Addendum to Technical Specifications
CHEATHAM POWER PLANT - ITEMS 1-15 TECHNICAL SPECIFICATIONS
Eaton AK-1-25-AR600NM (E/O) 520MC LSI Breakers with 40ms
1 ARMS Trip, Switch & Light, with door (or Approved Equal) 22
Eaton AK-1-50-AR1600M (E/O) 520MC LSI Breakers with 40ms ARMS
2 Switch & Light, with door (or Approved Equal) 3
3 Eaton AK-1-25-AR Lifting Yoke (or Approved Equal) 1
4 Eaton AK-1-50-AR Lifting Yoke (or Approved Equal) 1
Eaton MRR1000 Magnum Breaker Remote Racking Device (or Approved Equal) 5 Remote racking device to service both standard and narrow-frame circuit breakers. 1
6 Eaton PXG900E Gateway Device (or Approved Equal) 1
7 Heating and Venting Board (Motor Control Center) 60 Hz, Class 1B wiring, 480V 3-Phase Service, 65,000 Bracing, Bottom Incoming, NEMA 1 Gasketed 21"
Front Mt Only enclosure, 600A Copper Main Horizontal Bus, No Neutral, Main Breaker. Used X-Space: 55, Blank X-Space: 5, Future X-Space: 0, MCC Lead Time Code: B.
Qty List of Materials 1 HLD Main Bkr (600A trip)
1 PXM2270
2 600V Potential transformer 3 600A Current transformer
5 FVNR Starter Size 1 [HMCP] 3 FVC Contactor Size 1 [TM Ckt Brk] 3 FVC Contactor Size 3 [TM Ckt Brk]
1 HFD Bkr (15A trip) 1 HFD Bkr (50A trip)
1 HFD Bkr (150A trip) 8 100VA Individual CPT, Fused 3 150VA Individual CPT, Fused
22 N.C. Starter Aux Contacts, Size 1-4 22 N.O. Starter Aux Contacts, Size 1-4
SIS Power Wire Ring Tongue Terminals
1 RMS310 LS Trip 11 Wiremarkers at Each End
6 Pilot Light-PTT-10250T-LED (Off) 14 RotoTract (Unit Disconnect Mechanism)
11 Wiring Diagram on Door 6 Pilot Light-PTT-10250T-LED (On)
11 3 Pos. Sel. Sw., 10250T (Hand-Off-Auto)
8 Equipment Board 1 (Motor Control Center) 1 60 Hz, Class 1B wiring, 480V 3-Phase Service, 65,000 Bracing, Bottom Incoming, NEMA 1 Gasketed 21"
Front Mt Only enclosure, 600A Copper Main Horizontal Bus, No Neutral, Main Breaker. Used X-Space: 55, Blank X-Space: 5, Future X-Space: 0, MCC Lead Time Code: B.
Qty List of Materials 2 HLD Main 1 Bkr (600A trip), Lugs: 2-#400-500Kcmil
1 PXM2270
2 600V Potential transformer 3 600A Current transformer
7 FVNR Starter Size 1 [HMCP] 3 FVNR Starter Size 3 [HMCP]
3 FVC Compact Contactor Sz 3 [TM Ckt Brk] 1 HFD Bkr (100A trip)
1 HFD Bkr (40A trip) 2 HFD Bkr (150A trip) 2 HFD Bkr (20A trip)
7 100VA Individual CPT, Fused 6 150VA Individual CPT, Fused
26 N.O. Starter Aux Contacts, Size 1-4 26 N.C. Starter Aux Contacts, Size 1-4
19 RotoTract (Unit Disconnect Mechanism) 13 Wiremarkers at Each End
13 Terminal Block - Latching Pull-Apart, Std.
#16awg SIS Control Wire (Compact Units Only)
10 Solid State Overload Relay (Advanced) SIS Power Wire
13 Wiring Diagram on Door Ring Tongue Terminals
9 Equipment Board 2 (Motor Control Center) 1 60 Hz, Class 2C wiring, 480V 3-Phase Service, 65,000 Bracing, Bottom Incoming, NEMA 1 Gasketed 21"
Front Mt Only enclosure, 600A Copper Main Horizontal Bus, No Neutral, Main Breaker. Used X-Space: 77, Blank X-Space: 7, Future X-Space: 0, MCC Lead Time Code: C.
Qty List of Materials 2 HKD Main 1 Bkr (250A trip), Lugs: 2-#3/0-250Kcmil
2 PXM2270
6 600A Current transformer
4 600V Potential transformer 6 FVNR Starter Size 1 [HMCP] 2 FVNR Starter Size 2 [HMCP]
3 FVC Contactor Size 1 [TM Ckt Brk] 2 HFD Bkr (40A trip) 2 HFD Bkr (15A trip)
1 HFD Bkr (225A trip) 1 HFD Bkr (100A trip) 4 HFD Bkr (70A trip) 2 HFD Bkr (30A trip)
11 100VA Individual CPT, Fused 22 N.O. Starter Aux Contacts, Size 1-4 22 N.C. Starter Aux Contacts, Size 1-4
