This document provides details for a federal contract solicitation for repair work. The U.S. Army Corps of Engineers Savannah District will issue solicitation number W912HN23B4000 for repairs to Building 399 Sections E and F at Fort Benning, Georgia. The project magnitude is estimated between $25-$100 million. The contract type will be firm-fixed-price, and it is offered as a 100% small business set-aside under NAICS code 236220. The period of performance is 700 calendar days after notice to proceed. The proposal due date is July 14, 2023, and bids must be submitted electronically through PIEE. A site visit will be held on June 21, 2023, at 1:00 PM. The scope of work involves repairing and/or replacing building components in accordance with provided specifications and drawings.
View the file
Other files
Show all 14
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
STANTEC PROJECT NO.: 178451912
CONTRACT NO.: W912HN19D2000
DELIVERY ORDER NO.: W912HN20F2029P0001
Date: June 2023
US Army Corps of Engineers Savannah District 100 West Oglethorpe Avenue Savannah, Georgia
ARCHITECT/DESIGN:
Stantec Architecture Inc.
4798 New Broad Street, Suite 100
Orlando, Florida 32814
READY TO ADVERTISE (RTA)
STRUCTURAL INTERIOR DESIGN BROCHURE
BUILDING 399 TRAINEE BARRACKS UPGRADE
PROGRAM (TBUP) PHASE 3
FORT MOORE, GA
BINDER PREPARED BY:
Maureen McLaine, NCIDQ, Interior Designer Stantec Architecture, Inc.
STANTEC PROJECT NO.: 178451912
CONTRACT NO.: W912HN19D2000
DELIVERY ORDER NO.: W912HN20F2029P0001
Date: June 2023
US Army Corps of Engineers Savannah District 100 West Oglethorpe Avenue Savannah, Georgia
ARCHITECT/DESIGN:
Stantec Architecture Inc.
4798 New Broad Street, Suite 100
Orlando, Florida 32814
READY TO ADVERTISE (RTA)
STRUCTURAL INTERIOR DESIGN BROCHURE
BUILDING 399 TRAINEE BARRACKS UPGRADE
PROGRAM (TBUP) PHASE 3
FORT MOORE, GA
Index
1. Design Analysis
2. Floor Plans: AE111-114; AE121-125; AE131-134; AE141-144
3. Reflected Ceiling Plans: AE151-154; AE161-165; AE171-174
4. Typical Unit & Restroom Elevations: AE410-AE417
5. Floor Finish Plans: AF111-114; AF121-125; AF131-134; AF141-144
6. Finish Key & Typical Unit Room Finish Schedule: AF601
7. Room Finish Schedule: AF602 - AF603
8. Interior Finish Board
BINDER PREPARED BY:
Maureen McLaine, NCIDQ, Interior Designer Stantec Architecture, Inc.
DIVIDER 1
3.6
It is anticipated that the existing electrical system will be modified, and a new transformer will be installed by Flint EMC. The contractor will install the secondary lines from the new transformer to the individual building sections E and F. The contractor shall install new conduit using the existing conduit pathway after demolition of existing conduit and electrical lines.
3.2 ARCHITECTURAL
3.2.1 General Parameters
This is Phase III of the overall renovation of existing Building 399, Olsen Hall, at Ft. Moore, GA. The project includes the design for selective demolition and reconstruction of building sections ‘E’ and ‘F’, and section ‘D’ main communications room as defined in the design drawings.
3.2.2 Design Objectives and Provisions
The newly renovated spaces will include the following:
1. Single occupancy living units with private bathrooms, a storage closet, and a sleeping area. These living units will all be accessed from a main, central, interior corridor.
2. A percentage of the new rooms will be ABA accessible as determined in the design charrette meetings with the government and users.
3. Centralized utilities will be incorporated for efficiency. See narratives for mechanical, electrical, and plumbing trades.
4. A new elevator will be designed adjacent to existing stairs in building section ‘F’. It will be oversized to accommodate furniture and equipment transportation. It will also be used for ABA access to the upper floors. It is not anticipated that the elevator will be used by building residents as a typical means of vertical transport. See Appendix F for the elevator basis of design.
5. There are four stair towers located in sections ‘E’ and ‘F’. These towers and the adjacent functional spaces will be core areas for the building and provide main entries and exits in and out of the building.
a. Each core area on every floor will contain a laundry room, a public toilet room, a janitor’s closet, a storage room, an electrical room, and a telecom room.
b. The first-floor core areas will have a mechanical room. The second and third floors core area will have a public lounge.
6. In Section D Main Communications Room, the wall to the right side of the entrance door shall be renovated to support new backboards. This wall will hold all the Outside Plant (OSP) landing equipment for the 6 sections (including Sections E & F of this project) that enter from the tunnels. Space shall also be provided for the future renovation of section D OSP landing equipment. New equipment shall be provided to support the OSP terminations. The wall opposite the door shall support the terminations for all backbone cabling that connect the OSP coming from each section to the telecommunication patch panel that will be
3.7 terminated to a switch. A system shall be installed to support the transporting and mounting of the backbone across the room in a manner that does not compromise the cabling in the future.
7. At the Main Communications Room existing window shall be left in place, covered with drywall, and painted black on the side facing the window. Doors, door frames, and hardware shall be removed and replaced.
The door hardware shall be keyed according to the DPW Keying Requirements. The bathroom at next door existing unit will be repaired to a functional room.
3.2.3 Technical Requirements
Interior acoustical design includes STC 50 interior partitions for all occupied sleeping unit bathrooms, and lounges.
Typical interior wall construction consists of 3-5/8” metal studs at 16” o.c. with (1) layer of 5/8” gypsum board each side.
Increased energy efficiency will be created by replacing all the original doors and windows. Double doors and associated frame at exterior storage units will remain and receive new hardware and finish. New doors and windows will be designed to match the Phase I and II exterior designs. The exterior walls of the building will also be furred out and insulated to increase the insulation in the wall system.
The stairs and rails in each of the core areas will be refurbished. There will be a guardrail at the floor level landings for each set of stairs. Nosing’s will be repaired, and grip pads replaced.
The balcony rails and gated rails will be refurbished to maintain the original look.
The third-floor balcony exposed roof planking will be refinished, and the bird netting will be replaced.
The exterior walls will be restored to match the original building construction in areas where wall louvers are being removed as part of the mechanical renovation.
The doghouse roof access structures will have the windows and doors resealed to keep moisture out. The existing brick masonry will be repointed on these structures as well.
At the Main Communications Room openings in the concrete floor slab will need to be filled and patched.
3.3 STRUCTURAL INTERIOR DESIGN
3.3.1 General Parameters
This includes structural interior design elements and their supporting finishes throughout the building.
3.3.2 Design Objectives and Provisions
Natural light will be provided through windows in each bedroom along with ambient lighting provided through ceiling fixtures and table lamps located on nightstands. One color scheme will be provided for the walls in the Living unit with the intent to support the RFP ease of maintenance and to match existing building finishes.
3.8
The unit layouts are successful in creating a residential feel with a private sleeping area, sitting area, private bathroom, and step-in closets. Color scheme and supporting finishes create a modern and clean feeling for users.
Building materials have been chosen based upon Green Building Initiative (GBI) requirements, life cycle costs, maintenance requirements, availability, color, and texture as well as visual compatibility of the surrounding buildings and units. Interior construction includes interior partitions, interior doors, and fittings, floor and bathroom ceiling finishes, and fixed casework. For general use, Typical interior wall construction consists of 3- 5/8” metal studs at 16” o.c. with (1) layer of 5/8” gypsum board each side.
To increase energy efficiency, all exterior and interior doors and windows will be replaced, except for the exterior storage units which will only receive new finish and door hardware, and fourth floor tower windows. Flush solid core wood doors will be Grade A hardwood face veneer with transparent finish on hollow steel frames. Wood doors will be at dwelling unit entry and doors within dwelling units. New doors and windows will be designed to match Phases I and II exterior designs. Each entry door will have a peep hole.
Unit bathrooms millwork to be finished with plastic laminate and solid surface countertops.
Ceiling throughout units to be gypsum board while unit bathrooms are to be finished with moisture resistant gypsum board. Ceiling heights throughout the building will be 9’-0” to allow for the concealment of air conditioning ducts and utilities above. Wet areas receiving tile or surrounds will have cement backer board. The primary ceiling finish will be painted Benjamin Moore Chantilly Lace in a flat finish. All mechanical rooms, electrical, communication rooms will be exposed structure. Windowsills are solid surface.
Flooring in units and corridors to be luxury vinyl tile. Porcelain tile will be used along with narrow grouting in wet areas. The preferred flooring for the living units is luxury vinyl tile. Preferred finish is porcelain tile for the bathroom and showers. Epoxy flooring is used in stairs while sealed concrete is used for janitor, laundry, electrical, telecom, storage, and mechanical rooms. Stair nosing will be repaired, and grip pads replaced. Exterior corridors to be existing concrete.
All walls except bathrooms to receive eggshell finishes. Doors, door frames and bathroom walls to receive semigloss finish paint. Bathrooms to also include porcelain wall tile. Unit wall paint to be Benjamin Moore Desert Twilight, a light warm grey color. Painted doors and frames to be a darker brown grey to accent the wall paint and coordinate with the wood-look LVT flooring. Bathrooms and other walls throughout the building to be a lighter color, Benjamin Moore Natural Cream. Accent wall paint, Benjamin Moore Sag Harbor Gray, will be added to corridor walls to create a two-toned wall.
At the main Communications Room new flooring shall be a light colored VCT or sealed concrete. New finishes on the ceiling and walls shall be light in color.
3.4 STRUCTURAL
This is Phase III of the overall renovation of existing Building 399, Olson Hall, at Ft. Moore, GA. The project includes the design for selective demolition and reconstruction of building sections ‘E’ and ‘F’ as defined in the design drawings.
