AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT 1. CONTRACT ID CODE
2. AMENDMENT/MODIFICAITON NO. 3. EFFECTIVE DATE 4. REQUISITION/PURCHASE REQ. NO. 5. PROJECT NO. (If applicble)
7. ADMINISTERED BY (If other than Item 6) CODE
STANDARD FORM 30 (REV. 10-83)
Prescribed by GSA FAR (48 CFR) 53.243
FACILITY CODE
9A. AMENDMENT OF SOLICIATION NO.
9B. DATED (SEE ITEM 11)
10A. MODIFICATION OF CONTRACT/ORDER NO.
10B. DATED (SEE ITEM 13)
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers is extended, is not extended.
Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods:
(a)By completing items 8 and 15, and returning copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted;
or (c) By separate letter or telegram which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment your desire to change an offer already submitted, such change may be made by telegram or letter, provided each telegram or letter makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.
12. ACCOUNTING AND APPROPIRATION DATA (If required)
13. THIS ITEM ONLY APPLIES TO MODIFICATION OF CONTRACTS/ORDERS.
IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.
CHECK ONE A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT ORDER
NO. IN ITEM 10A.
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation date, etc. ) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).
C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER (Specify type of modification and authority)
E. IMPORTANT: Contractor is not, is required to sign this document and return copies to the issuing office.
Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.
15C. DATE SIGNED
15A. NAME AND TITLE OF SIGNER (Type or print)
16C. DATE SIGNED
16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)
14. DESCRIPTION OF AMENDMENT/MODIFICATION ( Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
PAGE OF PAGES
6. ISSUED BY CODE
8. NAME AND ADDRESS OF CONTRACTOR (No., street, county, State and ZIP Code) (X)
CODE
15B. CONTRACTOR/OFFEROR
(Signature of person authorized to sign)
16B. UNITED STATES OF AMERICA
(Signature of Contracting Officer)
NSN 7540-01-152-8070
Previous edition unusable
1 2
0002 29 MAY 2008
W912PL
CONTRACTING DIVISION
P.O. BOX 532711
LOS ANGELES, CA 90053-2325
SEE ITEM #6
W912PL-08-B-0001
29 APRIL 2008
TRES RIOS ENVIRONMENTAL RESTORATION PROJECT – PHASE II FLOW REGULATING WETLANDS, MARICOPA
COUNTY, AZ.
SEE PAGE 2 FOR ENCLOSURES
W912PL-08-B-0001
AMEND 0002
Enclosure Listing:
1) Revised Specs:
a. Project Table of Contents
b. Section 02300 Section 16131
c. Instrument Index – Section 13053
d. I/O List - Section 13226
2) Delete and Replace the following 10 Drawings:
Sheet 2 G-2
3 G-2A 7 G-6
110 CU301
286 E-501
302 EI101
320 EI119
321 EI120
364 EI163
373 EI172
All other terms and conditions remain unchanged.
Tres Rios Environ. Restor. Proj.-Regu1ating & Overbank Wetland 030400
W912PL-04-C-0008
DIVISION
01110 01143
01270A 01310 01312A 01320A 01320N 01330 01355A 01356A 01420 014 51A 01500A 01525 01572 01651 01661 01670 01770N 01780A 01781
DIVISION
02080 02100 02220
~ 02230 802300
02318 02373 02510 02580 02630
.&. 82661 02703 02722 02724 02725 02785 02810 02821 02914 02921
.&02930 02931 02935
DIVISION
03100A 03150A 03200A 03201
Ready To Advertise (RTA) /Submitta1
PROJECT TABLE OF CONTENTS
GENERAL REQUIREMENTS
SUMMARY OF WORK
COORDINATION WITH 91ST AVENUE WWTP OPERATION AND
MAINTENANCE DEPARTMENT
MEASUREMENT AND PAYMENT
ADMINISTRATIVE REQUIREMENTS
QUALITY CONTROL SYSTEM (QCS)
PROJECT SCHEDULE
CONSTRUCTION PROGRESS DOCUMENTATION
SUBMITTAL PROCEDURES
ENVIRONMENTAL PROTECTION
STORM WATER POLLUTION PREVENTION MEASURES
SOURCES FOR REFERENCE PUBLICATIONS
CONTRACTOR QUALITY CONTROL
TEMPORARY CONSTRUCTION FACILITIES
SAFETY AND OCCUPATIONAL HEALTH REQUIREMENTS
CONSTRUCTION AND DEMOLITION WASTE MANAGEMENT
TRANSPORTATION AND HANDLING OF MATERIALS AND EQUIPMENT
STORAGE OF MATERIALS AND EQUIPMENT
RECYCLED / RECOVERED MATERIALS
CLOSEOUT PROCEDURES
CLOSEOUT SUBMITTALS
OPERATION AND MAINTENANCE DATA
SITE CONSTRUCTION
PRECAST STRUCTURES
DIVERSION AND CONTROL OF WATER
DEMOLITION
CLEARING AND GRUBBING
EARTHWORK
CRUSHED STONE AND
GEOTEXTILE
ASPHALTIC CONCRETE
PAVEMENT MARKING
CULVERT PIPE
!If)r'E: LIlfER
GRAVEL
PAVING
HOT-MIX ASPHALT (HMA)
AGGREGATE BASE COURSE
INORGANIC MULCH
STABILIZED DECOMPOSED
BITUMINOUS FOG COATS
UNDERGROUND IRRIGATION
FENCING
NATIVE PLANT SALVAGE
SEEDING
TERRESTRIAL PLANTS
AQUATIC PLANTS
LANDSCAPE MAINTNEANCE
CONCRETE
FOR ROADS
GRANITE
SYSTEMS
STRUCTURAL CONCRETE FORMWORK
EXPANSION JOINTS, CONTRACTION JOINTS, AND WATERSTOPS
