AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT
Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.
15A. NAME AND TITLE OF SIGNER (Type or print)
30-105-04EXCEPTION TO SF 30
APPROVED BY OIRM 11-84
STANDARD FORM 30 (Rev. 10-83) Prescribed by GSA
FAR (48 CFR) 53.243
Solicitation No. W912HV-16-R-0006, Maintenance and Repair of Refrigeration Systems and Heating, Ventilation, and Air Conditioning Systems, Commissaries and Central Distribution Centers (CDC), MCAS Iw akuni and Kure Pier 6, Japan
See Continuation Page
1. CONTRACT ID CODE PAGE OF PAGES
J 1 5
16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)
16C. DATE SIGNED
BY
16B. UNITED STATES OF AMERICA15C. DATE SIGNED15B. CONTRACTOR/OFFEROR
(Signature of Contracting Officer)(Signature of person authorized to sign)
8. NAME AND ADDRESS OF CONTRACTOR (No., Street, County, State and Zip Code) X W912HV-16-R-0006
X 9B. DATED (SEE ITEM 11)
06-May-2016
10B. DATED (SEE ITEM 13)
9A. AMENDMENT OF SOLICITATION NO.
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
X The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offer is extended, X is not extended.
Offer must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended by one of the following methods:
(a) By completing Items 8 and 15, and returning 1 copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted;
or (c) By separate letter or telegram which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by telegram or letter, provided each telegram or letter makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.
12. ACCOUNTING AND APPROPRIATION DATA (If required)
13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS.
IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.
A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE
CONTRACT ORDER NO. IN ITEM 10A.
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation date, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(B).
C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER (Specify type of modification and authority)
E. IMPORTANT: Contractor is not, is required to sign this document and return copies to the issuing office.
14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
10A. MOD. OF CONTRACT/ORDER NO.
U0001
2. AMENDMENT/MODIFICATION NO. 5. PROJECT NO.(If applicable)
6. ISSUED BY
3. EFFECTIVE DATE
CODE
CONTRACTING DIVISION
USACE-JAPAN DISTRICT
RM 147, BLDG. 250
CAMP ZAMA
ZAMA-CITY, KANAGAWA 252-8511
JAPAN
W912HV 7. ADMINISTERED BY (If other than item 6)
4. REQUISITION/PURCHASE REQ. NO.
CODE
See Item 6
FACILITY CODECODE
EMAIL:TEL:
j2ctcsnm Rectangle j2ctcsnm Typewritten Text j2ctcsnm Rectangle j2ctcsnm Typewritten Text
W912HV-16-R-0006 (Am-0001)
SECTION SF 30 BLOCK 14 CONTINUATION PAGE
SUMMARY OF CHANGES
B. CHANGES TO SOLICITATION:
b. Revised Pages/Paragraphs: Attached hereto are revised pages/paragraphs added to solicitation. The revision mark (Am-0001) is shown on each new page of the specifications.
Section Page No(s)/Paragraph No(s).
B - (Supplies or Services and Prices) Pages 2 - 6
C - (Descriptions and Specifications) Pages 8 - 9 (Revised Iwakuni Performance Work Statement Commissary, Bldg. 615)
c. Replaced Pages/Paragraphs: The following sections/pages are replaced from the specifications.
Section Page No(s)/Paragraph No(s).