11 3 Pos. Sel. Sw., 10250T (Hand-Off-Auto) 11 Wiremarkers at Each End
SIS Power Wire 11 Wiring Diagram on Door Ring Tongue Terminals
8 Solid State Overload Relay (Advanced) 11 Terminal Block - Latching Pull-Apart, Std.
Option 10 Installation Support (Field Service Specialist per hour) 100
Option 11 Lighting Switchboard (Motor Control Center) 60 Hz, Class 1B wiring, 480V 3-Phase Service, 65,000 Bracing, Bottom Incoming, NEMA 1 Gasketed 21"
Front Mt Only enclosure, 600A Copper Main Horizontal Bus, No Neutral, Main Breaker. Used X-Space: 43, Blank X-Space: 17, Future X-Space: 0, MCC Lead Time Code: C
Qty List of Materials
3 HLD Main 1 Bkr (600A trip), Lugs: 2-#400-500Kcmil
2 PXM2270
6 600A Current transformer 4 600V Potential transformer
7 HFD Bkr (70A trip) 2 HFD Bkr (125A trip) 1 HFD Bkr (90A trip) 2 HFD Bkr (50A trip)
12 RotoTract (Unit Disconnect Mechanism) 10 Motor Load Block (100A)
3 RMS310 LS Trip 3 Manual Key Transfer
11 6" Door 3 12" Door
2 Thermostat- for enclosure space heater control 1 Wired Remote Racking Accessory
5 Sleeve Wrapped Insulated main bus 5 Vertical Copper Ground Bus
5 Labyrinth, Isolated/Insulated vertical bus barrier with shutters 5 65KA Bus Bracing
5 300A Horiz. Cu Gnd Bus, 1/4" x 1" Bar 5 150 Watt space heater
5 Tin Plated horizontal bus
Option 12 150 kVA Transformer 3 Phase, 150 KVA, 1 K-Factor 480 Primary Volts
208Y/120 Secondary Volts Temperature Rise 80C with 220C Insulation System
Copper Winding Material Sound Reduction : 0
NEMA ST-20 Audible Sound Level: 50 Efficiency : DOE 10 CFR Part 431 (2016)
UL Listed : Y Enclosure Type: NEMA 3R w/opt'l weathershield)
Qty List of Materials 1 3 Phase, 150 KVA, 480 Primary Volts, 208Y/120 Secondary Volts, 80C with 220C Insulation System
Temperature Rise, Copper Winding Material, 60 HZ 1 Transformer Lug Kit/1PH 100-167KVA or 3PH 150-300K
Option 13 Eaton Medium Voltage Assemblies (13.8 kV Snubber) (or Approved Equal) Protec Z HV 13.8 KV Snubber for 100KVA Transformers Type: PROTEC Z HV Model MM3-13.8kV
Identification number: 15049-06
14 750kVA Pad Mounted Transformer 1 kVA 750/862 kVA 3 Phase Substation Transformer
Installation Location Outdoor Temperature Rise 65
Cooling Class KNAN/Future KNAF Frequency 60
"K" Factor None Insulating fluid Envirotemp FR3 Efficiency Standard DOE 2016
Elevation Designed for operation up to 1000 m (3300 ft) above sea level High Voltage 4160 Delta
High Voltage Conductor Copper Winding Material BIL 60 kV
Taps 2 - 2.5% taps above and 2 - 2.5% taps below nominal High Voltage Bushing Location Sidewall
High Voltage Bushing Segment 2 High Voltage Phasing H3-H2-H1 (Left to Right)
HV Enclosure Type Full Height Air Chamber, Bottom Entry, Hinged Door with Padlock Provisions High Voltage Bushings Porcelain 4-hole spade bushing(s) (Qty: 3)
Load-break Switching 300A two position loadbreak switch Low Voltage 480 Delta
Low Voltage Conductor Copper Winding Material BIL 30kV
Low Voltage Bushing Location Sidewall Low Voltage Bushing Segment 4
Low Voltage Phasing X1-X2-X3 (Left to Right) LV Enclosure Type Full Height Air Chamber, Bottom Entry, Hinged Door with Padlock Provisions
Low Voltage Bushings Integral copper 6-hole spade bushing(s) (Qty: 3) Fan Package Provisions for Future Fan Cooling
Cooling Corrugate Type Cooling Fins Coatings ANSI 61 Light Grey 3 mil
Notifications Standard Aluminum Nameplate Nitrogen blanket With Purge Valve
Liquid Level Gauge Liquid Temp Gauge with Alarm Contacts
Pressure Vacuum Gauge Pressure Vacuum Gauge Pressure Relief Valve Valves
Upper Fill Plug Valves Drain Valve (1") with Sampler
Control Box NEMA 4 Control Box Accessories SO Cable for Control Wiring
Tank Full Vacuum Bracing Tank Welded Main Cover with Handhole
Tank Manhole Cover (Qty: 1) Tank Stainless Steel Ground Pads
Custom Feature External Visible Loadbreak Option
PERFORMANCE DATA:
