W912L7-18-B-5001-002-Add-Alter_SF_B736_Q&A.pdf

PDF 162 KB Posted

Attached to
Add-Alter Security Forces B736
Solicitation number
W912L7-18-B-5001
Issued by

About this file

Amendment 2: To incorporate questions and answers 1-10. Bid due date and time has not been changed.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

F8D3CE8046AW02 BKTZ122005

AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT

Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.

15A. NAME AND TITLE OF SIGNER (Type or print)

30-105-04EXCEPTION TO SF 30

APPROVED BY OIRM 11-84

STANDARD FORM 30 (Rev. 10-83) Prescribed by GSA

FAR (48 CFR) 53.243

To incorporate questions and answ ers 1-10. Bid due date and time has not been changed.

1. CONTRACT ID CODE PAGE OF PAGES

1 3

16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)

16C. DATE SIGNED

BY 23-May-2018

16B. UNITED STATES OF AMERICA15C. DATE SIGNED15B. CONTRACTOR/OFFEROR

(Signature of Contracting Officer)(Signature of person authorized to sign)

8. NAME AND ADDRESS OF CONTRACTOR (No., Street, County, State and Zip Code) X W912L7-18-B-5001

X 9B. DATED (SEE ITEM 11)

05-Apr-2018

10B. DATED (SEE ITEM 13)

9A. AMENDMENT OF SOLICITATION NO.

11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS

X The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offer is extended, X is not extended.

Offer must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended by one of the following methods:

(a) By completing Items 8 and 15, and returning copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted;

or (c) By separate letter or telegram which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN

REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by telegram or letter, provided each telegram or letter makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.

12. ACCOUNTING AND APPROPRIATION DATA (If required)

13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS.

IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.

A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE

CONTRACT ORDER NO. IN ITEM 10A.

B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation date, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(B).

C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:

D. OTHER (Specify type of modification and authority)

E. IMPORTANT: Contractor is not, is required to sign this document and return copies to the issuing office.

14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)

10A. MOD. OF CONTRACT/ORDER NO.

2. AMENDMENT/MODIFICATION NO. 5. PROJECT NO.(If applicable)

6. ISSUED BY

3. EFFECTIVE DATE

23-May-2018

CODE

118 CONTRACT OFFICE (FA6421)

118 CONTRACT & ADMINISTRATION 240 KNAPP BLV

NASHVILLE TN 37217-2538

W912L7 7. ADMINISTERED BY (If other than item 6)

4. REQUISITION/PURCHASE REQ. NO.

CODE

See Item 6

FACILITY CODECODE

EMAIL:TEL:

W912L7-18-B-5001

SECTION SF 30 BLOCK 14 CONTINUATION PAGE

SUMMARY OF CHANGES

SECTION 00800 - SPECIAL CONTRACT REQUIREMENTS

The following have been modified:

SPECIAL CONTRACT REQUIREMENTS

1. QUESTION- Specification section 16073.1.1.A –“The risers shall extend a minimum of 16” above the top of the roof.” Per UL standards we cannot allow any cable risers 9” above the roof deck. Please advise if the term risers here should be air terminals ( UL/NFPA standards are a minimum of 10” for air terminals )

1. ANSWER- This should be “air terminals”.

2. QUESTION- Specification section 16073.1.1.D – “ The installation shall conform with OSHA requirements for impalement protection “.Do the air terminals need to conform with CAL-OSHA requirements or are blunt /safety tipped air terminals approved?

2. ANSWER- Blunt/safety tip terminals are acceptable.

3. QUESTION- Specification section 16073.1.1.C –“ The system shall bear the Master Label”. In order to receive the UL Master Label certificate, the entire structure, including the new addition, is required to have LP system components afforded it. Does this meet with approval ?

3. ANSWER- Lightning system shall protect the entire building both old and new.

4. QUESTION- Specification section 16073.2.1.A – we may not be able to use copper components on areas of this structure. In order to conform with LP standards requirements, we will utilize system materials that are compatible with roofing materials being utilized in order to obtain the proper certification for this project. Does this meet with approval ?

4. ANSWER- Aluminum or copper material is acceptable

5. QUESTION- Specification section 16073.2.1.C –“ All connections shall be with the Burndy hyground system.”

i. Are these connections for below grade only.

i. ANSWER- Yes

ii. Are exothermic weld connections allowed as an alternate to the Burndy hyground series?

ii. ANSWER- Use of exothermic weld connections is acceptable.

6. QUESTION- Specification section 16073.3.1.A –“ All risers shall be concealed within the building construction.” The majority of the lightning protection installation for this project will be on an existing structure.

Please advise if down lead cables concealed in conduit ( pvc sch 80 ) on the exterior would meet approval?

6. ANSWER- All risers in the new building shall be concealed with the new walls. All risers in the existing building shall be concealed on the inside of the building where practical and turn out to exterior of building as close to grade as possible. Exposed conduit in the highbay area is acceptable. For all routing inside the existing building coordinate with the contracting officer.

7. QUESTION- Specification section 16073.3.1.B – “Looped from the air terminal risers extend a #4/0 awg copper conductor underground to the main electrical power service grounding triad and connect thereto”.

i. We assume that this comment is for the common grounding between a LP down lead cable to the electrical service ground, correct? UL prefers, for certification requirements, that a master ground bus be furnished and all connections of Lp system and other incoming service utilities attach to the bus as a common ground point.

i. ANSWER- Contractor shall provide ground bus as necessary to achieve the “Master Label” certification.

This shall also include any conduit and conductor routing necessary to achieve this label.

ii. A ground loop counterpoise is not required for this project, correct?

ii. ANSWER- Correct.

W912L7-18-B-5001

8. QUESTION- I am inquiring about the bid for the Alter Security Forces B736 Upgrades. We are a general contractor in Nashville. Do we have to be preapproved to be able to bid this project?

8. ANSWER- There is no preapproval from this office. All interested bidders must be registered to conduct business with the government via Caution-www.SAM.gov. All information regarding bid information is posted on FBO Caution-https://www.fbo.gov/spg/USA/NGB/DAHA40-3/W912L7-18-B-5001/listing.html pay particular attention to Section 00010 of the solicitation.

9. QUESTION- Can you tell me what general contractors are bidding this project?

9. ANSWER- There is no way to tell until bid closing. Numerous contractors were interested during the sources sought.

10. QUESTION- Please see the attached for our Substitution Request to be an approved manufacturer for Metal Roof & Wall panels for the above project.

10. ANSWER- Concerning any substitutions see Specification Section 01600 paragraph 1.5 A.2

(End of Summary of Changes)