C - (Technical Exhibit 7) Pages 45 - 48
Equipment List (Refrigeration & HVAC)
Section B – Supplies or Services and Prices
Maintenance and Repair of Refrigeration and HVAC Systems, Commissaries and CDC, MCAS Iwakuni and Kure Pier 6, Japan
Base Year: 01 AUGUST 2016 – 31 JULY 2017
UNIT
ITEM
NO. SUPPLIES/SERVICES QTY UNIT PRICE AMOUNT
0001 Monthly Preventive, Emergency Maintenance and Repair of Refrigeration Systems and associated Refrigeration Monitoring and Control Systems
0001AA Iwakuni Commissary, Building 615 12 MO ¥_________ ¥__________
0001AB Kure at Pier 6 Commissary, Building S-250 12 MO ¥_________ ¥__________
0001AC Iwakuni CDC, Building 170 12 MO ¥_________ ¥__________
0002 Monthly Preventive, Emergency Maintenance and Repair of HVAC Systems
0002AA Iwakuni Commissary, Building 615 12 MO ¥_________ ¥__________
0002AB Kure at Pier 6 Commissary, Building S-250 12 MO ¥_________ ¥__________
0003 Reimbursable Items 1 Year NTE ¥1,500,000
0004 Contract Manpower Reporting 1 Job ¥_________ ¥__________
Subtotal of Base Year: ¥___________ j2ctcsnm j2ctcsnm Typewritten Text j2ctcsnm
Option Year 1: 01 AUGUST 2017 – 31 JULY 2018
NO. SUPPLIES/SERVICES QTY UNIT PRICE AMOUNT
1001 Monthly Preventive, Emergency Maintenance and Repair of Refrigeration Systems and associated
1001AA Iwakuni Commissary, Building 615 12 MO ¥_________ ¥__________
1001AB Kure at Pier 6 Commissary, Building S-250 12 MO ¥_________ ¥__________
1001AC Iwakuni CDC, Building 170 12 MO ¥_________ ¥__________
1002 Monthly Preventive, Emergency Maintenance and
1002AA Iwakuni Commissary, Building 615 12 MO ¥_________ ¥__________
1002AB Kure at Pier 6 Commissary, Building S-250 12 MO ¥_________ ¥__________
1003 Reimbursable Items 1 Year NTE ¥1,500,000
1004 Contract Manpower Reporting 1 Job ¥_________ ¥__________
Subtotal of Option Year 1: ¥___________ j2ctcsnm Typewritten Text j2ctcsnm
Option Year 2: 01 AUGUST 2018 – 31 JULY 2019
NO. SUPPLIES/SERVICES QTY UNIT PRICE AMOUNT
2001 Monthly Preventive, Emergency Maintenance and Repair of Refrigeration Systems and associated
2001AA Iwakuni Commissary, Building 615 12 MO ¥_________ ¥__________
2001AB Kure at Pier 6 Commissary, Building S-250 12 MO ¥_________ ¥__________
2001AC Iwakuni CDC, Building 170 12 MO ¥_________ ¥__________
2002 Monthly Preventive, Emergency Maintenance and
2002AA Iwakuni Commissary, Building 615 12 MO ¥_________ ¥__________
2002AB Kure at Pier 6 Commissary, Building S-250 12 MO ¥_________ ¥__________
2003 Reimbursable Items 1 Year NTE ¥1,500,000
2004 Contract Manpower Reporting 1 Job ¥_________ ¥__________
Subtotal of Option Year 2: ¥___________ j2ctcsnm Typewritten Text j2ctcsnm
Option Year 3: 01 AUGUST 2019 – 31 JULY 2020
NO. SUPPLIES/SERVICES QTY UNIT PRICE AMOUNT
3001 Monthly Preventive, Emergency Maintenance and Repair of Refrigeration Systems and associated
3001AA Iwakuni Commissary, Building 615 12 MO ¥_________ ¥__________
3001AB Kure at Pier 6 Commissary, Building S-250 12 MO ¥_________ ¥__________
3001AC Iwakuni CDC, Building 170 12 MO ¥_________ ¥__________
3002 Monthly Preventive, Emergency Maintenance and
3002AA Iwakuni Commissary, Building 615 12 MO ¥_________ ¥__________
3002AB Kure at Pier 6 Commissary, Building S-250 12 MO ¥_________ ¥__________
3003 Reimbursable Items 1 Year NTE ¥1,500,000
3004 Contract Manpower Reporting 1 Job ¥_________ ¥__________
Subtotal of Option Year 3: ¥___________ j2ctcsnm Typewritten Text j2ctcsnm
Option Year 4: 01 AUGUST 2020 – 31 JULY 2021
NO. SUPPLIES/SERVICES QTY UNIT PRICE AMOUNT
4001 Monthly Preventive, Emergency Maintenance and Repair of Refrigeration Systems and associated
4001AA Iwakuni Commissary, Building 615 12 MO ¥_________ ¥__________
4001AB Kure at Pier 6 Commissary, Building S-250 12 MO ¥_________ ¥__________
4001AC Iwakuni CDC, Building 170 12 MO ¥_________ ¥__________
4002 Monthly Preventive, Emergency Maintenance and