Target Impedance - 5.80% +/- 7.5% IEEE Tolerance
Fluid Weight - 1966 lbs Total Weight - 5851 lbs
Fluid Volume - 256 Gallons Primary Conductor Material - CU
Secondary Conductor Material - CU
Option
Option 15 1200 A Lock Panel (Panelboard) 12Circuits, 1200A, Fully Rated, 480V 3Ph 3W, Tin Plated Copper Bus, 65k AIC, 1200A, NGH 3P Main
Breaker [Bottom Fed], Surface Mounted
1 1200A, NGH 3P Main Breaker 4 600A 310 Plus LS Trip Unit
1 310+LS Adj. Trip Unit, NG Frame, Included 2 500A, 3P LGH Branch Breaker 2 400A, 3P LGH Branch Breaker
1 Tin-Plated Copper Main Bus, 1200 Amps 1 Density Rated Cu Main Bus (1000A per sq. inch)
1 Std. Bolted Cu Ground Bar (Cu Cable Only) 1 Panel Nameplate - White with Black Letters
1 Type 4X Enclosure, Stainless Steel: WPRL43673-XN
CENTER HILL POWER PLANT - ITEMS 16-38 TECHNICAL SPECIFICATIONS
Eaton Magnum DS, 1600, (E/O) 520MC LSI with 40ms ARMS Trip, Switch &
16 Light, with door (or Approved Equal) 3
Eaton DB25-AR600NM/MO 520MC LSI with 40ms ARMS Trip, Switch & 17 Light, with door (or Approved Equal) 21
Eaton DB25-AR600NM/EO 520MC LSI with 40ms ARMS Trip, Switch & 18 Light, with door (or Approved Equal) 4
19 Eaton DB25-AR600NM Lifting Yoke (or Approved Equal) 2
Eaton MRR1000 Magnum Breaker Remote Racking Device (or Approved
Equal) Remote Racking Devices to service both standard and narrow-frame circuit breakers.
21 Eaton Automatic Transfer Switch (or Approved 1
Equal) Product Family: Wall Mount
Switch Type: Automatic Molded Case Switch 30A thru 1000A 480v, 60hz, 3 Phase, 3 Wire, 3 poles
Transition Mode: Open Controller Type: ATC-900
Continuous Current: 800 Amps Withstand: 50 KA
Normal Source Terminals: (4) 4/0-500 CU/AL Emergency Source Terminals: (4) 4/0-500 CU/AL
Load Side Terminals: (4) 4/0-500 CU/AL Neutral Terminals: No Neutral Bar
Standard Features: 1b, 2a, 3b, 4b, 5h, 5j, 5k, 5l, 5m, 6b, 7a, 8e, 10b, 10d, 12c, 12d, 12g, 12h, 14e, 14f, 15e, 15f, 22, 23m, 26h, 26j, 26k, 26l, 26m, 32a, 42, 48f, 48u, 49c, Optional Features: No Optional Features Selected
1 ATV9NB 3 Poles 800 Amps
1 AT Enclosure - Type-1 1 1b. Time Delay Normal to Emergency Adj. 0-9999 sec
1 2a. Time Delay Engine Start Adj. 0-120 sec 1 3b. Time Delay Emergency to Normal Adj. 0-9999 sec
1 4b. Time Delay Engine Cool-off Adj. 0-9999 sec 1 5h. Emergency (S2) Sensing Phase Reversal
1 5j. Emergency (S2) Sensing Under Voltage/Under Freq 1 5k. Emergency (S2) Sensing Over Voltage/Over Freq
1 5l. Emergency (S2) Sensing Voltage Unbalance 1 5m. Emergency (S2) Sensing Phase Loss
1 6b. Test Pushbutton 1 7a. Time Delay Engine Fail Adj. 0-6 sec
1 8e. Bypass All Timers 1 10b. Source Selector - Utility to Utility or Utility to Gen
1 10d. Source Selector - Generator to Generator 1 12c. LED Indicator Normal Position
1 12d. LED Indicator Emergency Position 1 12g. LED Indicator Normal Source Available
1 12h. LED Indicator Emergency Source Available
1 14e. Normal (S1) Source Available (1 Form C) 1 14f. Emergency (S2) Source Available (1 Form C)
1 15e. Normal (S1) Position Indication (1 Form C Micro Switch Outputs) 1 15f. Emergency (S2) Position Indication (1 Form C Micro Switch Outputs)
1 22. Ground Bar 1 23m. Auto Plant Exerciser Selectable-Disabled/Daily/Calendar Dates, 0-600 min, Load/No Load w/Fail
Safe 1 26h. Normal (S1) Sensing Phase Reversal
1 26j. Normal (S1) Sensing Under-voltage/Under-frequency 1 26k. Normal (S1) Sensing Over-voltage/Over-frequency
1 26l. Normal (S1) Sensing Voltage Unbalance 1 26m. Normal (S1) Sensing Phase Loss
1 32a. Time Delay Neutral Adjustable 0 - 120 seconds 1 42. IBC/CBC Seismic Qualified 1 48f. MODBUS Communication 1 48u. USB Port for Memory Stick
1 49c. Multi-Tap Transformer
22 Unit Board 1 (Motor Control Center) 1
Front Mt Only enclosure, 800A Copper Main Horizontal Bus, No Neutral, Main Breaker. Used X-Space: 48, Blank X-Space: 24, Future X-Space: 0, MCC Lead Time Code: C.
