REFERENCE DOCUMENT - PUMP STATION DRAWINGS 1.pdf
PDF 2 MB Posted
- Attached to
- Kentucky Lock - Lift Station Pump Repairs
- Solicitation number
- W912P526QA009
About this file
This document is a set of technical drawings and data sheets for the Kentucky Lock Wall Lift Station Pump Repairs project by the Tennessee Valley Authority. The drawings provide detailed schematics for electrical and control systems, including a control panel, wiring diagrams, and layout plans for a lift station. The data sheets list specific equipment components such as enclosures, power components, control components, switches, indicators, relays, and alarm components.
Key technical details include a duplex pump control system with 7.5 horsepower, 460 volt, 3-phase electrical configuration. The control panel includes multiple manufacturers' components like Hoffman enclosures, Square D breakers and switches, Symcom relays, and various sensors and indicators. The project involves renovations to an existing lock wall lift station, with detailed drawings showing the placement of electrical infrastructure, control panels, and utility connections across different elevations and site layouts.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
H3IPKTCP
Text Box Kentucky Lock Lock Wall Lift Station Pump Repairs Reference Document
Kentucky Lock Lock Wall Lift Station Pump Repairs
Kentucky Lock Lock Wall Lift Station Pump Repairs
Highlight
H3IPKTCP
Highlight
H3IPKTCP
Text Box Kentucky Lock Lock Wall Lift Station Pump Repairs
H3IPKTCP
Text Box Kentucky Lock Lock Wall Lift Station Pump Repairs
H3IPKTCP
Text Box Kentucky Lock Lock Wall Lift Station Pump Repairs
DOWNSTREAM LOCK EXCAVATION NOTES:
1. DOWNSTREAM LOCK EXCAVATION
CONTRACTOR SHALL RELOCATE 8-INCH D.I.P.
WATERLINE PER THE DETAILS THIS SHEET.
WATERLINE RELOCATION RELATED WORK ARE
HIGHLIGHTED BY CLOUDING.
2. ITEMS ON THIS DRAWING ARE CONCEPTUAL
AND THE WORK IS ONGOING AS PART OF A
SEPERATE CONTRACT. ACTUAL AS-BUILT SDU
CONTRACTOR PLANS WILL BE PROVIDED TO THE
CONTRACTOR THRU AMENDMENT OR AFTER
CONTRACT AWARD.
WATERLIN
E IN
FORAMTIO
N
DRAWIN
G. (S
EE D
OWNSTREAM
LO
CK EXCAVATIO
N N
OTES ABOVE.)
H3ECXCDH
Polygon
H3ECXCDH
Rectangle
H3ECXCDH
Polygon
H3IPKTCP
Text Box Kentucky Lock Lock Wall Lift Station Pump Repairs
DATA SHEET
AS BUILT
CONTROL PANEL DATE: November 2, 2018
PROJECT NAME: KENTUCKY LOCK RENOVATIONS PROJECT NO: 18-450
HORSEPOWER: 7.5 VOLTAGE: 460 PHASE: 3 TYPE: DUPLEX
QTY ITEM MFG MODEL #
ENCLOSURE & ACCESSORIES
1 ENCLOSURE HOFFMAN A48H3612SSLP3PT
1 SUBPANEL HOFFMAN A48P36
1 ENCLOSURE SERVICE LED LIGHT HOFFMAN LEDA1S35
1 BREAKER STANDS QCI FAB
1 DEAD FRONT INNER DOOR QCI FAB
1 METAL INTRINSIC BARRIER QCI FAB
MAIN POWER COMPONENTS
1 POWER BLOCK MARATHON 1403401
1 POWER MONITOR SYMCOM 201A
1 8 PIN BASE SQUARE D 8501-NR51
1 PM FUSE BLOCK SQUARE D 9080-FB3611CC
3 PM FUSES BUSSMAN FNQ-R1
2 CURRENT TRANSFORMERS DIVERSIFIED CMG-0101
2 CIRCUIT BREAKERS SQUARE D HDL36020
2 NEMA STARTERS SQUARE D 8536-SCO3V02H31S
2 SURGE SUPPRESSORS SQUARE D 9999-ST1
2 OVERLOAD RESET MODULES SQUARE D 9999-RR04
1 TRANSFORMER SQUARE D 9070T5000D1
2 PRIMARY FUSES (FU120) BUSSMAN FNQR 15
1 PRIMARY FUSE BLOCK SQUARE D 9080-FB2611CC
1 SECONDARY BREAKER SQUARE D QOU150
CONTROL COMPONENTS
1 CONTROL BREAKER SQUARE D QOU110
2 CONTROL BREAKERS SQUARE D QOU115
