Controlled by: USACE Controlled by: Louisville District CUI Category(ies): General Critical Infrastucture Information Distribution/Dissemination Control: FEDCON POC: Alexa Dukes Contracting Specialist alexa.l.dukes@usace.army.mil 502.315.3000

Materials shall be submitted to potential offerors currently certified in the Joint Certification Program (JCP) only.

D E

S

IG

N E

D B

Y

D R

A W

N B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

X

S O

L

IC

IT

A

T

IO

N N

O

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S L O

U

IS

V

IL

L E

D

IS

T R

IC

T

D

R M

A R

T

IN

L U

T H

E R

K

IN

G J

R P

L

L O

U

IS

V

IL

L E

K

Y

W

A R

D P

A R

K W

A Y

K

A N

S A

S C

IT

Y

M

O

SHEET ID

C O

R R

E C

T E

D F

IN

A

L

NOT FOR CONSTRUCTION

US ARMY CORPS

OF ENGINEERS

LOUISVILLE DISTRICT

C H

E C

K E

D B

Y

D

2 3

C

A

B

6 7 8 9

E

F

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

C U

I

CUI

R E

P L A

C E

A H

U -5

P N

Z

H T

V -1

P

W R

IG

H

T -P

A T

T E

R S

O N

A F

B

O H

IO

-1

-2

G J O

H N

S O

N

CONTROLLED BY: USACE

CONTROLLED BY: LOUISVILLE DISTRICT

CUI CATEGORY: GENERAL CRITICAL INFRASTRUCTURE INFORMATION

DISTRIBUTION/DISSEMINATION CONTROL: FEDCON

POC:

US Army Corps of Engineers ®

SOLICITATION NO.:

CONTRACT NO.:

ISSUE DATE:

P2#: 469978

LOUISVILLE DISTRICT

WRIGHT PATTERSON AIR FORCE BASE, OHIO

REPLACE AHU-5

PN: ZHTV-160060

16 FEBRUARY 2023

G-001_5

A T

U N

G S

E T

H

A T

U N

G S

E T

H

C O

V E

R S

H E

E T

G J O

H N

S O

N

M A

R K

D E

S C

R

IP

T

IO

N D

A T

E

W

2Q R

R

_C U

I_ Pl an s-

ARIMS: 200A Disposition: Maintain for 15 yrs after construction

28 February 2023

W912QR23R0022

S

IG

N E

D B

Y

D R

A W

N B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

X

S O

L

IC

IT

A

T

IO

N N

O

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S L O

U

IS

V

IL

L E

D

IS

T R

IC

T

D

R M

A R

T

IN

L U

T H

E R

K

IN

G J

R P

L

L O

U

IS

V

IL

L E

K

Y

W

A R

D P

A R

K W

A Y

K

A N

S A

S C

IT

Y

M

O

SHEET ID

C O

R R

E C

T E

D F

IN

A

L

NOT FOR CONSTRUCTION

US ARMY CORPS

OF ENGINEERS

LOUISVILLE DISTRICT

C H

E C

K E

D B

Y

D

2 3

C

A

B

6 7 8 9

E

F

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

C U

I

CUI

R E

P L A

C E

A H

U -5

P N

Z

H T

V -1

W R

IG

H

T -P

A T

T E

R S

O N

A F

B

O H

IO

-1

-2

G J O

H N

S O

N

G-002_5

A T

U N

G S

E T

H

A T

U N

G S

E T

H

S H

E E

T I

N D

E X

G J O

H N

S O

N

I-117_5 SECOND FLOOR WORKSTATION PANEL ELEVATIONS

I-116_5 SECOND FLOOR ENLARGED PANEL PLANS

I-115_5 SECOND FLOOR ENLARGED PANEL PLANS

I-114_5 SECOND FLOOR ENLARGED PANEL PLANS

I-113_5 SECOND FLOOR FURNITURE PLAN - AREA B

I-112_5 SECOND FLOOR FURNITURE PLAN - AREA A

I-111_5 SECOND FLOOR FURNITURE PLAN - AREA B KEY

I-110_5 SECOND FLOOR FURNITURE PLAN - AREA A KEY

I-109_5 SECOND FLOOR FURNITURE PLAN - OVERALL KEY

ID111_5 SECOND FLOOR DEMO FURNITURE PLAN - AREA B

ID110_5 SECOND FLOOR DEMO FURNITURE PLAN - AREA A

A-704_5 INTERIOR DETAILS AND ELEVATIONS

A-703_5 FINISH AND SIGNAGE SCHEDULE AND NOTES

A-702_5 SECOND FLOOR FINISH AND SIGNAGE PLAN - AREA B

A-701_5 SECOND FLOOR FINISH AND SIGNAGE PLAN - AREA A

A-602_5 DOOR DETAILS

A-601_5 DOOR SCHEDULE, DOOR & FRAME TYPES, DOOR DETAILS

A-523_5 PLAN DETAILS

A-522_5 PLAN DETAILS

A-521_5 PLAN DETAILS

A-512_5 PENETRATION DETAILS

A-502_5 PARTITION DETAILS

A-501_5 PARTITION TYPES

A-151_5 REFLECTED CEILING SECOND FLOOR PLAN - NEW

A-103_5 SECOND FLOOR PLAN - AREA B

A-102_5 SECOND FLOOR PLAN - AREA A

A-101_5 SECOND FLOOR PLAN - NEW

A-002_5 SECURE AREA SECOND FLOOR PLAN - NEW

A-001_5 OVERALL SECOND FLOOR PLAN

AD151_5 SECOND FLOOR REFLECTED CEILING PLAN - DEMOLITION

AD101_5 SECOND FLOOR PLAN - DEMOLITION

ARCHITECTURAL

H-104_5 REFERENCE - SECOND FLOOR PLAN WEST WING

H-103_5 REFERENCE - SECOND FLOOR PLAN WEST WING

H-102_5 HAZARDOUS BUILDING MATERIALS SECOND FLOOR PLAN - ACM

H-101_5 HAZARDOUS BUILDING MATERIALS PLAN NOTES

HAZARDOUS MATERIALS

AG003_5 SECOND FLOOR - LIFE SAFETY PLAN

AG002_5 BUILDING CODE AND LIFE SAFETY CRITERIA

AG001_5 LEGEND, ABBREVIATIONS AND GENERAL NOTES

GC101_5 SITE ACCESS PLAN

G-002_5 SHEET INDEX

G-001_5 COVER SHEET

GENERAL

SHEET NUMBER SHEET NAME

AHU-5 SHEET LIST

TN502_5 COMMUNICATIONS DETAILS

TN501_5 COMMUNICATIONS DETAILS

TN102_5 COMMUNICATIONS SECOND FLOOR PLAN - AREA B

TN101_5 COMMUNICATIONS SECOND FLOOR PLAN - AREA A

TN100_5 OVERALL SECOND FLOOR COMM PLAN

TC501_5 CABLE TRAY DETAILS

TC102_5 CABLE TRAY PLAN - AREA B

TC101_5 CABLE TRAY PLAN - AREA A

TC100_5 OVERALL CABLE TRAY PLAN

T-001_5 COMMUNICATIONS LEGEND

COMMUNICATIONS

EP602_5 ELECTRICAL PANEL SCHEDULES

EP601_5 ELECTRICAL ONE-LINE DIAGRAM

EP501_5 ELECTRICAL DETAILS

EP102_5 POWER SECOND FLOOR PLAN - AREA B

EP101_5 POWER SECOND FLOOR PLAN - AREA A

EP100_5 OVERALL SECOND FLOOR POWER PLAN

EL701_5 LIGHTING CONTROL WIRING DIAGRAMS

EL610_5 LIGHTING FIXTURE SCHEDULE

EL601_5 LIGHTING CONTROL SCHEDULE

EL501_5 LIGHTING DETAILS

EL102_5 LIGHTING SECOND FLOOR PLAN - AREA B

EL101_5 LIGHTING SECOND FLOOR PLAN - AREA A

EL100_5 OVERALL SECOND FLOOR LIGHTING PLAN

ED601_5 ELECTRICAL DEMOLITION ONE-LINE DIAGRAM

ED112_5 LIGHTING DEMOLITION SECOND FLOOR PLAN - AREA B

ED111_5 LIGHTING DEMOLITION SECOND FLOOR PLAN - AREA A

ED102_5 SYSTEMS DEMOLITION SECOND FLOOR PLAN - AREA B

ED101_5 SYSTEMS DEMOLITION SECOND FLOOR PLAN - AREA A

ED100_5 OVERALL SECOND FLOOR DEMOLITION PLAN

E-002_5 ELECTRICAL SYMBOLS LEGEND - 2 OF 2

E-001_5 ELECTRICAL SYMBOLS LEGEND - 1 OF 2

ELECTRICAL

FX102_5 FIRE SUPPRESSION SECOND FLOOR PLAN - AREA B

FX101_5 FIRE SUPPRESSION SECOND FLOOR PLAN - AREA A

FX100_5 FIRE SUPPRESSION OVERALL FLOOR PLAN

FX001_5 FIRE SUPPRESSION NOTES, LEGEND, AND ABBREVIATIONS

FA601_5 FIRE ALARM RISER DIAGRAM AND MATRIX

FA102_5 FIRE ALARM SECOND FLOOR PLAN - AREA B

FA101_5 FIRE ALARM SECOND FLOOR PLAN - AREA A

FA001_5 FIRE ALARM GENERAL NOTES, LEGEND, AND ABBREVIATIONS

FIRE PROTECTION

SHEET NUMBER SHEET NAME

AHU-5 SHEET LIST

M-803_5 HEATING HOT WATER SCHEMATIC

M-802_5 CHILLED WATER SCHEMATIC

M-801_5 AIRFLOW SCHEMATIC

M-705_5 MECHANICAL CONTROLS

M-704_5 MECHANICAL CONTROLS

M-703_5 MECHANICAL CONTROLS

M-702_5 MECHANICAL CONTROLS

M-701_5 MECHANICAL CONTROLS

M-700_5 CONTROLS SYMBOLS & ABBREVIATIONS

M-602_5 MECHANICAL SCHEDULES

M-601_5 MECHANICAL SCHEDULES

M-506_5 MECHANICAL DETAILS

M-505_5 MECHANICAL DETAILS

M-504_5 MECHANICAL DETAILS

M-503_5 MECHANICAL DETAILS

M-502_5 MECHANICAL DETAILS

M-501_5 MECHANICAL DETAILS

M-401_5 ENLARGED MECHANICAL ROOM W299 PLAN

M-303_5 AIR HANDLING UNIT DETAILS

M-302_5 MECHANICAL SECTIONS

M-301_5 MECHANICAL SECTIONS

M-202_5 HVAC PIPING SECOND FLOOR PLAN - AREA B

M-201_5 HVAC PIPING SECOND FLOOR PLAN - AREA A

M-102_5 HVAC DUCTWORK SECOND FLOOR PLAN - AREA B

M-101_5 HVAC DUCTWORK SECOND FLOOR PLAN - AREA A

MD401_5 ENLARGED MECH ROOM W299 DEMOLITION PLAN

MD103_5 HVAC DEMOLITION SECOND FLOOR PLAN - AHU-6 MODIFICATIONS

MD102_5 HVAC DUCTWORK DEMOLITION SECOND FLOOR PLAN - AREA B

MD101_5 HVAC DUCTWORK DEMOLITION SECOND FLOOR PLAN - AREA A

M-003_5 AHU ZONING SECOND FLOOR PLAN

M-002_5 AHU ZONING EXISTING SECOND FLOOR PLAN

M-001_5 MECHANICAL GENERAL NOTES, SYMBOLS AND ABBREVIATIONS

MECHANICAL

SHEET NUMBER SHEET NAME

AHU-5 SHEET LIST

M A

R K

D E

S C

R

IP

T

IO

N D

A T

E

W

2Q R

R

_C U

I_ Pl an s-

ARIMS: 200A Disposition: Maintain for 15 yrs after construction

LEGEND:

PROPOSED STAGING AND LAYDOWN

PROJECT LOCATION

NOTE:

1. ANY EXISTING SURFACES AND LANDSCAPE AREAS DAMAGED DURING CONSTRUCTION MUST BE REPAIRED, REFINISHED, RE-SEEDED, RE-SODDED AND AERATED IF NECESSARY TO RESTORE PROJECT AREA TO EQUAL OR BETTER CONDITION AT THE CONTRACTOR'S EXPENSE.