1 Ethernet communications to customer's network (copper wire) 2 NGH Main 1 Bkr (320A trip), Lugs: 2-#1-500Kcmil
1 Data Logging or Alarm Notification Capability Through Web Browser Interface 1 Ethernet communicating devices
1 16 Port Ethernet Switch - Managed 1 5A, 24V Power Supply
3 FVNR Starter Size 1 [HMCP] 2 FVNR Starter Size 3 [HMCP]
1 FVC Contactor Size 2 [TM Ckt Brk] 1 FVC Contactor Size 3 [TM Ckt Brk]
1 HFDTwin Bkr (15A /100A trip) 3 150VA Individual CPT, Fused 4 100VA Individual CPT, Fused
14 N.O. Starter Aux Contacts, Size 1-4 14 N.C. Starter Aux Contacts, Size 1-4
7 Terminal Block - Latching Pull-Apart, Std.
7 Wiremarkers at Each End #14awg SIS Control Wire
Spade Wire Terminals 5 Solid State Overload Relay (Advanced)
7 Starters/Contactors on EtherNet, 120VAC I/O (auto) 7 Wiring Diagram on Door
5 Pilot Light-PTT-10250T-LED (Run) SIS Power Wire
5 Pilot Light-PTT-10250T-LED (Stopped) 7 Motor Load Block (100A) 7 600V Cat 5 Ethernet Cable
2 RMS310+ LSI Trip 2 Manual Key Transfer
7 2 Unit PB, 10250T (Start/Stop) 2 Pilot Light-PTT-10250T-LED (Off) 2 Pilot Light-PTT-10250T-LED (On)
2 Thermostat- for enclosure space heater control 6 Sleeve Wrapped Insulated main bus
1 Freedom Arc Resistant MCC List Price Adder 6 Labyrinth, Isolated/Insulated vertical bus barrier with shutters
6 Tin Plated horizontal bus 6 65KA Bus Bracing
6 300A Horiz. Cu Gnd Bus, 1/4" x 1" Bar 6 600A Vertical Bus (Tin-plated cu)
6 Structure Bottom plates 6 150 Watt space heater
6 Bottom Vertical Bus Barrier 1 Enclosure End Braces, IBC/CBC Seismic Qualified
4 800A Copper Frnt Mtd 21" NEMA 1 Gasketed 2 Expansion chambers
23 Unit Board 2 (Motor Control Center) 1
Front Mt Only enclosure, 800A Copper Main Horizontal Bus, No Neutral, Main Breaker. Used X-Space: 48, 2 NGH Main 1 Bkr (320A trip), Lugs: 2-#1-500Kcmil 1 Data Logging or Alarm Notification Capability Through Web Browser Interface
1 Ethernet communicating devices 1 16 Port Ethernet Switch - Managed
1 5A, 24V Power Supply 3 FVNR Starter Size 1 [HMCP] 2 FVNR Starter Size 3 [HMCP]
1 FVC Contactor Size 2 [TM Ckt Brk] 1 FVC Contactor Size 3 [TM Ckt Brk]
1 HFDTwin Bkr (15A /100A trip) 3 150VA Individual CPT, Fused 4 100VA Individual CPT, Fused
14 N.O. Starter Aux Contacts, Size 1-4 14 N.C. Starter Aux Contacts, Size 1-4
7 Terminal Block - Latching Pull-Apart, Std.
7 Wiremarkers at Each End #14awg SIS Control Wire
Spade Wire Terminals 5 Solid State Overload Relay (Advanced)
7 Starters/Contactors on EtherNet, 120VAC I/O (auto) 7 Wiring Diagram on Door
5 Pilot Light-PTT-10250T-LED (Run) SIS Power Wire
5 Pilot Light-PTT-10250T-LED (Stopped) 7 Motor Load Block (100A) 7 600V Cat 5 Ethernet Cable
2 RMS310+ LSI Trip 2 Manual Key Transfer
7 2 Unit PB, 10250T (Start/Stop) 2 Pilot Light-PTT-10250T-LED (Off) 2 Pilot Light-PTT-10250T-LED (On)
2 Thermostat- for enclosure space heater control 6 Sleeve Wrapped Insulated main bus
1 Freedom Arc Resistant MCC List Price Adder 6 Labyrinth, Isolated/Insulated vertical bus barrier with shutters
6 Tin Plated horizontal bus 6 65KA Bus Bracing
6 300A Horiz. Cu Gnd Bus, 1/4" x 1" Bar 6 600A Vertical Bus (Tin-plated cu)
6 Structure Bottom plates 6 150 Watt space heater
6 Bottom Vertical Bus Barrier 1 Enclosure End Braces, IBC/CBC Seismic Qualified
24 Unit Board 3 (Motor Control Center) 1
Front Mt Only enclosure, 800A Copper Main Horizontal Bus, No Neutral, Main Breaker. Used X-Space: 48, 2 NGH Main 1 Bkr (320A trip), Lugs: 2-#1-500Kcmil
