 INSULATED 12GA WIRE.
ALL HOOKUP WIRE TO BE 18GA UNLESS OTHERWISE SPECIFIED IN THIS DRAWING
SET. APPROVED FERRULES MUST BE USED FOR ALL TERMINAL BLOCK
CONNECTIONS IN THIS PROJECT. UN-INSULATED FERRULES MAY BE USED WHERE
LARGER GAUGE WIRING IS REQUIRED TO BE CONNECTED.
ALL CABLE, WIRE AND TERMINAL MARKINGS MUST BE PRINTED IN BLACK TEXT ON
WHITE MARKERS (WHICH ARE APPROPRIATE FOR THE ENVIRONMENT) THAT
INDICATE CABLE, CIRCUIT OR TERMINAL NUMBER AS DOCUMENTED IN DRAWINGS.
HAND-WRITTEN LABELS ARE NOT ACCEPTABLE. MARK ALL NEW AND EXISTING
CUT/REUSED WIRING, AS INDICATED IN DRAWINGS AND/OR AS STATED BELOW,
WITHIN ONE INCH OF EACH TERMINATED END.
INCLUDE A COLOR CODING AND MARKING KEY LABEL ON THE INSIDE OF THE FRONT
DOOR OF IJB-1 ENCLOSURE (WITH INFORMATION INDICATED BELOW):
COLOR CODING AND WIRING IDENTIFICATION:
DC POWER WIRING -
BLUE: 24VDC POSITIVE, IDENTIFIED WITH "+24VDC" MARKING
BLACK: DC POWER SUPPLY GROUNDED RETURN, IDENTIFIED WITH "0V" MARKING
GREEN/YELLOW: PE (EARTH) GROUND - NO MARKING REQUIRED.
DC RELAY AND INTERLOCK LOGIC -
BROWN: RELAY/SWITCHED LOGIC, MARKED AS INDICATED IN ALL WIRING DIAGRAMS.
24VDC ANALOG INSTRUMENTATION -
BROWN: + SIDE OF 4-20MA LOOP
WHITE: - OF 4-20MA LOOP
MARK WIRES WITH ASSOCIATED RECEPTACLE AND PIN# (e.g. "R1-e5", "R2-d2", etc...)
OR AS INDICATED IN DRAWINGS
120VAC CONTROL -
ALL NEW 120VAC CONTROL WIRING, IN MCC, MUST BE BLACK INSULATED AND
MARKED AS INDICATED IN THESE DRAWINGS
EXISTING TRAY CABLES, CONDUCTORS WITHIN THESE CABLES, AND CONDUCTORS
IN EXISTING CONTROL PANELS / MCCs ARE DESIGNATED WITH PARENTHESIS - E.G.
(99L) IS AN EXISTING WIRE/CABLE TO EITHER REMAIN TERMINATED AS-IS OR
RECONNECTED AS INDICATED IN THIS DRAWING SET.
TD
F1 (75 FPM)
FLASHER MODULE, 24VDC, 75 FLASHES PER MINUTE
SINGLE SHOT, LEADING EDGE TRIGGERED W/ CONTROL
CONTACTS / ADJUSTABLE TIME MULTIFUNCTIONAL RELAY
SS (t MIN)
INDUCTIVE PROXIMITY SWITCH (NO)
W
2Q R
BA
8_
Pl an s-
FLOW
M1 M2
M3 M4
M5 M6 M7 M8 M9 M10 M11 M12 M13
M14
M15
M16 M17 M18 M19 M20 M21
L5
L6
L7 L8 L9
L10
L11 L12
R23 R24 R25 R26
R27 R28 R29 R30 R31 R32 R33 R34 R35 R36 R37 R38 R39 R40 R41 R42 R43
MAIN LOCK
AUX LOCK
GATE 4
GATE 3
V-3L
V-4
V-4R
CS-3
CS-4
CS-3L
CS-4R
RIVER WALL - MAIN LOCK (MR)
MIDDLE WALL - MAIN LOCK (MM)
ZT
V3L
ZSO
V3L
ZSC
V3L
ZT
V4R
ZSO
V4R
ZSC
V4R
ZT
V4
ZSO
V4
ZSC
V4
V3L-IJB1-4
V4-IJB1-4
V4-IJB1-4
IJB1-CS3-4
IJB1-CS4-4
IJB1-CS3-4
V4-IJB1-4
MIDDLE WALL - AUX LOCK (AM)
LAND WALL - AUX LOCK (AL)
J1 E-502
TYP. ALL VALVE
LOCATIONS
J11 E-403
IJB1-CS4JB-4
IJB1-CS3JB-4
NEW INSTRUMENTATION
C3
E-506 LEVER LOCKS
J1
E-403 NEW INSTRUMENTATION
C3
E-506 LEVER LOCKS
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
A
B
C
D
E
F
G
H
J
K
L
M
N
P
SU
BM
IT
TE
D B
Y:
C H
EC
KE
D B
Y:
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
IS
SU
E D
AT
E:
SI
ZE
M
AR
K
D
ES
C R
IP
TI
O N
D
AT
IS
VI
LL
E
D
IS
TR
IC
T
D
R . M
AR
TI
N L
U
TH
ER
K
IN
G
J R
. P
LA
C E
LO
U
IS
VI
LL
E, K Y
-M
AY
C O
N
TR
AC
T
N O
AN
SI
'D
C
AN
N
EL
TO
N
L O
C
KS
A N
D D
AM
C
AN
N
EL
TO
N
IN
TE
R
LO
C
KS
/D
AM
E
N C
O D
ER
S
U
PG
R
AD
ES
FY
4, P
C
ER
TI
FI
ED
F
IN
AL
J.
TI
M
BA
S
J.
M
O O
R E
J.
M
O O
R E
J.
TI
M
D
W N
ST
R
EA
M
IN
ST
R U
M
EN
T
LO
C
AT
IO
N
A N
D C
AB
LI
N G
P
LA
N V
IE
W
ES100
of Engineers
U .S
. A R
M Y
C O
R
PS
O F
EN
G
IN
EE
R S
PR
O D
U C
TI
O
N D
AT
A
1%
PR
O
D U
C
TI
O N
D
AT
A 2%
PR
O D
U C
TI
O
N D
AT
A
3%
PR
O
D U
C
TI
O N
D
AT
A 4%
1/32" = 1'-0"
E1 LOCK INSTRUMENT LOCATION PLAN - DOWNSTREAM
SCALE: 1/32" = 1'-0"
0 16'-0" 32'-0" 64'-0"
M
AT
C H
L
IN
E
- E
S1
PLAN
NORTH
W
2Q R
BA
8_
Pl an s-
M17 M18 M19 M20 M21 M22 M23 M24 M25 M26 M27 M29
M30
M31 M28 M32 M33 M34
M35
L9
L10
L11 L12 L13 L14 L15
L16
L17
L18
L19 L20 L21 L22 L23
L24 L25 L26 L27
R39 R40 R41 R42 R43 R44 R45 R46 R47 R48 R49
R50
R51 R52 R53
R54
R55 R56 R57
MAIN LOCK
AUX LOCK
MIDDLE WALL - AUX LOCK (AM)
LAND WALL - AUX LOCK (AL)
RIVER WALL - MAIN LOCK (MR)
MIDDLE WALL - MAIN LOCK (MM)
M
AI
N E
LE
C
TR
IC
AL
C
R O
SS
-O
VE
R
(E
ST
. 3
F T
D O
W N
/O
VE
R /U
P
INSTALL NEW ENCODER CABLES IN (UP TO) THREE (3) 3"
CONDUIT SECTIONS (TAGGED AS "TEL" AND/OR "SPARE")
ROUTED BETWEEN MH1 AND R51 GALLERY.
REFERENCE AS-BUILT DRAWING OC-390.1/5 FOR
ROUTING DETAILS IN DAM STRUCTURE.
VERTICAL DROP FROM MH1 TO R51 GALLERY IS 50FT.
GATE 2
GATE 1
V-3L V-2L
V-1
V-1R
PIER 2
GATE 1
GATE 2
CS-1
CS-2
CS-2L
CS-1R
CS-S
AU
X.
E
LE
C
TR
IC
AL
C R
O
SS
-O
VE
R (E
ST
. 3
F
T D
O W
N /O
VE
R
/U P
ZT
V3L
ZSO
V3L
ZSC
V3L
ZT
V2L
ZSO
V2L
ZSC
V2L
ZT
V1
ZSO
V1
ZSC
V1
ZT
V1R
ZSO
V1R
ZSC
V1R
ZT
G1
ZT
G2
MH1
MH2
V3L-IJB1-4
REFERENCE CROSSOVER PLAN AND ELEVATION
SHOWN ON AS-BUILT DRAWING OC-250.1/25
USE SPARE 4" DUCT FOR ALL NEW CABLES
ROUTED UNDER MAIN AND AUX LOCK CHAMBERS.
V1-IJB1-4
V2L-IJB1-4
OUTSIDE FACE OF
OPERATIONS BUILDING
IJB-1 TO BE MOUNTED ON FREESTANDING
STRUCTURE/PEDESTAL MOUNT LOCATED IN
APPROXIMATE AREA OF GALLERY (COORDINATE
WITH PROJECT). REFERENCE DRAWING E-400 FOR
IJB CONSTRUCTION DETAILS.
V1R-IJB1-4
IJB1-CS1-4
IJB1-CS2-4
IJB1-CSS-4
V2L-IJB1-4
V3L-IJB1-4
IJB1-CS3-4
V4-IJB1-4
V1-IJB1-4
IJB1-CS2-4
IJB1-CS1-4
G2-MCC-2
G1-MCC-2
G12-MCC-2
G11-MCC-2
G10-MCC-2
G3-MCC-2
G4-MCC-2
G5-MCC-2
G6-MCC-2
G7-MCC-2
G8-MCC-2
G9-MCC-2
G12-MCC-2
G11-MCC-2
G10-MCC-2
G3-MCC-2
G4-MCC-2
G5-MCC-2
G6-MCC-2
G7-MCC-2
G8-MCC-2
G9-MCC-2
G1-MCC-2
G2-MCC-2
V4-IJB1-4
V1R-IJB1-4
REFERENCE CROSSOVER PLAN AND ELEVATION
SHOWN ON AS-BUILT DRAWING OC-250.1/25
USE SPARE 4" DUCT FOR ALL NEW CABLES
ROUTED UNDER MAIN AND AUX LOCK CHAMBERS.