4002AA Iwakuni Commissary, Building 615 12 MO ¥_________ ¥__________
4002AB Kure at Pier 6 Commissary, Building S-250 12 MO ¥_________ ¥__________
4003 Reimbursable Items 1 Year NTE ¥1,500,000
4004 Contract Manpower Reporting 1 Job ¥_________ ¥__________
Subtotal of Option Year 4: ¥___________
BASE YEAR SUBTOTAL ¥_____________
OPTION YEAR 1 SUBTOTAL ¥_____________
OPTION YEAR 2 SUBTOTAL ¥_____________
OPTION YEAR 3 SUBTOTAL ¥_____________
OPTION YEAR 4 SUBTOTAL ¥_____________
GRAND TOTAL AMOUNT ¥_____________
j2ctcsnm Typewritten Text j2ctcsnm Typewritten Text j2ctcsnm
PERFORMANCE WORK STATEMENT
MAINTENANCE AND REPAIR OF REFRIGERATION SYSTEMS AND
HEATING, VENTILATION, AND AIR CONDITIONING SYSTEMS,
COMMISSARIES AND CDC, MCAS IWAKUNI AND KURE PIER 6,
JAPAN
20 March 2016 REVISED 25 May 2016
Prepared By U. S. Army Corps of Engineers Japan District j2ctcsnm
1. GENERAL. This is a non-personal services contract to perform maintenance on all commissary and Central Distribution Center (CDC) refrigeration systems including the Refrigeration Monitoring and Control System (RMCS) and commissary heating, ventilation and air-conditioning (HVAC) systems at the “MCAS
IWAKUNI COMMISSARY BLDG 615”; IWAKUNI CDC BLDG 170; AND KURE PIER 6 COMMISSARY
BLDG 250, Japan. The Government shall not exercise any supervision or control over the contract service providers performing the services herein. Such contract service providers shall be accountable solely to the Contractor who, in turn is responsible to the Government.
1.1. Description of Services/Introduction. The contractor shall provide all personnel, equipment, supplies, facilities, transportation, tools, materials, supervision, and other items and non-personal services necessary to perform MAINTENANCE AND REPAIR OF REFRIGERATION SYSTEMS AND
HEATING, VENTILATION, AND AIR CONDITIONING SYSTEMS, COMMISSARIES AND CDC,
MCAS IWAKUNI AND KURE PIER 6, as defined in this Performance Work Statement (PWS) except for those items specified as government furnished property and services. The contractor shall perform to the standards in this contract.
1.2. Scope. The Contractor shall provide all services, personnel, equipment, tools, parts, transportation, materials except as specified in Section 18. GOVERNMENT FURNISHED PROPERTY AND SERVICES, supervision, and other items necessary to perform MAINTENANCE AND REPAIR OF
REFRIGERATION SYSTEMS AND HEATING, VENTILATION, AND AIR CONDITIONING
SYSTEMS COMMISSARIES AND CDC, MCAS IWAKUNI AND KURE PIER 6, JAPAN.
1.3. Work and services to be provided by the Government are specified in Section 18. GOVERNMENT FURNISHED PROPERTY AND SERVICES. Work performed under this contract shall be conducted in accordance with the manufacturer’s recommendation and/or best commercial practices to operate the systems at optimum efficiency while maintaining the required operation, temperature and/or humidity conditions.
The estimated quantities of emergency work are listed in Technical Exhibit 2, Emergency Call Workload Estimates.
1.4. Period of Performance. Period of performance for Base Year shall be from 01August 2016 through 31 July 2017. Four (4) additional option years may be exercised at the discretion of the Contracting Officer.
2. CONTRACTOR REQUIREMENTS.
2.1. Perform refrigeration and HVAC periodic preventive maintenance (PPM) at the frequency recommended by equipment manufacturers and/or best commercial practices, but no less than on a monthly basis. The contractor shall also perform PPM on a monthly basis to ensure that all commissary main entrance and exit automatic door systems are clean and operational. The PPM shall include repairs, checks, tests, calibrations, adjustments, lubrications, and replacement of system parts. Loose parts including hinges shall be tightened and secured. Door surfaces including stainless frames shall be free of corrosions, dirt, and other foreign substances.