2. THE CONTRACTOR MUST ASSUME ALL RESPONSIBILITY ASSOCIATED WITH THE TEMPORARY STORAGE OF MATERIALS, TOOLS NAD EQUIPMENT

ON THE SITE.

3. THE CONTRACTOR MUST ADHERE TO ALL SECURITY AND SAFETY PROCEDURES AS REQUIRED BY WPAFB CONTRACTOR ENTRY/SECURITY

PROCEDURES INCLUDING, BUT NOT LIMITED TO, CONTRACTOR EMPLOYEE PARKING AND ACCESS TO THE BUILDING.

4. ALL HVAC EQUIPMENT MUST BE PROTECTED FROM WATER AND WEATHER DAMAGE. STORAGE ON SITE IS LIMITED AND JUST IN TIME DELIVERY

MUST BE PART OF THE CONSTRUCTION.

5. REMEDIATION TO THE EXISTING SITE WORK AND INSIDE OR OUTSIDE THE FACILITY MUST INCLUDE REPARI/REPLACEMENT OF PAVEMENTS, SIDEWALKS, RAMPS, GUARDRAILS, SOD, WALLS, FLOORS, CEILINGS, OR PIPING DAMAGED DURING THE CONSTRUCTION PROCESS.

6. THE CONTRACTOR IS TO COORDINATE ACCESS TO THE SITE, INCLUDING THE LOCATION OF TEMPORARY STORAGE TRAILERS WITH THE

GOVERNMENT. CONSTRUCTION TRAILER AND LAY DOWN AREA AREA MUST BE LOCATED AT OR NEAR THE INTERSECTIONS OF ZERO RD AND

WARNER ROBIN ST ADJACENT TO BUILDING 867, AREA A WPAFB.

7. TEMPORARY SECURE STORAGE STAGING AREA MUST BE WITHIN 5 MILE RADIUS OF CONSTRUCTION SITE (BUILDING 856). COORDINATE

LOCATION WITH THE GOVERNMENT PRIOR TO CONSTRUCTION.

8. CONTRACTOR TO PROVIDE ANY HEAT WHERE REQUIRED TO PROTECT THE BUILDING OR EQUIPMENT AND FOR ESCORTS IF REQUIRED FOR

INSTALLATION.

SI

TE

A C

C

ES

S

PL

AN

0 2000' 4000'

PROJECT LOCATION

(SEE ENLARGEMENT A)

COMMERCIAL

DELIVERY GATE

N. CENTRAL AVE

KAUFFMAN AVE

OH-235

A1 SITE ACCESS PLAN

SCALE: 1"=2000'

TRUE

NORTH

B5 ENLARGEMENT A

SCALE: 1"=200'

TRUE

NORTH

0 400'200'

SCALE IN FEET

SK

EE

L A

VE

NUE

NOVIC

K R

OAD

SKEEL AVE

OH-444

SPRUCE WAY

HEBBLE CREEK ROAD

W

ARNER ROBIN STREET

NEW

ARK STREET

SKEEL AVENUE

SA

C

R

AM

EN

TO

S

TR

EE

T

S. BROAD ST

GATE 15A

GATE 1A

PROJECT LOCATION

D

ES

IG

N

ED

B

Y:

D R

AW

N

B Y:

SU

BM

IT

TE

D B

Y:

SI

ZE

IS

SU

E D

AT

E:

C O

N

TR

AC

T

N O

X2

SO

LI

C

IT

AT

IO

N N

O

U S

AR

M

Y C

O R

PS

O

F

EN

G

IN

EE

R

S

LO

U

IS

VI

LL

E D

IS

TR

IC

T

D R

. M

AR

TI

N

L U

TH

ER

K

IN

G J

R . P

L.

LO

U

IS

VI

LL

E, K

Y

W

AR

D P

AR

KW

AY

, K

AN

SA

S C

IT

Y, M O

SHEET ID

C O

R R

EC

TE

D F

IN

AL

US ARMY CORPS

OF ENGINEERS

LOUISVILLE DISTRICT

C H

EC

KE

D B

Y:

D

2 3

C

A

B

6 7 8 9

E

F

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

C U

I

CUI

R

EP

LA

C

E

AH

U -5

PN

: Z

H

TV

-1

P2

: 4

W R

IG

H

T-

PA

TT

ER

SO

N

A

FB

, O H

IO

-1

6-

G .J

O H

N

SO

N

GC101_5

B.

H

AN

SE

N

J.

M

C M

AN

N

O N

K.

JE

N

SE

N

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

NOT FOR CONSTRUCTION

APPROX. 20'X16'

RESERVED OFFSITE

SPACE

APPROX. 30'X10'

RESERVED OFFSITE

SPACE

DEBRIS DUMPSTER

LOCATION

ALTERNATE DEBRIS

DUMPSTER LOCATION

RECYCLING

DUMPSTER LOCATION

OH-4

I-675

SKEEL AVE

KUGLICS BOULEVARD

SPRUCE W

AY

SKEEL AVE

O

KLAH

O M

A C

ITY ST

SAN

AN

TO

N

IO

AVE

W

2Q R

R

_C U

I_ Pl an s-

EXISTING DOOR

NEW DOOR

EXISTING WALL

NEW WALL (RE: PARTITION TYPE)

PLAN LEGEND:

ROOM NAME

ROOM NUMBER

PARTITION TYPE

DOOR NUMBER

WINDOW WALL TYPE

GLAZING TYPE

LOUVER TAG

GRID BUBBLE AND LINE

TOILET ACCESSORY TAG

L1

T1

W01

WORK

888W

1' - 0" A.F.F.

FURNITURE SYSTEM TAG

ROOM NAME

1i

CEILING HEIGHT TAG

EXISTING DOOR

DOOR TO BE REMOVED

EXISTING WALL

WALL TO BE REMOVED

DEMOLITION/EXISTING PLAN LEGEND

FIRE EXTINGUISHER PLACEMENT

SECTION, DETAIL, AND ELEVATION SYMBOL IDENTIFIERS:

DRAWING SEQUENCE NUMBER

INDICATES WHERE TITLE IS LOCATED

(MAY NOT BE PRESENT IF CALLOUT AND

TITLE ARE ON THE SAME DRAWING)

LETTER OR NUMBER DESIGNATOR

ONE OR TWO CHARACTER DISCIPLINE

DESIGNATOR (MAY NOT BE PRESENT IF

CALLOUT AND TITLE ARE ON DRAWINGS

WITHIN THE SAME DISCIPLINE)

WALL SECTION CALLOUT EXAMPLE:

DETAIL CALLOUT EXAMPLE:

ELEVATION CALLOUT EXAMPLE:

SECTION, DETAIL, AND ELEVATION TITLE EXAMPLE:

EXTERIORINTERIOR

SIM

AA888

A

AA888

A

AA888

NUMBER INDICATES DETAIL

SHEET NUMBER WHERE

ELEVATION IS DRAWN

A

AA888

NUMBER INDICATES

DETAIL

SHEET NUMBER WHERE

ELEVATION IS DRAWN

A

AA888

A

AA888

SIM

AA888

AA888

1 1

BUILDING SECTION CALLOUT EXAMPLE:

VIEW REFERENCE EXAMPLE:

NUMBER INDICATES DETAIL

SHEET NUMBER WHERE ELEVATION IS DRAWN

N

PLAN

NORTH

0 4' 8' 16'

LETTER AND NUMBER

INDICATE SHEET GRID

COORDINATE OF VIEW

NORTH ARROW EXAMPLE:

VIEW TITLE

A1

VIEW TITLE

VIEW SCALE

VIEW SCALE BAR

SCALE: 1/8" = 1'-0"

PLAN NORTH

TRUE NORTH

NORTH

INDICATING

PLAN NORTH

NORTH ARROW

INDICATING PLAN NORTH

AND TRUE NORTH

A-000_X

BUILDING DESIGNATOR

LETTER AND

NUMBER INDICATE

SHEET GRID

COORDINATE OF

VIEW

SHEET NUMBER

WHERE DETAIL IS

RIGID INSULATION

FACE BRICK

PLYWOOD

CONCRETE

MASONRY UNIT

CONCRETE

UNDISTURBED

EARTH

GROUT OR

GYPSUM BOARD

STEEL OR

FERROUS METALS

GRAVEL

FINISHED WOOD

BATT INSULATION

MATERIAL SYMBOLS

DIMENSION

LUMBER

METAL STUD WALL

BACKER ROD AND

SEALANT

ALUMINUM OR

NON-FERROUS METALS

SAND, PLASTER, OR

PORTLAND CEMENT

COMPACTED

FILL

TERRAZZO

GRASS

MASONRY

PARTICLE BOARD

GLUED-LAMINATED WOOD

PLASTIC LAMINATE

MATERIAL SYMBOLS

a. REFER TO H-SERIES SHEETS FOR ALL HAZARDOUS BUILDING MATERIAL, ASBESTOS/LEAD ABATEMENT, AND

UNIVERSAL WASTE REQUIREMENTS.

b. EXISTING FURNITURE FOR REFERENCE ONLY (TYPICAL). CONTRACTOR MUST FIELD VERIFY AND LABEL THE EXTENT OF ALL FURNITURE, EQUIPMENT, POWER POLES, COMPUTER POLES, CABLING WIRING AND DEMOUNTABLE PARTITIONS. CONTRACTOR MUST DISASSEMBLE, SORT FURNITURE FOR RE-USE, AND RE- ASSEMBLE AFTER CONSTRUCTION IS COMPLETE. LOCATION FOR STORAGE OF FURNITURE MUST BE

DETERMINED PRIOR TO COMMENCEMENT OF CONSTRUCTION.

c. CONTRACTOR IS RESPONSIBLE FOR INVENTORYING EACH ROOM PRIOR TO THE COMMENCEMENT OF CONSTRUCTION. CONTRACTOR MUST LABEL AND TAKE PHOTOS OF ALL EXISTING CONDITIONS TO ENSURE THAT THE FURNITURE, CABINETS, POWER, CCTV, CONFERENCE EQUIPMENT, ETC AND COMPUTER WIRING ARE ALL REPLACED IN THE SAME LOCATIONS. CONTRACTOR'S FAILURE TO TAKE GOOD RECORDS WILL NOT BE THE

GOVERNMENT'S RESPONSIBILITY.

d. PRIOR TO CONTRACTOR'S WORK, INDIVIDUALS' PERSONAL BELONGINGS WILL BE BOXED, MOVED AND/OR

STORED BY THE GOVERNMENT.

e. ALL FURNITURE WILL BE REMOVED FROM CONSTRUCTION AREA BY THE CONTRACTOR AND TURNED OVER TO NASIC. CONTRACTOR MUST STORE ALL FURNITURE TO BE RE-INSTALLED IN CONTRACTOR FURNISHED LOCKABLE TRAILERS ON WPAFB. CONTRACTOR MUST BEAR THE SOLE RESPONSIBILITY TO ENSURE THAT THE FURNITURE AND EQUIPMENT IS NOT DAMAGED, AND IS REINSTALLED WITH ASSOCIATED POWER POLES, COMPUTER POWER, COMPUTER FIBER, PHONES, ETC. IN THE SAME CONFIGURATION.

f. ALL ARTWORK TO BE REMOVED BY WPAFB PRIOR TO BEGINNING OF WORK.