INTERIOR FINISH BOARD
PN 90737
REPAIR OLSON HALL, BUILDING 399 TRAINEE BARRACKS
UPGRADE PROGRAM (TBUP) PHASE 3
FORT MOORE, GA
PT-01 Ceiling Paint Benjamin Moore
Chantilly Lace - Flat
PT-04 Unit Wall Paint Benjamin Moore
Desert Twilight - Eggshell
PT-02 Wall Paint Benjamin Moore
Natural Cream - Eggshell
PT-03 Wall Paint Benjamin Moore
Sag Harbor Gray - Eggshell
LVT-2 – Luxury Vinyl Tile Interface
Beech A00204
LVT-1 – Luxury Vinyl Tile Interface
Black Walnut A00201
Door Finish VT Industries
White Birch – Oasis OA18
PT-05 Door & Frame Paint Benjamin Moore
Night Horizon - Semigloss
PT-06 Bathroom Wall Paint Benjamin Moore
Natural Cream - Semigloss
REPAIR OLSON HALL, BUILDING 399 TRAINEE BARRACKS
UPGRADE PROGRAM (TBUP) PHASE 3
FORT MOORE, GA
PTB-1 Porcelain Tile Cove Base Atlas Concorde
Rift – Chalk Matte 6” x 12”
PTB -2 Porcelain Tile Trim Atlas Concorde
Rift – Chalk Matte 3” x 24”
PFT-1 Porcelain Floor Tile Atlas Concorde
Rift – Chalk Matte 12” x 24”
PWT-2 Porcelain Accent Wall Tile Atlas Concorde
Rift – Gravel Matte 12” x 24”
PFT-2 Porcelain Shower Floor Tile Atlas Concorde
Rift – Chalk Matte 2”x2” Mosaic
PWT-1 Porcelain Wall Tile Atlas Concorde
Rift – Chalk Matte 12” x 24”
CG-1 & CR-1 Corner Guard & Chair Rail
Johnsonite - Icicle
GR-1 Grout Mapei
105 Driftwood
RB-1 Rubber Base Tarkett
Traditional 6” - Icicle
REPAIR OLSON HALL, BUILDING 399 TRAINEE BARRACKS
UPGRADE PROGRAM (TBUP) PHASE 3
FORT MOORE, GA
PLAM-1 Plastic Laminate Wilsonart
Ebony Recon 7997-38
TS-1 Transition Strip PFT to LVT
Schluter – RENO-U Stainless Steel
TS-2 Transition Strip LVT-1 to LVT-2
Tarkett – CTA-80-M
TS-3 Transition Strip LVT to SC
Tarkett – CTA-80-J
SS-1 Solid Surface Corian
Neutral Aggregate
EL-1 - Elevator Cab Wall Finish Powder Coat Finish
F-129 – Elephant Ear
EL-2 / EL-3 -Elevator Cab Handrail & Door Finish
Metal Brushed Stainless Steel
TP-1 – Toilet Partition Scranton Products
Hiny Hiders – Grey OP
WT-1 – Window Treatment SWF Contract
Nightfall – Creamy Beige R6003
TS-4 Movement Joint Schluter – Dilex AKWS
DIVIDER 2
D
FD
W W
DN
UP
FD
F14 F13 F12 F11 F10 F9 F8 F7G1 F17 F16 F15
SECTION
MATCHLINE
SECTION F WESTSECTION G
NOT IN SCOPE
OF WORK
UNIT-A
F122
UNIT-A
F121
UNIT-B
F120
UNIT-C
F118
UNIT-A
F119
UNIT-A
F117
MECH RM
FM11
ABA UNIT-B
F116
UNIT-C
F115
ELEC RM
FE11
STAIR 4
FS14
CORR
FC14
STOR.
FV14
EGRESS
CORRIDOR
FC13
LAUNDRY
F113
RESTROOM
F114
CORR
FC15
TELECOM
FT11
AE406
A1
SECTION
MATCHLINE
SECTION F EASTSECTION F WEST
AE201
A1
A6
AE305
AE205
A1
A1
AE301
A1
AE301
AE205
H1
/2
004054 009
100 100 100 100
AE410
A1
CORR
FC16
AE411
A1
AE414
A1
5' - 0"
F -A
F -C
F -A
F -A
F -A
F -C
F -C
F -C
F M
F -A
F -A
F C
F
FC13-A
FC13-B
F C
FV14
F -A
F
F S
106 105 106106 106106106 106
FT11FT11
UP
UNIT-A
F111
A6
AE306
F -A
F -A
F E
10 10
01 03 01 03
01 01A
03 01 02A
02A
02A
01 01
TYP
6' - 6"
F -C
INSIDE
BALCONY
STOR
FV17
STOR
FV16
EXISTING
STORAGE
FV15
F V
-A
F V
F V
F V
ABA UNIT-B
F112
CORR
FC12
UNIT-A
F109
STAIR 3
FS13
F -D
F -D
F -D
F -D
F122-B F121-B F119-B F117-B
F120-B
F118-B
F -B
F115-B
F111-B
F112-B
F -D
F C
F S
F -A
F109-BF
-C
CORR
FC11
F C
-A
ELEVATOR
LOBBY
FL11
JANITOR
FJ11
ELEVATOR
F
FJ11
F -A
102106
13' - 1" 13' - 8" 13' - 4" 13' - 4 1/2" 17' - 1 1/2" 13' - 0"
/2
15' - 2" 15' - 0" 15' - 0" 15' - 0" 10' - 0"
FS14-A FS13-A
100 100 100A 100
034034
TYP.
TYP.
TYP.
5' - 0" FV4
F V
037 037
04A 04A
09B
04A
2' - 0"
AE405
H1
01A
BELOW
BELOW
RECENTLY
INSTALLED DOOR,
DOOR AND
HARDWARE TO
REMAIN
105 105 106
A14
AE301
FV05
SEE SHEET AE101 FOR
FOUNDATION LEVEL PLAN
AND EXISTING STORAGE
FV05 BELOW
A. CONTRACTOR TO FIELD VERIFY ALL DIMENSION AND EXISTING
CONDITIONS PRIOR TO START OF CONSTRUCTION. IF ANY DISCREPANCIES
WITH CONSTRUCTION DOCUMENTS, CONTRACTOR IS TO INFORM
CONTRACTING OFFICER IN WRITING PRIOR TO START OF CONSTRUCTION.
B. CONTRACTOR IS TO PROTECT ALL EXISTING ITEMS TO REMAIN FROM
DAMAGE DURING CONSTRUCTION. CONTRACTOR IS RESPONSIBLE FOR
REPAIRING, AND/ OR REPLACING DAMAGED ITEMS TO REMAIN WITH
EQUAL OR BETTER, TO THEIR ORIGINAL STATE, AT NO COST TO
GOVERNMENT.
C. REPOINT LOOSE MORTAR JOINTS, REPAIR CRACKS AND DAMAGE AT ALL
EXISTING MASONRY WALLS. ALL EXTERIOR MASONRY REPAIRS SHALL
MATCH HISTORIC CHARACTER, COLOR, AND PATTERN OF EXISTING
FACADE. ALL WORK TO BE AS PER HISTORIC PRESERVATION
REQUIREMENTS. FINAL SELECTIONS TO BE APPROVED BY CONTRACTING
OFFICER.
D. CLEAN AND PATCH ALL EXISTING STUCCO. REPAIR CRACKS AND DAMAGE.
ALL EXTERIOR STUCCO REPAIRS SHALL MATCH HISTORIC CHARACTER,
COLOR, AND PATTERN OF EXISTING FACADE. ALL WORK TO BE AS PER
HISTORIC PRESERVATION REQUIREMENTS. FINAL SELECTIONS TO BE
APPROVED BY CONTRACTING OFFICER.
E. ALL CORE DRILL LOCATIONS ARE TO BE VERIFIED BY GENERAL
CONTRACTOR (GC) PRIOR TO DRILLING. GC IS TO COORDINATE ALL FINAL
CORE DRILL LOCATIONS WITH ASSOCIATED TRADES PRIOR TO START OF
CONSTRUCTION.
F. EXISTING ROOF SYSTEM PENETRATIONS: COORDINATE DETAILS AND
CONSTRUCTION WITH MANUFACTURER AND INSTALLER OF EXISTING
ROOF SYSTEM TO AVOID LOSS OF EXISTING ROOF WARRANTY
G. CONTRACTOR TO PROVIDE BLOCKING AT ALL SURFACE (WALL, CEILING)
MOUNTED FIXTURES AND EQUIPMENT AS REQUIRED.
H. REMOVAL AND REINSTALLATION OF EXISTING GUTTERS AND
DOWNSPOUTS REQUIRED TO COMPLETE NEW WORK IS TO NOT VOID
EXISTING GUTTER AND DOWNSPOUT WARRANTIES.
I. REMOVAL AND REINSTALLATION OF EXISTING LIGHTNING PROTECTION
SYSTEM REQUIRED TO COMPLETE NEW WORK IS TO NOT VOID EXISTING
GUTTER AND DOWNSPOUT WARRANTIES.
J. CONTRACTOR TO COORDINATE ALL ACCESS PANEL LOCATIONS WITH
MECHANICAL, PLUMBING AND ELECTRICAL DRAWINGS PRIOR TO
INSTALLATION.
GENERAL NOTES:LEGEND:
1 HOUR FIRE RATED WALL
PARTITION TYPE SYMBOL, REFER
TO SHEETS AE701, AE702, AND
AE703
NEW INTERIOR PARTITION /
NEW INFILL WALL
EXISTING WALL TO REMAIN
2 HOUR FIRE RATED WALL,
SEE LIFE SAFETY PLANS
NOT IN SCOPE
1/2 HOUR FIRE RATED WALL
6" CONCRETE SLAB INFILL
US Army Corps of Engineers ®
SHEET ID
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
S A
V A
N N
A H
D
IS
T R
IC
T
W
E S
T O
G L E
T H
O R
P E
A V
E N
U E
S A
V A
N N
A H
G
E O
R G
IA
JO
N
E S
F R
A N
K
LI
N R
D , S
U
IT
E
R A
LE
IG
H , N
C
-3
(9
1-
(9
1-
F
A X
LI
C
E N
S E
F
-0
F O
R T
M O
O R
E G
E O
R G
IA
B
U
IL
D
IN
G
T
R A
IN
E
E B
A R
R A
C K
S U
P G
R A
D E
P R
O G
R A
M
(T B
U P
P
H A
S E
F
Y P
N
CONTROLLED UNCLASSIFIED INFORMATION
AE111
F
IR
S T
F L O
O R
P L A
N
S E
C T
IO
N
F W
E S
T
D V
A N
L O
O N
B M
O G
A L L A
P U
K B
R O
D B
E R
R B
L A
IR
J U
N E
B
- 7 -1
-2
C
A T
E G
O R
Y C
O D
E
F
IL
E N
A M
E A
E .D
W G
R E
A D
Y T
O A
D V
E R
T
IS
E
R T
A
1/8" = 1'-0"A1
FIRST FLOOR PLAN - F WEST
0 4' 8' 16' 24'
KEY PLAN
G
F
E
N.T.S.
