This file contains foodservice general notes, plumbing drawings, and HVAC legends for a Child Development Center construction project at Fort Liberty, North Carolina. The drawings detail requirements for foodservice equipment installation, plumbing, and HVAC systems in accordance with national standards including NSF, NFPA, state fire marshal, state board of health, and local health codes.
The documents specify that foodservice equipment must meet UL standards, steam-heated equipment must comply with ASME requirements, and all electrical/plumbing components must be installed to allow proper cleaning access. Key technical requirements include maintaining minimum clearances (2 inches off walls, 6 inches off floors), proper drainage installations, moisture-proof electrical components, and specific utility connection requirements. The drawings show plumbing layouts for areas D165-D172 (Toddler/Preschool Activity Rooms) including hot water, cold water, and return lines, as well as details for calibrated balance valves and expansion loops.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FOODSERVICE GENERAL NOTES
• ITEMS OF FOODSERVICE EQUIPMENT SHALL BE FABRICATED AND INSTALLED IN STRICT ACCORDANCE WITH THE LATEST STANDARDS PUBLISHED BY THE NATIONAL SANITATION FOUNDATION (NSF) OR THE EQUIVALENT, IN STRICT COMPLIANCE WITH ALL APPLICABLE NATIONAL, STATE, AND/OR LOCAL CODES AND STANDARDS.
• WORK AND MATERIALS SHALL BE IN COMPLIANCE WITH REQUIREMENTS OF APPLICABLE CODES, ORDINANCES, AND REGULATIONS INCLUDING, BUT NOT LIMITED TO, THOSE OF THE NATIONAL FIRE PROTECTION ASSOCIATION, STATE FIRE MARSHAL, STATE BOARD OF HEALTH, LOCAL HEALTH CODES, ETC.
• ELECTRICALLY OPERATED AND/OR HEATED EQUIPMENT, FABRICATED OR OTHERWISE, SHALL CONFORM TO THE LATEST STANDARDS OF NATIONAL ELECTRIC MANUFACTURERS' ASSOCIATION AND OF UNDERWRITERS
LABORATORIES, INC. EQUIPMENT SHALL BEAR THE U.L. LABEL.
• STEAM HEATED EQUIPMENT SHALL BE MANUFACTURED IN ACCORDANCE WITH A.S.M.E. CODE
REQUIREMENTS AND CARRY THE A.S.M.E. STAMP.
• NO EXTRA CHARGE WILL BE PAID FOR FURNISHING ITEMS REQUIRED BY REGULATIONS BUT NOT SPECIFIED
OR SHOWN ON THE DRAWINGS.
• RULINGS AND INTERPRETATIONS OF ENFORCING AGENCIES SHALL BE CONSIDERED PART OF THE
REGULATIONS.
• GENERAL CONTRACTOR TO SITE VERIFY ALL DIMENSIONS PRIOR TO CONSTRUCTION.
DISCLAIMER
• FOODSERVICE EQUIPMENT PLANS AND SPECIFICATIONS ARE INTENDED TO ILLUSTRATE TYPES AND
ARRANGEMENTS, INCLUDING SPACE AND UTILITY REQUIREMENTS, OF EQUIPMENT REQUIRED FOR THE PROJECT REGARDING THE DESIRED FUNCTION AND PRODUCT FLOW. THEY ARE INTENDED TO SERVE AS A REFERENCE TO THE LICENSED PROFESSIONAL ARCHITECT AND/OR ENGINEERS IN THE PREPARATION OF THEIR RESPECTIVE BID AND CONSTRUCTION DOCUMENTS. NO ARCHITECTURAL OR ENGINEERING DESIGN
SERVICES ARE INTENDED OR ASSUMED.
ERRORS AND OMISSIONS
• DESIGN DOCUMENTS INCLUDE DRAWINGS AND SPECIFICATIONS WHICH SHOULD BE REASONABLY CORRECT.
HOWEVER, THEIR COMPLETE ACCURACY IS NOT GUARANTEED. SHOULD DISCREPANCIES OCCUR, THEY
SHALL BE BROUGHT TO THE ATTENTION OF THE FOODSERVICE CONSULTANT AND/OR PROJECT
ARCHITECT/ENGINEER FOR THE CONFLICT TO BE CLARIFIED IN AN OFFICIAL REQUEST FOR INFORMATION.
• IT SHALL BE THE RESPONSIBILITY OF THE FOODSERVICE EQUIPMENT BIDDERS TO INFORM THE FOODSERVICE CONSULTANT OF ANY DISCREPANCIES FOUND WITHIN THESE DOCUMENTS TO INCLUDE:
WRITTEN SPECIFICATIONS, DRAWINGS, OR SCHEDULES, TO ALLOW AN OPPORTUNITY FOR THE CONSULTANT TO PREPARE AN ADDENDUM TO CORRECT SUCH DISCREPANCIES. BIDDING ON A KNOWN DISCREPANCY WITH THE INTENTION OF EQUIPMENT SUBSTITUTION OR PRICE GOUGING THROUGH CHANGE ORDERS WILL
NOT BE TOLERATED.
FOODSERVICE PLUMBING NOTES
• THIS PLUMBING PLAN AND COORDINATING SCHEDULE IS INTENDED TO SHOW ROUGH-IN LOCATIONS AND HEIGHTS, CONNECTION TYPES, POSITIONS, FIXTURE TYPES, AND LOAD REQUIREMENTS FOR FOODSERVICE EQUIPMENT SPECIFIED AND SCHEDULED FOR REUSE. THIS PLUMBING PLAN IS INTENDED TO SHOW PLUMBING REQUIREMENTS AND APPROXIMATE ROUGH-IN LOCATIONS ONLY. DO NOT USE FOR ACTUAL ROUGHING-IN. FOR FINAL ROUGH-IN LOCATIONS, SEE DIMENSIONED PLANS PROVIDED BY FOODSERVICE
EQUIPMENT CONTRACTOR.
• UTILITY REQUIREMENTS INDICATED ARE TO SERVE AS A REFERENCE TO THE LICENSED PROFESSIONAL ARCHITECT AND/OR ENGINEERS IN THE PREPARATION OF THEIR RESPECTIVE BID AND CONSTRUCTION DOCUMENTS. NO ARCHITECTURAL OR ENGINEERING DESIGN SERVICES ARE INTENDED OR ASSUMED. SEE
PLUMBING ENGINEER/ARCHITECT'S DRAWINGS FOR ADDITIONAL INFORMATION.
• PRIOR TO EQUIPMENT INSTALLATION, THE FOODSERVICE EQUIPMENT CONTRACTOR SHALL CHECK UTILITY ROUGH-IN LOCATIONS, COORDINATE FIELD CONDITIONS, AND CALL TO THE ATTENTION OF THE GENERAL CONTRACTOR ANY DISCREPANCIES BETWEEN THE FOODSERVICE UTILITY PLANS, THE EQUIPMENT
SPECIFIED, AND THE ROUGH-INS AS THEY OCCUR IN THE FIELD.
• SHOULD DISCREPANCIES OCCUR, THEY SHALL BE BROUGHT TO THE ATTENTION OF THE FOODSERVICE CONSULTANT AND/OR PROJECT ARCHITECT/ENGINEER FOR THE CONFLICT TO BE CLARIFIED IN AN OFFICIAL
REQUEST FOR INFORMATION.
• UTILITIES ARE BASED ON MANUFACTURER'S INFORMATION. ACTUAL ROUGHING-IN TO BE DETERMINED BY
CODE REQUIREMENTS AND/OR MANUFACTURER'S DIRECTIONS.
• EXPOSED UTILITY LINES AND PIPES SHALL BE INSTALLED IN A WAY THAT DOES NOT OBSTRUCT OR PREVENT THE CLEANING OF FLOORS, WALLS, AND CEILING AREAS (2 INCHES OFF WALLS AND 6 INCHES MINIMUM OFF
FLOORS).
