This is a technical specifications file containing detailed requirements for roof insulation, air barriers, rough carpentry, and other building materials for the construction of an Automated Record Fire Plus Range at Fort Campbell, Kentucky. The file includes specifications sections 06 10 00 (Rough Carpentry), 07 21 16 (Mineral Fiber Blanket Insulation), 07 22 00 (Roof Insulation & Underlayment), 07 27 10 (Building Air Barrier System), and 07 27 26 (Fluid-Applied Membrane Air Barriers).
The specifications detail material requirements including lumber grades, preservative treatments, insulation R-values, air barrier performance criteria, and installation methods. Key requirements include polyisocyanurate or polystyrene roof insulation, self-adhering modified asphalt underlayment, continuous air barrier systems, and mineral fiber blanket insulation. The carpentry section specifies lumber grades, fasteners, blocking, and installation requirements for framing and rough carpentry. Quality control requirements include inspection of air barrier installation, adhesion testing, moisture testing, and proper documentation of all testing and installation procedures. The work is being contracted through the US Army Corps of Engineers Louisville District for construction at Fort Campbell, Kentucky.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Solicitation For Automated Record Fire Plus Range Fort Campbell, Kentucky
P2: 506523
Design-Bid-Build
Specifications - Vol 2 of 2(Div 06 - 33) Certified Final Design
18 Decemeber 2024
W912QR25B0002
ARIMS: 200A
Disposition: Maintain for 15yrs after construction
W912QR25B0002_Specs_Vol2-0000
506523 Automated Record Fire Plus Range Fort Campbell, KY
*** SAFETY PAYS ***
Page i Certified Final
PROJECT TABLE OF CONTENTS
DIVISION SECTION AND TITLE ________________
DIVISION 00 – PROCUREMENT AND CONTRACTING REQUIREMENTS
00 10 00 PRICE BREAKOUT SCHEDULE
00 80 00.00 06 SPECIAL PROVISIONS
Construction Project Sign Details
Project Submittal Registry
TECHNICAL SPECIFICATIONS
DIVISION 01 – GENERAL REQUIREMENTS
01 11 00 SUMMARY OF WORK
01 32 01.00 06 PROJECT SCHEDULE
01 33 00 SUBMITTAL PROCEDURES
01 35 26.00 06 GOVERNMENT SAFETY REQUIREMENTS
01 42 00 SOURCES FOR REFERENCE PUBLICATIONS
01 45 00.15 10 RESIDENT MANAGEMENT SYSTEM CONTRACTOR MODE (RMS CM)
01 45 04.10 06 CONTRACTOR QUALITY CONTROL
Construction/Targetry Interface QA
01 45 35 SPECIAL INSPECTIONS
Statement/Schedule of Special Inspections
01 50 00 TEMPORARY CONSTRUCTION FACILITIES AND CONTROLS
01 57 19.00 06 TEMPORARY ENVIRONMENTAL CONTROLS AND PERMITS
Storm Water Pollution Prevention Plan (SWPPP) MEC Reconnaissance Letter Report
01 74 19 CONSTRUCTION WASTE MANAGEMENT AND DISPOSAL
01 78 23 OPERATION AND MAINTENANCE DATA
DIVISION 02 – EXISTING CONDITIONS
02 41 00 DEMOLITION
DIVISION 03 – CONCRETE
03 30 00 CAST-IN-PLACE CONCRETE
DIVISION 05 – METALS
05 12 00 STRUCTURAL STEEL
05 30 00 STEEL DECKS
*** SAFETY PAYS ***
Page ii Certified Final
05 40 00 COLD-FORMED METAL FRAMING
05 50 13 MISCELLANEOUS METAL FABRICATION
05 51 00 METAL STAIRS
DIVISION 06 – WOOD, PLASTIC AND COMPOSITES
06 10 00 ROUGH CARPENTRY
DIVISION 07 – THERMAL AND MOISTURE PROTECTION
07 21 16 MINERAL FIBER BLANKET INSULATION
07 22 00 ROOF INSULATION & UNDERLAYMENT
07 27 10 BUILDING AIR BARRIER SYSTEM
07 27 26 FLUID-APPLIED MEMBRANE AIR BARRIER
07 42 13 EXTERIOR METAL WALL PANELS
07 42 63 FABRICATED WALL PANEL ASSEMBLIES
07 60 00 FLASHING AND SHEET METAL
07 61 14.00 20 STEEL STANDING SEAM ROOFING
07 84 00 FIRESTOPPING
07 92 00 JOINT SEALANTS
DIVISION 08 – OPENINGS
08 11 13 STEEL DOORS AND FRAMES
08 51 13 ALUMINUM WINDOWS
08 71 00 DOOR HARDWARE
08 81 00 GLAZING
08 91 00 METAL WALL / DOOR LOUVERS
DIVISION 09 – FINISHES
09 22 00 SUPPORTS FOR PLASTER AND GYPSUM BOARD
09 29 00 GYPSUM BOARD
09 90 00 PAINTS AND COATINGS
DIVISION 10 – SPECIALTIES
10 14 00.10 EXTERIOR SIGNAGE
10 44 16 FIRE EXTINGUISHERS
DIVISION 13 – SPECIAL CONSTRUCTION
*** SAFETY PAYS ***
Page iii
13 34 19 METAL BUILDING SYSTEMS
DIVISION 23 – HEATING, VENTILATING AND AIR CONDITIONING (HVAC)
23 05 93 TESTING, ADJUSTING AND BALANCING FOR HVAC
23 07 00 THERMAL INSULATION FOR MECHANICAL SYSTEMS
23 30 00 HVAC AIR DISTRIBUTION
23 81 00 DECENTRALIZED UNITARY HVAC EQUIPMENT
DIVISION 26 – ELECTRICAL
26 05 73 POWER SYSTEM STUDIES
26 20 00 INTERIOR DISTRIBUTION SYSTEMS
26 41 00 LIGHTNING PROTECTION SYSTEM
26 51 00 INTERIOR LIGHTING
26 56 00 EXTERIOR LIGHTING
DIVISION 27 – COMMUNICATIONS
27 10 00 BUILDING TELECOMMUNICATIONS CABLING SYSTEM
27 51 16 PUBLIC ADDRESS SYSTEMS
DIVISION 31 – EARTHWORK
31 00 00.00 06 EARTHWORK
31 05 22.00 06 GEOTEXTILES USED AS FILTERS
31 11 00 CLEARING AND GRUBBING
DIVISION 32 – EXTERIOR IMPROVEMENTS
32 05 33 LANDSCAPE ESTABLISHMENT
32 15 00 AGGREGATE SURFACING
32 31 13 CHAIN LINK FENCES AND GATES
32 92 19 SEEDING
DIVISION 33 – UTILITIES
33 40 00 STORMWATER UTILITIES
33 71 02 UNDERGROUND ELECTRICAL DISTRIBUTION
33 82 00 TELECOMMUNICATIONS OUTSIDE PLAN (OSP)
-- End of Project Table of Contents --
506523 Automated Record Fire Range
SECTION TABLE OF CONTENTS
DIVISION 06 - WOOD, PLASTICS, AND COMPOSITES
SECTION 06 10 00
ROUGH CARPENTRY
08/16, CHG 2: 11/18
PART 1 GENERAL
1.1 REFERENCES
1.2 SUBMITTALS
1.3 DELIVERY AND STORAGE
1.4 GRADING AND MARKING
1.4.1 Lumber
1.4.2 Structural Glued Laminated Timber
1.4.3 Plywood
1.4.4 Structural-Use Panels
1.4.5 Preservative-Treated Lumber and Plywood
1.5 SIZES AND SURFACING
1.6 MOISTURE CONTENT