PLAN
NORTH
A
B C
DBUILDING 399
F
E
KEYNOTES
001 EXISTING TUNNEL. SEE MECHANICAL, PLUMBING, ELECTRICAL AND FIRE
PROTECTION DRAWINGS FOR SCOPE OF WORK - TYPICAL
004 EXISTING CONCRETE FLOOR SLAB
008 EXISTING MASONRY WALL. PATCH, REPAIR AS REQUIRED. FINISH AS
INDICATED. SEE SHEET AE215 FOR ADDITIONAL INFORMATION - TYPICAL
009 EXISTING STUCCO WALL. PATCH, REPAIR AS REQUIRED AND MATCH
ADJACENT FINISH AND TEXTURE. PREPARE SURFACES TO RECEIVE PAINT
AS INDICATED. SEE SHEET AE215 FOR ADDITIONAL INFORMATION - TYPICAL
010 EXISTING CONCRETE WALL. PREPARE SURFACES TO RECEIVE PAINT AS
INDICATED - TYPICAL
028 EXISTING CONCRETE SIDEWALK
034 EXISTING RAIN LEADER. REPLACE DAMAGED SECTIONS WITH NEW TO
MATCH EXISTING. PREPARE TO RECEIVE NEW FINISH AS INDICATED -
TYPICAL
037 EXISTING CLEANOUT. CLEAR OUT AND CLEAN TO NEAREST MAIN - TYPICAL
040 6" CONCRETE SLAB INFILL. SEE STRUCTURAL DRAWINGS FOR ADDITIONAL
INFORMATION
042 NEW FACE BRICK MASONRY INFILL TO MATCH EXISTING BRICK MASONRY.
ALL WORK TO BE AS PER HISTORIC PRESERVATION REQUIREMENTS. SEE
SHEET AE215 FOR ADDITIONAL INFORMATION - TYPICAL
044 DOOR AND FRAME AS SCHEDULED
048 INSULATED SPANDREL GLAZING
051 NEW DOOR HARDWARE AT EXISTING DOORS - TYPICAL
054 PATCH, REPAIR, AND PREPARE ALL EXISTING CONCRETE SLABS RECEIVING
NEW FINISHES AS SCHEDULED. ENSURE THAT REPAIRS AND FILLS ARE
LEVEL WITH EXISTING CONCRETE FLOOR SLAB AS PER FLOOR FINISH
MANUFACTURER RECOMMENDATIONS - TYPICAL
098 EXTERIOR FREESTANDING CONCRETE STAIRS. FINISH AND SIZE TO MATCH
EXISTING CONCRETE STAIRS AT EXTERIOR STORAGE UNITS
114 12"X12" ACCESS PANEL, 6" AFF. PAINT TO MATCH ADJACENT SURFACES.
LOCKABLE. SEE MECHANICAL AND PLUMBING DRAWINGS - TYPICAL
CLEAR
FLOOR
SPACE
6/2/2023
W W
UP
FD
F4 F3 F2 F1
F10 F9 F8 F7 F6 F5
SECTION E WESTSECTION F EAST
SECTION
MATCHLINE
STAIR 3
FS13
UNIT-A
F111
ABA UNIT-B
F112
ELEC RM
FE11
UNIT-A
F109
UNIT-A
F108
UNIT-C
F110
ABA UNIT-B
F106
UNIT-A
F107
UNIT-A
F105
UNIT-A
F103
UNIT-B
F104 UNIT-C
F102
UNIT-A
F101
UNIT-A
E139
CORR
FC11
CORR
FC12
SECTION F EASTSECTION F WEST
SECTION
MATCHLINE
CORR
EC19
A6
AE305
15' - 0" 15' - 0" 15' - 0" 15' - 0" 14' - 7"
/2
100 100 100 100 100 100
AE414
A1
F -A
F -C
F -C
F -A
F C
F -A
F -A
F -A
F -A
F -C
F -C
F -A
F -C
F -C
F -A
F -A
F -C
E -C
F -A
F -A
FC11
E -A
105 106105106 106 106
106 106 102
106 106 105 105
F E
A14
AE302
A9
AE303
A6
AE304
A6
AE306
106106
01 03 01
114 114
AE501
L12
EXISTING
STORAGE
FV13
STOR
FV12
STOR
FV11
F V
3 F
V
F V
F S
F -A
AE406
A1
F109-B F108-B
F110-B
F
-BF
-D
F -D
F104-B F -D
F102-B
CORR
FC11
F V
-A
FJ11
ELEVATOR
LOBBY
FL11
100100 100A
/4
/4
/4
13' - 9" 17' - 1 1/2" 14' - 4 3/4" 11' - 11 1/4" 13' - 8" 9' - 6"9' - 3"
/4
/2
/4
15' - 4"
20' - 1 1/2" 23' - 8"
FS13-A
AE201
H1
AE205
A1
F101-BF103-BF105-BF107-B
F112-B
F -D
F111-B
F -D
TYP.
TYP.
TYP.
TYP.
TYP.
04A
04A
09B 04A
01 03
04A
09B
04A 04A
BELOW
BELOW
AE502
E7
A14
AE301
FV03
AE112
L1
LEVEL
BELOW
A. CONTRACTOR TO FIELD VERIFY ALL DIMENSION AND EXISTING
CONDITIONS PRIOR TO START OF CONSTRUCTION. IF ANY DISCREPANCIES
WITH CONSTRUCTION DOCUMENTS, CONTRACTOR IS TO INFORM
CONTRACTING OFFICER IN WRITING PRIOR TO START OF CONSTRUCTION.
B. CONTRACTOR IS TO PROTECT ALL EXISTING ITEMS TO REMAIN FROM
DAMAGE DURING CONSTRUCTION. CONTRACTOR IS RESPONSIBLE FOR
REPAIRING, AND/ OR REPLACING DAMAGED ITEMS TO REMAIN WITH
EQUAL OR BETTER, TO THEIR ORIGINAL STATE, AT NO COST TO
GOVERNMENT.
C. REPOINT LOOSE MORTAR JOINTS, REPAIR CRACKS AND DAMAGE AT ALL
EXISTING MASONRY WALLS. ALL EXTERIOR MASONRY REPAIRS SHALL
MATCH HISTORIC CHARACTER, COLOR, AND PATTERN OF EXISTING
FACADE. ALL WORK TO BE AS PER HISTORIC PRESERVATION
REQUIREMENTS. FINAL SELECTIONS TO BE APPROVED BY CONTRACTING
OFFICER.
D. CLEAN AND PATCH ALL EXISTING STUCCO. REPAIR CRACKS AND DAMAGE.
ALL EXTERIOR STUCCO REPAIRS SHALL MATCH HISTORIC CHARACTER,
COLOR, AND PATTERN OF EXISTING FACADE. ALL WORK TO BE AS PER
HISTORIC PRESERVATION REQUIREMENTS. FINAL SELECTIONS TO BE
APPROVED BY CONTRACTING OFFICER.
E. ALL CORE DRILL LOCATIONS ARE TO BE VERIFIED BY GENERAL
CONTRACTOR (GC) PRIOR TO DRILLING. GC IS TO COORDINATE ALL FINAL
CORE DRILL LOCATIONS WITH ASSOCIATED TRADES PRIOR TO START OF
CONSTRUCTION.
F. EXISTING ROOF SYSTEM PENETRATIONS: COORDINATE DETAILS AND
CONSTRUCTION WITH MANUFACTURER AND INSTALLER OF EXISTING
ROOF SYSTEM TO AVOID LOSS OF EXISTING ROOF WARRANTY
G. CONTRACTOR TO PROVIDE BLOCKING AT ALL SURFACE (WALL, CEILING)
MOUNTED FIXTURES AND EQUIPMENT AS REQUIRED.
H. REMOVAL AND REINSTALLATION OF EXISTING GUTTERS AND
DOWNSPOUTS REQUIRED TO COMPLETE NEW WORK IS TO NOT VOID
EXISTING GUTTER AND DOWNSPOUT WARRANTIES.
I. REMOVAL AND REINSTALLATION OF EXISTING LIGHTNING PROTECTION
SYSTEM REQUIRED TO COMPLETE NEW WORK IS TO NOT VOID EXISTING
GUTTER AND DOWNSPOUT WARRANTIES.
J. CONTRACTOR TO COORDINATE ALL ACCESS PANEL LOCATIONS WITH
MECHANICAL, PLUMBING AND ELECTRICAL DRAWINGS PRIOR TO
INSTALLATION.
GENERAL NOTES:
LEGEND:
1 HOUR FIRE RATED WALL
PARTITION TYPE SYMBOL, REFER
TO SHEETS AE701, AE702, AND
AE703
NEW INTERIOR PARTITION /
NEW INFILL WALL
EXISTING WALL TO REMAIN
2 HOUR FIRE RATED WALL,
SEE LIFE SAFETY PLANS
NOT IN SCOPE
1/2 HOUR FIRE RATED WALL
F3 F2
EXISTING
STORAGE
FV03
FV03
6" CONCRETE SLAB INFILL
US Army Corps of Engineers ®
SHEET ID
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
S A
V A
N N
A H
D
IS
T R
IC
T
W
E S
T O
G L E
T H
O R
P E
A V
E N
U E
S A
V A
N N
A H
G
E O
R G
IA
JO
N
E S
F R
A N
K
LI
N R
D , S
U
IT
E
R A
LE
IG
H , N
C
-3
(9
1-
(9
1-
F
A X
LI
C
E N
S E
F
-0
F O
R T
M O
O R
E G
E O
R G
IA
B
U
IL
D
IN
G
T
R A
IN
E
E B
A R
R A
C K
S U
P G
R A
D E
P R
O G
R
U P
P
H A
S E
F
Y P
N
CONTROLLED UNCLASSIFIED INFORMATION
AE112
F
IR
S T
F L O
O R
P L A
N
S E
C T
IO
N
F E
A S
T
D V
A N
L O
O N
B M
O G
A L L A
P U
K B
R O
D B
E R
R B
L A
IR
J U
N E
B
- 7 -1
-2
C
A T
E G
O R
Y C
O D
E
F
IL
E N
A M
E A
E .D
W G
R E
A D
Y T
O A
D V
E R
T
IS
E
R T
A
1/8" = 1'-0"A1
FIRST FLOOR PLAN - SECTION F EAST
1/8" = 1'-0"L1
FOUNDATION/ TUNNEL
FLOOR - PARTIAL FLOOR
PLAN
0 4' 8' 16' 24'
KEY PLAN
G
F
E
N.T.S.
