B.086 APPENDICES VOL 3 OF 3 PART A_MADF - 505270 - OCTOBER 2025.pdf

PDF 34 MB Posted

Attached to
W912ER26RA001 - Amendment 0001, Missile Assembly Disassembly Facility (MADF) Renovation
Solicitation number
W912ER26RA001
Issued by

About this file

This document is a Request for Proposals (RFP) for the Missile Assembly Disassembly Facility (MADF) Renovation project located at Camp Subhan, Kuwait, issued by the U.S. Army Corps of Engineers Middle East District. The solicitation (W912ER26RA001) seeks a design-build contractor to rehabilitate an existing missile assembly and disassembly facility, with an estimated project value between $10 million and $25 million and a 409-calendar day performance period.

The project involves comprehensive renovation of the facility, including structural, architectural, and systems upgrades. Key technical documents include detailed site plans, demolition plans, and facility layout drawings showing modifications to interior spaces, walls, doors, and mechanical/electrical systems. The solicitation is structured as a full and open competition using Federal Acquisition Regulation (FAR) Part 15 Contract by Negotiation, with the North American Industry Classification System (NAICS) code 236220 and a small business size standard of $45,000,000. Contractors will be required to provide complete design and construction services adhering to Kuwaiti and U.S. building codes, safety, and security standards.

View the file

Other files

File Type Posted
Solicitation Amendment W912ER26RA0010001 SF 30 10152025.pdf PDF
Solicitation Amendment W912ER26RA0010001 SF 30 10142025 .pdf PDF
20251001_054158997_iOS.jpg JPG image
20251001_054102596_iOS.jpg JPG image
20251001_055013895_iOS.jpg JPG image
20251001_053252849_iOS.jpg JPG image
20251001_055634313_iOS.jpg JPG image
20251001_053412038_iOS.jpg JPG image
20251001_053156134_iOS.jpg JPG image
20251001_055938417_iOS.jpg JPG image
20251001_053306981_iOS.jpg JPG image
20251001_055636791_iOS.jpg JPG image
22baf8d0-82c8-410f-b83b-8a9cfd25b7dc.jpg JPG image
20251001_054946779_iOS.jpg JPG image
ebfe75d4-cf9e-4cba-9cf4-f356c4491581.jpg JPG image
20251001_055021317_iOS.jpg JPG image
20251001_054958394_iOS.jpg JPG image
6935b979-6f5b-4055-8b74-04020f4924ac.jpg JPG image
20251001_055852577_iOS.jpg JPG image
20251001_054844805_iOS.jpg JPG image
20251001_053236117_iOS.jpg JPG image
20251001_053053160_iOS.jpg JPG image
1dbe8a28-7040-4e62-90a6-9c407dfbfa80.jpg JPG image
45c2afeb-5e15-4ab7-bd06-4aedf8ee744d.jpg JPG image
20251001_054816308_iOS.jpg JPG image
3f7f4003-e4b1-4833-9c51-2a3163369ad8.jpg JPG image
20251001_054843575_iOS.jpg JPG image
20251001_054856788_iOS.jpg JPG image
20251001_053450681_iOS.jpg JPG image
76702807-0676-4731-bdde-caae4c841c6f.jpg JPG image
b65350bb-29b7-4858-a729-e4995741e39c.jpg JPG image
20251001_054813862_iOS.jpg JPG image
20251001_054656356_iOS.jpg JPG image
20251001_055757091_iOS.jpg JPG image
20251001_053415283_iOS.jpg JPG image
20251001_054928898_iOS.jpg JPG image
20251001_053409813_iOS.jpg JPG image
20251001_054119678_iOS.jpg JPG image
20251001_053620052_iOS.jpg JPG image
20251001_053305062_iOS.jpg JPG image
20251001_054344378_iOS.jpg JPG image
20251001_053349262_iOS.jpg JPG image
20251001_055018569_iOS.jpg JPG image
20251001_053318098_iOS.jpg JPG image
db8f7e58-4b43-467a-bb69-00d39dd91bef.jpg JPG image
20251001_054809143_iOS.jpg JPG image
20251001_055906213_iOS.jpg JPG image
20251001_052349709_iOS.jpg JPG image
20251001_055809886_iOS.jpg JPG image
1ec155ab-b15b-468e-91b3-cf0bee2e6757.jpg JPG image
Show 40 more

Latest 50 of 69 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Request for Proposals

Specifications for

MISSILE ASSEMBLY-

DISASSEMBLY FACILITIES

(MADF) RENOVATION, Kuwait

Volume 3 of 3

APPENDICES

PART A

US Army Corps of Engineers Middle East District

W912ER25Rxxxx

US Army Corps of Engineers ®

SU

BM

IT

TE

D B

Y:

C H

EC

KE

D B

Y:

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

C O

N

TR

AC

T

N O

IS

SU

E D

AT

E:

SI

ZE

M

AR

K

D

ES

C R

IP

TI

O N

D

AT

E

SHEET ID

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

O

N

M

L

K

J

I

H

G

F

E

D

C

B

A

MIDDLE EAST DISTRICT

CAMP SUBHAN, KUWAIT

KUWAIT AIR DEFENCE

MISSILE ASSEMBLY DISASSEMBLY FACILITY (MADF) RENOVATION

KW-505270

W912ER26R001

W912ER25C####

AUGUST 2025ISSUE DATE:

SOLICITATION NO.:

CONTRACT NO.:

/0 8/

KW

-5

0G

EN

-G I0

L.

SA

N D

AT

E

J.

H

IE

R

G

EI

ST

E.

ST

IL

LM

AN

D .R

AC

KM

AL

ES

PR

O

JE

C

T C

O

VE

R S

H

EE

T G

EN

ER

AL

IN

FO

R

M

AT

IO

N

GI001

GEN

M

ID

D

LE

E

AS

T D

IS

TR

IC

T

PR

IN

C E

FR

ED

ER

IC

K D

R

IV

E W

IN

C

H

ES

TE

R

, V A

W

2E R

C

AU

G

U

ST

PL

O

T D

AT

E:

FI

LE

N

AM

E:

IS

O A

SO

LI

C

IT

AT

IO

N N

O

W

2E R

A0

C

AM

P

SU

BH

AN

, K U

W

AI

T

KU

W

AI

T

AI

R D

EF

EN

C E

M

IS

SI

LE

A

SS

EM

BL

Y D

IS

AS

SE

M

BL

Y

FA

C

IL

IT

Y (M

AD

F)

R

EN

O

VA

TI

O

N

KW

-5

C D

C

KW-505270 - MISSILE ASSEMBLY DISASSEMBLY FACILITY (MADF) RENOVATION INDEX OF DRAWINGS

SHEET ID FILENAME REV. NO. AM / COP NO. TITLE

GENERAL

GI001 KW-505270GEN-GI001 PROJECT COVER SHEET

GI001 KW-505270SITE--GI001 SITE DESIGN COVER SHEET

SITE DESIGN

VF101 KW-505270ASITE-VF101 SURVEY CONTROL POINTS

CS101 KW-505270SITE--CS101 SITE PLAN

ARCHITECTURAL

AD101 KW-505270A-AD101 DEMOLITION PLAN

A-101 KW-505270A-A-101 FACILITY LAYOUT PLAN

US Army Corps of Engineers

U .S

. A R

M Y

C O

R

PS

O F

EN

G

IN

EE

R S

KUWAIT CITY

AL-JAHRA

SAUDI ARABIA

IRAQ

IRAN

PERSIAN

GULF

KUWAIT

KUWAIT

BAY

ABDALI

AL-KHIRAN

AL-WAFRAH

AHMADI

SHUMAYMAH

ARABIAN

GULF

© 2025 Microsoft Corporation © 2025 Maxar ©CNES (2025) Distribution Airbus DS © 2025 TomTom