CONCRETE REINFORCEMENT
STEEL BARS AND WELDED WIRE FABRIC FOR CONCRETE 1
~ Addendum NO.1 05-22-08
PROJECT TABLE OF CONTENTS Page 1 & Addendum NO.2 05-29-08
Tres Rios Environ. Restor. Proj.-Regulating & Overbank Wetland 030400 W9l2PL-04-C-OOOB Ready To Advertise (RTA) /Submittal
REINFORCEMENT FOR CIVIL WORKS
03300A 03371 03600
CAST-IN-PLACE STRUCTURAL CONCRETE
SHOTCRETE
GROUT
DIVISION 04 - MASONRY
04200 04270
MASONRY
GLASS MASONRY UNITS
DIVISION 05 - METALS
05051 05055A
05090A 05093 05502
05522 05532 05561 05602
ANCHOR BOLTS, TOGGLE BOLTS AND CONCRETE INSERTS
METALWORK FABRICATION, MACHINE WORK, MISCELLANEOUS
PROVISIONS
WELDING, STRUCTURAL
WELDING PRESSURE PIPING
METALS: MISCELLANEOUS, STANDARD ARTICLES, SHOP
FABRICATED ITEMS FOR CIVIL WORKS STRUCTURES
ALUMINUM HANDRAILS AND RAILINGS
ALUMINUM GRATING
CASTINGS
STEEL BULKHEAD STOP PLATES
DIVISION 06 - WOOD AND PLASTICS
06100 ROUGH CARPENTRY
DIVISION 07 - THERMAL AND MOISTURE PROTECTION
07121 BUILT-UP BITUMINOUS WATERPROOFING
07600 FLASHING AND SHEET METAL
07611N STEEL STANDING SEAM ROOFING
07920 JOINT SEALANTS
DIVISION 08 - DOORS AND WINDOWS
08110 STEEL DOORS AND FRAMES
08710S DOOR HARDWARE
DIVISION 09 - FINISHES
09510S ACOOSTICAL CEILINGS
09900 PAINTING
DIVISION 10 - SPECIALTIES
10201 METAL WALL AND DOOR LOUVERS
10400 IDENTIFICATION DEVICES
DIVISION 11 - EQUIPMENT
11200 480 VOLT MOTOR-OPERATED VALVE/GATE ACTUATORS
11215 SELF-PRIMING CENTRIFUGAL PUMPS
11286 ALUMINUM WEIR GATES AND APPURTENANCES
11289 SLUICE GATES AND APPURTENANCES
DIVISION 13 - SPECIAL CONSTRUCTION
PROJECT TABLE OF CONTENTS Page 2
Tres Rios Environ. Restor. Proj.-Regulating & Overbank Wetland 030400 W9l2PL-04-C-0008
13001 13005
13007
13008 13051 13052
&& 13053 13100A 13101
&13226 13260 13265 13266
AI 13850A
~ 13930A
DIVISION
15050N 15051 15108 15110 15119 15182 15200 15400 15700A 15950N 15995A
DIVISION
16050N 16065S 16121 16122
&16131 16132 16134 16135 16136 16137 16138 16141 16142 16143 16271 16282 16375A 16402 16441 16442 16501
Ready To Advertise
REFERENCE FORMS
PROCESS CONTROL
INSTRUMENTATION
PROCESS CONTROL
TESTING
PROCESS CONTROL
COMPUTER CONTROL
PROCESS CONTROL
INSTRUMENTS
(RTA) /Submittal
SYSTEM GENERAL REQUIREMENTS FOR PROCESS
SYSTEM, START-UP, COMMISSIONING AND FIELD
SYSTEM TRAINING
SYSTEM PROCESS CONTROL DESCRIPTION
SYSTEM PRIMARY SENSORS AND FIELD
PROCESS CONTROL SYSTEM INSTRUMENT INDEX
LIGHTNING PROTECTION SYSTEM
PROCESS CONTROL SYSTEM FIBER OPTIC CABLING - OUTDOOR
PROCESS CONTROL SYSTEM I/O LIST
CONTROL PANELS
PROCESS CONTROL SYSTEM PANELS AND ENCLOSURES
PROCESS CONTROL SYSTEM PANEL INSTRMENTS AND DEVICES
FIRE DETECTION AND ALARM SYSTEM, DIRECT CURRENT LOOP
WET PIPE SPRINKLER SYSTEM, FIRE PROTECTION
MECHANICAL
BASIC MECHANICAL MATERIALS AND METHODS
BURIED PIPING INSTALLATION
FIBERGLASS-REINFORCED POLYMER MORTAR PIPE
VALVE SCHEDULE
SPECIALTY VALVES AND APPURTENANCES
REFRIGERANT PIPING
PIPELINES, LIQUID PROCESS PIPING
PLUMBING, GENERAL PURPOSE
UNITARY HEATING AND COOLING EQUIPMENT
HVAC TESTING/ADJUSTING/BALANCING
COMMISSIONING OF HVAC SYSTEMS
ELECTRICAL
BASIC ELECTRICAL MATERIALS AND METHODS
SECONDARY GROUNDING
INTRUMENTATION CABLE
600 VOLT CABLE
RIGID CONDUIT
FLEXIBLE CONDUITS
EXPANSION/DEFLECTION FITTINGS
PULL BOXES
OUTLET BOXES
UNDERGROUND DUCT BANKS
MANHOLES AND HANDHOLES
RECEPTACLES
SNAP SWITCHES
DISCONNECT SWITCHES
DRY TYPE TRANSFORMERS
TRANSIENT VOLTAGE SURGE SUPPRESSION
ELECTRICAL DISTRIBUTION SYSTEM, UNDERGROUND
INTERIOR DISTRIBUTION SYSTEM
LOW-VOLTAGE DISTRIBUTION SWITCHBOARDS
LIGHTING, INSTRUMENTATION AND DISTRIBUTION PANELBOARDS
LIGHTING FIXTURES AND CONTROLS
-- End of Project Table of Contents - & Addendum No.1 05-22-08 & Addendum No. 2 05-29-08
PROJECT TABLE OF CONTENTS Page 3
Amendment No. 2 Modification to the specifications
Section 02300. Paragraph 3.8, should be revised as follows:
3.8 DISPOSITION AND DISPOSAL OF EXCAVATED MATERIALS
Excavated materials suitable for fills should be used directly in the work or placed in either temporary or permanent stockpiles. All excess excavated material not used for any part of the construction that is suitable for embankment fill is the property of the Owner and shall be placed in the permanent OBW stockpile as shown in the Drawings. Upon completion of the project, all other satisfactory excess excavated material not used for any part of the construction shall become the property of the Contractor, and shall either be placed in the designated permanent Northeast Stockpile site as shown on the drawings, or be disposed off project site at the Contractor's expense.