PLAN
NORTH
A
B C
DBUILDING 399
F
E
KEYNOTES
001 EXISTING TUNNEL. SEE MECHANICAL, PLUMBING, ELECTRICAL AND FIRE
PROTECTION DRAWINGS FOR SCOPE OF WORK - TYPICAL
004 EXISTING CONCRETE FLOOR SLAB
008 EXISTING MASONRY WALL. PATCH, REPAIR AS REQUIRED. FINISH AS
INDICATED. SEE SHEET AE215 FOR ADDITIONAL INFORMATION - TYPICAL
009 EXISTING STUCCO WALL. PATCH, REPAIR AS REQUIRED AND MATCH
ADJACENT FINISH AND TEXTURE. PREPARE SURFACES TO RECEIVE PAINT
AS INDICATED. SEE SHEET AE215 FOR ADDITIONAL INFORMATION - TYPICAL
010 EXISTING CONCRETE WALL. PREPARE SURFACES TO RECEIVE PAINT AS
INDICATED - TYPICAL
031 EXISTING CONCRETE STAIRS. CLEAN, REPAIR AS REQUIRED. PREPARE
SURFACES TO RECEIVE PAINT AND ANTI-SLIP NOSING STRIPS - TYPICAL
032 EXISTING CONCRETE STAIRS. CLEAN, REPAIR AS REQUIRED. PREPARE
STAIR TO RECEIVE ANTI-SLIP NOSING STRIPS - TYPICAL
034 EXISTING RAIN LEADER. REPLACE DAMAGED SECTIONS WITH NEW TO
MATCH EXISTING. PREPARE TO RECEIVE NEW FINISH AS INDICATED -
TYPICAL
037 EXISTING CLEANOUT. CLEAR OUT AND CLEAN TO NEAREST MAIN - TYPICAL
040 6" CONCRETE SLAB INFILL. SEE STRUCTURAL DRAWINGS FOR ADDITIONAL
INFORMATION
044 DOOR AND FRAME AS SCHEDULED
051 NEW DOOR HARDWARE AT EXISTING DOORS - TYPICAL
054 PATCH, REPAIR, AND PREPARE ALL EXISTING CONCRETE SLABS RECEIVING
NEW FINISHES AS SCHEDULED. ENSURE THAT REPAIRS AND FILLS ARE
LEVEL WITH EXISTING CONCRETE FLOOR SLAB AS PER FLOOR FINISH
MANUFACTURER RECOMMENDATIONS - TYPICAL
072 EXPANSION JOINT COVER. SEE SHEET AE507 FOR DETAILS
078 EJ. SEE DETAILS ON SHEET AE703
101 EXISTING DRAIN. CLEAR OUT AND CLEAN DRAIN TO NEAREST MAIN. MISSING
OR BROKEN DRAIN GRATES ARE TO BE REPLACED BY NEW TO MATCH
EXISTING. REPLACE CLEANOUT PLUG IF BROKEN OR MISSING - TYPICAL
114 12"X12" ACCESS PANEL, 6" AFF. PAINT TO MATCH ADJACENT SURFACES.
LOCKABLE. SEE MECHANICAL AND PLUMBING DRAWINGS - TYPICAL
FD
W
W
FD
E20F1 E26 E25 E24 E23 E22 E21
E17
E11
E12
E13
E14
E15
E16
E19
E18
SECTION
MATCHLINE
SECTION F
EAST
SECTION E WEST
UNIT-B
E138
UNIT-A
E139 UNIT-A
E137
UNIT-A
E133
ABA UNIT-B
E132
UNIT-C
E130
UNIT-A
E131
UNIT-A
E129
MECH RM
EM11
UNIT-A
E125
UNIT-A
E123
UNIT-A
E121
UNIT-A
E119
ELEC RM
EE13
RESTROOM
E128
STOR.
EV15
TELECOM
ET12
LOBBY
EL13
STAIR 2
ES12
CORR
EC19
SECTION
MATCHLINESE
C
TIO
N E
E A
ST
SE
C
TIO
N E
W E
ST
AE201
H1
A E 202A
AE202
H1
AE203
H1
LAUNDRY
E126
A E 204A
100 100 100 100 100 100 100
/2
/2
14' - 11" 15' - 0" 15' - 0" 15' - 0" 15' - 0" 15' - 0" 14' - 11"
5'
6"
/2
5' - 0"
11' - 11 1/2"
9' - 4 1/2" 13' - 5" 13' - 8" 13' - 10 1/2"
VESTIBULE
EC16
18' - 8 1/2"
' - 8
' - 7
/2
5' - 4"
UP
' - 1
/2
5' - 11"
AE416
A6
E -A
E -A
E -A
E -A
E -A
E -C
E -C
E -A
E -C
E -C
E -A
E -A
E -C
E -C
E -A
E -A
E
-A ET12
E
E S
EL13
E V
E E
E M
E126
E C
E 125-A
E 125-C
E 124-A
E 123-A
E 123-C
E 121-C
E 122-A
E 121A
E 120-A
E 119-C
E 117-C
E 117-A
E 118-A
E 116-A
E 116-C
E C
106 106 105
106 106 105105 106105 106A
E C
-A
A1
AE302
FC11
11' - 1 1/2"
9' - 7"
E E
A14
AE302
AE204
H1
E -C
E 119-A
E C
10 11
11A
0110 10
01 01
03A 03
0101 03
01A
02A
02A
02A
02A 02A
02A
10 11
01A
02A
02A
02A
02A
01A
01A
03C
11 01
09072
114 114
ALIGN
EC16
CORR
EC18
AE402
H1
INSIDE
BALCONY
03A
UNIT-C
E124
UNIT-C
E136
A
LIG
N
E 118-D
E12 0-
B E11 8-
B
E 120-D
E 122-B
E 122-D
E12 4-
B
E 124-D
E12 3-
B
E12 5-
B
E129-BE131-BE133-BE134-BE135-BE137-BE139-B
E138-B E -D
E -D E136-B E130-B
E -D
E -D
E -B
E11 6-
B
E11 7-
B
E11 9-
B
E12 1-
B
EXISTING
STORAGE
EV16
STOR.
EV17
STOR.
EV18
E V
-A
EV16E
V
E V
034031
1'
0"
6'
9"
8' - 7 1/2"
6' - 0 5/8"
9' - 6
10' - 6 3/4"
11' - 0
' - 6
02A
18' - 4 5/8"
5' - 6 5/8"
20' - 8 1/2"
02A
13' - 5" 17' - 1 1/2" 13' - 9 1/2" 8' - 9 5/8"
9'
3/
4"
/2
3/
4"
5'
0"
ES12-A
E E12-O
TYP.
TYP.
TYP.
TYP.
TYP.
TYP.
TYP.
09 03 12
11A
09 04A09B
04A
04A
04A
09 04A09B
04A 09
09B
04A
04 09 03 12
04A
04A
09B
04A
11A
04A
04A
04A
09B
04A
02A
04A
11A 11A
02A
UNIT-A
E134
ABA UNIT-B
E122
UNIT-C
E120
UNIT-A
E116
UNIT-A
E117
UNIT-B
E118
CORR
EC14
CORR
EC17
UNIT-A
E135
BELOW
BELOW
CORR
EC18
' - 2
/2
EC16-A
02A02A
ELEC RM
EE12
SEE
ELEVATIONS
EV06
AE113
L10
LEVEL
BELOW
A. CONTRACTOR TO FIELD VERIFY ALL DIMENSION AND EXISTING
CONDITIONS PRIOR TO START OF CONSTRUCTION. IF ANY DISCREPANCIES
WITH CONSTRUCTION DOCUMENTS, CONTRACTOR IS TO INFORM
CONTRACTING OFFICER IN WRITING PRIOR TO START OF CONSTRUCTION.
B. CONTRACTOR IS TO PROTECT ALL EXISTING ITEMS TO REMAIN FROM
DAMAGE DURING CONSTRUCTION. CONTRACTOR IS RESPONSIBLE FOR
REPAIRING, AND/ OR REPLACING DAMAGED ITEMS TO REMAIN WITH
EQUAL OR BETTER, TO THEIR ORIGINAL STATE, AT NO COST TO
GOVERNMENT.
C. REPOINT LOOSE MORTAR JOINTS, REPAIR CRACKS AND DAMAGE AT ALL
EXISTING MASONRY WALLS. ALL EXTERIOR MASONRY REPAIRS SHALL
MATCH HISTORIC CHARACTER, COLOR, AND PATTERN OF EXISTING
FACADE. ALL WORK TO BE AS PER HISTORIC PRESERVATION
REQUIREMENTS. FINAL SELECTIONS TO BE APPROVED BY CONTRACTING
OFFICER.
D. CLEAN AND PATCH ALL EXISTING STUCCO. REPAIR CRACKS AND DAMAGE.
ALL EXTERIOR STUCCO REPAIRS SHALL MATCH HISTORIC CHARACTER,
COLOR, AND PATTERN OF EXISTING FACADE. ALL WORK TO BE AS PER
HISTORIC PRESERVATION REQUIREMENTS. FINAL SELECTIONS TO BE
APPROVED BY CONTRACTING OFFICER.
E. ALL CORE DRILL LOCATIONS ARE TO BE VERIFIED BY GENERAL
CONTRACTOR (GC) PRIOR TO DRILLING. GC IS TO COORDINATE ALL FINAL
CORE DRILL LOCATIONS WITH ASSOCIATED TRADES PRIOR TO START OF
CONSTRUCTION.
F. EXISTING ROOF SYSTEM PENETRATIONS: COORDINATE DETAILS AND
CONSTRUCTION WITH MANUFACTURER AND INSTALLER OF EXISTING
ROOF SYSTEM TO AVOID LOSS OF EXISTING ROOF WARRANTY
G. CONTRACTOR TO PROVIDE BLOCKING AT ALL SURFACE (WALL, CEILING)
MOUNTED FIXTURES AND EQUIPMENT AS REQUIRED.
H. REMOVAL AND REINSTALLATION OF EXISTING GUTTERS AND
DOWNSPOUTS REQUIRED TO COMPLETE NEW WORK IS TO NOT VOID
EXISTING GUTTER AND DOWNSPOUT WARRANTIES.
