This document is Amendment 0004 to Solicitation W912P624B0013, an invitation for bids for the Upper Wabash Project Office construction project. The purpose of this amendment is to revise specifications 04 20 00, 07 92 00, 08 44 00, and 08 51 13, and to extend the bid due date from June 12, 2024 to June 14, 2024 at 9:30 AM. The bid opening will be held 1 hour after the new bid due time at 10:30 AM. The contracting agency is the U.S. Army Corps of Engineers Engineering District Chicago.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT
Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.
15A. NAME AND TITLE OF SIGNER (Type or print)
30-105-04EXCEPTION TO SF 30
APPROVED BY OIRM 11-84
STANDARD FORM 30 (Rev. 10-83) Prescribed by GSA
FAR (48 CFR) 53.243
The purpose of this amendment is to revise the follow ing speficiations and extend the offers due date.
The follow ing specif ications has been revised: A. 04 20 00, B. 07 92 00, C. 08 44 00, and D. 08 51 13
This amendment is also extending the offer due date FROM June 12, 2024 TO June 14, 2024 at 9:30AM. The bids w ill be annouced via a bid opening, 1 hour after the bid due time AT 10:30AM.
1. CONTRACT ID CODE PAGE OF PAGES
1 2
16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)
16C. DATE SIGNED
BY
16B. UNITED STATES OF AMERICA15C. DATE SIGNED15B. CONTRACTOR/OFFEROR
(Signature of Contracting Officer)(Signature of person authorized to sign)
8. NAME AND ADDRESS OF CONTRACTOR (No., Street , County, State and Zip Code) X W912P624B0013
X 9B. DATED (SEE ITEM 11)
01-May-2024
10B. DATED (SEE ITEM 13)
9A. AMENDMENT OF SOLICITATION NO.
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
X The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offer X is extended, is not extended.
Offer must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended by one of the following methods:
(a) By completing Items 8 and 15, and returning 1 copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted;
or (c) By separate letter or telegram which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN
REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by telegram or letter, provided each telegram or letter makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.
12. ACCOUNTING AND APPROPRIATION DATA (If required)
13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS.
IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.
A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE
CONTRACT ORDER NO. IN ITEM 10A.
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation date, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(B).
C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER (Specify type of modification and authority)
E. IMPORTANT: Contractor is not, is required to sign this document and return copies to the issuing office.
14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
10A. MOD. OF CONTRACT/ORDER NO.
U0004
2. AMENDMENT/MODIFICATION NO. 5. PROJECT NO.(If applicable)
6. ISSUED BY
3. EFFECTIVE DATE
11-Jun-2024
CODE
U.S. ARMY ENGINEER DISTRICT, CHICAGO
231 SOUTH LASALLE STREET SUITE 1500
CHICAGO IL 60604-1437
W912P6 7. ADMINISTERED BY (If other than item 6)
4. REQUISITION/PURCHASE REQ. NO.
CODE
See Item 6
FACILITY CODECODE
EMAIL:TEL:
W912P624B0013
SECTION SF 30 BLOCK 14 CONTINUATION PAGE
SUMMARY OF CHANGES
SECTION 00 10 00 - SOLICITATION
The required response date/time has changed from 12-Jun-2024 01:00 PM to 14-Jun-2024 09:30 AM.
SECTION 04 20 00
UNIT MASONRY
11/15, CHG 2: 05/19
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
AMERICAN CONCRETE INSTITUTE (ACI)
ACI 216.1 (2014) Code Requirements for Determining
Fire Resistance of Concrete and Masonry
Construction Assemblies
ACI 318 (2014; Errata 1-2 2014; Errata 3-5 2015;
Errata 6 2016; Errata 7-9 2017) Building
Code Requirements for Structural Concrete
(ACI 318-14) and Commentary (ACI 318R-14)
ACI 318M (2014; ERTA 2015) Building Code
Requirements for Structural Concrete &
Commentary
ACI SP-66 (2004) ACI Detailing Manual
ASTM INTERNATIONAL (ASTM)
ASTM A153/A153M (2016a) Standard Specification for Zinc
Coating (Hot-Dip) on Iron and Steel
Hardware
ASTM A167 (2011) Standard Specification for
Stainless and Heat-Resisting
Chromium-Nickel Steel Plate, Sheet, and
Strip
ASTM A185/A185M (2007) Standard Specification for Steel
Welded Wire Reinforcement, Plain, for
Concrete
ASTM A615/A615M (2022) Standard Specification for Deformed and Plain Carbon-Steel Bars for Concrete
Reinforcement
ASTM A641/A641M (2019) Standard Specification for
Zinc-Coated (Galvanized) Carbon Steel Wire
ASTM A653/A653M (2022) Standard Specification for Steel
Sheet, Zinc-Coated (Galvanized) or
Zinc-Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process
ASTM A951/A951M (2011) Standard Specification for Steel
Wire for Masonry Joint Reinforcement
ASTM A996/A996M (2016) Standard Specification for
Rail-Steel and Axle-Steel Deformed Bars for Concrete Reinforcement
ASTM A1008/A1008M (2021a) Standard Specification for Steel, Sheet, Cold-Rolled, Carbon, Structural, High-Strength Low-Alloy, High-Strength
Low-Alloy with Improved Formability, Solution Hardened, and Bake Hardenable
ASTM A1064/A1064M (2022) Standard Specification for
Carbon-Steel Wire and Welded Wire
Reinforcement, Plain and Deformed, for
Concrete
ASTM B370 (2022) Standard Specification for Copper
Sheet and Strip for Building Construction
ASTM C27 (1998; R 2022) Fireclay and High-Alumina
Refractory Brick
ASTM C55 (2017) Standard Specification for Concrete
Building Brick
ASTM C62 (2017) Standard Specification for Building
Brick (Solid Masonry Units Made from Clay or Shale)
