W912QR23R0022_CUI_SID-0002.pdf

PDF 4 MB Posted

Attached to
Wright-Patterson AFB Air Handling Unit 5
Solicitation number
W912QR23R0022
Issued by

View the file

Other files

Show all 12

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Controlled by: USACE Controlled by: Louisville District CUI Category(ies): General Critical Infrastucture Information Distribution/Dissemination Control: FEDCON POC: Alexa Dukes Contracting Specialist alexa.l.dukes@usace.army.mil 502.315.3000

Materials shall be submitted to potential offerors currently certified in the Joint Certification Program (JCP) only.

W912QR23R0022_CUI_SID-0002

Solicitation For Controlled Unclassified Information (CUI)

F/10856 - Replace AHU 5, WPAFB, OH

P2: 469978 Design-Bid-Build

Specifications -

STRUCTURAL INTERIOR DESIGN (SID)

28 February 2023

W912QR23R0022

Corrected Final Submittal

16 March 2023

W912QR23R0022-0002

Certified Final Submittal

ARIMS: 200A

Disposition: Maintain for 15yrs after construction

REPLACE AHU-5

WRIGHT PATTERSON AIR FORCE BASE, OHIO

SOLICITATION PACKAGE

STRUCTURAL INTERIOR DESIGN (SID)

FEBRUARY 2023

PROJECT NO. 110384

ZHTV090034

CUI

R ep la ce

A H

U -5

W rig ht -P at te rs on

A ir

Fo rc e B as e, O hi o

TABLE OF CONTENTS:

FLOOR FINISHES

WALL FINISHES

CEILING FINISHES

DRAWINGS

CUI

la ce

A H

U -5

W rig ht -P at te rs on

A ir

Fo rc e B as e, O hi o

FLOOR FINISHES

CPT-1

DESCRIPTION: MODULAR CARPET, 24” X 24”

MANUFACTURER: SHAW CONTRACT

PRODUCT / STYLE: DISPERSE 59576, QUARTER TURN

COLOR: MAGNETIC FIELDS

CPT-1

INSTALLATION IMAGES

CUI

la ce

A H

U -5

W rig ht -P at te rs on

A ir

Fo rc e B as e, O hi o

FLOOR FINISHES

EF-1

DESCRIPTION: STANDARD RESINOUS FLOORING

MANUFACTURER: SHERWIN WILLIAMS

PRODUCT / STYLE: 2 COAT / SILICON SAND

COLOR: COLOR MATCH TO SHERWIN WILLIAMS SW4031 STRUCTURAL GRAY

RF-1

DESCRIPTION: VINYL COMPOSITION TILE 12”X12”

MANUFACTURER: ARMSTRONG

PRODUCT / STYLE: IMPERIAL TEXTURE STANDARD EXCELON

COLOR: FORTRESSWHITE 51839

CUI

la ce

A H

U -5

W rig ht -P at te rs on

A ir

Fo rc e B as e, O hi o

WALL FINISHES

PA-1

DESCRIPTION: PAINT, EGGSHELL

MANUFACTURER: SHERWIN WILLIAMS

PRODUCT / STYLE: SW7649

COLOR: SILVERPLATE

PA-2

DESCRIPTION: PAINT, SEMI-GLOSS

MANUFACTURER: BENJAMIN MOORE

PRODUCT / STYLE: 2134-30

COLOR: IRON MOUNTAIN

PA-3

DESCRIPTION: PAINT, EGGSHELL

MANUFACTURER: SHERWIN WILLIAMS

PRODUCT / STYLE: SW6530

COLOR: REVEL BLUE

RB-1

DESCRIPTION: RUBBER BASE, 4”