1. TEMPORARY SECURE STORAGE REQUIREMENTS: IT IS THE CONTRACTOR’S RESPONSIBILITY TO PROVIDE TEMPORARY SECURE STORAGE SPACE/TRAILER FOR THE FURNITURE AND EQUIPMENT. REFER TO ADDITIONAL INFORMATION AND STORAGE REQUIREMENTS

BELOW.

2. COMMON ACCESS/EGRESS CORRIDORS: STAIR W5; ROOMS W208, W253, W279 AND W280 MUST BE MAINTAINED AS COMMON ACCESS/EGRESS CORRIDORS THROUGHOUT THE CONSTRUCTION PERIOD FOR FACILITY PERSONNEL. PRIOR TO PERFORMING WORK IN CORRIDORS, CONTRACTOR MUST PERFORM AN EGRESS ANALYSIS TO VERIFY EXIT ACCESS IS MAINTAINED FOR BUILDING OCCUPANTS IN ACCORDANCE WITH NFPA 101. CONTRACTOR TO PROVIDE MINIMUM 2 WEEK NOTICE TO BUILDING OCCUPANTS OF ANY EXITS THAT WILL BE BLOCKED DURING CONSTRUCTION ACTIVITIES. THESE ROOMS WILL BE LIMITED TO CONTRACTOR WORK (IE. ABATEMENT, DEMOLITION, AND NEW WORK AS DEFINED HERE-IN) FROM THE HOURS OF 1600 TO 2400. THE CORRIDORS MUST BE CLEARED OF ALL CONSTRUCTION MATERIALS AND EQUIPMENT DURING THE HOURS OF 0500 TO 1600. CONTRACTOR MUST SCHEDULE THE CONSTRUCTION WORK ACCORDINGLY. CONTRACTOR MUST COORDINATE WITH CONTRACTING OFFICER AND SECURITY OFFICER FOR ALL CONSTRUCTION EFFORTS.

THE FOLLOWING SYSTEMS MUST BE MAINTAINED AND FULLY FUNCTIONAL:

1. SECURITY INTRUSION DETECTION

2. SECURITY SURVEILLANCE

3. SECURITY TURNSTILE AND ALL ASSOCIATED APPARATUS

4. INTERCOM CALL BOX AT WEST ENTRANCE

3. CONTRACTOR MUST PROVIDE THE NECESSARY TEMPORARY SUPPORTING MEANS FOR THE FOLLOWING

SYSTEMS TO MAINTAIN A FULLY FUNCTIONAL EGRESS CORRIDOR;

1. HEATING AND VENTILATION (HVAC) SYSTEMS

2. HVAC DIRECT DIGITAL CONTROL SYSTEM

3. LIGHTING AND EGRESS EXIT LIGHTING SYSTEMS

4. FIRE ALARM SYSTEMS

5. FIRE SUPPRESSION SYSTEMS

6. ELECTRICAL POWER TO SUPPORT ALL AFOREMENTIONED SYSTEMS.

M A

X

BRACKET MOUNTED

R E

A C

H H

E

IG

H T

T O

A N

Y C

O N

T R

O

LS

A N

D O

P E

R A

T

IN

G M

E C

H A

N

IS

M

D E

S

IG

N E

D B

Y

D R

A W

N B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

X

S O

L

IC

IT

A

T

IO

N N

O

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S L O

U

IS

V

IL

L E

D

IS

T R

IC

T

D

R M

A R

T

IN

L U

T H

E R

K

IN

G J

R P

L

L O

U

IS

V

IL

L E

K

Y

W

A R

D P

A R

K W

A Y

K

A N

S A

S C

IT

Y

M

O

SHEET ID

C O

R R

E C

T E

D F

IN

A

L

NOT FOR CONSTRUCTION

US ARMY CORPS

OF ENGINEERS

LOUISVILLE DISTRICT

C H

E C

K E

D B

Y

D

2 3

C

A

B

6 7 8 9

E

F

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

C U

I

CUI

R E

P L A

C E

A H

U -5

P N

Z

H T

V -1

W R

IG

H

T -P

A T

T E

R S

O N

A F

B

O H

IO

-1

-2

G J O

H N

S O

N

AG001_5

B K

E N

N A

L E

Y

W N

E E

D L E

L E

G E

N D

A

B B

R E

V

IA

T

IO

N S

A N

D G

E N

E R

A L N

O T

E S

E V

A L E

Z Q

U E

Z

1. THE CONTRACTOR MUST INCLUDE ALL WORK REQUIRED TO COMPLY WITH ALL APPLICABLE CODES BY THE AUTHORITY HAVING JURISDICTION.

2. DIMENSIONS GOVERN. DETAILS GOVERN OVER PLANS AND ELEVATIONS. LARGE SCALE DETAILS OR PLANS GOVERN OVER SMALL SCALE DETAILS OR

PLANS. DO NOT SCALE DRAWINGS.

3. ALL FLOORS MUST BE INSPECTED FOR DAMAGE, WARPING OR OTHER NOTICEABLE DEVIATIONS AND PATCHED AND LEVELED PRIOR TO COVERING

WITH FLOOR FINISHES, OR ERECTION AND INSTALLATION OF COLD-FORMED FRAMING.

4. THE GENERAL CONTRACTOR WILL BE RESPONSIBLE FOR PROVIDING ALL MANUFACTURER'S RECOMMENDED MAINTENANCE PROCEDURES AND

SCHEDULES.

5. ANY MANUFACTURER'S OR BRAND NAME PRODUCTS INDICATED OR SPECIFIED ARE DONE SO TO ESTABLISH A MINIMUM LEVEL OF QUALITY.

6. ALL CONSTRUCTION MUST MEET OR EXCEED LOCAL INDUSTRY STANDARDS. DETAILS ARE PROVIDED TO INDICATE MINIMUM QUALITY AND TO GIVE STANDARDS OF CONSTRUCTION. IF A CONDITION IS NOT SPECIFICALLY DETAILED, SUBMIT A SIMILAR DETAIL FOR GUIDANCE AND APPROVAL.

7. THE LETTERS I, O, AND Q ARE NOT USED TO INDICATE DETAILS, SECTIONS OR ELEVATIONS.

8. PROVIDE PRESERVATIVE-TREATED WOOD AT ALL LOCATIONS WHERE WOOD IS IN DIRECT CONTACT WITH CONCRETE OR MASONRY.

9. PROVIDE FIRE-RESISTANT TREATED WOOD BLOCKING FOR SECURE ANCHORAGE OF ALL SHELVES, RUNNING TRIM, RAILINGS, SUSPENDED ITEMS, DOOR-STOPS, GRAB-BARS, AND OTHER SIMILAR WOODWORK, HARDWARE, SPECIALTIES, ACCESSORIES, FIXTURES, OR EQUIPMENT.

10. ALL WORK SHOWN ON DRAWINGS MUST BE BY THE CONTRACTOR UNLESS OTHERWISE NOTED BY THE ABBREVIATION NIC (NOT IN CONTRACT) .

11. PROVIDE WATER-RESISTANT GYPSUM BOARD AT ALL WET OR UNCONDITIONED AREAS INCLUDING, BUT NOT LIMITED TO, PARTITIONS BEHIND SINKS.

CONTRACTOR TO ENSURE THAT FIRE RATING IS MAINTAINED.

12. PAINT, STAIN, OR COAT ALL EXPOSED SURFACES OF CONSTRUCTION UNLESS NOTED OTHERWISE OR IF SURFACES ARE PRE-FINISHED.

13. PAINT ALL EXPOSED ELECTRICAL CONDUIT, ELECTRICAL RACEWAYS AND BOXES, MECHANICAL PIPING, DUCTS AND EQUIPMENT, AND PLUMBING PIPING WITH THE EXCEPTION OF PREFINISHED AND INSULATED ITEMS, TO MATCH THE ADJACENT SURFACE.

14. ALL CONDUITS, PLUMBING, PIPING, DUCTWORK, AND OTHER EQUIPMENT EXPOSED TO VIEW MUST BE LOCATED PARALLEL OR PERPENDICULAR TO

THE STRUCTURAL FRAMING SYSTEM.

15. THE CONTRACTOR MUST COORDINATE SIZE AND LOCATION OF HVAC, PLUMBING, ELECTRICAL AND TECHNOLOGY ITEMS OR OPENINGS TO AVOID

CONFLICTS BETWEEN SAID ITEMS, PRIOR TO PROCEEDING WITH RELATED WORK .

16. ARCHITECTURAL DETAILS ARE APPLICABLE WHERE INDICATED BY SECTION CUT, BY NOTE, OR BY DETAIL TITLE. INCORPORATE SIMILAR DETAILS AT SIMILAR CONDITIONS UNLESS NOTED OTHERWISE. THE CONTRACTOR MAY REQUEST A CLARIFICATION IF REQUIRED, OTHERWISE THE MORE

STRINGENT REQUIREMENTS WILL CONTROL.

17. ALL OPENING DIMENSIONS ARE NOMINAL. THE CONTRACTOR MUST FIELD MEASURE ALL OPENINGS AND COORDINATE WITH THE APPROPRIATE

SUPPLIER.

18. SEAL AROUND ALL DOOR AND WINDOW FRAMES, COUNTERTOPS, WALL-MOUNTED FIXTURES AND EQUIPMENT TO ADJACENT WALL SURFACES.

19. THE CONTRACTOR MUST REVIEW THE DIMENSIONS OF ALL EQUIPMENT IN THE PROJECT REGARDLESS OF THE SOURCE AND COORDINATE ACCESS TO THE SPACE AND VERIFY CLEAR FLOOR SPACE IS PROVIDED AS REQUIRED TO ENSURE EASE OF INSTALLATION.

20. ALL WORK MUST BE OF GOOD QUALITY, FREE FROM DEFECTS, AND IN ACCORDANCE WITH THE REQUIREMENTS OF THE CONTRACT DOCUMENTS.

21. THE CONTRACTOR MUST PROVIDE ACCESS DOORS OR PANELS AS REQUIRED FOR SERVICING OF PIPING, DUCTWORK, CABLE TRAYS, FIRE DAMPERS AND SIMILAR APPLICATIONS. ALL PROPOSED ACCESS DOOR LOCATIONS TO BE SUBMITTED FOR APPROVAL PRIOR TO INSTALLATION.

22. BRACE PARTITIONS, SUSPENDED CEILINGS, SOFFITS, SUSPENDED ITEMS, ETC. ONLY TO STRUCTURAL ELEMENTS ABOVE. DO NOT ANCHOR TO ROOF DECK, PLUMBING / SPRINKLER PIPES, DUCTWORK, ELECTRICAL CONDUIT OR SIMILAR ELEMENTS.