ASTM C67/C67M (2021) Standard Test Methods for Sampling and Testing Brick and Structural Clay Tile
ASTM C73 (2017) Standard Specification for Calcium
Silicate Brick (Sand-Lime Brick)
ASTM C90 (2022) Standard Specification for
Loadbearing Concrete Masonry Units
ASTM C126 (2022) Standard Specification for Ceramic
Glazed Structural Clay Facing Tile, Facing
Brick, and Solid Masonry Units
ASTM C129 (2017) Standard Specification for
Nonloadbearing Concrete Masonry Units
ASTM C207 (2018) Standard Specification for Hydrated
Lime for Masonry Purposes
ASTM C216 (2022) Standard Specification for Facing
Brick (Solid Masonry Units Made from Clay or Shale)
ASTM C270 (2019a; E 2019) Standard Specification for
Mortar for Unit Masonry
ASTM C315 (2007; R 2021) Standard Specification for
Clay Flue Linings and Chimney Pots
ASTM C476 (2022) Standard Specification for Grout for Masonry
ASTM C494/C494M (2019; E 2022) Standard Specification for
Chemical Admixtures for Concrete
ASTM C586 (2011) Standard Test Method for Potential
Alkali Reactivity of Carbonate Rocks as
Concrete Aggregates (Rock-Cylinder Method)
ASTM C616/C615M (2011) Standard Specification for Granite
Dimension Stone
ASTM C616/C616M (2010) Standard Specification for
Quartz-Based Dimension Stone
ASTM C641 (2017) Standard Test Method for Iron
Staining Materials in Lightweight Concrete
Aggregates
ASTM C652 (2022) Standard Specification for Hollow
Brick (Hollow Masonry Units Made from Clay or Shale)
ASTM C744 (2021) Standard Specification for Prefaced
Concrete and Calcium Silicate Masonry Units
ASTM C780 (2020) Standard Test Method for
Preconstruction and Construction
Evaluation of Mortars for Plain and
Reinforced Unit Masonry
ASTM C979/C979M (2016) Standard Specification for Pigments for Integrally Colored Concrete
ASTM C1019 (2019) Standard Test Method for Sampling and Testing Grout
ASTM C1314 (2014) Standard Test Method for
Compressive Strength of Masonry Prisms
ASTM C1384 (2012a) Standard Specification for
Admixtures for Masonry Mortars
ASTM C1405 (2015) Standard Specification for Glazed
Brick (Single Fired, Brick Units)
ASTM C1611/C1611M (2021) Standard Test Method for Slump Flow of Self-Consolidating Concrete
ASTM C1634 (2011) Standard Specification for Concrete
Facing Brick
ASTM D2000 (2018) Standard Classification System for
Rubber Products in Automotive Applications
ASTM D2287 (2019) Nonrigid Vinyl Chloride Polymer and
Copolymer Molding and Extrusion Compounds
ASTM E514/E514M (2020) Standard Test Method for Water
Penetration and Leakage Through Masonry
THE MASONRY SOCIETY (TMS)
TMS MSJC (2016) Masonry Standard Joint Committee's
(MSJC) Book - Building Code Requirements and Specification for Masonry Structures, Containing TMS 402/ACI 530/ASCE 5, TMS
602/ACI 530.1/ASCE 6, and Companion
Commentaries
1.2 SUBMITTALS
Government approval is required for submittals with a "G" or "S" classification. Submittals not having a "G" or "S" classification are for information only. When used, a code following the "G" classification identifies the office that will review the submittal for the Government.
Submit the following in accordance with Section 01 33 00 SUBMITTAL
PROCEDURES:
SD-02 Shop Drawings
Cut CMU Drawings; G, CS
Reinforcement Detail Drawings; G, CS
SD-03 Product Data
Hot Weather Procedures; G, CS
Cold Weather Procedures; G, CS
Concrete Masonry Units (CMU); G, CS
Cement; G, CS
Cementitious Materials; G, CS
Insulation; G, CS
SD-04 Samples
Concrete Masonry Units (CMU); G, CS
Admixtures for Masonry Mortar; G, CS
Anchors, Ties, and Bar Positioners; G, CS
Joint Reinforcement; G, CS
Clay Masonry Expansion-Joint Materials; G, CS
SD-05 Design Data
Masonry Compressive Strength; G, CS
Fire-Rated Concrete Masonry Units
Bracing Calculations; G, CS
SD-06 Test Reports
Fire-Rated Concrete Masonry Units
Field Testing of Mortar
Field Testing of Grout
Single-Wythe Masonry Wall Water Penetration Test
SD-07 Certificates
Concrete Masonry Units (CMU)
Cementitious Materials
Admixtures for Masonry Mortar
Admixtures for Grout
Anchors, Ties, and Bar Positioners
Joint Reinforcement
SD-08 Manufacturer's Instructions
Admixtures for Masonry Mortar
Admixtures for Grout
SD-10 Operation and Maintenance Data
Take-Back Program
SD-11 Closeout Submittals
Recycled Content of Cement; S
1.3 QUALITY ASSURANCE
1.4 DELIVERY, STORAGE, AND HANDLING
Deliver, store, handle, and protect material to avoid chipping, breakage, and contact with soil or contaminating material. Store and prepare materials in already disturbed areas to minimize project site disturbance and size of project site.
1.4.1 Masonry Units
Cover and protect masonry units from precipitation. Conform to handling and storage requirements of TMS MSJC.
a. Pack glazed brick, glazed structural clay tile, and prefaced concrete masonry units in the manufacturer's standard paper cartons, trays, or shrink wrapped pallets with a divider between each unit. Do not stack pallets. Do not remove units from cartons until cartons are placed on scaffolds or in the location where units are to be laid.
b. Mark prefabricated lintels on top sides to show either the lintel schedule number or the number and size of top and bottom bars.
1.4.2 Reinforcement, Anchors, and Ties
Store steel reinforcing bars, coated anchors, ties, and joint reinforcement above the ground. Maintain steel reinforcing bars and uncoated ties free of loose mill scale and loose rust.
1.4.3 Cementitious Materials, Sand and Aggregates
Deliver cementitious and other packaged materials in unopened containers, plainly marked and labeled with manufacturers' names and brands. Store cementitious material in dry, weathertight enclosures or completely cover.
