AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT

Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.

15A. NAME AND TITLE OF SIGNER (Type or print)

30-105-04EXCEPTION TO SF 30

APPROVED BY OIRM 11-84

STANDARD FORM 30 (Rev. 10-83) Prescribed by GSA

FAR (48 CFR) 53.243

Solicitation No. W912HV-16-R-0006, Maintenance and Repair of Refrigeration Systems and Heating, Ventilation, and Air Conditioning Systems, Commissaries and Central Distribution Centers (CDC), MCAS Iw akuni and Kure Pier 6, Japan

See Continuation Page

1. CONTRACT ID CODE PAGE OF PAGES

J 1 5

16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)

16C. DATE SIGNED

BY

16B. UNITED STATES OF AMERICA15C. DATE SIGNED15B. CONTRACTOR/OFFEROR

(Signature of Contracting Officer)(Signature of person authorized to sign)

8. NAME AND ADDRESS OF CONTRACTOR (No., Street, County, State and Zip Code) X W912HV-16-R-0006

X 9B. DATED (SEE ITEM 11)

06-May-2016

10B. DATED (SEE ITEM 13)

9A. AMENDMENT OF SOLICITATION NO.

11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS

X The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offer is extended, X is not extended.

Offer must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended by one of the following methods:

(a) By completing Items 8 and 15, and returning 1 copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted;

or (c) By separate letter or telegram which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by telegram or letter, provided each telegram or letter makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.

12. ACCOUNTING AND APPROPRIATION DATA (If required)

13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS.

IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.

A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE

CONTRACT ORDER NO. IN ITEM 10A.

B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation date, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(B).

C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:

D. OTHER (Specify type of modification and authority)

E. IMPORTANT: Contractor is not, is required to sign this document and return copies to the issuing office.

14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)

10A. MOD. OF CONTRACT/ORDER NO.

U0001

2. AMENDMENT/MODIFICATION NO. 5. PROJECT NO.(If applicable)

6. ISSUED BY

3. EFFECTIVE DATE

CODE

CONTRACTING DIVISION

USACE-JAPAN DISTRICT

RM 147, BLDG. 250

CAMP ZAMA

ZAMA-CITY, KANAGAWA 252-8511

JAPAN

W912HV 7. ADMINISTERED BY (If other than item 6)

4. REQUISITION/PURCHASE REQ. NO.

CODE

See Item 6

FACILITY CODECODE

EMAIL:TEL:

j2ctcsnm Rectangle j2ctcsnm Typewritten Text j2ctcsnm Rectangle j2ctcsnm Typewritten Text

W912HV-16-R-0006 (Am-0001)

SECTION SF 30 BLOCK 14 CONTINUATION PAGE

SUMMARY OF CHANGES

B. CHANGES TO SOLICITATION:

b. Revised Pages/Paragraphs: Attached hereto are revised pages/paragraphs added to solicitation. The revision mark (Am-0001) is shown on each new page of the specifications.

Section Page No(s)/Paragraph No(s).

B - (Supplies or Services and Prices) Pages 2 - 6

C - (Descriptions and Specifications) Pages 8 - 9 (Revised Iwakuni Performance Work Statement Commissary, Bldg. 615)

c. Replaced Pages/Paragraphs: The following sections/pages are replaced from the specifications.

Section Page No(s)/Paragraph No(s).

C - (Technical Exhibit 7) Pages 45 - 48

Equipment List (Refrigeration & HVAC)

Section B – Supplies or Services and Prices

Maintenance and Repair of Refrigeration and HVAC Systems, Commissaries and CDC, MCAS Iwakuni and Kure Pier 6, Japan

Base Year: 01 AUGUST 2016 – 31 JULY 2017

UNIT

ITEM

NO. SUPPLIES/SERVICES QTY UNIT PRICE AMOUNT

0001 Monthly Preventive, Emergency Maintenance and Repair of Refrigeration Systems and associated Refrigeration Monitoring and Control Systems