I. REMOVAL AND REINSTALLATION OF EXISTING LIGHTNING PROTECTION
SYSTEM REQUIRED TO COMPLETE NEW WORK IS TO NOT VOID EXISTING
GUTTER AND DOWNSPOUT WARRANTIES.
J. CONTRACTOR TO COORDINATE ALL ACCESS PANEL LOCATIONS WITH
MECHANICAL, PLUMBING AND ELECTRICAL DRAWINGS PRIOR TO
INSTALLATION.
GENERAL NOTES:
LEGEND:
1 HOUR FIRE RATED WALL
PARTITION TYPE SYMBOL, REFER
TO SHEETS AE701, AE702, AND
AE703
NEW INTERIOR PARTITION /
NEW INFILL WALL
EXISTING WALL TO REMAIN
2 HOUR FIRE RATED WALL,
SEE LIFE SAFETY PLANS
NOT IN SCOPE
1/2 HOUR FIRE RATED WALL
E23 E22
EXISTING
STORAGE
EV06
EV06
6" CONCRETE SLAB INFILL
US Army Corps of Engineers ®
SHEET ID
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
S A
V A
N N
A H
D
IS
T R
IC
T
W
E S
T O
G L E
T H
O R
P E
A V
E N
U E
S A
V A
N N
A H
G
E O
R G
IA
JO
N
E S
F R
A N
K
LI
N R
D , S
U
IT
E
R A
LE
IG
H , N
C
-3
(9
1-
(9
1-
F
A X
LI
C
E N
S E
F
-0
F O
R T
M O
O R
E G
E O
R G
IA
B
U
IL
D
IN
G
T
R A
IN
E
E B
A R
R A
C K
S U
P G
R A
D E
P R
O G
R
U P
P
H A
S E
F
Y P
N
CONTROLLED UNCLASSIFIED INFORMATION
AE113
F
IR
S T
F L O
O R
P L A
N
S E
C T
IO
N
E W
E S
T
D V
A N
L O
O N
B M
O G
A L L A
P U
K B
R O
D B
E R
R B
L A
IR
J U
N E
B
- 7 -1
-2
C
A T
E G
O R
Y C
O D
E
F
IL
E N
A M
E A
E .D
W G
R E
A D
Y T
O A
D V
E R
T
IS
E
R T
A
1/8" = 1'-0"A1
FIRST FLOOR PLAN - SECTION E WEST
0 4' 8' 16' 24'
KEY PLAN
G
F
E
N.T.S.
PLAN
NORTH
A
B C
DBUILDING 399
F
E
1/8" = 1'-0"L10
FOUNDATION/ TUNNEL
FLOOR - PARTIAL FLOOR
PLAN
KEYNOTES
001 EXISTING TUNNEL. SEE MECHANICAL, PLUMBING, ELECTRICAL AND FIRE
PROTECTION DRAWINGS FOR SCOPE OF WORK - TYPICAL
004 EXISTING CONCRETE FLOOR SLAB
008 EXISTING MASONRY WALL. PATCH, REPAIR AS REQUIRED. FINISH AS
INDICATED. SEE SHEET AE215 FOR ADDITIONAL INFORMATION - TYPICAL
009 EXISTING STUCCO WALL. PATCH, REPAIR AS REQUIRED AND MATCH
ADJACENT FINISH AND TEXTURE. PREPARE SURFACES TO RECEIVE PAINT
AS INDICATED. SEE SHEET AE215 FOR ADDITIONAL INFORMATION - TYPICAL
010 EXISTING CONCRETE WALL. PREPARE SURFACES TO RECEIVE PAINT AS
INDICATED - TYPICAL
011 EXISTING CONCRETE STAIRS. PREPARE SURFACES TO RECEIVE PAINT AS
INDICATED - TYPICAL
023 EXISTING LADDER. PREPARE SURFACES TO RECEIVE PAINT AS INDICATED -
TYPICAL
028 EXISTING CONCRETE SIDEWALK
031 EXISTING CONCRETE STAIRS. CLEAN, REPAIR AS REQUIRED. PREPARE
SURFACES TO RECEIVE PAINT AND ANTI-SLIP NOSING STRIPS - TYPICAL
032 EXISTING CONCRETE STAIRS. CLEAN, REPAIR AS REQUIRED. PREPARE
STAIR TO RECEIVE ANTI-SLIP NOSING STRIPS - TYPICAL
034 EXISTING RAIN LEADER. REPLACE DAMAGED SECTIONS WITH NEW TO
MATCH EXISTING. PREPARE TO RECEIVE NEW FINISH AS INDICATED -
TYPICAL
037 EXISTING CLEANOUT. CLEAR OUT AND CLEAN TO NEAREST MAIN - TYPICAL
040 6" CONCRETE SLAB INFILL. SEE STRUCTURAL DRAWINGS FOR ADDITIONAL
INFORMATION
042 NEW FACE BRICK MASONRY INFILL TO MATCH EXISTING BRICK MASONRY.
ALL WORK TO BE AS PER HISTORIC PRESERVATION REQUIREMENTS. SEE
SHEET AE215 FOR ADDITIONAL INFORMATION - TYPICAL
044 DOOR AND FRAME AS SCHEDULED
048 INSULATED SPANDREL GLAZING
051 NEW DOOR HARDWARE AT EXISTING DOORS - TYPICAL
072 EXPANSION JOINT COVER. SEE SHEET AE507 FOR DETAILS
101 EXISTING DRAIN. CLEAR OUT AND CLEAN DRAIN TO NEAREST MAIN. MISSING
OR BROKEN DRAIN GRATES ARE TO BE REPLACED BY NEW TO MATCH
EXISTING. REPLACE CLEANOUT PLUG IF BROKEN OR MISSING - TYPICAL
113 DRYER VENT COVER. PAINTED TO MATCH ADJACENT SURFACES
114 12"X12" ACCESS PANEL, 6" AFF. PAINT TO MATCH ADJACENT SURFACES.
LOCKABLE. SEE MECHANICAL AND PLUMBING DRAWINGS - TYPICAL
FD
DD W W
FD
E7
E8
E9
E10
E11
E4
E1
E2
E3
1 3 4
E5
E6
SECTION E EAST
SECTION
MATCHLINE
SECTION D
NOT IN SCOPE
OF WORK
LAUNDRY
E106
UNIT-A
E109
UNIT-E
E110
LOBBY
EL12
CORR
EC12
CORR
EC11
TELECOM
ET11
ELEC RM
EE11
RESTROOM
E108
STAIR 1
ES11
AE408
A1
SECTION
MATCHLINE
AE202H9
AE203H9
1"
5' - 0"
11' - 11 1/2"
EXISTING
STORAGE
EV12
UP
18' - 4 1/2"
AE415
A11
EV
E L
E C
E S11
E 111-C
E 109-C
E 115-C
E 113-C
E 115-A
E 109-A
E -B
E107-A
E
E T
E 114-A
EE11
E 112-A
E 113-A
E 111-A
E 110-D
E 110-B
E 110-A
E V 12-A
A9
AE302
EL11-A
EV11
E C 13-O
EC11-O
A
AE203
A9
STOR.
EV14
STOR.
EV13
E V14
E V13
E
STOR.
EV11
11A
01 1009
03C
03C
INSIDE
BALCONY
UNIT-C
E114
E11 4-
B
E 116-C
E11 5-
B
E11 3-
B
E 112-B
E 112-D
E 114-D
E11 1-
B
E10 9-
B
UNIT-A
E101
UNIT-A
E103
UNIT-A
E105
UNIT-F
E102
EV
E -B
E101-A
E -B
E103-A
E -B
E105-A
E107-C
E105-C
E103-C
E101-C
AE501
L1
18' - 8 1/2"
5' - 0"
12' - 10 3/4"
/4
/2
9'
6"
/4
/2
17' - 3 1/2" 18' - 8 1/2"
E S 11-A
TYP.
TYP.
09 04
04A 01
1004A
09B
04A
01A
03A
02A
02B
100104A
09B
11A
04A01
04A
09B
04A
04A
04A
ABA UNIT-B
E104
ABA UNIT-A
E107
ABA UNIT-B
E112
UNIT-A
E111
UNIT-A
E113
UNIT-A
E115
S
EC
TIO
N E
W
S T
S
EC
TIO
N E
E
AS
T
BELOW
BELOW
E102-D E102-B
E104-A
1B
08A
1B
072078
/4 "6
/2
/4
AE415
A1
E102-A
03C
E104-D
09 E104-B
AE414
A1
SIM/
OPP
HAND
/2
SEE
ELEVATION
AE114
F13
LEVEL
BELOW
A. CONTRACTOR TO FIELD VERIFY ALL DIMENSION AND EXISTING
CONDITIONS PRIOR TO START OF CONSTRUCTION. IF ANY DISCREPANCIES
WITH CONSTRUCTION DOCUMENTS, CONTRACTOR IS TO INFORM
CONTRACTING OFFICER IN WRITING PRIOR TO START OF CONSTRUCTION.
B. CONTRACTOR IS TO PROTECT ALL EXISTING ITEMS TO REMAIN FROM
DAMAGE DURING CONSTRUCTION. CONTRACTOR IS RESPONSIBLE FOR
REPAIRING, AND/ OR REPLACING DAMAGED ITEMS TO REMAIN WITH
EQUAL OR BETTER, TO THEIR ORIGINAL STATE, AT NO COST TO
GOVERNMENT.
C. REPOINT LOOSE MORTAR JOINTS, REPAIR CRACKS AND DAMAGE AT ALL
EXISTING MASONRY WALLS. ALL EXTERIOR MASONRY REPAIRS SHALL
MATCH HISTORIC CHARACTER, COLOR, AND PATTERN OF EXISTING
FACADE. ALL WORK TO BE AS PER HISTORIC PRESERVATION
REQUIREMENTS. FINAL SELECTIONS TO BE APPROVED BY CONTRACTING
OFFICER.
D. CLEAN AND PATCH ALL EXISTING STUCCO. REPAIR CRACKS AND DAMAGE.
ALL EXTERIOR STUCCO REPAIRS SHALL MATCH HISTORIC CHARACTER,
COLOR, AND PATTERN OF EXISTING FACADE. ALL WORK TO BE AS PER
HISTORIC PRESERVATION REQUIREMENTS. FINAL SELECTIONS TO BE
APPROVED BY CONTRACTING OFFICER.