US Army Corps of Engineers ®

SITE DESIGN COVER SHEET

SU

BM

IT

TE

D B

Y:

C H

EC

KE

D B

Y:

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

C O

N

TR

AC

T

N O

IS

SU

E D

AT

E:

SI

ZE

M

AR

K

D

ES

C R

IP

TI

O N

D

AT

E

SHEET ID

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

O

N

M

L

K

J

I

H

G

F

E

D

C

B

A

US Army Corps of Engineers

U .S

. A R

M Y

C O

R

PS

O F

EN

G

IN

EE

R S

MIDDLE EAST DISTRICT

CAMP SUBHAN, KUWAIT

KUWAIT AIR DEFENCE

MISSILE ASSEMBLY DISASSEMBLY FACILITY (MADF) RENOVATION

KW-505270

PROJECT LOCATION

PROJECT LOCATION

Scale: 1mm=1 000m

VICINITY PLAN1 Scale: 1mm=20m

PROJECT LOCATION2

M

ID

D

LE

E

AS

T D

IS

TR

IC

T

PR

IN

C E

FR

ED

ER

IC

K D

R

IV

E W

IN

C

H

ES

TE

R

, V A

W

2E R

C

AU

G

U

ST

PL

O

T D

AT

E:

FI

LE

N

AM

E:

IS

O A

C

AM

P

SU

BH

AN

, K U

W

AI

T

KU

W

AI

T

AI

R D

EF

EN

C E

M

IS

SI

LE

A

SS

EM

BL

Y D

IS

AS

SE

M

BL

Y

FA

C

IL

IT

Y (M

AD

F)

R

EN

O

VA

TI

O

N

KW

-5

C D

C

/0 8/

KW

-5

0S

IT

E- -G

I0

A.

FR

EE

M

AN

J.

H

IE

R

G

EI

ST

D .H

IC

KE

L

R .T

H O

M

AS

SI

TE

D

ES

IG

N

C O

VE

R

S H

EE

T

G

EN

ER

AL

IN

FO

R M

AT

IO

N

GI001

SITE

SO

LI

C

IT

AT

IO

N N

O

W

2E R

A0

1. DIMENSIONS SHOWN ARE IN METERS UNLESS OTHERWISE NOTED.

2. ELEVATIONS DERIVED FROM 2004 DESIGN DRAWINGS.

3. DRAWING IS FOR BIDDING PURPOSES ONLY. FINAL SITE DESIGN WILL BE THE

RESPONSIBILITY OF THE CONTRACTOR.

4. COORDINATES ARE FROM 2004 AS-BUILT, THE COORDINATE SYSTEM USED IS

UNKNOWN BUT MOST LIKELY A LOCAL COORDINATE SYSTEM.

AS BUILT COORDINATES

NAME NORTHING EASTING ELEVATION

GII-1 600.365 558.615 101.252

GII-2 644.316 796.035 97.806

GII-3 508.073 606.348 99.775

US Army Corps of Engineers

U .S

. A R

M Y

C O

R

PS

O F

EN

G

IN

EE

R S

1:200

SURVEY CONTROL POINTS1 0

m2.5 5

PLAN

NORTH

SU

BM

IT

TE

D B

Y:

C H

EC

KE

D B

Y:

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

C O

N

TR

AC

T

N O

IS

SU

E D

AT

E:

SI

ZE

M

AR

K

D

ES

C R

IP

TI

O N

D

AT

E

SHEET ID

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

O

N

M

L

K

J

I

H

G

F

E

D

C

B

A

/0 8/

KW

-5

0A

SI

TE

-V

F1

A.

FR

EE

M

AN

J.

H

IE

R

G

EI

ST

D .H

IC

KE

L

R T

H O

M

AS

SU

R

VE

Y

C O

N

TR

O L

PO

IN

TS

SI

TE

D

ES

IG

N

VF101

SITE

M

ID

D

LE

E

AS

T D

IS

TR

IC

T

PR

IN

C E

FR

ED

ER

IC

K D

R

IV

E W

IN

C

H

ES

TE

R

, V A

W

2E R

C

AU

G

U

ST

PL

O

T D

AT

E:

FI

LE

N

AM

E:

IS

O A

C

AM

P

SU

BH

AN

, K U

W

AI

T

KU

W

AI

T

AI

R D

EF

EN

C E

M

IS

SI

LE

A

SS

EM

BL

Y D

IS

AS

SE

M

BL

Y

FA

C

IL

IT

Y (M

AD

F)

R

EN

O

VA

TI

O

N

KW

-5

C D

C

SHEET KEYNOTES

GENERAL SHEET NOTES

KEY PLAN

SO

LI

C

IT

AT

IO

N N

O

W

2E R

1. DIMENSIONS SHOWN ARE IN METERS UNLESS OTHERWISE NOTED.

2. ELEVATIONS DERIVED FROM 2004 DESIGN DRAWINGS.

3. DRAWING IS FOR BIDDING PURPOSES ONLY. FINAL SITE DESIGN WILL BE THE

RESPONSIBILITY OF THE CONTRACTOR.

4. REGRADE SLOPES AROUND THE HILL TO REMOVE EROSION DAMAGE

CAUSED BY EXCESS WATER AND ADD GEOTEXTILES AND/OR STONES TO PREVENT

FUTURE EROSION.

5. CONTRACTOR TO REPAIR ANY DAMAGE TO ASPHALT DONE BY HEAVY

TRUCKS DURING CONSTRUCTION.

1. APPROXIMATE LOCATION OF EXISTING DOWNSPOUTS

2. AREA WITH TREES AND IRRIGATION SYSTEM

3. APPROXIMATE LOCATION OF EXTERIOR LIGHTS

4. GENERAL VICINITY OF FIRE PUMP HOUSE AND TWO WATER TANKS.

CONTRACTOR TO CONFIRM EXACT LOCATION AND UTILITY LINES GOING TO

EACH STRUCTURE.

5. REPLACE EXISTING SIDEWALK WITH NEW SIDEWALK THAT SLOPES AWAY

FROM THE BUILDING.

6. EMPTY, CLEAN, AND REFURBISH EXISTING SANITARY SEWER MANHOLES

7. REMOVE VEGETATION AROUND EXISTING SEPTIC TANK AND ABSORPTION

FIELD.

8. CLEAN OUT / CLEAR EXISTING SANITARY SEWER PIPES, MAKES SURE

THERE ARE NO EXISTING LEAKS.