0001AA Iwakuni Commissary, Building 615 12 MO ¥_________ ¥__________

0001AB Kure at Pier 6 Commissary, Building S-250 12 MO ¥_________ ¥__________

0001AC Iwakuni CDC, Building 170 12 MO ¥_________ ¥__________

0002 Monthly Preventive, Emergency Maintenance and Repair of HVAC Systems

0002AA Iwakuni Commissary, Building 615 12 MO ¥_________ ¥__________

0002AB Kure at Pier 6 Commissary, Building S-250 12 MO ¥_________ ¥__________

0003 Reimbursable Items 1 Year NTE ¥1,500,000

0004 Contract Manpower Reporting 1 Job ¥_________ ¥__________

Subtotal of Base Year: ¥___________ j2ctcsnm j2ctcsnm Typewritten Text j2ctcsnm

Option Year 1: 01 AUGUST 2017 – 31 JULY 2018

NO. SUPPLIES/SERVICES QTY UNIT PRICE AMOUNT

1001 Monthly Preventive, Emergency Maintenance and Repair of Refrigeration Systems and associated

1001AA Iwakuni Commissary, Building 615 12 MO ¥_________ ¥__________

1001AB Kure at Pier 6 Commissary, Building S-250 12 MO ¥_________ ¥__________

1001AC Iwakuni CDC, Building 170 12 MO ¥_________ ¥__________

1002 Monthly Preventive, Emergency Maintenance and

1002AA Iwakuni Commissary, Building 615 12 MO ¥_________ ¥__________

1002AB Kure at Pier 6 Commissary, Building S-250 12 MO ¥_________ ¥__________

1003 Reimbursable Items 1 Year NTE ¥1,500,000

1004 Contract Manpower Reporting 1 Job ¥_________ ¥__________

Subtotal of Option Year 1: ¥___________ j2ctcsnm Typewritten Text j2ctcsnm

Option Year 2: 01 AUGUST 2018 – 31 JULY 2019

NO. SUPPLIES/SERVICES QTY UNIT PRICE AMOUNT

2001 Monthly Preventive, Emergency Maintenance and Repair of Refrigeration Systems and associated

2001AA Iwakuni Commissary, Building 615 12 MO ¥_________ ¥__________

2001AB Kure at Pier 6 Commissary, Building S-250 12 MO ¥_________ ¥__________

2001AC Iwakuni CDC, Building 170 12 MO ¥_________ ¥__________

2002 Monthly Preventive, Emergency Maintenance and

2002AA Iwakuni Commissary, Building 615 12 MO ¥_________ ¥__________

2002AB Kure at Pier 6 Commissary, Building S-250 12 MO ¥_________ ¥__________

2003 Reimbursable Items 1 Year NTE ¥1,500,000

2004 Contract Manpower Reporting 1 Job ¥_________ ¥__________

Subtotal of Option Year 2: ¥___________ j2ctcsnm Typewritten Text j2ctcsnm

Option Year 3: 01 AUGUST 2019 – 31 JULY 2020

NO. SUPPLIES/SERVICES QTY UNIT PRICE AMOUNT

3001 Monthly Preventive, Emergency Maintenance and Repair of Refrigeration Systems and associated

3001AA Iwakuni Commissary, Building 615 12 MO ¥_________ ¥__________

3001AB Kure at Pier 6 Commissary, Building S-250 12 MO ¥_________ ¥__________

3001AC Iwakuni CDC, Building 170 12 MO ¥_________ ¥__________

3002 Monthly Preventive, Emergency Maintenance and

3002AA Iwakuni Commissary, Building 615 12 MO ¥_________ ¥__________

3002AB Kure at Pier 6 Commissary, Building S-250 12 MO ¥_________ ¥__________

3003 Reimbursable Items 1 Year NTE ¥1,500,000

3004 Contract Manpower Reporting 1 Job ¥_________ ¥__________

Subtotal of Option Year 3: ¥___________ j2ctcsnm Typewritten Text j2ctcsnm

Option Year 4: 01 AUGUST 2020 – 31 JULY 2021

NO. SUPPLIES/SERVICES QTY UNIT PRICE AMOUNT

4001 Monthly Preventive, Emergency Maintenance and Repair of Refrigeration Systems and associated

4001AA Iwakuni Commissary, Building 615 12 MO ¥_________ ¥__________

4001AB Kure at Pier 6 Commissary, Building S-250 12 MO ¥_________ ¥__________