G2-MCC-2
J1 E-502
TYP. ALL VALVE
LOCATIONS
E10 E-500
TYP. ALL GATE
LOCATIONS
J11 E-403
J1 E-403
IJB1-CS2JB-4
IJB1-CS1JB-4
NEW INSTRUMENTATION
C3
E-506 LEVER LOCKS
NEW INSTRUMENTATION
C3
E-506 LEVER LOCKS
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
A
B
C
D
E
F
G
H
J
K
L
M
N
P
SU
BM
IT
TE
D B
Y:
C H
EC
KE
D B
Y:
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
IS
SU
E D
AT
E:
SI
ZE
M
AR
K
D
ES
C R
IP
TI
O N
D
AT
IS
VI
LL
E
D
IS
TR
IC
T
D
R . M
AR
TI
N L
U
TH
ER
K
IN
G
J R
. P
LA
C E
LO
U
IS
VI
LL
E, K Y
-M
AY
C O
N
TR
AC
T
N O
AN
SI
'D
C
AN
N
EL
TO
N
L O
C
KS
A N
D D
AM
C
AN
N
EL
TO
N
IN
TE
R
LO
C
KS
/D
AM
E
N C
O D
ER
S
U
PG
R
AD
ES
FY
4, P
C
ER
TI
FI
ED
F
IN
AL
J.
TI
M
BA
S
J.
M
O O
R E
J.
M
O O
R E
J.
TI
M
PS
TR
EA
M
IN
ST
R
U M
EN
T
LO
C
AT
IO
N A
N D
C
AB
LI
N
G P
LA
N
V
IE
ES101
of Engineers
U .S
. A R
M Y
C O
R
PS
O F
EN
G
IN
EE
R S
PR
O D
U C
TI
O
N D
AT
A
1%
PR
O
D U
C
TI
O N
D
AT
A 2%
PR
O D
U C
TI
O
N D
AT
A
3%
PR
O
D U
C
TI
O N
D
AT
A 4%
1/32" = 1'-0"
B1 LOCK INSTRUMENT LOCATION PLAN - UPSTREAM
SCALE: 1/32" = 1'-0"
0 16'-0" 32'-0" 64'-0"
PLAN
NORTH
W
2Q R
BA
8_
Pl an s-
R47 R48 R49
R50
R51 R52
INSTALL NEW ENCODER CABLES IN (UP TO) THREE (3) 3"
CONDUIT SECTIONS (TAGGED AS "TEL" AND/OR "SPARE")
ROUTED BETWEEN MH1 AND R51 GALLERY.
REFERENCE AS-BUILT DRAWING OC-390.1/5 FOR
ROUTING DETAILS IN DAM STRUCTURE.
VERTICAL DROP FROM MH1 TO R51 GALLERY IS 50FT.
V-1R
PIER 2
PIER 3
PIER 4
GATE 1
GATE 2
GATE 3
GATE 4
ZT
V1R
ZSO
V1R
ZSC
V1R
ZT
G1
ZT
G2
ZT
G3
ZT
G4
MH1
MH2
MH3
MH4
V1R-IJB1-4
G4-MCC-2
G3-MCC-2
G2-MCC-2
G1-MCC-2
G12-MCC-2
G11-MCC-2
G10-MCC-2
G3-MCC-2
G4-MCC-2
G5-MCC-2
G6-MCC-2
G7-MCC-2
G8-MCC-2
G9-MCC-2
G2-MCC-2
E10 E-500
TYP. ALL GATE
LOCATIONS
PIER 5
PIER 6
PIER 7
PIER 8
GATE 4
GATE 5
GATE 6
GATE 7
GATE 8
ZT
G5
ZT
G6
ZT
G7
MH5
MH6
MH7
MH8
AS REQUIRED, INSTALL NEW ENCODER CABLES
IN (UP TO) THREE (3) 3" CONDUIT
SECTIONS (TAGGED AS "TEL" OR "SPARE")
ROUTED BETWEEN MH13 AND MH1
(AND WHICH TIE INTO ALL MANHOLES INDICATED).
REFERENCE AS-BUILT DRAWING
OC-390.1/3 FOR DAM AREA CONDUIT ROUTING DETAILS.
G8-MCC-2
G7-MCC-2
G5-MCC-2
ZT
G8
PIER 9
PIER 10
PIER 11
PIER 12
PIER 13
GATE 9
GATE 10
GATE 11
GATE 12
ZT
G9
ZT
G10
ZT
G11
ZT
G12
MH9
MH10
MH11
MH12
MH13
ROUTE NEW INSTRUMENT CABLE
IN SAME CONDUIT WHICH FIBER
CABLE WAS INSTALLED. PATHWAY
SHOWN IS AN APPROXIMATION
OF CONDUIT ROUTING
IN UPPER PORTION OF DAM.
G12-MCC-2
G12-MCC-2
G12-MCC-2
G11-MCC-2
G10-MCC-2
G9-MCC-2
G11-MCC-2
G11-MCC-2
G10-MCC-2
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
A
B
C
D
E
F
G
H
J
K
L
M
N
P
SU
BM
IT
TE
D B
Y:
C H
EC
KE
D B
Y:
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
IS
SU
E D
AT
E:
SI
ZE
M
AR
K
D
ES
C R
IP
TI
O N
D
AT
IS
VI
LL
E
D
IS
TR
IC
T
D
R . M
AR
TI
N L
U
TH
ER
K
IN
G
J R
. P
LA
C E
LO
U
IS
VI
LL
E, K Y
-M
AY
C O
N
TR
AC
T
N O
AN
SI
'D
C
AN
N
EL
TO
N
L O
C
KS
A N
D D
AM
C
AN
N
EL
TO
N
IN
TE
R
LO
C
KS
/D
AM
E
N C
O D
ER
S
U
PG
R
AD
ES
FY
4, P
C
ER
TI
FI
ED
F
IN
AL
J.
TI
M
BA
S
J.
M
O O
R E
J.
M
O O
R E
J.
TI
M
N
EW
A N
AL
O
G G
AT
E
C
AB
LI
N
G , U
PS
TR
EA
M
C
AB
LE
R
O U
TI
N
G P
LA
N
V
IE
ES102
of Engineers
U .S
. A R
M Y
C O
R
PS
O F
EN
G
IN
EE
R S
PR
O D
U C
TI
O
N D
AT
A
1%
PR
O
D U
C
TI
O N
D
AT
A 2%
PR
O D
U C
TI
O
N D
AT
A
3%
PR
O
D U
C
TI
O N
D
AT
A 4%
1/32" = 1'-0"
B1
DAM INSTRUMENT
LOC. PLAN GATES 1-4
SCALE: 1/32" = 1'-0"
0 16'-0" 32'-0" 64'-0" 1/32" = 1'-0"
B8
DAM INSTRUMENT
LOC. PLAN GATES 5-8
1/32" = 1'-0"
B14
DAM INSTRUMENT
LOC. PLAN GATES 9-12
PLAN
NORTH
PLAN
NORTH
PLAN
NORTH
W
2Q R
BA
8_
Pl an s-
DEMOLISH EXISTING ENCODER AND CABLE
AFTER DISCONNECTING ENCODER CABLE FROM
CONTROL ENCLOSURE TERMINALS,
REMOVE CABLE GRIP AND REPLACE WITH PLUG
TO SEAL UP CONDUIT (TO BE LEFT AS-IS)
DEMOLISH CHAIN DRIVE, GUARD, SPROCKETS AND
MOUNTS USED TO ACTUATE AND MOUNT EXISTING
ENCODER (ORIGINAL SELSYN POSITION INDICATOR)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
A
B
C
D
E
F
G
H
J
K
L
M
N
P
SU
BM
IT
TE
D B
Y:
C H
EC
KE
D B
Y:
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
IS
SU
E D
AT
E:
SI
ZE
M
AR
K
D
ES
C R
IP
TI
O N
D
AT
IS
VI
LL
E
D
IS
TR
IC
T
D
R . M
AR
TI
N L
U
TH
ER
K
IN
G
J R
. P
LA
C E
LO
U
IS
VI
LL
E, K Y
-M
AY
D R
AW
IN
G C
O D
E
AN
SI
'D
C
AN
N
EL
TO
N
L O
C
KS
A N
D D
AM
C
AN
N
EL
TO
N
IN
TE
R
LO
C
KS
/D
AM
E
N C
O D
ER
S
U
PG
R
AD
ES
FY
4, P
C
ER
TI
FI
ED
F
IN
AL
J.
TI
M
BA
S
J.
M
O O
R E
J.
M
O O
R E
J.
TI
M
BA
S
EN
C O
D
ER
A N
D D
R
IV
E G
EA
R
S
PO
SI
TI
O N
IN
D
IC
AT
O R
R
ET
R O
FI
T
D
EM
O , T
YP
IC
AL
G
AT
ED500
of Engineers
U .S
. A R
M Y
C O
R
PS
O F
EN
G
IN
EE
R S
PR
O D
U C
TI
O
N D
AT
A
1%
PR
O
D U
C
TI
O N
D
AT
A 2%
PR
O D
U C
TI
O
N D
AT
A
3%
PR
O
D U
C
TI
O N
D
AT
A 4%
XX
X
X
A1 EXISTING GATE POSITION ENCODER AND DRIVE GEAR - DEMO AND MODIFICATIONS (TYPICAL FOR ALL GATES 1 THROUGH 12)
NOT TO SCALE
W
2Q R
BA
8_
Pl an s-
DISCONNECT AND
REMOVE ALL ENCODER
TERMINATIONS TO
INCLUDE CONDUCTORS
ROUTED UP TO FIBER
CONVERTER
DEMOLISH FIBER CONVERTER MODULE, FIBER SPLICE JBOX WITH
ASSOCIATED WIRING/CABLE/FIBER COMPONENT REMOVAL INDICATED IN
DIAGRAM. ALL POWER SUPPLIES TO REMAIN
AS-IS INSIDE GATE CONTROL PANELS.
FIBER CABLE WHICH CURRENTLY ROUTES TO
OPS BUILDING MCC MUST BE COMPLETELY
REMOVED TO ALLOW INSTALLATION OF NEW
COPPER CONDUCTORS INSTALLED AS A PART
OF THIS UPGRADE.
TYPICAL GATE CONTROL PANEL INTERIOR
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
A
B
C
D
E
F
G
H
J
K
L
M
N
P
SU
BM
IT
TE
D B
Y:
C H
EC
KE
D B
Y:
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
IS
SU
E D
AT
E:
SI
ZE
M
AR
K
D
ES
C R
IP
TI
O N
D
AT
IS
VI
LL
E
D
IS
TR
IC
T
D
R . M
AR
TI
N L
U
TH
ER
K
IN
G
J R
. P
LA
C E
LO
U
IS
VI
LL
E, K Y
-M
AY
D R
AW
IN
G C
O D
E
AN
SI
'D
C
AN
N
EL
TO
N
L O
C
KS
A N
D D
AM
C
AN
N
EL
TO
N
IN
TE
R
LO
C
KS
/D
AM
E
N C
O D
ER
S
U
PG
R
AD
ES
FY
4, P
C
ER
TI
FI
ED
F
IN
AL
J.
TI
M
BA
S
J.
M
O O
R E
J.
M
O O
R E
J.