Handle cementitious materials in a manner that will prevent the inclusion of foreign materials and damage by water or dampness. Store sand and aggregates in a manner to prevent contamination and segregation.
1.5 PROJECT/SITE CONDITIONS
Conform to TMS MSJC for hot and cold weather masonry erection.
1.5.1 Hot Weather Procedures
When ambient air temperature exceeds 100 degrees F, or exceeds 90 degrees F and the wind velocity is greater than 8 mph, comply with TMS MSJC Article
1.8 D for: preparation prior to conducting masonry work; construction while masonry work is in progress; and protection for newly completed masonry.
1.5.2 Cold Weather Procedures
When ambient temperature is below 40 degrees F, comply with TMS MSJC
Article 1.8 C for: preparation prior to conducting masonry work;
construction while masonry work is in progress; and protection for newly completed masonry.
PART 2 PRODUCTS
2.1 SYSTEM DESCRIPTION
2.1.1 Design - Specified Compressive Strength of Masonry
The specified compressive strength of masonry, f'm, is as indicated for each type of masonry .
2.1.2 Performance - Verify Masonry Compressive Strength
Verify specified compressive strength of masonry using the "Unit Strength
Method" of TMS MSJC. Submit calculations and certifications of unit and mortar strength.
Verify specified compressive strength of masonry using the "Prism Test
Method" of TMS MSJC when the "Unit Strength Method" cannot be used. Submit test results.
2.2 MANUFACTURED UNITS
2.2.1 General Requirements
Do not change the source of materials, which will affect the appearance of the finished work, after the work has started except with Contracting
Officer's approval. Submit test reports from an approved independent laboratory. Certify test reports on a previously tested material as the same materials as that proposed for use in this project. Submit certificates of compliance stating that the materials meet the specified requirements.
2.2.2 Concrete Units
2.2.2.1 Aggregates
Test lightweight aggregates, and blends of lightweight and heavier aggregates in proportions used in producing the units, for stain-producing iron compounds in accordance with ASTM C641,visual classification method.
Do not incorporate aggregates for which the iron stain deposited on the filter paper exceeds the "light stain" classification.
Use industrial waste by-products (air-cooled slag, cinders, or bottom ash), ground waste glass and concrete, granulated slag, and expanded slag in aggregates.
2.2.2.2 Concrete Masonry Units (CMU)
2.2.2.2.1 Cement
Use only cement that has a low alkali content and is of one brand.
2.2.2.2.2 Recycled Content
Provide units with a minimum of 10 percent post-consumer recycled content, or a minimum of 40 percent post-industrial recycled content, based on mass, cost, or volume.Units may contain post-consumer or post-industrial recycled content.
2.2.2.2.3 Size
Provide units with specified dimension of 7 5/8 inches inches wide, 7 5/8 inches inches high, and 15 5/8 inches inches long.
2.2.2.2.4 Surfaces
Provide units with exposed surfaces that are smooth and of uniform texture.
2.2.2.2.5 Weather Exposure
Provide concrete masonry units with water-repellant admixture added during manufacture where units will be exposed to weather.
2.2.2.2.6 Unit Types
a. Hollow Load-Bearing Units: ASTM C90, normal weight. Provide load-bearing units for exterior walls, foundation walls, load-bearing walls, and shear walls.
b. Hollow Non-Load-Bearing Units: ASTM C129, normal weight. Load-bearing units may be provided in lieu of non-load-bearing units.
c. Solid Load-Bearing Units: ASTM C90, normal weight units. Provide solid units as indicated.
2.2.2.2.7 Jamb Units
Provide jamb units of the shapes and sizes to conform with wall units.
Solid units may be incorporated in the masonry work where necessary to fill out at corners, gable slopes, and elsewhere as approved.
Provide sash jamb units with a 3/4 by 3/4 inch groove near the center at end of each unit.
2.2.2.3 Split Face CMU Units
Provide units with patterned face shell: split face..
Units shall be fabircated with integral water repellent and shall be integrally colored during manufacture. Water repellant primer and stain shall also be applied to all split face unit walls after completion of exterior work and when the masonry is not subject to damage by construction activities..
2.2.2.4 Fire-Rated Concrete Masonry Units
For indicated fire-rated construction, provide concrete masonry units of minimum equivalent thickness for the fire rating indicated and the corresponding type of aggregates indicated in TABLE I. Units containing more than one of the aggregates listed in TABLE I will be rated by linear interpolation based on the percent by dry-rodded volume of each aggregate used in manufacturing the units.
TABLE I
FIRE-RATED CONCRETE MASONRY UNITS
Aggregate Type Minimum Equivalent Thickness for Fire-Resistance
Rating, inch
1/2 hour
3/4 hour
1 hour 1-1/2 hour hours
3 hours 4 hours
TABLE I
FIRE-RATED CONCRETE MASONRY UNITS
Aggregate Type Minimum Equivalent Thickness for Fire-Resistance
Rating, inch
Calcareous or siliceous gravel (other than limestone)
2.0 2.4 2.8 3.6 4.2 5.3 6.2
Limestone, cinders, or air-cooled slag
1.9 2.3 2.7 3.4 4.0 5.0 5.9
Expanded clay, expanded shale, or expanded slate
1.8 2.2 2.6 3.3 3.6 4.4 5.1
Expanded slag or pumice 1.5 1.9 2.1 2.7 3.2 4.0 4.7
Determine equivalent thickness in accordance with ACI 216.1. Where walls are to receive plaster or be faced with brick, or otherwise form an assembly; include the thickness of plaster or brick or other material in the assembly in determining the equivalent thickness. Submit calculation results.
2.2.2.5 Prefaced Concrete Masonry Units
Provide prefaced concrete masonry units where indicated on the drawings.