1.7 PRESERVATIVE TREATMENT
1.8 QUALITY ASSURANCE
1.8.1 Drawing Requirements
1.8.2 Data Required
PART 2 PRODUCTS
2.1 MATERIALS
2.1.1 Virgin Lumber
2.2 LUMBER
2.2.1 Framing Lumber
2.3 PLYWOOD
2.3.1 Wall Sheathing
2.3.1.1 Plywood
2.3.1.2 Structural-Use and OSB Panels
2.3.2 Roof Sheathing
2.3.2.1 Plywood
2.3.3 Other Uses
2.3.3.1 Plywood
2.4 UNDERLAYMENT
2.4.1 Plywood
2.5 OTHER MATERIALS
2.5.1 Building Paper
2.5.2 Trussed Rafters
2.5.3 Trussed Joists
2.5.4 Miscellaneous Wood Members
2.5.4.1 Nonstress Graded Members
2.5.4.2 Wood Bumpers
2.5.4.3 Sill Plates
2.5.4.4 Blocking
2.5.4.5 Rough Bucks and Frames
2.5.5 Adhesives
2.6 ROUGH HARDWARE
SECTION 06 10 00 Page 1
2.6.1 Bolts, Nuts, Studs, and Rivets
2.6.2 Anchor Bolts
2.6.3 Expansion Shields
2.6.4 Lag Screws and Lag Bolts
2.6.5 Wood Screws
2.6.6 Nails
2.6.7 Wire Nails
2.6.8 Clip Angles
2.6.9 Joist Hangers
2.6.10 Tie Straps
2.6.11 Joist Anchors
2.6.12 Door Buck Anchors
PART 3 EXECUTION
3.1 INSTALLATION
3.1.1 Sills
3.1.2 Beams and Girders
3.1.3 Roof Framing or Rafters
3.1.4 Joists
3.1.4.1 Floor (Ceiling) Framing
3.1.4.2 Doubled Joists
3.1.5 Subflooring
3.1.5.1 Wood
3.1.6 Columns and Posts
3.1.7 Wall Framing
3.1.7.1 Studs
3.1.7.2 Plates
3.1.8 Wall Sheathing
3.1.8.1 Plywood, Structural-Use Wall Sheathing
3.1.9 Wood Sheathing
3.1.10 Building Paper
3.1.11 Ceiling Joists
3.1.12 Plywood Roof Sheathing
3.1.13 Stair Framing
3.2 MISCELLANEOUS
3.2.1 Wood Roof Nailers, Edge Strips, Crickets, Curbs, and Cants
3.2.1.1 Roof Nailing Strips
3.2.1.2 Roof Edge Strips and Nailers
3.2.1.3 Crickets, Cants, and Curbs
3.2.2 Rough Wood Bucks
3.2.3 Wood Blocking
3.2.4 Wood Grounds
3.2.5 Wood Furring
3.2.6 Sill Plates
3.3 WASTE MANAGEMENT OF WOOD PRODUCTS
-- End of Section Table of Contents --
SECTION 06 10 00 Page 2
SECTION 06 10 00
ROUGH CARPENTRY
08/16, CHG 2: 11/18
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
AMERICAN INSTITUTE OF TIMBER CONSTRUCTION (AITC)
ANSI/AITC A190.1 (2007) American National Standard, Structural Glued Laminated Timber
AMERICAN LUMBER STANDARDS COMMITTEE (ALSC)
ALSC PS 20 (2015) American Softwood Lumber Standard
AMERICAN RAILWAY ENGINEERING AND MAINTENANCE-OF-WAY ASSOCIATION
(AREMA)
AREMA Eng Man (2017) Manual for Railway Engineering
AMERICAN SOCIETY OF MECHANICAL ENGINEERS (ASME)
ASME B18.2.1 (2012; Errata 2013) Square and Hex Bolts and Screws (Inch Series)
ASME B18.2.2 (2022) Nuts for General Applications:
Machine Screw Nuts, and Hex, Square, Hex Flange, and Coupling Nuts (Inch Series)
ASME B18.5.2.1M (2006; R 2011) Metric Round Head Short Square Neck Bolts
ASME B18.5.2.2M (1982; R 2010) Metric Round Head Square Neck Bolts
ASME B18.6.1 (2016) Wood Screws (Inch Series)
AMERICAN WOOD COUNCIL (AWC)
AWC NDS (2015) National Design Specification (NDS) for Wood Construction
AWC WFCM (2012) Wood Frame Construction Manual for One- and Two-Family Dwellings
AMERICAN WOOD PROTECTION ASSOCIATION (AWPA)
AWPA M2 (2019) Standard for the Inspection of Preservative Treated Wood Products for Industrial Use
SECTION 06 10 00 Page 3
AWPA M6 (2013) Brands Used on Preservative Treated Materials
APA - THE ENGINEERED WOOD ASSOCIATION (APA)
APA E30 (2016) Engineered Wood Construction Guide
APA E445 (2002) Performance Standards and Qualification Policy for Structural-Use Panels (APA PRP-108)
APA F405 (19) Product Guide: Performance Rated Panels
APA L870 (2010) Voluntary Product Standard, PS 1-09, Structural Plywood
APA S350 (2014) PS 2-10, Performance Standard for Wood-Based Structural-Use Panels
ASTM INTERNATIONAL (ASTM)
ASTM A153/A153M (2023) Standard Specification for Zinc Coating (Hot-Dip) on Iron and Steel Hardware
ASTM A307 (2021) Standard Specification for Carbon Steel Bolts, Studs, and Threaded Rod 60 000 PSI Tensile Strength
ASTM F547 (202) Standard Terminology of Nails for Use with Wood and Wood-Base Materials
ASTM F1667/F1667M (2021a) Standard Specification for Driven Fasteners: Nails, Spikes, and Staples
CALIFORNIA DEPARTMENT OF PUBLIC HEALTH (CDPH)
CDPH SECTION 01350 (2017; Version 1.2) Standard Method for the Testing and Evaluation of Volatile Organic Chemical Emissions from Indoor Sources using Environmental Chambers
FM GLOBAL (FM)
FM 4435 (2017) Roof Perimeter Flashing
INTERNATIONAL CODE COUNCIL (ICC)
ICC IBC (2021) International Building Code
NATIONAL HARDWOOD LUMBER ASSOCIATION (NHLA)
NHLA Rules (2015) Rules for the Measurement & Inspection of Hardwood & Cypress
SECTION 06 10 00 Page 4
NORTHEASTERN LUMBER MANUFACTURERS ASSOCIATION (NELMA)
NELMA Grading Rules (2013) Standard Grading Rules for Northeastern Lumber
REDWOOD INSPECTION SERVICE (RIS) OF THE CALIFORNIA REDWOOD
ASSOCIATION (CRA)
RIS Grade Use (1998) Redwood Lumber Grades and Uses
SOUTH COAST AIR QUALITY MANAGEMENT DISTRICT (SCAQMD)
SCAQMD Rule 1168 (2017) Adhesive and Sealant Applications
SOUTHERN CYPRESS MANUFACTURERS ASSOCIATION (SCMA)
SCMA Spec (1986; Supple. No. 1, Aug 1993) Standard Specifications for Grades of Southern Cypress
SOUTHERN PINE INSPECTION BUREAU (SPIB)
SPIB 1003 (2014) Standard Grading Rules for Southern Pine Lumber
TRUSS PLATE INSTITUTE (TPI)
TPI 1 (2014) National Design Standard for Metal Plate Connected Wood Truss Construction, Including Commentary and Appendices
TPI HIB (1991) Commentary and Recommendations for Handling, Installing and Bracing Metal Plate Connected Wood Trusses
U.S. GENERAL SERVICES ADMINISTRATION (GSA)
CID A-A-1923 (Rev A; Notice 1; Notice 2; Notice 3;
Notice 4) Shield, Expansion (Lag, Machine and Externally Threaded Wedge Bolt Anchors)
