W912QR24R0031_Specs-0002.pdf
PDF 2 MB Posted
- Solicitation number
- W912QR24R0031
About this file
This document is an Amendment to Solicitation W912QR24R0031 for the Design-Bid-Build construction of the Area Maintenance Support Activity (AMSA) located in Wilkes-Barre, Pennsylvania.
The amendment modifies several specification sections, including the Price Breakout Schedule, Door Hardware, and adds new sections for a Utility Monitoring and Control System (UMCS) and Electronic Security Systems. The drawings have also been revised, including changes to the Door Schedule, Architectural Finish Key & Flooring Transition Details, and First Floor Technology Plan. Offerors must acknowledge all amendments. All other terms and conditions remain unchanged.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| W912QR24R0031_Plans-0003.pdf | ||
| W912QR24R0031_Specs-0003.pdf | ||
| W912QR24R0031_Plans-0002.pdf | ||
| Site Visit Attendee List.xlsx | XLSX spreadsheet | |
| W912QR24R0031-0001.pdf | ||
| CHANGE NOTICE - SITE VISIT.docx | DOCX document | |
| W912QR24R0031_Specs_Vol1-0000.pdf | ||
| W912QR24R0031_Specs_Vol3-0000.pdf | ||
| W912QR24R0031_Specs_Vol2-0000.pdf | ||
| W912QR24R0031_Plans -0000.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT
Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.
15A. NAME AND TITLE OF SIGNER (Type or print)
30-105-04EXCEPTION TO SF 30
APPROVED BY OIRM 11-84
STANDARD FORM 30 (Rev. 10-83) Prescribed by GSA
FAR (48 CFR) 53.243
Solicitation W912QR24R0031 for the D/B/B construction of the Area Maintenance Support Activity located at Wilkes-Barre, PA is hereby modified as follow s:
See continuation page.
1. CONTRACT ID CODE PAGE OF PAGES
1 3
16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)
16C. DATE SIGNED
BY
16B. UNITED STATES OF AMERICA15C. DATE SIGNED15B. CONTRACTOR/OFFEROR
(Signature of Contracting Officer)(Signature of person authorized to sign)
8. NAME AND ADDRESS OF CONTRACTOR (No., Street , County, State and Zip Code) X W912QR24R0031
X 9B. DATED (SEE ITEM 11)
22-Aug-2024
10B. DATED (SEE ITEM 13)
9A. AMENDMENT OF SOLICITATION NO.
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
X The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offer is extended, X is not extended.
Offer must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended by one of the following methods:
(a) By completing Items 8 and 15, and returning 1 copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted;
or (c) By separate letter or telegram which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN
REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by telegram or letter, provided each telegram or letter makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.
12. ACCOUNTING AND APPROPRIATION DATA (If required)
13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS.
IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.
A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE
CONTRACT ORDER NO. IN ITEM 10A.
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation date, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(B).
C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER (Specify type of modification and authority)
E. IMPORTANT: Contractor is not, is required to sign this document and return copies to the issuing office.
14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
10A. MOD. OF CONTRACT/ORDER NO.
2. AMENDMENT/MODIFICATION NO.
5. PROJECT NO.(If applicable)
6. ISSUED BY
3. EFFECTIVE DATE
07-Oct-2024
CODE
U. S. ARMY ENGINEER DISTRICT, LOUISVILLE
600 DR. MARTIN LUTHER KING, JR. PLACE
ROOM 821
LOUISVILLE KY 40202-2239
W912QR 7. ADMINISTERED BY (If other than item 6)
4. REQUISITION/PURCHASE REQ. NO.
CODE
See Item 6
FACILITY CODECODE
EMAIL:TEL:
W912QR24R0031_Specs-0002
W912QR24R0031
SECTION SF 30 BLOCK 14 CONTINUATION PAGE
SUMMARY OF CHANGES
SECTION SF 30 - BLOCK 14 CONTINUATION PAGE (SF 30)
The following have been added by full text:
AMENDMENT 0002
SUMMARY OF AMENDMENT 0002 CHANGES:
1. The following SPECIFICATIONS have been modified:
a. 01 10 00 00 PRICE BREAKOUT SCHEDULE Revised and Reissued Price Breakout Schedule. Items have been deleted from NOTE NO. 5 and NOTE NO. 6 on Spec page 2.
b. 08 71 00 DOOR HARDWARE Specification page 18 revised and reissued.
2. The following SPECIFICATIONS have been added:
a. 25 10 10 UTILITY MONITORING AND CONTROL SYSTEM (UMCS) FRONT END AND
INTEGRATION
b. ELECTRONIC SECURITY SYSTEMS
3. The following DRAWINGS have been modified:
a. Sheet A-601 DOOR SCHEDULE Drawing has been revised and reissued.
b. Sheet S-001 ARCHITECTURAL FINISH KEY & FLOORING TRANSITION DETAILS Drawing has been revised and reissued.
c. Sheet T-201 FIRST FLOOR TECHNOLOGY PLAN Drawing has been revised and reissued. Added access control to doors 100J, 112 and 115.
4. Offerors must acknowledge all amendments.
5. All other terms and conditions remain unchanged.
(End of Summary of Changes)
P2 501675 Wilkes Barre AMSA Wilkes-Barre, PA
PRICE BREAKOUT SCHEDULE Page 1 Amendment 0002
SECTION 00 10 00 00
PRICE BREAKOUT SCHEDULE
Amendment 0002
OFFEROR’S NAME: ______________________________
Contract Line Item Number Description Unit Amount
Base Bid
0001 Primary Facility – AMSA Job $
0002 Site Work Job $
0003 Utility: Electric Job $ 1705
Total Base Bid Base $
Options
0004 Rock Excavation CY $
0005 OMAR Funded Items for AMSA Job $
0006 “Bona Fide Need” OMAR Funded Items Job $
0007 Heavy Duty Asphalt Paving Job $
0008 Heavy Duty Concrete Pavement/Parking Job $
0009 Loading Ramp Job $
0010 Wash Rack Job $
0011 SATS Canopy Job $
0012 6 EV Parking Spots Job $
Total Options Options $
Total Proposal (Base Bid and Options) Total $
NOTES FOR PRICE BREAKOUT SCHEDULE
NOTE NO. 1. CLIN 0001 includes all materials, labor, and work to construct the AMSA within a line five feet outside of the face of the building except that work covered by CLIN 0002.
NOTE NO. 2. CLIN 0002 includes all materials, labor, and work required to construct the demolition and site work for the AMSA within a line five feet outside the face of the building out to the construction limits except work covered by CLIN 0001.
NOTE NO. 3. CLIN 0003 includes the fee(s) to the Contractor related to completing and submitting any electric utility connection application(s). Includes estimated Cost for Electric Utility to install meter, service line and any/all associated fees. Contractor to pay Electric Utility directly. Refer to plans and specifications for further information. This is an estimated cost.