2.2. Be available for emergency service 24 hours/day, 7 days/week and furnish at least one (1), but not more than three (3) telephone numbers at which the contractor or his representative can be contacted 24 hours/day, 7 days/week.
2.3. Report to an authorized government personnel (AGP) immediately upon arrival at the commissary or CDC and notify the AGP when repairs have been completed.
2.4. Respond to an emergency call within two (2) hours for refrigeration equipment and complete emergency repairs within 24 hours after receiving the request from the AGP.
2.5. Respond to an emergency call by 0900 the following day for HVAC systems and complete emergency repairs within 24 hours of arrival after receiving the request from the AGP.
j2ctcsnm Typewritten Text j2ctcsnm
GROUP/DODAAC ISSUE DATE
Store Name 1‐Dec‐2015
Store Location AREA ‐ PACIFIC HQCWHB
Item Quantity Length (Ft) Manufacturer Model # Decription
Sys1‐1 1 8' Panasonic CVS‐EX085
Sys1‐2 1 12' Panasonic CVS‐EX025
Sys1‐3 1 12' Panasonic CVS‐EX025
Sys1‐4 1 12' Panasonic CVS‐EX025
Sys1‐5 1 12' Panasonic CVS‐EX025
Sys1‐6 1 12' Panasonic CVS‐EX025
Sys1‐7 1 12' Panasonic CVS‐EX025
Sys1‐8 1 12' Panasonic CVS‐EX025
Sys1‐9 1 8' Panasonic CVS‐EX085
Sys1‐10 1 12' Panasonic CVS‐EX025
Sys2‐11 1 12' Panasonic FZW‐EX025
Sys2‐12 1 12' Panasonic FZW‐EX025
Sys2‐13 1 12' Panasonic FZW‐EX025
Sys2‐15 1 12' Panasonic FZW‐EX025
Sys2‐16 1 8' Panasonic FZW‐EX085
Sys2‐17 1 8' Panasonic FZW‐EX085
Sys2‐18 1 12' Panasonic FPW‐EX025
Sys2‐19 1 12' Panasonic FPW‐EX025
Sys2‐20 1 8' Panasonic FPW‐EX085
Sys2‐21 1 12' Panasonic CPW‐EX025
Sys2‐23 1 12' Panasonic CPW‐EX025
Sys2‐24 1 12' Panasonic CPW‐EX025
Sys2‐25 1 12' Panasonic CPW‐EX025
Sys3‐26 1 12' Panasonic CPW‐EX025
Sys3‐27 1 12' Panasonic CPW‐EX025
Sys3‐28 1 3 DR Panasonic FLD‐EX0377LB
Sys3‐29 1 3 DR Panasonic FLD‐EX0377LB
Sys3‐30 1 3 DR Panasonic FLD‐EX0377LB
Sys3‐31 1 3 DR Panasonic FLD‐EX0377LB
Sys3‐32 1 3 DR Panasonic FLD‐EX0377LB
Sys3‐33 1 3 DR Panasonic FLD‐EX0377LB
Sys3‐34 1 3 DR Panasonic FLD‐EX0377LB
Sys3‐35 1 3 DR Panasonic FLD‐EX0377LB
Sys3‐36 1 3 DR Panasonic FLD‐EX0377LB
Sys3‐37 1 2 DR Panasonic FLD‐EX0277LB
Sys4‐38 1 2 DR Panasonic FLD‐EX0277LB
Sys4‐39 1 3 DR Panasonic FLD‐EX0377LB