23. EXTEND ALL FLOORING AND WALL-BASE COMPLETELY INTO RECESSES, UNDER OPEN COUNTERTOPS, AND BEHIND ALL EQUIPMENT.

24. ALL MATERIALS USED FOR CONSTRUCTION MUST BE NEW AND UNDAMAGED. THE CONTRACTOR MUST SUBMIT SHOP DRAWINGS FOR ALL WORK

SHOWN.

25. THE CONTRACTOR MUST BECOME FULLY ACQUAINTED WITH CONDITIONS RELATED TO THE WORK. ANY DISCREPANCIES BETWEEN THE DRAWINGS AND THE ACTUAL CONDITIONS MUST BE REPORTED TO THE CONTRACTING OFFICER FOR RESOLUTION PRIOR TO PROCEEDING WITH THE WORK .

26. EACH INSTALLER MUST EXAMINE SUBSTRATE AND/OR CONDITIONS UNDER WHICH THE WORK WILL BE INSTALLED AND REPORT TO THE CONTRACTOR IN WRITING ANY CONDITIONS DETRIMENTAL TO THE PROPER AND TIMELY EXECUTION OF THE INSTALLERS WORK. DO NOT PROCEED UNTIL UNSATISFACTORY CONDITIONS ARE CORRECTED. INSTALLATION WILL CONSTITUTE ACCEPTANCE OF THE SUBSTRATE AND/OR CONDITIONS.

27. "TYPICAL" (TYP) AS USED IN THESE DOCUMENTS MEANS THAT THE CONDITIONS OR DIMENSION IS THE SAME OR REPRESENTATIVE FOR SIMILAR

CONDITIONS THROUGHOUT.

28. CONTROL JOINTS (CJ) MUST BE INSTALLED AT ALL PARTITIONS. CJ AT GYPSUM PARTITIONS MUST BE MAXIMUM 30'-0" O.C., CJ AT CONCRETE MASONRY

UNIT PARTITIONS MUST BE MAXIMUM 20'-0" O.C., UNLESS OTHERWISE NOTED ON DRAWINGS.

29. NON-BEARING PARTITIONS MUST BE ISOLATED FROM THE BUILDING STRUCTURE TO PREVENT TRANSFER OF BUILDING LOADS FROM THE STRUCTURE

TO THE PARTITIONS.

30. THE CONTRACTOR MUST NOT CONSIDER DEMOLITION, REPAIR, AND ALTERATION NOTES TO BE ALL-INCLUSIVE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO INSPECT AND ASSESS EACH AREA AND TO FULFILL THE INTENT OF THE DESIGN INDICATED BY THE CONTRACT DOCUMENTS.

REFER TO SPECIFICATION SECTION 011100 - SUMMARY OF WORK AND SECTION 02 40 00 - DEMOLITION. CONTRACTOR MUST COORDINATE ARCHITECTURAL DEMOLITION DRAWINGS AND NOTES WITH HVAC, ELECTRICAL, FIRE PROTECTION, AND PLUMBING DRAWINGS AND NOTES. PATCH OR REBUILD ANY AREAS TO REMAIN THAT HAVE BEEN DAMAGED OR DISTURBED BY HVAC, ELECTRICAL, FIRE PROTECTION, AND PLUMBING DEMOLITION.

31. ALL "EXISTING" INFORMATION ON THE CONTRACT DOCUMENTS HAS BEEN OBTAINED FROM A PREVIOUS SET OF DRAWINGS, OR FROM FIELD INVESTIGATION AND SUCH "EXISTING" INFORMATION MUST BE FIELD VERIFIED BY ALL CONTRACTORS.

32. THE PREMISES WILL BE OCCUPIED AT ALL TIMES DURING THE CONSTRUCTION SCHEDULE. THE CONTRACTOR MUST COORDINATE WITH THE CONTRACTING OFFICER REGARDING ALL INTERRUPTIONS OF UTILITIES, TEMPORARY EXITS, DUST PARTITIONS, DELIVERIES, AND ALL OTHER JOB

REQUIREMENTS.

33. ALL ROOM NUMBERS ARE FOR CONSTRUCTION PURPOSES ONLY. USER HAS THE RIGHT TO RENAME AND/OR RENUMBER ROOMS.

34. THE CONTRACTOR IS TO COORDINATE ACCESS TO THE SITE, INCLUDING THE LOCATION OF TEMPORARY STORAGE TRAILERS WITH THE GOVERNMENT.

REFER TO SHEET GC101_5 FOR ADDITIONAL INFORMATION.

LONG LONGITUDE

LVR LOUVER

-M-

M METER

MACH MACHINE

MAINT MAINTENANCE

MAS MASONRY

MATL MATERIAL

MAX MAXIMUM

MECH MECHANICAL

MFR MANUFACTURER

MIN MINIMUM

MISC MISCELLANEOUS

MM MILLIMETER

MO MASONRY OPENING

MTD MOUNTED

MTL METAL

-N-

N NORTH

N/A NOT APPLICABLE

NIC NOT IN CONTRACT

NO NUMBER

NOM NOMINAL

NTP NOTICE TO PROCEED

NTS NOT TO SCALE

-O-

OC ON CENTER

OD OUTSIDE DIAMETER

OFF OFFICE

OPNG OPENING

OPP OPPOSITE

-P-

PA PUBLIC ADDRESS

PERIM PERIMETER

PKG PACKAGE

PL PLATE

PLMB PLUMBING

PLYWD PLYWOOD

PROJ PROJECT

PSF POUNDS PER SQUARE FOOT

PSI POUNDS PER SQUARE INCH

PVC POLYVINYL CHLORIDE

-R-

R RADIUS

R/A RETURN AIR

RCP REFLECTIVE CEILING PLAN

RD ROOF DRAIN

RECP RECEPTACLE

REFER REFERENCE

REINF REINFORCED

REQ'D REQUIRED

REV REVISION

RH RIGHT HAND

RO ROUGH OPENING

-S-

S SOUTH

S/A SUPPLY AIR

SCHED SCHEDULE

SECT SECTION

SF SQUARE FOOT

SID STRUCTURAL INTERIOR DESIGN

SIM SIMILAR

SPEC SPECIFICATION

SQ SQUARE, AS IN "SQ FT"

STC SOUND TRANSMISSION COEFFICIENT

STD STANDARD

STOR STORAGE

STRUCT STRUCTURAL

SUPP SUPPORT

SUSP SUSPENDED

SYS SYSTEM

-T-

TD TRENCH DRAIN

TECH TECHNICAL

THRU THROUGH

TLT TOILET

TO TOP OF, AS IN "TO STEEL"

TYP TYPICAL

-U-

UL UNDERWRITERS LABORATORY

UNO UNLESS NOTED OTHERWISE

UTIL UTILITY

-V-

VENT VENTILATE, VENTILATOR

VERT VERTICAL

VOL VOLUME

-W-

W WEST, WIDTH

W/ WITH

W/O WITHOUT

WC WATER CLOSET

WD WOOD

WH WATER HEATER

WPAFB WRIGHT-PATTERSON AIR FORCE BASE

WT WEIGHT

CFCI CONTRACTOR FURNISHED CONTRACTOR INSTALLED

CID COMPREHENSIVE INTERIOR DESIGN

CJ CONTROL JOINT, CONSTRUCTION JOINT

CL CENTER LINE

CLG CEILING

CLR CLEAR

CMU CONCRETE MASONRY UNIT

CO CLEANOUT

COL COLUMN

COMM COMMUNICATION

CONC CONCRETE

CONSTR CONSTRUCTION

CONT CONTINUOUS

CONTR CONTRACT, CONTRACTOR

COORD COORDINATE

CORR CORRUGATED OR CORRIDOR

CU CUBIC

°C CELSIUS

-D-

DBL DOUBLE

DEMO DEMOLITION

DESCR DESCRIPTION

DET DETAIL

DIA DIAMETER

DIAG DIAGONAL

DIM DIMENSION

DN DOWN

DR DOOR

DS DOWNSPOUT

DWG /

DWGS

DRAWING / DRAWINGS

-E-

E EAST

EA EACH

EEW EMERGENCY EYEWASH

EEWS EMERGENCY EYEWASH & SHOWER

EF EXHAUST FAN

EJ EXPANSION JOINT

EL ELEVATION, AS IN HEIGHT

ELAST ELASTOMERIC

ELEC ELECTRIC / ELECTRICAL

ELEV ELEVATOR, OR ELEVATION AS IN NORTH ELEV

EQ EQUAL

EQUIP EQUIPMENT

ETC AND SO FORTH (ETCETERA)

EW EACH WAY

EWC ELECTRIC WATER COOLER

EXH EXHAUST

EXIST EXISTING

EXP EXPANSION

EXT EXTERIOR

-F-

FD FLOOR DRAIN

FDN FOUNDATION

FE FIRE EXTINGUISHER WITH WALL BRACKET

FEC FIRE EXTINGUISHER CABINET

FF FINISH FLOOR

FF&E FURNITURE, FIXTURES & EQUIPMENT

FHC FIRE HOSE CABINET (WITH EXTINGUISHER &

BRACKET)

FHR FIRE HOSE REEL (WITH EXTINGUISHER & BRACKET)

FIN FINISHED, FINISH

FLR FLOOR

FT FEET / FOOT

°F FAHRENHEIT

-G-

GA GAUGE

GALV GALVANIZED

GFCI GOVERNMENT FURNISHED CONTRACTOR INSTALLED

GFGI GOVERNMENT FURNISHED GOVERNMENT

INSTALLED

GL GIRT LINE

GRTG GRATING

GYP GYPSUM

GYP BD GYPSUM BOARD

-H-

H HIGH

HD HAND

HDWR HARDWARE

HM HOLLOW METAL

HORIZ HORIZONTAL

HT HEIGHT

HVAC HEATING, VENTILATION & AIR CONDITIONING

-I-

ID INSIDE DIAMETER

IN INCH

INSUL INSULATION

INT INTERIOR

-J-

JAN JANITOR'S CLOSET

-L-

L LEFT, LONG, LENGTH

LAB LABORATORY

LAT LATITUDE

LAV LAVATORY

LB or # POUND

LGM LOGISTICS & MAINTENANCE

LH LEFT HAND

-A-

A/E ARCHITECT/ENGINEER

ACOUST ACOUSTICAL

ADJ ADJACENT, ADJUSTABLE

AFF ABOVE FINISH FLOOR

AHJ AUTHORITY HAVING JURISDICTION

ALT ALTERNATE

ALUM ALUMINUM

APPROX APPROXIMATE

ARCH ARCHITECTURE, ARCHITECT

-B-

BD BOARD

BITUM BITUMINOUS

BLDG BUILDING

BLKG BLOCKING

BO BOTTOM OF, AS IN "BO STEEL"

BTWN BETWEEN

-C-

CAB CABINET

CCTV CLOSED CIRCUIT TELEVISION

ABBREVIATIONS

SEE ADDITIONAL FINISH MATERIAL

ABBREVIATIONS IN THE MATERIAL LEGEND,

DRAWING A-703_5

PLAN LEGEND

ABBREVIATIONS

GENERAL NOTESCALLOUT IDENTIFICATION

GENERAL NOTES: CONSTRUCTION LIMITATIONS:

NOTE:

AT EXISTING GYPSUM BOARD WALLS TO RECEIVE FE BRACKET

REMOVE GYPSUM BOARD AS REQUIRED TO INSTALL FIRE-

RESISTANT TREATED WOOD BLOCKING FOR SECURE ANCHORAGE

OF FE BRACKET. REPAIR / REPLACE GYPSUM BOARD AND MAKE

WALL READY TO RECEIVE NEW WALL FINISH ACCORDING TO ROOM

FINISH SCHEDULE.