CERTIFIED FINAL
PRICE BREAKOUT SCHEDULE Page 2 Amendment 0002
NOTE NO. 4. CLIN 0004 is to establish a unit price per CY for determining payment based on the actual amount of Rock Excavation beyond what is identified in the specifications and drawings, to account for unforeseen sight conditions. ***This Option may be exercised within 365 days from issuance of Notice-to-Proceed (NTP).***
Amdt. 0002 **************************************************************************
NOTE NO. 5. CLIN 0005 includes all work required to furnish and install “OMAR Funded Equipment Items” OMAR Funded Equipment shall be contractor provided and contractor installed (CFCI). Item consists of the following: Metal Lockers. ***This Option may be exercised within 90 days from issuance of Notice-to-Proceed (NTP).***
NOTE NO. 6. CLIN 0006 includes all work required to furnish and install “Bona Fide Need OMAR funded Equipment Items” which are items not permanently attached to the construction. OMAR Funded Equipment shall be contractor provided and contractor installed (CFCI). Items consist of the following:
Refrigerator and Microwaves, Window Blinds, and Fire Extinguishers. ***This Option may be exercised within 600 days from issuance of Notice-to-Proceed (NTP).***
************************************************************************** Amdt. 0002
NOTE NO. 7. CLIN 0007 includes all materials, labor, and work, required to complete construction of Heavy Duty Asphalt Drive as shown on Civil drawings. ***This Option may be exercised within 90 days from issuance of Notice-to-Proceed (NTP).***
NOTE NO. 8. CLIN 0008 includes all construction costs to provide a concrete pavement for the MEP Lot; including but not limited to utilities, site lighting, landscaping, and other construction work. ***This Option may be exercised within 90 days from issuance of Notice-to-Proceed (NTP).***
NOTE NO. 9. CLIN 0009 includes all construction work required to construct the loading ramp as shown on the civil and structural drawings. ***This Option may be exercised within 90 days from issuance of Notice-to-Proceed (NTP).***
NOTE NO. 10. CLIN 0010 includes all construction costs to provide a two (2) vehicle wash rack and associated utilities and concrete aprons. ***This Option may be exercised within 90 days from issuance of Notice-to-Proceed (NTP).***
NOTE NO. 11. CLIN 0011 includes all construction costs to provide a SATS Canopy. ***This Option may be exercised within 90 days from issuance of Notice-to-Proceed (NTP).***
NOTE NO. 12. CLIN 0012 includes all construction costs to provide six (6) Level 2 EV Charging Spots.
***This Option may be exercised within 90 days from issuance of Notice-to-Proceed (NTP).***
SECTION 08 71 00
DOOR HARDWARE
02/16, CHG 4: 02/22
AMENDMENT 0002
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
ASTM INTERNATIONAL (ASTM)
ASTM E283 (2019) Standard Test Method for Determining the Rate of Air Leakage Through Exterior Windows, Curtain Walls, and Doors Under Specified Pressure Differences Across the Specimen
BUILDERS HARDWARE MANUFACTURERS ASSOCIATION (BHMA)
ANSI/BHMA A156.1 (2021) Butts and Hinges
ANSI/BHMA A156.2 (2022) Bored and Preassembled Locks and Latches
ANSI/BHMA A156.3 (2020) Exit Devices
ANSI/BHMA A156.4 (2013) Door Controls - Closers
ANSI/BHMA A156.5 (2020) Cylinder and Input Devices for Locks
ANSI/BHMA A156.6 (2021) Architectural Door Trim
ANSI/BHMA A156.7 (2016) Template Hinge Dimensions
ANSI/BHMA A156.8 (2021) Door Controls - Overhead Stops and Holders
ANSI/BHMA A156.13 (2022) Mortise Locks & Latches Series 1000
ANSI/BHMA A156.15 (2021) Release Devices Closer Holder, Electromagnetic and Electromechanical
ANSI/BHMA A156.16 (2023) Auxiliary Hardware
ANSI/BHMA A156.17 (2019) Self Closing Hinges & Pivots
ANSI/BHMA A156.18 (2020) Materials and Finishes
ANSI/BHMA A156.21 (2019) Thresholds
ANSI/BHMA A156.22 (2021) Gasketing
SECTION 08 71 00 Page 1
AMENDMENT 0002
ANSI/BHMA A156.24 (2012) Delayed Egress Locking Systems
ANSI/BHMA A156.25 (2013) Electrified Locking Devices
ANSI/BHMA A156.26 (2012) Continuous Hinges
ANSI/BHMA A156.29 (2012) Exit Locks, Exit Alarms, Alarms for Exit Devices
ANSI/BHMA A156.30 (2014) High Security Cylinders
ANSI/BHMA A156.31 (2013) Electric Strikes and Frame Mounted Actuators
ANSI/BHMA A156.36 (2010) Auxiliary Locks
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 70 (2023; ERTA 4 2023) National Electrical Code
NFPA 72 (2022; ERTA 22-1) National Fire Alarm and Signaling Code
NFPA 80 (2022) Standard for Fire Doors and Other Opening Protectives
NFPA 101 (2021; TIA 21-1) Life Safety Code
NFPA 252 (2022) Standard Methods of Fire Tests of Door Assemblies
STEEL DOOR INSTITUTE (SDI/DOOR)
SDI/DOOR A250.8 (2023) Specifications for Standard Steel Doors and Frames
U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)
36 CFR 1191 Americans with Disabilities Act (ADA) Accessibility Guidelines for Buildings and Facilities; Architectural Barriers Act (ABA) Accessibility Guidelines
UNDERWRITERS LABORATORIES (UL)
UL Bld Mat Dir (updated continuously online) Building Materials Directory
1.2 SUBMITTALS
Government approval is required for submittals with a "G" or "S" classification. Submittals not having a "G" or "S" classification are for information only. When used, a code following the "G" classification identifies the office that will review the submittal for the Government.
Submit the following in accordance with Section 01 33 00 SUBMITTAL
PROCEDURES:
SD-02 Shop Drawings
SECTION 08 71 00 Page 2
AMENDMENT 0002
Manufacturer's Detail Drawings; G
Verification of Existing Conditions; G
Hardware Schedule; G
Keying System; G
SD-03 Product Data
Hardware Items; G
SD-08 Manufacturer's Instructions
Installation
SD-10 Operation and Maintenance Data
Hardware Schedule Items, Data Package 1; G
SD-11 Closeout Submittals
Key Bitting
1.3 SHOP DRAWINGS
Submit manufacturer's detail drawings indicating all hardware assembly components and interface with adjacent construction. Indicate power components and wiring coordination for electrified hardware. Base shop drawings on verified field measurements and include verification of existing conditions.
1.4 PRODUCT DATA
Indicate fire-ratings at applicable components. Provide documentation of ABA/ADA accessibility compliance of applicable components, as required by 36 CFR 1191 Appendix D - Technical.
1.5 HARDWARE SCHEDULE
Provide Hardware Item List and Hardware Schedule containing the following information, and additional information as needed to identify the complete make up of each hardware set and its application to each opening:
1.5.1 Hardware Item List:
a. Hardware Type
b. Item Number
c. Quantity
d. Size(s)
e. Reference Publication / Type Number
f. Manufacturer's Name / Catalog Number
SECTION 08 71 00 Page 3
AMENDMENT 0002
g. Key Control Symbols
h. UL Mark (If fire rated and listed)
i. BHMA Finish(es)
j. Remarks
1.5.2 Hardware Schedule
a. Hardware Set Number
b. Opening Number(s)
c. Opening Description (single/double leaf, hand, size, door/frame material)
d. Fire Rating
e. Sound Rating
f. Hardware Items
g. Quantity
h. Size
i. BHMA Finish
j. Remarks
In addition, submit hardware schedule data package 1 in accordance with Section 01 78 23 OPERATION AND MAINTENANCE DATA.
