W912QR25B0053_Plans-0003.pdf

PDF 2 MB Posted

Attached to
WPAFB HPW HVAC Replacement
Solicitation number
W912QR25B0053
Issued by

About this file

This document is an Amendment of Solicitation/Modification of Contract (Standard Form 30) for a HVAC and Controls Renovation project at Wright-Patterson Air Force Base (WPAFB) in Ohio. Amendment 003 extends the submission date to 21 August 2025 at 10:00 AM EST and includes updates to several electrical plan sheets (ED210, ED211, ED212, ED220, E-210, E-601, E-602, and E-604). The amendment also updates construction wage rates using General Decision Number OH20250081, which applies to building construction projects in Greene County, Ohio. The wage determination includes various labor classifications with specified hourly rates, such as electricians at $38.00 per hour, pipefitters at $51.00 per hour, and cement masons at $32.71 per hour, among others. The project involves electrical and lighting modifications, with specific instructions for demolition and reinstallation of lighting fixtures across multiple building levels.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

W22W9K51353222

AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT

Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.

15A. NAME AND TITLE OF SIGNER (Type or print)

30-105-04EXCEPTION TO SF 30

APPROVED BY OIRM 11-84

STANDARD FORM 30 (Rev. 10-83) Prescribed by GSA

FAR (48 CFR) 53.243

SEE SUMMARY OF CHANGES

1. CONTRACT ID CODE PAGE OF PAGES

1 11

16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)

16C. DATE SIGNED

BY

16B. UNITED STATES OF AMERICA15C. DATE SIGNED15B. CONTRACTOR/OFFEROR

(Signature of Contracting Officer)(Signature of person authorized to sign)

8. NAME AND ADDRESS OF CONTRACTOR (No., Street , County, State and Zip Code) X W912QR25B0053

X 9B. DATED (SEE ITEM 11)

27-Jun-2025

10B. DATED (SEE ITEM 13)

9A. AMENDMENT OF SOLICITATION NO.

11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS

X The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offer X is extended, is not extended.

Offer must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended by one of the following methods:

(a) By completing Items 8 and 15, and returning 1 copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted;

or (c) By separate letter or telegram which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN

REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by telegram or letter, provided each telegram or letter makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.

12. ACCOUNTING AND APPROPRIATION DATA (If required)

13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS.

IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.

A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE

CONTRACT ORDER NO. IN ITEM 10A.

B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation date, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(B).

C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:

D. OTHER (Specify type of modification and authority)

E. IMPORTANT: Contractor is not, is required to sign this document and return copies to the issuing office.

14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)

10A. MOD. OF CONTRACT/ORDER NO.

2. AMENDMENT/MODIFICATION NO.

AMDT 0003

5. PROJECT NO.(If applicable)

6. ISSUED BY

3. EFFECTIVE DATE

11-Aug-2025

CODE

U. S. ARMY ENGINEER DISTRICT, LOUISVILLE

600 DR. MARTIN LUTHER KING, JR. PLACE

ROOM 821

LOUISVILLE KY 40202-2239

W912QR 7. ADMINISTERED BY (If other than item 6)

4. REQUISITION/PURCHASE REQ. NO.

CODE

See Item 6

FACILITY CODECODE

EMAIL:TEL:

W912QR25B0053_Plans-0003

W912QR25B0053

AMDT 0003

SECTION SF 30 BLOCK 14 CONTINUATION PAGE

SUMMARY OF CHANGES

SECTION SF 30 - BLOCK 14 CONTINUATION PAGE (SF 30)

The following have been added by full text:

SUMMARY OF CHANGES ADMT 0003

P2#: 513984 HVAC & CONTROLS RENOVATION F/20824

WPAFB, OH

Amendment 003

The submission date is extended to 21 August 2025 at 10:00 AM EST. Acknowledgment of this amendment and proposals are due at that time

SUMMARY OF CHANGES

1. The following SPECIFICATION SECTIONS have been revised and replaced in their entirety:

None.

2. The following SPECIFICATION SECTIONS have been added in their entirety:

None.

3. The following SPECIFICATION SECTIONS have been deleted in their entirety:

None

4. The following PLAN SHEETS have been revised and replaced in their entirety:

ED210 LEVEL 1 OVERALL - DEMO LIGHTING PLAN

ED211 LEVEL 1 WEST- DEMO LIGHTING PLAN

ED212 LEVEL 1 EAST - DEMO LIGHTING PLAN

ED220 LEVEL 2 – DEMO LIGHTING PLAN

E-210 LEVEL 1 WEST LIGHTING PLAN

E-601 ELECTRICAL SCHEDULES

E-602 ELECTRICAL SCHEDULES

E-604 ELECTRICAL PANEL SCHEDULES

5. The following PLAN SHEETS have been added new:

None.

6. The following PLAN SHEETS have been deleted in their entirety new:

None.

7. The following DOCUMENTS have been replaced in their entirety:

None.

8. The Construction Wage Rates have been replaced in their entirety.

SECTION 00 10 00 - SOLICITATION

The required response date/time has changed from 12-Aug-2025 01:00 PM to 21-Aug-2025 10:00 AM.

SECTION 00 73 00 - SUPPLEMENTARY CONDITIONS

The following have been modified:

WAGE RATES

"General Decision Number: OH20250081 07/25/2025

Superseded General Decision Number: OH20240081

State: Ohio

Construction Type: Building

County: Greene County in Ohio.

BUILDING CONSTRUCTION PROJECTS (does not include single family homes or apartments up to and including 4 stories).

Note: Contracts subject to the Davis-Bacon Act are generally required to pay at least the applicable minimum wage rate required under Executive Order 14026 or Executive Order 13658.

Please note that these Executive Orders apply to covered contracts entered into by the federal government that are subject to the Davis-Bacon Act itself, but do not apply to contracts subject only to the Davis-Bacon Related Acts, including those set forth at 29 CFR 5.1(a)(1).

|If the contract is entered |. Executive Order 14026 | |into on or after January 30, | generally applies to the | |2022, or the contract is | contract. | |renewed or extended (e.g., an |. The contractor must pay | |option is exercised) on or | all covered workers at | |after January 30, 2022: | least $17.75 per hour (or | | | the applicable wage rate | | | listed on this wage | | | determination, if it is | | | higher) for all hours | | | spent performing on the | | | contract in 2025. | |If the contract was awarded on |. Executive Order 13658 | |or between January 1, 2015 and | generally applies to the | |January 29, 2022, and the | contract. | |contract is not renewed or |. The contractor must pay all|

|extended on or after January | covered workers at least | |30, 2022: | $13.30 per hour (or the | | | applicable wage rate listed| | | on this wage determination,| | | if it is higher) for all | | | hours spent performing on | | | that contract in 2025. |

The applicable Executive Order minimum wage rate will be adjusted annually. If this contract is covered by one of the Executive Orders and a classification considered necessary for performance of work on the contract does not appear on this wage determination, the contractor must still submit a conformance request.

Additional information on contractor requirements and worker protections under the Executive Orders is available at http://www.dol.gov/whd/govcontracts.

Modification Number Publication Date 0 01/03/2025 1 02/07/2025 2 02/14/2025 3 03/14/2025 4 04/25/2025 5 05/30/2025 6 06/06/2025 7 07/18/2025 8 07/25/2025

ASBE0008-010 03/01/2025

Rates Fringes

ASBESTOS WORKER/HEAT & FROST

INSULATOR........................$ 35.23 23.04

BROH0018-003 06/01/2024

Rates Fringes

BRICKLAYER.......................$ 33.30 18.28

BROH0022-010 07/01/2024

Rates Fringes

TILE FINISHER....................$ 28.28 11.05

TILE SETTER......................$ 30.98 15.82

* CARP0002-017 06/01/2025

Rates Fringes

CARPENTER........................$ 30.96 18.44

ELEC0082-004 12/02/2024

Rates Fringes

ELECTRICIAN......................$ 38.00 22.49

ELEV0011-002 01/01/2025

Rates Fringes

ELEVATOR MECHANIC................$ 57.41 38.435+a+b

PAID HOLIDAYS:

a. New Year's Day, Memorial Day, Independence Day, Labor Day, Vetern's Day, Thanksgiving Day, the Friday after Thanksgiving, and Christmas Day.

b. Employer contributes 8% of regular hourly rate to vacation pay credit for employee who has worked in business more than 5 years; 6% for less than 5 years' service.

ENGI0018-034 05/01/2024

Rates Fringes

POWER EQUIPMENT OPERATOR

Crane.......................$ 44.14 16.41

ENGI0066-045 06/01/2017

Rates Fringes

POWER EQUIPMENT OPERATOR

Forklift....................$ 28.87 19.66 Grader/Blade................$ 32.42 19.66 Mechanic....................$ 32.92 19.66

IRON0044-020 06/01/2025

Rates Fringes

IRONWORKER, ORNAMENTAL...........$ 38.27 23.90

IRON0290-006 06/01/2024

Rates Fringes

IRONWORKER (Reinforcing and

Structural)......................$ 35.39 24.35

LABO0265-018 06/01/2024

Rates Fringes

LABORER

Mason Tender - Brick........$ 25.90 18.40

LABO1410-004 04/01/2024

Rates Fringes

LABORER

Common or General;

Asbestos Abatement (Removal from Ceilings, Floors, and Walls)..........$ 31.65 12.95

PAIN0249-005 05/01/2025

Rates Fringes

PAINTER (Brush and Roller).......$ 29.15 13.97

PAIN0387-002 11/01/2023

Rates Fringes

GLAZIER..........................$ 31.95 18.20

* PLAS0132-020 06/01/2025

Rates Fringes

CEMENT MASON/CONCRETE FINISHER...$ 32.71 19.27

PLUM0050-009 06/30/2025

Rates Fringes

PIPEFITTER (Excludes HVAC Pipe Installation)...............$ 51.00 32.56

PLUM0162-009 06/01/2024

Rates Fringes

PLUMBER (Includes HVAC Pipe Installation)....................$ 43.05 27.18

ROOF0042-001 08/01/2024

Rates Fringes

ROOFER...........................$ 33.00 19.42

SFOH0669-009 01/01/2025

Rates Fringes

SPRINKLER FITTER (Fire Sprinklers)......................$ 45.11 28.08

* UAVG-OH-0021 01/01/2019

Rates Fringes

OPERATOR: Oiler.................$ 27.56 16.37

* UAVG-OH-0025 01/01/2018

Rates Fringes

SHEET METAL WORKER, Excludes HVAC Duct and Unit Installation.....................$ 28.10 23.41

* UAVG-OH-0027 01/01/2018

Rates Fringes

OPERATOR:

Backhoe/Excavator/Trackhoe.......$ 34.84 14.76

SUOH2012-083 08/29/2014

Rates Fringes

DRYWALL HANGER AND METAL STUD

INSTALLER........................$ 21.02 4.21

FORM WORKER......................$ 22.41 9.01

LABORER: Mason Tender - Cement/Concrete..................$ 22.95 8.60

LABORER: Pipelayer..............$ 23.98 8.58

OPERATOR: Bobcat/Skid Steer/Skid Loader................$ 30.26 12.58

OPERATOR: Bulldozer.............$ 26.01 4.95

OPERATOR: Loader................$ 29.99 12.80

OPERATOR: Paver (Asphalt, Aggregate, and Concrete).........$ 30.28 13.29

OPERATOR: Roller................$ 28.25 12.61

PAINTER: Spray..................$ 22.78 12.40

SHEET METAL WORKER (HVAC Duct and HVAC Unit Installation Only)............................$ 26.41 17.34

TRUCK DRIVER: Dump (All Types)...$ 22.08 11.51

WELDERS - Receive rate prescribed for craft performing operation to which welding is incidental.