Where prefaced concrete masonry units are provided, concrete masonry unit backing may be omitted when the nominal thickness of the prefaced concrete masonry units is the same as the total indicated nominal thickness of the facing tile plus the backing.
a. Provide prefaced concrete masonry units conforming to ASTM C744 using masonry units conforming to ASTM C90, with the facing turned over the edges and ends of the unit at least 3/8 inch in the direction of the thickness of the unit to form a lip at least 1/16 inch thick. Limit variation in color and texture to that in the approved sample.
b. Provide all shapes and sized for a complete installation. Use bullnose units along sills and caps and at vertical external corners including door jambs, window jambs, and other such openings with a bullnose radius of 1 inch. Cove base units to meet finished floor surfaces.
2.3 EQUIPMENT
2.3.1 Vibrators
Maintain at least one spare vibrator on site at all times.
2.3.2 Grout Pumps
Pumping through aluminum tubes is not permitted.
2.4 MATERIALS
2.4.1 Mortar Materials
2.4.1.1 Cementitious Materials
Provide cementitious materials that conform to those permitted by ASTM C270.
2.4.1.2 Hydrated Lime and Alternates
Provide lime that conforms to one of the materials permitted by ASTM C207 for use in combination with portland cement, hydraulic cement, and blended hydraulic cement. Do not use lime in combination with masonry cement or mortar cement.
2.4.1.3 Colored Mortar
Use mortar pigment that conforms to ASTM C979/C979M. Add pigment to mortar to produce a uniform color as indicated on the drawings. Furnish pigments in accurately pre-measured and packaged units that can be added to a measured amount of cementitious materials or supply pigments via preblended cementitious materials or dry mortar mix.
a. In masonry cement or mortar cement, do not exceed 5 percent of cement weight for mineral oxide pigment; do not exceed 1 percent of cement weight for carbon black pigment.
b. In cement-lime mortar mix, do not exceed 10 percent of cementitious materials' weight for mineral oxide pigment; do not exceed 2 percent of cementitious materials' weight for carbon black pigment.
2.4.1.4 Admixtures for Masonry Mortar
In cold weather, use a non-chloride based accelerating admixture that conforms to ASTM C1384, unless Type III portland cement is used in the mortar.
In showers and kitchens, use mortar that contains a water-repellent admixture that conforms to ASTM C1384. Provide a water-repellent admixture, conforming to ASTM C1384 and of the same brand and manufacturer as the block's integral water-repellent, in the mortar used to place concrete masonry units that have an integral water-repellent admixture.
2.4.1.5 Aggregate and Water
Provide aggregate (sand) and water that conform to materials permitted by
ASTM C270.
2.4.2 Grout and Ready-Mix Grout Materials
2.4.2.1 Cementitious Materials for Grout
Provide cementitious materials that conform to those permitted by ASTM C476.
2.4.2.2 Admixtures for Grout
Water-reducing admixtures that conform to ASTM C494/C494M Type F or G and viscosity-modifying admixtures that conform to ASTM C494/C494M Type S are permitted for use in grout. Other admixtures require approval by the
Contracting Officer.
In cold weather, a non-chloride based accelerating admixture may be used subject to approval by the Contracting Officer; use accelerating admixture that is non-corrosive and conforms to ASTM C494/C494M, Type C.
2.4.2.3 Aggregate and Water
Provide fine and coarse aggregates and water that conform to materials permitted by ASTM C476.
2.5 MORTAR AND GROUT MIXES
2.5.1 Mortar Mix
a. Provide mortar Type N (for above grade exterior veneer masonry) or S
(for below grade exterior veneer masonry) unless specified otherwise herein. Do not use masonry cement in the mortar. Do not use air-entrainment in the mortar.
b. Use ASTM C270 Type M cement-lime mortar or mortar cement mortar for seismic-force-resisting elements indicated.
c. Provide mortar that conforms to ASTM C270. Use Type S mortar for foundation walls .
d. Provide Type N or S mortar for non-load-bearing, non-shear-wall interior masonry.
e. For field-batched mortar, measure component materials by volume. Use measuring boxes for materials that do not come in packages, such as sand, for consistent batching. Mix cementitious materials and aggregates between 3 and 5 minutes in a mechanical batch mixer with a sufficient amount of water to produce a workable consistency. Do not hand mix mortar unless approved by the Contracting Officer. Maintain workability of mortar by remixing or retempering. Discard mortar that has begun to stiffen or is not used within 2-1/2 hours after initial mixing.
f. For preblended mortar, follow manufacturer's mixing instructions.
2.5.2 Grout and Ready Mix Grout Mix
Use grout that conforms to ASTM C476, fine . Use conventional grout with a slump between 8 and 11 inches. Use self-consolidating grout with slump flow of 24 to 30 inches and a visual stability index (VSI) not greater than
1. Provide minimum grout strength of 2000 psi in 28 days, as tested in accordance with ASTM C1019. Do not change proportions and do not use materials with different physical or chemical characteristics in grout for the work unless additional evidence is furnished that grout meets the specified requirements. Use ready-mixed grout that conforms to ASTM C476.
2.6 ACCESSORIES
2.6.1 Grout Barriers
Grout barriers for vertical cores that consist of fine mesh wire, fiberglass, or expanded metal.
2.6.2 Anchors, Ties, and Bar Positioners
2.6.2.1 General
a. Fabricate anchors and ties without drips or crimps. Size anchors and ties to provide a minimum of 5/8 inch mortar cover from each face of masonry.
b. Fabricate steel wire anchors and ties from wire conforming to
ASTM A1064/A1064M and hot-dip galvanize in accordance with
ASTM A153/A153M.
c. Fabricate joint reinforcement in conformance with ASTM A951/A951M. Hot dip galvanize joint reinforcement in exterior walls and in interior walls exposed to moist environment in conformance with ASTM A153/A153M.
Galvanize joint reinforcement in other interior walls in conformance with ASTM A641/A641M; coordinate with paragraph JOINT REINFORCEMENT below.
d. Fabricate sheet metal anchors and ties in conformance with
ASTM A1008/A1008M. Hot dip galvanize sheet metal anchors and ties in exterior walls and in interior walls exposed to moist environment in compliance with ASTM A153/A153M Class B. Galvanize sheet metal anchors and ties in other interior walls in compliance with ASTM A653/A653M, Coating Designation G60.
e. Submit two anchors, ties and bar positioners of each type used, as samples.
