28 31 70.pdf
PDF 99 KB Posted
- Solicitation number
- W912ES25Q0063
About this file
This document is a detailed technical specification for an Interior Fire Alarm System, Addressable (Section 28 31 70) for a Lock and Dam 2 Central Control Station (CCS). The specification covers comprehensive requirements for a complete fire alarm system, including design, installation, equipment, testing, and documentation standards.
Key requirements include providing a fully supervised, non-coded, analog/addressable fire alarm system conforming to NFPA 72 and UL 864 standards. The system must include components such as a Fire Alarm Control Unit (FACU), manual stations, smoke and heat detectors, carbon monoxide detectors, addressable interface devices, control modules, notification appliances (audible and visual), and automatic fire alarm transmitters. The specification mandates rigorous testing procedures, detailed documentation, spare parts provisions, and 4 hours of government employee training. The system must be capable of transmitting alarm, supervisory, and trouble signals, with specific requirements for power supply, battery backup, surge protection, and environmental conditions. Importantly, the system must be independent of building security, management, and utility monitoring systems, except for control functions.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| W912ES25Q0063-0003 Amendment 3.pdf | ||
| 07 84 00.pdf | ||
| W912ES25Q0063-0002 Amendment 2.pdf | ||
| LD2 1st floor plan.pdf | ||
| LD2 2nd floor plan.pdf | ||
| W912ES25Q0063-0001 Amendment 1.pdf | ||
| W912ES25Q0063 RFQ for LD2 Fire Alarms.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Fire Alarm System LD2
SECTION 28 31 70
INTERIOR FIRE ALARM SYSTEM, ADDRESSABLE
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
FM GLOBAL (FM)
FM APP GUIDE (updated on-line) Approval Guide https://www.approvalguide.com/
INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)
IEEE C62.41.1 (2002; R 2008) Guide on the Surges Environment in Low-Voltage (1000 V and Less) AC Power Circuits
IEEE C62.41.2 (2002) Recommended Practice on Characterization of Surges in Low-Voltage (1000 V and Less) AC Power Circuits
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 4 (2018) Standard for Integrated Fire Protection and Life Safety System Testing
NFPA 70 (2023) National Electrical Code
NFPA 72 (2025) National Fire Alarm and Signaling Code
NFPA 90A (2024) Standard for the Installation of Air Conditioning and Ventilating Systems
NFPA 170 (2024; ERTA 1 2023) Standard for Fire Safety and Emergency Symbols
U.S. DEPARTMENT OF DEFENSE (DOD)
UFC 3-601-02 (2021) Fire Protection Systems Inspection, Testing, and Maintenance
UFC 4-010-06 (2023) Cybersecurity of Facility-Related Control Systems
UL SOLUTIONS (UL)
UL 268 (2023) UL Standard for Safety Smoke Detectors for Fire Alarm Systems
UL 268A (2008; Reprint Aug 2023) Smoke Detectors
SECTION 28 31 70 Page 1 for Duct Application
UL 464 (2023) UL Standard for Safety Audible Signaling Devices for Fire Alarm and Signaling Systems, Including Accessories
UL 497A (2001; Bul. 2019) UL Standard for Safety Secondary Protectors for Communications Circuits
UL 497B (2004; Reprint Feb 2022) UL Standard for Safety Protectors for Data Communications and Fire Alarm Circuits
UL 521 (1999; Reprint Feb 2023) UL Standard for Safety Heat Detectors for Fire Protective Signaling Systems
UL 864 (2023) UL Standard for Safety Control Units and Accessories for Fire Alarm Systems
UL 1283 (2017; Reprint Feb 2024) UL Standard for Safety Electromagnetic Interference Filters
UL 1449 (2021; Reprint Dec 2022) UL Standard for Safety Surge Protective Devices
UL 1638 (2023) UL Standard for Safety Visible Signaling Devices for Fire Alarm and Signaling Systems, Including Accessories
UL 1971 (2002; Reprint Feb 2024) UL Standard for Safety Signaling Devices for the Deaf and Hard of Hearing
UL 2034 (2024; Reprint Aug 2024) UL Standard for Safety Single and Multiple Station Carbon Monoxide Alarms
UL 2075 (2013; Bul. 2019) UL Standard for Safety Gas and Vapor Detectors and Sensors
UL Fire Prot Dir UL Product IQ (updated online) at https://productiq.ulpropsector.com/en
1.2 RELATED SECTIONS
Refer to the following sections for related work and coordination:
Section 07 84 00 FIRESTOPPING for additional work related to firestopping.
SECTION 28 31 70 Page 2
1.3 SUMMARY
1.3.1 Scope
a. This work includes designing and providing a new, complete, fire alarm system as described herein and in the statement of work for the Lock and Dam 2 Central Control Station (CCS). Include system wiring, raceways, pull boxes, terminal cabinets, outlet and mounting boxes, control equipment, initiating devices, notification appliances, supervising station fire alarm transmitters, and other accessories and miscellaneous items required for a complete operational system even though each item is not specifically mentioned or described. Provide system complete and ready for operation. Design and installation must comply with UFC 4-010-06 .
b. Provide equipment, materials, installation, workmanship, inspection, and testing in strict accordance with NFPA 72 , except as modified herein. Final quantity, system layout, and coordination are the responsibility of the Contractor.
c. The fire alarm system must be independent of the building security, building management, and energy/utility monitoring systems other than for control functions.
1.3.2 Qualified Fire Protection Engineer (QFPE)
Services of the QFPE must include:
a. Reviewing SD-02, SD-03, and SD-05 submittal packages for completeness and compliance with the provisions of this specification.