1.6 KEY BITTING CHART REQUIREMENTS
1.6.1 Requirements
Submit key bitting charts to the Contracting Officer prior to completion of the work. Include:
a. Complete listing of all keys (e.g. AA1 and AA2).
b. Complete listing of all key cuts (AA1-123456, AA2-123458).
c. Tabulation showing which key fits which door.
d. Copy of floor plan showing doors and door numbers.
e. Listing of 20 percent more key cuts than are presently required in each master system.
1.7 QUALITY ASSURANCE
1.7.1 Hardware Manufacturers and Modifications
Provide, as far as feasible, locks, hinges, and closers of one lock, hinge, or closer manufacturer's make. Modify hardware as necessary to provide
SECTION 08 71 00 Page 4
AMENDMENT 0002
features indicated or specified.
1.7.2 Key Shop Drawings Coordination Meeting
Prior to the submission of the key shop drawing, the Contracting Officer, Contractor, Door Hardware Subcontractor, using Activity and Base Locksmith must meet to discuss and coordinate key requirements for the facility.
1.8 DELIVERY, STORAGE, AND HANDLING
Deliver hardware in original individual containers, complete with necessary appurtenances including fasteners and instructions. Mark each individual container with item number as shown on hardware schedule. Deliver permanent keys and removable cores to the Contracting Officer, either directly or by certified mail. Deliver construction master keys with the locks.
PART 2 PRODUCTS
2.1 TEMPLATE HARDWARE
Hardware applied to metal or to prefinished doors must be manufactured using a template. Provide templates to door and frame manufacturers in accordance with ANSI/BHMA A156.7 for template hinges. Coordinate hardware items to prevent interference with other hardware.
2.2 HARDWARE FOR FIRE DOORS AND EXIT DOORS
Provide all hardware necessary to meet the requirements of NFPA 72 for door alarms, NFPA 80 for fire doors, NFPA 101 for exit doors, NFPA 252 for fire tests of door assemblies, ABA/ADA accessibility requirements, and all other requirements indicated, even if such hardware is not specifically mentioned in paragraph HARDWARE SCHEDULE. Provide Underwriters Laboratories, Inc. labels for such hardware in accordance with UL Bld Mat Dir or equivalent labels in accordance with another testing laboratory approved in writing by the Contracting Officer.
2.3 HARDWARE ITEMS
Clearly and permanently mark with the manufacturer's name or trademark, hinges, pivots, locks, latches, exit devices, bolts and closers where the identifying mark is visible after the item is installed. For closers with covers, the name or trademark may be beneath the cover. Coordinate electrified door hardware components with corresponding components specified in Division 28 ELECTRONIC SECURITY SYSTEMS (ESS).
2.3.1 Hinges
Provide in accordance with ANSI/BHMA A156.1. Provide hinges that are 4-1/2 by 4-1/2 inch unless otherwise indicated. Construct loose pin hinges for interior doors and reverse-bevel exterior doors so that pins are non-removable when door is closed. Other anti-friction bearing hinges may be provided in lieu of ball bearing hinges.
2.3.2 Continuous Hinges
Where continuous hinges are required, provide in accordance with
ANSI/BHMA A156.26.
SECTION 08 71 00 Page 5
AMENDMENT 0002
2.3.3 Spring Hinges
Provide in accordance with ANSI/BHMA A156.17.
2.3.4 Locks and Latches
a. At exterior locations provide locksets of full stainless steel type 302 or 304 construction including fronts, strike, escutcheons, knobs, bolts and all interior working parts. Marine Grade I, fully non-ferrous.
b. In non-air-conditioned interior environments or humid interior environments, provide interior locksets on the same Marine Grade I, fully non-ferrous as exterior locksets.
2.3.4.1 Mortise Locks and Latches
Provide in accordance with ANSI/BHMA A156.13, Series 1000, Operational Grade 1, Security Grade 2. Provide mortise locks with escutcheons not less than 7 by 2-1/4 inch with a bushing at least 1/4 inch long. Cut escutcheons to fit cylinders and provide trim items with straight, beveled, or smoothly rounded sides, corners, and edges. Provide knobs and roses of mortise locks with screwless shanks and no exposed screws.
2.3.4.2 Bored Locks and Latches
Provide in accordance with ANSI/BHMA A156.2, Series 4000, Grade 1.
2.3.4.3 Auxiliary Locks
Provide in accordance with ANSI/BHMA A156.36, Grade 1.
2.3.5 Exit Devices
Provide in accordance with ANSI/BHMA A156.3, Grade 1. Provide adjustable strikes for rim type and vertical rod devices. Provide open back strikes for pairs of doors with mortise and vertical rod devices. Provide touch bars in lieu of conventional crossbars and arms.
Use stainless steel or bronze base metal with plated finishes. Also include stainless steel fasteners and screws.
2.3.6 Exit Locks With Alarm
Provide in accordance with ANSI/BHMA A156.3 and ANSI/BHMA A156.29, Type E0431 (with full width horizontal actuating bar) for single doors; Type E0431 (with actuating bar) or E0471 (with actuating bar and top and bottom bolts, both leaves active) for pairs of doors, unless otherwise specified.
Provide terminals for connection to remote indicating panel. Provide door alarms integrated with the fire alarm system in accordance with NFPA 72.
2.3.7 Cylinders and Cores
Provide cylinders and cores with seven pin tumblers. Provide cylinders from the products of one manufacturer, and provide cores from the products of one manufacturer. Rim cylinders, mortise cylinders, and knobs of bored locksets have interchangeable cores which are removable by special control keys. Stamp each interchangeable core with a key control symbol in a concealed place on the core.
SECTION 08 71 00 Page 6
AMENDMENT 0002
Provide cylinders for new locks, including locks provided under other sections of this specification. Provide fully compatible cylinders of Grade 1 products from products of one manufacturer with interchangeable cores that are removable by a special control key. Factory set the cores with seven pin tumblers using the A4 system and F keyway. Submit a core code sheet with the cores. Provide master keyed cores in one system for this project. Provide construction interchangeable cores.
2.3.7.1 High Security Cylinders
Provide in accordance with ANSI/BHMA A156.30, security level B for all high security cylinder components.
2.3.8 Push Button Mechanisms
Provide in accordance with ANSI/BHMA A156.5, Grade 1.
2.3.9 Electrified Hardware
Comply with the requirements of NFPA 70 for wiring of electrified hardware.
2.3.9.1 Electric Strikes and Frame Mounted Actuators
Provide in accordance with ANSI/BHMA A156.31, Grade 1. Provide electric strikes and actuators as required to meet operational requirements.
Provide electric strikes that remain secure during power failure. Provide battery backup for continued operation during power failure. Provide strikes and actuators with a minimum opening force of 2300 pounds.
Provide facility interface devices that use direct current (dc) power to energize the solenoids. Provide electric strikes and actuators that incorporate end-of-line resistors to facilitate line supervision by the system. If not incorporated into the electric strike or local controller, provide metal oxide resistors (MOVs) to protect the controller from reverse current surges.