E. ALL CORE DRILL LOCATIONS ARE TO BE VERIFIED BY GENERAL
CONTRACTOR (GC) PRIOR TO DRILLING. GC IS TO COORDINATE ALL FINAL
CORE DRILL LOCATIONS WITH ASSOCIATED TRADES PRIOR TO START OF
CONSTRUCTION.
F. EXISTING ROOF SYSTEM PENETRATIONS: COORDINATE DETAILS AND
CONSTRUCTION WITH MANUFACTURER AND INSTALLER OF EXISTING
ROOF SYSTEM TO AVOID LOSS OF EXISTING ROOF WARRANTY
G. CONTRACTOR TO PROVIDE BLOCKING AT ALL SURFACE (WALL, CEILING)
MOUNTED FIXTURES AND EQUIPMENT AS REQUIRED.
H. REMOVAL AND REINSTALLATION OF EXISTING GUTTERS AND
DOWNSPOUTS REQUIRED TO COMPLETE NEW WORK IS TO NOT VOID
EXISTING GUTTER AND DOWNSPOUT WARRANTIES.
I. REMOVAL AND REINSTALLATION OF EXISTING LIGHTNING PROTECTION
SYSTEM REQUIRED TO COMPLETE NEW WORK IS TO NOT VOID EXISTING
GUTTER AND DOWNSPOUT WARRANTIES.
J. CONTRACTOR TO COORDINATE ALL ACCESS PANEL LOCATIONS WITH
MECHANICAL, PLUMBING AND ELECTRICAL DRAWINGS PRIOR TO
INSTALLATION.
GENERAL NOTES:
LEGEND:
1 HOUR FIRE RATED WALL
PARTITION TYPE SYMBOL, REFER
TO SHEETS AE701, AE702, AND
AE703
NEW INTERIOR PARTITION /
NEW INFILL WALL
EXISTING WALL TO REMAIN
2 HOUR FIRE RATED WALL,
SEE LIFE SAFETY PLANS
NOT IN SCOPE
1/2 HOUR FIRE RATED WALL
E9
E10
EV
044 101
009004
008008008
EXISTING
STORAGE
EV02
6" CONCRETE SLAB INFILL
US Army Corps of Engineers ®
SHEET ID
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
S A
V A
N N
A H
D
IS
T R
IC
T
W
E S
T O
G L E
T H
O R
P E
A V
E N
U E
S A
V A
N N
A H
G
E O
R G
IA
JO
N
E S
F R
A N
K
LI
N R
D , S
U
IT
E
R A
LE
IG
H , N
C
-3
(9
1-
(9
1-
F
A X
LI
C
E N
S E
F
-0
F O
R T
M O
O R
E G
E O
R G
IA
B
U
IL
D
IN
G
T
R A
IN
E
E B
A R
R A
C K
S U
P G
R A
D E
P R
O G
R
U P
P
H A
S E
F
Y P
N
CONTROLLED UNCLASSIFIED INFORMATION
AE114
F
IR
S T
F L O
O R
P L A
N
S E
C T
IO
N
E E
A S
T
D V
A N
L O
O N
B M
O G
A L L A
P U
K B
R O
D B
E R
R B
L A
IR
J U
N E
B
- 7 -1
-2
C
A T
E G
O R
Y C
O D
E
F
IL
E N
A M
E A
E .D
W G
R E
A D
Y T
O A
D V
E R
T
IS
E
R T
A
1/8" = 1'-0"A1
FIRST FLOOR PLAN - SECTION E EAST
1/8" = 1'-0"F13
FOUNDATION/ TUNNEL FLOOR - PARTIAL
FLOOR PLAN
0 4' 8' 16' 24'
KEY PLAN
G
F
E
N.T.S.
PLAN
NORTH
A
B C
DBUILDING 399
F
E
KEYNOTES
001 EXISTING TUNNEL. SEE MECHANICAL, PLUMBING, ELECTRICAL AND FIRE
PROTECTION DRAWINGS FOR SCOPE OF WORK - TYPICAL
004 EXISTING CONCRETE FLOOR SLAB
006 EXISTING CONCRETE COLUMN. CLEAN, PATCH AS REQUIRED. PREPARE
SURFACES TO RECEIVE NEW WORK AS INDICATED. ALSO SEE COLUMN
DETAILS ON SHEET AE501 - TYPICAL
008 EXISTING MASONRY WALL. PATCH, REPAIR AS REQUIRED. FINISH AS
INDICATED. SEE SHEET AE215 FOR ADDITIONAL INFORMATION - TYPICAL
009 EXISTING STUCCO WALL. PATCH, REPAIR AS REQUIRED AND MATCH
ADJACENT FINISH AND TEXTURE. PREPARE SURFACES TO RECEIVE PAINT
AS INDICATED. SEE SHEET AE215 FOR ADDITIONAL INFORMATION - TYPICAL
010 EXISTING CONCRETE WALL. PREPARE SURFACES TO RECEIVE PAINT AS
INDICATED - TYPICAL
011 EXISTING CONCRETE STAIRS. PREPARE SURFACES TO RECEIVE PAINT AS
INDICATED - TYPICAL
023 EXISTING LADDER. PREPARE SURFACES TO RECEIVE PAINT AS INDICATED -
TYPICAL
031 EXISTING CONCRETE STAIRS. CLEAN, REPAIR AS REQUIRED. PREPARE
SURFACES TO RECEIVE PAINT AND ANTI-SLIP NOSING STRIPS - TYPICAL
032 EXISTING CONCRETE STAIRS. CLEAN, REPAIR AS REQUIRED. PREPARE
STAIR TO RECEIVE ANTI-SLIP NOSING STRIPS - TYPICAL
034 EXISTING RAIN LEADER. REPLACE DAMAGED SECTIONS WITH NEW TO
MATCH EXISTING. PREPARE TO RECEIVE NEW FINISH AS INDICATED -
TYPICAL
037 EXISTING CLEANOUT. CLEAR OUT AND CLEAN TO NEAREST MAIN - TYPICAL
042 NEW FACE BRICK MASONRY INFILL TO MATCH EXISTING BRICK MASONRY.
ALL WORK TO BE AS PER HISTORIC PRESERVATION REQUIREMENTS. SEE
SHEET AE215 FOR ADDITIONAL INFORMATION - TYPICAL
044 DOOR AND FRAME AS SCHEDULED
048 INSULATED SPANDREL GLAZING
051 NEW DOOR HARDWARE AT EXISTING DOORS - TYPICAL
072 EXPANSION JOINT COVER. SEE SHEET AE507 FOR DETAILS
078 EJ. SEE DETAILS ON SHEET AE703
101 EXISTING DRAIN. CLEAR OUT AND CLEAN DRAIN TO NEAREST MAIN. MISSING
OR BROKEN DRAIN GRATES ARE TO BE REPLACED BY NEW TO MATCH
EXISTING. REPLACE CLEANOUT PLUG IF BROKEN OR MISSING - TYPICAL
113 DRYER VENT COVER. PAINTED TO MATCH ADJACENT SURFACES
114 12"X12" ACCESS PANEL, 6" AFF. PAINT TO MATCH ADJACENT SURFACES.
LOCKABLE. SEE MECHANICAL AND PLUMBING DRAWINGS - TYPICAL
173 NEW CONCRETE SIDEWALK. SEE CIVIL DRAWINGS
UP
D
FD FD FD FD
FD
W W
UP
F14 F13 F12 F11 F10 F9 F8 F7G1 F17 F16 F15
UNIT-A
F223
UNIT-A
F222
UNIT-B
F220
UNIT-A
F221
UNIT-A
F219
UNIT-A
F217
UNIT-B
F216
STOR.
FV21
TELECOM
FT21
STAIR 4
FS24
UNIT-A
F212
SECTION
MATCHLINE
SECTION F WESTSECTION G
NOT IN SCOPE
OF WORK
ELEC. RM.
FE21
SECTION
MATCHLINE
SECTION F EASTSECTION F WEST
AE201
A1
A5
AE305
A6
AE305
AE205
A1
A1
AE301
A1
AE301
AE205
H1
15' - 1 1/2" 15' - 0" 15' - 0" 15' - 0" 15' - 0"
200 200 200 200 200 200
CORR
FC24
CORR
FC26 5' - 0"
VESTIBULE
FC23
CORR
FC21
CORR
FC25
RESTROOM
F214
F -A
F -A
F -C
F -A
F -A
F -C
F -C
F -A
F -A
F -C
F -C
F -A
F -A
F -A
FV21
F T
F C
F
F
F S
B -C
205 205206 206 206 205206 206206 206206 206 206
F -A
F E
LAUNDRY
F213
A6
AE306
12' - 1 3/4"
/2
10 10 10 10
01 01
03 01
0101 01
06 06
02A
03A03C
02B
02A
/2
8' - 10 7/8" 6' - 0"
096 012
AE404
A6
UNIT-C
F215
UNIT-C
F218
UNIT-E
F210
CORR
FC22
STAIR 3
FS23
UNIT-A
F211
AE415
A11
SIM
AE410
A1
TYP
AE411
A1
TYP.
AE403
A6
F S
F -A
F -C
F211-B
F C
F -E
F -A
F212-B
F215-B
F -D
F216-B
F -D
F217-BF219-B
F -D
F218-B
F220-B
F -D
F221-BF222-BF223-B
JANITOR
FJ21
ELEVATOR
LOBBY
FL21
ELEVATOR
F
200 200 200A 200
AE405
A6
11' - 8"
/2
5' - 0" 13' - 1" 13' - 8" 13' - 4"
/2
16' - 10 1/2" 13' - 8" 13' - 0"
23' - 8" 9' - 9 3/4"
/2
ALIGN
14' - 11"
FJ21
034 101
020 020 101034
11 10
04A
09B09
04A
08 10
0101 01
02A
04A
04A09
07 03
04A
09B 09
04A
4' - 2"
7' - 4"
/2
2' - 0"
NEW WALL
INFILL
RECENTLY
INSTALLED DOOR,
DOOR AND
HARDWARE TO
REMAIN
1' - 0"
ALIGN
A14
AE301
A. CONTRACTOR TO FIELD VERIFY ALL DIMENSION AND EXISTING
CONDITIONS PRIOR TO START OF CONSTRUCTION. IF ANY DISCREPANCIES
WITH CONSTRUCTION DOCUMENTS, CONTRACTOR IS TO INFORM
CONTRACTING OFFICER IN WRITING PRIOR TO START OF CONSTRUCTION.