2.6.2.2 Wire Mesh Anchors
Provide wire mesh anchors of 1/4 inch mesh galvanized hardware cloth, conforming to ASTM A185/A185M, with length not less than 12 inches, at intersections of interior non-bearing masonry walls.
2.6.2.3 Wall Ties for Multi-Wythe Masonry Construction
Provide rectangular-shaped wall ties, fabricated of hot-dipped galvanized
W1.7 diameter steel wire. Provide rectangular wall ties no less than 4 inches wide.
Provide adjustable type wall ties, if approved for use, that consist of two essentially U-shaped elements fabricated of minimum W2.8 diameter steel wire or pintle type ties that are inserted to eyes of horizontal joint reinforcement, hot-dip galvanized. Provide adjustable ties with double pintle legs and allows a maximum offset of 1-1/4 inch between each element of the tie and maximum distance between connecting parts no more than 1/16 inch. Form the pintle and eye elements so that both can be in the same plane. Wall ties may also be of a continuous type conforming to paragraph
JOINT REINFORCEMENT.
2.6.2.4 Adjustable Anchors
2.6.2.4.1 Anchorage of Veneer to Light Gauge Steel or Concrete Backing
Use one of the following types of adjustable anchors to connect veneer to light gauge steel or concrete backing:
a. sheet metal at least 7/8 inch wide, 0.06 inch thick, and with corrugations having a wavelength of 0.3 to 0.5 inch and an amplitude of
0.06 to 0.10 inch or bent, notched or punched to provide equivalent performance;
b. wire anchors of minimum size W1.7 with ends bent to form a minimum 2 inches extension and without drips;
c. or wire pintle anchors used in conjunction with joint reinforcement.
Do not exceed 1/16 inch clearance between connecting parts of the tie.
Assemble adjustable anchors to prevent disengagement. Provide pintle anchors with one or more pintle legs of wire size W2.8 and an offset not exceeding 1-1/4 inch.
2.6.2.5 Veneer Anchor Screws
Provide screws for attachment of veneer anchors to cold-formed steel framing members of size as required by design to provide the needed pullout load capacity but not less than No. 12. Provide length of screws such that the screws penetrate the holding member by not less than 5/8 inch.
2.6.2.6 Bar Positioners
Factory-fabricate bar positioners, used to prevent displacement of reinforcing bars during the course of construction, from 9 gauge steel wire or equivalent, and hot-dip galvanized. Bar positioners must be suitable for intended use and be corrosion resistant steel. Bar positioners not fully contained within the wythe must be hot-dip galvanized.
2.6.3 Joint Reinforcement
Factory fabricate joint reinforcement in conformance with ASTM A951/A951M, welded construction. Provide ladder type joint reinforcement, having one longitudinal wire in the mortar bed of each face shell for hollow units and one wire for solid units and with all wires a minimum of 9 gauge. Size joint reinforcement to provide a minimum of 5/8 inch cover from each face.
Space crosswires not more than 16 inches. Provide joint reinforcement for straight runs in flat sections not less than 10 feet long. Provide joint reinforcement with factory formed corners and intersections. If approved for use, joint reinforcement may be furnished with adjustable wall tie features. Submit one piece of each type used, including corner and wall intersection pieces, showing at least two cross wires.
2.6.4 Reinforcing Steel Bars
Provide reinforcing steel bars and rods conforming to ASTM A615/A615M or
ASTM A996/A996M, Grade 60.
2.6.5 Concrete Masonry Control Joint Keys
Provide control joint keys of a factory fabricated solid section of natural or synthetic rubber (or combination thereof) conforming to ASTM D2000
M2AA-805 with a minimum durometer hardness of 80 or polyvinyl chloride conforming to ASTM D2287 Type PVC 654-4 with a minimum durometer hardness of 85. Form the control joint key with a solid shear section not less than
5/8 inch thick and 3/8 inch thick flanges, with a tolerance of plus or minus
1/16 inch, to fit neatly, but without forcing, in masonry unit jamb sash grooves.
2.6.6 Clay Masonry Expansion-Joint Materials
Provide backer rod and sealant, adequate to accommodate joint compression and extension equal to 50 percent of the width of the joint. Provide the backer rod of compressible rod stock of closed cell polyethylene foam, polyurethane foam, butyl rubber foam, or other flexible, nonabsorptive material as recommended by the sealant manufacturer. Provide sealant in conformance with Section 07 92 00 JOINT SEALANTS with a maximum volatile organic compound (VOC) content of 600 grams/liter.
Submit one piece of each type of material used.
2.6.7 Through Wall Flashing and Weeps
2.6.7.1 General
Provide coated copper, copper or stainless steel sheet, self-adhesive rubberized sheet, or reinforced membrane sheet flashing except that the material must be one which is not adversely affected by dampproofing material.
2.6.7.2 Coated-Copper Flashing
Provide 7 ounce, electrolytic copper sheet, uniformly coated on both sides with acidproof, alkaliproof, asphalt impregnated kraft paper or polyethylene sheets.
2.6.7.3 Copper or Stainless Steel Flashing
Provide copper sheet, complying with ASTM B370, minimum 16 ounce weight; or stainless steel, ASTM A167, Type 304 or 316, 0.015 inch thick, No. 2D finish. Provide with factory-fabricated deformations that mechanically bond flashing against horizontal movement in all directions, where deformations consist of dimples, diagonal corrugations, or a combination of dimples and transverse corrugations.
2.6.7.4 Reinforced Membrane Flashing
Provide polyester film core with a reinforcing fiberglass scrim bonded to one side. Provide membrane that is impervious to moisture, flexible, is not affected by caustic alkalis, and after being exposed for not less than
1/2 hour to a temperature of 32 degrees F, shows no cracking when, at that temperature, it is bent 180 degrees over a 1/16 inch diameter mandrel and then bent at the same point over the same size mandrel in the opposite direction 360 degrees.