2.3.9.1.1 Solenoid
Provide actuating solenoid for strikes and actuators that are rated for continuous duty, cannot dissipate more than 12 Watts and must operate on 12 or 24 Volts dc. Inrush current cannot exceed 1 ampere and the holding current cannot be greater than 500 milliamperes. Actuating solenoid must move from fully secure to fully open positions in less than 500 milliseconds.
2.3.9.1.2 Signal Switches
Provide strikes and actuators with signal switches to indicate to the system when the bolt is not engaged or the strike mechanism is unlocked.
Signal switches must report a forced entry to the system.
2.3.9.1.3 Tamper Resistance
Provide strike guards that prevent tampering with the latch bolt of the locking hardware or the latch bolt keeper of the electric strike. Strike guards to bolt through the door using tamper resistant screws. Provide strike guards made of 1/8 inch thick brass and that are 11-1/14 inch high by 1-5/8 inch wide, with a minimum 5/32 inch wide offset.
SECTION 08 71 00 Page 7
AMENDMENT 0002
2.3.9.1.4 Coordination
Provide electric strikes and actuators of a size, weight and profile compatible with each specified door frame. Field verify installation clearances prior to procurement.
2.3.9.1.5 Mounting Method
Provide electric strikes and actuators suitable for use with single and double doors, with mortise or rim type hardware specified, and for right or left hand mounting as specified. In double door installations, locate the lock in the active leaf and monitor the fixed leaf.
2.3.9.2 Electrified Mortise Locks
Provide in accordance with ANSI/BHMA A156.25, Grade 1. Provide electrified mortise locks that remain secure during power failure. Provide facility interface devices that use dc power to energize solenoids. Provide solenoids, resisters, and signal switches in accordance with paragraph
ELECTRIC STRIKES AND FRAME MOUNTED ACTUATORS.
2.3.9.2.1 Power Transfer Hinges
Provide power transfer hinges with each electrified lock that route power and monitoring signals from the lockset to the door frame. Coordinate power transfer hinges with door frames.
2.3.9.3 Release Devices
In accordance with ANSI/BHMA A156.15, Grade 1.
2.3.9.3.1 Closer Holders
Provide door mounted closer holder devices connected by integral releasing to fire detecting devices.
2.3.9.3.2 Release Devices
Provide door mounted electromechanical release devices connected to fire detecting devices.
2.3.9.4 Delayed Egress Locking System
Provide in accordance with ANSI/BHMA A156.24, Grade 1.
2.3.10 Keying System
Provide a master keying system
2.3.11 Lock Trim
Provide cast, forged, or heavy wrought construction and commercial plain design for lock trim.
2.3.11.1 Knobs and Roses
Provide in accordance with ANSI/BHMA A156.2 and ANSI/BHMA A156.13 for knobs, roses, and escutcheons. For unreinforced knobs, roses, and
SECTION 08 71 00 Page 8
AMENDMENT 0002
escutcheons, provide a 0.050 inch thickness. For reinforced knobs, roses, and escutcheons, provide an outer shell thickness of 0.035 inch and a combined total thickness of 0.070 inch, except at knob shanks. Provide knob shanks 0.060 inch thick.
2.3.11.2 Lever Handles
Provide lever handles where indicated in the Hardware Schedule. Provide in accordance with ANSI/BHMA A156.3 for mortise locks of lever handles for exit devices. Provide lever handle locks with a breakaway feature (such as a weakened spindle or a shear key) to prevent irreparable damage to the lock when force in excess of that specified in ANSI/BHMA A156.13 is applied to the lever handle. Provide lever handles return to within 1/2 inch of the door face.
2.3.12 Keys
Provide one file key, one duplicate key, and one working key for each key change . Provide one additional working key for each lock of each keyed-alike group.Provide a quantity of key blanks equal to 20 percent of the total number of file keys. Stamp each key with appropriate key control symbol and "U.S. property - do not duplicate." Do not place room number on keys.
2.3.13 Door Bolts
Provide in accordance with ANSI/BHMA A156.16. Provide dustproof strikes for bottom bolts, except at doors having metal thresholds. Provide automatic latching flush bolts in accordance with ANSI/BHMA A156.3, Type 25.
2.3.14 Closers
Provide in accordance with ANSI/BHMA A156.4, Series C02000, Grade 1, with PT 4C. Provide with brackets, arms, mounting devices, fasteners, full size covers, except at storefront mounting, and other features necessary for the particular application. Size closers in accordance with manufacturer's printed recommendations, or provide multi-size closers, Sizes 1 through 6, and list sizes in the Hardware Schedule. Provide manufacturer's 10 year warranty.
Use stainless steel inside bracketed or door mounted closers on exterior doors. Non-ferrous closers, such as aluminum or cast bronze, are permissible where door utilization is minimal. On interior doors use closers of 302 or 304 stainless steel or non-ferrous materials. On surface-mounted closers use or apply rust inhibiting finish on all ferrous parts. Also apply this finish on concealed closers.
2.3.14.1 Identification Marking
Engrave each closer with manufacturer's name or trademark, date of manufacture, and manufacturer's size designation in locations that will be visible after installation.
2.3.15 Overhead Holders
Provide in accordance with ANSI/BHMA A156.8.
SECTION 08 71 00 Page 9
AMENDMENT 0002
2.3.16 Door Protection Plates
Provide in accordance with ANSI/BHMA A156.6.
2.3.16.1 Sizes of Kick Plates
2 inch less than door width for single doors; 1 inch less than door width for pairs of doors. Provide 10 inch kick plates for flush doorsa.
2.3.17 Door Stops and Silencers
Provide in accordance with ANSI/BHMA A156.16. Silencers Type L03011.
Provide three silencers for each single door, two for each pair.
2.3.18 Thresholds
Provide in accordance with ANSI/BHMA A156.21. Use J35100, with vinyl or silicone rubber insert in face of stop, for exterior doors opening out, unless specified otherwise.
2.3.19 Weatherstripping Gasketing
Provide in accordance with ANSI/BHMA A156.22. Provide the type and function designation where specified in paragraph HARDWARE SCHEDULE.
Provide a set to include head and jamb seals, sweep strips, and, for pairs of doors, astragals. Air leakage of weatherstripped doors not to exceed
0.5 cubic feet per minute of air per square foot of door area when tested in accordance with ASTM E283. Provide weatherstripping with one of the following:
2.3.19.1 Extruded Aluminum Retainers
Extruded aluminum retainers not less than 0.050 inch wall thickness with vinyl, neoprene, silicone rubber, or polyurethane inserts. Provide clear (natural) anodized aluminum.
2.3.19.2 Interlocking Type
Zinc or bronze not less than 0.018 inch thick.
2.3.19.3 Spring Tension Type
Spring bronze or stainless steel not less than 0.008 inch thick.
2.3.20 Gasketing
Provide in accordance with ANSI/BHMA A156.22. Provide adjustable doorstops at heads,jambs and automatic door bottoms in accordance with the hardware set, of extruded aluminum, clear (natural) anodized, surface applied, with vinyl fin seals between plunger and housing. Provide doorstops with solid neoprene tube, silicone rubber, or closed cell sponge gasket. Provide door bottoms with adjustable operating rod and silicone rubber or closed cell sponge neoprene gasket. Provide doorstops that are mitered at corners.