M A

R K

D E

S C

R

IP

T

IO

N D

A T

E

W

2Q R

R

_C U

I_ Pl an s-

S

IG

N E

D B

Y

D R

A W

N B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

X

S O

L

IC

IT

A

T

IO

N N

O

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S L O

U

IS

V

IL

L E

D

IS

T R

IC

T

D

R M

A R

T

IN

L U

T H

E R

K

IN

G J

R P

L

L O

U

IS

V

IL

L E

K

Y

W

A R

D P

A R

K W

A Y

K

A N

S A

S C

IT

Y

M

O

SHEET ID

C O

R R

E C

T E

D F

IN

A

L

NOT FOR CONSTRUCTION

US ARMY CORPS

OF ENGINEERS

LOUISVILLE DISTRICT

C H

E C

K E

D B

Y

D

2 3

C

A

B

6 7 8 9

E

F

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

C U

I

CUI

R E

P L A

C E

A H

U -5

P N

Z

H T

V -1

W R

IG

H

T -P

A T

T E

R S

O N

A F

B

O H

IO

-1

-2

G J O

H N

S O

N

AG002_5

B K

E N

N A

L E

Y

W N

E E

D L E

B U

IL

D

IN

G

C O

D E

A N

D L

IF

E

S A

F E

T Y

C R

IT

E

R

IA

E V

A L E

Z Q

U E

Z

WPAFB IFS WPAFB INSTALLATION FACILITY STANDARDS APRIL 2021

UFC-4-010-01 DOD MINIMUM ANTITERRORISM STANDARDS FOR BUILDINGS DEC 2018

UFC-3-600-01 DESIGN: FIRE PROTECTION ENGINEERING FOR FACILITIES AUG 2016, CHANGE 2

UFC-1-200-01 DOD BUILDING CODE JUN 2016, CHANGE 2

NFPA 101 LIFE SAFETY CODE 2018

NFPA 90A

STANDARD FOR THE INSTALLATION OF AIR-CONDITIONING

AND VENTILATING SYSTEMS

NFPA 80 STANDARD FOR FIRE DOORS AND OTHER OPENING PROTECTIVES 2019

NFPA 72 NATIONAL FIRE ALARM AND SIGNALING CODE 2019

NFPA 70 NATIONAL ELECTRIC CODE 2017

NFPA 13 STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS 2019

NFPA 10 STANDARD FOR THE PORTABLE FIRE EXTINGUISHERS 2018

NFPA 1 NATIONAL FIRE CODE 2018

IPC INTERNATIONAL PLUMBING CODE 2015

IMC INTERNATIONAL MECHANICAL CODE 2015

IEBC INTERNATIONAL EXISTING BUILDING CODE 2015

IBC INTERNATIONAL BUILDING CODE 2015

ABBREVIATIONS TITLE EDITION

1. APPLICABLE CODES AND STANDARDS

* EXCEPT AS REQUIRED FOR OCCUPANCY SEPARATION, INCIDENTAL USE, AND OTHER PASSIVE FIRE PROTECTION.

ROOF CONSTRUCTION INCLUDING

SUPPORTING BEAMS AND JOISTS

IIB 0 HR

FLOOR CONSTRUCTION INCLUDING

SUPPORTING BEAMS AND JOISTS

IIB 0 HR

NON-BEARING INTERIOR WALL IIB 0 HR *

NON-BEARING EXTERIOR WALL IIB 0 HR *

BEARING INTERIOR WALL IIB 0 HR *

BEARING EXTERIOR WALL IIB 0 HR *

PRIMARY STRUCTURAL FRAME IIB 0 HR

BUILDING ELEMENT TYPE OF CONSTRUCTION FIRE RESISTANCE RATING

2. TYPE OF CONSTRUCTION (IBC 601)

OPEN OFFICE, CIRCULATION, RESTROOMS,

LOBBY, BREAKROOM

BUSINESS, GROUP B 304.1 6.1.11

AREAS OCCUPANCY IBC NFPA 101

3. CLASSIFICATION OF OCCUPANCY

* NO RATING REQUIRED IF EQUIPPED WITH AN AUTOMATIC SPRINKLER SYSTEM.

EXISTING MECHANICAL ROOM 1 HR FIRE BARRIER (NORTH & WEST WALLS) NFPA 101 38.3.2.1

EXISTING ELECTRICAL ROOM SMOKE PARTITION NFPA 101 38.3.2.1, 8.7.1.2

CORRIDOR 0 HR BARRIER * NFPA 101 38.3.6.1

EXISTING SHAFT ENCLOSURE 3 STORIES OR LESS 1 HR FIRE BARRIER NFPA 101 8.6.5

AREA REQUIRED RATING CODE

4. INCIDENTAL USE AND OTHER PASSIVE FIRE PROTECTION

* IBC 702 - FIRE SEPARATION DISTANCE = DISTANCE FROM BUILDING'S FACE TO CLOSEST INTERIOR LOT LINE, CENTERLINE OF A STREET ALLEY OR

PUBLIC WAY, OR IMAGINARY LINE BETWEEN TWO BUILDINGS.

B NORTH/SOUTH/WEST/EAST > 10 NO RATING

OCCUPANCY ELEVATION

RESTRICTIVE FIRE SEPARATION

DISTANCE (FT) *

FIRE RESISTIVE RATING OF

EXTERIOR WALL

5. BUILDING SEPARATION (IBC TABLE 602)

0 HR SMOKE PARTITION 0 HR (SELF CLOSING)

SMOKE DAMPERS ON

TRANSFER DUCT ONLY

0 HR NFPA 101: 8.4

1 HR FIRE BARRIER 3/4 HR

FIRE DAMPERS NOT

REQUIRED

1 HR

NFPA 90A: 5.3.1.1

AND 5.4.1.1, NFPA 101

TABLE 8.3.3.2.2

1 HR FIRE BARRIER FOR MEANS OF EGRESS

(INCLUDING STAIRWELLS)

1 HR NOT PERMITTED

1 HR

(PENETRATIONS

PERMITTED WHEN

SERVING THE

STAIRWELL)

NFPA 101 TABLE

8.3.3.2.2, 7.1.3.2.1

COMPONENT

FIRE DOOR/SHUTTER

ASSEMBLIES

DUCT PENETRATIONS

OTHER

PENETRATIONS

CODE

6. OPENING PROTECTION FOR FIRE AND SMOKE RESISITIVE CONSTRUCTION

LEVEL 2 COLLABORATION SPACE COLLABORATION ROOMS / SPACES <= 450 SF 1549 30 52

LEVEL 2

MECH ROOM, ELEC ROOM,

STORAGE

MECHANICAL, ELECTRICAL, OTHER BUILDING

EQUIPMENT SPACES

2345 500 5

LEVEL 2

CONFERENCE ROOM, BREAK

ROOM

ASSEMBLY WITHOUT FIXED SEATING 1105 15 NET 74

LEVEL 2 OFFICES, BATHROOMS BUSINESS AREAS 23975 150 160

FLOOR AREA FUNCTION OF SPACE AREA (SF)*

OCCUPANT

LOAD FACTOR

(SF/PERSON)

OCCUPANTS

7. OCCUPANT LOAD CALCULATIONS (NFPA 101, UFC 3-600-01)

* OCCUPANT LOAD ANALYSIS ONLY INCLUDES AREAS WITHIN THE PROJECT SCOPE OF WORK AND IS NOT INTENDED TO BE A FULL BUILDING ANALYSIS.

LEVEL 2 28,974 291 2 (7.4.1.1) 1/3 DIAGONAL (7.5.1.3.3)

FLOOR GROSS AREA (SF) OCCUPANTS REQUIRED EXITS (NFPA 101)

REQUIRED EXIT SEPARATION

(NFPA 101)

8. OCCUPANT LOAD SUMMARY AND MINUMUM EXITS FROM FLOOR

BUSINESS

LESS THAN 100 FT TRAVEL DISTANCE AND

LESS THAN 100 OCCUPANTS

100 FT OR GREATER TRAVEL DISTANCE OR

MORE THAN 100 OCCUPANTS

38.2.4

OCCUPANCY CONDITION PERMITTING ONE EXIT CONDITION REQUIRING TWO OR MORE EXITS CODE SECTION

9. MINIMUM EXITS OR EXIT ACCESSES FROM A SPACE OR AREA (NFPA 101)

BUSINESS 100 50 300

OCCUPANCY COMMON PATH LIMIT (FT) DEAD END LIMIT (FT) TRAVEL DISTANCE LIMIT (FT)

10. COMMON PATH, DEAD-END, AND TRAVEL DISTANCE LIMITS (NFPA 101, TABLE A.7.6)

STAIRWAYS PER PERSON 0.3 TABLE 7.3.3.1

OTHER EGRESS COMPONENTS PER PERSON 0.2 TABLE 7.3.3.1

EXISTING CORRIDOR SERVING LESS THAN 50 OCCUPANTS MINIMUM 28 SECTION 7.3.4.1.2

EXISTING CORRIDOR SERVING 50 OR MORE OCCUPANTS MINIMUM 44 SECTION 39.2.3.2

DOORS IN EGRESS ACCESS PER COMPONENT 32 SECTION 7.2.1.2.3.2

EXISTING STAIR IN EGRESS ACCESS MINIMUM 36 SECTION 7.2.2.2.1.1

COMPONENT REQUIREMENT WIDTH (IN) NFPA 101

11. MINIMUM EGRESS WIDTHS

BUSINESS CLASS C CLASS C CLASS C

OCCUPANCY EXITS EXIT ACESS CORRIDORS OTHER SPACES

12. MINIMUM INTERIOR FINISH RATINGS (NFPA 101, TABLE A.10.2.2)

SPRINKLERS PROVIDED THROUGHOUT THE BUILDING NOT REQUIRED REQUIRED

SPRINKLERS STANDPIPE FIRE EXTINGUISHERS

13. FIRE SUPPRESSION REQUIREMENTS (UFC 3-600-01 9-7, 9-10, 9-17)

MANUAL FIRE ALARM PULL STATIONS

PROVIDED AT EXITS

FLOW AND TAMPER SWITCHES, SPOT SMOKE

DETECTORS AT ALARM PANELS AND DUCT SMOKE

DETECTORS PROVIDED

VOICE MESSAGING, FIRE ALARM STROBES

MANUAL INITIATION AUTOMATIC INITIATION OCCUPANT NOTIFICATION

14. FIRE ALARM REQUIREMENTS (UFC 3-600-01 9-18)

NOT REQUIRED NOT REQUIRED SMOKE PARTITIONS WHERE NOTED

SMOKE CONTROL SYSTEM SMOKE AND HEAT VENTS PASSIVE SMOKE MANAGEMENT

15. SMOKE MANAGEMENT SYSTEMS (UFC 3-600-01 9-20)

M A

R K

D E

S C

R

IP

T

IO

N D

A T

E

W

2Q R

R

_C U

I_ Pl an s-

R O T E G E

P R O T E G E

PROTEGE

P R O T E G E

P R O T E G E

PROTEGE

P R O T E G E

P R O T E G E

P R O T E G E

P R O T E G E

PROTEGE

P R O T E G E

PROTEGE

P R O T E G E

P R O T E G E

P R O T E G E

P R O T E G E

P R O T E G E

C P

CP

C P

CP

S

S S

S

SS S

S S

S

SS SS

S S

S S

S

SS SSS

P

2 3 4 5 6 7 8 9 10 11 12 13 14 15

G

H

J

K

KL

L

M

N

Q

W1

W280

W253

W279

W299

W298

W209

W212

W210 W220D

W220

W220A

W204

W208

W5

W203E

W203D

W203C

W203

W203A

25' - 0" 20' - 0" 20' - 0" 20' - 0" 20' - 0" 20' - 0" 20' - 0" 20' - 0" 20' - 0" 20' - 0" 20' - 0" 20' - 0" 20' - 0" 20' - 11"

1'

W219

W225B

W225A

W209A

W209B

W209C

W209D

W209E

W209F

W209G

W209H

W221A W221B W221C

W221D W221E

W221F

138'CP:100'

203'CP:59'

126'CP:94'

187'CP:33'

W2

DN

DNDN

FE:BR

FE:BR

FE:BR

FE:BR

FE:BR

FE:BR

FE:BR

FE:BR

FE:BR

COMMON PATH OF TRAVEL

TRAVEL DISTANCE

EGRESS

PATH

COMMON PATH

TERMINATION POINT

EXIT DOOR

LIFE SAFETY GENERAL NOTES:

1. EXCEPT WHERE INDICATED, ALL LIFE SAFETY

FEATURES INCLUDING, BUT NOT LIMITED TO WALL

RATINGS, AND OCCUPANCY CLASSIFICATIONS

MUST REMAIN UNCHANGED.