• PLUMBING ENGINEER TO BE RESPONSIBLE FOR ALL CONCERNS AND ARRANGEMENTS REGARDING PENETRATIONS INTO THE FLOOR AND WALL. BUILDING OWNER TO APPROVE PRIOR TO CONSTRUCTION.
• PLUMBING ENGINEER TO LOCATE AREA DRAINS AS REQUIRED FOR GENERAL CLEANING OF THE FACILITY.
• PLUMBING COMPONENTS MUST NOT INTERFERE WITH THE OPERATION OF FOODSERVICE EQUIPMENT.
• WHEN APPLICABLE, PLUMBING CONTRACTOR TO INTERCONNECT DISHMACHINE WITH BOOSTER
HEATER/HEAT RECLAIMER AS PER MANUFACTURER'S INSTRUCTIONS.
• WHERE POSSIBLE, UTILITIES SHALL BE CONCEALED WITHIN BUILDING WALLS OR COLUMN CHASES, NOT RUN
ALONG WALL FACE. DO NOT STUB OUT OF FLOOR AND RUN ON THE FACE OF THE WALL.
• ANY AND ALL EXPOSED PIPING OR FITTINGS TO BE STAINLESS STEEL, CHROME PLATED, OR ENCLOSED IN A
CONCEALED, MOUNTED STAINLESS STEEL CHASE.
• ALL HORIZONTAL PIPING RUNS EXTENDED TO AND CONNECTED TO EQUIPMENT ITEMS SHALL BE AT THE
HIGHEST PRACTICAL ELEVATION AND NOT LESS THAN 6" ABOVE THE FINISHED FLOOR (TO PROVIDE
CLEARANCE FOR CLEANING).
• VENT PIPES TO BE CONCEALED IN WALLS OR COLUMN CHASES. USE LOOP VENTS FOR ISLAND FIXTURES, AS
ALLOWED BY LOCAL CODES.
• LINES ROUTED THROUGH EQUIPMENT SHALL NOT INTERFERE WITH THE INTENDED USE OF OR SERVICING OF
EQUIPMENT.
• DRINKING FOUNTAINS ARE BY PLUMBING TRADES. VERIFY UTILITY REQUIREMENTS WITH PLUMBING
ENGINEER.
• FLOOR DRAINS, FUNNEL FLOOR DRAINS, FLOOR SINKS, ETC. LOCATED AT FOOD PREP SINKS, POT WASHING SINKS, AND DISHMACHINES MUST HAVE REMOVABLE BASKETS TO CATCH FOOD PARTICLES. FLOOR TROUGH DRAINS MUST ALSO BE PROVIDED WITH REMOVABLE BASKETS AND TO BE INSTALLED FLUSH WITH THE FINISHED FLOOR. NO RAISED FLOOR SINKS SHALL BE INSTALLED. ALL DRAINS IN FOODSERVICE AREAS TO
BE RUN THROUGH GREASE INTERCEPTOR UNLESS OTHERWISE ALLOWED BY LOCAL CODE.
PLUMBING CONTRACTOR SHALL FURNISH AND INSTALL THE FOLLOWING:
• ALL PLUMBING WORK, LABOR, AND MATERIAL REQUIRED TO CONNECT THIS EQUIPMENT IS TO BE FURNISHED
BY PLUMBING CONTRACTOR UNLESS SPECIFICALLY CALLED FOR IN FOODSERVICE DOCUMENTS. PLUMBING CONTRACTOR SHALL INCLUDE ROUGHING-IN TO POINTS INDICATED ON ROUGHING-IN PLANS, FINAL CONNECTIONS FROM ROUGH-IN POINTS TO EQUIPMENT REQUIRING THOSE CONNECTIONS, AND THE SUPPLYING OF ALL NECESSARY MATERIALS AND LABOR FOR THIS WORK EXCEPT AS HEREINAFTER NOTED.
FOODSERVICE ELECTRICAL NOTES
• THIS ELECTRICAL PLAN AND COORDINATING SCHEDULE IS INTENDED TO SHOW ROUGH-IN LOCATIONS AND HEIGHTS, CONNECTION TYPES, POSITIONS, FIXTURE TYPES, AND LOAD REQUIREMENTS FOR FOODSERVICE EQUIPMENT SPECIFIED AND SCHEDULED FOR REUSE. THIS ELECTRICAL PLAN IS INTENDED TO SHOW ELECTRICAL REQUIREMENTS AND APPROXIMATE ROUGH-IN LOCATIONS ONLY. DO NOT USE FOR ACTUAL ROUGHING-IN. FOR FINAL ROUGH-IN LOCATIONS, SEE DIMENSIONED PLANS PROVIDED BY FOODSERVICE
EQUIPMENT CONTRACTOR.
• UTILITY REQUIREMENTS INDICATED ARE TO SERVE AS A REFERENCE TO THE LICENSED PROFESSIONAL ARCHITECT AND/OR ENGINEERS IN THE PREPARATION OF THEIR RESPECTIVE BID AND CONSTRUCTION DOCUMENTS. NO ARCHITECTURAL OR ENGINEERING DESIGN SERVICES ARE INTENDED OR ASSUMED. SEE
ELECTRICAL ENGINEER/ARCHITECT'S DRAWINGS FOR ADDITIONAL INFORMATION.
• PRIOR TO EQUIPMENT INSTALLATION, THE FOODSERVICE EQUIPMENT CONTRACTOR SHALL CHECK UTILITY ROUGH-IN LOCATIONS, COORDINATE FIELD CONDITIONS, AND CALL TO THE ATTENTION OF THE GENERAL CONTRACTOR ANY DISCREPANCIES BETWEEN THE FOODSERVICE UTILITY PLANS, THE EQUIPMENT
SPECIFIED, AND THE ROUGH-INS AS THEY OCCUR IN THE FIELD.
• SHOULD DISCREPANCIES OCCUR, THEY SHALL BE BROUGHT TO THE ATTENTION OF THE FOODSERVICE CONSULTANT AND/OR PROJECT ARCHITECT/ENGINEER FOR THE CONFLICT TO BE CLARIFIED IN AN OFFICIAL
REQUEST FOR INFORMATION.
• ELECTRICAL LOADS ARE BASED ON MANUFACTURER'S INFORMATION. MINIMUM CIRCUIT AMPACITY AND OVERCURRENT PROTECTION TO BE DETERMINED BY CODE REQUIREMENTS AND/OR MANUFACTURER'S
DIRECTIONS.
• EXPOSED UTILITY LINES AND PIPES SHALL BE INSTALLED IN A WAY THAT DOES NOT OBSTRUCT OR PREVENT THE CLEANING OF FLOORS, WALLS, AND CEILING MASTER SWITCH, INTERWIRE DOOR SWITCH, AND MAKE
FINAL CONNECTIONS.
• ELECTRICAL ENGINEER TO BE RESPONSIBLE FOR ALL CONCERNS AND ARRANGEMENTS REGARDING PENETRATIONS INTO THE FLOOR AND WALL. BUILDING OWNER TO APPROVE PRIOR TO CONSTRUCTION.
• ELECTRICAL ENGINEER TO LOCATE RECEPTACLES IN STORAGE AREA AS REQUIRED BY LOCAL BUILDING
CODE.
• ELECTRICAL COMPONENTS MUST NOT INTERFERE WITH THE OPERATION OF FOODSERVICE EQUIPMENT
• IT IS THE RESPONSIBILITY OF THE ELECTRICIAN TO REVIEW THE MANUFACTURERS' INSTALLATION
INSTRUCTIONS FOR ALL FOODSERVICE EQUIPMENT REQUIREMENT ELECTRICAL CONNECTIONS. SOME MAY
REQUIRE MULTIPLE CONNECTIONS.
