W912PA-17-R-0010 – Questions & Answers 6 September 2017
| QUESTION |
| ANSWER |
| 1. |
| Is there a separate control for the air heater system in the garage of building # 20056? |
In the garage, 2 Buderus Calorette are installed. They are supplied thru an electrical panel in the garage with 3-phases circuit breaker. Both have a separate control box Buderus ON/OFF switch with following alarms (default, power default, anti-freeze, ventilator thermal default). A thermostat Honeywell CM907 is also connected to the system and control both air heaters.