2.6.7.5 Rubberized Flashing
Provide self-adhesive rubberized asphalt sheet flashing consisting of 32-mil thick pliable and highly adhesive rubberized asphalt compound bonded completely and integrally to 8-mil thick, high density, cross-laminated polyethylene film to produce an overall thickness of 40 mils. Provide rubberized, asphalt-based mastic and surface conditioner that are each approved by flashing manufacturer for use with flashing material.
2.6.7.6 Weep Ventilators
Provide weep ventilators that are prefabricated from stainless steel or plastic. Provide inserts with grill or louver-type openings designed to allow the passage of moisture from cavities and to prevent the entrance of insects, and with a rectangular closure strip to prevent mortar droppings from clogging the opening. Provide ventilators with compressible flanges to fit in a standard 3/8 inch wide mortar joint and with height equal to the nominal height of the unit.
2.6.7.7 Single-Wythe Exterior Wall CMU Flashing System
In single-wythe exterior CMU walls, provide a system of CMU cell flashing pans and interlocking CMU web covers made from UV-resistant, high-density polyethylene. For exterior CMU walls, provide a flashing/weep system in open cores that do not receive grout. Cell flashing pans are to have integral weep spouts built into mortar bed joints that extend into the cell to prevent clogging with mortar.
2.6.7.8 Metal Drip Edge
Provide stainless steel drip edge, 15-mil thick, hemmed edges, with down-turned drip at the outside edge and upturned dam at the inside edge for use with membrane flashings.
2.6.8 RIGID BOARD-TYPE INSULATION
Provide rigid board-type insulation as specified in Section 07 21 13 BOARD
AND BLOCK INSULATION.
PART 3 EXECUTION
3.1 EXAMINATION
Prior to start of work, verify the applicable conditions as set forth in
TMS MSJC, inspection.
3.2 PREPARATION
3.2.1 Stains
Protect exposed surfaces from mortar and other stains. When mortar joints are tooled, remove mortar from exposed surfaces with fiber brushes and wooden paddles. Protect base of walls from splash stains by covering adjacent ground with sand, sawdust, or polyethylene.
3.2.2 Loads
Do not apply uniform loads for at least 12 hours or concentrated loads for at least 72 hours after masonry is constructed. Provide temporary bracing as required.
3.2.3 Concrete Surfaces
Where masonry is to be placed, clean concrete of laitance, dust, dirt, oil, organic matter, or other foreign materials and slightly roughen to provide a surface texture with a depth of at least 1/8 inch. Sandblast, if necessary, to remove laitance from pores and to expose the aggregate.
3.2.4 Shelf Angles
Adjust shelf angles as required to keep the masonry level and at the proper elevation.
3.2.5 Bracing
Provide bracing and scaffolding necessary for masonry work. Design bracing to resist wind pressure as required by OSHA and local codes and submit bracing calculations, sealed by a registered professional engineer. Do not remove bracing in less than 10 days.
3.3 ERECTION
3.3.1 General
a. Coordinate masonry work with the work of other trades to accommodate built-in items and to avoid cutting and patching. Lay masonry units in the indicated bond pattern. Lay facing courses level with back-up courses, unless the use of adjustable ties has been approved in which case the tolerances is plus or minus 1/2 inch. Adjust each unit to its final position while mortar is still soft and has plastic consistency.
b. Remove and clean units that have been disturbed after the mortar has stiffened, and relay with fresh mortar. Keep air spaces, cavities, chases, expansion joints, and spaces to be grouted free from mortar and other debris. Select units to be used in exposed masonry surfaces from those having the least amount of chipped edges or other imperfections detracting from the appearance of the finished work.
c. When necessary to temporarily discontinue the work, step (rack) back the masonry for joining when work resumes. Toothing may be used only when specifically approved by the Contracting Officer. Before resuming work, remove loose mortar and thoroughly clean the exposed joint.
Cover the top of walls subjected to rain or snow with nonstaining waterproof covering or membrane when work is not in process. Extend the covering a minimum of 610 mm 2 feet down on each side of the wall and hold securely in place.
d. Ensure that units being laid and surfaces to receive units are free of water film and frost. Lay solid units in a nonfurrowed full bed of mortar. Bevel mortar for veneer wythes and slope down toward the cavity side. Shove units into place so that the vertical joints are tight. Completely fill vertical joints between solid units with mortar, except where indicated at control, expansion, and isolation joints. Place hollow units so that mortar extends to the depth of the face shell at heads and beds, unless otherwise indicated. Mortar will be permitted to protrude up to 1/2 inch into the space or cells to be grouted. Provide means to prevent mortar from dropping into the space below or clean grout spaces prior to grouting.
3.3.1.1 Jointing
Tool mortar joints when the mortar is thumbprint hard. Tool horizontal joints after tooling vertical joints. Brush mortar joints to remove loose and excess mortar.
3.3.1.1.1 Tooled Joints
Tool mortar joints in exposed exterior and interior masonry surfaces concave , using a jointer that is slightly larger than the joint width so that complete contact is made along the edges of the unit. Perform tooling so that the mortar is compressed and the joint surface is sealed. Use a jointer of sufficient length to obtain a straight and true mortar joint.
No exterior joints are to be left un-tooled.
3.3.1.1.2 Flush Joints
Flush cut mortar joints in concealed masonry surfaces and joints at electrical outlet boxes in wet areas. Finish flush cut joints by cutting off the mortar flush with the face of the wall. Point joints in unparged masonry walls below grade tight. For architectural units, such as fluted units, completely fill both the head and bed joints and flush cut.
3.3.1.1.3 Door and Window Frame Joints
On the exposed interior side of exterior frames, rake joints between frames and abutting masonry walls to a depth of 3/8 inch. On the exterior side of exterior frames,rake joints between frames and abutting masonry walls to a depth of 3/8 inch.