TI
M
BA
S
EN
C O
D
ER
W
IR
IN
G
A N
D F
IB
ER
C O
N
VE
R
SI
O N
PO
SI
TI
O
N
IN
D
IC
AT
O
R R
ET
R
O
FI
T D
EM
O
, T
YP
IC
AL
G
AT
ED501
of Engineers
U .S
. A R
M Y
C O
R
PS
O F
EN
G
IN
EE
R S
PR
O D
U C
TI
O
N D
AT
A
1%
PR
O
D U
C
TI
O N
D
AT
A 2%
PR
O D
U C
TI
O
N D
AT
A
3%
PR
O
D U
C
TI
O N
D
AT
A 4%
XX
X
X
A1 EXISTING GATE POSITION ENCODER WIRING AND FIBER CONVERSION - DEMO AND MODIFICATIONS (TYPICAL FOR ALL GATES 1 THROUGH 12)
NOT TO SCALE
W
2Q R
BA
8_
Pl an s-
REMOVE ALL TWELVE (12) ENCODER FIBER
CABLES FROM CONDUIT SLEEVE WHICH DROPS
FROM MH1 (AT TOP OF DAM) DOWN INTO
MONOLITH R51 IN LOCK. THIS CONDUIT SHOULD
BE CLEAR OF ALL CABLE. CONTINUE REMOVAL IN
TRAY, THROUGH CROSSOVER, THEN TO M25
GALLERY WHERE IT RISES INTO BOTTOM OF
MCC IN OPERATIONS BUILDING.
MAIN ELECTRICAL CROSSOVER DUCT BANK (ROUTED
UNDER MAIN LOCK) ACCESS POINT IN M25 GALLERY
LOCATED DIRECTLY BELOW OPERATIONS BUILDING.
ALL TWELVE ENCODER FIBER CABLES EMERGE FROM
THIS POINT - THEN ROUTED TO MCC DIRECTLY
ABOVE (NOT SHOWN IN PHOTO). DEMOLISH ALL 12
FIBER CABLES CONTAINED IN SINGLE DUCT
DUCT BANK ACCESS TO AUXILIARY LOCK
ELECTRICAL CROSSOVER (FOR REFERENCE
ONLY). CABLE VPS-1 (TO BE REMOVED IN
FURTHER DIRECTIONS) EMERGE FROM
CROSSOVER HERE
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
A
B
C
D
E
F
G
H
J
K
L
M
N
P
SU
BM
IT
TE
D B
Y:
C H
EC
KE
D B
Y:
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
IS
SU
E D
AT
E:
SI
ZE
M
AR
K
D
ES
C R
IP
TI
O N
D
AT
IS
VI
LL
E
D
IS
TR
IC
T
D
R . M
AR
TI
N L
U
TH
ER
K
IN
G
J R
. P
LA
C E
LO
U
IS
VI
LL
E, K Y
-M
AY
D R
AW
IN
G C
O D
E
AN
SI
'D
C
AN
N
EL
TO
N
L O
C
KS
A N
D D
AM
C
AN
N
EL
TO
N
IN
TE
R
LO
C
KS
/D
AM
E
N C
O D
ER
S
U
PG
R
AD
ES
FY
4, P
C
ER
TI
FI
ED
F
IN
AL
J.
TI
M
BA
S
J.
M
O O
R E
J.
M
O O
R E
J.
TI
M
BA
S G
AL
LE
R Y
FI
BE
R C
AB
LE
S
PO
SI
TI
O N
IN
D
IC
AT
O R
R
ET
R O
FI
T
D
EM
O , T
YP
IC
AL
G
AT
ED502
of Engineers
U .S
. A R
M Y
C O
R
PS
O F
EN
G
IN
EE
R S
PR
O D
U C
TI
O
N D
AT
A
1%
PR
O
D U
C
TI
O N
D
AT
A 2%
PR
O D
U C
TI
O
N D
AT
A
3%
PR
O
D U
C
TI
O N
D
AT
A 4%
XX
X
X
A1 EXISTING GATE POSITION ENCODERS - GALLERY CABLE DEMO BETWEEN GATES AND MCC IN OPS BUILDING
NOT TO SCALE
W
2Q R
BA
8_
Pl an s-
ALL GATE POSITION INDICATORS TO REMAIN AS-IS
WITH ALL TERMINATIONS ON BACK SIDE TERMINALS
TO REMAIN CONNECTED
STEP 2 OF 2 - DISCONNECT AND REMOVE ALL FIBER
CABLES FROM GATES, FIBER SPLICE ENCLOSURE
AND ALL TWELVE (12) FIBER CONVERTERS AS
INDICATED IN PHOTO AND WIRING DIAGRAM. DO NOT
REMOVE ANY DIN RAIL OR WIRE DUCTS.
ALL GATE POSITION INDICATORS TO REMAIN AS-IS
WITH ALL TERMINATIONS ON BACK SIDE TERMINALS
TO REMAIN CONNECTED. ROLL AND SECURE
UN-TERMINATED INSTRUMENT CABLE PAST GRAY
WIRE DUCT FOR FUTURE INSTALLATION OF COPPER
CONDUCTORS FROM NEW ENCODER CABLES (WHICH
LAND ON NEW TERMINAL STRIP).
STEP 1 OF 2 - TEMPORARILY PULL FUSES F1 AND F2,
THEN DEMO ALL BLUE/BRN/GRN WIRES (+24/COM/G)
WHICH SUPPLY POWER TO FIBER CONVERTERS.
LEAVE ALL OTHER CONDUCTORS TERMINATED AS-IS.
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
A
B
C
D
E
F
G
H
J
K
L
M
N
P
SU
BM
IT
TE
D B
Y:
C H
EC
KE
D B
Y:
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
IS
SU
E D
AT
E:
SI
ZE
M
AR
K
D
ES
C R
IP
TI
O N
D
AT
IS
VI
LL
E
D
IS
TR
IC
T
D
R . M
AR
TI
N L
U
TH
ER
K
IN
G
J R
. P
LA
C E
LO
U
IS
VI
LL
E, K Y
-M
AY
D R
AW
IN
G C
O D
E
AN
SI
'D
C
AN
N
EL
TO
N
L O
C
KS
A N
D D
AM
C
AN
N
EL
TO
N
IN
TE
R
LO
C
KS
/D
AM
E
N C
O D
ER
S
U
PG
R
AD
ES
FY
4, P
C
ER
TI
FI
ED
F
IN
AL
J.
TI
M
BA
S
J.
M
O O
R E
J.
M
O O
R E
J.
TI
M
BA
S M
C C
C O
M
PO
N
EN
T
AN
D W
IR
IN
G
PO
SI
TI
O N
IN
D
IC
AT
O R
R
ET
R O
FI
T
D
EM
O , T
YP
IC
AL
G
AT
ED503
of Engineers
U .S
. A R
M Y
C O
R
PS
O F
EN
G
IN
EE
R S
PR
O D
U C
TI
O
N D
AT
A
1%
PR
O
D U
C
TI
O N
D
AT
A 2%
PR
O D
U C
TI
O
N D
AT
A
3%
PR
O
D U
C
TI
O N
D
AT
A 4%
XX
X
X
A1 EXISTING GATE POSITION ENCODERS - OPERATIONS BUILDING MCC WIRING AND COMPONENT DEMO
NOT TO SCALE
W
2Q R
BA
8_
Pl an s-
CLEAR SPACE IN M25 GALLERY FOR NEW
INSTRUMENT JUNCTION BOX (IJB-1) TO BE
INSTALLED IN FRONT OF CABLES TRAYS,
HERE ON FLOOR-MOUNTED PEDESTAL.
REFERENCE SITE PLANS FOR LOCATION.
SPARE/UNUSED 4" CONDUIT WHICH IS A PART
OF MAIN LOCK CROSSOVER DUCTBANK -
LOCATED IN M25 GALLERY
SPARE/UNUSED 4" CONDUIT WHICH IS A PART
OF AUX LOCK CROSSOVER DUCTBANK -
LOCATED IN M25 GALLERY
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
A
B
C
D
E
F
G
H
J
K
L
M
N
P
SU
BM
IT
TE
D B
Y:
C H
EC
KE
D B
Y:
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
IS
SU
E D
AT
E:
SI
ZE
M
AR
K
D
ES
C R
IP
TI
O N
D
AT
IS
VI
LL
E
D
IS
TR
IC
T
D
R . M
AR
TI
N L
U
TH
ER
K
IN
G
J R
. P
LA
C E
LO
U
IS
VI
LL
E, K Y
-M
AY
D R
AW
IN
G C
O D
E
AN
SI
'D
C
AN
N
EL
TO
N
L O
C
KS
A N
D D
AM
C
AN
N
EL
TO
N
IN
TE
R
LO
C
KS
/D
AM
E
N C
O D
ER
S
U
PG
R
AD
ES
FY
4, P
C
ER
TI
FI
ED
F
IN
AL
J.
TI
M
BA
S
J.
M
O O
R E
J.
M
O O
R E
J.
TI
M
BA
S
IJ
B-
M O
U N
TI
N
G A
R
EA
C
LE
AR
AN
C E
PO
SI
TI
O
N
IN
D
IC
AT
O
R R
ET
R
O
FI
T D
EM
O
, T
YP
IC
AL
G
AT
ED504
of Engineers
U .S
. A R
M Y
C O
R
PS
O F
EN
G
IN
EE
R S
PR
O D
U C
TI
O
N D
AT
A
1%
PR
O
D U
C
TI
O N
D
AT
A 2%
PR
O D
U C
TI
O
N D
AT
A
3%
PR
O
D U
C
TI
O N
D
AT
A 4%
XX
X
X
D1
NEW INSTRUMENT JUNCTION BOX (IJB-1) MOUNTING LOCATION
NOT TO SCALE
D11
AVAILABLE SPARE CROSSOVER DUCTS - AUX AND MAIN LOCKS
NOT TO SCALE
W
2Q R
BA
8_
Pl an s-
DEMO ENTIRE SELSYN ASSEMBLY TO INCLUDE ALL WALL MOUNT
COMPONENTS. DEMO CABLE ALL THE WAY TO AN ACCESSIBLE
POINT IN GALLERY. DEMO CABLE GRIP AND ENSURE CONDUIT IS
CLEAR FOR FUTURE INSTALLATION OF NEW ENCODER CABLE.
THE CONTRACTOR IS TO IDENTIFY AND PROVIDE
NEW THREADED 316SS INSERTS FOR
INSTALLATION OF NEW ENCODER MOUNTING
BRACKET ASSEMBLY AS REQUIRED. HOWEVER, IF
EXISTING INSERTS ARE SERVICEABLE, WITH A
SPACING WHICH CAN ACCOMMODATE NEW
BRACKETS DEFINED IN THIS DRAWING SET, THE
EXISTING THREADED INSERTS IN CONCRETE MAY
BE REUSED.
DEMO CHAIN AND UPPER SPROCKET
ALONG WITH SELSYN MOUNT, BUT DO NOT
REMOVE LOWER SPROCKET. VALVE
FULCRUM SENSOR ACTUATOR SHAFT AND
SPROCKET (NOT SHOWN) TO BE REUSED IN
FUTURE INSTALLATION
DEMO CHAIN, BUT PRESERVE
CHAIN GUARD AS-IS.