Section 16131. Paragraph 16131.1.3.A.3.c should read, “Schedule 40 PVC conduit for concrete encased duct bank runs and direct-bury conduit”.
Section 13053. Replace Instrument Index with attached Instrument Index.
Section 13226. Replace I/O List with attached I/O List.
Amend 0002 For Spec Sections 02300, 13053, 13226, 16131
Tres Rios Environ. Restor. Proj.-Regulating Overbank Wetland 030400
W912-PL-04-C-0008 ADDENDUM #2
INSTRUMENT INDEX
LOOP NO. EQUIP NO. DESCRIPTION LOCATION RANGE SPEC. SEC COMMENTS
LIT-100 Milltronics HydroRanger DWA-1 0-20 Ft. 13052
FIT-101 ADFM Flow Meter Shallow Water DWA-1 1.5-39 in. 13052
LIT-200 Milltronics HydroRanger DWA-2 0-20 Ft. 13052
FIT-201 ADFM Flow Meter Shallow Water DWA-2 1.5-39 in. 13052
LIT-300 Milltronics HydroRanger DWB-2 0-20 Ft. 13052
FIT-301 ADFM Flow Meter Shallow Water DWB-2 1.5-39 in. 13052
LIT-400 Milltronics HydroRanger DWB-3 0-20 Ft. 13052
FIT-401 ADFM Flow Meter Shallow Water DWB-3 1.5-39 in. 13052
FIT-505 ADFM Flow Meter Shallow Water FRW-1 1.5-39 in. 13052
FIT-506 ADFM Flow Meter Shallow Water FRW-1 1.5-39 in. 13052
FIT-507 ADFM Flow Meter Shallow Water FRW-1 1.5-39 in. 13052
LIT-504 Milltronics HydroRanger FRW-1 0-20 Ft. 13052
FIT-513 ADFM Flow Meter Shallow Water FRW-2 1.5-39 in. 13052
FIT-514 ADFM Flow Meter Shallow Water FRW-2 1.5-39 in. 13052
LIT-512 Milltronics HydroRanger FRW-2 0-20 Ft. 13052
FIT-523 ADFM Flow Meter Shallow Water FRW-3 1.5-39 in. 13052
FIT-524 ADFM Flow Meter Shallow Water FRW-3 1.5-39 in. 13052
LIT-522 Milltronics HydroRanger FRW-3 0-20 Ft. 13052
LIT-535 Milltronics HydroRanger SR DISCHARGE 0-20 Ft. 13052
LIT-545 Milltronics HydroRanger OBW 0-20 Ft. 13052
FIT-807 Magnetic flow Meter SB FEED 13052
FIT-808 Magnetic flow Meter SB FEED 13052
PSL-807 Pressure Switch SB FEED 13052
PSL-808 Pressure Switch SB FEED 13052
FIT-822 Magnetic flow Meter SB FEED 13052
PI-832 Pressure Gauge FRW INLET 13052
LSHH-832 Flygt ENM-10 FRW INLET 13052
LSL-832 Flygt ENM-10 FRW INLET 13052
LIT-830 Milltronics HydroRanger FRW INLET 0-20 Ft. 13052
LIT-831 Milltronics HydroRanger FRW INLET 0-20 Ft. 13052
FSH-835 Flow Switch EYEWASH 13052
AIT-840 pH analyzer FRW INLET 13052
AIT-841 Chlorine Analyzer FRW INLET 13052
AIT-842 pH analyzer FRW INLET 13052
13053-3
LOOP NO. EQUIP NO. DESCRIPTION LOCATION RANGE SPEC. SEC COMMENTS
AIT-843 Chlorine Analyzer FRW INLET 13052
AIT-844 pH analyzer FRW INLET 13052
AIT-845 Chlorine Analyzer FRW INLET 13052
FSL-841 Flow Switch CL2 Analyzer 13052
FSL-843 Flow Switch CL2 Analyzer 13052
FSL-845 Flow Switch CL2 Analyzer 13052
AS-FRW-1 Portable Sampler FRW INLET 13052
AS-FRW-2 Portable Sampler FRW INLET 13052
AS-FRW-3 Portable Sampler FRW INLET 13052
AS Auto Sampler FRW INLET 13052
AS-STY Auto Sampler FRW INLET 13052
AS-EFF Auto Sampler FRW-1 13052
PI-804 Carry Water Pressure Gauge SB CW 13052
PI-840 CO2 Tank Pressure Gauge CL2 Analyzer 0-100 PSI 13052
PI-841 CO2 Manifold Pressure Gauge CL2 Analyzer 0-100 PSI 13052
LSH-850 Sodium Bisulfite Leak Detection SB Line 13052
LSH-851 Sodium Bisulfite Leak Detection SB Line 13052
LSH-852 Sodium Bisulfite Leak Detection SB Line 13052
LSH-853 Sodium Bisulfite Leak Detection SB Line 13052
LSH-854 Sodium Bisulfite Leak Detection SB Line 13052
LSH-855 Sodium Bisulfite Leak Detection SB Line 13052
LSH-856 Sodium Bisulfite Leak Detection SB Line 13052
LSH-857 Sodium Bisulfite Leak Detection SB Line 13052
LSH-858 Sodium Bisulfite Leak Detection SB Line 13052
LSH-859 Sodium Bisulfite Leak Detection SB Line 13052
LSH-860 Sodium Bisulfite Leak Detection SB Line 13052
LSH-861 Sodium Bisulfite Leak Detection SB Line 13052
LSH-862 Sodium Bisulfite Leak Detection SB Line 13052 LSH-863 Sodium Bisulfite Leak Detection SB Line 13052
+ + END OF SECTION + +
13053-3
(--1--)
C C
S
C A
C O
N T
I& C
IN
S
P
P&ID
Sheet No. Service Description Tag Extension S er ia liz ed
K ey
I/O T yp e
D ev ic e
Lo op
FC
U
N o.