Sys4‐40 1 3 DR Panasonic FLD‐EX0377LB
Sys4‐41 1 3 DR Panasonic FLD‐EX0377LB
Sys4‐42 1 3 DR Panasonic FLD‐EX0377LB
Sys4‐43 1 3 DR Panasonic FLD‐EX0377LB
Sys4‐44 1 3 DR Panasonic FLD‐EX0377LB
Sys4‐45 1 3 DR Panasonic FLD‐EX0377LB
Sys4‐46 1 3 DR Panasonic FLD‐EX0377LB
Sys4‐47 1 3 DR Panasonic FLD‐EX0377LB
Sys4‐48 1 3 DR Panasonic FLD‐EX0377LB
Sys4‐49 1 3 DR Panasonic FLD‐EX0377LB
Sys3‐50 1 3 DR Panasonic FLD‐EX0377LB
Sys3‐51 1 3 DR Panasonic FLD‐EX0377LB
Sys5‐52 1 12' Panasonic CZW‐EX887
Sys5‐53 1 12' Panasonic CZW‐EX887
Sys5‐54 1 12' Panasonic CZW‐EX887
Sys5‐55 1 12' Panasonic CZW‐EX887
Sys5‐58 1 3 DR Panasonic FLD‐EX3077
Sys5‐59 1 3 DR Panasonic FLD‐EX3077
Sys5‐60 1 3 DR Panasonic FLD‐EX3077
Sys5‐61 1 3 DR Panasonic FLD‐EX3077
Sys5‐62 1 3 DR Panasonic FLD‐EX3077
Sys5‐63 1 3 DR Panasonic FLD‐EX3077
Sys5‐64 1 3 DR Panasonic FLD‐EX3077
Sys2‐65 1 3 DR Panasonic FLD‐EX3077
Iwakuni Commissary
Facility Equipment List Iwakuni Commissary
Refrigeration Equipment Display Cases j2ctcsnm Typewritten Text W912HV-16-R-0006 (Am-0001) j2ctcsnm
Store Location AREA ‐ PACIFIC HQCWHBIwakuni Commissary
Facility Equipment List Iwakuni Commissary
Item Quantity Length (Ft) Manufacturer Model # Decription
Sys2‐66 1 3 DR Panasonic FLD‐EX3077
Sys2‐67 1 3 DR Panasonic FLD‐EX3077
Sys2‐68 1 3 DR Panasonic FLD‐EX3077
SysX‐70 1 12' Panasonic EX3066MSY
SysX‐71 1 12' Panasonic EX3066MSY
SysX‐72 1 5' Panasonic EX3066MSY
SysX‐73 1 5' Panasonic EX3066MSY
Item Quantity Length (Ft) Manufacturer Model # Decription
S/C Sandwich Table 1 4 Ft Everest Refrigeration EPR2 115‐60‐1, 1/4 Hp, R‐134a
S/C Reach‐in Fridge 1 52 inches Traulsen G20010 115‐60‐1, S/C Island Case 1 8 FT Hill‐Phoenix OIMA 208‐60‐1, R404A
S/C Sushi Prep 1 4 FT Southern PSSC 115‐60‐1, R404A
S/C Grab‐n‐Go 1 4 FT Southern 1M04 115‐60‐1 item Quantity Location/Type Manufacturer Model # Decription
1‐104 1 44A Panasonic CC‐M8070
1‐107 1 55 Panasonic CC‐M8070
1‐108 1 55 Panasonic CC‐M8070
1‐109 1 56 Panasonic CC‐M8070
1‐110 1 56 Panasonic CC‐M8070
6‐101 1 43A Panasonic CC‐V5080H
6‐102 1 43A Panasonic CC‐V5080H
6‐103 1 43B Panasonic CC‐V9080HCP
6‐105 1 59 Panasonic CC‐D14020H
6‐106 1 59 Panasonic CC‐D14020H
6‐111 1 67 Panasonic CC‐V9020H
6‐112 1 67 Panasonic CC‐V9020H