9. SECTION OF SHOULDER, AND SIDEWALK TO BE REMOVED AND REPLACED

WITH ASPHALT FOR NEW VEHICLE RAMP.

10. NEW VEHICLE RAMP FOR NEW ROLL UP DOOR.

11. REPLACE EXISTING VEHICLE RAMP WITH NEW VEHICLE RAMP.

12. IF EXISTING VEHICLE RAMP, REPLACE WITH NEW VEHICLE RAMP,

OTHERWISE MAKE SURE THAT NEW ASPHALT RUNS FLUSH WITH THE CONCRETE

BASE UNDER THE CANOPY.

13. FULL DEPTH REPLACEMENT OF THE EXISTING ASPHALT.

CHAIN LINK SECURITY FENCE

ROAD CENTERLINE

US Army Corps of Engineers

U .S

. A R

M Y

C O

R

PS

O F

EN

G

IN

EE

R S

SCALE: 1:100

SITE PLAN1 0

m2.5 5

PLAN

NORTH

SU

BM

IT

TE

D B

Y:

C H

EC

KE

D B

Y:

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

C O

N

TR

AC

T

N O

IS

SU

E D

AT

E:

SI

ZE

M

AR

K

D

ES

C R

IP

TI

O N

D

AT

E

SHEET ID

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

O

N

M

L

K

J

I

H

G

F

E

D

C

B

A

/0 8/

KW

-5

0S

IT

E- -C

S1

A.

FR

EE

M

AN

D .H

IC

KE

L

D .H

IC

KE

L

R T

H O

M

AS

SI

TE

P

LA

N

SI

TE

D

ES

IG

N

CS101

SITE

M

ID

D

LE

E

AS

T D

IS

TR

IC

T

PR

IN

C E

FR

ED

ER

IC

K D

R

IV

E W

IN

C

H

ES

TE

R

, V A

W

2E R

C

AU

G

U

ST

PL

O

T D

AT

E:

FI

LE

N

AM

E:

IS

O A

C

AM

P

SU

BH

AN

, K U

W

AI

T

KU

W

AI

T

AI

R D

EF

EN

C E

M

IS

SI

LE

A

SS

EM

BL

Y D

IS

AS

SE

M

BL

Y

FA

C

IL

IT

Y (M

AD

F)

R

EN

O

VA

TI

O

N

KW

-5

C D

C

SHEET KEYNOTES

GENERAL SHEET NOTES

KEY PLAN

SO

LI

C

IT

AT

IO

N N

O

W

2E R

DISASSEMBLY CANNING/DECANNING

CANOPY

MECHANICALELEC/COMMO

OPEN OFFICE

SUPPLY

OFFICE

OFFICE

OFFICE

OFFICE

A

B

BREAK

ROOM

CHIEF

OFFICE

TOILET

VEST.

VEST.

ENLISTED

TOILET

OFFICERS

TOILET

OFFICE

JAN

2 3 4 5 6 7 8 9

C

COPY/

STOR.

TOILET

REMOVE EXISTING

PRE-FABRICATED

PAINT BOOTH

GENERAL NOTES

1. REMOVE ALL INTERIOR WALLS AND PARTITIONS AS WELL AS FIXTURES ON

THE HOST WALLS SHOWN IN DASHED LINE.

2. REMOVE ALL CEILING TILES AND GRIDS.

3. REMOVE ALL SLABS.

4. REMOVE THE DOOR INDICATED.

A1

B1

REMOVE DOUBLE

DOOR AND FRAME

8000 8000 7000 7000 8200 5800 7000 5850 7000

REMOVE ALL SLABS

63850

REMOVE DOUBLE

DOOR AND FRAME

SU

BM

IT

TE

D B

Y:

C H

EC

KE

D B

Y:

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

C O

N

TR

AC

T

N O

IS

SU

E D

AT

E:

SI

ZE

M

AR

K

D

ES

C R

IP

TI

O N

D

AT

E

SHEET ID

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

O

N

M

L

K

J

I

H

G

F

E

D

C

B

A

US Army Corps of Engineers

U .S

. A R

M Y

C O

R

PS

O F

EN

G

IN

EE

R S

SCALE:1:100

DEMOLITION PLAN1

M

ID

D

LE

E

AS

T D

IS

TR

IC

T

PR

IN

C E

FR

ED

ER

IC

K D

R

IV

E W

IN

C

H

ES

TE

R

, V A

W

2E R

C

AU

G

U

ST

PL

O

T D

AT

E:

FI

LE

N

AM

E:

IS

O A

C

AM

P

SU

BH

AN

, K U

W

AI

T

KU

W

AI

T

AI

R D

EF

EN

C E

M

IS

SI

LE

A

SS

EM

BL

Y D

IS

AS

SE

M

BL

Y

FA

C

IL

IT

Y (M

AD

F)

R

EN

O

VA

TI

O

N

KW

-5

C D

C

KW

-5

0A -A

D

S.

LI

N

J.

JE

N

KI

N S

S.

LI

N

R .T

H O

M

AS

D

EM

O

LI

TI

O

N P

LA

N

M

IS

SI

LE

A

SS

EM

BL

Y D

IS

AS

SE

M

BL

Y

FA

C

IL

IT

Y (M

AD

F)

AD101

A0 m2.5 5

UNLESS OTHERWISE NOTED, LINEAR

DIMENSIONS SHOWN ARE IN MILLIMETERS.

PLAN

NORTH

SO

LI

C

IT

AT

IO

N N

O

W

2E R

DISASSEMBLY ASSEMBLY

WORK

OPEN OFFICE

SUPPLY

OFFICE

OFFICEOFFICE

A

B

BREAK / PRAYER

ROOM

COMMAND

OFFICE

TOILET

121 122

VEST.

MALE WC

FEMALE WC

JAN

2 3 4 5 6 7 8 9

C

A1

B1

MECHANICAL

ROOM

COMM /

ELECTRICAL

ROOM

KITCHEN

OFFICE

OFFICE

OFFICE

OFFICE

NEW

PRE-FABRICATED

PAINT BOOTH

CLOSE EXISTING DOOR WALL OPENING NEW 3000mm ROLLUP DOOR

NEW EXTERIOR DOOR

NEW EXTERIOR DOOR

NEW 7500mm ROLLUP DOOR

LEGEND

NEW EXTERIOR WALL

EXISTING EXTERIOR WALL

NEW INTERIOR WALL

NEW 7500mm ROLLUP DOOR

NEW EXTERIOR DOOR

NEW DOUBLE DOORS

45205360

ALIGN NEW WALL TO EXISTING ALIGN NEW WALL TO

EXISTING COLUMN

29502950

8000 8000 7000 7000 8200 5800 7000 5850 7000

PLAN

NORTH

BOLLARD (TYP)

CLOSE EXISTING

DOOR WALL OPENING

63850

SU

BM

IT

TE

D B

Y:

C H

EC

KE

D B

Y:

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

C O

N

TR

AC

T

N O

IS

SU

E D

AT

E:

SI

ZE

M

AR

K

D

ES

C R

IP

TI

O N

D

AT

E

SHEET ID

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

O

N

M

L

K

J

I

H

G

F

E

D

C

B

A

US Army Corps of Engineers

U .S

. A R

M Y

C O

R

PS

O F

EN

G

IN

EE

R S

SCALE: 1:100

FACILITY LAYOUT PLAN1

M

ID

D

LE

E

AS

T D

IS

TR

IC

T

PR

IN

C E

FR

ED

ER

IC

K D

R

IV

E W

IN

C

H

ES

TE

R

, V A

W

2E R

C

AU

G

U

ST

PL

O

T D

AT

E:

FI

LE

N

AM

E:

IS

O A

C

AM

P

SU

BH

AN

, K U

W

AI

T

KU

W

AI

T

AI

R D

EF

EN

C E

M

IS

SI

LE

A

SS

EM

BL

Y D

IS

AS

SE

M

BL

Y

FA

C

IL

IT

Y (M

AD

F)

R

EN

O

VA

TI

O

N

KW

-5

C D

C

KW

-5

0A -A

-1

S.

