Text version

2-21-2018

LIGHTNING PROTECTION AIR TERMINAL. (TYPES A, B, C, ETC.)

G

GROUND SYSTEM CONDUCTOR #2/0 BARE COPPER,

(2'-0" BELOW GRADE WHEN INSTALLED UNDERGROUND)

LP

R E

P A

I R

L

G

H T

I N

G

P

R O

T E

C T

I O

N

B

B

G M

C

I s s u e

D a t e

P r o j e c t

S t a t u s

E n t e r a d d r e s s h e r e

B K

T Z

W e s t

E n d

A v e n u e

S u i t

N a s h v i l l e

T

N

T l

M C

N E

T W

O R

K C

O M d r a w b y

I S

S U

E

D

T

E c h e c k e d b y s h e e t o f

G O

O D

W Y

N M

I L

L S

C A

W O

O D

A

B

C

D

E

F

G

H

J

K

1 2 3 4 5 6 7 8 9 10 11 12

1 2 3 4 5 6 7 8 9 10 11 12

A

B

C

D

E

F

G

H

J

K

BIRMINGHAM

TUSCALOOSA

JACKSON

NASHVILLE

www.edmondsengineering.com

Project Number :

BNA16205

(205) 988-2069

(205) 752-9915

(601) 362-6478

(615) 265-8071

A C

H

E W

B

E L

E C

T R

I C

A L

L E

D G

E N

D

N

O T

S

E

T A

I L

S

E

APPROXIMATE LOCATION

OF RETAINING WALL

APPROXIMATE

LOCATION OF

RETAINING WALL

GENERAL NOTES:

01. INSTALL LIGHTNING PROTECTION SYSTEM PER

REQUIREMENTS OF NFPA 780, UFC 3-575-01, LPI 175, UL96A AND

AFI 32-1065 .

02. PROVIDE FINAL INSPECTION IN ACCORDANCE WITH

UFC 3-575-01.

03. REFER TO SPECIFICATIONS AND DETAILS FOR ADDITIONAL

REQUIREMENTS.

04. APPROXIMATION LOCATIONS OF RETAINING WALLS ARE

INDICATED ON THE PLANS. ADJUST LIGHTNING PROTECTION

SYSTEM LAYOUT AS REQUIRED TO AVOID INTERFERENCE WITH

RETAINING WALLS WHILE MAINTAINING CODE COMPLIANCE.

05. FINAL LAYOUT SHALL BE INCLUDED IN SHOP DRAWINGS.

KEYED NOTES:

01. APPROXIMATION OF GROUND RING LOOP. INSTALL PER

REQUIREMENTS OF NFPA 780.

R E

P A

G

H T

I N

G

P

R O

T E

C T

I O

N

B

B

G M

I s s u e

D a t e

P r o j e c t

S t a t u s

E n t e r a d d r e s s h e r e

B K

T Z s t

E e n u e

S u i s h v i l l e

T

N

C

N E

T W

O R

K C

O M d r a

I S

S

T

E c h e c k e d b y s h e e t o f

G O

O D

W Y

N M

I L

L S

C A

W O

O D

A

B

C

D

E

F

G

H

J

K

1 2 3 4 5 6 7 8 9 10 11 12

1 2 3 4 5 6 7 8 9 10 11 12

A

B

C

D

E

F

G

H

J

K

BIRMINGHAM

TUSCALOOSA

JACKSON

NASHVILLE

www.edmondsengineering.com

Project Number :

BNA16205

(205) 988-2069

(205) 752-9915

(601) 362-6478

(615) 265-8071

A C

H

E W

B

E L

E C

T R

I C

O O

F

P L

A N

S

B

L D

G

G

E N

E R

A T

O R

R O

O M

E

BLDG 747 ELECTRICAL ROOF PLAN

SCALE: 1/8" = 1'-0"

E1.01

LOCATION OF

EXISTING DOWN

CONDUCTOR

READING OF 0.587 OHMS

LOCATION OF EXISTING

DOWN CONDUCTOR

READING OF 8.653 OHMS

LOCATION OF EXISTING

DOWN CONDUCTOR

READING OF 54.39 OHMS

LOCATION OF

EXISTING DOWN

CONDUCTOR

READING OF 0.493 OHMS

LOCATION OF EXISTING

DOWN CONDUCTOR

READING OF 0.515 OHMS

NEW DOWN

CONDUCTOR,

TYPICAL

EXISTING AIR

TERMINAL,

TYPICAL

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX EX EX EX EX EX EX EX EX EX EX EX EX EX EX EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EXEXEXEXEXEXEXEXEXEXEXEXEXEX EXEX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

EX

NEW DOWN

CONDUCTOR

NEW DOWN

CONDUCTOR

NEW DOWN

CONDUCTOR

NEW DOWN

CONDUCTOR

NEW DOWN

CONDUCTOR

NEW DOWN

CONDUCTOR

NEW DOWN

CONDUCTOR

NEW DOWN

CONDUCTOR

NEW DOWN

CONDUCTOR

GENERAL NOTES:

01. INSPECT EXISTING LIGHTNING PROTECTION SYSTEM AND

BRING INTO COMPLIANCE WITH REQUIREMENTS OF NFPA 780,

UFC 3-575-01, LPI 175, UL96A AND AFI 32-1065.