Provide type and function designation where specified in paragraph HARDWARE
SETS.
2.3.21 Rain Drips
Provide in accordance with ANSI/BHMA A156.22. Provide extruded aluminum
SECTION 08 71 00 Page 10
AMENDMENT 0002
rain drips, not less than 0.08 inch thick, clear anodized finish. Provide the manufacturer's full range of color choices to the Contracting Officer for color selection. Provide rain drips with a 4 inch overlap on each side of each exterior door that is not protected by an awning, roof, eave or other horizontal projection. Set drips in sealant and fasten with stainless steel screws.
2.3.21.1 Door Rain Drips
Approximately 1-1/2 inch high by 5/8 inch projection. Align bottom with bottom edge of door.
2.3.21.2 Overhead Rain Drips
Approximately 1-1/2 inch high by 2-1/2 inch projection. Align bottom with door frame rabbet.
2.3.22 Auxiliary Hardware (Other than locks)
Provide in accordance with ANSI/BHMA A156.16, Grade 1.
2.3.23 Special Tools
Provide special tools, such as spanner and socket wrenches and dogging keys, as required to service and adjust hardware items.
2.4 FASTENERS
Provide fasteners of type, quality, size, and quantity appropriate to the specific application. Fastener finish to match hardware. Provide stainless steel or nonferrous metal fasteners in locations exposed to weather. Verify metals in contact with one another are compatible and will avoid galvanic corrosion when exposed to weather.
2.5 FINISHES
Provide in accordance with ANSI/BHMA A156.18. Provide hardware in BHMA 630 finish (satin stainless steel), unless specified otherwise. Provide items not manufactured in stainless steel in BHMA 626 finish (satin chromium plated) over brass or bronze, except aluminum paint finish for surface door closers, and exceptBHMA 600 finish (primed for painting) for steel hinges.
Provide hinges for exterior doors in stainless steel with BHMA 630 finish.
Furnish exit devices in BHMA 626 finish in lieu of BHMA 630 finish . Match exposed parts of concealed closers to lock and door trim. Match hardware finish for aluminum doors to the doors.
2.6 KEY CABINET AND CONTROL SYSTEM
Provide in accordance with ANSI/BHMA A156.5, Type required to yield a capacity (number of hooks) 50 percent greater than the number of key changes used for door locks.
PART 3 EXECUTION
3.1 INSTALLATION
Provide hardware in accordance with manufacturers' printed installation instructions. Fasten hardware to wood surfaces with full-threaded wood screws or sheet metal screws. Provide machine screws set in expansion
SECTION 08 71 00 Page 11
AMENDMENT 0002
shields for fastening hardware to solid concrete and masonry surfaces.
Provide toggle bolts where required for fastening to hollow core construction. Provide through bolts where necessary for satisfactory installation.
3.1.1 Weatherstripping Installation
Provide full contact, weathertight seals that allow operation of doors without binding the weatherstripping.
3.1.1.1 Stop Applied Weatherstripping
Fasten in place with color matched sheet metal screws not more than 9 inch on center after doors and frames have been finish painted.
3.1.1.2 Interlocking Type Weatherstripping
Provide interlocking, self adjusting type on heads and jambs and flexible hook type at sills. Nail weatherstripping to door 1 inch on center and to heads and jambs at 4 inch on center.
3.1.1.3 Spring Tension Type Weatherstripping
Provide spring tension type on heads and jambs. Provide bronze nails with bronze. Provide stainless steel nails with stainless steel. Space nails not more than 1-1/2 inch on center.
3.1.2 Installation
Provide as specified for stop applied weatherstripping.
3.1.3 Threshold Installation
Extend thresholds the full width of the opening and notch end for jamb stops. Set thresholds in a full bed of sealant and anchor to floor with cadmium-plated, countersunk, steel screws. For aluminum thresholds placed on top of concrete surfaces, coat the underside surfaces that are in contact with the concrete with fluid applied waterproofing as a separation measure prior to placement.
3.2 FIRE DOORS AND EXIT DOORS
Provide hardware in accordance with NFPA 72 for door alarms, NFPA 80 for fire doors, NFPA 101 for exit doors, and NFPA 252 for fire tests of door assemblies.
3.3 HARDWARE LOCATIONS
Provide in accordance with SDI/DOOR A250.8, unless indicated or specified otherwise.
a. Kick Plates: Push side of single-acting doors. Both sides of double-acting doors.
3.4 KEY CABINET AND CONTROL SYSTEM
Locate where directed. Tag one set of file keys and one set of duplicate keys. Place other keys in appropriately marked envelopes, or tag each key. Provide complete instructions for setup and use of key control
SECTION 08 71 00 Page 12
AMENDMENT 0002
system. On tags and envelopes, indicate door and room numbers or master or grand master key.
3.5 FIELD QUALITY CONTROL
After installation, protect hardware from paint, stains, blemishes, and other damage until acceptance of work. Submit notice of testing 15 days before scheduled, so that testing can be witnessed by the Contracting Officer. Adjust hinges, locks, latches, bolts, holders, closers, and other items to operate properly. Demonstrate that permanent keys operate respective locks, and give keys to the Contracting Officer. Correct, repair, and finish, errors in cutting and fitting and damage to adjoining work.
3.6 HARDWARE SETS
SECTION 08 71 00 Page 13
AMENDMENT 0002
Provide hardware for aluminum doors under this section. Deliver Hardware templates and hardware, except field applied hardware, to the aluminum door and frame manufacturer for use in fabricating doors and frames.
HW-1
HINGES (AS SPECIFIED)
1 PRIVACY LOCK MA321 OCCUPIED/VACANT (F22)
1 SURFACE CLOSER 4050A / 4050A EDA (CO2011/CO2021)
1 KICK PLATE 8400 10" X 2" LDW B-CS (J102)
1 WALL STOP WS406/407CVX (L52101)
1 SEALS 188S (R0E151)
FUNCTION: MA321 (F22) BATH/BEDROOM PRIVACY LOCK
LATCHBOLT RETRACTED BY LEVER FROM EITHER SIDE UNLESS OUTSIDE IS LOCKED
BY INSIDE THUMBTURN. TURNING INSIDE LEVER OR CLOSING DOOR UNLOCKS
OUTSIDE LEVER. TO UNLOCK FROM OUTSIDE, REMOVE EMERGENCY BUTTON, INSERT
EMERGENCY TURN (FURNISHED) IN ACCESS HOLE AND ROTATE.
HW-02
HINGES (AS SPECIFIED)
1 CLASSROOM LOCK T561 (F84)
1 WALL STOP WS406/407CCV (L52251)
FUNCTION: T561 (F84) CLASSROOM LOCK
OUTSIDE LEVER LOCKED AND UNLOCKED BY KEY. INSIDE LEVER ALWAYS UNLOCKED.