2. REFER TO ARCHITECTURAL LEGEND, ON DRAWING

AG001_5 FOR ADDITIONAL INFORMATION

REGARDING SYMBOLS AND ABBREVIATIONS.

3. REFER TO THE ELECTRICAL LIGHTING PLANS FOR

LOCATION OF EXIT SIGNS AND EMERGENCY

LIGHTING.

4. REFER TO THE FIRE SUPPRESSION AND ALARM

PLANS FOR LOCATION OF FIRE PROTECTION

DEVICES.

5. ALL EXISTING WALL CLASSIFICATIONS SHOWN

ARE BASED ON EXISTING DRAWINGS.

OCCUPANT LOAD LEGEND

EGRESS PATH

300'CP:100'

BUSINESS 1 PERSON / 150 SF GROSS

FIRE BARRIER LEGEND

SMOKE

PARTITION

CP

ASSEMBLY

BUILDING EQUIPMENT

1 PERSON / 15 SF NET

1 PERSON / 500 SF GROSS

BUSINESS

COLLABORATION

SPACE, <= 450 SF

1 PERSON / 30 SF GROSS

1 HR FIRE

BARRIER

FIRE EXTINGUISHER

FE:BR

-FE: FIRE EXTINGUISHER

-BR: BRACKET MOUNTED

2 HR FIRE

BARRIER

A:B:C TYPE DRY CHEMICAL

4A:20B:C NOT IN

SCOPE

SCOPE LEGEND

KEYPLAN

NOT TO SCALE

A B

D E

S

IG

N E

D B

Y

D R

A W

N B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

X

S O

L

IC

IT

A

T

IO

N N

O

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S L O

U

IS

V

IL

L E

D

IS

T R

IC

T

D

R M

A R

T

IN

L U

T H

E R

K

IN

G J

R P

L

L O

U

IS

V

IL

L E

K

Y

W

A R

D P

A R

K W

A Y

K

A N

S A

S C

IT

Y

M

O

SHEET ID

C O

R R

E C

T E

D F

IN

A

L

NOT FOR CONSTRUCTION

US ARMY CORPS

OF ENGINEERS

LOUISVILLE DISTRICT

C H

E C

K E

D B

Y

D

2 3

C

A

B

6 7 8 9

E

F

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

C U

I

CUI

R E

P L A

C E

A H

U -5

P N

Z

H T

V -1

W R

IG

H

T -P

A T

T E

R S

O N

A F

B

O H

IO

-1

-2

G J O

H N

S O

N

AG003_5

B K

E N

N A

L E

Y

W N

E E

D L E

S E

C O

N D

F L O

O R

L

IF

E S

A F

E T

Y P

L A

N E

V

A L E

Z Q

U E

Z

SCALE: 3/32" = 1'-0"A1

SECOND FLOOR - LIFE SAFETY PLAN

0 8' 16' 24'

PLAN

NORTH

A R

E A

A

A R

E A

B

M A

R K

D E

S C

R

IP

T

IO

N D

A T

E

W

2Q R

R

_C U

I_ Pl an s-

GENERAL NOTES:

LEAD BASED PAINT MUST BE ASSUMED TO BE PRESENT ON

EXISTING PAINTED COMPONENTS AND LEAD SOLDER JOINTS MUST

BE ASSUMED TO BE PRESENT WITHIN CONNECTION POINTS ON

EXISTING SEWER LINES THROUGHOUT THE MODIFICATION AREAS.

ALL CONTRACTORS MUST COMPLY WITH THE OCCUPATIONAL

SAFETY AND HEALTH ADMINISTRATION 29 CODE OF FEDERAL

REGULATIONS (CFR) 1926.62 LEAD IN CONSTRUCTION STANDARD

PRIOR TO ANY IMPACT OR DISTURBANCE OF THESE MATERIALS.

SOME OF THE REQUIREMENTS INCLUDED WITHIN THIS STANDARD

INCLUDE: INITIAL EXPOSURE MONITORING, PROVIDING PERSONAL

PROTECTIVE EQUIPMENT (PPE) AND HAND WASHING FACILITIES. IN

ADDITION, ALL WORK MUST BE CONDUCTED IN ACCORDANCE WITH

WPAFB GENERAL ENVIRONMENTAL PROTECTION REQUIREMENTS

SECTION 01 35 43.

THE CONTRACTOR (HAZARDOUS MATERIALS ABATEMENT

CONTRACTOR) IS RESPONSIBLE FOR FOLLOWING AND ADHERING TO

ALL APPLICABLE FEDERAL, STATE, AND LOCAL REGULATIONS

INCLUDING, BUT NOT LIMITED TO, THOSE SET FORTH BY THE UNITED

STATES ENVIRONMENTAL PROTECTION AGENCY (USEPA),

OCCUPATIONAL HEALTH AND SAFETY ADMINISTRATION (OSHA), AND

OHIO ENVIRONMENTAL PROTECTION AGENCY. CONTRACTOR MUST

MAINTAIN A VALID AND CURRENT LICENSE IN THE STATE OF OHIO AS

AN ASBESTOS ABATEMENT CONTRACTOR.

IF A MATERIAL THAT WAS NOT PART OF THE ASBESTOS

ASSESSMENT CONDUCTED FOR THIS PROJECT IS DISCOVERED

DURING THE COURSE OF RENOVATION THEN THE CONTRACTOR IS

RESPONSIBLE TO HAVE THE MATERIAL ANALYZED TO DETERMINE IF

IT CONTAINS ASBESTOS.

THE CONTRACTOR MUST DECONTAMINATE ALL BUILDING

MATERIALS, WHICH BECOME CONTAMINATED OR ARE DISTURBED

FROM ASBESTOS REMOVAL.

THE CONTRACTOR MUST COORDINATE ALL ON-SITE WORK WITH THE

ARCHITECT / ENGINEER, CONSTRUCTION MANAGER, GENERAL AND

SUB-CONTRACTORS, AND WPAFB TO FACILITATE THE PROMPT

COMPLETION OF ALL ASPECTS OF THE MODIFICATION PROJECT.

THE CONTRACTOR IS RESPONSIBLE FOR REMOVING AND DISPOSING

ALL NON-ACM BUILDING MATERIALS TO ACCESS ACM. ALL

SELECTIVE DEMOLITION WORK PRACTICES MUST OCCUR IN A FULL-

CONTAINMENT IN THE EVENT THAT ACM BECOMES DAMAGED VIA

DEMOLITION WORK PRACTICES.

THE CONTRACTOR IS RESPONSIBLE FOR THE COMPLETE REMOVAL

AND CLEANUP OF ALL PCB’S AND EQUIPMENT CONTAINING PCB’S

IDENTIFIED IN ENVIRONMENTAL SURVEY REPORT, ALL WORK MUST

BE IN ACCORDANCE WITH SPECIFICATION SECTIONS 01 35 43.

THE CONTRACTOR IS RESPONSIBLE TO COMPLETE ALL REMOVAL,

DISPOSAL, AND/OR DECONTAMINATION OF ALL UNIVERSAL WASTE

SPECIFIED IN THE SURVEY REPORT (REFER TO 01 35 43), ITEMS CAN

INCLUDE BUT ARE NOT LIMITED TO HALON’S, MERCURY CONTAINING

LAMPS, MERCURY CONTAINING SWITCHES, FIRE AND/OR SMOKE

DETECTORS WITH RADIOACTIVE SOURCES, NICAD, LITHIUM ION, AND

LEAD-ACID BATTERIES, AND EQUIPMENT CONTAINING OZONE-

DEPLETING REFRIGERANTS. THE CONTRACTOR IS RESPONSIBLE

FOR FOLLOWING AND ADHERING TO ALL APPLICABLE FEDERAL,

STATE, AND LOCAL REGULATIONS INCLUDING, BUT NOT LIMITED TO,

THOSE SET FORTH BY THE UNITED STATES ENVIRONMENTAL

PROTECTION AGENCY (USEPA) AND OCCUPATIONAL HEALTH AND

SAFETY ADMINISTRATION (OSHA), ALL WORK MUST BE IN

ACCORDANCE WITH SPECIFICATION SECTION 01 35 43.

SPECIAL CARE SHOULD BE TAKEN BY ALL CONTRACTORS WHEN

WORKING NEAR EXISTING ELECTRIC, WATER, GAS, AND STEAM

LINES.

ALL WORK MUST BE PERFORMED IN ACCORDANCE WITH WPAFB

SPECIFICATION SECTION 01 35 43.

COORDINATE DISPOSITION OF EXCESS RADIOACTIVE COMMODITIES,

E.G. IONIZATION TYPE SMOKE DETECTORS, RADIOLUMINESCENT

EMERGENCY EXIT SIGNS, OR ANY OTHER RADIOACTIVE COMMODITY

AND/OR RADIOACTIVE CONTAMINANT THROUGH THE INSTALLATION

RADIATION SAFETY OFFICER, 88 OMR/SGXB.

ALL METAL AND WIRING SHALL BE RECYCLED AT THE WPAFB BASE

RECYCLING CENTER. THE WPAFB RECYCLING CENTER IS AVAILABLE

FOR CONTRACTOR USE TO REDUCE WASTE DISPOSAL. ALL

RECYCLABLE METAL IS TO BE RECYCLED THROUGH THE BASE

RECYCLING CENTER. ALL RECYCLING MUST BE ACCOMPLISHED IN

ACCORDANCE WITH WPAFB SPECIFICATION SECTION 01 35 43.