4001AC Iwakuni CDC, Building 170 12 MO ¥_________ ¥__________

4002 Monthly Preventive, Emergency Maintenance and

4002AA Iwakuni Commissary, Building 615 12 MO ¥_________ ¥__________

4002AB Kure at Pier 6 Commissary, Building S-250 12 MO ¥_________ ¥__________

4003 Reimbursable Items 1 Year NTE ¥1,500,000

4004 Contract Manpower Reporting 1 Job ¥_________ ¥__________

Subtotal of Option Year 4: ¥___________

BASE YEAR SUBTOTAL ¥_____________

OPTION YEAR 1 SUBTOTAL ¥_____________

OPTION YEAR 2 SUBTOTAL ¥_____________

OPTION YEAR 3 SUBTOTAL ¥_____________

OPTION YEAR 4 SUBTOTAL ¥_____________

GRAND TOTAL AMOUNT ¥_____________

j2ctcsnm Typewritten Text j2ctcsnm Typewritten Text j2ctcsnm

PERFORMANCE WORK STATEMENT

MAINTENANCE AND REPAIR OF REFRIGERATION SYSTEMS AND

HEATING, VENTILATION, AND AIR CONDITIONING SYSTEMS,

COMMISSARIES AND CDC, MCAS IWAKUNI AND KURE PIER 6,

JAPAN

20 March 2016 REVISED 25 May 2016

Prepared By U. S. Army Corps of Engineers Japan District j2ctcsnm

1. GENERAL. This is a non-personal services contract to perform maintenance on all commissary and Central Distribution Center (CDC) refrigeration systems including the Refrigeration Monitoring and Control System (RMCS) and commissary heating, ventilation and air-conditioning (HVAC) systems at the “MCAS

IWAKUNI COMMISSARY BLDG 615”; IWAKUNI CDC BLDG 170; AND KURE PIER 6 COMMISSARY

BLDG 250, Japan. The Government shall not exercise any supervision or control over the contract service providers performing the services herein. Such contract service providers shall be accountable solely to the Contractor who, in turn is responsible to the Government.

1.1. Description of Services/Introduction. The contractor shall provide all personnel, equipment, supplies, facilities, transportation, tools, materials, supervision, and other items and non-personal services necessary to perform MAINTENANCE AND REPAIR OF REFRIGERATION SYSTEMS AND

HEATING, VENTILATION, AND AIR CONDITIONING SYSTEMS, COMMISSARIES AND CDC,

MCAS IWAKUNI AND KURE PIER 6, as defined in this Performance Work Statement (PWS) except for those items specified as government furnished property and services. The contractor shall perform to the standards in this contract.

1.2. Scope. The Contractor shall provide all services, personnel, equipment, tools, parts, transportation, materials except as specified in Section 18. GOVERNMENT FURNISHED PROPERTY AND SERVICES, supervision, and other items necessary to perform MAINTENANCE AND REPAIR OF

REFRIGERATION SYSTEMS AND HEATING, VENTILATION, AND AIR CONDITIONING

SYSTEMS COMMISSARIES AND CDC, MCAS IWAKUNI AND KURE PIER 6, JAPAN.

1.3. Work and services to be provided by the Government are specified in Section 18. GOVERNMENT FURNISHED PROPERTY AND SERVICES. Work performed under this contract shall be conducted in accordance with the manufacturer’s recommendation and/or best commercial practices to operate the systems at optimum efficiency while maintaining the required operation, temperature and/or humidity conditions.

The estimated quantities of emergency work are listed in Technical Exhibit 2, Emergency Call Workload Estimates.

1.4. Period of Performance. Period of performance for Base Year shall be from 01August 2016 through 31 July 2017. Four (4) additional option years may be exercised at the discretion of the Contracting Officer.