HW-03A
HINGES (AS SPECIFIED)
1 STOREROOM LOCK T581 (F86)
1 KICK PLATE 8400 10" X 2" LDW B-CS (J102)
1 WALL STOP WS406/407CCV (L52251)
FUNCTION: T581 (F86) STOREROOM LOCK
OUTSIDE LEVER FIXED. ENTRANCE BY KEY ONLY. INSIDE LEVER ALWAYS
UNLOCKEDHW-03B
HINGES (AS SPECIFIED)
1 STOREROOM LOCK w/ DUMMY
LEVER
T581 (F86)
2 KICK PLATE 8400 10" X 2" LDW B-CS (J102)
2 SURFACE CLOSER WITH HOLD OPEN 4050A Hw/PA
FUNCTION: T581 (F86) STOREROOM LOCK
OUTSIDE LEVERS FIXED. ENTRANCE BY KEY ONLY. INSIDE LEVERS ALWAYS
UNLOCKEDHW-03C
HINGES (AS SPECIFIED)
1 STOREROOM LOCK T581 (F86)
1 KICK PLATE 8400 10" X 2" LDW B-CS (J102)
1 SURFACE CLOSER WITH HOLD OPEN 4050A Hw/PA
FUNCTION: T581 (F86) STOREROOM LOCK
OUTSIDE LEVER FIXED. ENTRANCE BY KEY ONLY. INSIDE LEVER ALWAYS
UNLOCKED
SECTION 08 71 00 Page 14
AMENDMENT 0002
HW-04
HINGES (AS SPECIFIED)
1 PASSAGE SET T101S (F75)
1 SURFACE CLOSER 4050A SCUSH (CO2011/CO2021)
1 KICK PLATE 8400 10" X 2" LDW B-CS (J102)
1 SEALS 188S (R0E151)
1 DOOR SWEEP (BRUSH) 8192 (R3A436, R3A735)
1 THRESHOLD (PROFILE AS REQUIRED) (J32100, J32130)
FUNCTION: T101S (F75) PASSAGE LATCH
BOTH LEVERS ALWAYS UNLOCKED.
HW-05
HINGES (AS SPECIFIED)
1 CLASSROOM LOCK T561 (F84)
1 SURFACE CLOSER 4050A / 4050A EDA (CO2011/CO2021)
1 KICK PLATE 8400 10" X 2" LDW B-CS (J102)
1 WALL STOP WS406/407CCV (L52251)
1 SMOKE SEALS 188S (AT RATED OR SMOKE & DRAFT CONTROL
DRS ONLY) (R0E151)
FUNCTION: T561 (F84) CLASSROOM LOCK
OUTSIDE LEVER LOCKED AND UNLOCKED BY KEY. INSIDE LEVER ALWAYS UNLOCKED.
HW-06
HINGES (AS SPECIFIED)
1 STOREROOM LOCK T581 (F86)
1 LOCK GUARD LG
1 SURFACE CLOSER 4050A SCUSH (CO2011/CO2021)
1 KICK PLATE 8400 10" X 2" LDW B-CS (J102)
1 RAIN DRIP 142 (R3Y976)
1 SET GASKETING 429 (R3E164)
1 DOOR SWEEP 8198 (R3A536)
1 THRESHOLD (PROFILE AS REQUIRED) (J32100, J32130)
1 DOOR CONTACT (BY SECURITY SUPPLIER)
FUNCTION: T581 (F86) STOREROOM LOCK
OUTSIDE LEVER FIXED. ENTRANCE BY KEY ONLY. INSIDE LEVER ALWAYS
UNLOCKEDHW-07
HINGES (AS SPECIFIED)
1 MANUAL FLUSH BOLT FB458 (L04251)
1 CONST LATCHING BOLT FB51T / FB61T (TYPE 27)
1 STOREROOM LOCK T581 (F86)
1 COORDINATOR COR X FL (TYPE 21A)
2 SURFACE CLOSER 4050A SCUSH (CO2011/CO2021)
2 KICK PLATE 8400 10" X 1" LDW B-CS (J102)
SECTION 08 71 00 Page 15
AMENDMENT 0002
1 RAIN DRIP 142 (R3Y976)
1 SET WEATHERSTRIP 429 (R3E164)
1 MEETING STILE SEAL 8193 X 8193 (R3A436, R3A166, R3A735)
1 OVERLAP ASTRAGAL (BY DOOR SUPPLIER)
2 DOOR SWEEP 8198 (R3A536)
1 THRESHOLD (PROFILE AS REQUIRED) (J32100, J32130)
2 DOOR CONTACT (BY SECURITY SUPPLIER)
FUNCTION: T581 (F86) STOREROOM LOCK
OUTSIDE LEVER FIXED. ENTRANCE BY KEY ONLY. INSIDE LEVER ALWAYS
UNLOCKEDHW-08
HINGES (AS SPECIFIED)
1 STOREROOM LOCK T581 (F86)
1 ELECTRIC STRIKE 6211 FSE (A156.31, Grade 1)
1 SURFACE CLOSER 4050A / 4050A EDA (CO2011/CO2021)
1 KICK PLATE 8400 10" X 2" LDW B-CS (J102)
1 WALL STOP WS406/407CCV (L52251)
1 SMOKE SEALS 188S (AT RATED OR SMOKE & DRAFT CONTROL
DRS ONLY) (R0E151)
1 CREDENTIAL READER (BY SECURITY SUPPLIER)
1 DOOR CONTACT (BY SECURITY SUPPLIER)
1 POWER SUPPLY (BY ELECTRICAL)
1 WIRING DIAGRAMS RISER & POINT-TO-POINT (BY HARDWARE
SUPPLIER)
FUNCTION: T581 (F86) STOREROOM LOCK
OUTSIDE LEVER FIXED. ENTRANCE BY KEY ONLY. INSIDE LEVER ALWAYS
UNLOCKEDA VALID CREDENTIAL RELEASES ELECTRIC STRIKE.
HW-09
HINGES (AS SPECIFIED)
1 STOREROOM LOCK T581 (F86)
1 ELECTRIC STRIKE 6211 FSE (A156.31, Grade 1)
1 LOCK GUARD LG
1 SURFACE CLOSER 4050A SCUSH (CO2011/CO2021)
1 KICK PLATE 8400 10" X 2" LDW B-CS (J102)
1 RAIN DRIP 142 (R3Y976)
1 SET GASKETING 429 (R3E164)
1 DOOR SWEEP 8198 (R3A536)
1 THRESHOLD (PROFILE AS REQUIRED) (J32100, J32130)
1 CREDENTIAL READER (BY SECURITY SUPPLIER)
1 DOOR CONTACT (BY SECURITY SUPPLIER)
1 POWER SUPPLY (BY ELECTRICAL)
1 WIRING DIAGRAMS RISER & POINT-TO-POINT (BY HARDWARE
SUPPLIER)
SECTION 08 71 00 Page 16
AMENDMENT 0002
FUNCTION: T581 (F86) STOREROOM LOCK
OUTSIDE LEVER FIXED. ENTRANCE BY KEY ONLY. INSIDE LEVER ALWAYS
UNLOCKEDA VALID CREDENTIAL RELEASES ELECTRIC STRIKE.
HW-10
HINGES (AS SPECIFIED)
1 PANIC HARDWARE LD-99-NL (Grade 1, Type 1, Function 03)
1 INTERCHANGEABLE CORE (CYLINDER AS REQUIRED)
1 SURFACE CLOSER 4050A SCUSH (CO2011/CO2021)
1 KICK PLATE 8400 10" X 2" LDW B-CS (J102)
1 RAIN DRIP 142 (R3Y976)
1 SET GASKETING 429 (R3E164)
1 DOOR SWEEP 8198 (R3A536)
1 THRESHOLD (PROFILE AS REQUIRED) (J32100, J32130)
1 DOOR CONTACT (BY SECURITY SUPPLIER)
FUNCTION: (NL) LATCHBOLT RETRACTED INSIDE BY EXIT DEVICE PUSH PAD AND
OUTSIDE BY KEY IN CYLINDER. DOOR LOCKS WHEN KEY IS REMOVED AND DOOR IS
CLOSED.