CID A-A-1924 (Rev A; Notice 3) Shield, Expansion (Self Drilling Tubular Expansion Shell Bolt Anchors
CID A-A-1925 (Rev A; Notice 1; Notice 2; Notice 3;
Notice 4) Shield Expansion (Nail Anchors)
FS UU-B-790 (Rev A; Notice 2) Building Paper Vegetable Fiber: (Kraft, Waterproofed, Water Repellent and Fire Resistant)
WEST COAST LUMBER INSPECTION BUREAU (WCLIB)
WCLIB 17 (2015) Standard Grading Rules
WESTERN WOOD PRODUCTS ASSOCIATION (WWPA)
WWPA G-5 (2017) Western Lumber Grading Rules
SECTION 06 10 00 Page 5
1.2 SUBMITTALS
Government approval is required for submittals with a "G" or "S" classification. Submittals not having a "G" or "S" classification are for information only. When used, a code following the "G" classification identifies the office that will review the submittal for the Government.
Submit the following in accordance with Section 01 33 00 SUBMITTAL
PROCEDURES:
SD-02 Shop Drawings
Fabricated Structural Members; G , DO
Nailers and Nailing Strips; G , RO
Drawings of field erection details, including materials and methods of fastening nailers in conformance with Factory Mutual wind uplift rated systems specified in other Sections of these specifications.
SD-05 Design Data
Modifications of Structural Members; G , DO
Design analysis and calculations showing design criteria used to accomplish the applicable analysis.
SD-06 Test Reports
Preservative-treated Lumber and Plywood
SD-07 Certificates
Certificates of Grade SD-10 Operation and Maintenance Data
Take-back Program
Include contact information, summary of procedures, and the limitations and conditions applicable to the project. Indicate manufacturer's commitment to reclaim materials for recycling or reuse.
1.3 DELIVERY AND STORAGE
Deliver materials to the site in an undamaged condition. Store, protect, handle, and install prefabricated structural elements in accordance with manufacturer's instructions and as specified. Store materials off the ground to provide proper ventilation, with drainage to avoid standing water, and protection against ground moisture and dampness. Store materials with a moisture barrier at both the ground level and as a cover
SECTION 06 10 00 Page 6 forming a well ventilated enclosure. Store wood I-beams and glue-laminated beams and joists on edge. Adhere to requirements for stacking, lifting, bracing, cutting, notching, and special fastening requirements. Do not use materials that have visible moisture or biological growth. Remove defective and damaged materials and provide new materials. Store separated reusable wood waste convenient to cutting station and area of work.
1.4 GRADING AND MARKING
1.4.1 Lumber
Mark each piece of framing and board lumber or each bundle of small pieces of lumber with the grade mark of a recognized association or independent inspection agency. Such association or agency must be certified by the Board of Review, American Lumber Standards Committee, to grade the species used. Surfaces that are to be exposed to view must not bear grademarks, stamps, or any type of identifying mark. Hammer marking will be permitted on timbers when all surfaces will be exposed to view.
1.4.2 Structural Glued Laminated Timber
Mark each member with the mark of a recognized association or independent inspection agency that maintains continuing control over the quality of structural glued laminated timber products. The marking must indicate compliance with ANSI/AITC A190.1 and must include all identification information required by ANSI/AITC A190.1 . Structurally end-jointed lumber must also be certified and grade marked in accordance with ANSI/AITC A190.1 .
1.4.3 Plywood
Mark each sheet with the mark of a recognized association or independent inspection agency that maintains continuing control over the quality of the plywood. The mark must identify the plywood by species group or span rating, exposure durability classification, grade, and compliance with APA L870 . Surfaces that are to be exposed to view must not bear grademarks or other types of identifying marks.
1.4.4 Structural-Use Panels
Mark each panel with the mark of a recognized association or independent inspection agency that maintains continuing control over the quality of the panel. The mark must indicate end use, span rating, and exposure durability classification. Oriented Strand Board (OSB), APA F405 .
1.4.5 Preservative-Treated Lumber and Plywood
The Contractor is responsible for the quality of treated wood products.
Each treated piece must be inspected in accordance with AWPA M2 and permanently marked or branded, by the producer, in accordance with AWPA M6.
The Contractor must provide Contracting Officer's Representative (COR) with the inspection report of an approved independent inspection agency that offered products comply with applicable AWPA Standards. The appropriate Quality Mark on each piece will be accepted, in lieu of inspection reports, as evidence of compliance with applicable AWPA treatment standards.
SECTION 06 10 00 Page 7
1.5 SIZES AND SURFACING
ALSC PS 20 for dressed sizes of yard and structural lumber. Lumber must be surfaced four sides. Size references, unless otherwise specified, are nominal sizes, and actual sizes must be within manufacturing tolerances allowed by the standard under which the product is produced. Other measurements are IP or SI standard.
1.6 MOISTURE CONTENT
Air-dry or kiln-dry lumber. Kiln-dry treated lumber after treatment.