Construction (shop) drawings and calculations must be prepared by, or prepared under the immediate supervision of, the QFPE. The QFPE must affix their professional engineering stamp with signature to the shop drawings, calculations, and material data sheets, indicating approval prior to submitting the shop drawings to the DFPE.
b. Providing a letter documenting that the SD-02, SD-03, and SD-05 submittal package has been reviewed and noting any outstanding comments.
c. Performing in-progress construction surveillance prior to installation of ceilings (rough-in inspection).
d. Witnessing pre-Government and final Government functional performance testing and performing a final installation review.
e. Signing applicable certificates under SD-07.
1.4 DEFINITIONS
Wherever mentioned in this specification or on the drawings, the equipment, devices, and functions must be defined as follows:
1.4.1 Interface Device
An addressable device that interconnects hard wired systems or devices to an analog/addressable system.
SECTION 28 31 70 Page 3
1.4.2 Fire Alarm Control Unit (FACU)
A master control unit having the features of a fire alarm control unit
(FACU).
1.4.3 Remote Fire Alarm Control Unit
A control unit, physically remote from the fire alarm control unit, that receives inputs from automatic and manual fire alarm devices; may supply power to detection devices and interface devices; may provide transfer of power to the notification appliances; may provide transfer of condition to relays or devices connected to the control unit; and reports to and receives signals from the fire alarm and mass notification control unit.
1.4.4 Terminal Cabinet
A steel cabinet with locking, hinge-mounted door where terminal strips are securely mounted inside the cabinet.
1.4.5 Control Module and Relay Module
Terms utilized to describe emergency control function interface devices as defined by NFPA 72 .
1.4.6 Designated Fire Protection Engineer (DFPE)
The DoD fire protection engineer that oversees that Area of Responsibility for that project. This is sometimes referred to as the "cognizant" fire protection engineer. Interpret reference to "authority having jurisdiction" and/or AHJ in referenced standards to mean the Designated Fire Protection Engineer (DFPE). The DFPE may be responsible for review of the contractor submittals having a "G" designation, and for witnessing final inspection and testing.
1.4.7 Qualified Fire Protection Engineer (QFPE)
A QFPE is an individual who is a licensed professional engineer (P.E.), who has passed the fire protection engineering written examination administered by the National Council of Examiners for Engineering and Surveying (NCEES) and has relevant fire protection engineering experience.
1.5 SUBMITTALS
Government approval is required for submittals with a "G" or "S" classification. Submittals not having a "G" or "S" classification are for information only. When used, a code following the "G" classification identifies the office that will review the submittal for the Government.
Shop drawings (SD-02), product data (SD-03) and calculations (SD-05) must be prepared by the fire alarm designer and combined and submitted as one complete package. The QFPE must review the SD-02/SD-03/SD-05 submittal package for completeness and compliance with the Contract provisions prior to submission to the Government. The QFPE must provide a Letter of Confirmation that they have reviewed the submittal package for compliance with the contract provisions. This letter must include their registered professional engineer stamp and signature. Partial submittals and submittals not reviewed by the QFPE will be returned by the Government disapproved without review.
SECTION 28 31 70 Page 4
Submit the following in accordance with Section 01 33 00 SUBMITTAL
PROCEDURES:
SD-01 Preconstruction Submittals
Qualified Fire Protection Engineer (QFPE); G
Fire alarm system designer; G
Supervisor; G
Technician; G
Installer; G
Test Technician; G
SD-02 Shop Drawings
Nameplates; G
Instructions; G
Wiring Diagrams; G
System Layout; G
Notification Appliances; G
Initiating devices; G
Battery Power; G
Voltage Drop Calculations; G
SD-03 Product Data
Fire Alarm Control Unit (FACU); G
LCD Annunciator; G
Manual Stations; G
Smoke Detectors; G
Duct Smoke Detectors; G
Heat Detectors; G
Carbon monoxide detector; G
Addressable Interface Devices; G
Addressable Control Modules; G
SECTION 28 31 70 Page 5
Notification Appliances; G
Batteries; G
Battery Chargers; G
Surge Protective Devices; G
Alarm Wiring; G
Back Boxes and Conduit; G
Ceiling Bridges for Ceiling-Mounted Appliances; G
Terminal Cabinets; G
Digital Alarm Communicator Transmitter (DACT); G
Automatic Fire Alarm Transmitters (including housing); G
Environmental Enclosures or Guards; G
Document Storage Cabinet; G
SD-06 Test Reports
Test Procedures; G
SD-07 Certificates
Verification of Compliant Installation; G
Request for Government Final Test; G
SD-10 Operation and Maintenance Data
Operation and Maintenance (O&M) Instructions; G
Instruction of Government Employees; G
SD-11 Closeout Submittals
As-Built Drawings
Spare Parts
1.6 SYSTEM OPERATION
Fire alarm system components requiring power, except for the FACU(s) power supply, must operate on 24 volts DC unless noted otherwise in this section.
The interior fire alarm system must be a complete, supervised, noncoded, analog/addressable fire alarm system conforming to NFPA 72 , and UL 864 .
Systems meeting UL 2017 only are not acceptable. The system must be activated into the alarm mode by actuation of an alarm initiating device.
SECTION 28 31 70 Page 6
The system must remain in the alarm mode until the initiating device is reset and the control unit is reset and restored to normal.
1.6.1 Alarm Initiating Devices and Notification Appliances (Visual, Audible)
a. Connect alarm initiating devices to initiating device circuits (IDC) Class "B", or to signaling line circuits (SLC) Class "B" and installed in accordance with NFPA 72 .
b. Connect notification appliances to notification appliance circuits (NAC) Class "B".