1 Data Logging or Alarm Notification Capability Through Web Browser Interface 1 Ethernet communicating devices
1 16 Port Ethernet Switch - Managed 1 5A, 24V Power Supply
3 FVNR Starter Size 1 [HMCP] 2 FVNR Starter Size 3 [HMCP]
1 FVC Contactor Size 2 [TM Ckt Brk] 1 FVC Contactor Size 3 [TM Ckt Brk]
1 HFDTwin Bkr (15A /100A trip) 3 150VA Individual CPT, Fused 4 100VA Individual CPT, Fused
14 N.O. Starter Aux Contacts, Size 1-4 14 N.C. Starter Aux Contacts, Size 1-4
7 Terminal Block - Latching Pull-Apart, Std.
7 Wiremarkers at Each End #14awg SIS Control Wire
Spade Wire Terminals 5 Solid State Overload Relay (Advanced)
7 Starters/Contactors on EtherNet, 120VAC I/O (auto) 7 Wiring Diagram on Door
5 Pilot Light-PTT-10250T-LED (Run) SIS Power Wire
5 Pilot Light-PTT-10250T-LED (Stopped) 7 Motor Load Block (100A) 7 600V Cat 5 Ethernet Cable
2 RMS310+ LSI Trip 2 Manual Key Transfer
7 2 Unit PB, 10250T (Start/Stop) 2 Pilot Light-PTT-10250T-LED (Off) 2 Pilot Light-PTT-10250T-LED (On)
2 Thermostat- for enclosure space heater control 6 Sleeve Wrapped Insulated main bus
1 Freedom Arc Resistant MCC List Price Adder 6 Labyrinth, Isolated/Insulated vertical bus barrier with shutters
6 Tin Plated horizontal bus 6 65KA Bus Bracing
6 300A Horiz. Cu Gnd Bus, 1/4" x 1" Bar 6 600A Vertical Bus (Tin-plated cu)
6 Structure Bottom plates 6 150 Watt space heater
6 Bottom Vertical Bus Barrier 1 Enclosure End Braces, IBC/CBC Seismic Qualified
25 Installation Support (Field Service Specialist per hour) 300
26 Unit Board 4 (Motor Control Center) 1 60 Hz, Class 1B wiring, 480V 3-Phase Service, 65,000 Bracing, Bottom Incoming, NEMA 1 Gasketed 21"
Front Mt Only enclosure, 800A Copper Main Horizontal Bus, No Neutral, Main Breaker. Used X-Space: 54, Blank X-Space: 30, Future X-Space: 0, MCC Lead Time Code: C
1 Data Logging or Alarm Notification Capability Through Web Browser Interface 1 Ethernet communicating devices
2 NGH Main 1 Bkr (500A trip), Lugs: 2-#1-500Kcmil 1 Ethernet communications to customer's network (copper wire)
1 5A, 24V Power Supply 1 16 Port Ethernet Switch - Managed
6 FVNR Starter Size 1 [HMCP] 1 FVNR Starter Size 2 [HMCP] 2 FVNR Starter Size 3 [HMCP] 1 HFDTwin Bkr (15A /15A trip)
1 HFDTwin Bkr (100A /100A trip) 7 100VA Individual CPT, Fused 2 150VA Individual CPT, Fused
18 N.C. Starter Aux Contacts, Size 1-4 18 N.O. Starter Aux Contacts, Size 1-4
9 Motor Load Block (100A) #14awg SIS Control Wire
9 Solid State Overload Relay (Advanced) 9 Starters/Contactors on EtherNet, 120VAC I/O (auto)
9 Terminal Block - Latching Pull-Apart, Std.
9 Wiremarkers at Each End
SIS Power Wire Spade Wire Terminals
9 Wiring Diagram on Door 9 600V Cat 5 Ethernet Cable
2 RMS310+ LSI Trip 2 Manual Key Transfer
9 2 Unit PB, 10250T (Start/Stop) 9 Pilot Light-PTT-10250T-LED (Stopped)
9 Pilot Light-PTT-10250T-LED (Run) 3 12" Door
2 Thermostat- for enclosure space heater control 7 Sleeve Wrapped Insulated main bus
7 65KA Bus Bracing 1 Freedom Arc Resistant MCC List Price Adder
7 Labyrinth, Isolated/Insulated vertical bus barrier with shutters 7 300A Horiz. Cu Gnd Bus, 1/4" x 1" Bar
7 600A Vertical Bus (Tin-plated cu) 7 Structure Bottom plates 7 150 Watt space heater
7 Bottom Vertical Bus Barrier 1 Enclosure End Braces, IBC/CBC Seismic Qualified
7 Tin Plated horizontal bus 2 Expansion chambers
5 800A Copper Frnt Mtd 21" NEMA 1 Gasketed
27 Unit Board 5 (Motor Control Center) 1
Front Mt Only enclosure, 800A Copper Main Horizontal Bus, No Neutral, Main Breaker. Used X-Space: 60, 1 Ethernet communicating devices
2 NGH Main 1 Bkr (500A trip), Lugs: 2-#1-500Kcmil 1 Ethernet communications to customer's network (copper wire)
1 16 Port Ethernet Switch - Managed 1 5A, 24V Power Supply
3 FVNR Starter Size 1 [HMCP] 3 FVNR Starter Size 2 [HMCP] 2 FVNR Starter Size 3 [HMCP]
1 FVC Contactor Size 1 [TM Ckt Brk] 1 FVC Contactor Size 3 [TM Ckt Brk]
1 HFDTwin Bkr (90A /100A trip) 2 HFDTwin Bkr (50A /50A trip) 3 150VA Individual CPT, Fused 7 100VA Individual CPT, Fused
20 N.O. Starter Aux Contacts, Size 1-4 20 N.C. Starter Aux Contacts, Size 1-4
Spade Wire Terminals 10 Wiring Diagram on Door
SIS Power Wire 10 Terminal Block - Latching Pull-Apart, Std.