6‐113 1 77 Panasonic CC‐V5080H
7‐201 1 68 Panasonic CC‐D12020LH
7‐202 1 68 Panasonic CC‐D12020LH
7‐203 1 76 Panasonic CC‐D9020LH
7‐101 1 43A Panasonic CC‐V5080H
7‐102 1 43A Panasonic CC‐V5080H
7‐103 1 43B Panasonic CC‐V9080HCP
7‐104 1 44A Panasonic CC‐M6070H
7‐105 1 44A Panasonic CC‐M6070H
7‐109 1 55 Panasonic CC‐M6070
7‐110 1 55 Panasonic CC‐M6070
8‐106 1 59 Panasonic CC‐V9080H
8‐107 1 59 Panasonic CC‐V9080H
8‐108 1 59 Panasonic CC‐V9080H
8‐111 1 56 Panasonic CC‐M6070
8‐112 1 56 Panasonic CC‐M6071
8‐113 1 67 Panasonic CC‐D14020H
8‐114 1 67 Panasonic CC‐D14020H
9‐201 1 68 Panasonic CC‐D9020LH
9‐202 1 68 Panasonic CC‐D9020LH
9‐203 1 76 Panasonic CC‐D9020LH
Item Quantity Location/Type Manufacturer Model # Decription
CS‐1 1 MECH RM Panasonic LCU‐NS400MVP 29.2 (7.3 x 4) KW‐200V‐R404A
CS‐2 1 MECH RM Panasonic LCU‐NS350MVP 25.6 (7.3 x 3) + 3.7 KW‐200V‐R404A
CS‐3 1 MECH RM Panasonic LCU‐NS400MVP 29.2 (7.3 x 4) KW‐200V‐R404A
CS‐4 1 MECH RM Panasonic LCU‐NS350MVP 25.6 (7.3 x 3) + 3.7 KW‐200V‐R404A
CS‐5 1 MECH RM Panasonic LCU‐NS400MVP 29.2 (7.3 x 4) KW‐200V‐R404A
CS‐6 1 MECH RM Panasonic LCU‐NS400MVP 29.2 (7.3 x 4) KW‐200V‐R404A
CA‐7 1 MECH RM Panasonic LCU‐NS300MVP 21.9 (7.3 X 3) KW‐200V‐R404A
Compressor Systems
Self Contained Display Cases
Unit Coolers
Refrigeration Equipment Display Cases j2ctcsnm Typewritten Text W912HV-16-R-0006 (Am-0001) j2ctcsnm
Store Location AREA ‐ PACIFIC HQCWHBIwakuni Commissary
Facility Equipment List Iwakuni Commissary
Item Quantity Location/Type Manufacturer Model # Decription
ACC‐1 2 ROOF/MT Panasonic MCF‐N250NU‐SL
ACC‐2 2 ROOF/MT Panasonic MCF‐N200NU‐SL
ACC‐3 2 ROOF/MT Panasonic MCF‐N200NU‐SL
ACC‐4 2 ROOF/MT Panasonic MCF‐N200NU‐SL
ACC‐5 2 ROOF/MT Panasonic MCF‐N200NU‐SL
ACC‐6 2 ROOF/MT Panasonic MCF‐N250NU‐SL
ACC‐7 2 ROOF/MT Panasonic MCF‐N200NU‐SL
Quantity Location/Type Manufacturer Model # Decription
Quantity Location/Type Manufacturer Model # Decription
CA‐1 1 OUTDOOR Panasonic OCU‐GS2502MVF‐SL 18.2 (9.1 X 2) KW‐200V‐R404A
CA‐2 1 OUTDOOR Panasonic OCU‐GS3502MVF‐SL 25.5 (7.3 +9.1 + 9.1)KW‐200V‐R404A
CA‐3 1 OUTDOOR Panasonic OCU‐GS3002MVF‐SL 21.9KW‐200V‐R404A
Quantity Location/Type Manufacturer Model # Decription
RMCS 1 Customer Service Panasonic