FC
U
D ig i-L in k
R
IO
P an el
N am e
A dd re ss
I/O o r R eg is te r
A dd re ss
E xi st in g P oi nt
E ng U ni ts
Lo w (0
E ng
U ni ts
H ig h (1
E ng
U ni ts
A la rm
S et po in t
EI102 DWA-1 Water Level DWA-1 Level 0036025 AI LIT-100 LCP-RIO-1-TRW
EI102 Level Transmitter Fault LIT-100 Equip Alm DI YA-100 LCP-RIO-1-TRW
EI102 DWA-1 Water Flow DWA-1 Flow 0036026 AI FIT-101 LCP-RIO-1-TRW
EI102 DWA-1 Sluice Gate 1 DWA-1 Sluice Gate 1 GatePos 0036028 AI ZT-103 LCP-RIO-1-TRW
EI102 DWA-1 Sluice Gate 1 DWA-1 Sluice Gate 1 GateClsed DI ZIC-103 LCP-RIO-1-TRW
EI102 DWA-1 Sluice Gate 1 DWA-1 Sluice Gate 1 GateOpned DI ZIO-103 LCP-RIO-1-TRW
EI102 DWA-1 Sluice Gate 1 DWA-1 Sluice Gate 1 GateOpn DO HMS-103A LCP-RIO-1-TRW
EI102 DWA-1 Sluice Gate 1 DWA-1 Sluice Gate 1 GateCls DO HMS-103B LCP-RIO-1-TRW
EI102 DWA-1 Sluice Gate 1 DWA-1 Sluice Gate 1 CompMode DI HS-103 LCP-RIO-1-TRW
EI102 DWA-1 Sluice Gate 1 DWA-1 Sluice Gate 1 DiscClosed 0036029 DI YS-103 LCP-RIO-1-TRW
EI102 DWA-1 Sluice Gate 2 DWA-1 Sluice Gate 2 GatePos 0036031 AI ZT-104 LCP-RIO-1-TRW
EI102 DWA-1 Sluice Gate 2 DWA-1 Sluice Gate 2 GateClsed DI ZIC-104 LCP-RIO-1-TRW
EI102 DWA-1 Sluice Gate 2 DWA-1 Sluice Gate 2 GateOpned DI ZIO-104 LCP-RIO-1-TRW
EI102 DWA-1 Sluice Gate 2 DWA-1 Sluice Gate 2 GateOpn DO HMS-104A LCP-RIO-1-TRW
EI102 DWA-1 Sluice Gate 2 DWA-1 Sluice Gate 2 GateCls DO HMS-104B LCP-RIO-1-TRW
EI102 DWA-1 Sluice Gate 2 DWA-1 Sluice Gate 2 CompMode DI HS-104 LCP-RIO-1-TRW
EI102 DWA-1 Sluice Gate 2 DWA-1 Sluice Gate 2 DiscClosed 0036030 DI YS-104 LCP-RIO-1-TRW
EI103 DWA-2 Water Level DWA-2 Level 0036050 AI LIT-200 LCP-RIO-2-TRW
EI103 Level Transmitter Fault LIT-200 Equip Alm DI YA-200 LCP-RIO-2-TRW
EI103 DWA-2 Water Flow DWA-2 Flow 0036051 AI FIT-201 LCP-RIO-2-TRW
EI103 DWA-2 Sluice Gate 3 DWA-2 Sluice Gate 1 GatePos 0036053 AI ZT-203 LCP-RIO-2-TRW
EI103 DWA-2 Sluice Gate 3 DWA-2 Sluice Gate 1 GateClsed DI ZIC-203 LCP-RIO-2-TRW
EI103 DWA-2 Sluice Gate 3 DWA-2 Sluice Gate 1 GateOpned DI ZIO-203 LCP-RIO-2-TRW
EI103 DWA-2 Sluice Gate 3 DWA-2 Sluice Gate 1 GateOpn DO HMS-203A LCP-RIO-2-TRW
EI103 DWA-2 Sluice Gate 3 DWA-2 Sluice Gate 1 GateCls DO HMS-203B LCP-RIO-2-TRW
EI103 DWA-2 Sluice Gate 3 DWA-2 Sluice Gate 1 CompMode DI HS-203 LCP-RIO-2-TRW
EI103 DWA-2 Sluice Gate 3 DWA-2 Sluice Gate 1 DiscClosed 0036054 DI YS-203 LCP-RIO-2-TRW
EI103 DWA-2 Sluice Gate 4 DWA-2 Sluice Gate 2 GatePos 0036056 AI ZT-204 LCP-RIO-2-TRW
EI103 DWA-2 Sluice Gate 4 DWA-2 Sluice Gate 2 GateClsed DI ZIC-204 LCP-RIO-2-TRW
EI103 DWA-2 Sluice Gate 4 DWA-2 Sluice Gate 2 GateOpned DI ZIO-204 LCP-RIO-2-TRW
EI103 DWA-2 Sluice Gate 4 DWA-2 Sluice Gate 2 GateOpn DO HMS-204A LCP-RIO-2-TRW
EI103 DWA-2 Sluice Gate 4 DWA-2 Sluice Gate 2 GateCls DO HMS-204B LCP-RIO-2-TRW
SECTION 13226-4
EI103 DWA-2 Sluice Gate 4 DWA-2 Sluice Gate 2 CompMode DI HS-204 LCP-RIO-2-TRW
EI103 DWA-2 Sluice Gate 4 DWA-2 Sluice Gate 2 DiscClosed 0036055 DI YS-204 LCP-RIO-2-TRW
EI104 DWB-2 Water Level DWB-2 Level 0036075 AI LIT-300 LCP-RIO-3-TRW
EI104 Level Transmitter Fault LIT-300 Equip Alm DI YA-300 LCP-RIO-3-TRW
EI104 DWB-2 Water Flow DWB-2 Flow 0036076 AI FIT-301 LCP-RIO-3-TRW
EI104 DWB-2 Sluice Gate 5 DWB-2 Sluice Gate 1 GatePos 0036078 AI ZT-303 LCP-RIO-3-TRW
EI104 DWB-2 Sluice Gate 5 DWB-2 Sluice Gate 1 GateClsed DI ZIC-303 LCP-RIO-3-TRW
EI104 DWB-2 Sluice Gate 5 DWB-2 Sluice Gate 1 GateOpned DI ZIO-303 LCP-RIO-3-TRW
EI104 DWB-2 Sluice Gate 5 DWB-2 Sluice Gate 1 GateOpn DO HMS-303A LCP-RIO-3-TRW