B. CONTRACTOR IS TO PROTECT ALL EXISTING ITEMS TO REMAIN FROM
DAMAGE DURING CONSTRUCTION. CONTRACTOR IS RESPONSIBLE FOR
REPAIRING, AND/ OR REPLACING DAMAGED ITEMS TO REMAIN WITH
EQUAL OR BETTER, TO THEIR ORIGINAL STATE, AT NO COST TO
GOVERNMENT.
C. REPOINT LOOSE MORTAR JOINTS, REPAIR CRACKS AND DAMAGE AT ALL
EXISTING MASONRY WALLS. ALL EXTERIOR MASONRY REPAIRS SHALL
MATCH HISTORIC CHARACTER, COLOR, AND PATTERN OF EXISTING
FACADE. ALL WORK TO BE AS PER HISTORIC PRESERVATION
REQUIREMENTS. FINAL SELECTIONS TO BE APPROVED BY CONTRACTING
OFFICER.
D. CLEAN AND PATCH ALL EXISTING STUCCO. REPAIR CRACKS AND DAMAGE.
ALL EXTERIOR STUCCO REPAIRS SHALL MATCH HISTORIC CHARACTER,
COLOR, AND PATTERN OF EXISTING FACADE. ALL WORK TO BE AS PER
HISTORIC PRESERVATION REQUIREMENTS. FINAL SELECTIONS TO BE
APPROVED BY CONTRACTING OFFICER.
E. ALL CORE DRILL LOCATIONS ARE TO BE VERIFIED BY GENERAL
CONTRACTOR (GC) PRIOR TO DRILLING. GC IS TO COORDINATE ALL FINAL
CORE DRILL LOCATIONS WITH ASSOCIATED TRADES PRIOR TO START OF
CONSTRUCTION.
F. EXISTING ROOF SYSTEM PENETRATIONS: COORDINATE DETAILS AND
CONSTRUCTION WITH MANUFACTURER AND INSTALLER OF EXISTING
ROOF SYSTEM TO AVOID LOSS OF EXISTING ROOF WARRANTY
G. CONTRACTOR TO PROVIDE BLOCKING AT ALL SURFACE (WALL, CEILING)
MOUNTED FIXTURES AND EQUIPMENT AS REQUIRED.
H. REMOVAL AND REINSTALLATION OF EXISTING GUTTERS AND
DOWNSPOUTS REQUIRED TO COMPLETE NEW WORK IS TO NOT VOID
EXISTING GUTTER AND DOWNSPOUT WARRANTIES.
I. REMOVAL AND REINSTALLATION OF EXISTING LIGHTNING PROTECTION
SYSTEM REQUIRED TO COMPLETE NEW WORK IS TO NOT VOID EXISTING
GUTTER AND DOWNSPOUT WARRANTIES.
J. CONTRACTOR TO COORDINATE ALL ACCESS PANEL LOCATIONS WITH
MECHANICAL, PLUMBING AND ELECTRICAL DRAWINGS PRIOR TO
INSTALLATION.
GENERAL NOTES:
LEGEND:
1 HOUR FIRE RATED WALL
PARTITION TYPE SYMBOL, REFER
TO SHEETS AE701, AE702, AND
AE703
NEW INTERIOR PARTITION /
NEW INFILL WALL
EXISTING WALL TO REMAIN
2 HOUR FIRE RATED WALL,
SEE LIFE SAFETY PLANS
NOT IN SCOPE
1/2 HOUR FIRE RATED WALL
US Army Corps of Engineers ®
SHEET ID
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
S A
V A
N N
A H
D
IS
T R
IC
T
W
E S
T O
G L E
T H
O R
P E
A V
E N
U E
S A
V A
N N
A H
G
E O
R G
IA
JO
N
E S
F R
A N
K
LI
N R
D , S
U
IT
E
R A
LE
IG
H , N
C
-3
(9
1-
(9
1-
F
A X
LI
C
E N
S E
F
-0
F O
R T
M O
O R
E G
E O
R G
IA
B
U
IL
D
IN
G
T
R A
IN
E
E B
A R
R A
C K
S U
P G
R A
D E
P R
O G
R
U P
P
H A
S E
F
Y P
N
CONTROLLED UNCLASSIFIED INFORMATION
AE121
S E
C O
N D
F L O
O R
P L A
N
S E
C T
IO
N
F W
E S
T
D V
A N
L O
O N
B M
O G
A L L A
P U
K B
R O
D B
E R
R B
L A
IR
J U
N E
B
- 7 -1
-2
C
A T
E G
O R
Y C
O D
E
F
IL
E N
A M
E A
E .D
W G
R E
A D
Y T
O A
D V
E R
T
IS
E
R T
A
1/8" = 1'-0"A1
SECOND FLOOR PLAN - F WEST
0 4' 8' 16' 24'
KEY PLAN
G
F
E
N.T.S.
PLAN
NORTH
A
B C
DBUILDING 399
F
E
KEYNOTES
096 REINSTALL EXISTING HANDRAIL. SECURE TO EXISTING STRUCTURE.
REPLACE MISSING BOLTS. PREPARE SURFACES TO RECEIVE PAINT AS
INDICATED
101 EXISTING DRAIN. CLEAR OUT AND CLEAN DRAIN TO NEAREST MAIN. MISSING
OR BROKEN DRAIN GRATES ARE TO BE REPLACED BY NEW TO MATCH
EXISTING. REPLACE CLEANOUT PLUG IF BROKEN OR MISSING - TYPICAL
119 26"X26" ACCESS PANEL, 8" AFF. PAINT TO MATCH ADJACENT SURFACES.
LOCKABLE. IN RATED PARTITIONS USE RATED PANELS MATCHING WALL
RATING. SEE DETAIL A6/AE503 AND MECHANICAL DRAWINGS - TYPICAL
KEYNOTES
004 EXISTING CONCRETE FLOOR SLAB
006 EXISTING CONCRETE COLUMN. CLEAN, PATCH AS REQUIRED. PREPARE
SURFACES TO RECEIVE NEW WORK AS INDICATED. ALSO SEE COLUMN
DETAILS ON SHEET AE501 - TYPICAL
008 EXISTING MASONRY WALL. PATCH, REPAIR AS REQUIRED. FINISH AS
INDICATED. SEE SHEET AE215 FOR ADDITIONAL INFORMATION - TYPICAL
009 EXISTING STUCCO WALL. PATCH, REPAIR AS REQUIRED AND MATCH
ADJACENT FINISH AND TEXTURE. PREPARE SURFACES TO RECEIVE PAINT
AS INDICATED. SEE SHEET AE215 FOR ADDITIONAL INFORMATION - TYPICAL
010 EXISTING CONCRETE WALL. PREPARE SURFACES TO RECEIVE PAINT AS
INDICATED - TYPICAL
011 EXISTING CONCRETE STAIRS. PREPARE SURFACES TO RECEIVE PAINT AS
INDICATED - TYPICAL
012 EXISTING HANDRAIL. SECURE TO EXISTING STRUCTURE IF LOOSE. REPLACE
MISSING BOLTS. PREPARE SURFACES TO RECEIVE PAINT AS INDICATED -
TYPICAL
020 EXISTING GUTTER AND DOWNSPOUTS. REMOVE AND REINSTALL AS
REQUIRED TO COMPLETE NEW WORK
034 EXISTING RAIN LEADER. REPLACE DAMAGED SECTIONS WITH NEW TO
MATCH EXISTING. PREPARE TO RECEIVE NEW FINISH AS INDICATED -
TYPICAL
042 NEW FACE BRICK MASONRY INFILL TO MATCH EXISTING BRICK MASONRY.
ALL WORK TO BE AS PER HISTORIC PRESERVATION REQUIREMENTS. SEE
SHEET AE215 FOR ADDITIONAL INFORMATION - TYPICAL
044 DOOR AND FRAME AS SCHEDULED
048 INSULATED SPANDREL GLAZING
054 PATCH, REPAIR, AND PREPARE ALL EXISTING CONCRETE SLABS RECEIVING
NEW FINISHES AS SCHEDULED. ENSURE THAT REPAIRS AND FILLS ARE
LEVEL WITH EXISTING CONCRETE FLOOR SLAB AS PER FLOOR FINISH
MANUFACTURER RECOMMENDATIONS - TYPICAL
072 EXPANSION JOINT COVER. SEE SHEET AE507 FOR DETAILS
FD FD FD
W W
UP
F4 F3 F2 F1
F10 F9 F8 F7 F6 F5
UNIT-E
F210
ELEC. RM.
FE21
UNIT-A
F211
UNIT-A
F209
UNIT-C
F206
UNIT-A
F207
UNIT-A
F205
UNIT-A
F203
UNIT-B
F204
UNIT-A
F201
CORR
FC21
CORR
FC22
ELEVATOR
LOBBY
FL21
UNIT-A
F212
SECTION E WESTSECTION F EAST
SECTION
MATCHLINE
SECTION F EASTSECTION F WEST
SECTION
MATCHLINE
A9
AE303
A6
AE305
15' - 0" 15' - 0" 15' - 0" 15' - 0" 14' - 7"
200 200 200 200 200 200
CORR
EC29
UNIT-A
E239
B -C
F -A
F -C
F -A
F C
F -A
F -C
F -C
F -A
F -A
F -A
F -A
F -C
F -C
F -A
F -A
F -C
E -C
FC21
F -A
F -A
202 206 206 205 206 206 205205 206
F E
206206206
A14
AE302
A6
AE304
A6
AE306
E -A
101101
01 03 01
02A
01 01
01 01
01 01
01 01 01
01 030301
03 01
E C
078 072
AE501
L12
STAIR 3
FS23
UNIT-C
F202
UNIT-B
F208
AE415
A11
SIM
11A
060606
F201-B
F -D
F202-B
F204-B
F -D
F203-B
F -D
F206-B
F207-B
F -D
F208-B
F209-BF211-B
F -A
F -E
F212-B
F S
AE403
A6
13' - 1" 15' - 10 1/2" 13' - 8" 9' - 5 3/4"9' - 3 1/2" 13' - 8" 14' - 6"
15' - 4"
20' - 1 3/4"
23' - 8"
/2
/4
/2
/4
/4
200 200A 200
19' - 7" 10
FJ21
F205-B
8' - 0"
09 03
11A
04A 0904A
09B
04A 09
07 03
04A
09B
04A
04A
09B
04A
11A
F -B
A14
AE301
A. CONTRACTOR TO FIELD VERIFY ALL DIMENSION AND EXISTING
CONDITIONS PRIOR TO START OF CONSTRUCTION. IF ANY DISCREPANCIES
WITH CONSTRUCTION DOCUMENTS, CONTRACTOR IS TO INFORM
CONTRACTING OFFICER IN WRITING PRIOR TO START OF CONSTRUCTION.