Maximum moisture content of wood products must be as follows at the time of delivery to the job site:
a. Framing lumber and board, 19 percent maximum
1.7 PRESERVATIVE TREATMENT
a. 0.25 pcf intended for above ground use.
b. 0.40 pcf intended for ground contact and fresh water use. 0.60 pcf intended for Ammoniacal Copper Quaternary Compound (ACQ)-treated foundations. 0.80 to 1.00 pcf intended for ACQ-treated pilings. All wood must be air or kiln dried after treatment. Specific treatments must be verified by the report of an approved independent inspection agency, or the AWPA Quality Mark on each piece. Do not incise surfaces of lumber that will be exposed. Brush coat areas that are cut or drilled after treatment with either the same preservative used in the treatment or with a 2 percent copper naphthenate solution.
Plastic lumber must not be preservative treated. The following items must be preservative treated:
(1) Wood framing, woodwork, and plywood up to and including the subflooring at the first-floor level of structures having crawl spaces when the bottoms of such items are 24 inches or less from the earth underneath.
(2) Exterior wood steps, platforms, and railings; and all wood framing of open, roofed structures.
(3) Wood sills, soles, plates, furring, and sleepers that are less than 24 inches from the ground, furring and nailers that are set into or in contact with concrete or masonry.
(4) Nailers, edge strips, crickets, curbs, and cants for roof decks.
1.8 QUALITY ASSURANCE
1.8.1 Drawing Requirements
For fabricated structural members, trusses, qlu-lam members, indicate materials, details of construction, methods of fastening, and erection details. Include reference to design criteria used and manufacturers design calculations. Submit drawings for all proposed modifications of structural members. Do not proceed with modifications until the submittal
SECTION 06 10 00 Page 8 has been approved.
1.8.2 Data Required
Submit calculations and drawings for all proposed modifications of structural members. Do not proceed with modifications until the submittal has been approved.
PART 2 PRODUCTS
2.1 MATERIALS
2.1.1 Virgin Lumber
Lumber fabricated from old growth timber is not permitted. Avoid companies who buy, sell, or use old growth timber in their operations, when possible.
2.2 LUMBER
2.2.1 Framing Lumber
Framing lumber such as studs, plates, caps, collar beams, cant strips, bucks, sleepers, nailing strips, and nailers and board lumber such as subflooring and wall and roof sheathing must be one of the species listed in the table below. Minimum grade of species must be as listed.
SECTION 06 10 00 Page 9
Table of Grades for Framing and Board Lumber
Grading Rules Species Framing Board Lumber
WWPA G-5 standard grading rules
Aspen, Douglas Fir-Larch, Douglas Fir South, Engel mann Spruce-Lodgepole Pine, Engelm ann Spruce, Hem-Fir, Idaho White Pine, Lodgepole Pi ne, Mountain Hemlock, Mountain Hemlock-Hem-Fir, Ponderosa Pine-Sugar Pine, Ponderosa Pine-Lodgepole Pine, Subalpine Fir , White Woods, Western Woods, Western Cedars, Weste rn Hemlock
All Species:
Standard Light Framing or No. 3 Structural Light Framing (Stud Grade f or 2x4 nominal size, 10 feet and shorter)
All Species:
No. 3 Common
WCLIB 17 standard grading rules
Douglas Fir-Larch, Hem-Fir, Mountain Hemlock, Sitka Spruce, Western Cedars, Western Hemlock
All Species:
Standard Light Framing or No. 3 Stru ctural Light Framing (Stud Grade for 2x4 nominal si ze, 10 feet and shorter)
All Species:
Standard
SECTION 06 10 00 Page 10
Table of Grades for Framing and Board Lumber
Grading Rules Species Framing Board Lumber
SPIB 1003 standard grading rules
Southern Pine All Species:
Standard Light Framing or No. 3 Structural Light Framing (Stud Grade f or 2x4 nominal size, 10 feet and shorter)
No. 2 Boards
SCMA Spec standard specifications
Cypress No. 2 Common No. 2 Common
NELMA Grading Rules standard grad ing rules
Balsam Fir, Eastern Hemlock-Tamar ack, Eastern Spruce, Eastern White Pine, Northern P ine, Northern Pine-Cedar
All Species:
St andard Light Framing or No. 3 Structural Light Framing (Stud Grade for 2x4 nominal size, 10 feet and s horter)
All Species:
No. 3 Common except Standard for Eastern White and Northern Pine
RIS Grade Use st andard specifications
Redwood All Species:
St andard Light Framing or No. 3 Structural Light Framing (Stud Grade for 2x4 nominal size, 10 feet and s horter)
Construction Heart
SECTION 06 10 00 Page 11
Table of Grades for Framing and Board Lumber
Grading Rules Species Framing Board Lumber
NHLA Rules rules for the measurement and inspectio n of hardwood and cypress lumber
Cypress No. 2 Dimension No. 2 Common
2.3 PLYWOOD
APA L870 , APA S350 , APA E445 , and APA F405 respectively.
2.3.1 Wall Sheathing
2.3.1.1 Plywood
C-D Grade, Exposure 1, and a minimum thickness of 1/2 inch, except where indicated to have greater thickness. Provide exterior grade material with phenol resin for exterior applications.
2.3.1.2 Structural-Use and OSB Panels
Sheathing grade with durability equivalent to Exposure 1, Span Rating of 16/0 24/0 or greater.
2.3.2 Roof Sheathing
2.3.2.1 Plywood
C-D Grade, Exposure 1, with an Identification Index of not less than 24/0 .
Provide certified sustainably harvested plywood roof sheathing. Provide exterior grade material with phenol resin for all applications.
2.3.3 Other Uses
2.3.3.1 Plywood
Plywood for communications systems backboards shall be FSC-certified. C-D Grade, Exposure 1.
2.4 UNDERLAYMENT
Underlayment must conform to one of the following:
2.4.1 Plywood
Plywood must conform to APA L870 , underlayment grade with exterior glue, or C-C (Plugged) exterior grade 11/32 inch thick, 4 feet wide.
SECTION 06 10 00 Page 12
2.5 OTHER MATERIALS
2.5.1 Building Paper
FS UU-B-790 , Type I, Grade D, Style 1.
2.5.2 Trussed Rafters
Metal plate connected trusses designed in accordance with TPI 1 and TPI HIB and fabricated in accordance with TPI 1 .
2.5.3 Trussed Joists
Metal plate connected parallel chord wood trusses designed and fabricated in accordance with TPI 1 .
2.5.4 Miscellaneous Wood Members
2.5.4.1 Nonstress Graded Members
Members must include bridging, corner bracing, furring, grounds, and nailing strips. Members must be in accordance with TABLE I for the species used. Sizes must be as follows unless otherwise shown:
Member Size inch
Bridging 1 x 3 or 1 x 4 for use between members 2 x 12 and smaller; 2 x 4 for use between members larger than 2 x 12.
Corner bracing 1 x 4.