MANUFACTURER: ROPPE

PRODUCT / STYLE: 193, COVE

COLOR: 98 BLACK-BROWN

CG-1

DESCRIPTION: CORNER GUARD

MANUFACTURER: CONSTRUCTION

SPECIALTIES

PRODUCT / STYLE: ACROVYN SM-20

COLOR: FOLKSTONE 927

AP-1

DESCRIPTION: ACOUSTICAL PANEL

MANUFACTURER: CARNEGIE

PRODUCT / STYLE: XOREL-HAVANA

COLOR: 6249 NO.5

CUI

la ce

A H

U -5

W rig ht -P at te rs on

A ir

Fo rc e B as e, O hi o

CEILING FINISHES

ACT-1

DESCRIPTION: 24” X 48”ACOUSTICAL CEILING TILE

MANUFACTURER: ARMSTRONG

PRODUCT / STYLE: FINE FISSURED, SCHOOL ZONE, SQUARE LAY-IN

COLOR: 1714 WHITE

CUI

DRAWINGS

REPLACE AHU-5

WRIGHT PATTERSON AIR FORCE BASE, OHIO

CUI

P

2 3 4 5 6 7 8 9 10 11 12 13 14 15

G

H

J

K

KL

L

M

N

Q

W220

W220A

W220D

W212 W210

W209

W299

W298

W203E

W203

W203D

W203C

W204

/2

/4

W1

W227

W228

W226A W225B

W219 W226

W209A

W209B

W209C

W209D

W209E

W209F

W209G

W209H

W203A

W221A

W221B W221C

W221D W221E W221F

W202 W201

W201B

W201AW202B

W202A

W2

W279 W253

W280

A8

A-522_5

W225A

/8

EQ EQ

OTS

EXISTING CEILING GRID

APPROXIMATE LOCATIONN

O W O R K

EXISTING CEILING GRID

APPROXIMATE LOCATION N

O W O R K

EXISTING ACOUSTICAL

CEILING TO REMAIN

EXISTING ACOUSTICAL

CEILING TO REMAIN

INSTALL NEW ACOUSTICAL

CEILING AT SAME HEIGHT

AS DEMOED GYPSUM

BOARD CEILING

INSTALL NEW ACOUSTICAL

CEILING AT SAME HEIGHT

AS DEMOED GYPSUM

BOARD CEILING

1.1.1.

1.1.1.

1.

1.

1. 1.

1. 1.

1.

1. 1.

1.

1.

1.

1.

1.

1.

1.

1.

1.

1.

1.

W5

9' - 0"EXPOSED CEILING

GYPSUM BOARD CEILING

NEW 2' x 4' ACOUSTICAL CEILING TILE

2' x 2' EMERGENCY LIGHT FIXTURE - RECESSED

2' x 2' LIGHT FIXTURE - RECESSED

2' x 4' EMERGENCY LIGHT FIXTURE - RECESSED

2' x 4' LIGHT FIXTURE - RECESSED

CEILING HEIGHT ABOVE FINISH FLOOR

HVAC AIR SUPPLY GRILLE

HVAC LINEAR AIR SUPPLY GRILLE

HVAC EXHAUST OR RETURN GRILLE

COLUMN OR POWER POLE PENETRATING CEILING

EXIT SIGNAGE

GENERAL NOTES:

1. PROVIDE NEW 2X4 CEILING GRID AND CEILING TILES UNLESS OTHERWISE NOTED. REFER TO RCP

FOR LOCATIONS.

2. REMOVE AND REPLACE PLASTER CEILINGS AS REQUIRED TO MATCH EXISTING, INCLUDING LIGHTS

AND DIFFUSERS, AFTER COMPLETION OF MECHANICAL WORK IN PLENUM. PAINT CEILING TO MATCH

EXISTING. ACCESS PANELS TO BE THE SAME SIZE AND IN THE SAME PLACE AS BEFORE

CONSTRUCTION.

3. ALL NEW CEILINGS TO MATCH EXISTING CEILING HEIGHTS UNLESS OTHERWISE NOTED.

4. VERIFY LIGHT FIXTURE SIZE AND TYPE WITH ELECTRICAL DRAWINGS.

5. REFER TO SHEETS A-001_5 AND A-002_5 FOR SECURE AREA PERIMETER WALL LOCATIONS.

6. ALL CEILING AT 9'-0" UNLESS NOTED OTHERWISE.

NOT IN

SCOPE

SCOPE LEGEND

REFLECTED CEILING PLAN NOTES:

1. CENTER CEILING GRID IN ROOM AS SHOWN.

KEYPLAN

NOT TO SCALE

A B

D E

S

IG

N E

D B

Y

D R

A W

N B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

X

S O

L

IC

IT

A

T

IO

N N

O

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S L O

U

IS

V

IL

L E

D

IS

T R

IC

T

D

R M

A R

T

IN

L U

T H

E R

K

IN

G J

R P

L

L O

U

IS

V

IL

L E

K

Y

W

A R

D P

A R

K W

A Y

K

A N

S A

S C

IT

Y

M

O

SHEET ID

R E

A D

Y T

O A

D V

E R

T

IS

E

US ARMY CORPS

OF ENGINEERS

LOUISVILLE DISTRICT

C H

E C

K E

D B

Y

D

2 3

C

A

B

6 7 8 9

E

F

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

C U

I

CUI

R E

P L

A C

E A

H U

-5 P

N

Z H

T V

-1

W

R

IG

H T

-P A

T T

E R

S O

N A

F B

O

H

IO

-2

-2

G J O

H N

S O

N

A-151_5

B K

E N

N A

L E

Y

W N

E E

D L E

R E

F L E

C T

E D

C E

IL

IN

G S

E C

O N

D F

L O

O R

P L A

N

N E

W E

V

A L E

Z Q

U E

Z

SCALE: 3/32" = 1'-0"A1

SECOND FLOOR REFLECTED CEILING PLAN

0 8' 16' 24'

PLAN

NORTH

A R

E A

A

A R

E A

B

M A

R K

D E

S C

R

IP

T

IO

N D

A T

E

02-24-23

ROBERT J KENNALEY

ARCHITECT

LICENSE NO. A-6476

CUI

2 3 4 5 6 7 8

G

H

J

K

KL

L

M

N

W1

W253

A-704_5 A3A1

CONF ROOM

W221A

CONF ROOM

W221B

COLLAB ROOM

W221C

CONF ROOM

W221D

CONF ROOM

W221E

COLLAB ROOM

W221F

CONF ROOM

W220A

CONF ROOM

W220D

ELEC

W219

ELEC

W225B

W280

OPEN OFFICE

W220

CG1

CG1

CG1

S201

S202S203S204

S207 S206 S205

S208

S225

PA-3

SIM SIM

A-704_5A6

STOP NEW FINISHES AT

EXISTING CONTROL

JOINT.