B. CONTRACTOR IS TO PROTECT ALL EXISTING ITEMS TO REMAIN FROM
DAMAGE DURING CONSTRUCTION. CONTRACTOR IS RESPONSIBLE FOR
REPAIRING, AND/ OR REPLACING DAMAGED ITEMS TO REMAIN WITH
EQUAL OR BETTER, TO THEIR ORIGINAL STATE, AT NO COST TO
GOVERNMENT.
C. REPOINT LOOSE MORTAR JOINTS, REPAIR CRACKS AND DAMAGE AT ALL
EXISTING MASONRY WALLS. ALL EXTERIOR MASONRY REPAIRS SHALL
MATCH HISTORIC CHARACTER, COLOR, AND PATTERN OF EXISTING
FACADE. ALL WORK TO BE AS PER HISTORIC PRESERVATION
REQUIREMENTS. FINAL SELECTIONS TO BE APPROVED BY CONTRACTING
OFFICER.
D. CLEAN AND PATCH ALL EXISTING STUCCO. REPAIR CRACKS AND DAMAGE.
ALL EXTERIOR STUCCO REPAIRS SHALL MATCH HISTORIC CHARACTER,
COLOR, AND PATTERN OF EXISTING FACADE. ALL WORK TO BE AS PER
HISTORIC PRESERVATION REQUIREMENTS. FINAL SELECTIONS TO BE
APPROVED BY CONTRACTING OFFICER.
E. ALL CORE DRILL LOCATIONS ARE TO BE VERIFIED BY GENERAL
CONTRACTOR (GC) PRIOR TO DRILLING. GC IS TO COORDINATE ALL FINAL
CORE DRILL LOCATIONS WITH ASSOCIATED TRADES PRIOR TO START OF
CONSTRUCTION.
F. EXISTING ROOF SYSTEM PENETRATIONS: COORDINATE DETAILS AND
CONSTRUCTION WITH MANUFACTURER AND INSTALLER OF EXISTING
ROOF SYSTEM TO AVOID LOSS OF EXISTING ROOF WARRANTY
G. CONTRACTOR TO PROVIDE BLOCKING AT ALL SURFACE (WALL, CEILING)
MOUNTED FIXTURES AND EQUIPMENT AS REQUIRED.
H. REMOVAL AND REINSTALLATION OF EXISTING GUTTERS AND
DOWNSPOUTS REQUIRED TO COMPLETE NEW WORK IS TO NOT VOID
EXISTING GUTTER AND DOWNSPOUT WARRANTIES.
I. REMOVAL AND REINSTALLATION OF EXISTING LIGHTNING PROTECTION
SYSTEM REQUIRED TO COMPLETE NEW WORK IS TO NOT VOID EXISTING
GUTTER AND DOWNSPOUT WARRANTIES.
J. CONTRACTOR TO COORDINATE ALL ACCESS PANEL LOCATIONS WITH
MECHANICAL, PLUMBING AND ELECTRICAL DRAWINGS PRIOR TO
INSTALLATION.
GENERAL NOTES:
LEGEND:
1 HOUR FIRE RATED WALL
PARTITION TYPE SYMBOL, REFER
TO SHEETS AE701, AE702, AND
AE703
NEW INTERIOR PARTITION /
NEW INFILL WALL
EXISTING WALL TO REMAIN
2 HOUR FIRE RATED WALL,
SEE LIFE SAFETY PLANS
NOT IN SCOPE
1/2 HOUR FIRE RATED WALL
US Army Corps of Engineers ®
SHEET ID
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
S A
V A
N N
A H
D
IS
T R
IC
T
W
E S
T O
G L E
T H
O R
P E
A V
E N
U E
S A
V A
N N
A H
G
E O
R G
IA
JO
N
E S
F R
A N
K
LI
N R
D , S
U
IT
E
R A
LE
IG
H , N
C
-3
(9
1-
(9
1-
F
A X
LI
C
E N
S E
F
-0
F O
R T
M O
O R
E G
E O
R G
IA
B
U
IL
D
IN
G
T
R A
IN
E
E B
A R
R A
C K
S U
P G
R A
D E
P R
O G
R
U P
P
H A
S E
F
Y P
N
CONTROLLED UNCLASSIFIED INFORMATION
AE122
S E
C O
N D
F L O
O R
P L A
N
S E
C T
IO
N
F E
A S
T
D V
A N
L O
O N
B M
O G
A L L A
P U
K B
R O
D B
E R
R B
L A
IR
J U
N E
B
- 7 -1
-2
C
A T
E G
O R
Y C
O D
E
F
IL
E N
A M
E A
E .D
W G
R E
A D
Y T
O A
D V
E R
T
IS
E
R T
A
1/8" = 1'-0"A1
SECOND FLOOR PLAN - SECTION F EAST
0 4' 8' 16' 24'
KEY PLAN
G
F
E
N.T.S.
PLAN
NORTH
A
B C
DBUILDING 399
F
E
KEYNOTES
004 EXISTING CONCRETE FLOOR SLAB
006 EXISTING CONCRETE COLUMN. CLEAN, PATCH AS REQUIRED. PREPARE
SURFACES TO RECEIVE NEW WORK AS INDICATED. ALSO SEE COLUMN
DETAILS ON SHEET AE501 - TYPICAL
008 EXISTING MASONRY WALL. PATCH, REPAIR AS REQUIRED. FINISH AS
INDICATED. SEE SHEET AE215 FOR ADDITIONAL INFORMATION - TYPICAL
009 EXISTING STUCCO WALL. PATCH, REPAIR AS REQUIRED AND MATCH
ADJACENT FINISH AND TEXTURE. PREPARE SURFACES TO RECEIVE PAINT
AS INDICATED. SEE SHEET AE215 FOR ADDITIONAL INFORMATION - TYPICAL
010 EXISTING CONCRETE WALL. PREPARE SURFACES TO RECEIVE PAINT AS
INDICATED - TYPICAL
012 EXISTING HANDRAIL. SECURE TO EXISTING STRUCTURE IF LOOSE. REPLACE
MISSING BOLTS. PREPARE SURFACES TO RECEIVE PAINT AS INDICATED -
TYPICAL
034 EXISTING RAIN LEADER. REPLACE DAMAGED SECTIONS WITH NEW TO
MATCH EXISTING. PREPARE TO RECEIVE NEW FINISH AS INDICATED -
TYPICAL
054 PATCH, REPAIR, AND PREPARE ALL EXISTING CONCRETE SLABS RECEIVING
NEW FINISHES AS SCHEDULED. ENSURE THAT REPAIRS AND FILLS ARE
LEVEL WITH EXISTING CONCRETE FLOOR SLAB AS PER FLOOR FINISH
MANUFACTURER RECOMMENDATIONS - TYPICAL
072 EXPANSION JOINT COVER. SEE SHEET AE507 FOR DETAILS
078 EJ. SEE DETAILS ON SHEET AE703
101 EXISTING DRAIN. CLEAR OUT AND CLEAN DRAIN TO NEAREST MAIN. MISSING
OR BROKEN DRAIN GRATES ARE TO BE REPLACED BY NEW TO MATCH
EXISTING. REPLACE CLEANOUT PLUG IF BROKEN OR MISSING - TYPICAL
119 26"X26" ACCESS PANEL, 8" AFF. PAINT TO MATCH ADJACENT SURFACES.
LOCKABLE. IN RATED PARTITIONS USE RATED PANELS MATCHING WALL
RATING. SEE DETAIL A6/AE503 AND MECHANICAL DRAWINGS - TYPICAL
189 HANDRAIL TO MATCH EXISTING. PAINTED - TYPICAL
D
FD
FD FD
FD
FD
FD
W
W
E20F1 E26 E25 E24 E23 E22 E21
E17
E11
E12
E13
E14
E15
E16
E19
E18
UNIT-B
E238
UNIT-A
E239
UNIT-A
E237
UNIT-C
E236
UNIT-A
E235
UNIT-A
E234
UNIT-A
E233
UNIT-B
E232
UNIT-C
E230
UNIT-A
E231
UNIT-A
E229
UNIT-B
E224
LOUNGE
E227
UNIT-A
E225
UNIT-C
E222
UNIT-A
E223
UNIT-A
E221
UNIT-A
E219
UNIT-B
E220
UNIT-A
E217
UNIT-A
E216
RESTROOM
E228
ELEC. RM.
EE22
JC
EJ22
TELECOM
ET22
LOBBY
EL21
STAIR 2
ES22
STOR.
EV22
CORR
EC28
CORR
EC29
SECTION
MATCHLINESE
C
TIO
N C
E
AS
T
SE
C
TIO
N C
W E
ST
A E 202A
AE202
H1
AE203
H1
LAUNDRY
E226
/2
/2
14' - 11 1/2" 15' - 0" 15' - 0" 15' - 0" 15' - 0" 15' - 0" 14' - 11"
5' - 0"
11' - 11 1/2"
18' - 8 1/2"
008 011
20' - 8 1/2"
6' - 0"
CORR
EC26
CORR
EC25
CORR
EC27
' - 1
5' - 4"
E C
E
216-CE
216-A
E 217-A
E 217-C
E
219-CE
219-A
E 220-A
E 221-C
E 223-C
E 221-A
E 223-A
E 222-A
E 224-A
E 225-C
E 225-A
E22
E226
E E
EV22
E J 2E
S
E
E -A
E T
E -C
E -C
E -A
E -A
E -A
E -A
E -C
E -C
E -A
E -A
E -C
E -C
E -A
E -A
E -A
E -A
E -C
FC21
200 200 200 200 200 200 200
206 206 205 206 206 205205 206 205 206 206A
A1
AE302
A14
AE302
9' - 6
' - 4
3' - 2 1/2"
3'
1/
2"
E C
-O
E C 26-O
AE204
H1
EL21
E 218-A
' - 7
0101 03
01 01
11A
01 02
02A
11 09
01A
AE416
A6
SIM
6' - 8
3' - 6
' - 2
E C
AE402
A6
TYP.
SECTION
MATCHLINE
SECTION F
EAST
SECTION E WEST
E22 5-
B
E 224-D
E22 4-
B
E 222-D
E22 2-
B
E22 1-
B
E…