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
A
B
C
D
E
F
G
H
J
K
L
M
N
P
SU
BM
IT
TE
D B
Y:
C H
EC
KE
D B
Y:
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
IS
SU
E D
AT
E:
SI
ZE
M
AR
K
D
ES
C R
IP
TI
O N
D
AT
IS
VI
LL
E
D
IS
TR
IC
T
D
R . M
AR
TI
N L
U
TH
ER
K
IN
G
J R
. P
LA
C E
LO
U
IS
VI
LL
E, K Y
-M
AY
D R
AW
IN
G C
O D
E
AN
SI
'D
C
AN
N
EL
TO
N
L O
C
KS
A N
D D
AM
C
AN
N
EL
TO
N
IN
TE
R
LO
C
KS
/D
AM
E
N C
O D
ER
S
U
PG
R
AD
ES
FY
4, P
C
ER
TI
FI
ED
F
IN
AL
J.
TI
M
BA
S
J.
M
O O
R E
J.
M
O O
R E
J.
TI
M
BA
S
EN
C O
D
ER
A N
D D
R
IV
E G
EA
R
S
PO
SI
TI
O N
IN
D
IC
AT
O R
R
ET
R O
FI
T
D
EM
O , T
YP
IC
AL
V
AL
VE
ED505
of Engineers
U .S
. A R
M Y
C O
R
PS
O F
EN
G
IN
EE
R S
PR
O D
U C
TI
O
N D
AT
A
1%
PR
O
D U
C
TI
O N
D
AT
A 2%
PR
O D
U C
TI
O
N D
AT
A
3%
PR
O
D U
C
TI
O N
D
AT
A 4%
XX
X
X
A1 EXISTING VALVE POSITION SELSYN AND DRIVE GEAR DEMO (TYPICAL FOR ALL VALVE LOCATIONS)
NOT TO SCALE
W
2Q R
BA
8_
Pl an s-
DEMO ALL SELSYN CABLING AND
SPLICES BETWEEN ALL SIX (6)
SENSORS AND MCC
(SWITCHBOARD) IN ADDITION TO
ALL CABLES BETWEEN MCC AND
FIVE (5) CONTROL STATIONS.
DEMO ALL SELSYN CABLING AND SPLICES
BETWEEN ALL SIX (6) SENSORS AND MCC
(SWITCHBOARD) IN ADDITION TO ALL CABLES
BETWEEN MCC AND FIVE (5) CONTROL
STATIONS.
ALL SELSYN (VPSx) CABLES
COMBINE IN CULVERT VALVE
RELAY PANEL AS INDICATED IN
AS-BUILT DRAWINGS OC-250.1/8
AND /9.
ENSURE CONTROL STATION
CONDUIT SECTIONS BETWEEN
GALLERY AND CABINET, WHERE
VPSx CABLES ARE REMOVED, ARE
CLEAR FOR FUTURE USE WITH
NEW ENCODER CABLING.
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
A
B
C
D
E
F
G
H
J
K
L
M
N
P
SU
BM
IT
TE
D B
Y:
C H
EC
KE
D B
Y:
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
IS
SU
E D
AT
E:
SI
ZE
M
AR
K
D
ES
C R
IP
TI
O N
D
AT
IS
VI
LL
E
D
IS
TR
IC
T
D
R . M
AR
TI
N L
U
TH
ER
K
IN
G
J R
. P
LA
C E
LO
U
IS
VI
LL
E, K Y
-M
AY
D R
AW
IN
G C
O D
E
AN
SI
'D
C
AN
N
EL
TO
N
L O
C
KS
A N
D D
AM
C
AN
N
EL
TO
N
IN
TE
R
LO
C
KS
/D
AM
E
N C
O D
ER
S
U
PG
R
AD
ES
FY
4, P
C
ER
TI
FI
ED
F
IN
AL
J.
TI
M
BA
S
J.
M
O O
R E
J.
M
O O
R E
J.
TI
M
BA
S G
AL
LE
R Y
SE
LS
YN
C
AB
LE
S
PO
SI
TI
O N
IN
D
IC
AT
O R
R
ET
R O
FI
T
D
EM
O , T
YP
IC
AL
V
AL
ED506
of Engineers
U .S
. A R
M Y
C O
R
PS
O F
EN
G
IN
EE
R S
PR
O D
U C
TI
O
N D
AT
A
1%
PR
O
D U
C
TI
O N
D
AT
A 2%
PR
O D
U C
TI
O
N D
AT
A
3%
PR
O
D U
C
TI
O N
D
AT
A 4%
XX
X
X
A1 EXISTING RIVER-SIDE VALVE POSITION SENSOR - GALLERY CABLE DEMO BETWEEN VALVES AND MCC IN OPS BUILDING
NOT TO SCALE
A1 EXISTING LAND-SIDE AND MIDDLE VALVE POSITION SENSOR - GALLERY CABLE DEMO BETWEEN VALVES AND MCC IN OPS BUILDING
NOT TO SCALE
W
2Q R
BA
8_
Pl an s-
REMOVE ALL FOUR (4)
VALVE POSITION INDICATORS.
WORK LIGHT TO REMAIN
CONNECTED TO POWER SOURCE.
DEMO ALL CONTROL STATION
POWER WIRING BETWEEN VALVE
POSITION INDICATORS AND CS-S
VPS TERMINALS. MAKE NO
ALTERATIONS TO VALVE CONTROL
WIRING.
VPS4-M CABLE TO BE REMOVED
AND REPLACED WITH NEW
MULTI-PAIR ENCODER CABLE.
DEMO TO INCLUDE CABLE GRIP
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
A
B
C
D
E
F
G
H
J
K
L
M
N
P
SU
BM
IT
TE
D B
Y:
C H
EC
KE
D B
Y:
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
IS
SU
E D
AT
E:
SI
ZE
M
AR
K
D
ES
C R
IP
TI
O N
D
AT
IS
VI
LL
E
D
IS
TR
IC
T
D
R . M
AR
TI
N L
U
TH
ER
K
IN
G
J R
. P
LA
C E
LO
U
IS
VI
LL
E, K Y
-M
AY
D R
AW
IN
G C
O D
E
AN
SI
'D
C
AN
N
EL
TO
N
L O
C
KS
A N
D D
AM
C
AN
N
EL
TO
N
IN
TE
R
LO
C
KS
/D
AM
E
N C
O D
ER
S
U
PG
R
AD
ES
FY
4, P
C
ER
TI
FI
ED
F
IN
AL
J.
TI
M
BA
S
J.
M
O O
R E
J.
M
O O
R E
J.
TI
M
BA
S
ST
AT
IO
N C
S- S
M
ET
ER
S
AN
D
W
IR
IN
G
PO
SI
TI
O
N
IN
D
IC
AT
O
R R
ET
R
O
FI
T D
EM
O
, T
YP
IC
AL
V
AL
ED507
of Engineers
U .S
. A R
M Y
C O
R
PS
O F
EN
G
IN
EE
R S
PR
O D
U C
TI
O
N D
AT
A
1%
PR
O
D U
C
TI
O N
D
AT
A 2%
PR
O D
U C
TI
O
N D
AT
A
3%
PR
O
D U
C
TI
O N
D
AT
A 4%
XX
X
X
A1
STATION CS-S PANEL AND WIRING DEMO
NOT TO SCALE
W
2Q R
BA
8_
Pl an s-
REMOVE BOTH VALVE POSITION
INDICATORS FROM CONTROL
STATIONS CS-2 AND CS-3
DEMO ALL CONTROL STATION
CS-2 WIRING BETWEEN VALVE
POSITION INDICATORS AND CS-2
VPS TERMINALS. MAKE NO
ALTERATIONS TO VALVE CONTROL
WIRING. REFERENCE AS-BUILT
DRAWING OC-250.1/13 FOR
COMPLETE WIRING DIAGRAM
DEMO ALL CONTROL STATION
CS-3 WIRING BETWEEN VALVE
POSITION INDICATORS AND CS-3
VPS TERMINALS. MAKE NO
ALTERATIONS TO VALVE CONTROL
WIRING. REFERENCE AS-BUILT
DRAWING OC-250.1/13 FOR
COMPLETE WIRING DIAGRAM
ENSURE CONTROL STATION
CONDUIT SECTIONS BETWEEN
GALLERY AND CABINET, WHERE
VPSx CABLES WERE REMOVED, ARE CLEAR FOR FUTURE USE
WITH NEW ENCODER CABLING.
ENSURE CONTROL STATION
CONDUIT SECTIONS BETWEEN
GALLERY AND CABINET, WHERE
VPSx CABLES WERE REMOVED, ARE CLEAR FOR FUTURE USE
WITH NEW ENCODER CABLING.
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
A
B
C
D
E
F
G
H
J
K
L
M
N
P
SU
BM
IT
TE
D B
Y:
C H
EC
KE
D B
Y:
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
IS
SU
E D
AT
E:
SI
ZE
M
AR
K
D
ES
C R
IP
TI
O N
D
AT
IS
VI
LL
E
D
IS
TR
IC
T
D
R . M
AR
TI
N L
U
TH
ER
K
IN
G
J R
. P
LA
C E
LO
U
IS
VI
LL
E, K Y
-M
AY
D R
AW
IN
G C
O D
E
AN
SI
'D
C
AN
N
EL
TO
N
L O
C
KS
A N
D D
AM
C
AN
N
EL
TO
N
IN
TE
R
LO
C
KS
/D
AM
E
N C
O D
ER
S
U
PG
R
AD
ES
FY
4, P
C
ER
TI
FI
ED
F
IN
AL
J.
TI
M
BA
S
J.
M
O O
R E
J.
M
O O
R E
J.
TI
M
BA
S
PA
N
EL
S C
S-
AN
D
C S-
M
ET
ER
S
AN
D W
IR
IN
G
PO
SI
TI
O N
IN
D
IC
AT
O R
R
ET
R O
FI
T
D
EM
O , T
YP
IC
AL
V
AL
ED508
of Engineers
U .S
. A R
M Y
C O
R
PS
O F
EN
G
IN
EE
R S
PR
O D
U C
TI
O
N D
AT
A
1%
PR
O
D U
C
TI
O N
D
AT
A 2%
PR
O D
U C
TI
O
N D
AT
A
3%
PR
O
D U
C
TI
O N
D
AT
A 4%
XX
X
X
C1
CONTROL STATIONS CS-2 AND CS-3 PANEL AND WIRING DEMO
NOT TO SCALE
W
2Q R
BA
8_
Pl an s-
DEMO ALL CONTROL STATION CS-1
WIRING BETWEEN VALVE
POSITION INDICATORS AND CS-1
VPS TERMINALS. MAKE NO
ALTERATIONS TO VALVE CONTROL
WIRING. REFERENCE AS-BUILT
DRAWING OC-250.1/12 FOR
COMPLETE WIRING DIAGRAM
REMOVE ALL VALVE POSITION
INDICATORS FROM CONTROL
STATIONS CS-1 AND CS-4
DEMO ALL CONTROL STATION
CS-4 WIRING BETWEEN VALVE
POSITION INDICATORS AND CS-4
VPS TERMINALS. MAKE NO
ALTERATIONS TO VALVE CONTROL
WIRING. REFERENCE AS-BUILT
DRAWING OC-250.1/12 FOR
COMPLETE WIRING DIAGRAM
ENSURE CONTROL STATION
CONDUIT SECTIONS BETWEEN
GALLERY AND CABINET, WHERE
VPSx CABLES WERE REMOVED, ARE CLEAR FOR FUTURE USE
WITH NEW ENCODER CABLING.