EI104 DWB-2 Sluice Gate 5 DWB-2 Sluice Gate 1 GateCls DO HMS-303B LCP-RIO-3-TRW
EI104 DWB-2 Sluice Gate 5 DWB-2 Sluice Gate 1 CompMode DI HS-303 LCP-RIO-3-TRW
EI104 DWB-2 Sluice Gate 5 DWB-2 Sluice Gate 1 DiscClosed 0036079 DI YS-303 LCP-RIO-3-TRW
EI104 DWB-3 Sluice Gate 6 DWB-2 Sluice Gate 2 GatePos 0036081 AI ZT-304 LCP-RIO-3-TRW
EI104 DWB-3 Sluice Gate 6 DWB-2 Sluice Gate 2 GateClsed DI ZIC-304 LCP-RIO-3-TRW
EI104 DWB-3 Sluice Gate 6 DWB-2 Sluice Gate 2 GateOpned DI ZIO-304 LCP-RIO-3-TRW
EI104 DWB-3 Sluice Gate 6 DWB-2 Sluice Gate 2 GateOpn DO HMS-304A LCP-RIO-3-TRW
EI104 DWB-3 Sluice Gate 6 DWB-2 Sluice Gate 2 GateCls DO HMS-304B LCP-RIO-3-TRW
EI104 DWB-3 Sluice Gate 6 DWB-2 Sluice Gate 2 CompMode DI HS-304 LCP-RIO-3-TRW
EI104 DWB-3 Sluice Gate 6 DWB-2 Sluice Gate 2 DiscClosed 0036080 DI YS-304 LCP-RIO-3-TRW
EI105 DWB-3 Water Level DWB-3 Level 0036100 AI LIT-400 LCP-RIO-4-TRW
EI105 Level Transmitter Fault LIT-400 Equip Alm DI YA-400 LCP-RIO-4-TRW
EI105 DWB-3 Water Flow DWB-3 Flow 0036101 AI FIT-401 LCP-RIO-4-TRW
EI105 DWB-3 Sluice Gate 7 DWB-3 Sluice Gate 7 GatePos 0036103 AI ZT-403 LCP-RIO-4-TRW
EI105 DWB-3 Sluice Gate 7 DWB-3 Sluice Gate 7 GateClsed DI ZIC-403 LCP-RIO-4-TRW
EI105 DWB-3 Sluice Gate 7 DWB-3 Sluice Gate 7 GateOpned DI ZIO-403 LCP-RIO-4-TRW
EI105 DWB-3 Sluice Gate 7 DWB-3 Sluice Gate 7 GateOpn DO HMS-403A LCP-RIO-4-TRW
EI105 DWB-3 Sluice Gate 7 DWB-3 Sluice Gate 7 GateCls DO HMS-403B LCP-RIO-4-TRW
EI105 DWB-3 Sluice Gate 7 DWB-3 Sluice Gate 7 CompMode DI HS-403 LCP-RIO-4-TRW
EI105 DWB-3 Sluice Gate 7 DWB-3 Sluice Gate 7 DiscClosed 0036104 DI YS-403 LCP-RIO-4-TRW
EI105 DWB-3 Sluice Gate 8 DWB-3 Sluice Gate 8 GatePos 0036106 AI ZT-404 LCP-RIO-4-TRW
EI105 DWB-3 Sluice Gate 8 DWB-3 Sluice Gate 8 GateClsed DI ZIC-404 LCP-RIO-4-TRW
EI105 DWB-3 Sluice Gate 8 DWB-3 Sluice Gate 8 GateOpned DI ZIO-404 LCP-RIO-4-TRW
EI105 DWB-3 Sluice Gate 8 DWB-3 Sluice Gate 8 GateOpn DO HMS-404A LCP-RIO-4-TRW
EI105 DWB-3 Sluice Gate 8 DWB-3 Sluice Gate 8 GateCls DO HMS-404B LCP-RIO-4-TRW
EI105 DWB-3 Sluice Gate 8 DWB-3 Sluice Gate 8 CompMode DI HS-404 LCP-RIO-4-TRW
EI105 DWB-3 Sluice Gate 8 DWB-3 Sluice Gate 8 DiscClosed 0036105 DI YS-404 LCP-RIO-4-TRW
EI106 FRW-1 Water Level FRW-1 Level 0036125 AI LIT-504 LCP-RIO-7-TRW
EI106 Level Transmitter Fault LIT-504 Equip Alm DI YA-504 LCP-RIO-7-TRW
SECTION 13226-5
EI106 FRW-1 Weir Gate 1 FRW-1 Weir Gate 1 GatePos 0036126 AI ZT-501 LCP-RIO-7-TRW
EI106 FRW-1 Weir Gate 1 FRW-1 Weir Gate 1 GateClsed DI ZIC-501 LCP-RIO-7-TRW
EI106 FRW-1 Weir Gate 1 FRW-1 Weir Gate 1 GateOpned DI ZIO-501 LCP-RIO-7-TRW
EI106 FRW-1 Weir Gate 1 FRW-1 Weir Gate 1 GateOpn DO HMS-501A LCP-RIO-7-TRW
EI106 FRW-1 Weir Gate 1 FRW-1 Weir Gate 1 GateCls DO HMS-501B LCP-RIO-7-TRW
EI106 FRW-1 Weir Gate 1 FRW-1 Weir Gate 1 CompMode DI HS-501 LCP-RIO-7-TRW
EI106 FRW-1 Weir Gate 1 FRW-1 Weir Gate 1 DiscClosed 0036127 DI YS-501 LCP-RIO-7-TRW
EI106 FRW-1 Effluent Channel 9 FRW-1 Effluent Channel 9 Flow 0036201 AI FIT-505 LCP-RIO-7-TRW
EI106 FRW-1 Weir Gate 2 FRW-1 Weir Gate 2 GatePos 0036128 AI ZT-502 LCP-RIO-7-TRW
EI106 FRW-1 Weir Gate 2 FRW-1 Weir Gate 2 GateClsed DI ZIC-502 LCP-RIO-7-TRW
EI106 FRW-1 Weir Gate 2 FRW-1 Weir Gate 2 GateOpned DI ZIO-502 LCP-RIO-7-TRW
EI106 FRW-1 Weir Gate 2 FRW-1 Weir Gate 2 GateOpn DO HMS-502A LCP-RIO-7-TRW
EI106 FRW-1 Weir Gate 2 FRW-1 Weir Gate 2 GateCls DO HMS-502B LCP-RIO-7-TRW
EI106 FRW-1 Weir Gate 2 FRW-1 Weir Gate 2 CompMode DI HS-502 LCP-RIO-7-TRW
EI106 FRW-1 Weir Gate 2 FRW-1 Weir Gate 2 DiscClosed 0036129 DI YS-502 LCP-RIO-7-TRW