2. CONTRACTOR REQUIREMENTS.

2.1. Perform refrigeration and HVAC periodic preventive maintenance (PPM) at the frequency recommended by equipment manufacturers and/or best commercial practices, but no less than on a monthly basis. The contractor shall also perform PPM on a monthly basis to ensure that all commissary main entrance and exit automatic door systems are clean and operational. The PPM shall include repairs, checks, tests, calibrations, adjustments, lubrications, and replacement of system parts. Loose parts including hinges shall be tightened and secured. Door surfaces including stainless frames shall be free of corrosions, dirt, and other foreign substances.

2.2. Be available for emergency service 24 hours/day, 7 days/week and furnish at least one (1), but not more than three (3) telephone numbers at which the contractor or his representative can be contacted 24 hours/day, 7 days/week.

2.3. Report to an authorized government personnel (AGP) immediately upon arrival at the commissary or CDC and notify the AGP when repairs have been completed.

2.4. Respond to an emergency call within two (2) hours for refrigeration equipment and complete emergency repairs within 24 hours after receiving the request from the AGP.

2.5. Respond to an emergency call by 0900 the following day for HVAC systems and complete emergency repairs within 24 hours of arrival after receiving the request from the AGP.

j2ctcsnm Typewritten Text j2ctcsnm

GROUP/DODAAC ISSUE DATE

Store Name 1‐Dec‐2015

Store Location AREA ‐ PACIFIC HQCWHB

Item Quantity Length (Ft) Manufacturer Model # Decription

Sys1‐1 1 8' Panasonic CVS‐EX085

Sys1‐2 1 12' Panasonic CVS‐EX025

Sys1‐3 1 12' Panasonic CVS‐EX025

Sys1‐4 1 12' Panasonic CVS‐EX025

Sys1‐5 1 12' Panasonic CVS‐EX025

Sys1‐6 1 12' Panasonic CVS‐EX025

Sys1‐7 1 12' Panasonic CVS‐EX025

Sys1‐8 1 12' Panasonic CVS‐EX025

Sys1‐9 1 8' Panasonic CVS‐EX085

Sys1‐10 1 12' Panasonic CVS‐EX025

Sys2‐11 1 12' Panasonic FZW‐EX025

Sys2‐12 1 12' Panasonic FZW‐EX025

Sys2‐13 1 12' Panasonic FZW‐EX025

Sys2‐15 1 12' Panasonic FZW‐EX025

Sys2‐16 1 8' Panasonic FZW‐EX085

Sys2‐17 1 8' Panasonic FZW‐EX085

Sys2‐18 1 12' Panasonic FPW‐EX025

Sys2‐19 1 12' Panasonic FPW‐EX025

Sys2‐20 1 8' Panasonic FPW‐EX085

Sys2‐21 1 12' Panasonic CPW‐EX025

Sys2‐23 1 12' Panasonic CPW‐EX025

Sys2‐24 1 12' Panasonic CPW‐EX025

Sys2‐25 1 12' Panasonic CPW‐EX025