Note: Executive Order (EO) 13706, Establishing Paid Sick Leave for Federal Contractors applies to all contracts subject to the Davis-Bacon Act for which the contract is awarded (and any solicitation was issued) on or after January 1, 2017. If this contract is covered by the EO, the contractor must provide employees with 1 hour of paid sick leave for every 30 hours they work, up to 56 hours of paid sick leave each year.

Employees must be permitted to use paid sick leave for their own illness, injury or other health-related needs, including preventive care; to assist a family member (or person who is like family to the employee) who is ill, injured, or has other health-related needs, including preventive care; or for reasons resulting from, or to assist a family member (or person who is like family to the employee) who is a victim of, domestic violence, sexual assault, or stalking. Additional information on contractor requirements and worker protections under the EO is available at https://www.dol.gov/agencies/whd/government-contracts.

Unlisted classifications needed for work not included within the scope of the classifications listed may be added after award only as provided in the labor standards contract clauses (29CFR 5.5 (a) (1) (iii)).

The body of each wage determination lists the classifications and wage rates that have been found to be prevailing for the type(s) of construction and geographic area covered by the wage determination. The classifications are listed in alphabetical order under rate identifiers indicating whether the particular rate is a union rate (current union negotiated rate), a survey rate, a weighted union average rate, a state adopted rate, or a supplemental classification rate.

Union Rate Identifiers

A four-letter identifier beginning with characters other than ""SU"", ""UAVG"", ?SA?, or ?SC? denotes that a union rate was prevailing for that classification in the survey. Example:

PLUM0198-005 07/01/2024. PLUM is an identifier of the union whose collectively bargained rate prevailed in the survey for this classification, which in this example would be Plumbers.

0198 indicates the local union number or district council number where applicable, i.e., Plumbers Local 0198. The next number, 005 in the example, is an internal number used in processing the wage determination. The date, 07/01/2024 in the example, is the effective date of the most current negotiated rate.

Union prevailing wage rates are updated to reflect all changes over time that are reported to WHD in the rates in the collective bargaining agreement (CBA) governing the classification.

Union Average Rate Identifiers

The UAVG identifier indicates that no single rate prevailed for those classifications, but that 100% of the data reported for the classifications reflected union rates. EXAMPLE:

UAVG-OH-0010 01/01/2024. UAVG indicates that the rate is a weighted union average rate. OH indicates the State of Ohio.

The next number, 0010 in the example, is an internal number used in producing the wage determination. The date, 01/01/2024 in the example, indicates the date the wage determination was updated to reflect the most current union average rate.

A UAVG rate will be updated once a year, usually in January, to reflect a weighted average of the current rates in the collective bargaining agreements on which the rate is based.

Survey Rate Identifiers

The ""SU"" identifier indicates that either a single non-union rate prevailed (as defined in 29 CFR 1.2) for this classification in the survey or that the rate was derived by computing a weighted average rate based on all the rates reported in the survey for that classification. As a weighted average rate includes all rates reported in the survey, it may include both union and non-union rates. Example: SUFL2022-007 6/27/2024. SU indicates the rate is a single non-union prevailing rate or a weighted average of survey data for that classification. FL indicates the State of Florida. 2022 is the year of the survey on which these classifications and rates are based. The next number, 007 in the example, is an internal number used in producing the wage determination. The date, 6/27/2024 in the example, indicates the survey completion date for the classifications and rates under that identifier.

?SU? wage rates typically remain in effect until a new survey is conducted. However, the Wage and Hour Division (WHD) has the discretion to update such rates under 29 CFR 1.6(c)(1).

State Adopted Rate Identifiers

The ""SA"" identifier indicates that the classifications and prevailing wage rates set by a state (or local) government were adopted under 29 C.F.R 1.3(g)-(h). Example: SAME2023-007 01/03/2024. SA reflects that the rates are state adopted. ME refers to the State of Maine. 2023 is the year during which the state completed the survey on which the listed classifications and rates are based. The next number, 007 in the example, is an internal number used in producing the wage determination.

The date, 01/03/2024 in the example, reflects the date on which the classifications and rates under the ?SA? identifier took effect under state law in the state from which the rates were adopted.

WAGE DETERMINATION APPEALS PROCESS

1) Has there been an initial decision in the matter? This can be:

a) a survey underlying a wage determination

b) an existing published wage determination

c) an initial WHD letter setting forth a position on a wage determination matter

d) an initial conformance (additional classification and rate) determination

On survey related matters, initial contact, including requests for summaries of surveys, should be directed to the WHD Branch of Wage Surveys. Requests can be submitted via email to davisbaconinfo@dol.gov or by mail to:

Branch of Wage Surveys Wage and Hour Division U.S. Department of Labor 200 Constitution Avenue, N.W.

Washington, DC 20210

Regarding any other wage determination matter such as conformance decisions, requests for initial decisions should be directed to the WHD Branch of Construction Wage Determinations.

Requests can be submitted via email to BCWD-Office@dol.gov or by mail to:

Branch of Construction Wage Determinations Wage and Hour Division U.S. Department of Labor 200 Constitution Avenue, N.W.

Washington, DC 20210

2) If an initial decision has been issued, then any interested party (those affected by the action) that disagrees with the decision can request review and reconsideration from the Wage and Hour Administrator (See 29 CFR Part 1.8 and 29 CFR Part 7).

Requests for review and reconsideration can be submitted via email to dba.reconsideration@dol.gov or by mail to:

Wage and Hour Administrator U.S. Department of Labor 200 Constitution Avenue, N.W.

Washington, DC 20210

The request should be accompanied by a full statement of the interested party's position and any information (wage payment data, project description, area practice material, etc.) that the requestor considers relevant to the issue.

3) If the decision of the Administrator is not favorable, an interested party may appeal directly to the Administrative Review Board (formerly the Wage Appeals Board). Write to:

Administrative Review Board U.S. Department of Labor 200 Constitution Avenue, N.W.

Washington, DC 20210.

END OF GENERAL DECISION"

(End of Summary of Changes)

SS

WORKSPACE

OFFICE

OFFICE

LAB

6-MODE

HYDRAULIC

ROOM

6-MODE

ELECTRICAL

ROOM

VIBRATION

INSTRUMENT

DATA

ANALYSIS

UNISEX RR

141A

PRIVATE

OFFICE

CORRIDOR/ELECTRICAL

HELMET

IMPACT

TESTING

143D

FLIGHT

EQUIPMENT

PREP &

TESTING

143B OFFICE

TOOL ROOM

EQUIPMENT

ROOM

BIODYNAMICS

HORIZONTAL

IMPULSE

ACCELERATOR

133A

PROTOTYPING

LAB

CALIBRATION

LAB

NAMRU LAB

LAB

STORAGE

COMM

CLOSET

CORR. 3

LAB

124A

WOMEN'S RR

MEN'S RR

SHOWER/MOTHERING

KINEMATICS

LAB

CORR. 2ELECTRICAL

ROOM

PUMP ROOM

LOADING

DOCK

NAMRU LAB

NAMRU LAB

CONFERENCE

ROOM

NAMRU

EQUIPMENT

ROOM

111A

CORR. 3

BIODYNAMICS

VERTICAL

DECELERATOR

TOWER

WORKSPACE

CORR. 4

FAB SHOP

2 2

2 2

2 2

A.

B.

C.

D.

ANALYTICAL RESULTS INDICATE THAT ASBESTOS IS PRESENT IN

THE TSI PIPE WRAP.

SURVEY RESULTS OBSERVED 13 POTENTIAL MERCURY CONTAINING

DEVICES, INCLUDING THERMOSTATS THROUGHOUT THE BUILDINGS

AND THERMOMETERS ASSOCIATED WITH THE BUILDING'S AIR

HANDLERS.

ALL FLUORESCENT LIGHTS SHOULD BE ASSUMED TO BE MERCURY

CONTAINING AND ALL LIGHT BALLASTS ASSUMED TO CONTAIN PCBs

LEAD BASED PAINT (LBP), OF THE 41 DATA POINTS COLLECTED

THROUGHOUT THE BUILDING, NONE WERE FOUND TO CONTAIN LBP

1mg/cm2.

* ALL HAZARDOUS MATERIALS SHOULD BE HANDLED IN

ACCORDANCE WITH REQUIREMENTS.

HAZARDOUS MATERIALS DEMOLITION -

GENERAL NOTES

US Army Corps of Engineers ®

SHEET ID

U S

AR

M

Y C

O R

PS

O

F

EN

G

IN

EE

R

S

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

SI

ZE

C H

EC

KE

D B

Y:

AN

SI

D

IS

SU

E D

AT

E:

C O

N

TR

AC

T

N O

SO

LI

C

IT

AT

IO

N N

O

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A

D

AT

E M

AR

K

D

ES

C R

IP

TI

O N

PLAN NORTH

8' 16' 32'

1/16"=1'-0"SCALE:

KEY PLAN

EAST

WEST

NORTH

ED210

LE

VE

L

O

VE

R

AL

L

- D

EM

O

L

IG

H

TI

N G

P

LA

N

W R

IG

H

T-

PA

TT

ER

SO

N

A

IR

F O

R C

E

BB

AS

E, O H

IO

LO

U

IS

VI

LL

E D

IS

TR

IC

T

D R

. M

AR

TI

N

L U

TH

ER

K

IN

G

JR

. P

LA

C

E, LO

U

IS

VI

LL

E, K

Y, -2

J.