EF-1

VEST

W226

TOILET

W226A

CORRIDOR

W225A

DN

W287

W227

W228

EX-RF

CPT-1 EX-RF

CPT-1

EX-RF

ACOUSTICAL WALL

PANELS

1. SEE ROOM FINISH SCHEDULE FOR FLOOR AND WALL FINISHES NOT INDICATED ON

FLOOR PLANS.

2. SEE SPECIFICATION FOR FLOORING MATERIAL INSTALLATION REQUIREMENTS,

COORDINATION OF FLOORING ACCESSORIES AND TRANSITION STRIPS BETWEEN

DIFFERENT FLOOR CONDITIONS. PROVIDE THRESHOLDS PER SPECIFICATIONS AND

DRAWINGS.

3. FOR FLOORING MATERIAL TRANSITIONS WHICH OCCUR AT DOORWAYS, TERMINATE

FINISH TRANSITION AND TRANSITION STRIP UNDER THE DOOR AT THE DOOR STOP

OR CENTER UNDER THE CLOSED DOOR.

4. WHERE TWO OR MORE PAINTED FINISHES OCCUR ON THE SAME WALL FACE OR

CEILING SURFACE, A PAINT TRANSITION REVEAL IS TO PROVIDED AS INDICATED ON

THE DRAWINGS.

GENERAL FINISH PLAN NOTES:

GENERAL SIGNAGE PLACEMENT PLAN NOTES:

1. REFER TO SIGNAGE SCHEDULE AND DETAIL DRAWINGS FOR ADDITIONAL

INFORMATION.

2. REFER TO SIGNAGE SCHEDULE FOR SIGN LOCATION TAG, DOOR LOCATION,

SIGN TYPE, SIGN TEXT NUMBER, AND PLACEHOLDER MESSAGE TEXT.

3. REFER TO SIGNAGE MOUNTING HEIGHTS ON SIGNAGE DETAIL DRAWINGS.

SIGNS TO BE WALL-MOUNTED ON THE LATCH SIDE OF DOOR OR AS INDICATED.

HEIGHTS, CLEARANCES, AND CONFIGURATIONS SHOWN ARE TYPICAL AND

MUST APPLY IN ALL INSTANCES UNLESS NOTED OTHERWISE.

4. INTERIOR SIGNAGE MUST COMPLY WITH UFC REQUIREMENTS, GUIDANCE FOR

AIR FORCE SIGNAGE AS FOUND IN UFC 3-120-01 "SIGN STANDARDS, WITH

CHANGE 3" AND BASE STANDARDS.

5. CONTRACTOR MUST ENSURE SIGNAGE ROOM NUMBER COORDINATE WITH NEW

ROOM NUMBERS OR SIGNAGE MUST BE REPLACED TO MATCH EXISTING. RE:

A-703_5 FOR SCHEDULE OF SIGNS.

NOT IN

SCOPE

SCOPE LEGEND

KEYPLAN

NOT TO SCALE

A B

D E

S

IG

N E

D B

Y

D R

A W

N B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

X

S O

L

IC

IT

A

T

IO

N N

O

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S L O

U

IS

V

IL

L E

D

IS

T R

IC

T

D

R M

A R

T

IN

L U

T H

E R

K

IN

G J

R P

L

L O

U

IS

V

IL

L E

K

Y

W

A R

D P

A R

K W

A Y

K

A N

S A

S C

IT

Y

M

O

SHEET ID

R E

A D

Y T

O A

D V

E R

T

IS

E

US ARMY CORPS

OF ENGINEERS

LOUISVILLE DISTRICT

C H

E C

K E

D B

Y

D

2 3

C

A

B

6 7 8 9

E

F

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

C U

I

CUI

R E

P L A

C E

A H

U -5

P N

Z

H T

V -1

W R

IG

H

T -P

A T

T E

R S

O N

A F

B

O H

IO

-2

-2

G J O

H N

S O

N

A-701_5

T L E

E -W

E L L E

R

S B

R A

N N

A N

S E

C O

N D

F L O

O R

F

IN

IS

H

A N

D S

IG

N

A G

E P

L A

N

A R

E A

A R

L A

S T

E R

SCALE: 1/8" = 1'-0"A1

SECOND FLOOR FINISH AND SIGNAGE PLAN - AREA A

0 4' 8' 16'