Furring 1 x
Grounds Plaster thickness by 38.
Nailing strips 1 x 3 or 1 x 4 when used as shingle base or interior finish, otherwise 2 inch stock.
2.5.4.2 Wood Bumpers
AREMA Eng Man, Industrial grade cross ties
2.5.4.3 Sill Plates
Sill plates must be standard or number 2 grade.
2.5.4.4 Blocking
Blocking must be standard or number 2 grade.
SECTION 06 10 00 Page 13
2.5.4.5 Rough Bucks and Frames
Rough bucks and frames must be straight standard or number 2 grade.
2.5.5 Adhesives
Comply with applicable regulations regarding toxic and hazardous materials and as specified. Provide non-aerosol adhesive products used on the interior of the building (defined as inside of the weatherproofing system) meeting either emissions requirements of CDPH SECTION 01350 (limit requirements for either office or classroom spaces regardless of space type) or VOC content requirements of SCAQMD Rule 1168 . Provide certification or validation of indoor air quality for aerosol adhesives used on the interior of the building (inside of the weatherproofing system).
2.6 ROUGH HARDWARE
Unless otherwise indicated or specified, rough hardware must be of the type and size necessary for the project requirements. Sizes, types, and spacing of fastenings of manufactured building materials must be as recommended by the product manufacturer unless otherwise indicated or specified. Rough hardware exposed to the weather or embedded in or in contact with preservative treated wood, exterior masonry, or concrete walls or slabs must be hot-dip zinc-coated in accordance with ASTM A153/A153M . Nails and fastenings for fire-retardant treated lumber and woodwork exposed to the weather must be copper alloy or hot-dipped galvanized fasteners as recommended by the treated wood manufacturer.
2.6.1 Bolts, Nuts, Studs, and Rivets
ASME B18.2.1 , ASME B18.5.2.1M , ASME B18.5.2.2M and ASME B18.2.2 .
2.6.2 Anchor Bolts
ASTM A307, size as indicated, complete with nuts and washers.
2.6.3 Expansion Shields
CID A-A-1923 , CID A-A-1924 , and CID A-A-1925 . Except as shown otherwise, maximum size of devices must be 3/8 inch.
2.6.4 Lag Screws and Lag Bolts
ASME B18.2.1 .
2.6.5 Wood Screws
ASME B18.6.1 .
2.6.6 Nails
ASTM F547, size and type best suited for purpose. For sheathing and subflooring, length of nails must be sufficient to extend 1 inch into supports. In general, 8-penny or larger nails must be used for nailing through 1 inch thick lumber and for toe nailing 2 inch thick lumber;
16-penny or larger nails must be used for nailing through 2 inch thick lumber. Nails used with treated lumber and sheathing must be hot-dipped galvanized in accordance with ASTM A153/A153M . Nailing must be in
SECTION 06 10 00 Page 14 accordance with the recommended nailing schedule contained in AWC WFCM.
Where detailed nailing requirements are not specified, nail size and spacing must be sufficient to develop an adequate strength for the connection. The connection's strength must be verified against the nail capacity tables in AWC NDS. Reasonable judgment backed by experience must ensure that the designed connection will not cause the wood to split. If a load situation exceeds a reasonable limit for nails, a specialized connector must be used.
2.6.7 Wire Nails
ASTM F1667/F1667M .
2.6.8 Clip Angles
Steel, 3/16 inch thick, size as indicatedor best suited for intended use;
or zinc-coated steel or iron commercial clips designed for connecting wood members.
2.6.9 Joist Hangers
Steel or iron, zinc coated, sized to fit the supported member, of sufficient strength to develop the full strength of the supported member in accordance with ICC IBC , and furnished complete with any special nails required.
2.6.10 Tie Straps
For joists supported by the lower flange of steel beams, provide 1/8 by 1-1/2 inch steel strap, 2 feet long , except as indicated otherwise.
2.6.11 Joist Anchors
For joists supported by masonry walls, provide anchors 3/16 by 1 1/2 inch steel tee or strap, bent and of length to provide 4 inches embedment into wall and 12 inches along joist except as indicated otherwise. For joists parallel to masonry or concrete walls, provide anchors 1/4 by 1-1/4 inch minimum cross-sectional area, steel strap, length as necessary to extend over top of first three joists and into wall 4 inches, and with wall end of bend or pin type , except as indicated otherwise.
2.6.12 Door Buck Anchors
Metal anchors, 1/8 by 1-1/4 inch steel, 12 inches long, with ends bent 2 inches , except as indicated otherwise. Anchors must be screwed to the backs of bucks and built into masonry or concrete. Locate 8 inches above sills and below heads and not more than 24 inches intermediately between.
Anchorage of bucks to steel framing must be as necessary to suit the conditions.
PART 3 EXECUTION
3.1 INSTALLATION
Do not install building construction materials that show visual evidence of biological growth.
Conform to AWC WFCM unless otherwise indicated or specified. Select lumber sizes to minimize waste. Fit framing lumber and other rough
SECTION 06 10 00 Page 15 carpentry, set accurately to the required lines and levels, and secure in place in a rigid manner. Do not splice framing members between bearing points. Set joists, rafters, and purlins with their crown edge up. Frame members for the passage of pipes, conduits, and ducts. Do not cut or bore structural members for the passage of ducts or pipes without approval.
Reinforce all members damaged by such cutting or boring by means of specially formed and approved sheet metal or bar steel shapes, or remove and provide new, as approved. Provide as necessary for the proper completion of the work all framing members not indicated or specified.
Spiking and nailing not indicated or specified otherwise must be in accordance with the Nailing Schedule contained in ICC IBC ; perform bolting in an approved manner. Spikes, nails, and bolts must be drawn up tight.
3.1.1 Sills
Set sills level and square and wedge with steel or slate shims; point or grout with non-shrinking cement mortar to provide continuous and solid bearing. Anchor sills to the foundations as indicated. Provide bolts with plate washers and nuts. Bolts in exterior walls must be zinc-coated.
3.1.2 Beams and Girders
Set beams and girders level and in alignment and anchor to bearing walls, piers, or supports with U-shaped steel strap anchors. Embed anchors in concrete or masonry at each bearing and through-bolt to the beams or girders with not less than two bolts. Provide bolts not less than 1/2 inch in diameter and with plate washers under heads and nuts. Install beams and girders not indicated otherwise with 8 inch minimum end bearing on walls or supports. Install beams and girders into walls with 1/2 inch clearance at the top, end, and sides or standard steel wall-bearing boxes.
Provide joints and splices over bearings only and bolt or spike together.