02. AIR TERMINALS INDICATED ON THE PLANS ARE EXISTING

AND LOCATIONS ARE AN APPROXIMATION.

CONTRACTOR SHALL FIELD VERIFY EXACT LOCATIONS AND

INSPECT FOR CODE COMPLIANT INSTALLATION.

03. APPROXIMATE LOCATIONS OF EXISTING LIGHTNING

PROTECTION SYSTEM CONDUCTORS ARE INDICATED ON THE

PLANS. CONTRACTOR SHALL FIELD VERIFY EXACT LOCATIONS

AND INSPECT FOR CODE COMPLIANT INSTALLATION.

04. APPROXIMATE LOCATION OF EXISTING DOWN CONDUCTORS

ARE INDICATED ON THE PLANS. CONTRACTOR SHALL FIELD

VERIFY EXACT LOCATIONS OF ALL EXISTING DOWN

CONDUCTORS ASSOCIATED WITH THE LIGHTNING PROTECTION

SYSTEM AND INSPECT FOR CODE COMPLIANT INSTALLATION.

INDICATED RESISTANCE READINGS ARE AN APPROXIMATION

PROVIDED BY TENNESSEE AIR NATIONAL GUARD. CONTRACTOR

SHALL FIELD VERIFY RESISTANCE READINGS PRIOR TO

SUBMITTING BID.

05. APPROXIMATE LOCATIONS OF ANTICIPATED NEW DOWN

CONDUCTORS ARE INDICATED ON THE PLANS. CONTRACTOR

SHALL FIELD VERIFY INSTALLATION OF THE INDICATED DOWN

CONDUCTORS ARE REQUIRED BASED ON FIELD VERIFICATION OF

EXISTING LIGHTNING PROTECTION SYSTEM. INSTALL NEW

CONDUCTORS AS REQUIRED TO COMPLY WITH CODE

REQUIREMENTS.

06. CONTRACTOR SHALL FIELD VERIFY EXISTING LIGHTNING

PROTECTION SYSTEM AND PERFORM RESISTANCE READINGS

FOR VERIFICATION PRIOR TO SUBMITTING BID.

DOCUMENTATION OF PERFORMED READINGS AND FIELD

VERIFICATION FINDINGS SHALL BE INCLUDED WITH BID.

07. REFER TO SPECIFICATIONS AND DETAILS FOR ADDITIONAL

REQUIREMENTS.

08. FINAL LAYOUT SHALL BE INCLUDED IN SHOP DRAWINGS.

09. PROVIDE FINAL INSPECTION IN ACCORDANCE WITH

UFC 3-575-01.

10. ALL EQUIPMENT SHOWN IS EXISTING, UNLESS OTHERWISE

NOTED.

R E

P A

G

H T

I N

G

P

R O

T E

C T

I O

N

B

B

G M

I s s u e

D a t e

P r o j e c t

S t a t u s

E n t e r a d d r e s s h e r e

B K

T Z s t

E e n u e

S u i s h v i l l e

T

N

C

N E

T W

O R

K C

O M d r a

I S

S

T

E c h e c k e d b y s h e e t o f

G O

O D

W Y

N M

I L

L S

C A

W O

O D

A

B

C

D

E

F

G

H

J

K

1 2 3 4 5 6 7 8 9 10 11 12

1 2 3 4 5 6 7 8 9 10 11 12

A

B

C

D

E

F

G

H

J

K

BIRMINGHAM

TUSCALOOSA

JACKSON

NASHVILLE

www.edmondsengineering.com

Project Number :

BNA16205

(205) 988-2069

(205) 752-9915

(601) 362-6478

(615) 265-8071

A C

H

E W

B

E L

E C

T R

I C

A L

R O

O F

P

A

S

B L

E

BLDG 801 ELECTRICAL ROOF PLAN

SCALE: 1/8" = 1'-0"

E1.02

T0.01
E0.01
Sheets and Views
E0.01
E1.01
Sheets and Views
E1.01
E1.02
Sheets and Views
E1.02