RMCS 1 Mech Rm Johnson Controls
RMCS 1 Mech Rm Danfoss AK‐SC255
RMCS 1 Customer Service Mitsubishi
Ice Machine 1 Produce Scotsman FME 1504AS‐32B 208V‐60‐1, APP 02‐177 Item # Quantity Location/Type Manufacturer Model # Decription
FCV‐4 3 31D 2.6kW, 8L/min/200V‐3Ph/R410A
ACP‐M11 1 Roof Mitsubishi 50kW/56KW/200V‐3Ph/R410A
ACP‐M11‐1 6 4,5,9,10,11,6B Mitsubishi 2.2KW/2.5KW/200V‐1Ph/R410A
ACP‐M11‐2 6 70,72,73 Mistubish 4.5KW/5.0KW/200V‐1Ph/R410A
ACP‐M11‐3 1 80 Mitsubishi 4.5KW/5.0KW/200V‐1Ph/R410A
ACP‐M12 1 Roof Mitsubishi 22.4KW/25KW/200V‐3Ph/R410A
ACP‐M12‐1 7 6B,27B,34,45,57,35A,35 Mitsubishi 2.2KW/2.5KW/200V‐1Ph/R410A
ACP‐M12‐2 2 28,25 Mitsubishi 3.6KW/4.0KW/200V‐1Ph/R410A
ACP‐M12‐3 1 16B Mitsubishi 3.6KW/4.0KW/200V‐1Ph/R410A
ACP‐M21 1 Roof Mitsubishi 33.5KW/37.5KW/200V‐3Ph/R410A
ACP‐M21‐1 10 ,84,12A,12B,26A,27A,1 Mitsubishi 2.2KW/2.5KW/200V‐1Ph/R410A
ACP‐M21‐2 1 14B Mitsubishi 2.8KW/3.2KW/200V‐1Ph/R410A
ACP‐M21‐3 2 15 Mitsubishi 2.8KW/3.2KW/200V‐1Ph/R410A
ACP‐M21‐4 2 16A,17 Mitsubishi 3.6KW/4.0KW/200V‐1Ph/R410A
ACP‐1 6 97A,97B,31A, Roof Mistubishi 5.6KW/6.7KW/200V‐1Ph/R410A
ACP‐2 1 44B, Roof Mitsubishi 3.6KW/4.0KW/200V‐1Ph/R410A
RR‐1 4 Outdoor Mitsubishi ‐ 50 Hp EAHV‐P1500A‐STD 50hP/122KW/123KW/310LPM/200v‐3Ph/R407C
PCH‐1 4 31D Ebarra 50X40Fs2G63‐7E 319LPM/200V‐3Ph
PCH‐2 2 31D Ebarra 65X50FS2G65‐5E 637LPM/200V‐3Ph
RR‐2 2 Outdoor Mitsubishi ‐ 40 Hp EAHV‐P1200A‐STD 40Hp/98KW/254LPM/200V‐3Ph/R407C
PHH‐1 2 31D Ebarra 50X40Fs2G63‐7E 254LPM/200V‐3PH
TE‐1 1 31D 106L
TE‐2 1 31D 53L
HCHS‐1 1 31D 250 X 2500L
HCHS‐2 1 31D 250 X 2600L
HCHR‐1 1 31D 250 X 2800L
Condensers
HVAC Equipment
Heat Reclaim Coils
Condensing Unit
Additional Facility Equipment j2ctcsnm Typewritten Text W912HV-16-R-0006 (Am-0006) j2ctcsnm
Store Location AREA ‐ PACIFIC HQCWHBIwakuni Commissary
Facility Equipment List Iwakuni Commissary
APP 02‐177 Item # Quantity Location/Type Manufacturer Model # Decription
HCHR‐2 1 31D 250 X 1900L
HA‐1 1 31D 100 X 2000L
ACU‐1 1 31D Showatekko ZCH‐54DEK 46500CMH X 600Pa/42550CMH X 600Pa/200V‐3Ph
ACU‐2 1 31D Showatekko CH‐280EK 23500 CMH X 750Pa/200V‐3Ph
PH‐1 6 1,2A,2B 日本シーズ 線株式会社 DHWY150PSX 1.5KW/200V‐1Ph
PH‐2 2 31C 日本シーズ 線株式会社 DHWB150PX 1.5KW/200V‐1Ph
PH‐3 1 21A 日本シーズ 線株式会社 DHWY050ENSX 0.2KW/100V‐1Ph