Sys3‐26 1 12' Panasonic CPW‐EX025

Sys3‐27 1 12' Panasonic CPW‐EX025

Sys3‐28 1 3 DR Panasonic FLD‐EX0377LB

Sys3‐29 1 3 DR Panasonic FLD‐EX0377LB

Sys3‐30 1 3 DR Panasonic FLD‐EX0377LB

Sys3‐31 1 3 DR Panasonic FLD‐EX0377LB

Sys3‐32 1 3 DR Panasonic FLD‐EX0377LB

Sys3‐33 1 3 DR Panasonic FLD‐EX0377LB

Sys3‐34 1 3 DR Panasonic FLD‐EX0377LB

Sys3‐35 1 3 DR Panasonic FLD‐EX0377LB

Sys3‐36 1 3 DR Panasonic FLD‐EX0377LB

Sys3‐37 1 2 DR Panasonic FLD‐EX0277LB

Sys4‐38 1 2 DR Panasonic FLD‐EX0277LB

Sys4‐39 1 3 DR Panasonic FLD‐EX0377LB

Sys4‐40 1 3 DR Panasonic FLD‐EX0377LB

Sys4‐41 1 3 DR Panasonic FLD‐EX0377LB

Sys4‐42 1 3 DR Panasonic FLD‐EX0377LB

Sys4‐43 1 3 DR Panasonic FLD‐EX0377LB

Sys4‐44 1 3 DR Panasonic FLD‐EX0377LB

Sys4‐45 1 3 DR Panasonic FLD‐EX0377LB

Sys4‐46 1 3 DR Panasonic FLD‐EX0377LB

Sys4‐47 1 3 DR Panasonic FLD‐EX0377LB

Sys4‐48 1 3 DR Panasonic FLD‐EX0377LB

Sys4‐49 1 3 DR Panasonic FLD‐EX0377LB

Sys3‐50 1 3 DR Panasonic FLD‐EX0377LB

Sys3‐51 1 3 DR Panasonic FLD‐EX0377LB

Sys5‐52 1 12' Panasonic CZW‐EX887

Sys5‐53 1 12' Panasonic CZW‐EX887

Sys5‐54 1 12' Panasonic CZW‐EX887

Sys5‐55 1 12' Panasonic CZW‐EX887

Sys5‐58 1 3 DR Panasonic FLD‐EX3077

Sys5‐59 1 3 DR Panasonic FLD‐EX3077

Sys5‐60 1 3 DR Panasonic FLD‐EX3077

Sys5‐61 1 3 DR Panasonic FLD‐EX3077

Sys5‐62 1 3 DR Panasonic FLD‐EX3077

Sys5‐63 1 3 DR Panasonic FLD‐EX3077

Sys5‐64 1 3 DR Panasonic FLD‐EX3077

Sys2‐65 1 3 DR Panasonic FLD‐EX3077

Iwakuni Commissary

Facility Equipment List Iwakuni Commissary

Refrigeration Equipment Display Cases j2ctcsnm Typewritten Text W912HV-16-R-0006 (Am-0001) j2ctcsnm

Store Location AREA ‐ PACIFIC HQCWHBIwakuni Commissary

Facility Equipment List Iwakuni Commissary

Item Quantity Length (Ft) Manufacturer Model # Decription

Sys2‐66 1 3 DR Panasonic FLD‐EX3077

Sys2‐67 1 3 DR Panasonic FLD‐EX3077

Sys2‐68 1 3 DR Panasonic FLD‐EX3077

SysX‐70 1 12' Panasonic EX3066MSY

SysX‐71 1 12' Panasonic EX3066MSY

SysX‐72 1 5' Panasonic EX3066MSY

SysX‐73 1 5' Panasonic EX3066MSY

Item Quantity Length (Ft) Manufacturer Model # Decription

S/C Sandwich Table 1 4 Ft Everest Refrigeration EPR2 115‐60‐1, 1/4 Hp, R‐134a

S/C Reach‐in Fridge 1 52 inches Traulsen G20010 115‐60‐1, S/C Island Case 1 8 FT Hill‐Phoenix OIMA 208‐60‐1, R404A

S/C Sushi Prep 1 4 FT Southern PSSC 115‐60‐1, R404A

S/C Grab‐n‐Go 1 4 FT Southern 1M04 115‐60‐1 item Quantity Location/Type Manufacturer Model # Decription