EI106 FRW-1 Effluent Channel 10 FRW-1 Effluent Channel 10 Flow 0036202 AI FIT-506 LCP-RIO-7-TRW
EI106 FRW-1 Weir Gate 3 FRW-1 Weir Gate 3 GatePos 0036130 AI ZT-503 LCP-RIO-7-TRW
EI106 FRW-1 Weir Gate 3 FRW-1 Weir Gate 3 GateClsed DI ZIC-503 LCP-RIO-7-TRW
EI106 FRW-1 Weir Gate 3 FRW-1 Weir Gate 3 GateOpned DI ZIO-503 LCP-RIO-7-TRW
EI106 FRW-1 Weir Gate 3 FRW-1 Weir Gate 3 GateOpn DO HMS-503A LCP-RIO-7-TRW
EI106 FRW-1 Weir Gate 3 FRW-1 Weir Gate 3 GateCls DO HMS-503B LCP-RIO-7-TRW
EI106 FRW-1 Weir Gate 3 FRW-1 Weir Gate 3 CompMode DI HS-503 LCP-RIO-7-TRW
EI106 FRW-1 Weir Gate 3 FRW-1 Weir Gate 3 DiscClosed 0036131 DI YS-503 LCP-RIO-7-TRW
EI106 FRW-1 Effluent Channel 11 FRW-1 Effluent Channel 11 Flow 0036203 AI FIT-507 LCP-RIO-7-TRW
EI106 FRW-1 Effluent Channel 9,10,11 FRW-1 Effluent Channel 9,10,11 Sample Command 0036132 DO LCP-RIO-7-TRW
EI106 FRW-1 Effluent Channel 9,10,11 FRW-1 Effluent Channel 9,10,11 Sample Trouble 0036132 DI LCP-RIO-7-TRW
EI107 FRW-2 Water Level FRW-1 Level 0036150 AI LIT-512 LCP-RIO-6-TRW
EI107 Level Transmitter Fault LIT-512 Equip Alm DI YA-512 LCP-RIO-6-TRW
EI107 FRW-2 Weir Gate 4 FRW-2 Weir Gate 4 GatePos 0036151 AI ZT-510 LCP-RIO-6-TRW
EI107 FRW-2 Weir Gate 4 FRW-2 Weir Gate 4 GateClsed DI ZIC-510 LCP-RIO-6-TRW
EI107 FRW-2 Weir Gate 4 FRW-2 Weir Gate 4 GateOpned DI ZIO-510 LCP-RIO-6-TRW
EI107 FRW-2 Weir Gate 4 FRW-2 Weir Gate 4 GateOpn DO HMS-510A LCP-RIO-6-TRW
EI107 FRW-2 Weir Gate 4 FRW-2 Weir Gate 4 GateCls DO HMS-510B LCP-RIO-6-TRW
EI107 FRW-2 Weir Gate 4 FRW-2 Weir Gate 4 CompMode DI HS-510 LCP-RIO-6-TRW
EI107 FRW-2 Weir Gate 4 FRW-2 Weir Gate 4 DiscClosed 0036152 DI YS-510 LCP-RIO-6-TRW
EI107 FRW-2 Effluent Channel FRW-2 Effluent Channel 1Flow AI FIT-513 LCP-RIO-6-TRW
EI107 FRW-2 Weir Gate 5 FRW-2 Weir Gate 5 GatePos 0036153 AI ZT-511 LCP-RIO-6-TRW
EI107 FRW-2 Weir Gate 5 FRW-2 Weir Gate 5 GateClsed DI ZIC-511 LCP-RIO-6-TRW
EI107 FRW-2 Weir Gate 5 FRW-2 Weir Gate 5 GateOpned DI ZIO-511 LCP-RIO-6-TRW
SECTION 13226-6
EI107 FRW-2 Weir Gate 5 FRW-2 Weir Gate 5 GateOpn DO HMS-511A LCP-RIO-6-TRW
EI107 FRW-2 Weir Gate 5 FRW-2 Weir Gate 5 GateCls DO HMS-511B LCP-RIO-6-TRW
EI107 FRW-2 Weir Gate 5 FRW-2 Weir Gate 5 CompMode DI HS-511 LCP-RIO-6-TRW
EI107 FRW-2 Weir Gate 5 FRW-2 Weir Gate 5 DiscClosed 0036154 DI YS-511 LCP-RIO-6-TRW
EI107 FRW-2 Effluent Channel FRW-2 Effluent Channel 1Flow AI FIT-514 LCP-RIO-6-TRW
EI108 FRW-3 Weir Gate 6 FRW-3 Weir Gate 6 GatePos 0036180 AI ZT-520 LCP-RIO-5-TRW
EI108 FRW-3 Weir Gate 6 FRW-3 Weir Gate 6 GateClsed DI ZIC-520 LCP-RIO-5-TRW
EI108 FRW-3 Weir Gate 6 FRW-3 Weir Gate 6 GateOpned DI ZIO-520 LCP-RIO-5-TRW
EI108 FRW-3 Weir Gate 6 FRW-3 Weir Gate 6 GateOpn DO HMS-520A LCP-RIO-5-TRW
EI108 FRW-3 Weir Gate 6 FRW-3 Weir Gate 6 GateCls DO HMS-520B LCP-RIO-5-TRW
EI108 FRW-3 Weir Gate 6 FRW-3 Weir Gate 6 CompMode DI HS-520 LCP-RIO-5-TRW
EI108 FRW-3 Weir Gate 6 FRW-3 Weir Gate 6 DiscClosed 0036181 DI YS-520 LCP-RIO-5-TRW
EI108 FRW-3 Effluent Channel FRW-3 Effluent Channel 1Flow AI FIT-523 LCP-RIO-5-TRW
EI108 FRW-3 Weir Gate 7 FRW-3 Weir Gate 7 GatePos 0036182 AI ZT-521 LCP-RIO-5-TRW
EI108 FRW-3 Weir Gate 7 FRW-3 Weir Gate 7 GateClsed DI ZIC-521 LCP-RIO-5-TRW
EI108 FRW-3 Weir Gate 7 FRW-3 Weir Gate 7 GateOpned DI ZIO-521 LCP-RIO-5-TRW
EI108 FRW-3 Weir Gate 7 FRW-3 Weir Gate 7 GateOpn DO HMS-521A LCP-RIO-5-TRW
EI108 FRW-3 Weir Gate 7 FRW-3 Weir Gate 7 GateCls DO HMS-521B LCP-RIO-5-TRW
EI108 FRW-3 Weir Gate 7 FRW-3 Weir Gate 7 CompMode DI HS-521 LCP-RIO-5-TRW