ELECTRICAL CONTRACTOR SHALL FURNISH AND INSTALL THE FOLLOWING:
• ELECTRICAL ROUGH-IN
• ALL ELECTRICAL WORK, LABOR, AND MATERIAL REQUIRED TO CONNECT THIS EQUIPMENT IS TO BE
FURNISHED BY ELECTRICAL CONTRACTOR UNLESS SPECIFICALLY CALLED FOR IN FOODSERVICE
DOCUMENTS. ELECTRICAL CONTRACTOR SHALL INCLUDE ROUGHING-IN TO POINTS INDICATED ON ROUGHING-IN PLANS, FINAL CONNECTIONS FROM ROUGH-IN POINTS TO EQUIPMENT REQUIRING THOSE CONNECTIONS, AND THE SUPPLYING OF ALL NECESSARY MATERIALS AND LABOR FOR THIS WORK EXCEPT AS
HEREINAFTER NOTED.
• ELECTRICAL BUILDING SERVICES INCLUDING BUT NOT LIMITED TO CONDUIT, WIRING, LINE AND DISCONNECT SWITCHES, SAFETY CUTOFFS AND FITTINGS, CONTROL PANELS, FUSES. BOXES AND FITTINGS REQUIRED FOR COMPLETE INSTALLATION (EXCEPT INTERNAL WIRING AS SPECIFIED OR INDICATED OTHERWISE ON
DRAWINGS).
• FINAL ELECTRICAL CONNECTIONS TO EQUIPMENT SHALL BE BY THE ELECTRICAL CONTRACTOR, INCLUDING ALL REQUIRED MATERIALS (SUCH AS LINE AND DISCONNECT SWITCHES, SAFETY CUTOUTS, CONTROL PANELS, FUSE BOXES OR OTHER ELECTRICAL CONTROLS, FITTINGS, CONDUITS AND CONNECTIONS). ITEMS NOT FURNISHED AS A STANDARD PART OF THE EQUIPMENT BY THE MANUFACTURER ARE TO BE FURNISHED AND INSTALLED BY THE ELECTRICAL CONTRACTOR. STARTING SWITCHES PROVIDED BY FOODSERVICE EQUIPMENT CONTRACTOR AND FURNISHED LOOSE AS A STANDARD BY THE EQUIPMENT MANUFACTURER ARE
TO BE MOUNTED AND WIRED COMPLETE UNDER THE ELECTRICAL CONTRACT.
• FINAL CONNECTIONS, INCLUDING MOUNTING AND WIRING OF STARTERS AND SWITCHES FURNISHED AS PART
OF THE FOODSERVICE EQUIPMENT (UNLESS OTHERWISE INDICATED ON DRAWINGS).
• JUNCTION BOXES, ELECTRICAL OUTLETS, COVER PLATES, SWITCHES, ETC. NOT BUILT INTO FIXTURES OR EQUIPMENT. ALL RECEPTACLES, COVER PLATES, ETC. IN FOODSERVICE AREAS SHALL BE MOISTURE PROOF.
ELECTRICIAN TO PROVIDE BRUSHED STAINLESS STEEL COVER PLATES AT ALL SERVICE AND CONVENIENCE
OUTLETS.
• PLUGS AND CORDS THAT ARE NEMA RATED AND UL APPROVED FOR MANUFACTURER AND FABRICATED
EQUIPMENT.
• SHUNT-TRIP CIRCUIT BREAKERS OR DISCONNECTS FOR FIRE SUPPRESSION SYSTEM SHUT-OFF FOR EQUIPMENT BENEATH VENTILATORS AS REQUIRED BY NFPA-96 AND LOCAL, STATE, AND NATIONAL CODES.
• GFI RECEPTACLES AS REQUIRED BY LOCAL, STATE, AND NATIONAL CODES.
• DISCONNECTS OR OTHER DEVICES AS MAY BE REQUIRED BY LOCAL, STATE, AND NATIONAL CODES.
FOODSERVICE PLUMBING NOTES-CON'T
• ALL WATER AND WASTE SERVICE TO POINT OF ROUGH-IN AS SHOWN ON PLAN. ROUGH-IN OUTLETS TO STUB 4" OUT OF WALLS AT HEIGHT INDICATED FROM FINISHED FLOOR TO CENTERLINE OF SERVICE LINE. FLOOR ROUGH-INS TO STUB UP 3" ABOVE FINISHED FLOOR OR CURB. ALL FLOOR OPENINGS OR PENETRATIONS TO
BE SEALED WATERTIGHT.
• FINAL CONNECTIONS TO EQUIPMENT, INCLUDING ALL MATERIALS (STOPS, LINE STRAINERS, TAILPIECES, VALVES, FILTERS, TRAPS, CHECK VALVES, PIPING OF SUPPLY AND WASTE LINES FROM BUILDING SERVICE TO
ROUGH-IN, TUBING, ETC.) REQUIRED FOR A COMPLETE INSTALLATION.
• PRESSURE REDUCING AND/OR REGULATING VALVES FOR DISHWASHERS, BOOSTER HEATERS, OR AS
OTHERWISE NOTED IN ALL FOODSERVICE AREAS.
• FLOOR SINKS, COMPLETE WITH TOP GRATES AND REMOVABLE SEDIMENT BUCKETS. FIXTURES TO BE SET
FLUSH WITH FINISHED FLOOR, EXCEPT AS OTHERWISE NOTED.
• WASTE LINES, DIRECT OR INDIRECT, EXCEPT AS OTHERWISE NOTED. MINIMUM DIAMETER OF LINE SHALL BE AS INDICATED ON PLAN REGARDLESS OF CONNECTION, AND SHALL BE PITCHED DOWNWARD. MAINTAIN DRAIN LINES AS HIGH AS POSSIBLE (MINIMUM 6" CLEAR ABOVE FINISHED FLOOR) FOR SANITATION AND
CLEANING. WASTE LINES SHALL HAVE ADEQUATE CLEAN-OUT PROVISIONS PER LOCAL CODES.
• INDIRECT CONDENSATE DRAINLINES FOR WALK-IN COOLER/FREEZER, PITCHED 1/4" PER 12" OF HORIZONTAL
RUN AND TERMINATING IN A P-TRAP OVER A FLOOR SINK.
• INSULATION OF ALL DRAINLINES WITHIN FREEZER COMPARTMENTS.
• REQUIRED GREASE INTERCEPTORS, OUTSIDE THE BUILDING WHERE POSSIBLE. INDOOR GREASE
INTERCEPTORS ARE TO BE RECESSED, FLUSH WITH THE TOP OF THE FINISHED FLOOR (UNLESS SPECIFIED OTHERWISE) AND REMOVAL OF COVER SHALL NOT INTERFERE WITH THE OPERATION OF FOODSERVICE
EQUIPMENT. STRICT COORDINATION WITH EQUIPMENT AND LOCAL CODES REQUIRED IF GREASE
INTERCEPTOR IS TO BE SET ABOVE THE FLOOR OR UNDER EQUIPMENT.
• VACUUM BREAKERS AS REQUIRED BY LOCAL, STATE, AND NATIONAL CODES.
• INSULATION ON HOT WATER AND CONDENSATE RETURN LINES WITHIN THE FOODSERVICE AREAS. SUCH
LINES ARE TO BE COLOR-CODED ACCORDING TO LOCAL CODES.
• CLEAN OUT VALVES FOR STEAM AND CONDENSATE RETURN LINES.
• ITEMS NOT FURNISHED AS A STANDARD PART OF THE EQUIPMENT BY THE MANUFACTURER. FAUCETS
PROVIDED BY FOODSERVICE EQUIPMENT CONTRACTOR AND FURNISHED LOOSE AS STANDARD BY
EQUIPMENT MANUFACTURERS ARE TO BE MOUNTED AND PLUMBED COMPLETE UNDER THE PLUMBING
CONTRACT.
FOODSERVICE ELECTRICAL NOTES-CON''T
• ELECTRICAL COMPONENTS MUST NOT INTERFERE WITH THE OPERATION OF FOODSERVICE EQUIPMENT
• IT IS THE RESPONSIBILITY OF THE ELECTRICIAN TO REVIEW THE MANUFACTURERS' INSTALLATION
INSTRUCTIONS FOR ALL FOODSERVICE EQUIPMENT REQUIREMENT ELECTRICAL CONNECTIONS. SOME MAY
REQUIRE MULTIPLE CONNECTIONS.