3.1.3 Roof Framing or Rafters
Tops of supports or rafters must form a true plane. Ridge, and hip members must be of depth equal to cut on rafters where practicable, but in no case less than depth of rafters and nominally 2 inches thick. Rafters must have full and solid bearing on plates. Hips and ridges must be straight and true intersections of roof planes. Necessary crickets and watersheds must be formed. Rafters, except hip and valley rafters, must be spiked to wall plate and to ceiling joists with no less than three 8-penny nails or bolted by angles unless otherwise indicated. Rafters must be toe-nailed to ridge, or hip members with at least three 8-penny nails. Rafters must be braced to prevent movement until permanent bracing, decking or sheathing is installed. Hip rafters must be secured to wall plates by clip angles. Openings in roof must be framed with headers and trimmers. Unless otherwise indicated, headers carrying more than two rafters and trimmers supporting headers carrying more than one rafter must be double. Hip rafters longer than the available lumber must be butt jointed and scabbed. Install trussed rafters in accordance with
TPI HIB .
3.1.4 Joists
Provide joists of the sizes and spacing indicated, accurately and in alignment, and of uniform width. Joists must have full bearing on sills, plates, beams, girders, and trusses; provide laps over bearing only and spike. Where joists are of insufficient length to produce a 12 inch lap, butt joists over bearing and provide wood scabs 2 nominal inches thick by
SECTION 06 10 00 Page 16 depth of joists by 24 inches long or metal straps 1/4 by 1 1/2 inch by not less than 18 inches long nailed to each joist with not less than four 10-penny nails, or approved sheet metal connectors installed in accordance with the manufacturer's recommendations. Provide metal hangers for joists framing into the side of headers, beams, or girders.The minimum joist end bearing must be 4 inches, and joists built into concrete or masonry must have a 1/2 inch minimum clearance at the top, end, and sides. For joists approved to be bored for the passage of pipes or conduits, bore through the neutral axis of the joist. Provide steel joist hangers of proper size and type to receive the ends of all framed joists unless otherwise indicated.
3.1.4.1 Floor (Ceiling) Framing
Except where otherwise indicated joists must have bearings not less than 4 inches on concrete or masonry and 1-1/2 inches on wood or metal. Joists, trimmers, headers, and beams framing into carrying members at the same relative levels must be carried on joist hangers. Joists must be lapped and spiked together at bearings or butted end-to-end with scab ties at joint and spiked to plates. Openings in floors must be framed with headers and trimmers. Headers carrying more than two tail joists and trimmers supporting headers carrying more than one tail joist must be doubled, unless otherwise indicated. Joists built into masonry must be provided with a beveled fire cut so that the top of the joist does not enter the wall more than 1 inch or standard steel wall bearing boxes.
Install engineered wood joists in accordance with distributor's instructions.
3.1.4.2 Doubled Joists
Provide under bearing walls and partitions running parallel with the floor joists, around stairways, and at other openings where joists are cut and framed. Double, space for clearance, block apart 4 feet on center, rigidly frame, and spike together joists under partitions that are to receive ducts, pipes, and conduits.
3.1.5 Subflooring
3.1.5.1 Wood
Subflooring must be applied diagonally with end joints made over supports. Each board must bear on at least three supports and must be nailed at each support using two nails for boards 6 inches and less in width and three nails for boards more than 6 inches in width.
3.1.6 Columns and Posts
Set columns and posts, plumb, in alignment, and with full and uniform bearing. Do not embed the bottom and bearing surfaces of posts columns in concrete or set in direct contact with concrete slabs on grade.
3.1.7 Wall Framing
3.1.7.1 Studs
Select studs for straightness and set plumb, true, and in alignment. In walls and partitions more than 8 feet tall, provide horizontal bridging at not more than 8 feet o.c. using nominal 2 inch material of the same width as the studs; install the bridging flat. Sizes and spacing of studs must
SECTION 06 10 00 Page 17 be as indicated. Double studs at jambs and heads of openings and triple at corners to form corner posts. Frame corner posts to receive sheathing, lath, and interior finish. Truss over openings exceeding 4 feet in width or use a header of sufficient depth. Toe-nail studs to sills or sole plates with four 8-penny nails or fasten with metal nailing clips or connectors. Anchor studs abutting concrete or masonry walls thereto near the top and bottom and at midheight of each story using expansion bolts or powder-actuated drive studs.
3.1.7.2 Plates
Use plates for walls and partitions of the same width as the studs to form continuous horizontal ties. Splice single plates; stagger the ends of double plates. Double top plates in walls and bearing partitions, built up of two nominal 2 inch thick members. Top plates for nonbearing partitions must be single or double plates of the same size as the studs.
Nail lower members of double top plates and single top plates to each stud and corner post with two 16-penny nails. Nail the upper members of double plates to the lower members with 10-penny nails, two near each end, and stagger 16 inches o.c. intermediately between. Nail sole plates on wood construction through the subfloor to each joist and header; stagger nails. Anchor sole plates on concrete with expansion bolts, one near each end and at not more than 6 feet o.c., or with powder-actuated fasteners, one near each end and at not more than 3 feet o.c. Provide plates cut for the passage of pipes or ducts with a steel angle as a tie for the plate and bearing for joist.
3.1.8 Wall Sheathing
3.1.8.1 Plywood, Structural-Use Wall Sheathing
Apply horizontally or vertically. Extend sheathing over and nail to sill and top plate. Abut sheathing edges over centerlines of supports. Allow 1/8 inch spacing between panels and 1/8 inch at windows and doors. If sheathing is applied horizontally, stagger vertical end joints. Nail panels with 6-penny nails spaced 6 inches o.c. along edges of the panel and 12 inches o.c. over intermediate supports. Keep nails 3/8 inches away from panel ledges. Provide 2 by 4 blocking for horizontal edges not otherwise supported.
3.1.9 Wood Sheathing
Sheathing end joints must be made over framing members and so alternated that there will be at least two boards between joints on the same support. Each board must bear on at least three supports. Boards must be nailed at each support using two nails for boards 6 inches and less in width and three nails for boards more than 6 inches in width. Roof sheathing must not be installed where roof decking is installed.
3.1.10 Building Paper
Provide building paper where indicated. Apply paper shingle fashion, horizontally, beginning at the bottom of the wall. Lap edges 4 inches, and nail with one inch, zinc-coated roofing nails, spaced 12 inches o.c.
and driven through tin discs.
3.1.11 Ceiling Joists
Size as indicated and set accurately and in alignment. Toe-nail joists to
SECTION 06 10 00 Page 18 all plates with not less than three 10-penny nails. Frame openings in ceilings with headers and trimmers.
3.1.12 Plywood Roof Sheathing
Install with the grain of the outer plies or long dimension at right angles to supports. Stagger end joints and locate over the centerlines of supports. Allow 1/8 inch spacing at panel ends and 1/4 inch at panel edges. Nail panels with 8-penny common nails or 6-penny annular rings or screw-type nails spaced 6 inches o.c. at supported edges and 12 inches o.c. at intermediate bearings. Do not use staples in roof sheathing.
Where the support spacing exceeds the maximum span for an unsupported edge, provide adequate blocking, tongue-and-groove edges, or panel edge clips, in accordance with APA E30 .