LI

N

J.

JE

N

KI

N S

S.

LI

N

R .T

H O

M

AS

FA

C

IL

IT

Y

LA

YO

U

T

PL

AN

M

IS

SI

LE

A

SS

EM

BL

Y

D

IS

AS

SE

M

BL

Y

FA

C

IL

IT

Y

(M

AD

F)

A-101 A0 m2.5 5

UNLESS OTHERWISE NOTED, LINEAR

DIMENSIONS SHOWN ARE IN MILLIMETERS.

SO

LI

C

IT

AT

IO

N N

O

W

2E R

NOTE: Vestibule area was constructed per section 1/SS-4

Missiles Assembly Disassembly Facility (MADF)

Life and Safety Assessment, Kuwait Air Defense, Camp Subhan, Kuwait

JOC TO NO: W912ER22F0139

Prepared For

U.S. ARMY CORPS OF ENGINEERS

Life and Safety Assessment for

Fire Fighting System

Prepared By MVL USA, Inc.

2722 E Michigan Ave Suite 209, Lansing, MI 48912

INDEX

S.NO TABLE OF CONTENT

PAGE

NO.

1 PROJECT SPECIFICATION 3

2 SCOPE OF WORK 15

4 TECHNICAL EVALUATION 17

5 CONTRACTOR RECOMMENDATION 30

6 SPECIALIST CREDENTIALS 32

Life and Safety Assessment for Fire Fighting System

PROJECT SPECIFICATION

UFC 1-201-02

1 June 2014

UNIFIED FACILITIES CRITERIA (UFC)

ASSESSMENT OF EXISTING

FACILITIES FOR USE IN MILITARY

OPERATIONS

APPROVED FOR PUBLIC RELEASE; DISTRIBUTION UNLIMITED

Damaged or partially collapsed multi-story buildings or structures with damage to more than 10% of the overall building footprint are unsafe to occupy; consult Reachback.

Remove any non-structural debris and loose finishes that are considered a falling hazard. Engage professional engineering personnel to determine appropriate repair measures or to evaluate the potential for removal of damaged or loose structural elements that could pose a falling hazard. To prevent overloading of the structure, locate storage and/or heavy equipment on ground supported floor slabs.

4-4 FIRE PROTECTION

This section includes survey methods and lists of common deficiencies found with regard to fire protection in existing facilities. The information herein is limited to fire protection requirements that affect life safety of occupants, without consideration for mission continuity. Survey the building by conducting a walk-through of each room.

Complete the checklist for Detailed Evaluations that is included in Appendix E.

This document provides guidance related to fire separation of buildings for preventing fire spread between buildings. For requirements for space separation between buildings related to anti-terrorism/force protection, refer to UFC 4-010-01. It is not the intent of this document to supersede UFC 4-010-01.

For definitions of terms used in this section, see Appendix C.

Reachback assistance is required for any modification or additions to any fire protection systems.

4-4.1 Fire Protection Detailed Evaluations.

These requirements are not for use in engineering evaluations.

4-4.1.1 Building Separation.

Perform the following assessments:

• Determine the building separation from any nearby buildings as defined in Appendix C-1.

• If the building is less than 30 ft. (9.1 m.) from adjacent buildings, the following criteria must be met:

Table 4-1 Separation Requirements

Separation Distance “X”

Exterior Wall Construction of Building to be Occupied Factory Industrial, Business or Storage Occupancies

Billeting, Institutional or Assembly Occupancies

X < 10 ft.

(X < 3.1 m.)

Contiguous Exterior wall with No Openings

Contiguous Exterior wall with:

1) Noncombustible Exterior

Facing,

2) No Openings or Protected

Openings 10 ≤ X < 30 ft.

(3.1 m. ≤ X <

9.1 m.)

Contiguous Exterior wall with No Openings, or Protected Openings

Contiguous Exterior Wall with No Openings, or Protected

Openings

X ≥ 30 ft.

(X ≥ 9.1 m.)

No restrictions No restrictions

4-4.1.2 Building Height.

Perform the following assessments on the building:

• Determine the number of stories of the building as defined in Appendix C- 1.

• Determine the construction type of the building, combustible or non-combustible, as defined in Appendix C-1.

• Determine the existence of vertical openings as defined in Appendix C-1.

Building requirements or restrictions based on Building Height are as follows:

• Buildings of non-combustible construction, or of any construction with a functional automatic sprinkler system throughout, and with no vertical openings connecting more than 2 stories, can be safely occupied up to 3 floors above grade.

• Buildings of combustible construction, without an automatic sprinkler system, or with unprotected vertical openings between more than 2 floors, can be safely occupied up to 2 floors above grade.

• Building basement levels can be safely occupied by occupancies other than billeting, institutional or assembly.

• Sub-basement levels as defined in Appendix C-1 cannot be safely occupied.

4-4.1.3 Occupancy.

Determine the following:

• Confirm the planned occupancy (ies) as defined in Appendix C-3.

Building requirements based on Occupancy type are as follows:

• Dining, medical (non-inpatient), administrative, and/or recreational facilities may be collocated in a single structure.

• Where mixed occupancies as defined in Appendix C-3 exist, the most restrictive life safety requirements (including allowable travel distances, building separation requirements, fire protection requirements, and fire alarm requirements herein) for the occupancies involved are applied.

4-4.1.4 Means of Egress.

Perform the following assessments and calculations regarding Means of Egress:

• Survey all building areas to be occupied and determine the following:

a. Number of exits (as defined in Appendix C-2) per floor,

b. Width of exit doors as defined in the Exit Capacity definition in Appendix C-2,

c. Internal width of exit stairs as defined in the Exit Capacity discussion in Appendix C-2,

d. Longest travel distance per floor as defined in Appendix C-2,

e. Length of any dead end corridors as defined in Appendix C-2,

f. Existence of any large areas (over 2000 sq. ft. (186 sq. m.)) with only one door or path leading to an exit.

g. Measure the area(s) to be used as assembly spaces.

h. Confirm if any assembly occupancies are provided with only one door or exit path leading to an exit from the assembly space.

• Confirm one of the following:

o Each exit remains unlocked in the direction of egress when the area is occupied, OR:

o Any locked doors in an exit path are under the control of the occupants of the room/space, and are provided with panic hardware as defined in Appendix C-2.