1.6.2 Functions and Operating Features
The system must provide the following functions and operating features:
a. Power, annunciation, supervision, and control for the system.
Addressable systems must be microcomputer (microprocessor or microcontroller) based with a minimum word size of eight bits with sufficient memory to perform as specified.
b. Visual alarm notification appliances must be synchronized as required by NFPA 72 .
c. Electrical supervision of the primary power (AC) supply, presence of the battery, battery voltage, and placement of system modules within the control unit.
d. An audible and visual trouble signal to activate upon a single break or open condition, or ground fault. The trouble signal must also operate upon loss of primary power (AC) supply, absence of a battery supply, low battery voltage, or removal of alarm or supervisory control unit modules. After the system returns to normal operating conditions, the trouble signal must again sound until the trouble is acknowledged. A smoke detector in the process of being verified for the actual presence of smoke must not initiate a trouble condition.
e. A trouble signal silence feature that must silence the audible trouble signal, without affecting the visual indicator.
f. Program capability via switches in a locked portion of the FACU to bypass the automatic notification appliance circuits, features.
Operation of this programmed action must indicate on the FACU display as a supervisory or trouble condition. Notification appliance bypass must be selectable by floor.
g. Alarm functions must override trouble or supervisory functions.
Supervisory functions must override trouble functions.
h. The system must be capable of being programmed from the control unit keyboard. Programmed information must be stored in non-volatile memory.
i. The system must be capable of operating, supervising, and/or monitoring non-addressable alarm and supervisory devices.
SECTION 28 31 70 Page 7
j. There must be no limit, other than maximum system capacity, as to the number of addressable devices that may be in alarm simultaneously.
k. Where the fire alarm system is responsible for initiating an action in another emergency control device or system, such as the HVAC system, the addressable fire alarm relay must be located in the vicinity of the emergency control device.
l. An alarm signal must automatically initiate the following functions:
(1) Transmission of an alarm signal to the fire department.
(2) Visual indication of the device operated on the FACU, and on the remote annunciator.
(3) Actuation of alarm notification appliances.
(4) Recording of the event electronically in the history log of the
FACU.
m. A supervisory signal must automatically initiate the following functions:
(1) Visual indication of the device operated on the FACU, remote annunciator.
(2) Transmission of a supervisory signal to the fire department.
(3) Operation of a duct smoke detector must shut down the appropriate air handler in accordance with NFPA 90A in addition to other requirements of this paragraph and as allowed by NFPA 72 .
(4) Recording of the event electronically in the history log of the
FACU.
n. A trouble condition must automatically initiate the following functions:
(1) Visual indication of the device operated on the FACU, and on the remote annunciator.
(2) Transmission of a trouble signal to the fire department.
(3) Recording of the event electronically in the history log of the
FACU.
o. Activation of a carbon monoxide alarm initiating device must automatically initiate the following functions:
(1) Visual indication of the device operated on the FACU , and on the remote annunciator.
(2) Transmission of a carbon monoxide alarm signal to the fire
SECTION 28 31 70 Page 8 department.
(3) Activation of all strobes and the carbon monoxide alarm signal throughout the building.
(4) Recording of the event electronically in the history log of the
FACU.
p. System control equipment must be programmed to provide a 60-minute to 180-minute delay in transmission of trouble signals resulting from primary power failure.
1.7 QUALITY ASSURANCE
1.7.1 Submittal Documents
1.7.1.1 Preconstruction Submittals
Within 36 days of contract award but not less than 14 days prior to commencing any work on site, the Contractor must submit the following for review and approval. SD-02, SD-03 and SD-05 submittals received prior to the review and approval of the qualifications of the fire alarm subcontractor and QFPE must be returned disapproved without review. All resultant delays must be the sole responsibility of the Contractor.
1.7.1.2 Shop Drawings
Shop drawings must not be smaller than ANSI D. Drawings must comply with the requirements of NFPA 72 and NFPA 170 . Minimum scale for floor plans must be 1/8"=1'.
1.7.1.3 Nameplates
Nameplate illustrations and data to obtain approval by the Contracting Officer before installation.
1.7.1.4 Wiring Diagrams
One electric copy copies of point-to-point wiring diagrams showing the points of connection and terminals used for electrical field connections in the system, including interconnections between the equipment or systems that are supervised or controlled by the system. Diagrams must show connections from field devices to the FACU and remote FACU, initiating circuits, switches, relays and terminals, including pathway diagrams between the control unit and shared communications equipment within the protected premises. Point-to-point wiring diagrams must be job specific and must not indicate connections or circuits not being utilized. Provide complete riser diagrams indicating the wiring sequence of all devices and their connections to the control equipment. Include a color-code schedule for the wiring.
1.7.1.5 System Layout
One electronic copy copies of plan view drawing showing device locations, terminal cabinet locations, junction boxes, other related equipment, conduit routing, conduit sizes, wire counts, conduit fill calculations, wire color-coding, circuit identification in each conduit, and circuit layouts for all floors. Indicate candela rating of each visual notification appliance. Clearly identify the locations of isolation
SECTION 28 31 70 Page 9 modules. Indicate the addresses of all devices, modules, relays, and similar. Indicate if the environment for the FACU is within its environmental listing (e.g. temperature/humidity).
Provide a complete description of the system operation in matrix format similar to the "Typical Input/Output Matrix" included in the Annex of
NFPA 72 .