10 Wiremarkers at Each End 8 Solid State Overload Relay (Advanced)
2 Fdr Bkr 120V Shunt Trip 8 Pilot Light-PTT-10250T-LED (Stopped)
10 Starters/Contactors on EtherNet, 120VAC I/O (auto) 8 Pilot Light-PTT-10250T-LED (Run)
#14awg SIS Control Wire 10 600V Cat 5 Ethernet Cable
2 Pilot Light-PTT-10250T-LED (On) 2 Manual Key Transfer 2 RMS310+ LSI Trip
2 Pilot Light-PTT-10250T-LED (Off) 10 Motor Load Block (100A)
10 2 Unit PB, 10250T (Start/Stop) 2 Thermostat- for enclosure space heater control 1 Freedom Arc Resistant MCC List Price Adder
7 Sleeve Wrapped Insulated main bus 7 65KA Bus Bracing
7 300A Horiz. Cu Gnd Bus, 1/4" x 1" Bar 7 Labyrinth, Isolated/Insulated vertical bus barrier with shutters
7 Structure Bottom plates 7 600A Vertical Bus (Tin-plated cu)
7 150 Watt space heater 7 Bottom Vertical Bus Barrier
1 Enclosure End Braces, IBC/CBC Seismic Qualified 7 Tin Plated horizontal bus
2 Expansion chambers 5 800A Copper Frnt Mtd 21" NEMA 1 Gasketed
28 Unit Board 6 (Motor Control Center) 1
Front Mt Only enclosure, 800A Copper Main Horizontal Bus, No Neutral, Main Breaker. Used X-Space: 77, Blank X-Space: 31, Future X-Space: 0, MCC Lead Time Code: C.
1 Ethernet communicating devices 1 Data Logging or Alarm Notification Capability Through Web Browser Interface
2 NGH Main 1 Bkr (500A trip), Lugs: 2-#1-500Kcmil 1 5A, 24V Power Supply
1 16 Port Ethernet Switch - Managed 15 FVNR Starter Size 1 [HMCP]
2 FVC Contactor Size 2 [TM Ckt Brk] 2 FVC Contactor Size 3 [TM Ckt Brk] 1 FVC Contactor Size 4 [TM Ckt Brk]
1 HFDTwin Bkr (50A /50A trip) 1 HFDTwin Bkr (50A /100A trip) 2 150VA Individual CPT, Fused 1 200VA Individual CPT, Fused 17 100VA Individual CPT, Fused
40 N.C. Starter Aux Contacts, Size 1-4 40 N.O. Starter Aux Contacts, Size 1-4
20 Wiremarkers at Each End SIS Power Wire
#14awg SIS Control Wire 20 Terminal Block - Latching Pull-Apart, Std.