• Confirm that exits are not blocked or obstructed by materials, so that access to exits is available.

• Confirm that enclosed exit stairs are not used to store materials.

• Calculate occupant loads based on the parameters given in Appendix C-3.

Measure overall areas of spaces to be occupied.

• Calculate the exit capacity as defined in Appendix C-2 based on the number of exits for a space.

• Compare the calculated exit capacity to the calculated occupant load. It is unsafe to occupy the space if the occupant load is higher than the exit capacity.

• Compare the measured travel distance to the travel distance limits for the occupancy involved from the definitions section in Appendix C-2.

4-4.1.5 Automatic Sprinkler Systems and Fire Suppression Systems.

Automatic sprinkler system is required for billeting occupancy and a fire suppression system is required for kitchen grills/hoods.

Perform the following assessments on the automatic sprinkler systems (if provided):

• Identify any existing sprinkler, standpipe, hose stations, or other fire suppression system in the building.

• A qualified person should confirm that existing water supplies (fire pump, water storage tanks, or public water system) are in service. Fire pumps should be operated by decreasing the sprinkler system pressure or flowing water in the system to determine if the fire pump starts automatically on pressure drop.

• Qualified persons include persons trained specifically within the trades of building engineering or maintenance, or active fire protection systems maintenance or installation. Contact Reachback for assistance before conducting any testing of these systems.

4-4.1.6 Fire Alarm Systems.

Fire alarm systems are required for the following:

a. A building with billeting occupancy (smoke detection is strongly recommended to be included)

b. A building with assembly occupancy.

c. A building with institutional occupancy.

d. A building with business occupancy over 5,000 sq. ft. (465 sq. m.) in a basement, second or third floors.

Perform the following assessments on the fire alarm systems (if provided):

• If building has existing fire alarm notification systems, a person, specifically trained in building engineering or maintenance, or trained in fire alarm system installation or maintenance, should determine if the notification systems are functional by operating the system. Confirm that notification appliances produce audible levels of sound in all areas of the building, or record what portions of the building have fire alarm notification appliances. If speakers are provided, confirm that the language used in the announcement is understood by the planned occupants.

• If a fire detection system is present, determine the extent of the system’s coverage.

Fire alarm systems provided for the purpose of compliance with this document may be battery operated multiple station type smoke alarm systems, interconnected either by wires or wireless type.

4-4.1.7 Hazardous Areas.

Perform the following assessments:

• Identify hazardous areas and equipment as defined in Appendix C-1.

• Existence of hazardous areas or equipment without fixed separation by walls or space separation is not safe, see the section entitled, “Hazardous Areas” for mitigation.

4-4.1.8 Interior Finish.

Perform the following assessments of the building’s interior finishes:

• Determine the interior finish in occupied areas through observations.

• Gypsum wallboard (or sheetrock), unpainted or painted metal, 3/8 inch (9.5 mm) painted or unpainted plywood, concrete block or other stone materials provide acceptable interior finish. Combustible fabrics or textiles, and rigid or sprayed-on plastic foam insulations are not acceptable as interior finishes for occupied areas.

4-4.1.9 Vertical Openings.

Perform the following assessments:

• Identify any vertical openings as defined in Appendix C-1 that exist within occupied floors.

• Vertical openings connecting more than 2 stories is not safe.

4-4.2 Mitigation Measures.

4-4.2.1 Building Separation.

For single story structures, if the fire separation criteria are not met, a mitigating measure to provide protected openings can be provided with HESCO or other similar barriers, free-standing pre-cast concrete type barriers, or sandbag revetments between buildings. If these barriers are at least as tall as the eave of the taller of the two buildings to be separated, separation between the building under consideration can be considered adequate. For taller buildings, it is also acceptable to cover existing glazed openings in exterior walls from the interior side with plywood, metal or gypsum board, or to locate sandbags along the interior side of the wall opening. Open doorways can be protected by providing solid core wood or metal doors with no glazed openings and an automatic closer. Open louvers can be provided with an extended metal cover. If this issue cannot be addressed through these field mitigation measures, obtain Reachback assistance to identify additional options.

4-4.2.2 Building Height.

Limiting occupancy to lower levels and to a single basement promotes more timely and safe relocation of persons. If it is possible to reliably limit occupancy of higher floors through administrative procedures, then it would not be necessary to physically block access to higher floors.

If building height issues cannot be resolved with field modifications given herein, if it is desired to occupy levels higher or lower than those stated herein, or if repairs to vertical openings are planned, use Reachback for technical assistance.

4-4.2.3 Occupancy.

It may be possible to mitigate existing occupancy deficiencies by providing passive or active fire protection systems.

Reachback for technical assistance is necessary for technical solutions to mixed occupancy issues that cannot be addressed by the mitigation measures presented herein.

4-4.2.4 Means of Egress.

If there are not a sufficient number of exits, the exits do not provide sufficient exit capacity, or actual travel distances exceed the travel distance limits provided herein, an exit (or exits as needed) can be added by providing an exterior exit in an exterior wall if practical. If on an upper level floor, an exit door to a fire escape can be built if practical, with Reachback assistance. Fire escapes must be constructed of noncombustible materials and supported by surrounding grade if practical (rather than hung from the building). If security or other constraints do not permit installation of a fixed external fire escape ladder, provide a portable fire escape ladder in each room near an above grade window. Newly provided second exits or escape ladders should be separated by as much distance as practical from the other existing exit within a space. Contact Reachback assistance before beginning any new construction work or modifying existing construction.

Exit paths from spaces must be provided only through spaces of less hazardous occupancies that are under control of the persons egressing, and not subject to locking.

For example, an exit path from one office through another office that is not subject to locking is acceptable. An egress path from an office through a storage room subject to locking, or through a boiler room is not acceptable. A second option for exiting should be provided in this situation, or the office area should not be occupied. It is not safe for Assembly occupancies to be located in areas with only one exit path, and should be relocated if it is not possible to provide a second exit path from the space.

One option for compliance is to only occupy the portion of a space within the allowable travel distance for the occupancy. If functioning sprinkler systems are provided for the occupied areas, contact Reachback if additional travel distance and dead end allowances are needed.

4-4.2.5 Automatic Sprinkler Systems.

For a billeting occupancy, the lack of automatic sprinkler systems in a building is a deficiency. For buildings with planned occupancy for billeting limit the total area of billeting occupancy to less than 7,000 sq. ft. (650 sq. m.) per level, and provide one of the following four options to mitigate this deficiency(a or b or c or d):

a. A fire watch covering all areas of the building.

b. Direct exits from each living unit, or from each open area to the exterior.

c. Solid, contiguous, full height stud or Concrete masonry unit type (CMU) wall partitions subdividing each living unit, and functioning battery operated smoke alarms within each living unit. Smoke alarms must be either wired multiple station, or wireless multiple station type.

d. Limit the number of beds to less than 10 within an occupied building.

For open bays planned for billeting occupancy greater than 7000, sq. ft. (650 sq. m.), contact Reachback support for assistance. Occupancy load, egress and ceiling height must be evaluated in order to determine appropriate mitigating fire protection system, active and/or passive requirements.