H

O O

VE

R

A.

TY

LE

R

R .B

AR

N

AR

D

M

AR

C

H

H

VA

C

C O

N

TR

O

LS

R

EN

O

VA

TI

O

N F

/2

FY

PR

O

JE

C

T N

O . P

2# : 5

4, Z

H

TV

C

ER

TI

FI

ED

F

IN

AL

D .R

IC

H

TE

R

GENERAL NOTES

1. REFER TO SHEET E-001 FOR GENERAL NOTES, ABBREVIATIONS, AND

SYMBOLS.

2. EXISTING CONDUIT PATHWAYS AND DEVICE AND LIGHTING BACKBOXES

SHALL REMAIN FOR REUSE WHERE POSSIBLE. ALL WIRING AND

CABLING SHALL BE REMOVED BACK TO THE SOURCE UNLESS NOTED

OTHERWISE.

3. A DASHED FIXTURE INDICATES THAT THE FIXTURE IS TO BE

DEMOLISHED AND A FIXTURE THAT IS SOLID IS EXISTING TO REMAIN.

SCALE: 1/16" = 1'-0"ED210

1 LEVEL 1 - LIGHTING DEMO PLAN

AM

EN

D

M

EN

T

7/

/2

KEY NOTES

1. ALL LIGHTS IN THIS AREA ARE TO BE REMOVED, STORED, AND

REINSTALLED UPON COMPLETION OF HVAC RENOVATION.

2. ALL LIGHTS IN THIS AREA ARE TO BE DEMOLISHED

W

2Q R

B0

3_

Pl an s-

WORKSPACE

BIODYNAMICS

HORIZONTAL

IMPULSE

ACCELERATOR

133A

PROTOTYPING

LAB

CALIBRATION

LAB

NAMRU LAB

LAB

STORAGE

COMM

CLOSET

119 CORR. 3

LAB

124A

WOMEN'S RR

MEN'S RR

CORR. 2

NAMRU LAB

NAMRU LAB

CONFERENCE

ROOM

NAMRU

EQUIPMENT

ROOM

111A

CORR. 3

CORR. 4

LOADING

DOCK

PUMP ROOM

ELECTRICAL

ROOM

2 2

SHOP

STORAGE

130A

STAIR 3

STAIR 1

A.

B.

C.

D.

ANALYTICAL RESULTS INDICATE THAT ASBESTOS IS PRESENT IN

THE TSI PIPE WRAP.

SURVEY RESULTS OBSERVED 13 POTENTIAL MERCURY CONTAINING

DEVICES, INCLUDING THERMOSTATS THROUGHOUT THE BUILDINGS

AND THERMOMETERS ASSOCIATED WITH THE BUILDING'S AIR

HANDLERS.

ALL FLUORESCENT LIGHTS SHOULD BE ASSUMED TO BE MERCURY

CONTAINING AND ALL LIGHT BALLASTS ASSUMED TO CONTAIN PCBs

LEAD BASED PAINT (LBP), OF THE 41 DATA POINTS COLLECTED

THROUGHOUT THE BUILDING, NONE WERE FOUND TO CONTAIN LBP

1mg/cm2.

* ALL HAZARDOUS MATERIALS SHOULD BE HANDLED IN

ACCORDANCE WITH REQUIREMENTS.

HAZARDOUS MATERIALS DEMOLITION -

GENERAL NOTES

US Army Corps of Engineers ®

SHEET ID

U S

AR

M

Y C

O R

PS

O

F

EN

G

IN

EE

R

S

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

SI

ZE

C H

EC

KE

D B

Y:

AN

SI

D

IS

SU

E D

AT

E:

C O

N

TR

AC

T

N O

SO

LI

C

IT

AT

IO

N N

O

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A

D

AT

E M

AR

K

D

ES

C R

IP

TI

O N

PLAN NORTH

4' 8' 16'

1/8"=1'-0"SCALE:

KEY PLAN

WEST

ED211

LE

VE

L

W

ES

T

- D

EM

O

L

IG

H

TI

N G

P

LA

N

W R

IG

H

T-

PA

TT

ER

SO

N

A

IR

F O

R C

E

BB

AS

E, O H

IO

LO

U

IS

VI

LL

E D

IS

TR

IC

T

D R

. M

AR

TI

N

L U

TH

ER

K

IN

G

JR

. P

LA

C

E, LO

U

IS

VI

LL

E, K

Y, -2

J.

H

O O

VE

R

A.

T

YL

ER

R . B

AR

N

AR

D

M

AR

C

H

H

VA

C

C O

N

TR

O

LS

R

EN

O

VA

TI

O

N F

/2

FY

PR

O

JE

C

T N

O . P

2# : 5

4, Z

H

TV

C

ER

TI

FI

ED

F

IN

AL

D . R

IC

H

TE

R

GENERAL NOTES

1. REFER TO SHEET E-001 FOR GENERAL NOTES, ABBREVIATIONS, AND

SYMBOLS.

2. EXISTING CONDUIT PATHWAYS AND DEVICE AND LIGHTING BACKBOXES

SHALL REMAIN FOR REUSE WHERE POSSIBLE. ALL WIRING AND CABLING

SHALL BE REMOVED BACK TO THE SOURCE UNLESS NOTED OTHERWISE.

3. A DASHED FIXTURE INDICATES THAT THE FIXTURE IS TO BE DEMOLISHED

AND A FIXTURE THAT IS SOLID IS EXISTING TO REMAIN.

SCALE: 1/8" = 1'-0"ED211

1 LEVEL 1 WEST - LIGHTING DEMO PLAN

KEY NOTES

1. ALL LIGHTS IN THIS AREA ARE TO BE REMOVED, STORED, AND

REINSTALLED UPON COMPLETION OF HVAC RENOVATION.

2. ALL LIGHTS IN THIS AREA ARE TO BE DEMOLISHED

AM

EN

D

M

EN

T

7/

/2

W

2Q R

B0

3_

Pl an s-

SS

SS

OFFICE

OFFICE

LAB

6-MODE

HYDRAULIC

ROOM

6-MODE

ELECTRICAL

ROOM

VIBRATION

INSTRUMENT

DATA

ANALYSIS

UNISEX RR

141A

PRIVATE

OFFICE

CORRIDOR/ELECTRICAL

HELMET

IMPACT

TESTING

143D

FLIGHT

EQUIPMENT

PREP &

TESTING

143B

OFFICE

TOOL ROOM

EQUIPMENT

ROOM

BIODYNAMICS

VERTICAL

DECELERATOR

TOWER

WORKSPACE

6-MODE

143A

6-MODE

CONTROL

143E

MEDICAL

EXAMINATION

& DATA

BANK

143C

A.

B.

C.

D.

ANALYTICAL RESULTS INDICATE THAT ASBESTOS IS PRESENT IN

THE TSI PIPE WRAP.

SURVEY RESULTS OBSERVED 13 POTENTIAL MERCURY CONTAINING

DEVICES, INCLUDING THERMOSTATS THROUGHOUT THE BUILDINGS

AND THERMOMETERS ASSOCIATED WITH THE BUILDING'S AIR

HANDLERS.

ALL FLUORESCENT LIGHTS SHOULD BE ASSUMED TO BE MERCURY

CONTAINING AND ALL LIGHT BALLASTS ASSUMED TO CONTAIN PCBs

LEAD BASED PAINT (LBP), OF THE 41 DATA POINTS COLLECTED

THROUGHOUT THE BUILDING, NONE WERE FOUND TO CONTAIN LBP

1mg/cm2.

* ALL HAZARDOUS MATERIALS SHOULD BE HANDLED IN

ACCORDANCE WITH REQUIREMENTS.

HAZARDOUS MATERIALS DEMOLITION -

GENERAL NOTES

US Army Corps of Engineers ®

SHEET ID

U S

AR

M

Y C

O R

PS

O

F

EN

G

IN

EE

R

S

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

SI

ZE

C H

EC

KE

D B

Y:

AN

SI

D

IS

SU

E D

AT

E:

C O

N

TR

AC

T

N O

SO

LI

C

IT

AT

IO

N N

O

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A

D

AT

E M

AR

K

D

ES

C R

IP

TI

O N

PLAN NORTH

4' 8' 16'

1/8"=1'-0"SCALE:

KEY PLAN

EAST

ED212

LE

VE

L

EA

ST

D

EM

O

L

IG

H

TI

N G

P

LA

N

W R

IG

H

T-

PA

TT

ER

SO

N

A

IR

F O

R C

E

BB

AS

E, O H

IO

LO

U

IS

VI

LL

E D

IS

TR

IC

T

D R

. M

AR

TI

N

L U

TH

ER

K

IN

G

JR

. P

LA

C

E, LO

U

IS

VI

LL

E, K

Y, -2

J.

H

O O

VE

R

A.

T

YL

ER

R . B

AR

N

AR

D

M

AR

C

H

H

VA

C

C O

N

TR

O

LS

R

EN

O

VA

TI

O

N F

/2

FY

PR

O

JE

C

T N

O . P

2# : 5

4, Z

H

TV

C

ER

TI

FI

ED

F

IN

AL

D . R

IC

H

TE

R

GENERAL NOTES

1. REFER TO SHEET E-001 FOR GENERAL NOTES, ABBREVIATIONS, AND

SYMBOLS.

2. EXISTING CONDUIT PATHWAYS AND DEVICE AND LIGHTING BACKBOXES

SHALL REMAIN FOR REUSE WHERE POSSIBLE. ALL WIRING AND

CABLING SHALL BE REMOVED BACK TO THE SOURCE UNLESS NOTED

OTHERWISE.

3. A DASHED FIXTURE INDICATES THAT THE FIXTURE IS TO BE

DEMOLISHED AND A FIXTURE THAT IS SOLID IS EXISTING TO REMAIN.

SCALE: 1/8" = 1'-0"ED212

1 LEVEL 1 EAST- LIGHTING DEMO PLAN

KEY NOTES

1. ALL LIGHTS IN THIS AREA ARE TO BE REMOVED, STORED, AND

REINSTALLED UPON COMPLETION OF HVAC RENOVATION.

2. ALL LIGHTS IN THIS AREA ARE TO BE DEMOLISHED

AM

EN

D

M

EN

T

7/

/2

W

2Q R

B0

3_

Pl an s-

CORR.

1 1

1 1

A.

B.

C.

D.

ANALYTICAL RESULTS INDICATE THAT ASBESTOS IS PRESENT IN

THE TSI PIPE WRAP.