1.7.1.6 Notification Appliances
Calculations and supporting data on each circuit to indicate that there is at least 25 percent spare capacity for notification appliances. Annotate data for each circuit on the drawings.
1.7.1.7 Initiating Devices
Calculations and supporting data on each circuit to indicate that there is at least 25 percent spare capacity for initiating devices. Annotate data for each circuit on the drawings.
1.7.1.8 Battery Power
Calculations and supporting data as required in paragraph Battery Power Calculations for alarm, alert, and supervisory power requirements.
Calculations including ampere-hour requirements for each system component and each control unit component, and the battery recharging period, must be included on the drawings.
1.7.1.9 Voltage Drop Calculations
Voltage drop calculations for each notification circuit indicating that sufficient voltage is available for proper operation of the system and all components, at a minimum rated voltage of the system operating on batteries. Include the calculations on the system layout drawings.
1.7.1.10 Product Data
One electronic copy copies of annotated descriptive data to show the specific model, type, and size of each item. Catalog cuts must also indicate the NRTL listing. The data must be highlighted to show model, size, and options that are intended for consideration. Data must be adequate to demonstrate compliance with all contract requirements.
Product data for all equipment must be combined into a single submittal.
Provide an equipment list identifying the type, quantity, make, and model number of each piece of equipment to be provided under this submittal.
The equipment list must include the type, quantity, make and model of spare equipment. Types and quantities of equipment submitted must coincide with the types and quantities of equipment used in the battery calculations and those shown on the shop drawings.
1.7.1.11 Operation and Maintenance (O&M) Instructions
One electronic copy copies of the Operation and Maintenance Instructions.
The O&M Instructions must be prepared in a single volume or in multiple volumes, with each volume indexed, and may be submitted as a Technical Data Package. Manuals must be approved prior to training. The Interior
SECTION 28 31 70 Page 10
Fire Alarm System Operation and Maintenance Instructions must include the following:
a. Manufacturer Data Package containing:
(1) Safety precautions and hazards
(2) Environmental conditions
(3) Preventive maintenance plan, schedule, and procedures
(4) Troubleshooting guides and diagnostic techniques
(5) Wiring and control diagrams
(6) Maintenance and repair procedures
(7) Removal and replacement instructions
(8) Spare parts and supply list
(9) Product submittal data
(10) Parts Identification
(11) Testing equipment and special tool information
(12) Warranty information
(13) Testing and performance data
b. Operating manual outlining step-by-step procedures required for system startup, operation, and shutdown. The manual must include the manufacturer's name, model number, service manual, parts list, and preliminary equipment list complete with description of equipment and their basic operating features.
c. Maintenance manual listing routine maintenance procedures, possible breakdowns and repairs, and troubleshooting guide. The manuals must include conduit layout, equipment layout and simplified wiring, and control diagrams of the system as installed.
d. Complete procedures for system revision and expansion, detailing both equipment and software requirements.
e. Printouts of configuration settings for all devices.
f. Routine maintenance checklist. The routine maintenance checklist must be arranged in a columnar format. The first column must list all installed devices, the second column must state the maintenance activity or state no maintenance required, the third column must state the frequency of the maintenance activity, and the fourth column provided for additional comments or reference. All data (devices, testing frequencies, and similar) must comply with UFC 3-601-02 .
g. A final Equipment List must be submitted with the Operating and Maintenance (O&M) manual.
1.7.1.12 As-Built Drawings
The drawings must show the system as installed, including deviations from both the project drawings and the approved shop drawings. These drawings must be submitted within two weeks after the final Government test of the system. At least one set of the as-built (marked-up) drawings must be provided at the time of, or prior to the final Government test.
SECTION 28 31 70 Page 11
1.7.2 Qualifications
1.7.2.1 Fire Alarm System Designer
The fire alarm system designer must be certified as a Level III (minimum) Technician by National Institute for Certification in Engineering Technologies (NICET) in the Fire Alarm Systems subfield of Fire Protection Engineering Technology or meet the qualifications for a QFPE.
1.7.2.2 Supervisor
A NICET Level III or IV fire alarm technician must supervise the installation of the fire alarm system. The fire alarm technicians supervising the installation of equipment must be factory trained in the installation, adjustment, testing, and operation of the equipment specified herein and on the drawings.
1.7.2.3 Technician
Fire alarm technicians with a minimum of four years of experience must be utilized to install and terminate fire alarm devices, cabinets and control units. The fire alarm technicians installing the equipment must be factory trained in the installation, adjustment, testing, and operation of the equipment specified herein and on the drawings.
1.7.2.4 Installer
Fire alarm installer with a minimum of two years of experience utilized to assist in the installation of fire alarm devices, cabinets and control units . A licensed electrician must be allowed to install wire, cable, conduit and backboxes for the fire alarm system system. The fire alarm installer must be factory trained in the installation, adjustment, testing, and operation of the equipment specified herein and on the drawings.
1.7.2.5 Test Technician
Fire alarm technicians with a minimum of eight years of experience and NICET Level III or IVutilized in testing and certification of the installation of the fire alarm devices, cabinets and control units. The fire alarm technicians testing the equipment must be factory trained in the installation, adjustment, testing, and operation of the equipment installed as part of this project.
1.7.2.6 Manufacturer
Components must be of current design and must be in regular and recurrent production at the time of installation. Provide design, materials, and devices for a protected premises fire alarm system, complete, conforming to NFPA 72 , except as specified herein.