ENSURE CONTROL STATION
CONDUIT SECTIONS BETWEEN
GALLERY AND CABINET, WHERE
VPSx CABLES WERE REMOVED, ARE CLEAR FOR FUTURE USE
WITH NEW ENCODER CABLING.
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
A
B
C
D
E
F
G
H
J
K
L
M
N
P
SU
BM
IT
TE
D B
Y:
C H
EC
KE
D B
Y:
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
IS
SU
E D
AT
E:
SI
ZE
M
AR
K
D
ES
C R
IP
TI
O N
D
AT
IS
VI
LL
E
D
IS
TR
IC
T
D
R . M
AR
TI
N L
U
TH
ER
K
IN
G
J R
. P
LA
C E
LO
U
IS
VI
LL
E, K Y
-M
AY
D R
AW
IN
G C
O D
E
AN
SI
'D
C
AN
N
EL
TO
N
L O
C
KS
A N
D D
AM
C
AN
N
EL
TO
N
IN
TE
R
LO
C
KS
/D
AM
E
N C
O D
ER
S
U
PG
R
AD
ES
FY
4, P
C
ER
TI
FI
ED
F
IN
AL
J.
TI
M
BA
S
J.
M
O O
R E
J.
M
O O
R E
J.
TI
M
BA
S
PA
N
EL
S C
S-
AN
D
C S-
M
ET
ER
S
AN
D W
IR
IN
G
PO
SI
TI
O N
IN
D
IC
AT
O R
R
ET
R O
FI
T
D
EM
O , T
YP
IC
AL
V
AL
ED509
of Engineers
U .S
. A R
M Y
C O
R
PS
O F
EN
G
IN
EE
R S
PR
O D
U C
TI
O
N D
AT
A
1%
PR
O
D U
C
TI
O N
D
AT
A 2%
PR
O D
U C
TI
O
N D
AT
A
3%
PR
O
D U
C
TI
O N
D
AT
A 4%
XX
X
X
A1
CONTROL STATIONS CS-1 AND CS-4 PANEL AND WIRING DEMO
NOT TO SCALE
W
2Q R
BA
8_
Pl an s-
MFG SUPPLIED STAINLESS STEEL
BACK PANEL. REFERENCE IJB
BACK PANEL CONSTRUCTION DETAIL
VIEW E11 (THIS SHEET)
24"
24"
8"
CONTINUOUS HINGED LID
IJB-1
24VDC INSTRUMENTATION
8"
3"
CREATE CUSTOM LABEL
LEFT 120VAC MULTIPLE CABLE TRANSIT (MCT) AND
RECEPTACLES. MARK ALL CONNECTORS AND
RECEPTACLES AS INDICATED IN WIRING DIAGRAMS AND
ARRANGE RECEPTACLES AS INDICATED IN THIS SHEET.
SEE CABLE ASSIGNMENT AND INSERT OD RANGE DETAIL
DRAWING VIEW A1 (THIS SHEET) FOR MCT.
ENCLOSURE, 24 X 24 X 8 INCH NEMA
4X, 304 STAINLESS STEEL
CONSTRUCTION W/ CONTINUOUS
HINGE AND DOOR CLAMPS. SUPPLIED
WITH STAINLESS STEEL BACK PANEL
FOR INTERIOR COMPONENT
MOUNTING.
a f a b c d e f a f a b c d e f a f a b c d e f a f a b c d e f a f a b c d e f a f a b c d e f a f a b c d e f a f a b c d e f
R1
US MAIN LOCK
SENSORS
R2
DS MAIN LOCK
SENSORS
R3
AUX LOCK
SENSORS
R4
AUX LOCK AO
TO CS
R5
MAIN LOCK AO
TO CS
R6
MAIN LOCK AO
TO OPS
R7
MAIN LOCK
INTLK TO CS
R8
AUX LOCK
INTLK TO CS
BULKHEAD CONNECTOR AND PLUG ASSEMBLY
V1R-IJB1-4
V1-IJB1-4
V4R-IJB1-4
V4-IJB1-4
V3L-IJB1-4
V2L-IJB1-4
IJB1-CS3-4
IJB1-CS2-4
IJB1-CSS-4
IJB1-CS4-4
IJB1-CS1-4A1
IJB1-CS2JB-4
IJB1-CS4JB-4
IJB1-CS1JB-4
IJB1-CS3JB-4
DRILL/TAP FOR #10 GROUND SCREW
NEAR EACH RECEPTACLE
(IN APPROXIMATE AREA SHOWN) FOR
SHIELD DRAIN TERMINATIONS (TYP)
MCT FOR SPARE/ALTERNATE
CABLE ENTRY POINT TO INTERPOSING
RELAYS ON LOWER DIN RAIL
INSTALL BREATHER-
DRAIN TO MITIGATE
CONDENSATION/MOISTURE
LEFT 120VAC MCT LAYOUT
(LEFT SIDE OF IJB AS VIEWED
FROM FRONT)
2 POSITION INSERT MODULE FOR CABLES
WITH .14" TO .65" OUTER DIAMETER
(REFERENCE CABLE SCHEDULE FOR CABLE OD)
1 POSITION INSERT MODULE FOR CABLES
WITH .37" TO 1.28" OUTER DIAMETER
(REFERENCE CABLE SCHEDULE FOR CABLE OD)
NOTE - ALL UNUSED MCT
INSERTS REMAIN SEALED.
REARRANGE INSERTS AS
REQUIRED. FRAME/INSERT
SYSTEM RATED NEMA 4X.
120VAC POWER IN
MCC-IJB1-4
IJB1-MCC-4
R
- U
PS
TR
EA
M M
AI
N
L O
C K
SE
N
SO
R
S
A1 E-516
BULKHEAD CONNECTOR AND PLUG ASSEMBLY
MARK ALL CABLE
AND RECEPTACLES AS
INDICATED IN WIRING
DIAGRAMS
NOTE - CONNECTOR
BACK SHELLS CAN BE
MODIFIED OR REPLACED
TO ACCOMMODATE FUTURE
CABLE/CONNECTIVITY
ADDITIONS. HOUSING/INSERT
SYSTEM RATED NEMA 4X.
UPPER MARKER INDICATES
UPPER FEED THROUGH TERMINALS
LOWER MARKER INDICATES
LOWER FEED THROUGH TERMINALS
STAINLESS PANEL SCREW
SECURES DIN RAIL WITH
SPRING LOCK
AND FLAT WASHER
(ALL STAINLESS)
21"
STANDARD FEED THROUGH DUAL-LEVEL TERMINAL BLOCK - GRAY
GRAY, 24-10 AWG, CONTACTS RATED AT 28A
BRIDGE PLUG CONNECTIONS FOR ELECTRICAL
BONDING TO ADJACENT TERMINALS. MULTIPLE
BRIDGE PLUGS CAN BE USED FOR OVERLAPPING
BONDING CONNECTIONS.
PE (POTENTIAL EARTH) DUAL LEVEL TERMINAL BLOCK - GREEN/YELLOW
USED FOR SHIELD DRAIN GROUNDING ONLY
ALL FOUR (4) TERMINALS BONDED TOGETHER, THEN BONDED
TO DIN RAIL THROUGH METALLIC GROUNDING CLAMP. WITH DIN
RAIL ELECTRICALLY CONNECTED TO PANEL (WHICH IS BOLTED DIRECT
TO ENCLOSURE SHELL) THE ENTIRE ENCLOSURE BECOMES GROUNDED
WHEN A SINGLE GROUND WIRE IS CONNECTED TO ANY OF THESE TERMINALS.
DO NOT USE THIS TERMINAL BLOCK FOR ANYTHING OTHER THAN
SHIELD DRAIN OR EARTH GROUNDING CONNECTIONS.
FUSED 24VDC
DISTRIBUTION AND PE/0V
TERMINALS
PS-1 - 24VDC / 10A POWER SUPPLY WITH DIAGNOSTIC IND.
"DC OK" DRY CONTACTS. PS ABLE TO OPERATE IN PARALLEL WITH
IDENTICAL TYPE OF SUPPLY (IF REQUIRED)
4-20 MA ANALOG SIGNAL
REPEATERS - 4 WAY
(VALVE POSITION INDICATION)
ZT
-V
ZT
-V
1R
ZT
-V
2L
ZT
-V
3L
ALL 1x3 WIRE DUCT FOR 24VDC / ANALOG WIRING ONLY
ARRANGE ALL COMPONENTS
AND ADD ANY ADDITIONAL
TERMINAL BLOCKS AS REQUIRED
(GROUND TERMINALS OR OTHER FEED THROUGH)
A12
A12
A2
NEMA:
IEC:A1
14 INPUT 13
A2
NEMA:
IEC:
14INPUT 13
A1
V1C
A2
NEMA:
IEC:
14INPUT 13
A1
V1R C
A2
NEMA:
IEC:
14INPUT 13
A1
V4C
A2
NEMA:
IEC:
14INPUT 13
A1
V4R C
A2
NEMA:
IEC:
14INPUT 13
A1
V2LC
A2
NEMA:
IEC:
14INPUT 13
A1
V3LCZT
-V
ZT
-V
4R
AIO
M
IO
SM
U
SM
D
SA
U
SA
D U M
M
D M
M
U
AM
D
AM
A2
NEMA:
IEC:A1
14 INPUT 13
A2
NEMA:
IEC:A1
14 INPUT 13
A2
NEMA:
IEC:A1
14 INPUT 13
U M
AL
INTERPOSING RELAYS FOR 120VAC CONTROLS
LOCATED IN MCC ABOVE THIS PANEL -
REFERENCE RELAY SCHEDULE FOR DESCRIPTION OF
ALL RELAYS INDICATED IN THIS DRAWING.