EI108 FRW-3 Weir Gate 7 FRW-3 Weir Gate 7 DiscClosed 0036183 DI YS-521 LCP-RIO-5-TRW
EI108 FRW-3 Effluent Channel FRW-3 Effluent Channel 1Flow AI FIT-524 LCP-RIO-5-TRW
EI108 FRW-3 Water Level FRW-3 Level 0036175 AI LIT-522 LCP-RIO-5-TRW
EI108 Level Transmitter Fault LIT-522 Equip Alm DI YA-522 LCP-RIO-5-TRW
EI109 Effluent Channel Effluent Channel Level AI LIT-535 LCP-RIO-8-TRW
EI109 Level Transmitter Fault LIT-535 Equip Alm AI YA-535 LCP-RIO-8-TRW
EI109 SR Weir Gate 8 SR Weir Gate 8 GatePos AI ZT-531 LCP-RIO-8-TRW
EI109 SR Weir Gate 8 SR Weir Gate 8 GateClsed DI ZIC-531 LCP-RIO-8-TRW
EI109 SR Weir Gate 8 SR Weir Gate 8 GateOpned DI ZIO-531 LCP-RIO-8-TRW
EI109 SR Weir Gate 8 SR Weir Gate 8 GateOpn DO HMS-531A LCP-RIO-8-TRW
EI109 SR Weir Gate 8 SR Weir Gate 8 GateCls DO HMS-531B LCP-RIO-8-TRW
EI109 SR Weir Gate 8 SR Weir Gate 8 CompMode DI HS-531 LCP-RIO-8-TRW
EI109 SR Weir Gate 8 SR Weir Gate 8 DiscClosed DI YS-531 LCP-RIO-8-TRW
EI109 SR Weir Gate 9 SR Weir Gate 9 GatePos AI ZT-532 LCP-RIO-8-TRW
EI109 SR Weir Gate 9 SR Weir Gate 9 GateClsed DI ZIC-532 LCP-RIO-8-TRW
EI109 SR Weir Gate 9 SR Weir Gate 9 GateOpned DI ZIO-532 LCP-RIO-8-TRW
EI109 SR Weir Gate 9 SR Weir Gate 9 GateOpn DO HMS-532A LCP-RIO-8-TRW
EI109 SR Weir Gate 9 SR Weir Gate 9 GateCls DO HMS-532B LCP-RIO-8-TRW
EI109 SR Weir Gate 9 SR Weir Gate 9 CompMode DI HS-532 LCP-RIO-8-TRW
EI109 SR Weir Gate 9 SR Weir Gate 9 DiscClosed DI YS-532 LCP-RIO-8-TRW
SECTION 13226-7
EI109 SR Weir Gate 10 SR Weir Gate 10 GatePos AI ZT-533 LCP-RIO-8-TRW
EI109 SR Weir Gate 10 SR Weir Gate 10 GateClsed DI ZIC-533 LCP-RIO-8-TRW
EI109 SR Weir Gate 10 SR Weir Gate 10 GateOpned DI ZIO-533 LCP-RIO-8-TRW
EI109 SR Weir Gate 10 SR Weir Gate 10 GateOpn DO HMS-533A LCP-RIO-8-TRW
EI109 SR Weir Gate 10 SR Weir Gate 10 GateCls DO HMS-533B LCP-RIO-8-TRW
EI109 SR Weir Gate 10 SR Weir Gate 10 CompMode DI HS-533 LCP-RIO-8-TRW
EI109 SR Weir Gate 10 SR Weir Gate 10 DiscClosed DI YS-533 LCP-RIO-8-TRW
EI109 SR Weir Gate 11 SR Weir Gate 11 GatePos AI ZT-534 LCP-RIO-8-TRW
EI109 SR Weir Gate 11 SR Weir Gate 11 GateClsed DI ZIC-534 LCP-RIO-8-TRW
EI109 SR Weir Gate 11 SR Weir Gate 11 GateOpned DI ZIO-534 LCP-RIO-8-TRW
EI109 SR Weir Gate 11 SR Weir Gate 11 GateOpn DO HMS-534A LCP-RIO-8-TRW
EI109 SR Weir Gate 11 SR Weir Gate 11 GateCls DO HMS-534B LCP-RIO-8-TRW
EI109 SR Weir Gate 11 SR Weir Gate 11 CompMode DI HS-534 LCP-RIO-8-TRW
EI109 SR Weir Gate 11 SR Weir Gate 11 DiscClosed DI YS-534 LCP-RIO-8-TRW
EI110 Effluent Channel Effluent Channel Water Level 0036225 AI LIT-545 LCP-RIO-8-TRW
EI110 Effluent Channel LIT-545 Equip Alm DI YA-545 LCP-RIO-8-TRW
EI112 Sodium Bisufite Pump 1 Sodium Bisufite Pump 1 Flow 0036302 AI FIT-807 LCP-TRW
EI112 Sodium Bisufite Pump 1 Sodium Bisufite Pump 1 Press 0036300 DI PSL-807 LCP-TRW
EI112 Sodium Bisufite Pump 2 Sodium Bisufite Pump 2 Flow 0036303 AI FIT-808 LCP-TRW
EI112 Sodium Bisufite Pump 2 Sodium Bisufite Pump 2 Press 0036301 DI PSL-808 LCP-TRW
EI112 91st. Water Flow 91ST. Water Flow 0036306 AI FIT-822 LCP-TRW
EI112 Sodium Bisufite Pump 1 SB LINE 1 Open 0036304 DO HMS-807A LCP-TRW
EI112 Sodium Bisufite Pump 1 SB LINE 1 Close DO HMS-807B LCP-TRW
EI112 Sodium Bisufite Pump 1 SB LINE 1 Opened DI ZSO-807 LCP-TRW
EI112 Sodium Bisufite Pump 1 SB LINE 1 Closed DI ZSC-807 LCP-TRW
EI112 Sodium Bisufite Pump 2 SB LINE 2 Open 0036305 DO HMS-808A LCP-TRW
EI112 Sodium Bisufite Pump 2 SB LINE 2 Close DO HMS-808B LCP-TRW
EI112 Sodium Bisufite Pump 2 SB LINE 2 Opened DI ZSO-808 LCP-TRW