Spade Wire Terminals 2 Fdr Bkr 120V Shunt Trip
2 RMS310+ LSI Trip 20 Wiring Diagram on Door
20 Starters/Contactors on EtherNet, 120VAC I/O (auto) 20 Motor Load Block (100A) 20 600V Cat 5 Ethernet Cable
2 Manual Key Transfer 15 Pilot Light-PTT-10250T-LED (Run)
15 Pilot Light-PTT-10250T-LED (Stopped) 15 Solid State Overload Relay (Advanced)
5 Pilot Light-PTT-10250T-LED (On) 5 Pilot Light-PTT-10250T-LED (Off)
20 2 Unit PB, 10250T (Start/Stop) 2 12" Door 1 18" Door
2 Thermostat- for enclosure space heater control 9 Sleeve Wrapped Insulated main bus
1 Freedom Arc Resistant MCC List Price Adder 9 Labyrinth, Isolated/Insulated vertical bus barrier with shutters
9 Tin Plated horizontal bus 9 65KA Bus Bracing
9 300A Horiz. Cu Gnd Bus, 1/4" x 1" Bar 9 600A Vertical Bus (Tin-plated cu)
9 Structure Bottom plates 9 150 Watt space heater
9 Bottom Vertical Bus Barrier 1 Enclosure End Braces, IBC/CBC Seismic Qualified
7 800A Copper Frnt Mtd 21" NEMA 1 Gasketed
Option 29 Eaton Arc Flash Limiter Retrofills (or Approved Equal)
• VCP-T 15kV 40kA Draw-out Breaker
• VCP-T 15kV Cassette
• PROTEC-Z 13.8kV snubber per AFL assembly
• Copper Connections/cable from existing switch to breaker
• Mounting platform for the VCP-TR Breaker
• 520MCV Digitrip with ARMS
• Current Sensors for the 520MCV trip unit (secondary side of XFMR)
• Eaton Digitrip DT3000 for primary protection with Control Transformers on the primary side of the switch
• NEMA 1 indoor control box with local control switch, lock-out relay, ARMS selector switch, and local breaker indication lights
• Indoor Enclosure – MVS (90”H X 36”W + 20”W LV Compartment X 55”D)
• 1200A Copper tin plated main bus
• Copper – tin plated bus
• 15kV Switch 1200A, 40kA mom, 40kA fc
3 NGH Main 1 Bkr (600A trip), Lugs: 2-#1-500Kcmil 1 Ethernet communications to customer's network (copper wire)
2 IQ150
4 600V Potential transformer 4 600A Current transformer
1 HFD Bkr (225A trip) 1 HFD Bkr (100A trip)
1 HFDTwin Bkr (150A /150A trip) 4 HFDTwin Bkr (100A /100A trip) 1 HFDTwin Bkr (50A /100A trip) 5 HFDTwin Bkr (50A /50A trip)
3 Manual Key Transfer 3 RMS310+ LSI Trip
1 Motor Load Block (100A) 1 Pilot Light-PTT-10250T-LED (On, Run, Fast, Forward)
1 Pilot Light-PTT-10250T-LED (Off, Stopped) 1 2 Unit PB, 10250T (Start/Stop)
2 Fdr Bkr 120V Shunt Trip 1 30 in. blank relay panel
1 6" Door 3 12" Door 2 18" Door
2 Thermostat- for enclosure space heater control 11 Sleeve Wrapped Insulated main bus
11 Bottom Vertical Bus Barrier 1 Enclosure End Braces, IBC/CBC Seismic Qualified
1 Freedom Arc Resistant MCC List Price Adder 11 65KA Bus Bracing
11 300A Horiz. Cu Gnd Bus, 1/4" x 1" Bar 11 Labyrinth, Isolated/Insulated vertical bus barrier with shutters
11 Tin Plated horizontal bus 2 800A Vertical Bus (Tin-plated cu)
11 Structure Bottom plates 11 150 Watt space heater
9 600A Vertical Bus (Tin-plated cu) 1 Bus Tie Transition
2 Expansion chambers 8 800A Copper Frnt Mtd 21" NEMA 1 Gasketed
1 120V AC to 125VDC Transfer Switch Contactor and Relays
Option 30 Lighting Switchboard (Motor Control Center) 1
Front Mt Only enclosure, 800A Copper Main Horizontal Bus, No Neutral, Main Breaker. Used X-Space: 95, Blank X-Space: 37, Future X-Space: 0, MCC Lead Time Code: U.
1 Ethernet communicating devices
Option 31 Eaton PXG900E Gateway Device (or Approved Equal) 1
Option 32 150 kVA Transformer 3 Phase, 150 KVA, 1 K-Factor 480 Primary Volts
208Y/120 Secondary Volts Temperature Rise 80C with 220C Insulation System
Copper Winding Material Sound Reduction : 0
NEMA ST-20 Audible Sound Level: 55 Efficiency : DOE 10 CFR Part 431 (2016)
UL Listed : Y Enclosure Type: NEMA 3R w/opt'l weathershield
Operating Frequency: 60 HZ
1 3 Phase, 150 KVA, 480 Primary Volts, 208Y/120 Secondary Volts, 80C with 220C Insulation System Temperature Rise, Copper Winding Material, 60 HZ
1 Transformer Lug Kit/1PH 100-167KVA or 3PH 150-300K
Option 33 1000kVA Transformer Power Transformer, Cast Coil or Resibloc, R = Utility & Power Generation, 1000, Air Terminal Chamber, Switchboard, Right, 12 Month Standard Warranty, Point of Shipment
1000 KVA TX1
3 Phase 60 Hertz, 80/80 Degree C Rise, AA/FA
