1. Main Office – Conference Room (Figure 3: The material list does not provide the count of the required fixtures. Please provide the quantities.)
Quantity of 11 Panel light fixtures 2’x4’ and 12 dimmable can lights
2. Main Office – Conference Room (Figure 3: The photo shows can lights; are these included with the RFQ? If so, what are your requirements and what are the quantities?)
Quantity of 12 dimmable can lights that are 90W 120v
3. Welding Building – (Figure 10: The SOW talks about adding and additional 5 high bay lights; from 10 to 15. The addendum material list shows only 10 fixtures are required. Please clarify, do you need 10 or 15?)
Quantity of 15 light fixtures total
4. North Storage – Open Bay (Figure 11: Are the shown Fixtures 4’ or 8’ fixtures? If 8’, would you require consistent high bay products that will be installed in the other buildings?)
They are 4’ fixtures and we would like to stay consistent in all high bay areas with 4’ high bay fixtures
5. Outdoor 1 – (Figure 14: The shown fixture appears to be a 175W MH Wall Pack; please confirm current wattage so an appropriate LED replacement fixtures can be specified.
Yes 175W MH Wall Pack
6. Outdoor 2 – (Figure 15: The shown fixture appears to be a 250W MH Flood Light; please confirm current wattage so an appropriate LED replacement fixtures can be specified.
Yes 250W MH Flood Light
7. Outdoor 3 – (Figure 4: The shown fixture appears to be a 75W or 125W MH Wall Pack; please confirm current wattage so an appropriate LED replacement fixtures can be specified. Please provide quantities.
Yes 125W MH Wall Pack
8. Please provide ceiling height on all high bay lighting areas.
25’ max height on all high bay areas
9. Are all fixtures 120/277V? if not, please identify which fixtures are not All are building are 120V but the following: Welding building interior are 480V and one flood light on the exterior of the mill building riverward side is 480V but can be converted to 120V
10. Is there clear access to the current high bay lights; free from obstacles? If not, please identify what areas will require special lift equipment and description on how the bulbs are currently replace (Equipment, etc.)
The upper shop has bird netting in place that will be on the contractor to remove and put back up (probably be most economical for cut hole in netting and zip tie back together for future blub replacement. This area is all gravel so off road lift would be best suited.
All building other buildings are a concrete and can be accessed by JIG lift type equipment.