EI112 Sodium Bisufite Pump 2 SB LINE 2 Closed DI ZSC-808 LCP-TRW
EI113 Sample Pump 1 SP 1 Pump Run Stat DI IS-831 LCP-TRW
EI113 Sample Pump 2 SP 2 Pump Run Stat DI IS-832 LCP-TRW
EI113 Sample Pump 2 SP 2 Pump EquipAuto DI HS-832 LCP-TRW
EI113 Sample Pump 2 SP 2 MtrStart DO HMS-832A LCP-TRW
EI113 Sample Pump 2 SP2 MtrStop DO HMS-832B LCP-TRW
EI113 FRW Water Level HHi1 FRW Water HiHiLevel 0036331 DI LSHH-832 LCP-TRW
EI113 FRW Water Level LSL FRW Water LoLevel 0036335 DI LSL-832 LCP-TRW
EI113 FRW Water Level 1 FRW Level 1 0036332 AI LIT-830 LCP-TRW
EI113 Level Transmitter Fault LIT-830 Equip Alm DI YA-830 LCP-TRW
SECTION 13226-8
EI113 FRW Water Level 2 FRW Level 2 0036333 AI LIT-831 LCP-TRW
EI113 Level Transmitter Fault LIT-831 Equip Alm DI YA-831 LCP-TRW
E114 Emergency Eyewash Flow Swithc Eyewash FlowPresent 0036352 DI FS-835 LCP-TRW
EI114 Analyzer Room Sampler AS Sample Command 0036350 DO LCP-TRW
EI114 Analyzer Room Sampler AS Sample Trouble 0036350 DI LCP-TRW
EI114 Analyzer Room Sampler AS-STY Sample Command 0036351 DO LCP-TRW
EI114 Analyzer Room Sampler AS-STY Sample Trouble 0036351 DI LCP-TRW
EI115 Sample Pump 2 SP 2 Ph 0036375 AI AIT-840 LCP-TRW
EI115 Sample Pump 2 AIT-840 EquipAlrm DI YA-840 LCP-TRW
EI115 Chlorine Aanlyzer 1 SP 2 ChenConc 0036378 AI AIT-841 LCP-TRW
EI115 Chlorine Aanlyzer 1 AIT-841 EquipAlrm DI YA-841 LCP-TRW
EI115 Chlorine Aanlyzer 1 Ch Analyzer 1 FlowPresent DI FSL-841 LCP-TRW
EI115 Sample Pump 2 SP 2 Ph 0036375 AI AIT-842 LCP-TRW
EI115 Sample Pump 2 AIT-842 EquipAlrm DI YA-842 LCP-TRW
EI115 Chlorine Aanlyzer 2 SP 2 ChenConc 0036378 AI AIT-843 LCP-TRW
EI115 Chlorine Aanlyzer 2 AIT-841 EquipAlrm DI YA-843 LCP-TRW
EI115 Chlorine Aanlyzer 2 Ch Analyzer 2 FlowPresent DI FSL-843 LCP-TRW
EI115 Sample Pump 2 SP 2 Ph 0036375 AI AIT-844 LCP-TRW
EI115 Sample Pump 2 AIT-844 EquipAlrm DI YA-844 LCP-TRW
EI115 Chlorine Aanlyzer 3 SP 2 ChenConc 0036378 AI AIT-845 LCP-TRW
EI115 Chlorine Aanlyzer 3 AIT-845 EquipAlrm DI YA-845 LCP-TRW
EI115 Chlorine Aanlyzer 3 Ch Analyzer 3 FlowPresent DI FSL-845 LCP-TRW
EI116 Sodium Bisulfite Test Vault 1 SB Test Vault 1 ChemLeak 0036307 DI LSH-850 LCP-TRW
EI116 Sodium Bisulfite Test Vault 2 SB Test Vault 2 ChemLeak 0036308 DI LSH-851 LCP-TRW
EI116 Sodium Bisulfite Test Vault 3 SB Test Vault 3 ChemLeak 0036309 DI LSH-852 LCP-TRW
EI116 Sodium Bisulfite Test Vault 4 SB Test Vault 4 ChemLeak 0036310 DI LSH-853 LCP-TRW
EI116 Sodium Bisulfite Test Vault 5 SB Test Vault 5 ChemLeak 0036311 DI LSH-854 LCP-TRW
EI116 Sodium Bisulfite Test Vault 5 SB Test Vault 6 ChemLeak 0036312 DI LSH-855 LCP-TRW
EI116 Sodium Bisulfite Test Vault 5 SB Test Vault 7ChemLeak 0036313 DI LSH-856 LCP-TRW
EI116 Sodium Bisulfite Test Vault 5 SB Test Vault 8 ChemLeak 0036314 DI LSH-857 LCP-TRW
EI116 Sodium Bisulfite Test Vault 5 SB Test Vault 9 ChemLeak 0036315 DI LSH-858 LCP-TRW
EI116 Sodium Bisulfite Test Vault 5 SB Test Vault 10 ChemLeak 0036316 DI LSH-859 LCP-TRW
EI116 Sodium Bisulfite Test Vault 5 SB Test Vault 11 ChemLeak 0036317 DI LSH-860 LCP-TRW
EI116 Sodium Bisulfite Test Vault 5 SB Test Vault 12 ChemLeak 0036318 DI LSH-861 LCP-TRW
EI116 Sodium Bisulfite Test Vault 5 SB Test Vault 13 ChemLeak 0036319 DI LSH-862 LCP-TRW
EI116 Sodium Bisulfite Test Vault 5 SB Test Vault 14 ChemLeak 0036320 DI LSH-863 LCP-TRW
EI101 Fire Alarm Indication DI LCP-TRW
SECTION 13226-9
DIGITAL INPUTS (126)
DIGITAL OUTPUTS (47)
ANALOG INPUTS (50)
ANALOG OUTPUTS (0)
TOTAL (223)
SECTION 13226-10
File details come from the government source that posted it. Updated .