1.7.3 Regulatory Requirements
Equipment and material must be listed or approved. Listed or approved, as used in this Section, means listed, labeled or approved by a Nationally Recognized Testing Laboratory (NRTL) such as UL Fire Prot Dir or FM APP GUIDE. The omission of these terms under the description of any item of equipment described must not be construed as waiving this requirement. All listings or approvals by testing laboratories must be
SECTION 28 31 70 Page 12 from an existing ANSI or UL published standard. The recommended practices stated in the manufacturer's literature or documentation must be considered as mandatory requirements.
1.8 DELIVERY, STORAGE, AND HANDLING
Protect equipment delivered and placed in storage from the weather, humidity, and temperature variation, dirt and dust, and other contaminants.
1.9 MAINTENANCE
1.9.1 Spare Parts
Furnish the following spare parts in the manufacturers original unopened containers:
a. Two complete sets of system keys.
b. Two of each type of fuse required by the system.
c. One manual stations.
d. Two of each type of detector installed.
e. Two of each type of detector base and head installed.
f. One of each type of audible and visual alarm device installed.
g. One of each type of addressable monitor module installed.
h. One of each type of addressable control module installed.
i. One low voltage, , and one 120 VAC surge protective device.
1.9.2 Special Tools
Software, connecting cables and proprietary equipment, necessary for the maintenance, testing, and reprogramming of the equipment must be furnished to the Contracting Officer, prior to the instruction of Government employees.
PART 2 PRODUCTS
2.1 GENERAL PRODUCT REQUIREMENT
All fire alarm equipment must be listed for use under the applicable reference standards.
2.2 MATERIALS AND EQUIPMENT
2.2.1 Standard Products
Provide materials, equipment, and devices that have been tested by a nationally recognized testing laboratory and listed for fire protection service when so required by NFPA 72 or this specification. Select material from one manufacturer, where possible, and not a combination of manufacturers, for any particular classification of materials. Material
SECTION 28 31 70 Page 13 and equipment must be the standard products of a manufacturer regularly engaged in the manufacture of the products for at least 2 years prior to bid opening.
2.2.2 Nameplates
Major components of equipment must have the manufacturer's name, address, type or style, model or serial number, catalog number, date of installation, installing Contractor's name and address, and the contract number provided on a new name plate permanently affixed to the item or equipment. Major components include, but are not limited to, the following:
a. FACU
Nameplates must be etched metal or plastic, permanently attached by screws to control units or adjacent walls.
2.2.3 Keys
Keys and locks for equipment, control units and devices must be identical. .
2.2.4 Instructions
Provide a typeset printed or typewritten instruction card mounted behind a Lexan plastic or glass cover in a stainless steel or aluminum frame.
Install the instructions on the interior of the FACU. The card must show those steps to be taken by an operator when a signal is received as well as the functional operation of the system under all conditions, normal, alarm, supervisory, and trouble. The instructions and their mounting location must be approved by the Contracting Officer before being posted.
2.3 FIRE ALARM CONTROL UNIT
Provide a complete fire alarm control unit (FACU) fully enclosed in a lockable steel cabinet as specified herein. Operations required for testing or for normal care, maintenance, and use of the system must be performed from the front of the enclosure. If more than a single unit is required at a location to form a complete control unit, the unit cabinets must match exactly. The system must be capable of defining any module as an alarm module and report alarm trouble, loss of polling, or as a supervisory module, and reporting supervisory short, supervisory open or loss of polling such as waterflow switches, valve supervisory switches, fire pump monitoring, independent smoke detection systems, relays for output function actuation.
a. Each control unit must provide power, supervision, control, and logic for the entire system, utilizing solid state, modular components, internally mounted and arranged for easy access. Each control unit must be suitable for operation on a 120 volt, 60 hertz, normal building power supply. Provide each control unit with supervisory functions for power failure, internal component placement, and operation.
b. Visual indication of alarm, supervisory, or trouble initiation on the FACU must be by liquid crystal display or similar means with a minimum of 80 characters.
SECTION 28 31 70 Page 14
2.3.1 Cabinet
Install control unit components in cabinets large enough to accommodate all components and also to allow ample gutter space for interconnection of control units as well as field wiring. The cabinet must be a sturdy steel housing, complete with back box, hinged steel door with cylinder lock, and surface or semi-recessed mounting provisions as appropriate for the chosen location. The enclosure must be identified by an engraved phenolic resin nameplate. Lettering on the nameplate must say "Fire Alarm control unit" and must not be less than 1-inch high. Provide prominent rigid plastic or metal identification plates for lamps, circuits, meters, fuses, and switches.
2.3.2 Silencing Switches
2.3.2.1 Alarm Silencing Switch
Provide an alarm silencing switch at the FACU that must silence the audible and visual notification appliances. Subsequent activation of initiating devices must cause the notification appliances to re-activate.
2.3.2.2 Supervisory/Trouble Silencing Switch
Provide supervisory and trouble silencing switch(es) that must silence the audible trouble and supervisory signal(s), but not extinguish the visual indicator. This switch must be overridden upon activation of a subsequent supervisory or trouble condition. Audible trouble indication must resound automatically every 24 hours after the silencing feature has been operated if the supervisory or trouble condition still exists.
2.3.3 Non-Interfering
Power and supervise each circuit such that a signal from one device does not prevent the receipt of signals from any other device. Initiating devices must be manually reset by switch from the FACU after the initiating device or devices have been restored to normal.
2.3.4 Memory
Provide each control unit with non-volatile memory and logic for all functions. The use of long life batteries, capacitors, or other age-dependent devices must not be considered as equal to non-volatile processors, PROMS, or EPROMS.