PH‐4 1 21B 日本シーズ 線株式会社 DHWY050ENSX 0.4KW/100V‐1PH
UH‐1 6 36A Sinko HW‐90‐2 17.2KW/50LPM/5490CMH/200V‐3Ph
ACP‐3 1 36A, Roof 14.0KW/600CMH/200V‐3PH
ACP‐4 1 36A, Roof 28.0KW/23.3KW/1420CMH/200V‐3Ph
ACP‐5 1 14B, Roof 28.0KW/23.3KW/1750CMH/200V‐3Ph
ACP‐6 1 73‐2nd Flr, Roof 22.4KW/18.7KW/1000CMH/200V‐3PH
ACP‐7 2 73‐2nd Flr, Roof 28.0KW/23.3KW/2000CMH/200V‐3Ph
CC‐1 2 12A 100V‐1Ph, Central Controller
HEU‐1 1 31D Mitsubishi LGH‐N100RHW 600 CMH X 150 Pa/100V‐1Ph
FS‐1 3 36A Panasonic FY‐50MTUS 4000 CMH X 70 Pa/200V‐3Ph
FS‐2 2 31D Panasonic FY‐90KTUS4 11050 CMH X 100 Pa/200V‐3Ph
FS‐3 1 31D Ebara AIM65.58 22100 CMH X 320 Pa/200V‐3Ph
FS‐4 1 Fire Pump RM Panasonic FY‐25GTU3 620 CMH X 50 Pa/200v‐3Ph
FE‐1 3 36A, Roof Sanyo UAF‐50EN3 4000 CMH X 50Pa/200V‐3Ph
FE‐2 1 20A Panasonic FY‐12NCS3 160 CMH X 50 Pa/100V‐1Ph
FE‐3 1 20B Panasonic FY‐15NCS3 180 CMH X 50 Pa/100V‐1Ph
FE‐4 2 25,28 Panasonic FY‐12NCS3 140 CMH X 50 Pa/100V‐1Ph
FE‐5 1 31C Panasonic FY‐15NCS3 180 CMH X 50 Pa/100V‐1Ph
FE‐6 1 32 Panasonic FY‐15NCS3 240 CMH X 100 Pa/100V‐1Ph
FE‐7 1 70 Panasonic FY‐18NCS3 360 CMH X 50 Pa/100V‐1Ph
FE‐8 2 26B,27B Panasonic FY‐18NCF3 430 CMH X 100 Pa/100v‐1Ph
FE‐9 2 26A,27A Panasonic FY‐18NCF3 470 CMH X 150 Pa/100v‐1Ph
FE‐10 1 9,10,11 Panasonic FY‐23NCS3 1080 CMH X 150 Pa/100V‐1Ph
FE‐11 1 73‐Roof Panasonic FY‐26TCX3/UAF‐40N 1200 CMH X 250Pa/200V‐3Ph
FE‐12 1 73‐Roof Panasonic FY‐28TCH3/UAF‐40N 2000 CMH X 400 Pa/200V‐3Ph
FE‐13 1 73‐Roof Panasonic FY‐28TCH3/UAF‐40N 3150 CMH X 400 Pa/200V‐3Ph
FE‐14 1 38 Panasonic FY‐28TCH3 3050 CMH X 250 Pa/200V‐3Ph
FE‐15 3 31D, Roof Sanyo UAF‐75EN3 14734 CMH X 60Pa/200V‐3Ph
FE‐16 1 23 Panasonic FY‐18NCS3 350 CMH X 100Pa/100V‐1Ph
FE‐17 1 Fire Pump RM Panasonic FY‐25GTU3 620 CMH X 50Pa/200V‐3Ph
FE‐18 1 Generator RM Panasonic EF‐30BTD‐V 960 CMH X 50Pa/200V‐3Ph
FE‐19 1 99A Panasonic FY‐12NCS3 160 CMH X 50 Pa/100V‐1Ph
ACT‐1 9 1,2A,2B,36A,100D Mitsubishi GK‐3009T 900 CMH/200V‐3Ph
ACT‐2 3 1,2A,2B Mitsubishi GK‐3012T 1200 CMH/200V‐3Ph
ACT‐3 5 36A Mitsubishi MK‐3509TA 900 CMH/200V‐3Ph
VAV‐1 1 69 6716 CMH/100V‐1Ph
VAV‐2 2 69 8395 CMH/100V‐1Ph
FE‐Underfloor 2 68 & 76 Fractional Hp
Additional Notes
HVAC Equipment j2ctcsnm Typewritten Text W912HV-16-R-0006 (Am-0001) j2ctcsnm
Prepared By