For occupancies other than billeting, building automatic sprinkler systems can be mitigating factors for certain other deficiencies. The lack of an automatic sprinkler systems throughout the occupancy or building is not a deficiency for occupancies other than Billeting.

4-4.2.6 Fire Alarm Systems.

Fire alarm systems (notification) are required in certain occupancies as noted in the section entitled, “Fire Alarm Systems” located in Fire Protection Detailed Evaluation paragraphs.

The existence of a complete, functional sprinkler system in all areas of a building, with water flow alarms is sufficient mitigation for a fire detection and alarm system or fire alarm notification system.

A 24 hour fire watch is a mitigating factor for the lack of a fire notification system. A person on duty having a portable horn or sounding device to notify all occupants in case of a fire event is a mitigating factor for an automatic alarm system. If the building is not occupied 24 hours a day, the fire watch is only necessary while the building is occupied.

New equipment installation or repairs beyond simple corrections need to be conducted under the guidance of Reachback assistance. If fire alarm systems are not provided and are needed, or if it is desired to provide a fire alarm system as a mitigating factor or any other reason, contact Reachback support for assistance.

4-4.2.7 Hazardous Areas.

Hazardous areas or hazardous equipment without fixed separation by walls is a deficiency. For hazardous equipment, as defined in Appendix C-1, this issue can be resolved by the existence of, or by providing a fixed suppression system (wet or dry chemical system typically), or providing a separating wall around the equipment area.

Space separation of at least 25 ft. (7.6 m) from occupied buildings is also mitigation for unprotected hazardous equipment.

Existing or planned hazardous areas need segregation and/or fire protection (as discussed herein) if these areas are to remain in service within a building. Relocation of hazardous areas outside the building in a separated area is the preferred option, if possible. It is acceptable to remove hazardous equipment from service by administrative controls if it can be confirmed that the system will remain unused.

The preferred method of mitigating hazardous material or waste storage is removal of the storage to a location outside and separated from occupied buildings by at least 50 ft.

(15.2 m). Any detailed evaluations of ventilation or containment systems, or improvements for these systems needs to be through Reachback assistance.

Installation of new construction enclosure walls, automatic sprinkler system, fire suppression systems, repairs or modifications of existing hazardous equipment to reduce its hazard, needs to be conducted with Reachback for technical assistance. It needs to be confirmed that a new hazard (inadequate ventilation, etc.) is not created by enclosing a hazardous operation.

4-4.2.8 Interior Finish.

In order to provide a thermal/fire barrier, exposed combustible insulation (polystyrene, polyurethane, paper or similar types of insulation), or combustible finishes (cork, plastic or fiberglass panels, cloth or similar finishes) can be covered with ½ inch (12.7 mm) layer of gypsum wallboard, 3/8 inch (9.5 mm) plywood, 22 gage corrugated steel, or removed, if possible. Exposed foam-in-place insulation is considered a highly

SCOPE OF WORK

Job Contract Order (JOC) for Missiles Assembly Disassembly Facility (MADF) Life and Safety Assessment

Statement of Work:

1.0 Project Description:

Kuwait Air Defense Missile Assembly and Disassembly Facility was constructed in 2006, No record of previous testing and maintenance available except for acceptance testing performed as part of the final inspection process back in 2006. Contractor to perform life and safety assessment on the systems below and prepare detailed assessment report indicating the condition of each system, recommendation for repair and or replacement, from the visual inspection, firefighting system is currently shut down. All work shall be completed per the applicable UFC codes and Kuwait Fire Force Codes.

2.0 Scope of Work

A. The Contractor Shall provide management, personnel, materials, equipment, supplies, facilities, transportations, tools, materials, and other items necessary to perform life and safety assessment for the Facility. tasks in this scope as follows, giving priority to items “1” and “2”:

1. Assessment and Functional Inspection of the grounding system,

2. Assessment and Functional inspection of lightening protection system,

3. Assessment and functional inspection of firefighting system including fire alarm and fire suppression, and pump house,

4. Assessment and functional inspection of HVAC system, Humidification System, and exhaust system,

5. Assessment and Functional inspection of the entire electrical system,

6. Assessment and functional inspection of the plumbing system, including the booster pumps in the pump house, and underground sewarlines

7. Assessment and function inspection of the 3 Ton Overhead crane,

8. Assessment and functional inspection for the GRP tank

3.0 Assessment Report

After concluding and performing the assessment for the above systems, Contractor to submit to the Government detailed assessment report indicating the methods and procedures used in the assessment, condition of each system, list of any parts or equipment’s that require repair and / or replacement, and the cause of failure if any system found to be failed or nonfunctional.

Encl. 2

TECHNICAL EVALUATION

MAIN FIRE PUMP – ELECTRIC

1. MOTOR IS RUNNING BUT THE PUMP IS

DECOUPLED.

2. ABNORMAL BEARING SOUND OBSERVED IN THE

MOTOR.

3. GLAND PACKING COMPLETELTY WORNOUT.

4. SHAFT FOUND CORRODED AT COUPLING

5. ALL GROOVED COUPLINGS TO BE REPLACED

6. ELECTRICAL PANEL LOOKS IN GOOD

CONDITION.

7. MAJOR OVERHAULING OF PUMP AND MOTOR

ARE REQUIRED TO PUT BACK INTO OPERATION.

8. PUMP/MOTOR IS COVERED BY THICK LAYER OF

DUST AND DEBRIS DUE TO NO MAINTENANCE

DONE SINCE MORE THAN 10 YEARS

9. CHECK VALVE IS COMPLETELY RUSTED

MAIN FIRE PUMP – DIESEL

1. BATTERIES ARE DISCHARGED TO BE REPLACED.

2. MAJOR OVERHAULING IS REQUIRED FOR THE COMPLETE DIESEL PUMP

3. DEISEL TANK FUEL LEVEL IS LOW, MAJOR CLEANING OF TANK WILL BE NECESSARY

4. MOST OF THE PIPE SUPPORTS ARE CORRODED.

5. ELECTRICAL PANEL SEEMS TO BE FINE, BUT THE AVR UNIT FOUND OVERHEATING.

6. PUMP/MOTOR IS COVERED BY THICK LAYER OF DUST AND DEBRIS DUE TO NO MAINTENANCE

DONE SINCE MORE THAN 10 YEARS

7. PRESSURE GAUGES ARE IN EXTRMELY POOR CONDITION, TO BE REPLACED.

8. CHECK VALVE IS COMPLETELY RUSTED TO BE REPLACED 8”

9. THE FULE TANK OUTLET PIPES ARE NOT SUPPORTED PROPERLY

JOCKEY PUMP :

1. PUMP IS WORKING BUT HAS ABNORMAL BEARING SOUND. COMPLETE

OVERHAULING FOR THE MOTOR AND PUMP IS RECOMMENDED.

2. PIPELINES, SUPPORTS, FLANGES AND VALVES ARE CORRODED, TO BE

RECONDITIONED.

3. ELECTRICAL PANEL IS FOUND OPERATIONAL AND IN GOOD CONDITION.

FIRE PUMP ROOM PIPING

1. FLOW METER IS IN WRONG POSITION.

2. ALL FLEXIBLE COUPLINGS ARE

RUSTED/ TO BE REPLACED.