3.3.1.1.4 Joint Widths
a. Construct brick masonry with mortar joint widths equal to the difference between the specified and nominal dimensions of the unit, within tolerances permitted by TMS MSJC.
b. Provide 3/8 inch wide mortar joints in concrete masonry, except for prefaced concrete masonry units.
c. Provide 3/8 inch wide mortar joints on unfaced side of prefaced concrete masonry units and not less than 3/16 inch nor more than 1/4 inch wide on prefaced side.
d. Maintain mortar joint widths within tolerances permitted by TMS MSJC
3.3.1.2 Cutting and Fitting
Use full units of the proper size wherever possible, in lieu of cut units.
Locate cut units where they would have the least impact on the architectural aesthetic goals of the facility. Perform cutting and fitting, including that required to accommodate the work of others, by masonry mechanics using power masonry saws. Concrete masonry units may be wet or dry cut. Before being placed in the work, dry wet-cut units to the same surface-dry appearance as uncut units being laid in the wall. Provide cut edges that are clean, true and sharp.
a. Carefully make openings in the masonry so that wall plates, cover plates or escutcheons required by the installation will completely conceal the openings and will have bottoms parallel with the masonry bed joints. Provide reinforced masonry lintels above openings over 12 inches wide for pipes, ducts, cable trays, and other wall penetrations, unless steel sleeves are used.
b. Do not reduce masonry units in size by more than one-third in height and one-half in length. Do not locate cut products at ends of walls, corners, and other openings.
3.3.1.3 Unfinished Work
Rack back unfinished work for joining with new work. Toothing may be resorted to only when specifically approved by the Contracting Officer.
Remove loose mortar and thoroughly clean the exposed joints before laying new work.
3.3.1.4 Clay Masonry Expansion Joints
Provide clay masonry expansion joints as indicated. Construct by leaving a gap . Ensure that no mortar or other noncompressible materials are within the joint. Install backer rod and sealant in accordance with Section
07 92 00 JOINT SEALANTS.
3.3.1.5 Control Joints
Provide control joints in concrete masonry as indicated. Construct by raking out mortar within the head joint in accordance with the details shown on the Drawings. Form a continuous vertical joint at control joint locations, including through bond beams, by utilizing half blocks in alternating courses on each side of the joint. Interrupt the control joint key in courses containing continuous bond beam reinforcement. Do not interrupt the horizontal reinforcement and grout at the control joint.
Where mortar was placed in the joint, rake both faces of the control joints to a depth of 3/4 inch. Install backer rod and sealant on both faces in accordance with Section 07 92 00 JOINT SEALANTS.
3.3.1.6 Decorative Architectural Units
Place decorative masonry units with the patterned face shell properly aligned in the completed wall.
3.3.2 Anchored Veneer Construction
a. Construct exterior masonry wythes to the thickness indicated on the drawings. Provide a minimum 2-3/4 inch air space behind the masonry veneer and face of rigid board insulation. Provide means to ensure that the cavity space and flashings are kept clean of mortar droppings and other loose debris. Maintain chases and raked-out joints free from mortar and debris.
b. Place masonry in running bond pattern. Provide continuous single wire joint reinforcement of wire size W1.7 (MW11) at a maximum spacing of 16 inches on center vertically. Mechanically attach anchors to the joint reinforcement with clips or hoooks.
c. For veneer with a masonry backup wythe, lay up both the inner and the outer wythes together except when adjustable joint reinforcement assemblies are approved for use. When both wythes are not brought up together, install through-wall flashings with the exterior wythe, securing the top edge of the flashing with a termination bar and sealant, or protect flashings that are installed with the interior wythe from damage until they are fully enclosed in the wall.
d. . For adjustable two piece anchors, anchors of wire size W1.7 (MW11), and 22 gage corrugated sheet-metal anchors, provide at least one anchor for each 2 sq. ft of wall area. For other anchors, provide one anchor
(brick ties) to connect the veneer to its backing for each 2.5 sq. ft of wall area. Provide additional anchors around openings larger than 16 inch in either direction. Space anchors around perimeter of opening at a maximum of 24 inches on center. Place anchors within 12 inches of openings. Anchors with drips are not permitted.
f. With solid units, embed anchors in mortar joint and extend into the veneer a minimum of 1-1/2 inch, with at least 5/8 inch mortar cover to the outside face.
g. With hollow units, embed anchors in mortar or grout and extend into the veneer a minimum of 1-1/2 inch, with at least 5/8 inch mortar or grout cover to outside face.
3.3.3 Reinforced, Single Wythe Concrete Masonry Units Walls
3.3.3.1 Concrete Masonry Unit Placement
a. Fully bed units used to form piers, pilasters, columns, starting courses on footings, solid foundation walls, lintels, and beams, and where cells are to be filled with grout in mortar under both face shells and webs. Provide mortar beds under both face shells for other units. Mortar head joints for a distance in from the face of the unit not less than the thickness of the face shell.
b. Solidly grout foundation walls below grade.
c. Submit drawings showing elevations of walls exposed to view and indicating the location of all cut CMU products.
3.3.3.2 Preparation for Reinforcement
Lay units in such a manner as to preserve the unobstructed vertical continuity of cores to be grouted. Remove mortar protrusions extending 1/2 inch or more into cells before placing grout. Position reinforcing bars accurately as indicated before placing grout. Where vertical reinforcement occurs, fill cores solid with grout in accordance with paragraph PLACING
GROUT in this Section.
3.3.4 Cavity Walls (Multi-Wythe Noncomposite Walls
Provide a continuous cavity as indicated. Bevel mortar beds away from cavity to prevent projection into cavity when bricks are shoved in place.
Keep cavities clear and clean of mortar droppings. At the bottom of cavity walls, in the course immediately above the through-wall flashing, temporarily omit one brick every 4 feet. Clean mortar droppings and debris out of the cavity through the temporary openings at least once each day masonry is laid, and more often when required to keep the cavities clean.
Fill in the openings with bricks and mortar after the wall is complete and the cavity has been inspected and found clean.
Securely tie the two wythes together with horizontal joint reinforcement, or provide ties to connect the masonry wythes in sufficient quantity.
Provide additional ties around openings larger than 16 inches in either direction. Space ties around perimeter of opening at a maximum of 3 feet on center. Place ties within 12 inchesof openings. Ties with drips are not permitted.
