This is the SOW for CLIN 0002 only. Please provide the pricing difference to do this electrical work instead of the electrical in the SOW for CLIN 0001.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Plumbing.pdf | ||
| BLDG2040_New_Water_and_Drain.pdf | ||
| RFI_Response_dated_19_Sep_2014_DV_Lounge.docx | DOCX document | |
| PJM142033_-SOW_-_Remodel_VIP_Lounge.doc | DOC document | |
| W912K6-12-R-0007.pdf | ||
| PJM142033_-Plans_-_Remodel_VIP_Lounge.docm | DOCM document | |
| Lounge_Pictures.docx | DOCX document |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CLIN 0002 OPTION STATEMENT OF WORK
2.5 Install Electrical 100 AMP SUB Panel
2.5.1 Furnish and install new square D, QO132M100C, QO 100 A, 32 SPACE 32 CIRCUIT, Main Breaker Load Center, 3- single pole, with the lowest amperage breaker 20amp.Contractor shall recess panel as necessary into CMU as to fit flush in proposed 3” stud wall, final location to be coordinated with proposed cabinets and approved by COR.Contractor shall ground cable conduits and panel in compliance with NEC requirements.
2.5.3 Furnish and Install approximately 210’ of 2” EMT FROM VIP lounge to Mechanical room in building 2045 to include all J-BOXES pipe hangers and any other associated hardware to include all wall penetrations to accomplish the conduit run. The conduit run shall be installed above the ceiling tiles
2.5.4 3 install approximately 210’ of Electrical wire through new 2” EMT FROM VIP lounge to Mechanical room in building 2045.
2.5.5 Rewire room with 12-2 and 12-3 (where circuit is supplied for lighting) in 3/4” and ½” EMT to proposed 100 AMP panel to include:
1. Dedicated 110 20 AMP GFI Duplex Receptacle flush mount for a refrigerator final location to be coordinated with proposed cabinets and approved by COR.
2. Dedicated 110 20 AMP Duplex Receptacle flush mount for microwave final location to be coordinated with proposed cabinets and approved by COR.
3. Dedicated 110 20 AMP GFI Duplex Receptacle flush mount for Ice Maker final location to be coordinated with proposed cabinets and approved by COR.
4. Dedicated 110 20 AMP GFI QUAD Receptacle flush mount for entertainment center final location to be coordinated with proposed cabinets and approved by COR.
5. Dedicated 110 20 AMP GFI Duplex Receptacle externally mounted for Vending Machine final location to be approved by COR.
6. Dedicated 110 20 AMP circuit for existing ceiling fans two each on one circuit, inspect and determine if existing wiring is up to code and able to support dimmer and speed control functions. Replace existing switches new switches shall be dimmer and speed control capable.
7. Dedicated 110 20 AMP GFI Duplex Receptacle flush mount for Counter top, GFI receptacle serving a total of three each. Final location to be coordinated with proposed cabinets and approved by COR.
8. Dedicated 110 20 AMP GFI Duplex Receptacle flush mount for convenience outlets, GFI Receptacle serving a total of four each.
9. Dedicated 110 20 AMP circuit for under cabinet lighting to be placed on a dimmer switch Final location to be coordinated with proposed cabinets and approved by COR.
10. Dedicated 110 20 AMP circuit to be capped off in the floor future. Final location to be approved by COR.
11. Dedicated 110 20 AMP circuit for Track lighting along beam where ceiling fans are mounted wired back to a dimmer switch room to be split into two zones , Final location to be approved by COR. Tract lighting to be two 4’ tracks with 3 each LED adjustable lights urban bronze.