HW-11
HINGES (AS SPECIFIED)
1 PANIC HARDWARE LD-9947-EO (Grade 1, Type 8, Function 01)1 PANIC HARDWARE LD-9947-NL (Grade 1, Type 8, Function
03)1 INTERCHANGEABLE CORE (CYLINDER AS REQUIRED)
2 SURFACE CLOSER 4050A SCUSH (CO2011/CO2021)
2 KICK PLATE 8400 10" X 1" LDW B-CS (J102)
1 RAIN DRIP 142 (R3Y976)
1 SET WEATHERSTRIP 429 (R3E164)
1 MEETING STILE SEAL 8193 X 8193 (R3A436, R3A166, R3A735)
2 DOOR SWEEP 8198 (R3A536)
1 THRESHOLD (PROFILE AS REQUIRED) (J32100, J32130)
2 DOOR CONTACT (BY SECURITY SUPPLIER)
FUNCTION: (NL) LATCHBOLT RETRACTED INSIDE BY EXIT DEVICE PUSH PAD AND
OUTSIDE BY KEY IN CYLINDER. DOOR LOCKS WHEN KEY IS REMOVED AND DOOR IS
CLOSED.
Amdt. #0002 ******************************************************
HW-11A
HINGES (AS SPECIFIED)
1 KEYED REMOVABLE MULLION KR-4954 STAB
1 PANIC HARDWARE LD-99-EO
SECTION 08 71 00 Page 17
AMENDMENT 0002
1 PANIC HARDWARE LD-99-NL
1 INTERCHANGEABLE CORE (CYLINDER AS REQUIRED)
2 SURFACE CLOSER 4050A SCUSH
2 KICK PLATE 8400 10" X 1" LDW B-CS
1 RAIN DRIP 142
1 SEALS 700NA
1 MEETING STILE SEAL 8193 X 8193
2 DOOR SWEEP 8198
1 CAST THRESHOLD 1/2" X 5" 425HD
2 DOOR CONTACT (BY SECURITY SUPPLIER)
FUNCTION: (NL) LATCHBOLT RETRACTED INSIDE BY EXIT DEVICE PUSH PAD AND
OUTSIDE BY KEY IN CYLINDER. DOOR LOCKS WHEN KEY IS REMOVED AND DOOR IS
CLOSED.
******************************************************** Amdt. #0002
HW-12
HINGES (AS SPECIFIED)
1 FIRE EXIT HARDWARE 99-L-F X 499F (Grade 1, Type 1, Function 08)
1 INTERCHANGEABLE CORE (CYLINDER AS REQUIRED)
1 SURFACE CLOSER 4050A SCUSH (CO2011/CO2021)
1 KICK PLATE 8400 10" X 2" LDW B-CS (J102)
1 SMOKE SEALS 188S (AT RATED OR SMOKE & DRAFT CONTROL
DRS ONLY) (R0E151)
FUNCTION: (L) LATCHBOLT RETRACTED INSIDE BY EXIT DEVICE PUSH PAD AND
OUTSIDE BY LEVER. KEY IN EXTERIOR CYLINDER LOCKS OR UNLOCKS LEVER.
HW-13
1 CONTINUOUS HINGE 700 EPT (A51031B)
1 POWER TRANSFER EPT10
1 ELEC PANIC HARDWARE QEL-99-NL-OP (Grade 1, Type 1, Function 03)
1 INTERCHANGEABLE CORE (CYLINDER AS REQUIRED)
1 90 DEG OFFSET PULL 8190 10"
1 OH STOP 100S (C01541)
1 SURFACE CLOSER 4050A EDA (CO2021)
1 RAIN DRIP 142 (R3Y976)
1 SET WEATHERSTRIP (BY DR/FR SUPPLIER)
SECTION 08 71 00 Page 18
AMENDMENT 0002
1 DOOR SWEEP (BRUSH) 8192 (R3A436, R3A735)
1 THRESHOLD (PROFILE AS REQUIRED) (J32100, J32130)
1 CREDENTIAL READER (BY SECURITY SUPPLIER)
1 DOOR CONTACT (BY SECURITY SUPPLIER)
1 POWER SUPPLY (BY ELECTRICAL)
1 WIRING DIAGRAMS RISER & POINT-TO-POINT (BY HARDWARE
SUPPLIER)
FUNCTION: (NL) LATCHBOLT RETRACTED INSIDE BY EXIT DEVICE PUSH PAD AND
OUTSIDE BY KEY IN CYLINDER. DOOR LOCKS WHEN KEY IS REMOVED AND DOOR IS
CLOSED. A VALID CREDENTIAL WILL UNLOCK THE DOOR.
HW-14
1 CONTINUOUS HINGE 700 (A51031B)
1 PANIC HARDWARE CD-99-NL-OP (Grade 1, Type 1, Function
03)2 INTERCHANGEABLE CORE (CYLINDER AS REQUIRED)
1 90 DEG OFFSET PULL 8190 10"
1 OH STOP 100S (C01541)
SURFACE CLOSER 4050A EDA (CO2021)
FUNCTION: (NL) Latchbolt retracted inside by exit device push pad and outside by key in cylinder. Door locks when key is removed and door is closed. Access from exterior when exit device push pad is dogged down.
HW-15
All hardware by door supplier.
HW-16
1 HINGES (AS SPECIFIED)
1 PUSH PLATE 8200 6" X 16"
1 PULL PLATE 8303 10" 4" X 16"
1 SURFACE CLOSER 4050A / 4050A EDA (CO2011/CO2021)
1 KICK PLATE 8400 10" X 2" LDW B-CS (J102)
1 WALL STOP WS406/407CVX (L52101)
1 SEALS 188S (R0E151)
1 DOOR SWEEP (BRUSH) 8192 (R3A436, R3A735)
1 THRESHOLD (PROFILE AS REQUIRED) (J32100, J32130)
SECTION 08 71 00 Page 19
AMENDMENT 0002
FUNCTION: Push/Pull
-- End of Section --
SECTION 08 71 00 Page 20
AMENDMENT 0002
SECTION 25 10 10
AMENDMENT 0002
Amdt. #0002 ****************************************************
UTILITY MONITORING AND CONTROL SYSTEM (UMCS) FRONT END AND INTEGRATION
02/19, CHG 1: 05/21
PART 1 GENERAL
1.1 SUMMARY
Provide a Utility Monitoring and Control System (UMCS) which performs supervisory monitoring and supervisory control of base-wide building control systems and utility control systems using: Niagara Framework with Fox protocol as indicated and shown. Integrate field control systems installed per Section 23 09 23.02 BACNET DIRECT DIGITAL CONTROL FOR HVAC AND OTHER BUILDING CONTROL SYSTEMS to the UMCS via Niagara Framework Supervisory Gateways as specified.