SURVEY RESULTS OBSERVED 13 POTENTIAL MERCURY CONTAINING

DEVICES, INCLUDING THERMOSTATS THROUGHOUT THE BUILDINGS

AND THERMOMETERS ASSOCIATED WITH THE BUILDING'S AIR

HANDLERS.

ALL FLUORESCENT LIGHTS SHOULD BE ASSUMED TO BE MERCURY

CONTAINING AND ALL LIGHT BALLASTS ASSUMED TO CONTAIN PCBs

LEAD BASED PAINT (LBP), OF THE 41 DATA POINTS COLLECTED

THROUGHOUT THE BUILDING, NONE WERE FOUND TO CONTAIN LBP

1mg/cm2.

* ALL HAZARDOUS MATERIALS SHOULD BE HANDLED IN

ACCORDANCE WITH REQUIREMENTS.

HAZARDOUS MATERIALS DEMOLITION -

GENERAL NOTES

US Army Corps of Engineers ®

SHEET ID

U S

AR

M

Y C

O R

PS

O

F

EN

G

IN

EE

R

S

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

SI

ZE

C H

EC

KE

D B

Y:

AN

SI

D

IS

SU

E D

AT

E:

C O

N

TR

AC

T

N O

SO

LI

C

IT

AT

IO

N N

O

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A

D

AT

E M

AR

K

D

ES

C R

IP

TI

O N

PLAN NORTH

4' 8' 16'

1/8"=1'-0"SCALE:

KEY PLAN

WEST

ED220

LE

VE

L

- D

EM

O L

IG

H

TI

N

G P

LA

N

W R

IG

H

T-

PA

TT

ER

SO

N

A

IR

F O

R C

E

BB

AS

E, O H

IO

LO

U

IS

VI

LL

E D

IS

TR

IC

T

D R

. M

AR

TI

N

L U

TH

ER

K

IN

G

JR

. P

LA

C

E, LO

U

IS

VI

LL

E, K

Y, -2

J.

H

O O

VE

R

A.

T

YL

ER

R . B

AR

N

AR

D

M

AR

C

H

H

VA

C

C O

N

TR

O

LS

R

EN

O

VA

TI

O

N F

/2

FY

PR

O

JE

C

T N

O . P

2# : 5

4, Z

H

TV

C

ER

TI

FI

ED

F

IN

AL

D . R

IC

H

TE

R

KEY NOTES

1. ALL LIGHTS IN THIS AREA ARE TO BE REMOVED, STORED, AND REINSTALLED

UPON COMPLETION OF HVAC RENOVATION.

2. ALL LIGHTS IN THIS AREA ARE TO BE DEMOLISHED.

GENERAL NOTES

1. REFER TO SHEET E-001 FOR GENERAL NOTES, ABBREVIATIONS, AND SYMBOLS.

2. EXISTING CONDUIT PATHWAYS AND DEVICE AND LIGHTING BACKBOXES SHALL

REMAIN FOR REUSE WHERE POSSIBLE. ALL WIRING AND CABLING SHALL BE

REMOVED BACK TO THE SOURCE UNLESS NOTED OTHERWISE.

3. A DASHED FIXTURE INDICATES THAT THE FIXTURE IS TO BE DEMOLISHED AND A

FIXTURE THAT IS SOLID IS EXISTING TO REMAIN.

SCALE: 1/8" = 1'-0"ED220

1 LEVEL 2 - LIGHTING DEMO PLAN

AM

EN

D

M

EN

T

7/

/2

W

2Q R

B0

3_

Pl an s-

A1 A1E A1

A1

A1EA1A1A1E

A1A1EA1A1

A1EA1A1A1E

A1E

A1 A1

A1 A1

A1E A1 A1E

A1

A1E

A1A1E A1 A1E

A1

A1E

A1EA1EA1A1EA1A1E

A1E

A1E A1 A1

A1 A1 A1

A1 A1 A1E

A1E

A3E

A2A2EA2A2

A3

A3A3E

A3EA3

A3A3E

A1E

A1

A1E A1

A1

A1

A1

A1

A1E

FE F

FEF

A2A2A2A2E

A2A2EA2A2

A2A2A2A2E

A2

A2E

A1E

A1 A1E A1 A1E A1 A1E

X

JC

WORKSPACE

LAB

STORAGE

PROTOTYPING

LAB

NAMRU LAB

COMM

CLOSET

CALIBRATION

LAB

NAMRU

CHEMICAL

STORAGE

ELEV.

ENTRY

ELEVATOR

MECHANICAL

ELECTRICAL

ROOM

NAMRU LAB

NAMRU

SHOP

CORR. 3

CORR. 4

STAIR 3

MEN'S RR

SHOP

STORAGE

130A

WOMEN'S RR

NAMRU LAB

LOADING

DOCK

PUMP ROOM

STAIR 1

STORAGE

CORR. 3

BIODYNAMICS

HORIZONTAL

IMPULSE

ACCELERATOR

133A

LAB

124A

MANNEQUIN

LAB

124B

LOBBY

CORR. 1

BIODYNAMICS

VERTICAL

IMPLUSE

ACCELERATOR

STAIR

131A

SHOWER/MOTHERING

KINEMATICS

LAB

OPERATIONAL

PRODUCTS

DEVELOPMENT

BRANCH

NAMRU

EQUIPMENT

ROOM

111A

CORR. 2

CONFERENCE

A1E

A1

A1E

A1

A1E

X

X

X

X

X

X

X

X

A1

A1

A1E

A1

US Army Corps of Engineers ®

SHEET ID

U S

AR

M

Y C

O R

PS

O

F

EN

G

IN

EE

R

S

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

SI

ZE

C H

EC

KE

D B

Y:

AN

SI

D

IS

SU

E D

AT

E:

C O

N

TR

AC

T

N O

SO

LI

C

IT

AT

IO

N N

O

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A

D

AT

E M

AR

K

D

ES

C R

IP

TI

O N

PLAN NORTH

4' 8' 16'

1/8"=1'-0"SCALE:

KEY PLAN

WEST

E-210

LE

VE

L

W

ES

T

- L

IG

H

TI

N

G P

LA

N

W R

IG

H

T-

PA

TT

ER

SO

N

A

IR

F O

R C

E

BB

AS

E, O H

IO

LO

U

IS

VI

LL

E D

IS

TR

IC

T

D R

. M

AR

TI

N

L U

TH

ER

K

IN

G

JR

. P

LA

C

E, LO

U

IS

VI

LL

E, K

Y, -2

J.

H

O O

VE

R

A.

T

YL

ER

R . B

AR

N

AR

D

M

AR

C

H

H

VA

C

C O

N

TR

O

LS

R

EN

O

VA

TI

O

N F

/2

FY

PR

O

JE

C

T N

O . P

2# : 5

4, Z

H

TV

C

ER

TI

FI

ED

F

IN

AL

D . R

IC

H

TE

R

GENERAL NOTES

1. REFER TO SHEET E-001 FOR GENERAL NOTES, ABBREVIATIONS, AND

SYMBOLS.

2. CONNECT ALL NEW FIXTURES TO EXISTING LIGHTING CIRCUIT SERVING THE

AREA. EXTEND HOMERUN WIRING AS REQUIRED.

KEY NOTES

1. ALL LIGHTS IN THIS AREA ARE TO BE REINSTALLED UPON COMPLETION OF

HVAC RENOVATION.

SCALE: 1/8" = 1'-0"E-210

1 LEVEL 1 WEST - LIGHTING PLAN

AM

EN

D

M

EN

T

7/

/2

W

2Q R

B0

3_

Pl an s-

US Army Corps of Engineers ®

SHEET ID

U S

AR

M

Y C

O R

PS

O

F

EN

G

IN

EE

R

S

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

SI

ZE

C H

EC

KE

D B

Y:

AN

SI

D

IS

SU

E D

AT

E:

C O

N

TR

AC

T

N O

SO

LI

C

IT

AT

IO

N N

O

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A

D

AT

E M

AR

K

D

ES

C R

IP

TI

O N

E-601

EL

EC

TR

IC

AL

S

C H

ED

U

LE

S

W R

IG

H

T-

PA

TT

ER

SO

N

A

IR

F O

R C

E

BB

AS

E, O H

IO

LO

U

IS

VI

LL

E D

IS

TR

IC

T

D R

. M

AR

TI

N

L U

TH

ER

K

IN

G

JR

. P

LA

C

E, LO

U

IS

VI

LL

E, K

Y, -2

J.

H

O O

VE

R

A.

T

YL

ER

R . B

AR

N

AR

D

M

AR

C

H

H

VA

C

C O

N

TR

O

LS

R

EN

O

VA

TI

O

N F

/2

FY

PR

O

JE

C

T N

O . P

2# : 5

4, Z

H

TV

C

ER

TI

FI

ED

F

IN

AL

D . R

IC

H

TE

R

EQUIPMENT CONNECTIONS SCHEDULE

NAME PANEL CKT # LOAD DESCRIPTION

EQUIPMENT CIRCUIT INFORMATION

FEEDER

DISCONNECT INFORMATION

NOTESV POLES Φ W MCA MOCP FURNISHED

BY

INSTALLED

BY TYPE SWITCH

RATING

NEMA

TYPE

MECHANICAL

AC-1 PPB (E) 21,23 A/C 208 2 1 332 1.6 15 A20 EC EC UNFUSED 30 A 1

AC-2 PPD (E) 22,24 A/C 208 2 1 104 0.5 15 A20 EC EC UNFUSED 30 A 1

B-1 PDC (E) 15 BOILER 480 3 3 576,980 694 900 C1000 EC EC UNFUSED 1,200 A 1

CHWP-1 PP4 (E) 1,3,5 CHILLED WATER PUMP 480 3 3 13,960 16.8 30 C30 EC EC UNFUSED 30 A 1 CHWP-2 PP4 (E) 7,9,11 CHILLED WATER PUMP 480 3 3 13,960 16.8 30 C30 EC EC UNFUSED 30 A 1 CU-1 PPB (E) 21,23 CONDENSING UNIT 208 2 1 6,050 29.1 35 A40 EC EC UNFUSED 60 A 1 CU- 2 PPD (E) 22,24 CONDENSING UNIT 208 2 1 3,432 16.5 20 A20 EC EC UNFUSED 30 A 1

