This is a Questions and Answers amendment to a Blanket Purchase Agreement (BPA) solicitation.
BPA Solicitation #W912HQ26QA017 Amendment 01 provides clarifications in response to contractor inquiries regarding four line items. For Line 1, a 15kV 1/0 AWG aluminum concentric neutral cable (1,500 FT), the government specified 133% insulation level, TR-XLPE insulation material, jacketed construction, and stranded conductor configuration with concentric neutral construction set at 16 #14AWG strands. For Line 2, a 15kV 500 MCM copper concentric neutral cable (500 FT), the requirements include 133% insulation level, TR-XLPE preferred insulation, jacketed construction mandatory, and compressed stranding with 1/3 neutral at 17 #10AWG strands. For Line 11, the 500 MCM cold shrink splice kit (3 EA) is confirmed as 15kV rated with wire shielding, insulation diameter range of 0.84-1.38 inches, and manufacturer identified as 3M with corrected part number 00054007441014. For Line 12, the 500 MCM barrel compression lugs (9 barrels total, 3 PK units) require a 0.72-inch stud hole size, standard aluminum barrel construction compatible with both AL and CU conductors. All terms and conditions of the original solicitation remain unchanged.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| BPA Solicitation Amendment 02.pdf | ||
| Solicitation - W912HQ26QA017.pdf | ||
| B08.02 Solicitation_AttachmentA_Pricing Schedule.xlsx | XLSX spreadsheet |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
BPA Solicitation # W912HQ26QA017
Amendment 01
The purpose of Amendment 01 to this solicitation is to provide answers to the questions received.
All other terms and conditions stay the same.
Questions:
1. Please confirm for line 1:
a. 133% insulation level
b. Required concentric-neutral percentage or neutral wire construction
c. EPR versus XLPE/TR-XLPE
d. Jacketed versus unjacketed
e. Solid versus stranded/compressed aluminum conductor
2. For line 2:
a. 100% or 133% insulation level
b. XLPE versus TR-XLPE acceptability
c. Concentric-neutral percentage or wire construction
d. Jacket requirement
e. Required standards and conductor stranding
11. For line 11:
a. Confirm 15kV rating, cable insulation diameter range, shield type, jacket configuration, and exact quantity.
12. For line 12:
a. Confirm stud-hole size, barrel type, conductor range, plating, total quantity required
# Type MFR PN Column 19 Shortcode
DESCRIP
TION
QT
Y
UO
M
1 Cable
NASSA
U
NATIO
NAL
CABLE NNC2665X
NASSAU
NATIONAL
CABLE-
NNC2665X
NNC-
NNC2665X
15kV 1/0
AWG
aluminum concentri
1,5
00 FT
c neutral cable
2 Cable
NASSA
U
NATIO
NAL
CABLE
NNC5001
UDTR-
XLPE
NASSAU
NATIONAL
CABLE-
NNC5001
UDTR-
XLPE
NNC-
NNC5001
UDTR-
XLPE
15kV 500
MCM
copper concentri c neutral cable 500 FT
1 Splice Kit
NO
MFR
PROVI
DED
054007- 44101
NO MFR
PROVIDED
-054007- 44101
054007- 44101
500 MCM
cold shrink splice kit 3 EA
Compres sion Lug 3M
054007- 13335 /
BROWN
3M- 054007- 13335
3M- 054007- 13335
500 MCM
barrel compress ion lugs, 3/PK;
alternate identifier:
color code brown 3 PK
Answers:
1a. 133% insulation Level
1b. This is set based on the Part Number at 16 #14AWG Strands
1c.TR-XLPE (Better for use on ground)
1d. Jacketed
1e. Stranded
2a. 133%
2b. TR-XLPE Preferred
2c. 1/3 neutral @ 17 #10AWG Strands
2d. Must be jacketed
2e. Compressed Stranding
11a. 15KV, 0.84-1.38IN, Wire Shielded, and 3 Kits ( Also for record the MFR is 3M and the part Number is actually 00054007441014)
12a. .72IN, Standard barrel Aluminum, AL or CU conductors, 9 Barrels total