1.1.1 System Requirements
Provide a UMCS as specified and indicated, and in accordance with the following characteristics:
1.1.1.1 General System Requirements
a. The system performs supervisory monitoring and control functions including but not limited to Scheduling, Alarm Handling, Trending, Overrides, Report Generation, and Electrical Demand Limiting as specified.
b. The system includes a Graphical User Interface which allows for graphical navigation between systems, graphical representations of systems, access to real-time data for systems, ability to override points in a system, and access to all supervisory monitoring and control functions.
c. All software used by the UMCS and all software used to install and configure the UMCS is licensed to and delivered to the installation.
d. All necessary documentation, configuration information, configuration tools, programs, drivers, and other software is licensed to and otherwise remains with the Government such that the Government or their agents are able to repair, replace, upgrade, and expand the system without subsequent or future dependence on the Contractor. Software licenses must not require periodic fees and must be valid in perpetuity.
e. Provide sufficient documentation and data, including rights to documentation and data, such that the Government or their agents can execute work to repair, replace, upgrade, and expand the system without subsequent or future dependence on the Contractor.
f. The UMCS interfaces directly to ASHRAE 135, CEA-709.1-D, MODBUS Protocol, MODBUS TCP/IP, OPC DA, and Niagara Framework field control systems as specified and may interface to field control systems using other
SECTION 25 10 10 Page 1
AMENDMENT 0002
protocols via an M&C Software protocol driver or a Gateway.
g. For UMCS systems with Monitoring and Control Software functionality implemented in Monitoring and Control (M&C) Controller Hardware, provide sufficient additional controller hardware to support the full capacity requirements as specified.
h. All Niagara Framework components have an unrestricted interoperability license with a Niagara Compatibility Statement (NiCS) following the Tridium Open NiCS Specification and have a value of "ALL" for "Station Compatibility In", "Station Compatibility Out", "Tool Compatibility In" and "Tool Compatibility Out". Note that this will result in the following entries in the license.dat file:
accept.station.in="*" accept.station.out="*" accept.wb.in="*" accept.wb.out="*"
i. The version of Niagara Framework used on this project must be Version
4.0 or later.
1.1.1.2 Niagara Framework Requirements
The UMCS must use the Niagara Framework and must communicate with Niagara Framework field control systems using the Fox protocol over the Government furnished IP network as indicated and specified.
1.1.2 Symbols, Definition and Abbreviations
Use symbols, definitions, and engineering unit abbreviations indicated in the contract drawings for displays, submittals and reports. For symbols, definitions and abbreviations not in the contract drawings use terms conforming at a minimum to IEEE Stds Dictionary and the ASHRAE FUN IP, as applicable.
1.1.3 System Units and Accuracy
Use English (inch-pound) units for displays, print-outs and calculations.
Perform calculations with an accuracy of at least three significant figures. For displays and printouts present values to at least three significant figures.
1.1.4 Data Packages/Submittals Requirements
Technical data packages consisting of computer software and technical data (meaning technical data which relates to computer software) which are specifically identified in this project and which may be defined/required in other specifications must be delivered strictly in accordance with the CONTRACT CLAUSES and in accordance with the Contract Data Requirements List, DD Form 1423. Data delivered must be identified by reference to the particular specification paragraph against which it is furnished. All submittals not specified as technical data packages are considered shop drawings under the Federal Acquisition Regulation Supplement (FARS) and must contain no proprietary information and must be delivered with unrestricted rights.
1.2 RELATED SECTIONS
Cybersecurity requirements related to this Section are specified in a
SECTION 25 10 10 Page 2
AMENDMENT 0002
separate cybersecurity specification derived from UFGS 25 05 11. Section 25 05 11.01 CBERSECURITY FOR LOW-IMPACT HVAC CONTROL SYSTEMS specifies cybersecurity requirements related to this Section.
1.3 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
AMERICAN SOCIETY OF HEATING, REFRIGERATING AND AIR-CONDITIONING
ENGINEERS (ASHRAE)
ASHRAE 135 (2020; Interpretation 1-8 2021; Errata 1-2 2021; Addenda CD 2021; Addenda BV-CE 2022;
Interpretation 9-12 2022; Interpretation 13-24 2023; Addenda BV-CF 2023; Errata 3 2023) BACnet—A Data Communication Protocol for Building Automation and Control Networks
ASHRAE FUN IP (2021) Fundamentals Handbook, I-P Edition
CONSUMER ELECTRONICS ASSOCIATION (CEA)
CEA-709.1-D (2014) Control Network Protocol Specification
CEA-709.3 (1999; R 2015) Free-Topology Twisted-Pair Channel Specification
CEA-852-C (2014) Tunneling Device Area Network Protocols Over Internet Protocol Channels
INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)
IEEE 1815 (2015; CORR 2016) Exchanging Information Between Networks Implementing IEC 61850 and IEEE Std 1815
IEEE C62.41 (1991; R 1995) Recommended Practice on Surge Voltages in Low-Voltage AC Power Circuits
IEEE Stds Dictionary (2009) IEEE Standards Dictionary: Glossary of Terms & Definitions
INTERNET ENGINEERING TASK FORCE (IETF)
IETF RFC 4361 (2006) Node-specific Client Identifiers for Dynamic Host Configuration Protocol Version Four (DHCPv4)
IETF RFC 7465 (2015) Prohibiting RC4 Cipher Suites
RFC 821 (2001) Simple Mail Transfer Protocol (SMTP)
SECTION 25 10 10 Page 3
AMENDMENT 0002
LONMARK INTERNATIONAL (LonMark)
LonMark Interoperability Guide (2005) LonMark Application-Layer Interoperability Guide and LonMark Layer 1-6 Interoperability Guide; Version 3.4
LonMark SNVT List (2014) LonMark SNVT Master List; Version 15
LonMark XIF Guide (2001) LonMark External Interface File Reference Guide; Revision 4.402
MODBUS ORGANIZATION, INC (MODBUS)
MODBUS Protocol (2012) Modbus Application Protocol Specification; Version 1.1b3
MODBUS TCP/IP (2006) Modbus Messaging on TCP/IP Implementation Guide; Version V1.0b
NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)
NEMA 250 (2020) Enclosures for Electrical Equipment (1000 Volts Maximum)
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 70 (2023) National Electrical Code
NFPA 262 (2023) Standard Method of Test for Flame Travel and Smoke of Wires and Cables for Use in Air-Handling Spaces
OPC FOUNDATION (OPC)
OPC DA (Ver 3.0; Errata) OPC Data Access (DA)
TELECOMMUNICATIONS INDUSTRY ASSOCIATION (TIA)
TIA-568.1 (2020e) Commercial Building Telecommunications Infrastructure Standard
TIA-606 (2021d) Administration Standard for Telecommunications Infrastructure
TIA-607 (2019d) Generic Telecommunications Bonding and Grounding (Earthing) for Customer Premises
TRIDIUM, INC (TRIDIUM)
Niagara Framework (2021) NiagaraAX User's Guide
Tridium Open NiCS (2021) Understanding the NiagaraAX Compatibility Statement (NiCS)
U.S. FEDERAL COMMUNICATIONS COMMISSION (FCC)
FCC EMC (2002) FCC Electromagnetic Compliance…
This is the start of the file's text. The full file is on GovTribe.