ALL 1x3 WIRE DUCT FOR 24VDC / ANALOG WIRING ONLY
ALL 1x3 WIRE DUCT FOR 24VDC / ANALOG WIRING ONLY
CM1 CM2 CM3 CM4 CM5 CM6
A2
NEMA:
IEC:
14INPUT 13
A1
C
2LL
A2
NEMA:
IEC:
14INPUT 13
A1
C
1LL
A2
NEMA:
IEC:
14INPUT 13
A1
C
3LL
A2
NEMA:
IEC:
14INPUT 13
A1
C
4LL
U
AAL
D
AAL
D M
AL
A2
NEMA:
IEC:
14INPUT 13
A1
AN
O
E
A2
NEMA:
IEC:
14INPUT 13
A1
AN
O
F
A2
NEMA:
IEC:
14INPUT 13
A1
M N
O F
A2
NEMA:
IEC:
14INPUT 13
A1
M N
O E
AUXILIARY LOCK RELAYS
MAIN LOCK RELAYS
INTERPOSING RELAYS - DC CONNECTIONS ON TOP (AS INDICATED)
PS-CSx
BOND PE/ENCLOSURE TO
POWER SUPPLY 0V HERE
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
A
B
C
D
E
F
G
H
J
K
L
M
N
P
SU
BM
IT
TE
D B
Y:
C H
EC
KE
D B
Y:
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
IS
SU
E D
AT
E:
SI
ZE
M
AR
K
D
ES
C R
IP
TI
O N
D
AT
IS
VI
LL
E
D
IS
TR
IC
T
D
R . M
AR
TI
N L
U
TH
ER
K
IN
G
J R
. P
LA
C E
LO
U
IS
VI
LL
E, K Y
-M
AY
D R
AW
IN
G C
O D
E
AN
SI
'D
C
AN
N
EL
TO
N
L O
C
KS
A N
D D
AM
C
AN
N
EL
TO
N
IN
TE
R
LO
C
KS
/D
AM
E
N C
O D
ER
S
U
PG
R
AD
ES
FY
4, P
C
ER
TI
FI
ED
F
IN
AL
J.
TI
M
BA
S
J.
M
O O
R E
J.
M
O O
R E
J.
TI
M
BA
S
IJ
B-
EN
C
LO
SU
R E
IN
ST
R U
M
EN
T
JU
N C
TI
O
N B
O X
LA
YO
U T
E-400 of Engineers
U .S
. A R
M Y
C O
R
PS
O F
EN
G
IN
EE
R S
PR
O D
U C
TI
O
N D
AT
A
1%
PR
O
D U
C
TI
O N
D
AT
A 2%
PR
O D
U C
TI
O
N D
AT
A
3%
PR
O
D U
C
TI
O N
D
AT
A 4%
XX
X
X
G1 INSTRUMENT JUNCTION BOX IJB-1 CONSTRUCTION
3" = 1'-0"
E11 IJB-1 BACK PANEL CONSTRUCTION
6" = 1'-0"
A12 DUAL LEVEL TERMINAL BLOCK ELEVATION AND SCHEMATIC
6" = 1'-0"
A1 INSTRUMENT JUNCTION BOX MCT AND RECEPTACLE DETAIL
6" = 1'-0"
W
2Q R
BA
8_
Pl an s-
IJB-CSx
24VDC INTERLOCK RELAYS
8"
3"
ENCLOSURE, 16 X 16 X 6 INCH NEMA 4X,
304 STAINLESS STEEL CONSTRUCTION
W/ CONTINUOUS HINGE AND DOOR
CLAMPS. SUPPLIED WITH STAINLESS
STEEL BACK PANEL FOR INTERIOR
COMPONENT MOUNTING.
16"
6"
MFG SUPPLIED STAINLESS STEEL
BACK PANEL. REFERENCE IJB
BACK PANEL CONSTRUCTION DETAIL
VIEW G12 (THIS SHEET)
CONTINUOUS HINGED LID CREATE CUSTOM LABEL
FOR ALL FOUR (4) CONTROL
STATION INTERLOCK
ASSEMBLIES - IJB-CS1,2,3,4
120VAC POWER
TO DEDICATED BRANCH
CIRCUIT AT ASSOCIATED
CONTROL HOUSE
INSTALL BREATHER-
DRAIN TO MITIGATE
CONDENSATION/MOISTURE
a f a b c d e f
R9-12
CS INTERLOCK
INTEGRATION
CS1JB-CS1-8
IJB1-CS1JB-4
RECEPTACLE
DESIGNATIONS
INDICATED IN
WIRING DIAGRAMS
CS1/R9
a f a b c d e f
R13-16
CS INTERLOCK
INSTRUMENTS
RECEPTACLE
DESIGNATIONS
INDICATED IN
WIRING DIAGRAMS
DRILL/TAP FOR #10
GROUND SCREW NEAR EACH
RECEPTACLE (IN APPROXIMATE
AREA SHOWN) FOR SHIELD DRAIN
TERMINATIONS (TYP)
A1 E400
CS2JB-CS2-8
IJB1-CS2JB-4
CS2/R10
CS3JB-CS3-8
IJB1-CS3JB-4
CS3/R11
CS4JB-CS4-8
IJB1-CS4JB-4
CS4/R12
LL1-CS1JB-4 CS1/R13
CS2/R14
CS3/R15
CS4/R16
LL2-CS2JB-4
LL3-CS3JB-4
LL4-CS4JB-4
A2
NEMA:
IEC:A1
14 INPUT 13
C R
E
A2
NEMA:
IEC:A1
14 INPUT 13
C R
S
A2
NEMA:
IEC:A1
14 INPUT 13
C R
AL
A2
NEMA:
IEC:A1
14 INPUT 13
U M
O R
1 3
FM
24VDC / 10A POWER SUPPLY
WITH DIAGNOSTIC IND."DC OK" DRY CONTACTS
ABLE TO OPERATE IN PARALLEL WITH
IDENTICAL TYPE OF SUPPLY
(IF REQUIRED)
PS-CSx
1 3
SS
FLASHER MODULE (FM) - 24 VDC / 75 FPM
SINGLE SHOT (SS) - POSITIVE
EDGE TRIGGER W/10 MIN OFF DELAY
MOUNT BOTH MODULES TO DIN
RAIL WITH ADAPTOR ACCESSORY
OPERATIONAL READY (xxOR) RELAYS
CHANGE DESIGNATION AT EACH CONTROL STATION
LOCATION. REFERENCE WIRING AND RELAY SCHEDULE FOR
PROPER DESIGNATION OF THIS RELAY
TON
BOND PE/ENCLOSURE TO
POWER SUPPLY 0V HERE
FUSED 24VDC
DISTRIBUTION
(F1 AND F2) AND PE/0V
TERMINALS TS-CSx
FOR 4 PAIR CABLE
CONNECTION
TO IJB-1
DIODE MODULE, 4 DIODE
REQUIRED AT ALL STATIONS
(1N5408 1000V 3A GP DIODE)
DM
TIME ON DELAY MULTIFUNCTION RELAY SET TO TURN ON
(ENGAGE CONTACTS) 2 MINUTES AFTER COIL IS ENERGIZED
(CAN BE ADJUSTED TO UP TO 1 HOUR) THIS RELAY IS ONLY REQUIRED FOR
DOWNSTREAM STATIONS CS-3 AND CS-4
A2
NEMA:
IEC:A1
14 INPUT 13
C R
N L
NEUTRAL LATCH CONTROL RELAYS (CRNL)
ONLY USED IN UPSTREAM CONTROL STATIONS
CS-1 AND CS-2
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
A
B
C
D
E
F
G
H
J
K
L
M
N
P
SU
BM
IT
TE
D B
Y:
C H
EC
KE
D B
Y:
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
IS
SU
E D
AT
E:
SI
ZE
M
AR
K
D
ES
C R
IP
TI
O N
D
AT
IS
VI
LL
E
D
IS
TR
IC
T
D
R . M
AR
TI
N L
U
TH
ER
K
IN
G
J R
. P
LA
C E
LO
U
IS
VI
LL
E, K Y
-M
AY
D R
AW
IN
G C
O D
E
AN
SI
'D
C
AN
N
EL
TO
N
L O
C
KS
A N
D D
AM
C
AN
N
EL
TO
N
IN
TE
R
LO
C
KS
/D
AM
E
N C
O D
ER
S
U
PG
R
AD
ES
FY
4, P
C
ER
TI
FI
ED
F
IN
AL
J.
TI
M
BA
S
J.
M
O O
R E
J.
M
O O
R E
J.
TI
M
BA
S
IJ
B- C
S1 T
H R
O U
G H
C S4
E N
C
LO
SU
R
ES
IN
ST
R
U M
EN
T
JU
N
C
TI
O N
B O
X
LA
YO
U
T
E-401 of Engineers
U .S
. A R
M Y
C O
R
PS
O F
EN
G
IN
EE
R S
PR
O D
U C
TI
O
N D
AT
A
1%
PR
O
D U
C
TI
O N
D
AT
A 2%
PR
O D
U C
TI
O
N D
AT
A
3%
PR
O
D U
C
TI
O N
D
AT
A 4%
XX
X
X
G1 INSTRUMENT JUNCTION BOX CS1 THROUGH CS4 CONSTRUCTION
3" = 1'-0"
G12 CS1 THROUGH CS4 BACK PANEL CONSTRUCTION
6" = 1'-0"
W
2Q R
BA
8_
Pl an s-
L1 L2
PE/GND +24 COM
F1
.5 A
GRN BLUE BRN
F2
A
+24 VDC
BLU
BR
N
VAC IN
BL
U
EXISTING POWER SUPPLY, FUSING AND DISTRIBUTION TO
BE (RE)USED TO SUPPLY POWER FOR ALL NEW TAINTER GATE
ENCODERS. REFERENCE DEMO DRAWING ED503 PRIOR TO
BEGINNING MODIFICATIONS SHOWN ON THIS SHEET.
VOLTAGE ADJUST
IN
ST
R U
M
EN
T C
AB
LE
U P
AN
D
O
VE
R T
O G
AT
E
PO
SI
TI
O
N
IN
D
IC
AT
O
R S
IN
A
D
JA
C
EN
T M
C C
S
EC
TI
O
N
REPLACE 1.5" WIRE DUCT AS REQUIRED IF 50% MAX FILL
CANNOT BE ACHIEVED WITH NEW ENCODER CABLES. REFERENCE
CABLE SCHEDULE FOR PLANNED NOMINAL CABLE OD'S.
PE/GRN-YEL
ZT-G1
PE/GRN-YEL
ZT-G2
PE/GRN-YEL
ZT-G3
PE/GRN-YEL
ZT-G4
PE/GRN-YEL
ZT-G5
PE/GRN-YEL
ZT-G6
PE/GRN-YEL
ZT-G7
PE/GRN-YEL
ZT-G8
PE/GRN-YEL
ZT-G9
PE/GRN-YEL
ZT-G10
PE/GRN-YEL
ZT-G11
PE/GRN-YEL
ZT-G12
STANDARD FEED THROUGH DUAL-LEVEL TERMINAL BLOCK - GRAY
(REFERENCE SECTION VIEW FOR DETAILS)
UPPER MARKER INDICATES
UPPER FEED THROUGH TERMINALS
LOWER MARKER INDICATES
LOWER FEED THROUGH TERMINALS
STAINLESS PANEL SCREW
SECURES DIN RAIL WITH
SPRING LOCK
AND FLAT WASHER
(ALL STAINLESS)
STANDARD FEED THROUGH DUAL-LEVEL TERMINAL BLOCK - GRAY, 24-10 AWG, CONTACTS RATED AT 28A
BRIDGE PLUG CONNECTIONS FOR ELECTRICAL
BONDING TO ADJACENT TERMINALS. MULTIPLE
BRIDGE PLUGS CAN BE USED FOR OVERLAPPING
BONDING CONNECTIONS.