A R

E A

A

A R

E A

B PLAN

NORTH

M A

R K

D E

S C

R

IP

T

IO

N D

A T

E

02-24-23

ROBERT J KENNALEY

ARCHITECT

LICENSE NO. A-6476

CUI

8 9 10 11 12 13 14 15

J

K

KL

L

M

N

Q

W2

OPEN OFFICE

W298

MECHANICAL

W299

OFFICE

W210

OFFICE

W212

CORRIDOR

W208

W279

CONF ROOM

W209A

CONF ROOM

W209B

OFFICE

W209C

OFFICE

W209D

OFFICE

W209E

OFFICE

W209F

OFFICE

W209G

OFFICE

W209H

OFFICE

W203D

CONF ROOM

W204

CONF ROOM

W203E

CONF ROOM

W220D

TOILET

W201

VEST

W201A

VEST

W201B

COLLAB ROOM

W203

OPEN OFFICE

W209

BREAK

W203A

CG1 CG1

CG1CG1CG1CG1

CG1

CG1CG1

CG1CG1

OFFICE

W203C

S209

S210

S211

S212

S213

S214

S215

S216

S217

S218

S219

S220

S221

S222

S223 S224

CG1

CG1

CG1

CG1

CG1

CG1

CG1

PA-3

PA-3

PA-3

PA-3

PA-3

A-704_5 A3

A1

A3

SIMSIM

A-704_5A3

SIM

STOP NEW FINISHES AT

EXISTING CONTROL JOINT.

EF-1

W202

W202A W202B

CORRIDOR

W280

CPT-1

EX-RF

CPT-1EX-RF

CPT-1

EX-RF

ACOUSTICAL

WALL PANELS

ACOUSTICAL

WALL PANELS

ACOUSTICAL

WALL PANELS

SIM

1. SEE ROOM FINISH SCHEDULE FOR FLOOR AND WALL FINISHES NOT INDICATED ON

FLOOR PLANS.

2. SEE SPECIFICATION FOR FLOORING MATERIAL INSTALLATION REQUIREMENTS,

COORDINATION OF FLOORING ACCESSORIES AND TRANSITION STRIPS BETWEEN

DIFFERENT FLOOR CONDITIONS. PROVIDE THRESHOLDS PER SPECIFICATIONS AND

DRAWINGS.

3. FOR FLOORING MATERIAL TRANSITIONS WHICH OCCUR AT DOORWAYS, TERMINATE

FINISH TRANSITION AND TRANSITION STRIP UNDER THE DOOR AT THE DOOR STOP

OR CENTER UNDER THE CLOSED DOOR.

4. WHERE TWO OR MORE PAINTED FINISHES OCCUR ON THE SAME WALL FACE OR

CEILING SURFACE, A PAINT TRANSITION REVEAL IS TO PROVIDED AS INDICATED ON

THE DRAWINGS.

GENERAL FINISH PLAN NOTES:

GENERAL SIGNAGE PLACEMENT PLAN NOTES:

1. REFER TO SIGNAGE SCHEDULE AND DETAIL DRAWINGS FOR ADDITIONAL

INFORMATION.

2. REFER TO SIGNAGE SCHEDULE FOR SIGN LOCATION TAG, DOOR LOCATION,

SIGN TYPE, SIGN TEXT NUMBER, AND PLACEHOLDER MESSAGE TEXT.

3. REFER TO SIGNAGE MOUNTING HEIGHTS ON SIGNAGE DETAIL DRAWINGS.

SIGNS TO BE WALL-MOUNTED ON THE LATCH SIDE OF DOOR OR AS INDICATED.

HEIGHTS, CLEARANCES, AND CONFIGURATIONS SHOWN ARE TYPICAL AND

MUST APPLY IN ALL INSTANCES UNLESS NOTED OTHERWISE.

4. INTERIOR SIGNAGE MUST COMPLY WITH UFC REQUIREMENTS, GUIDANCE FOR

AIR FORCE SIGNAGE AS FOUND IN UFC 3-120-01 "SIGN STANDARDS, WITH

CHANGE 3" AND BASE STANDARDS.

5. CONTRACTOR MUST ENSURE SIGNAGE ROOM NUMBER COORDINATE WITH NEW

ROOM NUMBERS OR SIGNAGE MUST BE REPLACED TO MATCH EXISTING. RE:

A-703_5 FOR SCHEDULE OF SIGNS.

NOT IN

SCOPE

SCOPE LEGEND

KEYPLAN

NOT TO SCALE

A B

D E

S

IG

N E

D B

Y

D R

A W

N B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

X

S O

L

IC

IT

A

T

IO

N N

O

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S L O

U

IS

V

IL

L E

D

IS

T R

IC

T

D

R M

A R

T

IN

L U

T H

E R

K

IN

G J

R P

L

L O

U

IS

V

IL

L E

K

Y

W

A R

D P

A R

K W

A Y

K

A N

S A

S C

IT

Y

M

O

SHEET ID

R E

A D

Y T

O A

D V

E R

T

IS

E

US ARMY CORPS

OF ENGINEERS

LOUISVILLE DISTRICT

C H

E C

K E

D B

Y

D

2 3

C

A

B

6 7 8 9

E

F

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

C U

I

CUI

R E

P L A

C E

A H

U -5

P N

Z

H T

V -1

W R

IG

H

T -P

A T

T E

R S

O N

A F

B

O H

IO

-2

-2

G J O

H N

S O

N

A-702_5

T L E

E -W

E L L E

R

S B

R A

N N

A N

S E

C O

N D

F L O

O R

F

IN

IS

H

A N

D S

IG

N

A G

E P

L A

N

A R

E A

B R

L A

S T

E R

SCALE: 1/8" = 1'-0"A1

SECOND FLOOR FINISH AND SIGNAGE PLAN - AREA B

0 4' 8' 16'

