Questions Received 16 January 2019;

Answers are provided by end customer

1. Are the ceilings suspend or hard lid? Please provide drawings.

0. The true ceiling is approximately 13’ with a false ceiling of acoustical panels 4’ below or 9’ above true floor. Unfortunately the drawings would provide little help. I went through every drawing I have and they are of little use. I will be happy to present those drawings during the walk through to see if anything can be gained.

1. Will wiring be in Wire Trays above ceiling, or conduit?

1. The wiring enters the room through metal conduit and is disturbed throughout the room using a metal tray.

1. Is a UPS required for the CAC and IDS?

2. UPS / battery backup is required

1. What is the proposed location of the workstation & Control Panel?

3. The control panel will be adjacent to the entry door (only door) and the workstation will be approximately 24 ft on the opposite side of the room.

1. What current CAC system is in place? Please provide technical date including Make/Model & Year Installed?

4. Our system does not currently utilize CACs for access. It is a HID ProxPro wall switch keypad reader model 5355AGK00.