3.3.5 ANCHORAGE
3.3.5.1 Anchorage to Concrete
Anchor masonry to the face of concrete columns, beams, or walls with dovetail anchors spaced not over 16 inches on centers vertically and 24 inches on center horizontally.
3.3.5.2 Anchorage at Intersecting Walls
Provide wire mesh anchors at maximum 16 inches spacing at intersections of interior non-bearing masonry walls.
Anchor structural masonry walls with horizontal joint reinforcement spaced no more than 16 inches on center and overlapping masonry units , unless the drawings indicate a movement joint at the intersection.
3.3.6 Lintels
3.3.6.1 Masonry Lintels
Construct masonry lintels with lintel units filled solid with grout in all courses and reinforced with a minimum of two No. 4 bars in the bottom course unless otherwise indicated. Extend lintel reinforcement beyond each side of masonry opening 40 bar diameters or 24 inches, whichever is greater. Support reinforcing bars in place prior to grouting and locate
1/2 inch above the bottom inside surface of the lintel unit.
3.3.6.2 Steel Lintels
Provide steel lintels as shown on the Drawings. Set lintels in a full bed of mortar with faces plumb and true. Provide steel lintels with a minimum bearing length of 8 inches unless otherwise indicated. In partially grouted masonry, provide fully grouted units under the full lintel bearing length, unless otherwise indicated.
3.3.7 Sills and Copings
Set sills and copings in a full bed of mortar with faces plumb and true.
Slope sills and copings to drain water. Mechanically anchor copings and sills longer than 4 feet as indicated.
3.4 INSTALLATION
3.4.1 Bar Reinforcement Installation
3.4.1.1 Preparation
Submit detail drawings showing bar splice locations. Identify bent bars on a bending diagram and reference and locate such bars on the drawings.
Show wall dimensions, bar clearances, and wall openings. Utilize bending details that conform to the requirements of ACI SP-66. No approval will be given to the shop drawings until the Contractor certifies that all openings, including those for mechanical and electrical service, are shown. If, during construction, additional masonry openings are required, resubmit the approved shop drawings with the additional openings shown along with the proposed changes. Clearly highlight location of these additional openings. Provide wall elevation drawings with minimum scale of
1/4 inch per foot. Submit drawings including plans, elevations, and details of wall reinforcement; details of reinforcing bars at corners and wall intersections; offsets; tops, bottoms, and ends of walls; control and expansion joints; lintels; and wall openings.
Clean reinforcement of loose, flaky rust, scale, grease, mortar, grout, and other coatings that might destroy or reduce its bond prior to placing grout. Do not use bars with kinks or bends not shown on the approved shop drawings. Place reinforcement prior to grouting. Unless otherwise indicated, extend vertical wall reinforcement to within 2 inches of tops of walls.
3.4.1.2 Positioning Bars
a. Accurately place vertical bars within the cells at the positions indicated on the drawings. Maintain a minimum clearance of 1/2 inch between the bars and masonry units. Provide minimum clearance between parallel bars of 1/2 inch between the bars and masonry units for coarse grout and a minimum clearance of 1/4 inch between the bars and masonry units for fine grout. Provide minimum clearance between parallel bars of 1 inch or one diameter of the reinforcement, whichever is greater.
Vertical reinforcement may be held in place using bar positioners located near the ends of each bar and at intermediate intervals of not more than 192 diameters of the reinforcement or by other means to prevent displacement beyond permitted tolerances. As masonry work progresses, secure vertical reinforcement to prevent displacement beyond allowable tolerances.
b. Wire column and pilaster lateral ties in position around the vertical reinforcing bars. Place lateral ties in contact with the vertical reinforcement and do not place in horizontal mortar bed joints.
c. Position horizontal reinforcing bars as indicated. Stagger splices in adjacent horizontal bars, unless otherwise indicated.
d. Form splices by lapping bars as indicated. Do not cut, bend or eliminate reinforcing bars. Foundation dowel bars may be field-bent when permitted by TMS MSJC.
3.4.1.3 Splices of Bar Reinforcement
Lap splice reinforcing bars as indicated. When used, provide welded or mechanical connections that develop at least 125 percent of the specified yield strength of the reinforcement.
3.4.2 Placing Grout
3.4.2.1 General
Fill cells containing reinforcing bars with grout. Solidly grout hollow masonry units in walls or partitions supporting plumbing, heating, or other mechanical fixtures, voids at door and window jambs, and other indicated spaces. Solidly grout cells under lintel bearings on each side of openings for full height of openings. Solidly grout walls below grade, lintels, and bond beams. Units other than open end units may require grouting each course to preclude voids in the units.
Discard site-mixed grout that is not placed within 1-1/2 hours after water is first added to the batch or when the specified slump is not met without adding water after initial mixing. Discard ready-mixed grout that does not meet the specified slump without adding water other than water that was added at the time of initial discharge. Allow sufficient time between grout lifts to preclude displacement or cracking of face shells of masonry units. Provide a grout shear key between lifts when grouting is delayed and the lower lift loses plasticity. If blowouts, flowouts, misalignment, or cracking of face shells should occur during construction, tear down the wall and rebuild.
3.4.2.2 Horizontal Grout Barriers
Embed horizontal grout barriers in mortar below cells of hollow units receiving grout.
3.4.2.3 Grout Holes and Cleanouts
3.4.2.3.1 Grout Holes
Provide grouting holes in slabs, spandrel beams, and other in-place overhead construction. Locate holes over vertical reinforcing bars or as required to facilitate grout fill in bond beams. Provide additional openings spaced not more than 16 inches on centers where grouting of hollow unit masonry is indicated. Fom such openings not less than 4 inches in diameter or 3 by 4 inches in horizontal dimensions. Upon completion of grouting operations, plug and finish grouting holes to match surrounding surfaces.
3.4.2.3.2 Cleanouts for Hollow Unit Masonry Construction
For hollow masonry units. provide cleanout holes at the bottom of every grout pour in cores containing vertical reinforcement when the height of the grout…