2.3.5 Field Programmability
Provide control units and control units that are fully field programmable for both input and output of control, initiation, notification, supervisory, and trouble functions. The system program configuration must be menu driven. System changes must be password protected. Any proprietary equipment and proprietary software needed by qualified technicians to implement future changes to the fire alarm system must be provided as part of this contract.
2.3.6 Input/Output Modifications
The FACU must contain features that allow the bypassing of input devices from the system or the modification of system outputs. These control features must consist of a control unit mounted keypad. Any bypass or
SECTION 28 31 70 Page 15 modification to the system must indicate a trouble condition on the FACU.
2.3.7 Resetting
Provide the necessary controls to prevent the resetting of any alarm, supervisory, or trouble signal while the alarm, supervisory or trouble condition on the system still exists.
2.3.8 Walk Test
The FACU must have a walk test feature. When using this feature, operation of initiating devices must result in limited system outputs, so that the notification appliances operate for only a few seconds and the event is indicated in the history log, but no other outputs occur.
2.3.9 History Logging
The control unit must have the ability to store a minimum of 400 events in a log. These events must be stored in a battery-protected memory and must remain in the memory until the memory is downloaded or cleared manually.
Resetting of the control unit must not clear the memory.
2.3.10 Manual Access
An operator at the control unit, having a proper access level, must have the capability to manually access the following information for each initiating device.
a. Primary status.
b. Device type.
c. Present average value.
d. Present sensitivity selected.
e. Detector range (normal, dirty).
2.3.11 Heat Detector Self-Test Routines
Automatic self-test routines must be performed on each detector that will functionally check detector sensitivity electronics and ensure the accuracy of the value being transmitted. Any detector that fails this test must indicate a trouble condition with the detector location at the control unit.
2.4 REMOTE ANNUNCIATOR
2.4.1 LCD Annunciator
Provide a flush mounted annunciator that includes an LCD display. The display must indicate the device in trouble/alarm or any supervisory device. Display the device name, address.
A building floor plan must be provided and mounted (behind Plexiglass or similar protective material) at the annunciator location. The floor plan must indicate all rooms by name and number including the locations of stairs and elevators. The floor plan must show all devices and their programmed address to facilitate identification of their physical location
SECTION 28 31 70 Page 16 from the LCD display information.
2.5 MANUAL STATIONS
Provide metal or plastic, surface mounted, double-action, addressable manual stations, that are not subject to operation by jarring or vibration. Stations must be equipped with screw terminals for each conductor. Stations that require the replacement of any portion of the device after activation are not permitted. Stations must be finished in red with molded raised lettering operating instructions of contrasting color. The use of a key must be required to reset the station.
2.6 SMOKE DETECTORS
2.6.1 Spot Type Detectors
Provide addressable photoelectric smoke detectors as follows:
a. Provide analog/addressable photoelectric smoke detectors utilizing the photoelectric light scattering principle for operation in accordance with UL 268 . Smoke detectors must be listed for use with the FACU.
b. Provide self-restoring type detectors that do not require any readjustment after actuation at the FACU to restore them to normal operation. The detector must have a visual indicator to show actuation.
c. Vibration must have no effect on the detector's operation. Protect the detection chamber with a fine mesh metallic screen that prevents the entrance of insects or airborne materials. The screen must not inhibit the movement of smoke particles into the chamber.
d. Provide twist lock bases with screw terminals for each conductor. The detectors must maintain contact with their bases without the use of springs.
e. The detector address must identify the particular unit, its location within the system, and its sensitivity setting. Detectors must be of the low voltage type rated for use on a 24 VDC system.
2.6.2 Duct Smoke Detectors
Duct-mounted addressable photoelectric smoke detectors must consist of a smoke detector, as specified in paragraph Spot Type Detectors, mounted in a special housing fitted with duct sampling tubes. Detector circuitry must be mounted in a metallic or plastic enclosure exterior to the duct.
It is not permitted to cut the duct insulation to install the duct detector directly on the duct. Detectors must be listed for operation over the complete range of air velocities, temperature and humidity expected at the detector when the air-handling system is operating.
Detectors must be powered from the FACU.
a. Sampling tubes must run the full width of the duct. The duct detector package must conform to the requirements of NFPA 90A, UL 268A , and must be listed for use in air-handling systems. The control functions, operation, reset, and bypass must be controlled from the
FACU.
b. Lights to indicate the operation and alarm condition must be visible
SECTION 28 31 70 Page 17 and accessible with the unit installed and the cover in place. Remote indicators must be provided where required by NFPA 72 . Remote indicators as well as the affected fan units must be properly identified in etched plastic placards.
c. Detectors must provide for control of auxiliary contacts that provide control, interlock, and shutdown functions specified in NFPA 90A.
Auxiliary contacts provide for this function must be located within 3 feet of the controlled circuit or appliance. The auxiliary contacts must be supplied by the fire alarm system manufacturer to ensure complete system compatibility.
2.7 HEAT DETECTORS
2.7.1 Heat Detectors
Heat detectors must be analog/addressable and designed for detection of fire by fixed temperature in accordance with UL 521 . The alarm condition must be determined by comparing detector value with the stored values..
Detectors located in areas subject to moisture, exterior atmospheric conditions, or hazardous locations as defined by NFPA 70 , must be types approved for such locations.
2.7.1.1 Fixed Temperature Detectors
Detectors must be surface mounted in the horizontal orientation and supported independently of wiring connections. Detectors must be self-restoring. The detectors must have a specific temperature setting of 135 degrees F.