1‐104 1 44A Panasonic CC‐M8070

1‐107 1 55 Panasonic CC‐M8070

1‐108 1 55 Panasonic CC‐M8070

1‐109 1 56 Panasonic CC‐M8070

1‐110 1 56 Panasonic CC‐M8070

6‐101 1 43A Panasonic CC‐V5080H

6‐102 1 43A Panasonic CC‐V5080H

6‐103 1 43B Panasonic CC‐V9080HCP

6‐105 1 59 Panasonic CC‐D14020H

6‐106 1 59 Panasonic CC‐D14020H

6‐111 1 67 Panasonic CC‐V9020H

6‐112 1 67 Panasonic CC‐V9020H

6‐113 1 77 Panasonic CC‐V5080H

7‐201 1 68 Panasonic CC‐D12020LH

7‐202 1 68 Panasonic CC‐D12020LH

7‐203 1 76 Panasonic CC‐D9020LH

7‐101 1 43A Panasonic CC‐V5080H

7‐102 1 43A Panasonic CC‐V5080H

7‐103 1 43B Panasonic CC‐V9080HCP

7‐104 1 44A Panasonic CC‐M6070H

7‐105 1 44A Panasonic CC‐M6070H

7‐109 1 55 Panasonic CC‐M6070

7‐110 1 55 Panasonic CC‐M6070

8‐106 1 59 Panasonic CC‐V9080H

8‐107 1 59 Panasonic CC‐V9080H

8‐108 1 59 Panasonic CC‐V9080H

8‐111 1 56 Panasonic CC‐M6070

8‐112 1 56 Panasonic CC‐M6071

8‐113 1 67 Panasonic CC‐D14020H

8‐114 1 67 Panasonic CC‐D14020H

9‐201 1 68 Panasonic CC‐D9020LH

9‐202 1 68 Panasonic CC‐D9020LH

9‐203 1 76 Panasonic CC‐D9020LH

Item Quantity Location/Type Manufacturer Model # Decription

CS‐1 1 MECH RM Panasonic LCU‐NS400MVP 29.2 (7.3 x 4) KW‐200V‐R404A

CS‐2 1 MECH RM Panasonic LCU‐NS350MVP 25.6 (7.3 x 3) + 3.7 KW‐200V‐R404A

CS‐3 1 MECH RM Panasonic LCU‐NS400MVP 29.2 (7.3 x 4) KW‐200V‐R404A

CS‐4 1 MECH RM Panasonic LCU‐NS350MVP 25.6 (7.3 x 3) + 3.7 KW‐200V‐R404A

CS‐5 1 MECH RM Panasonic LCU‐NS400MVP 29.2 (7.3 x 4) KW‐200V‐R404A

CS‐6 1 MECH RM Panasonic LCU‐NS400MVP 29.2 (7.3 x 4) KW‐200V‐R404A

CA‐7 1 MECH RM Panasonic LCU‐NS300MVP 21.9 (7.3 X 3) KW‐200V‐R404A

Compressor Systems

Self Contained Display Cases

Unit Coolers

Refrigeration Equipment Display Cases j2ctcsnm Typewritten Text W912HV-16-R-0006 (Am-0001) j2ctcsnm

Store Location AREA ‐ PACIFIC HQCWHBIwakuni Commissary

Facility Equipment List Iwakuni Commissary

Item Quantity Location/Type Manufacturer Model # Decription

ACC‐1 2 ROOF/MT Panasonic MCF‐N250NU‐SL

ACC‐2 2 ROOF/MT Panasonic MCF‐N200NU‐SL

ACC‐3 2 ROOF/MT Panasonic MCF‐N200NU‐SL

ACC‐4 2 ROOF/MT Panasonic MCF‐N200NU‐SL

ACC‐5 2 ROOF/MT Panasonic MCF‐N200NU‐SL

ACC‐6 2 ROOF/MT Panasonic MCF‐N250NU‐SL

ACC‐7 2 ROOF/MT Panasonic MCF‐N200NU‐SL

Quantity Location/Type Manufacturer Model # Decription

Quantity Location/Type Manufacturer Model # Decription

CA‐1 1 OUTDOOR Panasonic OCU‐GS2502MVF‐SL 18.2 (9.1 X 2) KW‐200V‐R404A

CA‐2 1 OUTDOOR Panasonic OCU‐GS3502MVF‐SL 25.5 (7.3 +9.1 + 9.1)KW‐200V‐R404A

CA‐3 1 OUTDOOR Panasonic OCU‐GS3002MVF‐SL 21.9KW‐200V‐R404A

Quantity Location/Type Manufacturer Model # Decription

RMCS 1 Customer Service Panasonic

RMCS 1 Mech Rm Johnson Controls

RMCS 1 Mech Rm Danfoss AK‐SC255

RMCS 1 Customer Service Mitsubishi

Ice Machine 1 Produce Scotsman FME 1504AS‐32B 208V‐60‐1, APP 02‐177 Item # Quantity Location/Type Manufacturer Model # Decription