DDC PPB (E) 40 DDC 120 1 1 500 4.2 20 A20 N/A N/A N/A 0 A 1

DOAS-1 ERV M-PDP1 1,3,5 (WATTAGE ASSUMED) 480 3 3 590 0.7 20 C20 MC EC UNFUSED 60 A 1

DOAS-1 RETURN M-PDP1 6,8,10 480 3 3 8,560 10.3 15 C20 MC EC UNFUSED 30 A 1

DOAS-1 SUPPLY M-PDP1 7,9,11 480 3 3 25,000 30.1 35 C40 MC EC UNFUSED 60 A 1 ENSURE NO CP FOR

THIS FCU

EF-1 M-PDP2 7,9,11 EXHAUST FAN 480 3 3 1,745 2.1 20 C20 EC EC UNFUSED 30 A 3R

EF-2 M-PDP2 1,3,5 EXHAUST FAN 480 3 3 1,330 1.6 20 C20 EC EC UNFUSED 30 A 3R

EF-3 PPA-SEC. 2 (E) 33 EXHAUST FAN 120 1 1 1,176 9.8 20 A20 EC EC UNFUSED 20 A 3R ENSURE NO CP FOR

THIS FCU

EF-4 M-PDP2 2,4,6 EXHAUST FAN 480 3 3 1,745 2.1 20 C20 EC EC UNFUSED 30 A 3R

EF-5 PPA-SEC. 2 (E) 35 EXHAUST FAN 120 1 1 1,656 13.8 20 A20 EC EC UNFUSED 20 A 3R

FCU-1-01 PDPA (E) 21 FAN COIL UNIT 277 1 1 970 3.5 15 A20 EC EC UNFUSED 20 A 1

FCU-1-01-CP-A PDPA (E) 21 CONDENSATE PUMP 277 1 1 222 0.8 15 A20 EC EC UNFUSED 20 A 1

FCU-1-02 PDPA (E) 21 FAN COIL UNIT 277 1 1 803 2.9 15 A20 EC EC UNFUSED 20 A 1

FCU-1-02-CP-A PDPA (E) 21 CONDENSATE PUMP 277 1 1 222 0.8 15 A20 EC EC UNFUSED 20 A 1

FCU-1-03 PDPA (E) 21 FAN COIL UNIT 277 1 1 803 2.9 20 A20 EC EC UNFUSED 20 A 1

FCU-1-03-CP-A PDPA (E) 21 CONDENSATE PUMP 277 1 1 222 0.8 15 A20 EC EC UNFUSED 20 A 1 FCU-1-04 PP-8P (E) 17 FAN COIL UNIT 277 1 1 1,717 6.2 20 A20 EC EC UNFUSED 20 A 1 FCU-1-04-CP-A PP-8P (E) 17 CONDENSATE PUMP 277 1 1 222 0.8 15 A20 EC EC UNFUSED 20 A 1

FCU-1-05 PP-8P (E) 13 FAN COIL UNIT 277 1 1 420 1.5 15 A20 EC EC UNFUSED 20 A 1

FCU-1-06 PDPA (E) 20,22,24 FAN COIL UNIT 480 3 3 6,100 7.3 30 C30 EC EC UNFUSED 30 A 1 FCU-1-06-CP-A PDPB (E) 14 CONDENSATE PUMP 277 1 1 222 0.8 15 A20 EC EC UNFUSED 20 A 1 FCU-1-07 PP-8P (E) 25,27,29 FAN COIL UNIT 480 3 3 6,100 7.3 20 C20 EC EC UNFUSED 30 A 1 FCU-1-07-CP-A PDPB (E) 14 CONDENSATE PUMP 277 1 1 222 0.8 15 A20 EC EC UNFUSED 20 A 1

FCU-1-08 PDPA (E) 23 FAN COIL UNIT 277 1 1 745 2.7 20 A20 EC EC UNFUSED 20 A 1

FCU-1-08-CP-A PDPA (E) 23 CONDENSATE PUMP 277 1 1 222 0.8 15 A20 EC EC UNFUSED 20 A 1

FCU-1-09 PDPA (E) 19 FAN COIL UNIT 277 1 1 150 0.5 20 A20 EC EC UNFUSED 20 A 1

FCU-1-10 PDPA (E) 21 FAN COIL UNIT 277 1 1 520 1.9 15 A20 EC EC UNFUSED 20 A 1

FCU-1-11 PDPA (E) 23 FAN COIL UNIT 277 1 1 803 2.9 20 A20 EC EC UNFUSED 20 A 1

FCU-1-11-CP-A PDPA (E) 23 CONDENSATE PUMP 277 1 1 222 0.8 15 A20 EC EC UNFUSED 20 A 1

FCU-1-12 PDPA (E) 19 FAN COIL UNIT 277 1 1 1,717 6.2 20 A20 EC EC UNFUSED 20 A 1

FCU-1-12-CP-A PDPA (E) 19 CONDENSATE PUMP 277 1 1 222 0.8 15 A20 EC EC UNFUSED 20 A 1

FCU-1-13 PDPA (E) 23 FAN COIL UNIT 277 1 1 803 2.9 20 A20 EC EC UNFUSED 20 A 1

FCU-1-13-CP-A PDPA (E) 23 CONDENSATE PUMP 277 1 1 222 0.8 15 A20 EC EC UNFUSED 20 A 1 FCU-1-14 M-PDP1 24,26,28 FAN COIL UNIT 480 3 3 2,710 3.3 20 C20 EC EC UNFUSED 30 A 1 FCU-1-14-CP-A PDPB (E) 14 CONDENSATE PUMP 277 1 1 222 0.8 15 A20 EC EC UNFUSED 20 A 1 FCU-1-15 PP-8P (E) 26,28,30 FAN COIL UNIT 480 3 3 6,100 7.3 20 C20 EC EC UNFUSED 30 A 1 FCU-1-15-CP-A PDPB (E) 14 CONDENSATE PUMP 277 1 1 222 0.8 15 A20 EC EC UNFUSED 20 A 1

FCU-1-16 M-PDP1 4 FAN COIL UNIT 277 1 1 1,939 7 20 A20 EC EC UNFUSED 20 A 1

FCU-1-17 M-PDP1 18,20,22 FAN COIL UNIT 480 3 3 7,780 9.4 20 C20 EC EC UNFUSED 30 A 1 FCU-1-17-CP-A M-PDP1 4 CONDENSATE PUMP 277 1 1 222 0.8 15 A20 EC EC UNFUSED 20 A 1

FCU-1-18 M-PDP2 8 FAN COIL UNIT 277 1 1 1,800 6.5 15 A20 EC EC UNFUSED 20 A 1

FCU-1-18-CP-A M-PDP2 8 CONDENSATE PUMP 277 1 1 222 0.8 15 A20 EC EC UNFUSED 20 A 1

FCU-1-19 PP-8P (E) 19 FAN COIL UNIT 277 1 1 803 2.9 20 A20 EC EC UNFUSED 20 A 1

FCU-1-19-CP-A PP-8P (E) 19 CONDENSATE PUMP 277 1 1 222 0.8 15 A20 EC EC UNFUSED 20 A 1

FCU-1-20 PP-8P (E) 19 FAN COIL UNIT 277 1 1 803 2.9 20 A20 EC EC UNFUSED 20 A 1

FCU-1-20-CP-A PP-8P (E) 19 CONDENSATE PUMP 277 1 1 222 0.8 15 A20 EC EC UNFUSED 20 A 1

FCU-1-21 PP-8P (E) 19 FAN COIL UNIT 277 1 1 803 2.9 20 A20 EC EC UNFUSED 20 A 1

EQUIPMENT CONNECTIONS SCHEDULE

NAME PANEL CKT # LOAD DESCRIPTION

EQUIPMENT CIRCUIT INFORMATION

FEEDER

DISCONNECT INFORMATION

NOTESV POLES Φ W MCA MOCP FURNISHED

BY

INSTALLED

BY TYPE SWITCH

RATING

NEMA

TYPE

FCU-1-21-CP-A PP-8P (E) 19 CONDENSATE PUMP 277 1 1 222 0.8 15 A20 EC EC UNFUSED 20 A 1

FCU-1-22 PP-8P (E) 19 FAN COIL UNIT 277 1 1 803 2.9 20 A20 EC EC UNFUSED 20 A 1

FCU-1-22-CP-A PP-8P (E) 19 CONDENSATE PUMP 277 1 1 222 0.8 15 A20 EC EC UNFUSED 20 A 1

FCU-1-23 PP-8P (E) 21 FAN COIL UNIT 277 1 1 803 2.9 20 A20 EC EC UNFUSED 20 A 1

FCU-1-23-CP-A PP-8P (E) 21 CONDENSATE PUMP 277 1 1 222 0.8 15 A20 EC EC UNFUSED 20 A 1

FCU-1-24 PP-8P (E) 21 FAN COIL UNIT 277 1 1 803 2.9 20 A20 EC EC UNFUSED 20 A 1

FCU-1-24-CP-A PP-8P (E) 21 CONDENSATE PUMP 277 1 1 222 0.8 15 A20 EC EC UNFUSED 20 A 1

FCU-1-25 PP-8P (E) 21 FAN COIL UNIT 277 1 1 803 2.9 20 A20 EC EC UNFUSED 20 A 1

FCU-1-25-CP-A PP-8P (E) 21 CONDENSATE PUMP 277 1 1 222 0.8 15 A20 EC EC UNFUSED 20 A 1

FCU-1-26 PP-8P (E) 23 FAN COIL UNIT 277 1 1 803 2.9 20 A20 EC EC UNFUSED 20 A 1

FCU-1-26-CP-A PP-8P (E) 23 CONDENSATE PUMP 277 1 1 222 0.8 15 A20 EC EC UNFUSED 20 A 1

FCU-1-27 PP-8P (E) 23 FAN COIL UNIT 277 1 1 970 3.5 20 A20 EC EC UNFUSED 20 A 1

FCU-1-27-CP-A PP-8P (E) 23 CONDENSATE PUMP 277 1 1 222 0.8 20 A20 EC EC UNFUSED 20 A 1

FCU-1-28 PP-8P (E) 23 FAN COIL UNIT 277 1 1 803 2.9 20 A20 EC EC UNFUSED 20 A 1

FCU-1-29 B (E) 38,40,42 FAN COIL UNIT 480 3 3 2,830 3.4 20 C20 EC EC UNFUSED 30 A 1 FCU-1-29-CP-A PDPB (E) 16 CONDENSATE PUMP 277 1 1 222 0.8 20 A20 EC EC UNFUSED 20 A 1