2.8 CARBON MONOXIDE DETECTOR
Analog/addressable carbon monoxide (CO) detectors must be listed to UL 2075 and set to respond to the sensitivity limits of UL 2034 . Carbon monoxide detectors must be listed for use with fire alarm control units. Detectors must be surface mounted in the horizontal orientation and supported independently of wiring connections. Detectors must be self-restoring.
For FACU with no listed compatible addressable CO detectors, provide listed 4-wire detectors. Do not provide CO detectors with local alarms.
Detector must be provided with an LED status indicator.
a. Where 4-wire CO detectors are necessary, each 4-wire CO detector must be individually monitored via addressable interface modules for alarm and off normal/trouble conditions (including loss of power to the individual detector). Power circuits for 4-wire CO detectors must be dedicated to powering the CO detectors only. Battery powered and 120 VAC powered detectors are prohibited.
b. Wiring connections must be made by means of screw terminals and detectors must be equipped with trouble relays. Detectors must be able to mount a single-gang electrical box.
c. A trouble condition at an individual CO detector must not affect any other CO detectors. CO detectors must be powered by the FACU.
d. Detectors must be provided with a means to test CO gas entry into the CO sensing cell.
SECTION 28 31 70 Page 18
2.9 ADDRESSABLE INTERFACE DEVICES
The initiating device being monitored must be configured as a Class "B" initiating device circuits. The module must be listed as compatible with the control unit. The module must provide address setting means compatible with the control unit's SLC supervision and store an internal identifying code. Monitor module must contain an integral LED that flashes each time the monitor module is polled and is visible through the device cover plate. Pull stations with a monitor module in a common backbox are not required to have an LED. Modules must be listed for the environmental conditions in which they will be installed.
2.10 ADDRESSABLE CONTROL MODULES
The control module must be capable of operating as a relay (dry contact form C) for interfacing the control unit with other systems, and to control door holders or initiate elevator fire service. The module must be listed as compatible with the control unit. The indicating device or the external load being controlled must be configured as Class B notification appliance circuits. The system must be capable of supervising, audible, visual and dry contact circuits. The control module must have both an input and output address. The supervision must detect a short on the supervised circuit and must prevent power from being applied to the circuit. The control model must provide address setting means compatible with the control unit's SLC supervision and store an internal identifying code. The control module must contain an integral LED that flashes each time the control module is polled and is visible through the device cover plate. Control Modules must be listed for the environmental conditions in which they will be installed.
2.11 NOTIFICATION APPLIANCES
2.11.1 Audible Notification Appliances
Audible appliances must conform to the applicable requirements of UL 464 .
Appliances must be connected into notification appliance circuits.
Surface mounted audible appliances must be painted red. Recessed audible appliances must be installed with a grill that is painted red.
2.11.1.1 Horns
Horns must be surface-mounted, with the matching mounting backbox surface mounted vibrating type suitable for use in an electrically supervised circuit. Horns must produce a sound rating of at least 85 dBA at 10 feet.
Horns used in exterior locations must be specifically listed or approved for outdoor use and be provided with metal housing and protective grilles.
2.11.2 Visual Notification Appliances
Visual notification appliances must conform to the applicable requirements of UL 1638 , UL 1971 and conform to the Architectural Barriers Act (ABA).
Visual Notification Appliances must have clear high intensity optic lens, xenon flash tubes, or light emitting diode (LED) and be marked "Alert" in letters of contrasting color. The light pattern must be disbursed so that it is visible above and below the strobe and from a 90 degree angle on both sides of the strobe. Strobe flash rate must be 1 flash per second and a minimum of 15 candela based on the UL 1971 test. Strobe must be surface mounted.
SECTION 28 31 70 Page 19
2.12 ELECTRIC POWER
2.12.1 Primary Power
Power must be 120 VAC 60 Hz service for the FACU from the AC service to the building in accordance with NFPA 72 .
2.13 SECONDARY POWER SUPPLY
Provide for system operation in the event of primary power source failure. Transfer from normal to auxiliary (secondary) power or restoration from auxiliary to normal power must be automatic and must not cause transmission of a false alarm.
2.13.1 Batteries
Provide sealed, maintenance-free, sealed lead acid batteries as the source for emergency power to the FACU. Batteries must contain suspended electrolyte. The battery system must be maintained in a fully charged condition by means of a solid state battery charger. Provide an automatic transfer switch to transfer the load to the batteries in the event of the failure of primary power.
2.13.1.1 Capacity
Battery size must be the following capacity. This capacity applies to every control unit associated with this system, including fire alarm transmitters.
a. Sufficient capacity to operate the fire alarm system under supervisory and trouble conditions, including audible trouble signal devices for 48 hours and audible and visual signal devices under alarm conditions for an additional 15 minutes.
2.13.1.2 Battery Power Calculations
a. Verify that battery capacity exceeds supervisory and alarm power requirements for the criteria noted in the paragraph "Capacity" above.
(1) Substantiate the battery calculations for alarm and supervisory power requirements. Include ampere-hour requirements for each system component and each control unit component, and compliance with UL 864 .
(2) Provide complete battery calculations for both the alarm and supervisory power requirements. Submit ampere-hour requirements for each system component with the calculations.
(3) Provide voltage drop calculations to indicate that sufficient voltage is available for proper operation of the system and all components. Calculations must be performed using the minimum rated voltage of each component.
b. For battery calculations assume a starting voltage of 24 VDC for starting the calculations to size the batteries. Calculate the required Amp-Hours for the specified standby time, and then calculate the required Amp-Hours for the specified alarm time. Using 20.4 VDC as starting voltage, perform a voltage drop calculation for circuits
SECTION 28 31 70 Page 20 containing device and/or appliances remote from the power sources.
