1. Question: Is the canopy structure is over the firing line and if it must meet the ETL 11-18 RT60 of

1.5 seconds reverb time or the 85 dBA requirement?

1. Answer: The roof is over the berm where bullets impact the soil. It is not over the firing points and does not have to meet the ETL 11-18 RT60 of 1.5 seconds reverb time or the 85 dBA requirement.

2. Question: Can the northwest chain link fence can be removed and replaced during the construction process?

2. Answer: Removal of the existing chain linked fence to provide access is acceptable. Fence must be restored to original condition following construction

3. Question: What is the structural support of the southwest wall of the existing canopy to be demolished?

3. Answer: It consists of a shallow concrete foundation that is protected by railroad ties