QUESTIONS AND ANSWERS

1. Surge Suppression is required per AFI-132-1065 and UFC 3-575-01 on electrical and data lines.

Are we to include this in the price?

Response:

1. No do not include in the bid price. We believe the building has suppression devices per code. If during construction it is determined that these devices are not installed per code, the owner

(TNANG) will address this on a case by case basis.

2. Are we to bid to a General Contractor? Or as a prime?

Response:

2. You can act as the prime because this is solely a lightning protection system installation.