3. ALL PIPE SUPPORTS ON FLOOR ARE

RUSTED AND TO BE REPLACED

4. TEST VALVE NAME PLATE IS WRONG,

IT MUST BE NORMALLY CLOSED BUT

THE NAME PLATE INDICATES

NORMALLY OPEN.

5. MAIN ENTRANCE DOOR IS CORRODED

TO BE RE-CONDITIONED OR

REPLACED.

6. OVERALL, ALL PIPING HAS TO BE

PAINTED AND SUPPORTS TO BE

REPLACED.

FIRE WATER GRP TANKS 1 AND 2

1. MAJOR WATER LEAKAGE IS OBSERVED

2. ALL PANEL BOLTS AND OVERALL STRUCTURE OBSERVED CORRODED.

3. TOO MUCH OF VEGETATION IS OBSERVED AROUND THE TANKS, TO BE CLEANED.

4. GROOVED COUPLINGS HAVE TO BE REPLACED AS THEY ARE CORRODED.

5. RECOMMENDED TO RPLACE BOTH THE TANKS WITH NEW TANKS AS THIS IS THE MOST CRITICAL

PART OF THE FACILITY.

6. PIPE SUPPORTS ARE CORODED, TO BE REPLACED.

FIRE WATER GRP TANK NO 1

1. PIPES AND FITTINGS FOUND CORRODED.

2. ALGAE FORMATION OBSERVED DUE TO

WATER LEAK FROM TANK SINCE LONG

TIME WHICH HAS NOT BE ADDRESSED.

3. LEAKAGE WATER IS GETTING

ACCUMULATED AND STAGNATED BELOW

THE TANK CREATING ENVIRONMENTAL

HAZARD AND FOUL SMELL AND

ATTRACTING HARMFUL CREATURES AND

ALSO LEADING TO VEGETATION GROWTH

FIRE WATER GRP TANK NO 2

1. PIPES AND FITTINGS FOUND CORRODED.

2. TANK STRUCTURE, NUT BOLTS, FLANGES, VALVES AND SUPPORTS ARE FOUND CORRODED.

3. WATER IS GETTING ACCUMULATED AND STAGNATED BELOW THE TANK CREATING

ENVIRONMENTAL HAZARD AND FOUL SMELL AND ATTRACTING HARMFUL CREATURES AND ALSO

LEADING TO VEGETATION GROWTH

SHED FIRE PIPING NETWORK

1. ALL PIPE SUPPORTS TO BE REPLACED.

2. ALL SPRINKLERS TO BE REPLACED

3. PAINTING OF ENTIRE FIRE PIPING IS

REQUIRED.

4. PRESSURE TESTING HAS TO BE DONE TO

CHECK THE CONDITION OF LEAK

ELECTRICAL ROOM FIREFIGHTING PIPELINE

1. MOST OF THE FITTINGS, VALVES, FLANGES AND

FASTERNERS ARE CORRODED AND SOME KIND

OF FOAM FORMATION IS OBSERVED ON THE

FLANGES.

2. FIRE DEPARTMENT CONNECTION IS FOUND

RUSTED.

3. ALL GROOVED COUPLINGS TO BE REPLACED

4. HEAVY DUST ACCUMLATION OBSERVED ON THE

BFP AND ENTIRE FIRE FIGHTING SYSTEM,

POORLY MAINTAINED

FIRE SUPRESSION

SYSTEM

1. SYSTEM HAS TO BE

COMPLETELY

REPLACED AS IT IS

NOT WORKING AND

IN EXTREME POOR

CONDITION DUE TO

NO MAINTAINECE AT

ALL IN THE SYSTEM

CREATING

HAZARDOUS

SITUATION TO THE

WORKING STAFF IN

THE PAINT BOOTH

POST INDICATOR VALVE

1. POORLY MAINTAINED.

2. PAINTING IS REQUIRED.

3. PRESSURE TESTING IS REQUIRED

4. CURRENTLY NO WATER IN THE LINE DUE TO

UNOPERATIONAL SYSTEM

FIRE HYDRANT – 01

CONDITION SEEMS TO BE FINE, GENERAL

SERVICING OF HYDRANTS IS NECESSARY.

PRESSURE TEST HAS TO BE CONDUCTED TO

ENSURE THE UNDERGROUND DI PIPE

CONDITION IS FINE. GENERAL PAINTING IS

REQUIRED. NO WATER OBSERVED IN THE

HYDRANT

FIRE HYDRANT – 02

CONDITION SEEMS IS EXTREMELY

WORST. THE BASE FOUNDATION

CONCRETE HAS FLOWN AWAY

WITH THE RAIN WATER, NEW

FOUNDATION WILL BE REQUIRED

FOR THE HYDRANT

FIRE HYDRANT – 03

CONDITION SEEMS TO BE FINE, GENERAL SERVICING

OF HYDRANTS IS NECESSARY. PRESSURE TEST HAS TO

BE CONDUCTED TO ENSURE THE UNDERGROUND DI

PIPE CONDITION IS FINE. GENERAL PAINTING IS

REQUIRED. NO WATER IS OBSERVED IN THE HYDRANT

CONTRACTOR’S RECOMMENDATION

Contractor’s Recommendations

1. The Firefighting system is totally un-operational; the fire main pumps & jockey pump has not been maintained periodically resulting into failure of the firefighting system for the entire facility.

2. Heavy dust accumulation upon all the equipment & services for long time has made the situation worse calling resulting into corrosion of major firefighting accessories in fire pump room & entire building.

3. The fire water storage tanks are found heavily leaking and poorly maintained and resulting into environmental hazards as well as lack of water availability for the firefighting.

4. As the facility is missile assembly & disassembly, which involves a highest risk of fire hazards, for the safety of the occupants, we recommend for immediate evacuation of the facility until the entire firefighting system is reconditioned, tested & commissioned thoroughly for appropriate operations.

5. We recommend for major overhauling of all the fire main pumps & jockey pump and replacement of all supports, grooved fittings, valves, flow meter, pressure gauges etc.

6. We strongly recommend for the replacement of both the fire water GRP tanks with new tanks as the condition of the existing tanks is poor.

7. Deficiencies shall be mitigated by posting warning notice on the fire pump room as well as the building entrance as “high risk of fire hazards”.

Life and Safety Assessment, Kuwait Air Defense, Camp Subhan, Kuwait

MIDDLE EAST DISTRICT

Life and Safety Assessment for Plumbing, Sewer System and Compressed Air System.

NO.

1 PROJECT SPECIFICATION 11

2 SCOPE OF WORK 15

3 TECHNICAL EVALUATION OF PLUMBING & SEWER SYSTEM 17

4 CONTRACTOR RECOMMENDATION 37

5 CHEMICAL ANALYSIS OF POTABLE WATER 39

6 SPECIALIST CREDENTIALS 42

of Engineers

KU - MADF Life and Safety Assessment

CONTRACT NO: W912ER20D0002/W912ER22F0139

Response to Comments on Transmittal no.: 22 00 00-1

(Life and Safety Assessment for Plumbing System)

ITEM REFERENCE COR REVIEW REMARKS CONTRACTOR RESPONSE STATUS

1.