A R

E A

A

A R

E A

B

PLAN

NORTH

M A

R K

D E

S C

R

IP

T

IO

N D

A T

E

02-24-23

ROBERT J KENNALEY

ARCHITECT

LICENSE NO. A-6476

CUI

1. REFER TO FINISH LEGEND FOR BASIS OF DESIGN INTERIOR FINISH

MATERIALS. FINISHES WHICH MATCH TECHNICAL SPECIFICATIONS ARE

CONSIDERED EQUAL AND MAY BE CONSIDERED FOR APPROVAL. MATCH

EXISTING PATTERNS AND FINISHES IN KIND.

2. REFER TO SPECIFICATIONS FOR FINISH TECHNICAL REQUIREMENTS.

3. REFER TO ELECTRICAL DRAWINGS, MECHANICAL DRAWINGS, AND

COMMUNICATION DRAWINGS FOR COORDINATION OF BUILDING FINISHES

TO BUILDING SYSTEMS.

4. ALL PAINTING MUST BE COMPLETED BY CONTRACTOR DURING OFF-SHIFT

HOURS.

5. CONTRACTOR TO ELECTROSTATICALLY PAINT ALL NEW AND EXISTING

METAL DOORS AND HAND ROLL DOOR FRAMES WITHIN PROJECT

BOUNDARY. COLOR TO MATCH FACILITY STANDARD: PA-2.

6. CONTRACTOR TO PAINT ALL WALLS IN AHU-5 AREA.

7. PAINT BOTH SIDES OF WALL IN MECHANICAL ROOM W299 ONE COAT

WHITE, INCLUDING ABOVE CEILING. PAINT SECURE SPACE EXTERIOR

BOUNDARY WALLS WITHIN PROJECT AREA, INCLUDING ABOVE CEILING.

8. RE-LABEL JUNCTION BOXES AND OTHER EQUIPMENT IN MECHANICAL

ROOM W299 WHERE LABELS WILL BE PAINTED OVER.

9. IN MECHANICAL ROOM W299, PAINT MISC. STEEL, EXISTING LOUVER

BLANK OFF PANEL TO REMAIN. TEMPORARILY REMOVE PANEL AND RE-

INSTALL AFTER INSTALLATION OF AIR HANDLING UNIT.

10. IN MECHANICAL ROOM W299, EXISTING CONCRETE FLOOR TO BE

PROPERLY PREPARED TO RECEIVE PAINTED FINISH AS SCHEDULED.

PREPARE FLOOR SURFACE TO REMOVE ALL DIRT, OIL, GREASE,

POWDERY AND PEELING PAINT, AND OTHER CONTAMINANTS. ETCHING,

BEAD BLASTING OR OTHER APPROVED MEANS WILL BE REQUIRED.

REPAIR ALL CRACKS AND OTHER SURFACE IMPERFECTIONS WITH HIGH

QUALITY COMPOUNDS. APPLY 2 COATS LOW VOC EPOXY PAINT, PER

MANUFACTURER'S RECOMMENDATION. APPLY SILICON SAND TO

MIXTURE FOR SLIP RESISTANCE. COLOR MUST BE BY SHERWIN WILLIAMS

APPROVED BY WPAFB. MOISTURE LEVELS MUST BE TESTED AND AT

ACCEPTABLE LEVELS PRIOR TO PAINTING, PER MANUFACTURER'S

RECOMMENDATION.

11. IN MECHANICAL ROOM W299, EXISTING CEILING TO REMAIN. PATCH,

CLEAN, AND PAINT. PAINT WALLS SAME COLOR AS CEILING.

12. PROVIDE CORNER GUARDS (CG-1) AS INDICATED ON PLANS.

13. ALL SECURE AREA PERIMETER WALLS MUST BE PAINTED ABOVE CEILING

TO UNDERSIDE OF DECK ABOVE, AND BELOW RAISED ACCESS FLOOR TO

FLOOR SLAB BELOW.

GENERAL ROOM FINISH SCHEDULE NOTES:GENERAL SIGNAGE SCHEDULE NOTES:

1. REFER TO SPECIFICATION SECTION 10 14 00.20 INTERIOR

SIGNAGE FOR BASIS OF DESIGN OR EQUIVALENT, PRODUCT

STYLE AND COLOR.

2. REFER TO SIGNAGE PLACEMENT DRAWINGS FOR LOCATION

OF INTERIOR SIGNS.

3. REFER TO SIGNAGE DETAILS FOR SIGNAGE CONSTRUCTION

AND MOUNTING ELEVATION.