FCU-1-30 PDPA (E) 21 FAN COIL UNIT 277 1 1 420 1.5 20 A20 EC EC UNFUSED 20 A 1

FCU-1-31 PDPA (E) 23 FAN COIL UNIT 277 1 1 910 3.3 15 A20 EC EC UNFUSED 20 A 1

FCU-1-31-CP-A PDPA (E) 23 CONDENSATE PUMP 277 1 1 222 0.8 15 A20 EC EC UNFUSED 20 A 1 FCU-1-32 PP-8P (E) 15 FAN COIL UNIT 277 1 1 1,606 5.8 20 A20 EC EC UNFUSED 20 A 1

FCU-2-01 PDPA (E) 19 FAN COIL UNIT 277 1 1 910 3.3 15 A20 EC EC UNFUSED 20 A 1

FCU-2-01-CP-A PDPA (E) 19 CONDENSATE PUMP 277 1 1 222 0.8 15 A20 EC EC UNFUSED 20 A 1

FCU-2-02 M-PDP1 4 FAN COIL UNIT 277 1 1 802 2.9 15 A20 EC EC UNFUSED 20 A 1

FCU-2-02-CP-A M-PDP1 4 CONDENSATE PUMP 277 1 1 222 0.8 15 A20 EC EC UNFUSED 20 A 1

FCU-2-03 PDPA (E) 19 FAN COIL UNIT 277 1 1 803 2.9 5 A20 EC EC UNFUSED 20 A 1

FCU-2-04 M-PDP1 2 FAN COIL UNIT 277 1 1 1,606 5.8 5 A20 EC EC UNFUSED 20 A 1

FCU-2-04-CP-A M-PDP1 2 CONDENSATE PUMP 277 1 1 222 0.8 15 A20 EC EC UNFUSED 20 A 1

FCU-2-05 M-PDP1 2 FAN COIL UNIT 277 1 1 803 2.9 20 A20 EC EC UNFUSED 20 A 1

FCU-2-05-CP-A M-PDP1 2 CONDENSATE PUMP 277 1 1 222 0.8 15 A20 EC EC UNFUSED 20 A 1

FCU-2-06 M-PDP1 2 FAN COIL UNIT 277 1 1 803 2.9 20 A20 EC EC UNFUSED 20 A 1

FCU-2-06-CP-A M-PDP1 2 CONDENSATE PUMP 277 1 1 222 0.8 15 A20 EC EC UNFUSED 20 A 1

FCU-2-07 M-PDP1 42 FAN COIL UNIT 277 1 1 803 2.9 20 A20 EC EC UNFUSED 20 A 1

FCU-2-07-CP-A M-PDP1 42 CONDENSATE PUMP 277 1 1 222 0.8 15 A20 EC EC UNFUSED 20 A 1

FCU-2-08 M-PDP1 42 FAN COIL UNIT 277 1 1 803 2.9 20 A20 EC EC UNFUSED 20 A 1

FCU-2-08-CP-A M-PDP1 42 CONDENSATE PUMP 277 1 1 222 0.8 15 A20 EC EC UNFUSED 20 A 1

FCU-2-09 M-PDP1 42 FAN COIL UNIT 277 1 1 803 2.9 20 A20 EC EC UNFUSED 20 A 1

FCU-2-10 M-PDP1 42 FAN COIL UNIT 277 1 1 1,316 4.8 20 A20 EC EC UNFUSED 20 A 1

FCU-2-10-CP-A M-PDP1 42 CONDENSATE PUMP 277 1 1 222 0.8 15 A20 EC EC UNFUSED 20 A 1

GMU-1 PPB (E) 39 120 1 1 2,300 19.2 20 PLUG AND

CORD

N/A N/A N/A 0 A 1

H-1 M-PDP1 25,27,29 HIGH PRESSURE ATOMIZATION 480 3 3 3,900 4.7 15 C20 EC EC UNFUSED 30 A 1

H-2 M-PDP1 30,32,34 IN ROOM STEAM 480 3 3 10,000 12 20 C20 EC EC UNFUSED 30 A 1

H-3 PPA-SEC. 2 (E) 39 ULTRA SONIC HUMIDIFIER 115 1 1 1,380 12 20 PLUG AND

CORD

N/A N/A N/A 0 A 1

H-3 CP-A PDPA (E) 23 CONDENSATE PUMP 277 1 1 222 0.8 15 A20 EC EC UNFUSED 20 A 1

H-4 PPA-SEC. 2 (E) 41 ULTRA SONIC HUMIDIFIER 115 1 1 1,380 12 15 PLUG AND

CORD

N/A N/A N/A 0 A 1

H-5 M-PDP1 37,39,41 IN ROOM STEAM 480 3 3 10,000 12 20 C20 EC EC UNFUSED 30 A 1

H-6 M-PDP1 37,39,41 IN ROOM STEAM 480 3 3 10,000 12 20 C20 EC EC UNFUSED 30 A 1

H-6-CP-A PDPB (E) 14 CONDENSATE PUMP 277 1 1 222 0.8 15 A20 EC EC UNFUSED 20 A 1

H-7 M-PDP1 37,39,41 IN ROOM STEAM 480 3 3 10,000 12 20 C20 EC EC UNFUSED 30 A 1

H-7-CP-A PDPB (E) 14 CONDENSATE PUMP 277 1 1 222 0.8 15 A20 EC EC UNFUSED 20 A 1

H-8 M-PDP1 31,33,35 IN ROOM STEAM 480 3 3 10,000 12 20 C20 EC EC UNFUSED 30 A 1

H-8-CP-A PDPA (E) 19 CONDENSATE PUMP 277 1 1 222 0.8 15 A20 EC EC UNFUSED 20 A 1

HEAT TRACE L200 (E) 29 HEAT TRACE 120 1 1 1,800 15 20 A20 EC EC N/A 15 A 1

HPCH-1 PDC (E) 16 HEAT PUMP CHILLER 480 3 3 438,353 527.3 600 C600 EC EC UNFUSED 600 A 1

HVLS-1 M-PDP1 12,14,16 HVLS FAN 480 3 3 3,900 4.7 20 C20 EC EC UNFUSED 30 A 1

HVLS-2 M-PDP1 12,14,16 HVLS FAN 480 3 3 3,900 4.7 20 C20 EC EC UNFUSED 30 A 1

HVLS-3 M-PDP1 13,15,17 HVLS FAN 480 3 3 3,900 4.7 20 C20 EC EC UNFUSED 30 A 1

HVLS-4 M-PDP1 13,15,17 HVLS FAN 480 3 3 3,900 4.7 20 C20 EC EC UNFUSED 30 A 1

HWP-1 PP4 (E) 13,15,17 HOT WATER PUMP 480 3 3 7,316 8.8 20 C20 EC EC UNFUSED 30 A 1 HWP-2 PP4 (E) 14,16,18 HOT WATER PUMP 480 3 3 7,316 8.8 20 C20 EC EC UNFUSED 30 A 1

RO-1 PPB (E) 42 RO 120 1 1 2,300 19.2 25 A30 EC EC UNFUSED 20 A 1

UH-1 PPD (E) 27,29 UNIT HEATER 208 2 1 500 2.4 20 A20 EC EC UNFUSED 20 A 1

UH-2 PPD (E) 23,25 UNIT HEATER 208 2 1 500 2.4 20 A20 EC EC UNFUSED 20 A 1

UH-3-1 M-PDP1 19,21,23 UNIT HEATER 480 3 3 500 0.6 20 C20 EC EC UNFUSED 30 A 1

UH-3- 2 M-PDP1 19,21,23 UNIT HEATER 480 3 3 500 0.6 20 C20 EC EC UNFUSED 30 A 1

VAV-1 PPD (E) 26 VARIABLE AIR VOLUME 120 1 1 1,500 12.5 20 C30 EC EC UNFUSED 30 A 1 VAV-2 PPD (E) 28 VARIABLE AIR VOLUME 120 1 1 1,500 12.5 20 A20 EC EC UNFUSED 20 A 1 VAV-3 PPD (E) 30 VARIABLE AIR VOLUME 120 1 1 1,500 12.5 20 A20 EC EC UNFUSED 20 A 1 VAV-4 PPD (E) 21 VARIABLE AIR VOLUME 120 1 1 1,500 12.5 20 A20 EC EC UNFUSED 20 A 1

MECHANICAL: 121

AM

EN

D

M

EN

T

7/

/2

W

2Q R

B0

3_

Pl an s-

SHEET ID

U S

AR

M

Y C

O R

PS

O

F

EN

G

IN

EE

R

S

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

SI

ZE

C H

EC

KE

D B

Y:

AN

SI

D

IS

SU

E D

AT

E:

C O

N

TR

AC

T

N O

SO

LI

C

IT

AT

IO

N N

O

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A

D

AT

E M

AR

K

D

ES

C R

IP

TI

O N

E-602

EL

EC

TR

IC

AL

S

C H

ED

U

LE

S

W R

IG

H

T-

PA

TT

ER

SO

N

A

IR

F O

R C

E

BB

AS

E, O H

IO

LO

U

IS

VI

LL

E D

IS

TR

IC

T

D R

. M

AR

TI

N

L U

TH

ER

K

IN

G

JR

. P

LA

C

E, LO

U

IS

VI

LL

E, K

Y, -2

J.

H

O O

VE

R

A.

