This is a Questions and Answers amendment to a Blanket Purchase Agreement (BPA) solicitation.

BPA Solicitation #W912HQ26QA017 Amendment 01 provides clarifications in response to contractor inquiries regarding four line items. For Line 1, a 15kV 1/0 AWG aluminum concentric neutral cable (1,500 FT), the government specified 133% insulation level, TR-XLPE insulation material, jacketed construction, and stranded conductor configuration with concentric neutral construction set at 16 #14AWG strands. For Line 2, a 15kV 500 MCM copper concentric neutral cable (500 FT), the requirements include 133% insulation level, TR-XLPE preferred insulation, jacketed construction mandatory, and compressed stranding with 1/3 neutral at 17 #10AWG strands. For Line 11, the 500 MCM cold shrink splice kit (3 EA) is confirmed as 15kV rated with wire shielding, insulation diameter range of 0.84-1.38 inches, and manufacturer identified as 3M with corrected part number 00054007441014. For Line 12, the 500 MCM barrel compression lugs (9 barrels total, 3 PK units) require a 0.72-inch stud hole size, standard aluminum barrel construction compatible with both AL and CU conductors. All terms and conditions of the original solicitation remain unchanged.

View the file

Other files

File Type Posted
BPA Solicitation Amendment 02.pdf PDF
Solicitation - W912HQ26QA017.pdf PDF
B08.02 Solicitation_AttachmentA_Pricing Schedule.xlsx XLSX spreadsheet

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

BPA Solicitation # W912HQ26QA017

Amendment 01

The purpose of Amendment 01 to this solicitation is to provide answers to the questions received.

All other terms and conditions stay the same.

Questions:

1. Please confirm for line 1:

a. 133% insulation level

b. Required concentric-neutral percentage or neutral wire construction

c. EPR versus XLPE/TR-XLPE

d. Jacketed versus unjacketed

e. Solid versus stranded/compressed aluminum conductor

2. For line 2:

a. 100% or 133% insulation level

b. XLPE versus TR-XLPE acceptability

c. Concentric-neutral percentage or wire construction

d. Jacket requirement

e. Required standards and conductor stranding

11. For line 11:

a. Confirm 15kV rating, cable insulation diameter range, shield type, jacket configuration, and exact quantity.

12. For line 12:

a. Confirm stud-hole size, barrel type, conductor range, plating, total quantity required

# Type MFR PN Column 19 Shortcode

DESCRIP

TION

QT

Y

UO

M

1 Cable

NASSA

U

NATIO

NAL

CABLE NNC2665X

NASSAU

NATIONAL

CABLE-

NNC2665X

NNC-

NNC2665X

15kV 1/0

AWG

aluminum concentri

1,5

00 FT

c neutral cable

2 Cable

NASSA

U

NATIO

NAL

CABLE

NNC5001

UDTR-

XLPE

NASSAU

NATIONAL

CABLE-

NNC5001

UDTR-

XLPE

NNC-

NNC5001

UDTR-

XLPE

15kV 500

MCM

copper concentri c neutral cable 500 FT

1 Splice Kit

NO

MFR

PROVI

DED

054007- 44101

NO MFR

PROVIDED

-054007- 44101

054007- 44101

500 MCM

cold shrink splice kit 3 EA

Compres sion Lug 3M

054007- 13335 /

BROWN

3M- 054007- 13335

3M- 054007- 13335

500 MCM

barrel compress ion lugs, 3/PK;

alternate identifier:

color code brown 3 PK

Answers:

1a. 133% insulation Level

1b. This is set based on the Part Number at 16 #14AWG Strands

1c.TR-XLPE (Better for use on ground)

1d. Jacketed

1e. Stranded

2a. 133%

2b. TR-XLPE Preferred

2c. 1/3 neutral @ 17 #10AWG Strands

2d. Must be jacketed

2e. Compressed Stranding

11a. 15KV, 0.84-1.38IN, Wire Shielded, and 3 Kits ( Also for record the MFR is 3M and the part Number is actually 00054007441014)

12a. .72IN, Standard barrel Aluminum, AL or CU conductors, 9 Barrels total