PE (POTENTIAL EARTH) DUAL LEVEL TERMINAL BLOCK - GREEN/YELLOW
USED FOR SHIELD DRAIN GROUNDING ONLY
ALL FOUR (4) TERMINALS BONDED TOGETHER, THEN BONDED
TO DIN RAIL THROUGH METALLIC GROUNDING CLAMP. WITH DIN
RAIL ELECTRICALLY CONNECTED TO PANEL (WHICH IS BOLTED DIRECT
TO ENCLOSURE SHELL) THE ENTIRE ENCLOSURE BECOMES GROUNDED
WHEN A SINGLE GROUND WIRE IS CONNECTED TO ANY OF THESE TERMINALS.
DO NOT USE THIS TERMINAL BLOCK FOR ANYTHING OTHER THAN
SHIELD DRAIN CONNECTIONS.
K12 E-402
K12 E-402
ROUTE ALL NEW ENCODER CABLES UP TO NEW OR EXISTING
DUCT FROM M25 GALLERY AREA/CABLE TRAY DIRECTLY
BELOW MCC. REPLACE 1.5" WIRE DUCT AS REQUIRED IF 50% MAX FILL
CANNOT BE ACHIEVED WITH NEW ENCODER CABLES. REFERENCE
CABLE SCHEDULE FOR PLANNED NOMINAL CABLE OD'S.
MOUNT ALL NEW COMPONENTS TO EXISTING DIN RAIL
VERIFY/ADJUST ZERO AND SPAN
FOR ALL 12 GATE POSITION METERS
ONCE NEW ENCODER INSTALLATION
IS COMPLETE. REPLACE UNSERVICEABLE METERS AS
REQUIRED WITH SAME MODEL NUMBER OR,
ALTERNATIVELY, PERFORM A COMPLETE
REPLACEMENT OF ALL THESE METERS
IN SAME LOCATION WHICH HAVE SAME LEVEL
OF FUNCTIONALITY.
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
A
B
C
D
E
F
G
H
J
K
L
M
N
P
SU
BM
IT
TE
D B
Y:
C H
EC
KE
D B
Y:
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
IS
SU
E D
AT
E:
SI
ZE
M
AR
K
D
ES
C R
IP
TI
O N
D
AT
IS
VI
LL
E
D
IS
TR
IC
T
D
R . M
AR
TI
N L
U
TH
ER
K
IN
G
J R
. P
LA
C E
LO
U
IS
VI
LL
E, K Y
-M
AY
D R
AW
IN
G C
O D
E
AN
SI
'D
C
AN
N
EL
TO
N
L O
C
KS
A N
D D
AM
C
AN
N
EL
TO
N
IN
TE
R
LO
C
KS
/D
AM
E
N C
O D
ER
S
U
PG
R
AD
ES
FY
4, P
C
ER
TI
FI
ED
F
IN
AL
J.
TI
M
BA
S
J.
M
O O
R E
J.
M
O O
R E
J.
TI
M
BA
S
FO
R A
LL
N
EW
G
AT
E
EN
C
O D
ER
C
O N
N
EC
TI
O
N S
G
- G
AN
AL
O G
S
EN
SO
R
M C
C P
AN
EL
M O
D
IF
IC
AT
IO
N
E-402 of Engineers
U .S
. A R
M Y
C O
R
PS
O F
EN
G
IN
EE
R S
PR
O D
U C
TI
O
N D
AT
A
1%
PR
O
D U
C
TI
O N
D
AT
A 2%
PR
O D
U C
TI
O
N D
AT
A
3%
PR
O
D U
C
TI
O N
D
AT
A 4%
XX
X
X
A1 MCC BACK PANEL MODIFICATIONS - ADJACENT TO GATE POSITION PANEL METERS
6" = 1'-0"
K12 DUAL LEVEL TERMINAL BLOCK ELEVATION AND SCHEMATIC
6" = 1'-0"
B12 EXISTING GATE POSITION INDICATORS
NOT TO SCALE
W
2Q R
BA
8_
Pl an s-
B7 B7
B7
ALL SELSYN GAUGES TO
BE REPLACED WITH NEMA 4X
4-20mA LOOP POWERED, SUNLIGHT
VISIBLE DISPLAYS (TYP ALL STATIONS).
RIVER WALL VALVE 4R RIVER WALL VALVE 1R
MIDDLE WALL VALVE 4 MIDDLE WALL VALVE 1
RETROFIT OPERATOR PANELS WITH INDICATED
GRAPHICS PRINTED ON SINGLE-PIECE
BLACK THERMOPLASTIC
POLYCARBONATE FILM WITH WHITE 3/16" TEXT,
PERMANENTLY ADHERED TO 14GA 300
SERIES STAINLESS STEEL PLATE WHICH IS
LASER/WATER JET CUT FOR ALL OPERATORS
AND INDICATORS SHOWN. BOLT THIS PRINTED
FLAT/CUT PANEL (WITH MOUNTED INDICATORS)
TO ENCLOSURE TOP LID, WHICH HAS
ALSO BEEN CUT TO MATCH COMPONENT
LOCATIONS FOR PROPER CLEARANCE.
SECURE TO CONSOLE WITH STAINLESS
STEEL #8-32 BUTTON HEAD SCREWS.
TYPICAL FOR ALL THREE PANEL RETROFITS.
ORIGINAL SELSYN METER CUTOUTS (APPROXIMATION).
CUT AND REMOVE ADDITIONAL SHEET METAL TO CREATE SINGLE OPENING INTO
EXISTING LOWER TERMINATION ENCLOSURES FOR MOUNTING AND WIRING OF RETROFIT PANELS
LAND WALL VALVE 2L
LAND WALL VALVE 3L
REFERENCE SHEET E-606 DETAIL A1 FOR
FULL OPERATOR/INDICATOR
DESCRIPTIONS AND ARRANGEMENTS
RIVER WALL VALVE 4R RIVER WALL VALVE 1R
MIDDLE WALL VALVE 4 MIDDLE WALL VALVE 1
INTERLOCK
ALARM
LOCKED
GRNRED
LEVER LOCK
OVERRIDE
LEVER LOCK
EXT
DS LEVERS
NOT LOCKED
RED
LEVERS
IN NEUTRAL
WHT
BLK
PB
ALARM
SILENCE
RED
PB
9.00
RET
INTERLOCK
ALARM
LOCKED
GRNRED
LEVER LOCK
OVERRIDE
LEVER LOCK
EXT
RED
LEVERS
IN NEUTRAL
WHT
BLK
PB
ALARM
SILENCE
RED
PB
RET
DS LEVERS
NOT LOCKED
RIVER WALL VALVE 4R RIVER WALL VALVE 1R
MIDDLE WALL VALVE 4 MIDDLE WALL VALVE 1
RIVER WALL VALVE 4R RIVER WALL VALVE 1R
MIDDLE WALL VALVE 4 MIDDLE WALL VALVE 1
11.7512.25
12.50
0.50
0.50
CS-2 AND CS-3
RETROFIT PANELS
CS-1 AND CS-4
RETROFIT PANELS
CS-S RETROFIT
PANEL
ALL METERS READ VALVE OPEN
AS A SCALED PERCENTAGE OF 4-20mA
PROCESS VARIABLE WITH ADDITIONAL
BAR GRAPH OPTION
5.125
ZI
V4R
ZI
V4
ZI
V1
ZI
V1R
ZI
V4R
ZI
V4
ZI
V1
ZI
V1R
2.75
8.50
LAND WALL VALVE 2L
LAND WALL VALVE 3L
INTERLOCK
ALARM
LOCKED
GRNRED
LEVER LOCK
OVERRIDE
LEVER LOCK
EXT
DS LEVERS
NOT LOCKED
RED
LEVERS
IN NEUTRAL
WHT
BLK
PB
ALARM
SILENCE
RED
PB
RET
2.25
5.50
12.00
1.75
4.25
1.50 3.50
9.00
ZI
V2L
ZI
V3L
INTERLOCK
ALARM
LOCKED
GRNRED
LEVER LOCK
OVERRIDE
LEVER LOCK
EXT
RED
LEVERS
IN NEUTRAL
WHT
BLK
PB
ALARM
SILENCE
RED
PB
RET
DS LEVERS
NOT LOCKED
3.125
THIS DETAIL IS SHOWING
CONTROL/INDICATORS FOR
DOWNSTREAM STATIONS ONLY -
REFERENCE SHEET E-606 DETAIL A1
FOR FULL OPERATOR/INDICATOR
DESCRIPTIONS AND ARRANGEMENTS
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
A
B
C
D
E
F
G
H
J
K
L
M
N
P
SU
BM
IT
TE
D B
Y:
C H
EC
KE
D B
Y:
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
IS
SU
E D
AT
E:
SI
ZE
M
AR
K
D
ES
C R
IP
TI
O N
D
AT
IS
VI
LL
E
D
IS
TR
IC
T
D
R . M
AR
TI
N L
U
TH
ER
K
IN
G
J R
. P
LA
C E
LO
U
IS
VI
LL
E, K Y
-M
AY
D R
AW
IN
G C
O D
E
AN
SI
'D
C
AN
N
EL
TO
N
L O
C
KS
A N
D D
AM
C
AN
N
EL
TO
N
IN
TE
R
LO
C
KS
/D
AM
E
N C
O D
ER
S
U
PG
R
AD
ES
FY
4, P
C
ER
TI
FI
ED
F
IN
AL
J.
TI
M
BA
S
J.
M
O O
R E
J.
M
O O
R E
J.
TI
M
BA
S
AN
D
IN
TE
R
LO
C
K C
O N
TR
O
LS
FO
R A
LL
N
EW
V
AL
VE
S
EN
SO
R
C O
N N
EC
TI
O N
S C
O N
TR
O
L
ST
AT
IO
N M
O D
IF
IC
AT
IO
N
E-403 of Engineers
U .S
. A R
M Y
C O
R
PS
O F
EN
G
IN
EE
R S
PR
O D
U C
TI
O
N D
AT
A
1%
PR
O
D U
C
TI
O N
D
AT
A 2%
PR
O D
U C
TI
O
N D
AT
A
3%
PR
O
D U
C
TI
O N
D
AT
A 4%
XX
X
X
A1 CS-S VALVE POSITION INDICATOR RETROFIT
3" = 1'-0"
J1 CS-2 AND CS-3 VALVE POSITION INDICATOR RETROFIT
3" = 1'-0"
J11 CS-1 AND CS-4 VALVE POSITION INDICATOR RETROFIT
3" = 1'-0"
B7 VALVE POSITION INDICATOR RETROFIT DETAILS
6" = 1'-0"
W
2Q R
BA
8_
Pl an s-
H2
F12 E-501
30 35
ACTUAL POSITION OF REDUCING GEAR/TRANSMISSION COMPONENT MOUNTING
MAY NOT MATCH AS-BUILT DRAWINGS. THIS SHOULD NOT INTERFERE WITH THIS
INSTALLATION. REFERENCE AS-BUILT DRAWING OC-370.1/1 FOR MACHINERY
CONSTRUCTION DETAILS.