FCV‐4 3 31D 2.6kW, 8L/min/200V‐3Ph/R410A

ACP‐M11 1 Roof Mitsubishi 50kW/56KW/200V‐3Ph/R410A

ACP‐M11‐1 6 4,5,9,10,11,6B Mitsubishi 2.2KW/2.5KW/200V‐1Ph/R410A

ACP‐M11‐2 6 70,72,73 Mistubish 4.5KW/5.0KW/200V‐1Ph/R410A

ACP‐M11‐3 1 80 Mitsubishi 4.5KW/5.0KW/200V‐1Ph/R410A

ACP‐M12 1 Roof Mitsubishi 22.4KW/25KW/200V‐3Ph/R410A

ACP‐M12‐1 7 6B,27B,34,45,57,35A,35 Mitsubishi 2.2KW/2.5KW/200V‐1Ph/R410A

ACP‐M12‐2 2 28,25 Mitsubishi 3.6KW/4.0KW/200V‐1Ph/R410A

ACP‐M12‐3 1 16B Mitsubishi 3.6KW/4.0KW/200V‐1Ph/R410A

ACP‐M21 1 Roof Mitsubishi 33.5KW/37.5KW/200V‐3Ph/R410A

ACP‐M21‐1 10 ,84,12A,12B,26A,27A,1 Mitsubishi 2.2KW/2.5KW/200V‐1Ph/R410A

ACP‐M21‐2 1 14B Mitsubishi 2.8KW/3.2KW/200V‐1Ph/R410A

ACP‐M21‐3 2 15 Mitsubishi 2.8KW/3.2KW/200V‐1Ph/R410A

ACP‐M21‐4 2 16A,17 Mitsubishi 3.6KW/4.0KW/200V‐1Ph/R410A

ACP‐1 6 97A,97B,31A, Roof Mistubishi 5.6KW/6.7KW/200V‐1Ph/R410A

ACP‐2 1 44B, Roof Mitsubishi 3.6KW/4.0KW/200V‐1Ph/R410A

RR‐1 4 Outdoor Mitsubishi ‐ 50 Hp EAHV‐P1500A‐STD 50hP/122KW/123KW/310LPM/200v‐3Ph/R407C

PCH‐1 4 31D Ebarra 50X40Fs2G63‐7E 319LPM/200V‐3Ph

PCH‐2 2 31D Ebarra 65X50FS2G65‐5E 637LPM/200V‐3Ph

RR‐2 2 Outdoor Mitsubishi ‐ 40 Hp EAHV‐P1200A‐STD 40Hp/98KW/254LPM/200V‐3Ph/R407C

PHH‐1 2 31D Ebarra 50X40Fs2G63‐7E 254LPM/200V‐3PH

TE‐1 1 31D 106L

TE‐2 1 31D 53L

HCHS‐1 1 31D 250 X 2500L

HCHS‐2 1 31D 250 X 2600L

HCHR‐1 1 31D 250 X 2800L

Condensers

HVAC Equipment

Heat Reclaim Coils

Condensing Unit

Additional Facility Equipment j2ctcsnm Typewritten Text W912HV-16-R-0006 (Am-0006) j2ctcsnm