T

YL

ER

R . B

AR

N

AR

D

M

AR

C

H

H

VA

C

C O

N

TR

O

LS

R

EN

O

VA

TI

O

N F

/2

FY

PR

O

JE

C

T N

O . P

2# : 5

4, Z

H

TV

C

ER

TI

FI

ED

F

IN

AL

LIGHTING FIXTURE SCHEDULE

TYPE MANUFACTURER CATALOG NO. VOLTAGE WATTS LAMP MOUNTING HEIGHT REMARKS

A1 LITHONIA CPX 2X4 AL08 SWW7 M2 120 V 51 W LED RECESSED PER CEILING 2X4 TROFFER

A1E LITHONIA CPX 2X4 AL08 SWW7 IM2 LBLP CP10 HE SD A 120 V 51 W LED RECESSED PER CEILING 2X4 TROFFER WITH EMERGENCY BATTERY BACKUP

A2 LITHONIA CPX 2X4 AL08 SWW7 M2 120 V 37 W LED RECESSED PER CEILING 2X4 TROFFER

A2E LITHONIA CPX 2X4 AL08 SWW7 IM2 LBLP CP10 HE SD A 120 V 37 W LED RECESSED PER CEILING 2X4 TROFFER WITH EMERGENCY BATTERY BACKUP

A3 LITHONIA CPX 2X4 AL08 SWW7 M2 120 V 29 W LED RECESSED PER CEILING 2X4 TROFFER

A3E LITHONIA CPX 2X4 AL08 SWW7 IM2 LBLP CP10 HE SD A 120 V 29 W LED RECESSED PER CEILING 2X4 TROFFER WITH EMERGENCY BATTERY BACKUP B1 LITHONIA ZL1D-L48-3000LM-FST-MVOLT-35K-80CRI-BAA-WH-ZACVH M100 120 V 30 W LED PENDANT PER CEILING HEIGHT PENDANT FIXTURE

B1E LITHONIA ZL1D-L48-3000LM-FST-MVOLT-35K-80CRI-E10W-BAA-WH-ZACVH

M100

120 V 30 W LED PENDANT PER CEILING HEIGHT PENDANT FIXTURE WITH EMERGENCY BATTERY BACKUP

F LITHONIA LDN6-40/15-L06/AR-LSS-MVOLT-GZ10-BAA 120 V 38 W LED CEILING RECESSED PER CEILING HEIGHT DOWNLIGHT FE LITHONIA LDN6-40/15-L06/AR-LSS-MVOLT-GZ10-E10WCP BAA 120 V 38 W LED CEILING RECESSED PER CEILING HEIGHT DOWNLIGHT WITH EMERGENCY BATTERY BACKUP X LITHONIA LQM S W 3 R 120/277 EL N SD <varies> 5 W LED WALL/CEILING SURFACE 8' - 0" / PER CEILING LED EXIT SIGN WITH EMERGENCY BATTERY BACKUP

AM

EN

D

M

EN

T

7/

/2

CABLE SCHEDULE (CU)

LABEL CB

RATING

# OF

SETS

PHASE

CONDUCTORS

NEUTRAL

CONDUCTORS

GROUNDING

CONDUCTORS CONDUIT

# SIZE # SIZE # SIZE

A

A20 20 A 1 1 #12 1 #12 1 #12 3/4" A30 30 A 1 1 #10 1 #10 1 #10 3/4" A40 40 A 1 1 #8 1 #8 1 #10 3/4" A50 50 A 1 1 #6 1 #6 1 #10 1" A60 60 A 1 1 #4 1 #4 1 #10 1" A70 70 A 1 1 #4 1 #4 1 #8 1" A80 80 A 1 1 #3 1 #3 1 #8 1-1/2" A90 90 A 1 1 #2 1 #2 1 #8 1-1/2" A100 100 A 1 1 #1 1 #1 1 #8 1-1/2" A110 110 A 1 1 #1 1 #1 1 #6 1-1/2" A125 125 A 1 1 #1 1 #1 1 #6 1-1/2" A150 150 A 1 1 #1/0 1 #1/0 1 #6 1-1/2" A175 175 A 1 1 #2/0 1 #2/0 1 #6 1-1/2" A200 200 A 1 1 #3/0 1 #3/0 1 #6 2" A225 225 A 1 1 #4/0 1 #4/0 1 #4 2"

A250 250 A 1 1 250KCMIL 1 250KCMIL 1 #4 2"

A300 300 A 1 1 350KCMIL 1 350KCMIL 1 #4 2-1/2"

A350 350 A 1 1 500KCMIL 1 500KCMIL 1 #4 3"

A400 400 A 2 1 #3/0 1 #3/0 1 #3 2" A450 450 A 2 1 #4/0 1 #4/0 1 #2 2"

B B20 20 A 1 3 #12 0 N/A 1 #12 3/4" B30 30 A 1 3 #10 0 N/A 1 #10 3/4" B40 40 A 1 3 #8 0 N/A 1 #10 1" B50 50 A 1 3 #6 0 N/A 1 #10 1" B60 60 A 1 3 #4 0 N/A 1 #10 1-1/2" B70 70 A 1 3 #4 0 N/A 1 #8 1-1/2" B80 80 A 1 3 #3 0 N/A 1 #8 1-1/2" B90 90 A 1 3 #2 0 N/A 1 #8 1-1/2" B100 100 A 1 3 #1 0 N/A 1 #8 1-1/2" B110 110 A 1 3 #1 0 N/A 1 #6 1-1/2" B125 125 A 1 3 #1/0 0 N/A 1 #6 1-1/2" B150 150 A 1 3 #1/0 0 N/A 1 #6 2" B175 175 A 1 3 #2/0 0 N/A 1 #6 2" B200 200 A 1 3 #3/0 0 N/A 1 #6 2" B225 225 A 1 3 #4/0 0 N/A 1 #4 2-1/2"

B250 250 A 1 3 250KCMIL 0 N/A 1 #4 2-1/2"

B300 300 A 1 3 350KCMIL 0 N/A 1 #4 3"

B350 350 A 1 3 500KCMIL 0 N/A 1 #3 3"

B400 400 A 2 3 #3/0 0 N/A 1 #3 2" B450 450 A 2 3 #4/0 0 N/A 1 #2 2-1/2"

B500 500 A 2 3 250KCMIL 0 N/A 1 #2 2-1/2"

B600 600 A 2 3 350KCMIL 0 N/A 1 #1 3"

C C20 20 A 1 3 #12 1 #12 1 #12 3/4" C30 30 A 1 3 #10 1 #10 1 #10 3/4" C40 40 A 1 3 #8 1 #8 1 #10 1" C50 50 A 1 3 #6 1 #6 1 #10 1" C60 60 A 1 3 #4 1 #4 1 #10 1-1/4" C70 70 A 1 3 #4 1 #4 1 #8 1-1/4" C80 80 A 1 3 #3 1 #3 1 #8 1-1/4" C90 90 A 1 3 #2 1 #2 1 #8 1-1/2" C100 100 A 1 3 #1 1 #1 1 #8 2" C110 110 A 1 3 #1 1 #1 1 #6 2" C125 125 A 1 3 #1 1 #1 1 #6 2" C150 150 A 1 3 #1/0 1 #1/0 1 #6 2" C175 175 A 1 3 #2/0 1 #2/0 1 #6 2" C200 200 A 1 3 #3/0 1 #3/0 1 #6 2-1/2" C225 225 A 1 3 #4/0 1 #4/0 1 #4 2-1/2"

C250 250 A 1 3 250KCMIL 1 250KCMIL 1 #4 2-1/2"

C300 300 A 1 3 350KCMIL 1 350KCMIL 1 #4 3-1/2"

C350 350 A 1 3 500KCMIL 1 500KCMIL 1 #3 3-1/2"

C400 400 A 2 3 #3/0 1 #3/0 1 #3 2-1/2" C450 450 A 2 3 #4/0 1 #4/0 1 #2 2-1/2"

C500 500 A 2 3 250KCMIL 1 250KCMIL 1 #2 3"

C600 600 A 2 3 350KCMIL 1 350KCMIL 1 #1 3"

C800 800 A 4 3 300KCMIL 1 300KCMIL 1 #1/0 3"

C1000 1,000 A 4 3 250KCMIL 1 250KCMIL 1 #2/0 3"

C1200 1,200 A 4 3 350KCMIL 1 350KCMIL 1 #3/0 3-1/2"

C1600 1,600 A 5 3 500KCMIL 1 500KCMIL 1 #4/0 4"

C2000 2,000 A 6 3 500KCMIL 1 500KCMIL 1 250KCMIL 4"

C2500 2,500 A 7 3 500KCMIL 1 500KCMIL 1 350KCMIL 4"

C3000 3,000 A 8 3 500KCMIL 1 500KCMIL 1 500KCMIL 4"

C4000 4,000 A 11 3 500KCMIL 1 500KCMIL 1 500KCMIL 4"

N C20N 20 A 1 3 #10 1 #8 1 #10 1" C30N 30 A 1 3 #6 1 #3 1 #10 1-1/4" C40N 40 A 1 3 #6 1 #1 1 #10 1-1/4" C50N 50 A 1 3 #4 1 #1 1 #8 1-1/2" C60N 60 A 1 3 #3 1 #1/0 1 #8 1-1/2" C70N 70 A 1 3 #2 1 #2/0 1 #8 2" C80N 80 A 1 3 #1 1 #3/0 1 #8 2" C90N 90 A 1 3 #1 1 #4/0 1 #6 2"

C100N 100 A 1 3 #1 1 250KCMIL 1 #6 2"

C110N 110 A 1 3 #1/0 2 #1/0 1 #6 2-1/2" C125N 125 A 1 3 #2/0 2 #2/0 1 #6 2-1/2" C150N 150 A 1 3 #3/0 2 #3/0 1 #6 2-1/2" C175N 175 A 1 3 #4/0 2 #4/0 1 #4 3"

C200N 200 A 1 3 250KCMIL 2 250KCMIL 1 #4 3"

C225N 225 A 1 3 300KCMIL 2 300KCMIL 1 #4 3-1/2"

C250N 250 A 1 3 500KCMIL 2 500KCMIL 1 #3 4"

C300N 300 A 1 3 500KCMIL 2 500KCMIL 1 #3 4"

C350N 350 A 2 3 #4/0 2 #4/0 1 #2 3"

C400N 400 A 2 3 250KCMIL 2 250KCMIL 1 #2 3"

C450N 450 A 2 3 300KCMIL 2 300KCMIL 1 #1 3-1/2"

C500N 500 A 2 3 500KCMIL 2 500KCMIL 1 #1/0 4"

C600N 600 A 2 3 500KCMIL 2 500KCMIL 1 #1/0 4"

C800N 800 A 4 3 250KCMIL 2 250KCMIL 1 #2/0 3"

C1000N 1,000 A 4 3 500KCMIL 2 500KCMIL 1 #4/0 4"

C1200N 1,200 A 4 3 500KCMIL 2 500KCMIL 1 #4/0 4"

C1600N 1,600 A 6 3 500KCMIL 2 500KCMIL 1 250KCMIL 4"

C2000N 2,000 A 7 3 500KCMIL 2 500KCMIL 1 350KCMIL 4"

C2500N 2,500 A 9 3 500KCMIL 2 500KCMIL 1 500KCMIL 4"

C3000N 3,000 A 10 3 500KCMIL 2 500KCMIL 1 500KCMIL 4"

C4000N 4,000 A 11 3 750KCMIL 2 750KCMIL 1 750KCMIL 5"

S

C2000S 2,000 A 6 3 500KCMIL 1 500KCMIL 0 N/A 4"

W

2Q R

B0

3_

Pl an s-

SHEET ID

U S

AR

M

Y C

O R

PS

O

F

EN

G

IN

EE

R

S

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

SI

ZE

C H

EC

KE

D B

Y:

AN

SI

D

IS

SU

E D

AT

E:

C O

N

TR

AC

T

N O

SO

LI

C

IT

AT

IO

N N

O

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A

D

AT

E M

AR

K

D

ES

C R

IP

TI

O N

E-604

EL

EC

TR

IC

AL

P

AN

EL

S C

H

ED

U

LE

S

W R

IG

H

T-

PA

TT

ER

SO

N

A

IR

F O

R C

E

BB

AS

E, O H

IO

LO

U

IS

VI

LL

E D

IS

TR

IC

T

D R

. M

AR

TI

N

L U

TH

ER

K

IN

G

JR

. P

LA

C

E, LO

U

IS

VI

LL

E, K

Y, -2

J.