3.1.13 Stair Framing
Cut carriages to exact shape required to receive treads and risers, with risers of uniform height and treads of uniform width. Provide trimmers, nailers, and blocking as required to support finish materials.
3.2 MISCELLANEOUS
3.2.1 Wood Roof Nailers, Edge Strips, Crickets, Curbs, and Cants
Provide sizes and configurations indicated or specified and anchored securely to continuous construction.
3.2.1.1 Roof Nailing Strips
Provide roof nailing strips for roof decks as indicated and specified herein. Apply nailing strips in straight parallel rows in the direction and spacing indicated. Strips must be surface applied.
a. Surface-Applied Nailers: Must be 3 inches wide and of thickness to finish flush with the top of the insulation. Anchor strips securely to the roof deck with powder actuated fastening devices or expansion shields and bolts, spaced not more than 24 inches o.c. On decks with slopes of one inch or more, provide surface applied wood nailers for securing insulation.
b. Embedded Nailers: Must be nominal 2 by 3 with 2 inch sides beveled.
Set and anchor nailers to finish flush with the roof deck surface.
3.2.1.2 Roof Edge Strips and Nailers
Provide at perimeter of roof, around openings through roof, and where roofs abut walls, curbs, and other vertical surfaces. Except where indicated otherwise, nailers must be 6 inches wide and the same thickness as the insulation. Anchor nailers securely to underlying construction.
Anchor perimeter nailers in accordance with FM 4435 .
3.2.1.3 Crickets, Cants, and Curbs
Provide wood saddles or crickets, cant strips, curbs for scuttles and ventilators, and wood nailers bolted to tops of concrete or masonry curbs and at expansion joints, as indicated, specified, or necessary .
SECTION 06 10 00 Page 19
3.2.2 Rough Wood Bucks
2 inch nominal thickness. Set wood bucks true and plumb. Anchor bucks to concrete or masonry with steel straps extending into the wall 8 inches minimum. Place anchors near the top and bottom of the buck and space uniformly at 2 foot maximum intervals.
3.2.3 Wood Blocking
Provide proper sizes and shapes at proper locations for the installation and attachment of wood and other finish materials, fixtures, equipment, and items indicated or specified.
3.2.4 Wood Grounds
Provide for fastening wood trim, finish materials, and other items to plastered walls and ceilings. Install grounds in proper alignment and true with an 8 foot straightedge.
3.2.5 Wood Furring
Provide where shown and as necessary for facing materials specified.
Except as shown otherwise, furring strips must be nominal one by 3, continuous, and spaced 16 inches o.c. Erect furring vertically or horizontally as necessary. Nail furring strips to masonry. Do not use wood plugs. Provide furring strips around openings, behind bases, and at angles and corners. Furring must be plumb, rigid, and level and must be shimmed as necessary to provide a true, even plane with surfaces suitable to receive the finish required.
3.2.6 Sill Plates
Sill plates must be set level and square and anchor bolted at not more than 6 feet on centers and not more than 12 inches from end of each piece. A minimum of two anchors must be used for each piece.
3.3 WASTE MANAGEMENT OF WOOD PRODUCTS
In accordance with the Waste Management Plan and as specified. Separate and reuse scrap sheet materials larger than 2 square feet, framing members larger than 16 inches, and multiple offcuts of any size larger than 12 inches. Clearly separate damaged wood and other scrap lumber for acceptable alternative uses on site, including bracing, blocking, cripples, ties, and shims.
Coordinate with manufacturer for take-back program and submit manufacturer's policy statement on program. Fold up metal banding, flatten, and recycle.
Separate treated, stained, painted, and contaminated wood and place in designated area for hazardous materials. Dispose of according to local regulations.Do not burn scrap lumber that has been pressure treated, or lumber that is less than one year old.
-- End of Section --
SECTION 06 10 00 Page 20
SECTION TABLE OF CONTENTS
DIVISION 07 - THERMAL AND MOISTURE PROTECTION
SECTION 07 21 16
MINERAL FIBER BLANKET INSULATION
08/23
PART 1 GENERAL
1.1 REFERENCES
1.2 SUBMITTALS
1.3 CERTIFICATIONS
1.3.1 Insulation Products
1.3.2 Adhesives and Sealants
1.4 DELIVERY, STORAGE, AND HANDLING
1.4.1 Delivery
1.4.2 Storage
1.5 SAFETY PRECAUTIONS
1.5.1 Respirators
1.5.2 Other Safety Concerns
PART 2 PRODUCTS
2.1 BLANKET INSULATION
2.1.1 Recycled Materials
2.1.2 Energy Star
2.1.3 Prohibited Materials
2.2 BLOCKING
2.3 ACCESSORIES
2.3.1 Adhesive
2.3.2 Mechanical Fasteners
2.3.3 Wire Mesh
PART 3 EXECUTION
3.1 EXISTING CONDITIONS
3.2 PREPARATION
3.2.1 Blocking Around Heat Producing Devices
3.3 INSTALLATION
3.3.1 Insulation
3.3.1.1 Electrical wiring
3.3.1.2 Continuity of Insulation
3.3.1.3 Installation at Bridging and Cross Bracing
3.3.1.4 Cold Climate Requirement
3.3.1.5 Insulation without Affixed Vapor Retarder
3.3.1.6 Sizing of Blankets
3.3.1.7 Special Requirements for Floors
3.3.1.8 Access Panels and Doors
3.3.2 Installation of Separate Vapor Retarder
-- End of Section Table of Contents --
SECTION 07 21 16 Page 1
SECTION 07 21 16
MINERAL FIBER BLANKET INSULATION
08/23
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
ASTM INTERNATIONAL (ASTM)
ASTM C665 (2023) Standard Specification for Mineral-Fiber Blanket Thermal Insulation for Light Frame Construction and Manufactured Housing
ASTM C930 (2019) Standard Classification of Potential Health and Safety Concerns Associated with Thermal Insulation Materials and Accessories
ASTM D5359 (1998; R 2021) Standard Specification for Glass Cullet Recovered from Waste for Use in Manufacture of Glass Fiber
ASTM E84 (2023) Standard Test Method for Surface Burning Characteristics of Building Materials
ASTM E136 (2024a) Standard Test Method for Assessing Combustibility of Materials Using a Vertical Tube Furnace at 750 Degrees C
CALIFORNIA DEPARTMENT OF PUBLIC HEALTH (CDPH)
CDPH SECTION 01350 (2017; Version 1.2) Standard Method for the Testing and Evaluation of Volatile Organic Chemical Emissions from Indoor Sources using Environmental Chambers
GREEN SEAL (GS)
GS-36 (2013) Adhesives for Commercial Use
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 70 (2023; ERTA 7 2023; TIA 23-15) National Electrical Code
SCIENTIFIC CERTIFICATION SYSTEMS (SCS)
SCS SCS Global Services (SCS) Indoor Advantage
SECTION 07 21 16 Page 2
SOUTH COAST AIR QUALITY MANAGEMENT DISTRICT (SCAQMD)
SCAQMD Rule 1168 (2017) Adhesive and Sealant Applications
U.S. DEPARTMENT OF ENERGY (DOE)
Energy Star (1992; R 2006) Energy Star Energy Efficiency Labeling System (FEMP)
U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)
29 CFR 1910.134 Respiratory Protection
UNDERWRITERS LABORATORIES (UL)
UL 2818 (2022) GREENGUARD Certification Program For Chemical Emissions For Building Materials, Finishes And Furnishings
1.2 SUBMITTALS
Government approval is required for submittals with a "G" or "S" classification. Submittals not having a "G" or "S" classification are for information only. When used, a code following the "G" classification identifies the office that will review the submittal for the Government.