G2 E-501
B2 E-501
H2
C2C2
Gx-MCC-2
WIRE TROUGH
ROUTE ENCODER CABLE THROUGH MACHINERY COMPONENTS WITH TRAY
OR CONDUIT (SUPPORTED AND PROTECTED AS REQUIRED BY CODE)
TO EXISTING WIRE TROUGH LOCATED BELOW CONTROL ENCLOSURE.
DO NOT SECURE CABLE OR CABLE SUPPORTS TO LARGE REMOVABLE COVER FOR ALL
GATE DRIVE MACHINERY. ONCE IN WIRE TROUGH, ROUTE CABLE THROUGH SAME
CONDUIT USED BY PREVIOUS ENCODER FIBER CABLES (AFTER DEMO/REMOVAL)
TO MCC AREA AS INDICATED IN DRAWINGS ES101, 102.
MAINTAIN MAXIMUM DISTANCE
BETWEEN NEW 4-20MA CABLES
AND EXISTING AC POWER WIRING
IN TROUGH. MAKE NO
TERMINATIONS TO ANY
COMPONENTS IN CONTROL
ENCLOSURE AND MAKE NO SPLICE
CONNECTIONS IN WIRE WAY.
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
A
B
C
D
E
F
G
H
J
K
L
M
N
P
SU
BM
IT
TE
D B
Y:
C H
EC
KE
D B
Y:
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
IS
SU
E D
AT
E:
SI
ZE
M
AR
K
D
ES
C R
IP
TI
O N
D
AT
IS
VI
LL
E
D
IS
TR
IC
T
D
R . M
AR
TI
N L
U
TH
ER
K
IN
G
J R
. P
LA
C E
LO
U
IS
VI
LL
E, K Y
-M
AY
D R
AW
IN
G C
O D
E
AN
SI
'D
C
AN
N
EL
TO
N
L O
C
KS
A N
D D
AM
C
AN
N
EL
TO
N
IN
TE
R
LO
C
KS
/D
AM
E
N C
O D
ER
S
U
PG
R
AD
ES
FY
4, P
C
ER
TI
FI
ED
F
IN
AL
J.
TI
M
BA
S
J.
M
O O
R E
J.
M
O O
R E
J.
TI
M
BA
S
AL
L
TA
IN
TE
R G
AT
ES
, G 1-
G
PO
SI
TI
O
N
IN
D
IC
AT
O
R R
ET
R
O
FI
T
EL
EV
AT
IO
N
A N
D P
LA
N
V
IE
W S, T
YP
IC
AL
G
AT
E-500 of Engineers
U .S
. A R
M Y
C O
R
PS
O F
EN
G
IN
EE
R S
PR
O D
U C
TI
O
N D
AT
A
1%
PR
O
D U
C
TI
O N
D
AT
A 2%
PR
O D
U C
TI
O
N D
AT
A
3%
PR
O
D U
C
TI
O N
D
AT
A 4%
XX
X
X
C2 ZT-Gx GATE POS. ENCODER RETROFIT PLAN VIEW 1/2" = 1'-0"
H2 ZT-Gx GATE POS. ENCODER RETROFIT, FACING DIAL 1/2" = 1'-0"
E10 ZT-Gx GATE POS. ENCODER RETROFIT, ELEVATION (TYPICAL DRIVE SIDE) 1/2" = 1'-0"
W
2Q R
BA
8_
Pl an s-
Ø1/4" X 12.5 MM SHAFT
1.664"
Ø1.417"
5-PIN M12 CONNECTOR
M3x0.5 6mm
(TYP)
Ø1.024"
90 DEG (TYP)
ROLLER CHAIN SPROCKET
3/4" SHAFT SIZE WITH 1/4" SET SCREW
2.05" DIA, 24 TEETH, 1/4" PITCH
INSTALL ON GATE POSITION DIAL
SHAFT IN APPROXIMATE LOCATION
ROLLER CHAIN SPROCKET
3/4" SHAFT SIZE WITH 1/4" SET SCREW
2.05" DIA, 24 TEETH, 1/4" PITCH
INSTALL ON GATE POSITION DIAL
SHAFT IN APPROXIMATE LOCATION
(CHAIN NOT SHOWN FOR CLARITY)
EX. ANTI-BACKLASH WEIGHT
AND SHEAVE ASSY - RELOCATE ON
SHAFT AS NEEDED
3.
2.5"
SECURE 1-5/8" STRUT CHANNEL
TO ENCLOSURE WALL
(BACKSIDE OF DIAL FACE)
WITH COUNTER-SUNK / FH SCREWS.
ROLLER CHAIN SPROCKET
1/2" SHAFT SIZE WITH 1/4" SET SCREW
2.05" DIA, 24 TEETH, 1/4" PITCH-
INSTALLED ON 1/2" X 6" 304 SS
ROTARY SHAFT
CONTINUOUS GATE POS.
ALL (12) TAGS: ZT - Gxx
MOUNTED TO CUSTOM FABRICATED
6.5" X 6" X 2.7" BRACKET CONSTRUCTED
FROM 14 GA 304 SS. SHIM BRACKET
OR OTHER COMPONENTS AS NEEDED
FOR PROPER ALIGNMENT OF SHAFTS.
ULTRA-CORROSION RESISTANT
MOUNTED ACETAL BALL BEARINGS
FOR 1/2" SHAFT, W/ 1-21/64" MOUNTING
HEIGHT, 1/4" SET SCREW -
5" X 1-1/2" X 2-9/16" OVERALL DIMS.
SPACE AS INDICATED TO ALLOW FOR
GEAR MOUNTING IN BETWEEN BEARINGS
(IF NEEDED TO ACCOMMODATE AS-BUILT
CONSTRUCTION OF DIAL SHAFT)
FABRICATE 6" X 6" X 6" ENCODER
COMPONENT MOUNTING BRACKET WITH 1/4"
THICK 304 STAINLESS STEEL.
FLEXIBLE SHAFT COUPLING (F-F),
REDUCING FROM 1/2" TO 1/4" SHAFT
ZTG1-JB-2
EX. GATE POSITION DIAL FACE
NEMA 4X CORROSION/WASHDOWN
RESISTANT PVC ENCLOSURE
4" X 4" X 2 3/8"
SECURE CABLE TO ENCODER MOUNT
ZTG1-JB-2
ZTG12-JB-2
POSITION STRUT CHANNELS TO
ALLOW FOR PROPER CLEARANCE
OF EXISTING STRUCTURES AND
FASTENERS. ENSURE THEY ARE
INSTALLED PARALLEL TO ALLOW FOR
HORIZONTAL POSITIONING OF ENCODER
BRACKET
EX. GATE POSITION DIAL FACE
SINGLE STRAND CORROSION-
RESISTANT (STAINLESS STEEL)
CHAIN. TRADE SIZE 25-SS
G1-MCC-2
G12-MCC-2
Gx-JB
MAKE WIRING
SPLICE
CONNECTIONS
INSIDE JB
ADJUST CHAIN TENSION BY
SHIFTING ENCLOSURE AWAY
(ON STRUT CHANNEL) FROM
DIAL SHAFT
ADJUST FRONT-BACK
SPROCKET ALIGNMENT
WITH SET SCREW(S)
EX. GATE POSITION DIAL FACE
6.
16"
SHIM AS REQUIRED TO COMPENSATE
FOR IRREGULAR SURFACES AND
ANGULAR MISALIGNMENT OF SPROCKETS
CONTINUOUS GATE POS.
ALL (12) TAGS: ZT - Gxx
MOUNTED TO CUSTOM FABRICATED
6.5" X 6" X 2.7" BRACKET CONSTRUCTED
FROM 14 GA 304 SS. SHIM BRACKET
OR OTHER COMPONENTS AS NEEDED
FOR PROPER ALIGNMENT OF SHAFTS.
6.00"
FLEXIBLE SHAFT COUPLING (F-F),
REDUCING FROM 1/2" TO 1/4" SHAFT
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
A
B
C
D
E
F
G
H
J
K
L
M
N
P
SU
BM
IT
TE
D B
Y:
C H
EC
KE
D B
Y:
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
IS
SU
E D
AT
E:
SI
ZE
M
AR
K
D
ES
C R
IP
TI
O N
D
AT
IS
VI
LL
E
D
IS
TR
IC
T
D
R . M
AR
TI
N L
U
TH
ER
K
IN
G
J R
. P
LA
C E
LO
U
IS
VI
LL
E, K Y
-M
AY
D R
AW
IN
G C
O D
E
AN
SI
'D
C
AN
N
EL
TO
N
L O
C
KS
A N
D D
AM
C
AN
N
EL
TO
N
IN
TE
R
LO
C
KS
/D
AM
E
N C
O D
ER
S
U
PG
R
AD
ES
FY
4, P
C
ER
TI
FI
ED
F
IN
AL
J.
TI
M
BA
S
J.
M
O O
R E
J.
M
O O
R E
J.
TI
M
BA
S
AL
L
TA
IN
TE
R G
AT
ES
, G 1-
G
PO
SI
TI
O
N
IN
D
IC
AT
O
R R
ET
R
O
FI
T D
ET
AI
LS
, T
YP
IC
AL
G
AT
E-501 of Engineers
U .S
. A R
M Y
C O
R
PS
O F
EN
G
IN
EE
R S
PR
O D
U C
TI
O
N D
AT
A
1%
PR
O
D U
C
TI
O N
D
AT
A 2%
PR
O D
U C
TI
O
N D
AT
A
3%
PR
O
D U
C
TI
O N
D
AT
A 4%
XX
X
X
G2 ENCODER RETROFIT DETAIL, AS VIEWED FACING BACK OF DIAL FACE
3" = 1'-0"
B2 ENCODER RETROFIT DETAIL, TOP VIEW
3" = 1'-0"
F12 ENCODER RETROFIT DETAIL, SIDE VIEW
3" = 1'-0"
B12 ZT-Gx ENCODER OVERALL DIMENSIONS 3" = 1'-0"
W
2Q R
BA
8_
Pl an s-
LOWER STRUT
MOUNT PLATE
V1-IJB1-4
A8
ZS
C
-V xx
ZS
O
-V xx
Vxx-JB
Vxx-JB
ZSO-Vxx
ZSC-Vxx
D1 E-503
A8
A1 A1
A1
A1
UPPER SPROCKET
MOUNT PLATE
4"
ASSEMBLE AND INSTALL NEW SENSOR
MOUNT WITH 1-5/8" STRUT CHANNEL.
ALL CHANNELS, FASTENERS, BRACKETS
ICE…
This is the start of the file's text. The full file is on GovTribe.