4. REFER TO ARCHITECTURAL DRAWINGS FOR COORDINATION

OF SIGNAGE INSTALLATION TO WALL CONSTRUCTION.

SIGNAGE MUST BE ANCHORED THRU THE SURFACE APPLIED

WALL FINISHES TO THE SUBSTRATE WALL.

5. ALL HARDWARE/MOUNTING ATTACHMENTS TO BE

CONCEALED AND APPROPRIATE FOR THE RECEIVING

BUILDING SURFACE.

6. ALL SIGNAGE MUST COMPLY WITH THE MOST CURRENT

VERSION OF THE ARCHITECTURAL BARRIERS ACT (ABA).

7. INSTALL FIRE EXTINGUISHER IDENTIFICATION SIGN ABOVE

ALL FIRE EXTINGUISHER CABINETS AND WALL BRACKET

MOUNTED EXTINGUISHERS. SEE LIFE SAFETY PLANS FOR

FIRE EXTINGUISHER LOCATIONS.

8. GENERAL CONTRACTOR IS RESPONSIBLE FOR

COORDINATING WITH SIGNAGE MANUFACTURER(S) TO

PROVIDE ANY ADDITIONAL SIGNAGE AS REQUIRED BY

GOVERNING MUNICIPALITY AT THE SITE LOCATION.

9. ALL MESSAGE TEXT AS SHOWN ON THE SIGN SCHEDULE IS A

PLACE HOLDER ONLY AND IS NOT THE FINAL TEXT

MESSAGE. ALL MESSAGE TEXT MUST BE CONFIRMED BY

GOVERNMENT END USER PRIOR TO SIGNAGE SHOP

DRAWINGS.