2.13.2 Battery Chargers
Provide a solid state, fully automatic, variable charging rate battery charger. The charger must be capable of providing 120 percent of the connected system load and must maintain the batteries at full charge. In the event the batteries are fully discharged (20.4 Volts dc), the charger must recharge the batteries back to 95 percent of full charge within 48 hours after a single discharge cycle as described in paragraph CAPACITY above. Provide pilot light to indicate when batteries are manually placed on a high rate of charge as part of the unit assembly if a high rate switch is provided.
2.14 SURGE PROTECTIVE DEVICES
Surge protective devices must be provided to suppress all voltage transients which might damage fire alarm control unit components. Systems having circuits located outdoors, communications equipment must be protected against surges induced on any signaling line circuit. Cables and conductors, that serve as communications links, must have surge protection circuits installed at each end. The surge protective device must wire in series to the power supply of the protected equipment with screw terminations. Line voltage surge arrestor must be installed directly adjacent to the power panel where the FACU breaker is located.
a. Surge protective devices for nominal 120 VAC must be UL 1449 listed with a maximum 500 volt suppression level and have a maximum response time of 5 nanoseconds. The surge protective device must also meet IEEE C62.41.1 and IEEE C62.41.2 category B tests for surge capacity.
The surge protective device must feature multi-stage construction and be provided with a long-life indicator lamp (either light emitting diode or neon) which extinguishes upon failure of protected components. Any unit fusing must be externally accessible.
b. Surge protective devices for nominal 24 VAC, fire alarm telephone dialer, or ethernet connection must be UL 497B listed, meet IEEE C62.41.1 and have a maximum response time of 1-nanosecond. The surge protective device must feature multi-stage construction and be self-resetting. The surge protective device must be a base and plug style. The base assembly must have screw terminals for fire alarm wiring. The base assembly must accept "plug-in" surge protective module.
c. All surge protective devices (SPD) must be the standard product of a single manufacturer and be equal or better than the following:
(1) For 120 VAC nominal line voltage: UL 1449 and UL 1283 listed, series connected 120 VAC, 20A rated, surge protective device in a NEMA 4x enclosure. Minimum 50,000 amp surge current rating with EMI/RFI filtering and a dry contact circuit for remote monitoring of surge protection status.
(2) For 24-volt nominal line voltage: UL 497B listed, series connected low voltage, 24-volt, 5A rated, loop circuit protector, base and replaceable module.
(3) For alarm telephone dialers: UL 497A listed, series connected, 130-volt, 150 mA rated with self-resetting fuse, dialer circuit
SECTION 28 31 70 Page 21 protector with modular plug and play.
(4) For IP-DACTS: UL 497B listed, series connected, 6.4-volt, 1.5A rated with 20 kA/pair surge current, data network protector with modular plug and play.
2.15 WIRING
2.15.1 Alarm Wiring
IDC and SLC wiring must be fiber optic or solid copper cable in accordance with the manufacturers requirements. Copper signaling line circuits and initiating device circuit field wiring must be No. 14 AWG size conductors at a minimum. Visual notification appliance circuit conductors, that contain audible alarm appliances, must be copper No. 14 AWG size conductors at a minimum. Wire size must be sufficient to prevent voltage drop problems. Circuits operating at 24 VDC must not operate at less than the listed voltages for the detectors and/or appliances. Power wiring, operating at 120 VAC minimum, must be a minimum No. 12 AWG solid copper having similar insulation. Acceptable power-limited cables are FPL, FPLR or FPLP as appropriate with red colored covering. Nonpower-limited cables must comply with NFPA 70 .
2.16 AUTOMATIC FIRE ALARM TRANSMITTERS
2.16.1 Digital Alarm Communicator Transmitter (DACT)
Provide DACT. Transmitter must have a means to transmit alarm, supervisory, and trouble conditions via a single transmitter. Transmitter must have a source of power for operation that conforms to NFPA 72 .
Transmitter must be capable of initiating a test signal daily at any selected time. Transmitters integrated into the control unit are permitted.
2.16.2 Signals to Be Transmitted to the Base Receiving Station
The following signals must be sent to the base receiving station:
a. Manual pull stations
b. Smoke detectors
c. Duct smoke detectors
d. Carbon monoxide detectors
e. Heat detectors
2.17 ENVIRONMENTAL ENCLOSURES OR GUARDS
Environmental enclosures must be provided to permit fire alarm components to be used in areas that exceed the environmental limits of the listing.
The enclosure must be listed for the device or appliance as either a manufactured part number or as a listed compatible accessory for the component is currently listed. Guards required to deter mechanical damage must be either a listed manufactured part or a listed accessory for the
SECTION 28 31 70 Page 22 category of the initiating device or notification appliance.
PART 3 EXECUTION
3.1 VERIFYING ACTUAL FIELD CONDITIONS
Before commencing work, examine all adjoining work on which the contractor's work is in any way dependent for perfect workmanship according to the intent of this specification section, and report to the Contracting Officer's Representative any condition which prevents performance of first class work. No "waiver of responsibility" for incomplete, inadequate or defective adjoining work will be considered unless notice has been filed before submittal of a proposal.
3.2 INSTALLATION
3.2.1 Fire Alarm Control Unit (FACU)
Locate the FACU in coordination with the Lockmaster. Surface mount the enclosure with the top of the cabinet 6 feet above the finished floor or center the cabinet at 5 feet, whichever is lower. Conductor terminations must be labeled and a drawing containing conductors, their labels, their circuits, and their interconnection must be permanently mounted in the FACU.
This is the start of the file's text. The full file is on GovTribe.