ELECTRICAL CONTRACTOR SHALL FURNISH AND INSTALL THE FOLLOWING:
• ELECTRICAL ROUGH-IN
• ALL ELECTRICAL WORK, LABOR, AND MATERIAL REQUIRED TO CONNECT THIS EQUIPMENT IS TO BE
FURNISHED BY ELECTRICAL CONTRACTOR UNLESS SPECIFICALLY CALLED FOR IN FOODSERVICE
DOCUMENTS. ELECTRICAL CONTRACTOR SHALL INCLUDE ROUGHING-IN TO POINTS INDICATED ON ROUGHING-IN PLANS, FINAL CONNECTIONS FROM ROUGH-IN POINTS TO EQUIPMENT REQUIRING THOSE CONNECTIONS, AND THE SUPPLYING OF ALL NECESSARY MATERIALS AND LABOR FOR THIS WORK EXCEPT
AS HEREINAFTER NOTED.
• ELECTRICAL BUILDING SERVICES INCLUDING BUT NOT LIMITED TO CONDUIT, WIRING, LINE AND DISCONNECT SWITCHES, SAFETY CUTOFFS AND FITTINGS, CONTROL PANELS, FUSES. BOXES AND FITTINGS REQUIRED FOR COMPLETE INSTALLATION (EXCEPT INTERNAL WIRING AS SPECIFIED OR INDICATED OTHERWISE ON
DRAWINGS).
• FINAL ELECTRICAL CONNECTIONS TO EQUIPMENT SHALL BE BY THE ELECTRICAL CONTRACTOR, INCLUDING ALL REQUIRED MATERIALS (SUCH AS LINE AND DISCONNECT SWITCHES, SAFETY CUTOUTS, CONTROL PANELS, FUSE BOXES OR OTHER ELECTRICAL CONTROLS, FITTINGS, CONDUITS AND CONNECTIONS). ITEMS NOT FURNISHED AS A STANDARD PART OF THE EQUIPMENT BY THE MANUFACTURER ARE TO BE FURNISHED AND INSTALLED BY THE ELECTRICAL CONTRACTOR. STARTING SWITCHES PROVIDED BY FOODSERVICE EQUIPMENT CONTRACTOR AND FURNISHED LOOSE AS A STANDARD BY THE EQUIPMENT MANUFACTURER
ARE TO BE MOUNTED AND WIRED COMPLETE UNDER THE ELECTRICAL CONTRACT.
• FINAL CONNECTIONS, INCLUDING MOUNTING AND WIRING OF STARTERS AND SWITCHES FURNISHED AS PART
OF THE FOODSERVICE EQUIPMENT (UNLESS OTHERWISE INDICATED ON DRAWINGS).
• JUNCTION BOXES, ELECTRICAL OUTLETS, COVER PLATES, SWITCHES, ETC. NOT BUILT INTO FIXTURES OR EQUIPMENT. ALL RECEPTACLES, COVER PLATES, ETC. IN FOODSERVICE AREAS SHALL BE MOISTURE PROOF.
ELECTRICIAN TO PROVIDE BRUSHED STAINLESS STEEL COVER PLATES AT ALL SERVICE AND CONVENIENCE
OUTLETS.
• PLUGS AND CORDS THAT ARE NEMA RATED AND UL APPROVED FOR MANUFACTURER AND FABRICATED
EQUIPMENT.
• SHUNT-TRIP CIRCUIT BREAKERS OR DISCONNECTS FOR FIRE SUPPRESSION SYSTEM SHUT-OFF FOR EQUIPMENT BENEATH VENTILATORS AS REQUIRED BY NFPA-96 AND LOCAL, STATE, AND NATIONAL CODES.
• GFI RECEPTACLES AS REQUIRED BY LOCAL, STATE, AND NATIONAL CODES.
• DISCONNECTS OR OTHER DEVICES AS MAY BE REQUIRED BY LOCAL, STATE, AND NATIONAL CODES.
• ELECTRICIAN TO PROVIDE "TOMB STONE" STYLE HIGH IMPACT POLYCARBONATE OUTLET COVER WITH
HINGED BASE AND WATER PROOF GASKET AT +2" AFF. PROVIDE TYPE OF OUTLET AS SHOWN ON PLAN. UNIT SHALL HAVE A MINIMUM OF TWO 3/4" CONDUITS ENTER THROUGH THE BOTTOM OF EACH BOX. ALIGN
CONDUITS PARALLEL WITH TABLE OR CABINET.
WHEN APPLICABLE, THE ELECTRICAL CONTRACTOR SHALL PROVIDE CIRCUIT AND WIRING, INSTALL ELECTRICAL COMPONENTS (PROVIDED BY THE FOODSERVICE EQUIPMENT CONTRACTOR), AND INTERWIRE
BETWEEN THE FOLLOWING:
• EXHAUST HOODS FURNISHED BY FOODSERVICE EQUIPMENT CONTRACTOR WITH LIGHT FIXTURES, EMPTY
CONDUIT TO JUNCTION BOX, AND PRE-WIRE PACKAGE. ELECTRICAL CONTRACTOR TO INTERCONNECT TO
SWITCHES AND MAKE ALL FINAL CONNECTIONS.
• FIRE SUPPRESSION SYSTEM FURNISHED BY FOODSERVICE EQUIPMENT CONTRACTOR WITH APPLIANCE SHUT-OFF FEATURE. ELECTRICAL CONTRACTOR TO INTERCONNECT TO SHUNT TRIPS PER MANUFACTURER'S
DIAGRAM SO AS TO SHUT OFF ALL EQUIPMENT UNDER HOODS WITH ACTIVATED.
• POWER TO ALL ELECTRICALLY OPERATED COOKING EQUIPMENT UNDER HOODS TO BE FROM PANEL WHERE MAIN BREAKER IS INTERWIRED WITH THE FIRE SUPPRESSION SYSTEM AND/OR FIRE TERMINAL BLOCK IN THE UTILITY DISTRIBUTION SYSTEM SO THAT THE POWER SHUT-OFF IS ACHIEVED UPON EITHER MANUAL OR AUTOMATIC OPERATION OF THE FIRE SUPPRESSION SYSTEM. ALL INTERWIRING BY ELECTRICAL
CONTRACTOR.
• HOOD CONTROLS AND FIRE SUPPRESSION SYSTEMS EACH REQUIRE 24-HOUR EMERGENCY ELECTRICAL
SERVICE.
• ELECTRICAL CONTRACTOR TO PROVIDE CIRCUITS ON ROOF FOR EXHAUST/SUPPLY FANS. VERIFY UTILITIES REQUIRED WITH MECHANICAL CONTRACTOR AND LOCATION OF UNITS WITH GENERAL CONTRACTOR. FINAL
CONNECTIONS BY ELECTRICAL CONTRACTOR.
• DISHMACHINE SHALL BE FURNISHED BY FOODSERVICE EQUIPMENT CONTRACTOR PRE-WIRED TO INTEGRAL
CONTROL PANEL AND READY FOR FINAL CONNECTION BY ELECTRICAL CONTRACTOR.
• DISHMACHINE SHALL BE FURNISHED WITH EXHAUST FAN CONTROL SWITCH BY FOODSERVICE EQUIPMENT CONTRACTOR. ELECTRICAL CONTRACTOR TO INTERCONNECT TO EXHAUST FAN SO THAT FAN OPERATES
WHEN DISHMACHINE IS TURNED ON.
• DISHMACHINE SHALL BE FURNISHED WITH LIMIT SWITCH BY FOODSERVICE EQUIPMENT CONTRACTOR.
ELECTRICAL CONTRACTOR TO INTERCONNECT AND MAKE FINAL CONNECTIONS.
• COLD STORAGE ROOMS SHALL BE FURNISHED BY FOODSERVICE EQUIPMENT CONTRACTOR WITH PRE- WIRED LIGHT AND SWITCH AT DOOR PANEL. ELECTRICAL CONTRACTOR TO PROVIDE INTERCONNECTING
WIRING TO EXTRA LIGHT FIXTURES AND MAKE FINAL CONNECTIONS.