2 CONTROL BREAKERS SQUARE D QOU120
2 FUSE TERMINAL BLOCK SQUARE D NSYTRV42SF6
1 FUSE 5AMP (FU139) BUSSMAN AGC 5
1 HANDY BOX RACO 660
1 RECEPTACLE (15A) LEVITON BR-15-I
1 GFI RECEPTACLE (15A) LEVITON GFNT1-I
1 CONDENSATION HEATER HOFFMAN DAH8001A
SWITCHES & INDICATORS
2 3 POSITION SELECTOR SWITCHES SQUARE D 9001-SKS43B
2 CONTACT BLOCKS (N.O. & N.C.) SQUARE D 9001-KA1
3 CONTACT BLOCKS (N.C.) SQUARE D 9001-KA3
6 CONTACT BLOCK (N.O.) SQUARE D 9001-KA2
7 PUSH BUTTONS SQUARE D 9001-SKR1U
2 GREEN LENS SQUARE D 9001-G31
2 RED LENS SQUARE D 9001-R31
5 AMBER LENS SQUARE D 9001-A31
1 BLUE LENS SQUARE D 9001-L31
2 GREEN INDICATOR LIGHTS SQUARE D 9001-SKT38LG
2 RED INDICATOR LIGHTS SQUARE D 9001-SKT38LR
5 AMBER INDICATOR LIGHTS SQUARE D 9001-SKT38LY
1 BLUE INDICATOR LIGHTS SQUARE D 9001-SKT38LL
2 ELAPSED TIME METERS ENM T50B212
RELAYS & MISC COMPONENTS
1 LEVEL CONTROLLER PRECISION DIGITAL PD6000-6R4
13 CONTROL RELAYS SQUARE D RXM4AB2F7
16 RELAY BASES IDEC SY4S-05
3 CONTROL RELAYS 12VDC SQUARE D RXM4AB2JD
2 SEAL FAIL RELAYS SYMCOM PC100-LLC-CZ
1 TIME DELAY RELAY IDEC GE1A-C10HA110
4 8 PIN BASES SQUARE D 8501-NR51
1 ALTERNATOR DIVERSIFIED ARB-120-ABA
1 GROUND BAR SQUARE D PK9GTA
H3IPKTCP
Text Box Kentucky Lock Lock Wall Lift Station Pump Repairs Reference Document
DATA SHEET
AS BUILT
CONTROL PANEL DATE: November 2, 2018
PROJECT NAME: KENTUCKY LOCK RENOVATIONS PROJECT NO: 18-450
HORSEPOWER: 7.5 VOLTAGE: 460 PHASE: 3 TYPE: DUPLEX
1 GROUND LUG BURNDY KA25U
32 TERMINAL BLOCKS SQUARE D 9080-GR6
ALARM COMPONENTS
1 BATTERY BACKUP ALTRONIX AX-AL62412CX
1 EXTRA BATTERY UNIVERSAL BATTERY UB-1280
1 FUSE TERMINAL BLOCK SQUARE D NSYTRV42SF6
1 FUSE BUSSMAN AGC1.5
1 ALARM LIGHT 12V INGRAM AC/DC RAAVC100PRG
1 ALARM HORN (12-24vdc) WHEELOCK MT4-12/24-SG
2 PUSH BUTTONS SQUARE D 9001-SKR1U
2 CONTACT BLOCK (N.O.) SQUARE D 9001-KA2
1 FLASHER QCI 12VDC
LABELS
1 TYPE 5 QCI SILENCE
2 TYPE 5 QCI RUNNING
2 TYPE 5 QCI PUMP FAIL
2 TYPE 5 QCI PUMP FAIL
RESET
2 TYPE 5 QCI SEAL FAIL
2 TYPE 5 QCI SEAL FAIL
RESET
2 TYPE 5 QCI SEAL FAIL
TEST
1 TYPE 5 QCI FLOAT BACKUP
ACTIVE
1 TYPE 5 QCI FLOAT BACKUP
RESET
1 TYPE 5 QCI ALARM
TEST
1 TYPE 5 QCI CONTROL
POWER ON
1 TYPE 5 QCI PUMP NO.1
HAND OFF AUTO
1 TYPE 5 QCI PUMP NO.2
HAND OFF AUTO
1 TYPE 5 QCI PUMP NO.1
NO FLOW
1 TYPE 5 QCI PUMP NO.2
NO FLOW
1 TYPE 1 QCI PUMP NO.1
1 TYPE 1 QCI PUMP NO.2
1 TYPE 1 QCI GFI
1 TYPE 1 QCI HEATER /
ENCLOSURE LIGHT
1 TYPE 1 QCI SITE LIGHTING
1 TYPE 1 QCI ALARM RECEPTACLE
1 TYPE 1 QCI CONTROL
1 TYPE 1 QCI “BLANK”
INTRINSICALLY SAFE
1 INTRINSICALLY SAFE RELAY IDEC EB3C-R05AN
1 INTRINSICALLY SAFE RELAY PEPPERL & FUCHS Z787.H
10 TERMINAL BLOCKS SQUARE D 9080-GR6
Kentucky Lock
Kentucky Lock
Kentucky Lock
Kentucky Lock
Kentucky Lock
| Electrical Circuit ID & Location |
| Electrical Circuit ID & Location |
| Electrical Typical Lift Station Cabinet Layout & Wiring Diagram |
| Upstream Landwall Plan |
| Upstream Landwall Operations Bldg. & Lift Sta. Details |
| Upstream Landwall Lift Sta. & Sewer Transition View & Section |
| Lift Station & Control Panel Details |
| Data Sheet As Built |
| Data Sheet As Built |
| Pump Control Panel Electrical Schematic |
| Pump Control Panel Electrical Schematic |
| Pump Control Panel Electrical Schematic |
| Pump Control Panel Enclosure Layout |
File details come from the government source that posted it. Updated .