30 Average / 40 Maximum Ambient
5.75 Percent Impedance with +/- ANSI Standard Tolerance
Phase relation Dd0 3300 Feet Maximum Altitude
64 dB(a) Guaranteed Sound Level (AA) Eddy K-Factor: 1, Stray K-Factor: 1
Approximate Dimensions: Ht 90 in X Wd 102 in X Dp 66 in Approximate Total Weight: 11900 lbs
HIGH VOLTAGE 13800 Delta
95 KV BIL
Taps: +2 -2 2.5%
Copper Conductor Termination in ANSI segment 2
HV Air Terminal Chamber Porcelain Bus Supports - HV
LOW VOLTAGE 480 Delta
30 KV BIL
Taps: No Taps
Copper Conductor Termination in ANSI segment 4
Porcelain Bus Supports - LV
CORE/COIL
1 3 Phase, 300 KVA, 2400 Primary Volts, 480 Secondary Volts, 80C with 220C Insulation System
Temperature Rise, Copper Winding Material, 60 HZ 1 CUSTOM: Primary Voltage
1 CUSTOM: Secondary Voltage 1 CUSTOM: Winding Material 1 CUSTOM: Temperature Rise
1 CUSTOM: CSA Labeled
Qty List of Materials 1 3 Phase, 50 KVA, 480 Primary Volts, 208Y/120 Secondary Volts, 150C with 220C Insulation System
Temperature Rise, Copper Winding Material, 60 HZ 1 Weathershield Kit for 50 KVA transformer
1 Transformer Lug Kit/1PH 50-75KVA or 3PH 75-112.5KV 1 CUSTOM: Winding Material
1 CUSTOM: Stainless Steel (304) Enclosure 1 CUSTOM: Anti-Fungus Protection
1 CUSTOM: OSHPD Compliant (verify mounting method in OSP)
Option 34 300kVA Pad Mounted Transformer 2
3 Phase, 300 KVA, 1 K-Factor
2400 Primary Volts 480 Secondary Volts
Temperature Rise 80C with 220C Insulation System Copper Winding Material
Sound Reduction : 0 NEMA ST-20 Audible Sound Level: 60
Efficiency : DOE 10 CFR Part 431 (2016) Enclosure Type: NEMA 3R
Option 35 Switchyard 50 kVA Transformer 2
3 Phase, 50 KVA, 1 K-Factor
480 Primary Volts 208Y/120 Secondary Volts
Temperature Rise 150C with 220C Insulation System Copper Winding Material
Sound Reduction : 0 NEMA ST-20 Audible Sound Level: 45
Efficiency : DOE 10 CFR Part 431 (2016) Enclosure Type: NEMA 3R w/opt'l weathershield
Stainless Steel (304) Enclosure
Option 36 Eaton Switchyard Switchgear (or Approved Equal) Panel (L-102)
18 Circuits, 100A, Fully Rated, 208Y/120V 3Ph 4W, Copper Bus, 10k AIC, [Bottom Fed], Flush Mounted
Qty List of Materials 1 Retrofit Panel, 100A, Main Lugs Only
12 20A, 1P BAB Branch Breaker 1 Custom Retrofit Trim 1 No Enclosure: No Box
1 100A Lighting Contactor
Panel (L-101) 18Circuits, 100A, Fully Rated, 208Y/120V 3Ph 4W, Copper Bus, 10k AIC, [Bottom Fed], Flush Mounted
Qty List of Materials 1 Retrofit Panel, 100A, Main Lugs Only
12 20A, 1P BAB Branch Breaker 1 Custom Retrofit Trim 1 No Enclosure: No Box
1 100A Lighting Contactor
Panel (L-104)
18Circuits, 100A, Fully Rated, 208Y/120V 3Ph 4W, Copper Bus, 10k AIC, [Bottom Fed], Flush Mounted
Qty List of Materials 1 Retrofit Panel, 100A, Main Lugs Only
10 20A, 1P BAB Branch Breaker 1 Custom Retrofit Trim
1 Split Bus
Panel (L-103)
Qty List of Materials 1 Retrofit Panel, 100A, Main Lugs Only
6 20A, 2P BAB Branch Breaker 1 Custom Retrofit Trim
1 Supply GHB DC Breakers
Panel (DC)
Panel (P-101) 42Circuits, 225A, Fully Rated, 208Y/120V 3Ph 4W, Copper Bus, 10k AIC, 175A, 3P ED Main
Breaker [Bottom Fed], Flush Mounted
Qty List of Materials 1 Retrofit Panel, 225A, ED Main Breaker
2 70A, 3P BAB-H Branch Breaker 2 100A, 3P BAB-H Branch Breaker 4 50A, 3P BAB-H Branch Breaker 8 30A, 2P BAB-H Branch Breaker
1 Custom Retrofit Trim 1 No Enclosure: No Box
1 100A Lighting Contactor
Panel (P-102) 42Circuits, 225A, Fully Rated, 208Y/120V 3Ph 4W, Copper Bus, 10k AIC, 175A, 3P ED Main
Breaker[Bottom Fed], Flush Mounted
Qty List of Materials 1 Retrofit Panel, 225A, ED Main Breaker
2 70A, 3P BAB-H Branch Breaker 2 100A, 3P BAB-H Branch Breaker 4 50A, 3P BAB-H Branch Breaker 8 30A, 2P BAB-H Branch Breaker
1 Custom Retrofit Trim 1 No Enclosure: No Box
1 100A Lighting Contactor
Panel (DC/AC Transfer Switch) ATS DC/AC 50A - 120VAC to 125VDC Contactor Transfer switch in Nema 3R box
37 Eaton Medium Voltage Assemblies (13.8 kV Snubber) (or Approved Equal) 1 Protec Z HV 13.8 KV Snubber for 100KVA Transformers Type: PROTEC Z HV Model MM3-13.8kV
Identification number: 15049-06
38 Eaton Breaker Tester MTK2000 (or Approved Equal) 1
Breaker Tester for DB25-AR600NM breakers