• REFRIGERATION SYSTEMS SHALL BE FURNISHED AND INSTALLED BY FOODSERVICE EQUIPMENT CONTRACTOR. DEFROST CONTROL WIRING BETWEEN FREEZER CONDENSING UNIT AND EVAPORATOR COIL SHALL BE BY ELECTRICAL CONTRACTOR. FINAL ELECTRICAL DROPS AND DISCONNECTS FOR CONDENSING
UNITS AND EVAPORATOR COILS SHALL BE FURNISHED BY ELECTRICAL CONTRACTOR
• DISPOSERS SHALL BE FURNISHED BY FOODSERVICE EQUIPMENT CONTRACTOR WITH SOLENOID VALVE AND AUTO-REVERSING CONTROL CENTER WITH MAGNETIC STARTER AND START/STOP BUTTONS. INTERWIRING
AND FINAL CONNECTION BY ELECTRICAL CONTRACTOR.
• UTILITY DISTRIBUTION SYSTEM SHALL BE FURNISHED BY FOODSERVICE EQUIPMENT CONTRACTOR PRE- WIRED AND READY FOR FINAL CONNECTION BY ELECTRICAL CONTRACTOR. FOODSERVICE EQUIPMENT CONTRACTOR TO FURNISH CORD AND PLUG SETS FOR INSTALLATION TO EQUIPMENT BY ELECTRICAL CONTRACTOR. ANY NECESSARY INTERWIRING AND FINAL CONNECTIONS TO THE EQUIPMENT SHALL BE BY
THE ELECTRICAL CONTRACTOR.
• AIR CURTAIN FAN TO BE FURNISHED BY FOODSERVICE EQUIPMENT CONTRACTOR WITH DOOR SWITCH.
ELECTRICAL CONTRACTOR TO PROVIDE MASTER SWITCH, INTERWIRE DOOR SWITCH, AND MAKE FINAL
CONNECTIONS.
SHEET ID
D R
A W
N B
Y
D E
S
IG
N B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
F
IL
E N
A M
E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
C H
E C
K E
D B
Y
A
C A
T E
G O
R Y
C O
D E
A N
S I D
P lo t D a te
F ile P a th
US Army Corps of Engineers ®
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
B
C
D
E
F
G
H
J
K
L
M
N
P
B
IM
/F o rt B ra g g
C D
C /F o rt
L ib e rt y C
D C
.r v t
/7
/2
:2
:2
A
M
N O
V E
M B
E R
W H
N -2
-B
-4
L H
O W
A R
D
L H
O W
A R
D
R R
U P
P E
-1
-0
QF000
F O
O D
S E
R V
IC
E
G E
N E
R A
L N
O T
E S
S A
V A
N N
A H
D
IS
T R
IC
T
W
O
G L E
T H
O R
P E
A V
E
S A
V A
N N
A H
G
A
C A
M A
C H
O F
O O
D S
E R
V
IC
E D
E S
IG
N
M
E D
L O
C K
B R
ID
G
E R
D N
O R
C R
O S
S G
A
C A
M A
C H
O U
S A
.C O
M
.5
.1
F O
R T
L
IB
E R
T Y
N
O R
T H
C A
R O
L
IN
A C
H
IL
D D
E V
E L O
P M
E N
T C
E N
T E
R F
Y P
N
V O
L U
M N
B U
IL
D
IN
G
J C
A M
A C
H O
R E
A D
Y T
O A
D V
E R
T
IS
E
R T
A
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E
R
E V
IS
E
D B
Y A
M E
N D
M E
N T
JA
N
TODDLER/PRESCHOOL
ACTIVITY ROOM
D165
PRE-K/
KINDERGARTEN
ACTIVITY ROOM
D166
TODDLER/PRESCHOOL
ACTIVITY ROOM
D168
TODDLER/PRESCHOOL
ACTIVITY ROOM
D167
TODDLER/PRESCHOOL
ACTIVITY ROOM
D171
TODDLER/PRESCHOOL
ACTIVITY ROOM
D172
D169
P-2A
P-5A
PL403
PL403
WH-1
CBV-1 CBV-2
CBV-3
CBV-4
CBV-5
3 3
3/4"
HWR
1 1/2"
HW
2 1/2"
CW
2 1/2"
CW
3/4"
HWR
1 1/2"
HW
2" CW
3/4"
HWR
1 1/2"
HW
2" CW
1 1/4"
HW 3/4"
HWR
WHA-A
WHA-A
1" CW
SHEET ID
D R
AW
N
B Y:
D
ES
IG
N
B Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
FI
LE
N
AM
E:
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
U .S
. A R
M Y
C O
R
PS
O F
EN
G
IN
EE
R S
C H
EC
KE
D B
Y:
A
C
AT
EG
O
R Y
C O
D E:
AN
SI
D
NORTH ARROW
GENERAL SHEET NOTES
KEY PLAN
PLAN NORTH
Pl ot
D at e:
Fi le P at h:
US Army Corps of Engineers ®
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
B
C
D
E
F
G
H
J
K
L
M
N
P
C :\U se rs
\k 6e nd cm
9\ D oc um e n ts
\F Y2
6 _
PN
2 1
1_ C
D C
_P
LU
M B_
R
_ k 6e nd cm
9.
rv t 1/
7/ 2 0
:3 4:
A
M
N O
VE
M
BE
R
W
2H N
-2 5-
B-
C .M
EL
EN
D
EZ
N
AR
VA
EZ
C .M
EL
EN
D
EZ
N
AR
VA
EZ
J.
D
EA
C
O N
0-
-0
PL105
FI
R
ST
F
LO
O
R D
O M
ES
TI
C P
LU
M
BI
N
G P
LA
N
AR
EA
D
SA
VA
N N
AH
D
IS
TR
IC
T
W . O
G
LE
TH
O
R
PE
A
VE
SA
VA
N
N
AH
, G A
FO
R
T
LI
BE
R
TY
, N
O R
TH
C
AR
O
LI
N
A C
H
IL
D D
EV
EL
O
PM
EN
T
C
EN
TE
R
FY
P N
VO
LU
M
E
-B U
IL
D
IN
G
S.
M
AR
IK
O
R
EA
D Y
TO
A
D
VE
R
TI
SE
(R
TA
A B
C
D
1/8" = 1'-0"
FIRST FLOOR DOMESTIC PLUMBING PLAN - AREA D1 8 6 2 0 8 164
1. PIPING SHOWN OFFSET FOR CLARITY.
2. SEE SHEET P-001 FOR LEGEND AND NOTES.
3. PROVIDE ACCESS PANELS ON WALLS FOR ACCESS TO ALL PLUMBING
EQUIPMENT, CLEANOUTS, ETC.
4. CONTRACTOR TO LOCATE ALL ABOVE CEILING EQUIPMENT, VALVES, ETC. IN
ACCESSIBLE CEILING AREAS. DO NOT LOCATE THESE ITEMS ABOVE HARD CEILING
AREAS.
5. INSTALL SHUT OFF VALVES AT EACH FIXTURE. INSTALL BRANCH SHUTOFF VALVES
WHERE INDICATED ON PLANS. LOCATE AND ORIENT VALVE OPERATORS FOR EASE OF
ACCESS AND FULL LIMITS OF OPERATION.
6. MECHANICAL EQUIPMENT SHALL BE CLEAR OF OBSTRUCTIONS WITHIN ITS CLEARANCE
ON THE SIDES AS WELL AS BELOW THE UNITS. FILTERS SHALL BE ACCESSIBLE TO
REPLACE, AND UNITS SHALL BE EASY TO REMOVE FOR REPLACEMENT AND
MAINTENANCE. MAINTENANCE SPACE IS CONSIDERED MANDATORY AND CONFLICT WITH
OTHER DISCIPLINES, AND BUILDING SYSTEMS SUCH AS BUT NOT LIMITED TO;
FIRE SPRINKLERS, FIRE ALARM DEVICES, ELECTRICAL DEVICES, PIPING, WIRING,
CONDUIT, LIGHTING, AND TEMPERATURE CONTROL COMPONENTS WILL BE REQUIRED
TO BE ALTERED, ADJUSTED, CHANGED, AND/OR REROUTED AT THE
CONTRACTOR'S EXPENSE.