D E

S

IG

N E

D B

Y

D R

A W

N B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

X

S O

L

IC

IT

A

T

IO

N N

O

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S L O

U

IS

V

IL

L E

D

IS

T R

IC

T

D

R M

A R

T

IN

L U

T H

E R

K

IN

G J

R P

L

L O

U

IS

V

IL

L E

K

Y

W

A R

D P

A R

K W

A Y

K

A N

S A

S C

IT

Y

M

O

SHEET ID

R E

A D

Y T

O A

D V

E R

T

IS

E

US ARMY CORPS

OF ENGINEERS

LOUISVILLE DISTRICT

C H

E C

K E

D B

Y

D

2 3

C

A

B

6 7 8 9

E

F

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

C U

I

CUI

R E

P L A

C E

A H

U -5

P N

Z

H T

V -1

W R

IG

H

T -P

A T

T E

R S

O N

A F

B

O H

IO

-2

-2

G J O

H N

S O

N

A-703_5

T L E

E -W

E L L E

R

S B

R A

N N

A N

F

IN

IS

H

S

IG

N

A G

E S

C H

E D

U L E

S A

N D

N O

T E

S R

L A

S T

E R

ROOM FINISH SCHEDULE

ROOM

NUMBER

ROOM

NAME FLOOR

BASE WALLS

CEILING REMARKSMATERIAL NORTH EAST SOUTH WEST

LEVEL 2

W201 TOILET - - - - - - ACT-1 ONLY EXISTING CEILING TO BE REPLACED

W201A VEST - - - - - - ACT-1 ONLY EXISTING CEILING TO BE REPLACED

W201B VEST - - - - - - ACT-1 ONLY EXISTING CEILING TO BE REPLACED

W203 COLLAB ROOM CPT-1 RB-1 PA-1 PA-1 PA-1 / PA-3 PA-1 / PA-3 ACT-1

W203A BREAK CPT-1 RB-1 PA-1 / PA-3 PA-1 PA-1 PA-1 ACT-1

W203C OFFICE CPT-1 RB-1 PA-1 PA-1 PA-1 PA-1 ACT-1

W203D OFFICE CPT-1 RB-1 PA-1 PA-1 PA-1 PA-1 ACT-1

W203E CONF ROOM CPT-1 RB-1 PA-1 PA-1 / PA-3 PA-1 PA-1 ACT-1

W204 CONF ROOM CPT-1 RB-1 PA-1 PA-1 PA-1 PA-1 ACT-1

W208 CORRIDOR EXISTING RB-1 PA-1 PA-1 PA-1 PA-1 ACT-1

W209 OPEN OFFICE CPT-1 RB-1 PA-1 PA-1 PA-1 PA-1 ACT-1

W209A CONF ROOM CPT-1 RB-1 PA-1 PA-1 PA-1 PA-1 ACT-1

W209B CONF ROOM CPT-1 RB-1 PA-1 PA-1 PA-1 PA-1 ACT-1

W209C OFFICE CPT-1 RB-1 PA-1 PA-1 PA-1 PA-1 ACT-1

W209D OFFICE CPT-1 RB-1 PA-1 PA-1 PA-1 PA-1 ACT-1

W209E OFFICE CPT-1 RB-1 PA-1 PA-1 PA-1 PA-1 ACT-1

W209F OFFICE CPT-1 RB-1 PA-1 PA-1 PA-1 PA-1 ACT-1

W209G OFFICE CPT-1 RB-1 PA-1 PA-1 PA-1 PA-1 ACT-1

W209H OFFICE CPT-1 RB-1 PA-1 PA-1 PA-1 PA-1 ACT-1

W210 OFFICE - - - - - - ACT-1 ONLY EXISTING CEILING TO BE REPLACED

W212 OFFICE - - - - - - ACT-1 ONLY EXISTING CEILING TO BE REPLACED

W219 ELEC EF-1 - PA-1 PA-1 PA-1 PA-1 ACT-1

W220 OPEN OFFICE CPT-1 RB-1 PA-1 PA-1 / PA-3 PA-1 PA-1 / PA-3 ACT-1

W220A CONF ROOM CPT-1 RB-1 PA-1 PA-1 PA-1 PA-1 ACT-1

W220D CONF ROOM CPT-1 RB-1 PA-1 PA-1 PA-1 PA-1 ACT-1

W221A CONF ROOM CPT-1 RB-1 PA-1 PA-1 PA-1 PA-1 ACT-1

W221B CONF ROOM CPT-1 RB-1 PA-1 PA-1 PA-1 PA-1 ACT-1

W221C COLLAB ROOM CPT-1 RB-1 PA-1 PA-1 PA-1 PA-1 ACT-1

W221D CONF ROOM CPT-1 RB-1 PA-1 PA-1 PA-1 PA-1 ACT-1

W221E CONF ROOM CPT-1 RB-1 PA-1 PA-1 PA-1 PA-1 ACT-1

W221F COLLAB ROOM CPT-1 RB-1 PA-1 PA-1 PA-1 PA-1 ACT-1

W225A CORRIDOR EXISTING RB-1 PA-1 PA-1 PA-1 PA-1 ACT-1

W225B ELEC EF-1 - PA-1 PA-1 PA-1 PA-1 ACT-1

W226 VEST - - - - - - ACT-1 ONLY EXISTING CEILING TO BE REPLACED

W226A TOILET - - - - - - ACT-1 ONLY EXISTING CEILING TO BE REPLACED

W253 CORRIDOR EXISTING RB-1 PA-1 PA-1 PA-1 PA-1 ACT-1 SEE A-701_5 AND A-702_5 FINISH PLANS FOR

FINISH EXTENT

W279 CORRIDOR RF-1 RB-1 PA-1 PA-1 PA-1 PA-1 ACT-1 MATCH EXISTING TILE AT NEW ALCOVE

W298 OPEN OFFICE CPT-1 RB-1 PA-1 PA-1 PA-1 PA-1 ACT-1

W299 MECHANICAL EF-1 - - - - - - SEE GENERAL NOTES FOR MORE INFORMATION

FINISH LEGEND - BASIS OF DESIGN OR EQUIVALENT

MATERIAL DESCRIPTION MANUF. MODEL

PRODUCT

NUMBER COLOR REMARKS

CEILING FINISHES

ACT-1 24" x 48" x 3/4" ARMSTRONG FINE FISSURED, SCHOOL ZONE, SQUARE LAY-IN

1714 WHITE

FLOOR FINISHES

CPT-1 CARPET TILE - 24" X 24" SHAW CONTRACT DISPERSE 59576 MAGNETIC FIELDS

EF-1 STANDARD RESINOUS FLOORING SHERWIN WILLIAMS 2 COAT / SILICON SAND - SW4031 STRUCTURAL GRAY

EX-RF EXISTING RESILIENT FLOORING - - - - -

RF-1 VINYL COMPOSITION TILE 12"X12" ARMSTRONG IMPERIAL TEXTURE STANDARD

EXCELON