Submit the following in accordance with Section 01 33 00 SUBMITTAL
PROCEDURES:
SD-03 Product Data
Blanket Insulation; G
Recycled Content for Insulation Materials; S
Energy Star Label for Insulation Materials; S
Sill Sealer Insulation
Accessories
SD-07 Certificates
Indoor Air Quality for Adhesives; S
SD-08 Manufacturer's Instructions
Insulation
1.3 CERTIFICATIONS
Submit required indoor air quality certifications and validations in one submittal package.
1.3.1 Insulation Products
Provide product certified to meet indoor air quality requirements by UL 2818 (Greenguard) Gold, SCS Global Services Indoor Advantage Gold or provide certification by other third-party programs. Provide current
SECTION 07 21 16 Page 3 product certification from certification body.
1.3.2 Adhesives and Sealants
Provide products certified to meet indoor air quality requirements by UL 2818 (Greenguard) Gold, SCS Global Services Indoor Advantage Gold or provide certification or validation by other third-party programs that products meet the requirements of this Section. Provide current product certification documentation from certification body. When product does not have certification, provide validation that product meets the indoor air quality product requirements cited herein.
1.4 DELIVERY, STORAGE, AND HANDLING
1.4.1 Delivery
Deliver materials to site in original sealed wrapping bearing manufacturer's name and brand designation, specification number, type, grade, R-value, and class. Store and handle to protect from damage. Do not allow insulation materials to become wet, soiled, crushed, or covered with ice or snow. Comply with manufacturer's recommendations for handling, storing, and protecting of materials before and during installation.
1.4.2 Storage
Inspect materials delivered to the site for damage; unload and store out of weather in manufacturer's original packaging. Store only in dry locations, not subject to open flames or sparks, and easily accessible for inspection and handling.
1.5 SAFETY PRECAUTIONS
1.5.1 Respirators
Provide installers with dust/mist respirators, training in their use, and protective clothing, all approved by National Institute for Occupational Safety and Health (NIOSH)/Mine Safety and Health Administration (MSHA) in accordance with 29 CFR 1910.134 .
1.5.2 Other Safety Concerns
Consider other safety concerns and measures as outlined in ASTM C930.
PART 2 PRODUCTS
2.1 BLANKET INSULATION
ASTM C665, Type I, blankets without membrane coverings; Class A, membrane-faced surface with a flame spread of 25 or less, except a flame spread rating of 25 or less and a smoke developed rating of 150 or less when tested in accordance with ASTM E84.
Provide insulation with R-Value as indicated on drawings
2.1.1 Recycled Materials
Provide insulation materials containing the following minimum percentage of recycled material content by weight:
SECTION 07 21 16 Page 4
a. Fiberglass: 20 percent glass cullet complying with ASTM D5359
b. Mineral wool: 75 percent recovered materials content from slag
Provide data identifying percentage of recycled content for insulation materials.
2.1.2 Energy Star
Provide insulation materials that are Energy Star labeled. Provide data identifying Energy Star label for insulation materials.
2.1.3 Prohibited Materials
Do not provide asbestos-containing materials.
2.2 BLOCKING
Wood, metal, unfaced mineral fiber blankets in accordance with ASTM C665, Type I, or other approved materials. Use only non-combustible materials meeting the requirements of ASTM E136 for blocking around chimneys and heat producing devices.
2.3 ACCESSORIES
2.3.1 Adhesive
As recommended by the insulation manufacturer. Provide non-aerosol adhesive products used on the interior of the building (defined as inside of the weatherproofing system) that meet either emissions requirements of CDPH SECTION 01350 (limit requirements for either office or classroom spaces regardless of space type) or VOC content requirements of SCAQMD Rule 1168 . Provide aerosol adhesives used on the interior of the building that meet either emissions requirements of CDPH SECTION 01350 (use the office or classroom requirements, regardless of space type) or VOC content requirements of GS-36. Provide certification or validation of indoor air quality for adhesives.
2.3.2 Mechanical Fasteners
Corrosion resistant fasteners as recommended by the insulation manufacturer.
2.3.3 Wire Mesh
Corrosion resistant and as recommended by the insulation manufacturer.
PART 3 EXECUTION
3.1 EXISTING CONDITIONS
Before installing insulation, ensure that surfaces that will be in contact with the insulation are dry and free of projections which could cause voids, compressed insulation, or punctured vapor retarders. If moisture or other conditions are found that do not allow the workmanlike installation of the insulation, do not proceed but notify Contracting Officer of such conditions.
SECTION 07 21 16 Page 5
3.2 PREPARATION
3.2.1 Blocking Around Heat Producing Devices
Install non-combustible blocking around heat producing devices to provide the following clearances:
a. Recessed lighting fixtures, including wiring compartments, ballasts, and other heat producing devices, unless these are certified by the manufacturer for installation surrounded by insulation: 3 inches from outside face of fixtures and devices or as required by NFPA 70 and, if insulation is to be placed above fixture or device, 24 inches above fixture.
3.3 INSTALLATION
3.3.1 Insulation
Install and handle insulation in accordance with manufacturer's instructions. Keep material dry and free of extraneous materials. Any materials that show visual evidence of biological growth due to presence of moisture must not be installed on the building project. Ensure personal protective clothing and respiratory equipment is used as required. Observe safe work practices.
3.3.1.1 Electrical wiring
Do not install insulation in a manner that would sandwich electrical conductors, that are not installed in conduit, between two layers of insulation.
3.3.1.2 Continuity of Insulation
Install blanket insulation to butt tightly against adjoining blankets and to studs, rafters, joists, sill plates, headers and any obstructions.
Provide continuity and integrity of insulation at corners, wall to ceiling joints, roof, and floor. Avoid creating thermal bridges.
3.3.1.3 Installation at Bridging and Cross Bracing
Insulate at bridging and cross bracing by splitting blanket vertically at center and packing one half into each opening. Butt insulation at bridging and cross bracing; fill in bridged area with loose or scrap insulation.
3.3.1.4 Cold Climate Requirement
Place insulation to the outside of pipes.
3.3.1.5…