M
AR
K D
ES
C
R
IP
TI
O
N D
AT
E
R
EV
IS
ED
IN
A C
C O
R D
AN
C
E W
IT
H
A M
EN
D
M
EN
T
JA
N
1. HW EXPANSION LOOP SIZE HW EXPANSION LOOPS AT 16" WIDE BY 32" TALL.
PIPE ANCHORS AND GUIDES SEE DETAIL 5 EXPANSION LOOP DETAIL (TYP.) ON
SHEET PL503.
2. HWR EXPANSION LOOP (TYP.) SIZE HWR EXPANSION LOOPS AT 8.8" WIDE BY 17.5" TALL.
PIPE ANCHORS AND GUIDES SEE DETAIL 5 EXPANSION LOOP DETAIL (TYP.) ON
SHEET PL503.
3. CALIBRATED BALANCE VALVE WITH CHECK VALVE AND SHUT OFF VALVES
(TYPICAL ALL DOMESTIC HOT WATER RETURNS). SEE DETAIL 4 ON SHEET PL505.
SEE CALIBRATED BALANCE VALVE SCHEDULE ON SHEET PL602 FOR DESIGN FLOW.
KEYED NOTES
PIPING SYMBOLS
CHILLED WATER SUPPLY
CHILLED WATER RETURN
MAKE-UP WATER
REFRIGERANT HOT GAS
REFRIGERANT SUCTION
REFRIGERANT LIQUID
PIPE ANCHOR
PIPE GUIDE
EXPANSION JOINT
VENTURI
GATE VALVE
GLOBE VALVE
HOSE VALVE WITH CAP
BUTTERFLY VALVE
CHECK VALVE
BALANCING VALVE
CALIBRATED BALANCING VALVE
BALL VALVE
PLUG VALVE
SOLENOID VALVE
SAFETY OR PRESSURE RELIEF, ANGLE VALVE
SAFETY OR PRESSURE RELIEF, STRAIGHT THRU VALVE
PRESSURE REDUCING VALVE (PRV)
AUTOMATIC CONTROL VALVE, 2 WAY
AUTOMATIC CONTROL VALVE, 3 WAY
ELECTRICALLY OPERATED VALVE
BLIND FLANGE
LATERAL Y
CAP
ELBOW, 90º
ELBOW, 90º TURNED UP
ELBOW, 90º TURNED DOWN
ELBOW, 45º
TEE
TEE, OUTLET TURNED UP
TEE, OUTLET TURNED DOWN
CONCENTRIC REDUCER
ECCENTRIC REDUCER (STRAIGHT INVERT)
UNION
FLEXIBLE PIPE CONNECTION
PRESSURE GAGE
TEMPERATURE GAGE
THERMOMETER
PRESSURE/TEMPERATURE TEST PORT
SANITARY DRAIN
STORM DRAIN
VENT
ACID WASTE DRAIN
ACID VENT
DRAINLINE
DOMESTIC COLD WATER
DOMESTIC HOT WATER
DOMESTIC HOT WATER CIRCULATING
GAS
GAS VENT
COMPRESSED AIR
MEDICAL AIR
MEDICAL OXYGEN
MEDICAL VACUUM
NITROGEN
NITROUS OXIDE
FIRE PROTECTION WATER SUPPLY
FIRE DEPARTMENT CONNECTION
FP
NOX
NIT
VAC
OXY
AIR
A
GV
G
D
AV
AW
CWS
CWR
MU
HG
RS
RL
PA
PG
S
WFD
WATERFLOW DETECTOR
OS&Y VALVE
PLUG
FLOOR DRAIN W/TRAP
WALL CLEAN OUT (FCO, FLOOR CLEAN OUT)
WATER HAMMER ARRESTER
HOSE BIBB
WALL HYDRANT
DOUBLE CHECK VALVE BACKFLOW PREVENTER
REDUCED PRESSURE BACKFLOW PREVENTER
Y-TYPE STRAINER
Y-TYPE STRAINER WITH HOSE DRAIN VALVE
UPRIGHT FIRE SPRINKLER HEAD
PENDANT FIRE SPRINKLER HEAD
SIDEWALL FIRE SPRINKLER HEAD
VACUUM GAGE
*PROVIDE SHUT OFF COCK WITH SIPHON OR PULSATION DAMPENER.
FD
WCO
WHA
HB
WH
12x6
90º ELBOW, ROUND OR FLAT OVAL
(SMOOTH OR 5 PIECE ELBOWS)
MITERED 90º ELBOW, ROUND OR FLAT OVAL
RECTANGULAR DUCT WITH 1" INTERNAL LINER
DUCT SIZE IS THE CLEAR INSIDE DIMENSION
45º ELBOW, ROUND OR FLAT OVAL
(SMOOTH OR 3 PIECE ELBOWS)
DIVIDED FLOW FITTING
TAP-IN BRANCH, RECTANGULAR
BRANCH DUCT, CONICAL LATERAL FITTING, ROUND
OR FLAT OVAL
BRANCH DUCT, CONICAL TEE FITTING, ROUND OR
FLAT OVAL
BRANCH DUCT, "Y" FITTING, ROUND OR FLAT OVAL
SUPPLY DUCT SECTION, RECTANGULAR
EXHAUST OR RETURN DUCT SECTION, RECTANGULAR
90º ELBOW TURNED UP, RECTANGULAR
90º ELBOW TURNED DOWN, RECTANGULAR
90º ELBOW TURNED UP, ROUND; FLAT OVAL SIMILAR
90º ELBOW TURNED DOWN, ROUND; FLAT OVAL
SIMILAR
CEILING DIFFUSER (ARROWS INDICATE THROW
DIRECTIONS)
CEILING DIFFUSER (ARROWS INDICATE THROW
DIRECTIONS)
CEILING REGISTER OR GRILLE (RETURN OR EXHAUST)
CEILING REGISTER OR GRILLE (SUPPLY)
REGISTER OR GRILLE
CEILING DIFFUSER WITH FLEXIBLE DUCT
CONNECTION (ARROWS INDICATE THROW
DIRECTION)
LIGHT TROFFER WITH FLEXIBLE DUCT CONNECTION.