51839 FORTRESS WHITE MATCH TO EXISTING

WALL FINISHES

AP-1 ACOUSTICAL PANEL FABRIC CARNEGIE XOREL HAVANA 6249 NO.5

CG-1 4' HIGH CORNER GUARD CONSTRUCTION SPECIALTIES ACROVYN SM-20 FOLKSTONE 927 INSTALLED AT ALL OUTSIDE CORNERS OF

GYPSUM BOARD WALLS

PA-1 ACRYLIC/LATEX SHERWIN WILLIAMS EGGSHELL SW7649 SILVERPLATE INTERIOR ROOM WALL PAINT

PA-2 ACRYLIC/LATEX BENJAMIN MOORE SEMI-GLOSS 2134-30 IRON MOUNTAIN METAL DOORS AND FRAMES

PA-3 ACRYLIC/LATEX SHERWIN WILLIAMS EGGSHELL SW6530 REVEL BLUE INTERIOR ROOM WALL PAINT

RB-1 4" TOED WALL BASE ROPPE RUBBER BASE 193, COVE 98 BLACK BROWN

SIGNAGE SCHEDULE - SECOND FLOOR

SIGN

CODE

SIGN

TYPE

ROOM

NUMBER MESSAGE TEXT

S201 A W220 OPEN OFFICE

S202 A W221C COLLABORATION ROOM

S203 A W221B CONFERENCE ROOM

S204 A W221A CONFERENCE ROOM

S205 A W221F COLLABORATION ROOM

S206 A W221E CONFERENCE ROOM

S207 A W221D CONFERENCE ROOM

S208 A W220A CONFERENCE ROOM

S209 A W220D CONFERENCE ROOM

S210 A W209A CONFERENCE ROOM

S211 A W209C OFFICE

S212 A W209B CONFERENCE ROOM

S213 A W209D OFFICE

S214 A W209E OFFICE

S215 A W209F OFFICE

S216 A W209G OFFICE

S217 A W209H OFFICE

S218 A W203D OFFICE

S219 A W203C OFFICE

S220 A W204 CONFERENCE ROOM

S221 A W204 CONFERENCE ROOM

S222 A W298 OPEN OFFICE

S223 A W203 OPEN OFFICE

S224 A W209 OPEN OFFICE

S225 A W220 OPEN OFFICE

M A

R K

D E

S C

R

IP

T

IO

N D

A T

E

02-24-23

ROBERT J KENNALEY

ARCHITECT

LICENSE NO. A-6476

CUI

LEVEL 2

842' - 4 5/8"

RB-1

PA-1

E6

CL

VARIES

EQ. 4' - 0" 4' - 0"

VARIES

EQ.

CENTER VISUAL

DISPLAY ON WALL.

4"

A7 A7

3'

LEVEL 2

842' - 4 5/8"

3'

AP-1

8' - 0"

VARIES

EQ.

RB-1

PA-1

CL

CENTER PANEL(S)

ON WALL

LEVEL 2

842' - 4 5/8"

A1

CL

RB-1

PA-1

CENTER MARKERBOARD

ON WALL

REFER TO FF&E

FOR MORE

INFORMATION

VARIES

EQ.

3'

4"

9"

/2

PERMANENT RAISED TEXT 1 1/2"

HIGH WITH BRAILLE HELVETICA

NEUE 55 ROMAN

3/8" THICK MATTE ACRYLIC

CLEAR WINDOW

INSERT AREA - UPDATEABLE

PAPER

8"

3" x 9"

PAPER INSERT

3/ 4"

4' -0 T O '-0

3"

BASE LINE OF HIGHEST COPY MOUNTED

NO HIGHER THAN 60" AFF

BASELINE OF LOWEST COPY MOUNTED

NO LOWER THAN 48" AFF

MOUNT SIGN ON LATCH SIDE OF DOOR

EXISTING RESILIENT

FLOORING

RESINOUS

FLOORING

RESINOUS FLOORING

PERIMETER TRIM PER

SPECIFICATIONS

RESINOUS FLOORING

EXISTING RESILIENT

FLOORING

CARPETING

ADA COMPLIANT SLOPING

METAL EDGE TRIM

CARPETING

D E

S

IG

N E

D B

Y

D R

A W

N B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

X

S O

L

IC

IT

A

T

IO

N N

O

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S L O

U

IS

V

IL

L E

D

IS

T R

IC

T

D

R M

A R

T

IN

L U

T H

E R

K

IN

G J

R P

L

L O

U

IS

V

IL

L E

K

Y

W

A R

D P

A R

K W

A Y

K

A N

S A

S C

IT

Y

M

O

SHEET ID

R E

A D

Y T

O A

D V

E R

T

IS

E

US ARMY CORPS

OF ENGINEERS

LOUISVILLE DISTRICT

C H

E C

K E

D B

Y

D

2 3

C

A

B

6 7 8 9

E

F

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

C U

I

CUI

R E

P L A

C E

A H

U -5

P N

Z

H T

V -1

W R

IG

H

T -P

A T

T E

R S

O N

A F

B

O H

IO

-2

-2

G J O

H N

S O

N

A-704_5

T L E

E -W

E L L E

R

W N

E E

D L E

IN

T

E R

IO

R

D E

T A

IL

S

A N

D E

L E

V A

T

IO

N S

R L A

S T

E R

SCALE: 1/4" = 1'-0"A1

TYPICAL CONFERENCE ROOM MEDIA ELEVATION

SCALE: 1/4" = 1'-0"A3

TYPICAL SINGLE ACOUSTICAL PANEL ELEVATION

SCALE: 1/4" = 1'-0"A6

TYPICAL MARKERBOARD ELEVATION

SCALE: 3" = 1'-0"C1

SIGN TYPE A

SCALE: 1/2" = 1'-0"D1

TYP. SIGNAGE MOUNTING - WALL

SCALE: 12" = 1'-0"C3

FLOOR TRANSITION - RESINOUS TO RESILIENT

SCALE: 12" = 1'-0"D3

FLOOR TRANSITION - RESILIENT TO CARPET

0 2' 4' 8'0 2' 4' 8'0 2' 4' 8'

0 3" 6" 9" 0 1" 2"

0 1" 2"0 1' 2' 4' M A

R K

D E

S C

R

IP

T

IO

N D

A T

E

02-24-23

ROBERT J KENNALEY

ARCHITECT

LICENSE NO. A-6476

CUI

CUI COVER
Cover Amdt 0002