H

O O

VE

R

A.

T

YL

ER

R . B

AR

N

AR

D

M

AR

C

H

H

VA

C

C O

N

TR

O

LS

R

EN

O

VA

TI

O

N F

/2

FY

PR

O

JE

C

T N

O . P

2# : 5

4, Z

H

TV

C

ER

TI

FI

ED

F

IN

AL

D . R

IC

H

TE

R

(E) Elevator 15,360 VA 70.00% 10,752 VA

(E) Transformer 83,138 VA 80.00% 66,511 VA

(E) Other 7,680 VA 100.00% 7,680 VA TOTAL EST. DEMAND CURRENT 174 A

(E) Non-Continuous 11,520 VA 100.00% 11,520 VA TOTAL CONNECTED CURRENT: 224 A

(E) Motor 11,520 VA 70.00% 8,064 VA TOTAL ESTIMATED DEMAND: 144,633 VA

(E) Mechanical Equipment 38,400 VA 70.00% 26,880 VA TOTAL CONNECTED LOAD: 186,513 VA Mechanical Equipment 18,895 VA 70.00% 13,226 VA

LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS

NOTES: PROVIDE PROVISIONS FOR LOCKING IN THE OPEN POSITION FOR BREAKERS FEEDING TO REMOTELY LOCATED TRANSFORMERS.

LEGEND:

TOTAL AMPS: 224 A 224 A 225 A

TOTAL LOAD: 62,151 VA 62,086 VA 62,275 VA

31 SPACE -- 1 -- -- 1 -- SPACE 32

29 -- -- -- 3.84 3.84 -- -- -- 30 27 -- -- -- 3.84 3.84 -- -- -- 28

25 (E) WATER BOOSTER PUMP 30 A 3 3.84 3.84 3 30 A (E) RM 114 COMPRESSOR 26

23 FCU-1-08,1-11,1-13,1-31 20 A 1 4.37 2.03 -- -- -- 24

21 FCU-1-01,02,03,30 20 A 1 4.18 2.03 -- -- -- 22

19 FCU-09,12 20 A 1 4.25 2.03 3 20 A FCU-1-06 20

17 -- -- -- 3.84 2.56 -- -- -- 18 15 -- -- -- 3.84 2.56 -- -- -- 16

13 (E) UNLABELED 30 A 3 3.84 2.56 3 20 A (E) AIR HANDLING UNIT 6 RM 107 14

11 -- -- -- 2.56 5.12 -- -- -- 12 9 -- -- -- 2.56 5.12 -- -- -- 10

7 (E) BATTERY CHARGER 20 A 3 2.56 5.12 3 40 A (E) ELEVATOR 8

5 -- -- -- 6.4 27.71 -- -- -- 6 3 -- -- -- 6.4 27.71 -- -- -- 4

1 (E) VACUUM PUMP RM 121 50 A 3 6.4 27.71 3 125 A (E) TRANSFORMER T-2 2

CKT CIRCUIT DESCRIPTION TRIP POLES A B C POLES TRIP CIRCUIT DESCRIPTION CKT

MOUNTING: Surface WIRES: 4 BUS RATING: 175 A

SUPPLY FROM: PDC (E) PHASES: 3 MAINS TYPE: MCB

LOCATION: BIODYNAMICS VERTICAL... VOLTS: 480Y/277V A.I.C. RATING: EXISTING

Branch Panel: PDPA (E)

TOTAL EST. DEMAND CURRENT 100 A

Water Pumps 13,416 VA 50.00% 6,708 VA TOTAL CONNECTED CURRENT: 149 A

(E) Receptacle 26,880 VA 68.60% 18,440 VA TOTAL ESTIMATED DEMAND: 36,123 VA

(E) Lighting 2,880 VA 125.00% 3,600 VA TOTAL CONNECTED LOAD: 53,712 VA Mechanical Equipment 10,536 VA 70.00% 7,375 VA

LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS

NOTES: PROVIDE PROVISIONS FOR LOCKING IN THE OPEN POSITION FOR BREAKERS FEEDING TO REMOTELY LOCATED TRANSFORMERS.

LEGEND:

TOTAL AMPS: 159 A 140 A 152 A

TOTAL LOAD: 18,869 VA 16,837 VA 18,007 VA

29 -- -- -- 0.25 1.5 1 20 A VAV-3 30

27 UH-3 20 A 2 0.25 1.5 1 20 A VAV-2 28

25 -- -- -- 0.25 1.5 1 20 A VAV-1 26

23 UH-2 20 A 2 0.25 1.77 -- -- -- 24

21 VAV-4 20 A 1 1.5 1.77 2 20 A CU-2 & AC-2 22

19 -- -- -- 2.22 3.38 -- -- -- 20

17 -- -- -- 2.22 3.38 2 50 A (E) SOUTH DISCONNECT FOR TEMP AC 18

15 (E) RM 111 AIR COMP 40 A 3 2.22 1.92 1 20 A (E) DED RECEPT COMM CLTS 16

13 (E) UNLABELED 20 A 1 1.92 1.92 1 20 A (E) UNLABELED 14

11 (E) UNLABELED 20 A 1 1.92 2.88 1 30 A (E) UNLABELED 12

9 (E) CUBE 107A UNDER FLOOR 20 A 1 1.92 1.92 1 20 A (E) UNLABELED 10

7 (E) UNDER FLOOR 20 A 1 1.92 1.92 1 20 A (E) UNLABELED 8

5 (E) UNLABELED 20 A 1 1.92 1.92 1 20 A (E) UNLABELED 6

3 (E) UNLABELED 20 A 1 1.92 1.92 1 20 A (E) UNLABELED 4

1 (E) UNLABELED 20 A 1 1.92 1.92 1 20 A (E) UNLABELED 2

CKT CIRCUIT DESCRIPTION TRIP POLES A B C POLES TRIP CIRCUIT DESCRIPTION CKT

MOUNTING: Surface WIRES: 4 BUS RATING: 100 A

SUPPLY FROM: T-PPD (E) PHASES: 3 MAINS TYPE: MLO

LOCATION: BIODYNAMICS VERTICAL... VOLTS: 208Y/120V A.I.C. RATING: EXISTING

Branch Panel: PPD (E)

GENERAL NOTES

1. REFER TO SHEET E-001 FOR GENERAL NOTES, ABBREVIATIONS, AND SYMBOLS.

2. ALL NEW LOADS ARE SIGNIFIED BY DARKER TEXT IN THE PANEL SCHEDULES. ALL

EXISTING LOADS ARE GRAYED OUT.

TOTAL EST. DEMAND CURRENT 42 A

Water Pumps 11,520 VA 50.00% 5,760 VA TOTAL CONNECTED CURRENT: 53 A

(E) Non-Continuous 23,040 VA 100.00% 23,040 VA TOTAL ESTIMATED DEMAND: 35,262 VA

(E) Mechanical Equipment 7,680 VA 70.00% 5,376 VA TOTAL CONNECTED LOAD: 43,791 VA Mechanical Equipment 1,551 VA 70.00% 1,086 VA

LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS

NOTES: PROVIDE PROVISIONS FOR LOCKING IN THE OPEN POSITION FOR BREAKERS FEEDING TO REMOTELY LOCATED TRANSFORMERS.

LEGEND:

TOTAL AMPS: 56 A 52 A 51 A

TOTAL LOAD: 15,410 VA 14,302 VA 14,080 VA

31 SPACE -- 1 -- -- 1 -- SPACE 32

29 SPACE -- 1 -- -- 1 -- SPACE 30

27 SPACE -- 1 -- -- 1 -- SPACE 28

25 SPACE -- 1 -- -- 1 -- SPACE 26

23 SPACE -- 1 -- -- 1 -- SPACE 24

21 SPACE -- 1 -- -- 1 -- SPACE 22

19 SPACE -- 1 -- -- 1 -- SPACE 20

17 SPACE -- 1 -- -- 1 -- SPACE 18

15 SPACE -- 1 -- 0.22 1 20 A FCU-1-29-CP-A 16

13 SPACE -- 1 -- 1.33 1 20 A FCU-1-6,7,12,14,15-CP-A 14

11 -- -- -- 2.56 3.84 -- -- -- 12 9 -- -- -- 2.56 3.84 -- -- -- 10

7 (E) AIR COMPRESSOR 20 A 3 2.56 3.84 3 20 A (E) NON-CONTINUOUS 8

5 -- -- -- 3.84 3.84 -- -- -- 6 3 -- -- -- 3.84 3.84 -- -- -- 4

1 (E) BACK-FLOW PUMPS 30 A 3 3.84 3.84 3 20 A (E) NON-CONTINUOUS 2

CKT CIRCUIT DESCRIPTION TRIP POLES A B C POLES TRIP CIRCUIT DESCRIPTION CKT

MOUNTING: Surface WIRES: 4 BUS RATING: 400 A

SUPPLY FROM: PDC (E) PHASES: 3 MAINS TYPE: MCB

LOCATION: Room 302 VOLTS: 480Y/277V A.I.C. RATING: EXISTING

Branch Panel: PDPB (E)

TOTAL EST. DEMAND CURRENT 146 A

(E) Receptacle 60,416 VA 58.28% 35,208 VA TOTAL CONNECTED CURRENT: 214 A

(E) Lighting 10,560 VA 125.00% 13,200 VA TOTAL ESTIMATED DEMAND: 52,682 VA Receptacle 360 VA 100.00% 360 VA TOTAL CONNECTED LOAD: 76,928 VA Mechanical Equipment 5,592 VA 70.00% 3,914 VA

LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS

NOTES: PROVIDE PROVISIONS FOR LOCKING IN THE OPEN POSITION FOR BREAKERS FEEDING TO REMOTELY LOCATED TRANSFORMERS.

LEGEND:

TOTAL AMPS: 225 A 215 A 204 A