"S" INDICATES SUPPLY, NUMBER INDICATES CFM
CEILING LINEAR SLOT OR INTEGRATED CEILING
DIFFUSER (CLSD) WITH FLEXIBLE DUCT CONNECTION
(ARROWS INDICATE THROW DIRECTION)
STATIC PRESSURE SENSOR
HUMIDIFIER
SECURITY BAR
DOUBLE WALL DUCTWORK (2" INTERNAL INSULATION
WITH PERFORATED LINER)
DUCT DIMENSIONS ARE OUTSIDE SHEETMETAL
DIMENSIONS
24x24 DW
SB
H
SPS
S-000
VD
VD
VD
12X6(L)
MISC SYMBOLS DOUBLE LINE
DUCTWORK SYMBOLS
DOUBLE LINE
DUCTWORK SYMBOLS
SINGLE LINE
DUCTWORK SYMBOLS
PIPING SYMBOLS
36"Ø
36x18
VD
M
BDD
FD
3FD
FSD
SD
R
R
D
D
DF
SPS
RECTANGULAR DUCT (FIRST FIGURE IS FOR SIDE SHOWN,
SECOND FIGURE IS FOR SIDE NOT SHOWN)
ROUND DUCT
FLAT OVAL DUCT (FIRST FIGURE IS FOR SIDE SHOWN,
SECOND FIGURE IS FOR SIDE NOT SHOWN)
FLEXIBLE ROUND DUCT
FLEXIBLE DUCT CONNECTION
MANUAL OPPOSED BLADE VOLUME DAMPER
MOTORIZED DAMPER
BACK DRAFT DAMPER
FIRE DAMPER, 1 1/2 HOUR FIRE RATED
FIRE DAMPER, 3 HOUR FIRE RATED
COMBINATION FIRE/SMOKE DAMPER
SMOKE DAMPER
DUCT TRANSITION
INCLINED RISE W/RESPECT TO AIR FLOW, RECTANGULAR
INCLINED DROP W/RESPECT TO AIR FLOW, RECTANGULAR
INCLINED RISE W/RESPECT TO AIR FLOW, ROUND OR FLAT
OVAL
INCLINED DROP W/RESPECT TO AIR FLOW, ROUND OR
FLAT OVAL
90º ELBOW, RECTANGULAR
90º ELBOW, ROUND OR FLAT OVAL (SMOOTH OR 5-PIECE
ELBOWS)
45º ELBOW, RECTANGULAR
45º ELBOW, ROUND OR FLAT OVAL (SMOOTH OR 3-PIECE
ELBOWS)
DIVIDED FLOW FITTING, RECTANGULAR
RECTANGULAR TAP-IN BRANCH OR ROUND OR FLAT OVAL
CONICAL TEE
INCLINED CONICAL TAKE-OFF, ROUND OR FLAT OVAL
"Y" FITTING, ROUND OR FLAT OVAL
90º ELBOW TURNED UP, RECTANGULAR
90º ELBOW TURNED DOWN, RECTANGULAR
90º ELBOW TURNED UP, ROUND; FLAT OVAL SIMILAR
90º ELBOW TURNED DOWN, ROUND; FLAT OVAL SIMILAR
CEILING DIFFUSER (ARROWS INDICATE THROW
DIRECTIONS)
CEILING REGISTER OR GRILLE, EXHAUST OR RETURN
CEILING REGISTER OR GRILLE, SUPPLY
STATIC PRESSURE SENSOR
END OF DUCT RUN
ES
H
T
N
S
UC
12x6 OR 12/6
12"Ø
12x6
VD
M
BDD
FD
3FD
FSD
SD
R
D
R
D
ROOM NUMBER
ROUND DUCT
FLAT OVAL DUCT
POINT OF CONNECTION BETWEEN NEW AND EXISTING
WORK
POINT BETWEEN EXISTING WORK TO REMAIN AND
EXISTING WORK TO BE REMOVED
EXISTING WORK TO BE REMOVED
EXISTING WORK TO REMAIN
WATER SENSOR (LOCATED BELOW ACCESS FLOOR)
HVAC SYSTEM EMERG SHUT-OFF SWITCH
SMOKE DETECTOR
INTERVAL TIMER
HUMIDISTAT
THERMOSTAT
NIGHT THERMOSTAT
WALL SWITCH
PT
SD
* PROVIDE SHUT OFF COCK WITH SIPHON OR PULSATION DAMPENER.
RECTANGULAR DUCT (FIRST FIGURE IS FOR SIDE
SHOWN, SECOND FIGURE IS FOR SIDE NOT SHOWN)
ROUND DUCT
FLAT OVAL DUCT (FIRST FIGURE IS FOR SIDE SHOWN,
SECOND FIGURE IS FOR SIDE NOT SHOWN)
FLEXIBLE ROUND DUCT
FLEXIBLE DUCT CONNECTION
MANUAL OPPOSED BLADE VOLUME DAMPER
MOTORIZED DAMPER
BACK DRAFT DAMPER
FIRE DAMPER, 1 1/2 HOUR FIRE RATED
FIRE DAMPER, 3 HOUR FIRE RATED
COMBINATION FIRE/SMOKE DAMPER
SMOKE DAMPER
DUCT TRANSITION, ROUND OR FLAT OVAL TO
RECTANGULAR
DUCT TRANSITION, RECTANGULAR TO ROUND OR
FLAT OVAL
DUCT TRANSITION, RECTANGULAR, ROUND, OR FLAT
OVAL
INCLINED RISE W/RESPECT TO AIR FLOW,
RECTANGULAR
INCLINED DROP W/RESPECT TO AIR FLOW,
RECTANGULAR
INCLINED RISE W/RESPECT TO AIR FLOW, ROUND OR
FLAT OVAL
INCLINED DROP W/RESPECT TO AIR FLOW, ROUND OR
FLAT OVAL
90º ELBOW, RECTANGULAR WITH TURNING VANES
45º ELBOW, RECTANGULAR WITH TURNING VANES
DOOR UNDERCUT, SEE DOOR SCHEDULES FOR SIZE
CO CARBON MONOXIDE SENSOR
T
SS
V
V
SD
TS TEMPERATURE SENSOR
SHEET ID
D R
A W
N B
Y
D E
S
IG
N B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
F
IL
E N
A M
E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
C H
E C
K E
D B
Y
A
C A
T E
G O
R Y
C O
D E
A N
S I D
P lo t D a te
F ile P a th
US Army Corps of Engineers ®
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
B
C
D
E
F
G
H
J
K
L
M
N
P
C
U s e rs \K
E
N X
S W
W \O n e
D ri v e
U S
A rm y C o rp s o f E n g in e e rs \D o c u m e n ts
\F Y
P
N
C
D C
H
V A
C R
K
E N
X S
W W
.r v t
/7
/2
:4
:2
A
M
N O
V E
M B
E R
W H
N -2
-B
-4
S W
Y L L
IE
S W
Y L L
IE
J D
E A
C O
N -1
-0
M-001
H V
A C
L E
G E
N D
S A
V A
N N
A H
D
IS
T R
IC
T
W
O
G L E
T H
O R
P E
A V
E
S A
V A
N N
A H
G
A
F O
R T
L
IB
E R
T Y
N
O R
T H
C A
R O
L
IN
A C
H
IL
D D
E V
E L O
P M
E N
T C
E N
T E
R F
Y P
N
V O
L U
M E
B U
IL
D
IN
G
S M
A R
IK
O
R E
A D
Y T
O A
D V
E R
T
IS
E
R T
A
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E
R
E V
IS
E
D I
N A
C C
O R
D A
N C
E W
IT
H
A M
E N
D M
E N
T
J A
N
A. REFER TO SPECIFICATIONS FOR MATERIALS AND METHODS OF CONSTRUCTION
B. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR THE EXACT LOCATION OF ALL
CEILING MOUNTED DEVICES
C. REFER TO ARCHITECTURAL INTERIOR ELEVATION DRAWINGS, WHERE THE ARCHITECT HAS
DRAWN SUCH ELEVATIONS, FOR THE LOCATIONS OF ALL WALL MOUNTED DEVICES
D. ALL DUCTWORK SIZES SHOWN ARE FREE AIR STREAM DIMENSIONS
E. COORDINATE ALL SLAB PENETRATIONS AND SLEEVES PRIOR TO EACH CONCRETE PLACEMENT
F. PERFORM WORK IN ACCORDANCE WITH THE LATEST EDITIONS, REVISIONS, AMENDMENTS, OR APPLICABLE STATUTES, ORDINANCES, CODES OR REGULATIONS OF FEDERAL, STATE AND LOCAL
AUTHORITIES HAVING JURISDICTION IN EFFECT ON THE DATE BIDS ARE RECEIVED, UNLESS
SPECIFIED OTHERWISE
G. WHERE APPROVAL CODES HAVE BEEN ESTABLISHED BY OSHA, UNDERWRITERS LABORATORY,
AMERICAN CODES, ANSI, ASME, ASA, ASHRAE, ASTM, ARI, NEC, NFPA, SMACNA, OR THE STATE
FIRE INSURANCE REGULATORY BODY THESE STANDARDS SHALL BE FOLLOWED WHETHER OR
NOT INDICATED ON THE DRAWINGS AND SPECIFICATIONS
H. ALL WIRING AND ELECTRICAL CONTROLS SHALL BE INSTALLED IN ACCORDANCE WITH NFPA 70 (N.E.C.). MOTOR EFFICIENCIES SHALL BE IN ACCORDANCE WITH ELECTRICAL SPECIFICATIONS
I. WIRING AND CONDUIT FOR THE PROPER OPERATION OF MOTORIZED DAMPERS IS A REQUIREMENT OF THE CONTRACT. COORDINATION OF THESE CIRCUITS SHALL BE THE RESPONSIBILITY OF THE
