boiler replacement RFQ post-site visit questions
1. I would like to know who your BACNET controls vendor is and can you provide their phone number?
A: ESI 703-471-6310
2. Can a dumpster be placed on site for the demolition portion of the boiler replacement work and be placed near the location of the boilers?
A: YES
3. Can the existing concrete equipment pads for the boilers be reused? Both equipment pads seem to be in good condition.
A: YES
4. The boiler in Bldg. 2584 has a pump located behind the boiler that Mr. Roberts said has been abandoned in place. Should we cap piping to pump and leave the pump in place as is?
A: Contractor shall cap at nearest shut-off valve. Pump remains.
5. What kind of expansion tank do you want used: the floor mounted bladder type or like the kind mounted in the ceiling?
A: Ceiling mounting unless floor type is small enough for required safety clearance.
6. Are we just replacing isolation valves for the boilers?
A: Contractor shall replace all valves as per manufacture spec. to the first isolation valve only.
7. Is there pump info for the 2- B&G pumps in Bldg. 2582?
8. Has line B.2 been deleted from the scope of work?
A:YES
9. Contractor BID shall include pot feeders in their installation and procurement proposal. Both building #2582 and #2584.
image1.JPG image2.JPG