CONTACT WPAFB RECYCLING PROGRAM MANAGER AT 937-257-5060

TO CONFIRM WHAT MATERIALS ARE RECYCLABLE AND TO

COORDINATE TURN-IN. THE CONTRACTOR SHALL SUBMIT A

QUARTERLY SUMMARY REPORT TO THE GOVERNMENT CONTRACT

REPRESENTATIVE IAW WPAFB SPECIFICATION SECTION 01 35 43

STATING (1) THE COST TO RECYCLE AND THE TONNAGE OF

CONSTRUCTION AND DEMOLITION MATERIALS RECYCLED, (2) THE

COST TO DIVERT/REUSE THE TONNAGE OF CONSTRUCTION AND

DEMOLITION MATERIALS DIVERTED/REUSE, (3) THE COST TO MULCH

AND THE TONNAGE AND COST OF CONSTRUCTION AND DEMOLITION

MATERIALS MULCHED, (4) THE COST FOR WASTE-TO-ENERGY AND

THE TONNAGE OF CONSTRUCTION AND DEMOLITION MATERIALS

CONVERTED FROM WASTE-TO-ENERGY, (5) THE COST TO LANDFILL

AND THE TONNAGE OF CONSTRUCTION AND DEMOLITION

MATERIALS LAND-FILLED, (6) THE COST TO INCINERATE AND THE

TONNAGE OF CONSTRUCTION AND DEMOLITION MATERIALS

INCINERATED, AND (7) EXPLANATION OF THE DIVERSION RATE IF

LESS THAN 60%. THE QUARTERLY SUMMARY REPORTS SHALL BE

RECEIVED ON APRIL 7, JULY 7, OCTOBER 7, AND JANUARY 7

COVERING THE THREE MONTHS PRIOR. THE QUARTERLY SUMMARY

REPORTS SHALL BE ON THE WPAFB DIVERSION FORM. FOR

ADDITIONAL INFORMATION CONTACT THE RECYCLING PM, BRIAN

ROBINSON, AT 937-257-5060 OR BRIAN.ROBINSON.5@US.AF.MIL.

TURN-IN ALL MERCURY CONTAINING DEVICES, SWITCHES AND

THERMOSTATS TO 88 CEG/CEIE IN ACCORDANCE WITH WPAFB

SPECIFICATION SECTION 01 35 43 FOR RECYCLING.

TURN-IN ALL MERCURY CONTAINING LAMPS TO 88 CEG/CEIE IN

ACCORDANCE WITH WPAFB SPECIFICATION SECTION 01 35 43.

TURN-IN ALL PCB CONTAINING LIGHT BALLAST TO 88 CEG/CEIE IN

ACCORDANCE WITH WPAFB SPECIFICATION SECTION 01 35 43.

REMOVE AND DISPOSE OF ANY ASBESTOS CONTAINING MATERIAL IN

ACCORDANCE WITH WPAFB SPECIFICATION SECTION 01 35 43.

RECOVER AND RECLAIM ANY REFRIGERANT IN ACCORDANCE WITH

WPAFB SPECIFICATION SECTION 01 35 43.

ANY USE OF RADIOACTIVE MATERIALS BY THE CONTRACTOR,

INCLUDING MOISTURE DENSITY GAUGES, MUST BE APPROVED BY

THE WPAFB RADIATION SAFETY OFFICER A MINIMUM OF 30

CALENDAR DAYS PRIOR TO BEING BROUGHT ONTO WPAFB. THIS

REQUIREMENT IS FROM WPAFB 40-201.

NO ASBESTOS-CONTAINING MATERIAL MUST BE INSTALLED DURING

THIS PROJECT.

30 DAYS PRIOR TO START OF WORK, THE CONTRACTOR SHALL TAKE

A REPRESENTATIVE SAMPLE OF THE HVAC SYSTEM WATER TO

DETERMINE WHETHER IT CAN BE DRAINED DIRECTLY INTO THE

SANITARY SEWER. ANALYZE THE WATER TO DETERMINE THE TOTAL

LEVEL OF EACH OF THE FOLLOWING: ARSENIC, CADMIUM,

CHROMIUM, COPPER, CYANIDE, LEAD, MERCURY, MOLYBDENUM,

NICKEL, SELENIUM, SILVER, ZINC, SULFIDE, OIL AND GREASE,

PHOSPHORUS, COD AND BOD. THE LAB PERFORMING THE

ANALYSES MUST BE CERTIFIED BY OHIO EPA TO ANALYZE FOR

THESE PARAMETERS. PROVIDE A COPY OF THE LAB’S REPORT TO

THE CONTRACTING OFFICER, WHO WILL IN TURN FORWARD IT TO 88

CEG/CEIEA FOR A DETERMINATION ON THE WASTEWATER DISPOSAL

METHOD.

ALL WINDOW AND DOOR FRAME CAULKING AND GLAZING WILL BE

TREATED AS CONTAINING ASBESTOS UNLESS TESTING PROVES IT

TO BE ASBESTOS FREE.

THE GENERATION OF FUGITIVE EMISSIONS MUST BE KEPT TO A

MINIMUM USING APPROVED DUST SUPPRESSING METHODS SUCH AS

WATER SPRAYS ON AREA OF HIGH DUST GENERATION. FOR

ADDITIONAL INFORMATION PLEASE CONTACT THE 88 CEG/CEIEA AIR

PM CHET POWERS AT 937-257-3349 OR BY EMAIL AT

CHET.POWERS@US.AF.MIL.

ALL HAZARDOUS MATERIALS MUST BE PROPERLY MANAGED,

LABELED AND STORED. ANY HAZARDOUS WASTE GENERATED FROM

THIS CONSTRUCTION ACTIVITY MUST BE PROPERLY

CHARACTERIZED, LABELED AND MANAGED BY TRAINED EMPLOYEE

OF THE CONTRACTOR WITH KNOWLEDGE OF THE ACTIVITY /

PROCESS WHERE THE WASTE WAS GENERATED. ALL HAZARDOUS

WASTE WILL BE TURNED OVER TO THE GOV’T FOR DISPOSAL. IN

ADDITION PROPER COORDINATION IS NEEDED WITH 88 CEG/CEIEC.

QUESTIONS CONCERNING THE REQUIREMENTS FOR STORAGE AND

DISPOSAL OF ANY HAZARDOUS MATERIALS CAN BE ADDRESSED BY

THE 88 CEG/CEIEC HAZARDOUS MATERIALS PM AT

KAREN.BEASON@US.AF.MIL OR 937-257-5899 OR 88 CEG/CEIEC

HAZARDOUS WASTE PM, MARIA.CRUSET@US.AF.MIL OR

937-257-0023.

UPON COMPLETION, ALL EXPOSED SURFACES IN EACH ABATEMENT

WORK AREA MUST BE MADE FREE OF ALL VISIBLE DUST AND DEBRIS

VIA THE USE AND APPLICATION OF THE ENGINEERING AND WORK

PRACTICE CONTROLS AND PROCEDURES SPECIFIED. THE ABSENCE

OF FIBERS IN EACH WORK AREA WILL BE VERIFIED AND

DOCUMENTED BY USE OF AN AGGRESSIVE AIR SAMPLING METHOD,

PHASE-CONTRAST MICROSCOPY (PCM) AND TRANSMISSION

ELECTRON MICROSCOPY (TEM). THE CONTRACTOR’S FAILURE TO

MEET THE SPECIFIED CLEARANCE CRITERIA WILL REQUIRE HIM TO

RECLEAN AND RETEST AT HIS OWN EXPENSE.

ALL ASBESTOS ABATEMENT WORK MAY BE DONE DURING NORMAL

WORKING HOURS UNLESS THE AREA IS A COMMON ACCESS EGRESS

CORRIDOR AND THEN THE WORK MUST BE DONE AFTER NORMAL

WORKING HOURS (1600-2400) OR WEEKENDS.

THE OFFICE AREAS OUTSIDE OF CONSTRUCTION WILL REMAIN

OCCUPIED BY WPAFB DURING CONSTRUCTION. CONTRACTOR MUST

PROVIDE CRITICAL BARRIER TO PREVENT AIRBORNE ASBESTOS IN A

WORK AREA FROM MIGRATING TO AN ADJACENT AREA. SEE H-102_5

FOR CONSTRUCTION AREA LIMITS.

CONTRACTOR MUST SEAL AND PROTECT ALL HVAC SYSTEM,

SUPPLY AND RETURN AIR CONNECTING DUCT. ALL AIR HANDLING

UNITS WILL NEED TO BE ISOLATED OR SHUT DOWN TO MEET

SPECIFICATION SECTION 01 35 43. ALL VENTILATION EXHAUST AIR

TO THE OUTSIDE MUST BE HEPA FILTERED DURING ABATEMENT.

ALL EXISTING OFFICE FURNITURE AND EQUIPMENT MUST BE

REMOVED AND STORED BY CONTRACTOR PRIOR TO ABATEMENT

WORK.

PRIOR TO BEGINNING MODIFICATION TO BLDG. 856 NOTIFICATION OF

DEMOLITION AND MODIFICATION IS REQUIRED TO THE REGIONAL AIR

POLLUTION AND CONTROL AGENCY (RAPCA) A MINIMUM OF 10

CALENDAR DAYS PRIOR TO BEGINNING CONSTRUCTION.

SOIL DISTURBANCE DURING THIS PROJECT, INCLUDING EQUIPMENT

STAGING AREAS, WILL REQUIRE EROSION CONTROL MEASURES.

FOR PROJECTS THAT DISTURB LESS THAN AN ACRE OF SOIL, AN

EROSION CONTROL PLAN IS REQUIRED PRIOR TO SOIL

DISTURBANCE. FOR PROJECTS THAT DISTURB MORE THAN AN ACRE,

A NOTICE OF INTENT (NOI) MUST BE APPROVED BY THE OHIO EPA

PRIOR TO ANY SOIL BEING DISTURBED AS WELL AS A STORM WATER

POLLUTION PREVENTION PLAN (SWPPP) APPROVED BY 88

CEG/CEIEA. PLEASE CONTACT THE 88 CEG/CEIEA WATER PM MIKE

VAUGHN, (937-257-8028 OR MICHAEL.VAUGHN.3@US.AF.MIL) FOR

ADDITIONAL INFORMATION.

IF ANY REFRIGERANT-CONTAINING EQUIPMENT SCHEDULED FOR

NEW INSTALLATION, INCLUDING WATER COOLERS, THEY MUST

UTILIZE AN HFC REFRIGERANT. CFC AND HCFC REFRIGERANTS ARE

NOT AUTHORIZED FOR NEW EQUIPMENT INSTALLATION. FOR

ADDITIONAL INFORMATION PLEASE CONTACT THE 88 CEG/CEIEA AIR

PROGRAM MR. CHET POWERS AT 937-257-3349 OR

CHET.POWERS@US.AF.MIL.

SUBMIT A REFRIGERANT RECORD WITHIN ONE DAY OF COMPLETION

OF WORK INVOLVING REFRIGERANTS TO THE 88 CEG/CEIEA AIR

PROGRAM, CHET POWERS AT 937-257-3349 OR

CHET.POWERS@US.AF.MIL.

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

14.

15.

16.

17.

18.

19.

20.

21.

22.

23.

24.

25.

26.

27.

28.

29.

30.

31.

32.