HVAC SYSTEMS CONTRACTOR
J. ALL INDICATED AIR FLOW CAPACITIES WERE CALCULATED AT ALTITUDE CONDITIONS
K. ALL FLOOR MOUNTED EQUIPMENT IN MECHANICAL ROOMS SHALL BE MOUNTED ON 6" HIGH
HOUSEKEEPING PADS. THESE PADS SHALL EXTEND 6" BEYOND THE EQUIPMENT IN ALL
DIRECTIONS. SEE STRUCTURAL DETAILS FOR PAD CONSTRUCTION
L. DRAWINGS ARE SCHEMATIC AND ARE TO SHOW DESIGN INTENT, AND IT IS THE RESPONSIBILITY
OF THE CONTRACTOR TO COORDINATE PLACEMENTS
M. PROVIDE ACCESS PANELS AS REQUIRED TO PROVIDE ACCESS TO ALL MECHANICAL EQUIPMENT, VALVES, AND DAMPERS
N. ALL OUTSIDE EQUIPMENT, AT GRADE SHALL BE MOUNTED ON 6" HIGH HOUSEKEEPING PADS.
THESE PADS SHALL EXTEND 6" BEYOND THE EQUIPMENT IN ALL DIRECTIONS. SEE STRUCTURAL
DETAILS FOR PAD CONSTRUCTION
O. ALL PIPING SHALL COMPLETELY AVOID FOUNDATION AND FOOTINGS. SEAL ALL FLOOR AND WALL
PENETRATIONS. REFER TO PENETRATION DETAILS
P. CONTRACTOR SHALL COORDINATE ALL HVAC EQUIPMENT, PIPING, AND DUCTWORK WITH ALL
OTHER TRADES.
Q. CHILLER SHALL BE LOCATED IN MECHANICAL EQUIPMENT YARD
R. CHILLED WATER PIPING TO/FROM CHILLER SHALL BE ABOVE GROUND
S. ALL ROOF-MOUNTED EQUIPMENT SHALL BE COLOR-KEYED WITH ADJACENT EXTERIOR COLOR
T. COORDINATE INDOOR DUCTLESS SPLIT UNITS INSTALLATION LOCATIONS WITH ELECTRICAL
EQUIPMENT, TELECOMMUNICATION EQUIPMENT, CABLE TRAYS, RACKS, AND VSS EQUIPMENT IN
TELECOMMUNICATION ROOM, ELECTRICAL ROOMS, VSS EQUIPMENT ROOM
U. ALL WALL MOUNTED THERMOSTATS, TEMPERATURE SENSORS, SPACE PRESSURE SENSORS AND
CO SENSORS SHALL BE INSTALLED 4'-0" ABOVE FINISHED FLOOR UNLESS NOTED OTHERWISE.
LOCATIONS SHOWN ON FLOOR PLANS FOR THERMOSTATS, TEMPERATURE SENSORS, SPACE
PRESSURE SENSORS AND CO SENSORS ARE INTENDED TO INDICATE THE SELECTED AREA OF
OPERATION. CONTRACTOR SHALL FIELD COORDINATE EXACT LOCATIONS TO ENSURE THE
THERMOSTATS, TEMPERATURE SENSORS, SPACE PRESSURE SENSORS OR CO SENSORS ARE
NOT OBSTRUCTED BY ANY BUILDING ELEMENT OR FURNISHING FOR PROPER OPERATION
V. ALL ROOF-MOUNTED EQUIPMENT (I.E. EXHAUST FANS, ETC.) SHALL BE ATTACHED TO
ADEQUATELY-SIZED PRE-FABRICATED EQUIPMENT MOUNTING SUPPORTS. CONFIGURATION OF
MOUNTING SUPPORTS SHALL BE COORDINATED WITH THE ACTUAL EQUIPMENT INSTALLED.
MOUNTING SUPPORTS SHALL BE ATTACHED TO THE ROOF IN A MANNER COMPATIBLE WITH THE
ROOFING SYSTEM MANUFACTURER'S INSTALLATION AND MATERIAL REQUIREMENTS. MOUNTING
SUPPORTS SHALL BE WEATHER RESISTANT AND SUITABLE FOR LOCAL TEMPERATURES AND
WIND SPEED CONDITIONS
W. ALL FAN AND PUMP MOTORS USED IN VARIABLE FLOW SYSTEMS SHALL BE SUITABLE AND
DESIGNED FOR VARIABLE SPEED APPLICATIONS
X. DURING CONSTRUCTION THE CONTRACTOR SHALL PROTECT ALL STORED AND ON-SITE
EQUIPMENT AND MATERIALS FROM MOISTURE DAMAGE AND CONTAMINATION
Y. ALL PIPING AND EQUIPMENT SHALL BE INSTALLED SO THAT MAINTENANCE OR REMOVAL CAN BE
ACCOMPLISHED WITHOUT THE REMOVAL OF ANY OTHER PIPING AND/OR EQUIPMENT
Z. PROVIDE SLEEVES AND PREPARED OPENINGS FOR DUCTS, PIPING, AND OTHER PENETRATING
ITEMS AS REQUIRED AND PER SPECIFICATIONS
AA. SEE CONTROL SHEET FOR LOCATIONS OF CONTROLS SENSORS/TRANSMITTERS. COORDINATE
INSTALLATION OF CONTROL DEVICES WITH CONTROLS CONTRACTOR
BB. ALL DRYER EXHAUST VENT WALL CAPS SHALL BE COLOR-KEYED WITH ADJACENT EXTERIOR
COLOR
CC. ALL EQUIPMENT AT GRADE (I.E. AIR COOLED CHILLER, MAKE-UP AIR UNIT, DUCTLESS SPLIT
SYSTEM OUTDOOR UNITS, ETC.) SHALL BE ATTACHED TO ADEQUATELY-SIZED PRE-FABRICATED
EQUIPMENT MOUNTING SUPPORTS. CONFIGURATION OF MOUNTING SUPPORTS SHALL BE
COORDINATED WITH THE ACTUAL EQUIPMENT INSTALLED. MOUNTING SUPPORTS SHALL BE
WEATHER RESISTANT AND SUITABLE FOR LOCAL TEMPERATURES AND WIND SPEED CONDITIONS
DD. PROPER EXPANSION SEPARATION PROVISIONS SHALL BE INCORPORATED INTO THE
MECHANICAL SYSTEM (PIPING, DUCTWORK, EQUIPMENT, CONTROLS WIRING, ETC.) THAT
CROSSES BUILDING EXPANSION SEPARATION JOINTS. EXPANSION BRACING, RESTRAINTS, AND
SEPARATION PROVISIONS SHALL BE DESIGNED AND INSTALLED IN ACCORDANCE WITH THE
PROJECT SPECIFICATIONS
EE. ALL DUCTWORK SYSTEMS SHALL MEET THE REQUIREMENTS OF SEAL CLASS A. DUCT STATIC
PRESSURE CLASSIFICATION PER SMACNA DUCT CONSTRUCTION STANDARDS SHALL BE AS
FOLLOWS: 4 IN. W.G. FOR SUPPLY DUCT UPSTREAM OF VAV TERMINAL UNITS, 2 IN. W.G. FOR
SUPPLY DUCT DOWNSTREAM OF VAV TERMINAL UNITS AND FOR SUPPLY DUCT SERVED BY FAN
COIL UNITS, AND 2 IN. W.G. FOR OUTSIDE AIR, EXHAUST AIR, SUPPLY AIR AND RETURN AIR DUCT
SYSTEMS.
GENERAL NOTES
| QF000 FOODSERVICE GENERAL NOTES |
| PL105 FIRST FLOOR DOMESTIC PLUMBING PLAN - AREA D |
| M-001 HVAC LEGEND |