Store Location AREA ‐ PACIFIC HQCWHBIwakuni Commissary

Facility Equipment List Iwakuni Commissary

APP 02‐177 Item # Quantity Location/Type Manufacturer Model # Decription

HCHR‐2 1 31D 250 X 1900L

HA‐1 1 31D 100 X 2000L

ACU‐1 1 31D Showatekko ZCH‐54DEK 46500CMH X 600Pa/42550CMH X 600Pa/200V‐3Ph

ACU‐2 1 31D Showatekko CH‐280EK 23500 CMH X 750Pa/200V‐3Ph

PH‐1 6 1,2A,2B 日本シーズ 線株式会社 DHWY150PSX 1.5KW/200V‐1Ph

PH‐2 2 31C 日本シーズ 線株式会社 DHWB150PX 1.5KW/200V‐1Ph

PH‐3 1 21A 日本シーズ 線株式会社 DHWY050ENSX 0.2KW/100V‐1Ph

PH‐4 1 21B 日本シーズ 線株式会社 DHWY050ENSX 0.4KW/100V‐1PH

UH‐1 6 36A Sinko HW‐90‐2 17.2KW/50LPM/5490CMH/200V‐3Ph

ACP‐3 1 36A, Roof 14.0KW/600CMH/200V‐3PH

ACP‐4 1 36A, Roof 28.0KW/23.3KW/1420CMH/200V‐3Ph

ACP‐5 1 14B, Roof 28.0KW/23.3KW/1750CMH/200V‐3Ph

ACP‐6 1 73‐2nd Flr, Roof 22.4KW/18.7KW/1000CMH/200V‐3PH

ACP‐7 2 73‐2nd Flr, Roof 28.0KW/23.3KW/2000CMH/200V‐3Ph

CC‐1 2 12A 100V‐1Ph, Central Controller

HEU‐1 1 31D Mitsubishi LGH‐N100RHW 600 CMH X 150 Pa/100V‐1Ph

FS‐1 3 36A Panasonic FY‐50MTUS 4000 CMH X 70 Pa/200V‐3Ph

FS‐2 2 31D Panasonic FY‐90KTUS4 11050 CMH X 100 Pa/200V‐3Ph

FS‐3 1 31D Ebara AIM65.58 22100 CMH X 320 Pa/200V‐3Ph

FS‐4 1 Fire Pump RM Panasonic FY‐25GTU3 620 CMH X 50 Pa/200v‐3Ph

FE‐1 3 36A, Roof Sanyo UAF‐50EN3 4000 CMH X 50Pa/200V‐3Ph

FE‐2 1 20A Panasonic FY‐12NCS3 160 CMH X 50 Pa/100V‐1Ph

FE‐3 1 20B Panasonic FY‐15NCS3 180 CMH X 50 Pa/100V‐1Ph

FE‐4 2 25,28 Panasonic FY‐12NCS3 140 CMH X 50 Pa/100V‐1Ph

FE‐5 1 31C Panasonic FY‐15NCS3 180 CMH X 50 Pa/100V‐1Ph

FE‐6 1 32 Panasonic FY‐15NCS3 240 CMH X 100 Pa/100V‐1Ph

FE‐7 1 70 Panasonic FY‐18NCS3 360 CMH X 50 Pa/100V‐1Ph

FE‐8 2 26B,27B Panasonic FY‐18NCF3 430 CMH X 100 Pa/100v‐1Ph

FE‐9 2 26A,27A Panasonic FY‐18NCF3 470 CMH X 150 Pa/100v‐1Ph

FE‐10 1 9,10,11 Panasonic FY‐23NCS3 1080 CMH X 150 Pa/100V‐1Ph

FE‐11 1 73‐Roof Panasonic FY‐26TCX3/UAF‐40N 1200 CMH X 250Pa/200V‐3Ph

FE‐12 1 73‐Roof Panasonic FY‐28TCH3/UAF‐40N 2000 CMH X 400 Pa/200V‐3Ph

FE‐13 1 73‐Roof Panasonic FY‐28TCH3/UAF‐40N 3150 CMH X 400 Pa/200V‐3Ph

FE‐14 1 38 Panasonic FY‐28TCH3 3050 CMH X 250 Pa/200V‐3Ph

FE‐15 3 31D, Roof Sanyo UAF‐75EN3 14734 CMH X 60Pa/200V‐3Ph

FE‐16 1 23 Panasonic FY‐18NCS3 350 CMH X 100Pa/100V‐1Ph

FE‐17 1 Fire Pump RM Panasonic FY‐25GTU3 620 CMH X 50Pa/200V‐3Ph

FE‐18 1 Generator RM Panasonic EF‐30BTD‐V 960 CMH X 50Pa/200V‐3Ph

FE‐19 1 99A Panasonic FY‐12NCS3 160 CMH X 50 Pa/100V‐1Ph

ACT‐1 9 1,2A,2B,36A,100D Mitsubishi GK‐3009T 900 CMH/200V‐3Ph

ACT‐2 3 1,2A,2B Mitsubishi GK‐3012T 1200 CMH/200V‐3Ph

ACT‐3 5 36A Mitsubishi MK‐3509TA 900 CMH/200V‐3Ph

VAV‐1 1 69 6716 CMH/100V‐1Ph

VAV‐2 2 69 8395 CMH/100V‐1Ph

FE‐Underfloor 2 68 & 76 Fractional Hp

Additional Notes