D E

S

IG

N E

D B

Y

D R

A W

N B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

X

S O

L

IC

IT

A

T

IO

N N

O

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S L O

U

IS

V

IL

L E

D

IS

T R

IC

T

D

R M

A R

T

IN

L U

T H

E R

K

IN

G J

R P

L

L O

U

IS

V

IL

L E

K

Y

W

A R

D P

A R

K W

A Y

K

A N

S A

S C

IT

Y

M

O

SHEET ID

C O

R R

E C

T E

D F

IN

A

L

NOT FOR CONSTRUCTION

US ARMY CORPS

OF ENGINEERS

LOUISVILLE DISTRICT

C H

E C

K E

D B

Y

D

2 3

C

A

B

6 7 8 9

E

F

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

C U

I

CUI

R E

P L A

C E

A H

U -5

P N

Z

H T

V -1

W R

IG

H

T -P

A T

T E

R S

O N

A F

B

O H

IO

-1

-2

G J O

H N

S O

N

H-101_5

N L A

S H

L E

Y

A T

U N

G S

E T

H

H A

Z A

R D

O U

S B

U

IL

D

IN

G M

A T

E R

IA

L S

P L A

N N

O T

E S

G J O

H N

S O

N

M A

R K

D E

S C

R

IP

T

IO

N D

A T

E

W

2Q R

R

_C U

I_ Pl an s-

UP

UP

W220E

W220

C O

R W

W227 W226A

W226 W225A

W

W

0B

W220A

W220C

W220D COR W280

W

W210

W

4A

W209

W214

W299

W

0F

W

C

O R

W298

W204 W203F W203A

W

3B

W203C

W

3D W

3E W203

DN

DNDN

LEGEND:

CONSTRUCTION AREA LIMITS

PROJECT AREA

NOT IN

SCOPE

SCOPE LEGEND

KEYPLAN

NOT TO SCALE

A B

D E

S

IG

N E

D B

Y

D R

A W

N B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

X

S O

L

IC

IT

A

T

IO

N N

O

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S L O

U

IS

V

IL

L E

D

IS

T R

IC

T

D

R M

A R

T

IN

L U

T H

E R

K

IN

G J

R P

L

L O

U

IS

V

IL

L E

K

Y

W

A R

D P

A R

K W

A Y

K

A N

S A

S C

IT

Y

M

O

SHEET ID

C O

R R

E C

T E

D F

IN

A

L

NOT FOR CONSTRUCTION

US ARMY CORPS

OF ENGINEERS

LOUISVILLE DISTRICT

C H

E C

K E

D B

Y

D

2 3

C

A

B

6 7 8 9

E

F

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

C U

I

CUI

R E

P L A

C E

A H

U -5

P N

Z

H T

V -1

W R

IG

H

T -P

A T

T E

R S

O N

A F

B

O H

IO

-1

-2

G J O

H N

S O

N

H-102_5

N L A

S H

L E

Y

A T

U N

G S

E T

H

H A

Z A

R D

O U

S B

U

IL

D

IN

G M

A T

E R

IA

L S

S E

C O

N D

F L O

O R

P L A

N

A C

M

G J O

H N

S O

N

SCALE: 1/16" = 1'-0"A1

HAZARDOUS BUILDING MATERIALS - ACM

SCALE IN FEET

0 8' 16' 32'

PLAN

NORTH

GENERAL NOTES:

1. APPROXIMATELY 1,300 SQUARE FEET OF CATEGORY II ACM DUCT INSULATION WRAP AND

ADHESIVE ASSOCIATED WITH AHU-5 IS ANTICIPATED TO BE REMOVED AS PART OF THIS

PROJECT.

2. DAMAGE PIPE JOINTS AND INSULATION AROUND THE PIPES WERE OBSERVED IN

MECHANICAL ROOM W299 (PIPING ASSOCIATED WITH AHU-5). 5 PIPE JOINTS/FITTINGS AND

36 LINEAR FEET OF CATEGORY II ACM PIPING WERE NOTED IN THIS LOCATION AND WILL BE

REMOVED AS PART OF THIS PROJECT.

3. THERE IS 10 SQUARE FEET OF ASSUMED ACM VIBRATION CLOTH AND 10 SQUARE FEET OF

ASSUMED ACM GASKETS ASSOCIATED WITH THE REMOVAL OF AHU-5.

4. THERE IS ONE ELECTRICAL BOX ASSOCIATED WITH AHU-5 WHICH CONTAINS ~100 SQUARE

FEET OF TRANSITE PANEL THAT WILL BE REMOVED AS PART OF THIS PROJECT.

5. CATEGORY II ACM MASTIC ASSOCIATED WITH AHU-5 WAS DETERMINED TO BE PRESENT

WITHIN/ON THE UNIT. THE FOLLOWING WERE TYPES OF MASTIC IDENTIFIED:

• YELLOW DUCT MASTIC – ~15 SQUARE FEET APPLIED ON AHU-5 DUCT TRANSITION SEAM

• GRAY DUCT MASTIC – ~25 SQUARE FEET APPLIED ON AHU-5 SEAMS OF THE ENTIRE UNIT

THESE MATERIALS WILL NEED TO BE REMOVED AS PART OF THIS MODIFICATION PROJECT.

6. CATEGORY II ACM WHITE ADHESIVE (~71 SQUARE FEET) AND GRAY CAULK (~10.25 SQUARE

FEET) WERE DETERMINED TO BE PRESENT ON THE VAV BOXES THROUGHOUT THE

MODIFICATION AREAS AND WILL NEED TO BE REMOVED AS PART OF THIS MODIFICATION

PROJECT.

7. REMOVAL AND DISPOSAL IN ACCORDANCE WITH SPECIFICATION SECTION 01 35 43.

8. ASBESTOS CONTAMINATED BUILDING COMPONENTS ARE NOT REGULATED ASBESTOS

CONTAINING MATERIALS (RACM). HOWEVER, ALL MODIFICATION / DEMOLITION WORK

IMPACTING THESE COMPONENTS MUST BE PERFORMED IN ACCORDANCE WITH OSHA

ASBESTOS STANDARD 29 CFR 1926.1101.

M A

R K

D E

S C

R

IP

T

IO

N D

A T

E

W

2Q R

R

_C U

I_ Pl an s-

S

IG

N E

D B

Y

D R

A W

N B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

X

S O

L

IC

IT

A

T

IO

N N

O

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S L O

U

IS

V

IL

L E

D

IS

T R

IC

T

D

R M

A R

T

IN

L U

T H

E R

K

IN

G J

R P

L

L O

U

IS

V

IL

L E

K

Y

W

A R

D P

A R

K W

A Y

K

A N

S A

S C

IT

Y

M

O

SHEET ID

C O

R R

E C

T E

D F

IN

A

L

NOT FOR CONSTRUCTION

US ARMY CORPS

OF ENGINEERS

LOUISVILLE DISTRICT

C H

E C

K E

D B

Y

D

2 3

C

A

B

6 7 8 9

E

F

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

C U

I

CUI

R E

P L A

C E

A H

U -5

P N

Z

H T

V -1

W R

IG

H

T -P

A T

T E

R S

O N

A F

B

O H

IO

-1

-2

G J O

H N

S O

N

H-103_5

N L A

S H

L E

Y

A T

U N

G S

E T

H

R E

F E

R E

N C

E

S E

C O

N D

F L O

O R

P L A

N W

E S

T W

IN

G

G J O

H N

S O

N

FOR REFERENCE ONLY

M A

R K

D E

S C

R

IP

T

IO

N D

A T

E

W

2Q R

R

_C U

I_ Pl an s-

S

IG

N E

D B

Y

D R

A W

N B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

X

S O

L

IC

IT

A

T

IO

N N

O

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S L O

U

IS

V

IL

L E

D

IS

T R

IC

T

D

R M

A R

T

IN

L U

T H

E R

K

IN

G J

R P

L

L O

U

IS

V

IL

L E

K

Y

W

A R

D P

A R

K W

A Y

K

A N

S A

S C

IT

Y

M

O

SHEET ID

C O

R R

E C

T E

D F

IN

A

L

NOT FOR CONSTRUCTION

US ARMY CORPS

OF ENGINEERS

LOUISVILLE DISTRICT

C H

E C

K E

D B

Y

D

2 3

C

A

B

6 7 8 9

E

F

CONTROLLED UNCLASSIFIED INFORMATION (CUI)

C U

I

CUI

R E

P L A

C E

A H

U -5

P N

Z

H T

V -1

W R

IG

H

T -P

A T

T E

R S

O N

A F

B

O H

IO

-1

-2

G J O

H N

S O

N

H-104_5

N L A

S H

L E

Y

A T

U N

G S

E T

H

R E

F E

R E

N C

E

S E

C O

N D

F L O

O R

P L A

N W

E S

T W

IN

G

G J O

H N

S O

N

FOR REFERENCE ONLY

M A

R K

D E

S C

R

IP

T

IO

N D

A T

E

W

2Q R

R

_C U

I_ Pl an s-

WALL AND FLOOR LEGEND

EXISTING DEMOUNTABLE PARTITIONS & DOOR(S) - TO BE DEMOLISHED

RE: DETAIL A1 ON SHEET A-512_5

EXISTING PARTITIONS - TO REMAIN

EXISTING PARTITIONS - TO BE DEMOLISHED

EXISTING RAISED ACCESS FLOOR INCLUDING RAMPS/STEPS,

HANDRAILS, AND PEDESTALS - TO BE REMOVED.

IN ADDITION, REMOVE ALL ADHESIVES AND/OR PEDESTAL

ATTACHMENTS TO THE EXISTING SLAB.

PREP/REPAIR EXISTING SLAB FOR NEW FINISHES INDICATED

P

2 3 4 5 6

G

H

J

K

KL

L

M

N

Q

25' - 0" 20' - 0" 20' - 0" 20' - 0" 20' - 0"

1'

W5

W220

W253

W1

W280

W220A W220D

W212 W210

W209

W299

W208

W298

W203A

W203E

W203

W279

W226A

W226

W227 W225B W219

W225A

W2

W202 W201

W201BW202BW202A

W220E

W220B

W220F

W214A

W214

W203D

W204

W203C W203B

W203F

W220C

6'

DN

DNDN

D01

K02D02

D03

D03

D03

D03

D03

D03

D03

D03 D03

GENERAL NOTES: DEMOLITION PLAN

1. EXISTING CONDITIONS SHOWN ON DRAWINGS ARE FOR INFORMATIONAL PURPOSES ONLY AND DO NOT SHOW ALL CONDITIONS THAT MAY AFFECT THE WORK OF THIS CONTRACT. REFER TO ALL ARCHITECTURAL, PLUMBING, MECHANICAL AND ELECTRICAL DRAWINGS FOR ADDITIONAL DEMOLITION INFORMATION AND COORDINATION. ANY DISCREPANCIES NOTED WHICH WILL IMPACT THE SCHEDULE FOR CONSTRUCTION OR HAVE AN EFFECT ON THE CONTINUED OPERATION OF BUSINESS AT THIS FACILITY MUST BE BROUGHT TO THE IMMEDIATE ATTENTION OF THE CONTRACTING OFFICER FOR RESOLUTION.

2. FIELD VERIFY EXISTING CONDITIONS BEFORE COMMENCING ANY WORK. CONTRACTING OFFICER MUST BE NOTIFIED IMMEDIATELY OF ANY DISCREPANCIES DETRIMENTAL TO THE PROPER EXECUTION OF NEW CONSTRUCTION.

3. ALL DEMOLITION WORK MUST COMPLY WITH APPLICABLE BUILDING CODE AND ALL APPLICABLE LOCAL, STATE, AND FEDERAL LAWS, ORDINANCES, AND REGULATIONS. ANY WORK DONE OUTSIDE OF CODE WITHOUT GOVERNMENT

KNOWLEDGE WILL BE REPLACED AT CONTRACTOR EXPENSE EVEN IF SHOWN ON DRAWINGS.

4. PROTECT ALL ADJACENT AREAS FROM THE DEMOLITION. REPAIR OR REPLACE, AT NO COST TO THE GOVERNMENT, ALL AREAS OR ITEMS DAMAGED DURING THE DEMOLITION.

5. WHEN UNANTICIPATED MECHANICAL, ELECTRICAL OR…