SECTION 22 00

The KTR needed to utilize the forms in Appendix E as stated in UFC 1-201-02 (Assessment of Existing Facilities for Use in Military Operations) to include the cover page, the building sketch and sections pertaining to the plumbing system.

Concur. The filled in form(Appendix E from UFC 1-201-02) has been enclosed. Page 06 & 07 Of 53

2.

In reference to the water quality test, the KTR needs to clearly indicate if based on the test results can the water be considered potable.

Concur. Contractor has been enclosed the revised quality test with clear states that the results comply with the given specification limits for potable system. Page 40 & 41 Of 53

3.

Following the Appendix format provide the condition found opposite to suggested mitigation in addition to providing additional notes and completely prepare a detailed Assessment Report as indicated in Item 3 of the scope of works.

Concur. The filled in form(Appendix E from UFC 1-201-02) has been enclosed. Page 06 & 07 Of 53

4.

For the Potable Water System:

In fire pump room where the potable water is connected, the KTR's recommendation to rehabilitate the same tapping connection is not allowed as this pipe (clearly painted red) which should exclusively be used for fire suppression system for the facility. If the current base water network is utilizing a common main pipeline for both fire suppression and potable water, the tapping point should be from the water main and not on the fire pump room pipe header. The assessment needs to identify if this condition exists.

The assessment needs to indicate whether there is a potable water supply from the base network or if not there needs to be a trucked in water supply with the following conditions:

That the potable water system needs to have a provision for both trucked in water supply and a provision to receive water from the base water network.

Is there a need for adequate water treatment (i.e. filtration, etc.) to comply with potable water standards?

The KTR needs to establish if a need for disinfection is required for the existing piping network for the facility.

Identify the appropriate location for the potable water system equipment within the facility compound.

Identify in the sketch the location of the potable water network as much as possible and to include where the pipes were originally drawing water from the base water mains.

Determine whether the GRP tank located near the entrance is only for Fire Suppression or does it include the potable water network.

What is the present condition of the potable water line from the fire pump room to the facility

Concur. The tapping for the plumbing line can be taken from the base line (details required, as its details are not present in given set of drawings) without interfering with the fire water line, thru a saddle tee.

There is no potable water supply from base network. The tapping has been given from fire suppression system which is not acceptable. Moreover, as the fire suppression is completely shut down, there is no water flow in the fire and plumbing line. A temporary arrangement with a small tank and small pump has been arranged to feed the plumbing line which shall be filled by external source like water tanker.

Concur.

There is a need for adequate water treatment to comply with potable water standards.

There is a need to establish disinfection for the existing piping network for the facility as the service has been closed for a long time.

The pumps for the potable water system are in appropriate location. The tapping for the plumbing line can be taken from the main line and connected to pumps in fire pump room.

In the asbuilt drawing M PR-1, the water supply to the tank is given by a 2” CPVC pipe.The pipe is going underground and to check the continuation of the line excavation is required to check where the pipe is connected to.Probably only after checking the existing base line, the provision for connection for plumbing line can be determined.Morepver continuation or connection to baseline is not shown in drawing M PR-1 and neither any detail is shown in any of the set of drawings provided.

The GRP tank located near the entrance which has been temporarily arranged is only feeding the potable water network.

There is no water supply in potable water line from the fire pump room to facility, as the fire suppression system is shut down and the tapping taken from it to the plumbing services doesn’t supply water. Hence a temporary arrangement with a small tank and small pump has been arranged to feed the plumbing line which shall be filled by external source like water tanker.

For Sewer System:

The sewage manhole is still usable and does not need to be replaced.

Identify if there is a need to have the existing sewer system leak tested.

Identify in the sketch where the sewer line is located and where the water is flowing.

Clearly tabulate the fixtures and their locations which needs repair/replacements

Concur.

There is no requirement for leak to be tested in existing sewer line as the system seems to be good.

As per As built drawing DS-01, the sewer line from 5 Rooms (Room No. 102,102A, 104,105

& 107) is exiting thru 3 Nos 150 mm dia sleeve to the external sewer line whose continuation is mentioned in drawing SD-DS-06 which is not provided with the set of drawings.

Concur.Enclosed in the tabulated list of fixtures to be repaired/replaced.

PROJECT TITLE Kuwait

LOCATION KU - MADF Life and Safety Assessment

DATE

01/29/2023

TRANSMITTAL NO.

22 00 00-1

Item Description Variation QA Code

1 Life and Safety Assessment for Plumbing, No X

SECTION III - GOVERNMENT REVIEW REMARKS

Code X - Receipt Acknowledged but does not comply

1.1 The KTR needed to utilize the forms in Appendix E as stated in UFC 1-201-02 (Assessment of Existing Facilities for Use in Military Operations to include the cover page, the building sketch and sections pertaining to the plumbing system.

1.2 In reference to the water quality test, the KTR needs to clearly indicate if based on the test results can the water be considered potable.

1.3 Following the Appendix format provide the condition found opposite to suggested mitigation in addition to providing additional notes and completely prepare a detailed Assessment Report as indicated in Item 3 of the scope of works.

1.4 For the Potable Water System

1.4.1 In fire pump room where the potable water is connected, the KTR's recommendation to rehabilitate the same tapping connection is not allowed as this pipe (clearly painted red) which should exclusively be used for fire suppression system for the facility. If the current base water network is utilizing a common main pipeline for both fire suppression and potable water, the tapping point should be from the water main and not on the fire pump room pipe header. The assessment needs to identify if this condition exists.

1.4.2 The assessment needs to indicate whether there is a potable water supply from the base network or if not there needs to be a trucked in water supply with the following conditions:

1.4.2a That the potable water system needs to have a provision for both trucked in water supply and a provision to receive water from the base water network.

1.4.2b Is there a need for adequate water treatment (i.e. filtration, etc.) to comply with potable water standards?

1.4.2c The KTR needs to establish if a need for disinfection is required for the existing piping network for the facility.

1.4.2d Identify the appropriate location for the potable water system equipment within the facility compound.

1.4.3 Identify in the sketch the location of the potable water network as much as possible and to include where the pipes were originally drawing water from the base water mains.

1.4.4 Determine whether the GRP tank located near the entrance is only for Fire Suppression or does it include the potable water network.

1.4.5 What is the present condition of the potable water line from the fire pump room to the facility.

1.5 For Sewer System

1.5.1 The sewage manhole is still usable and does not need to be replaced.

1.5.2 Identify if there is a need to have the existing sewer system leak tested.

1.5.3 Identify in the sketch where the sewer line is located and where the water is flowing.

1.5.4 Clearly tabulate the fixtures and their locations which needs repair/replacements.

CONTRACT NO.

W912ER20D0002

W912ER22F0139

PAGE

TRANSMITTAL OF SHOP DRAWINGS, EQUIPMENT DATA

MATERIAL SAMPLES, OR MANUFACTURER'S

CERTIFICATES OF COMPLIANCE

Attachment to ENG FORM 4025-R

Detailed Evaluation Checklist for Building Occupancy

BUILDING DESCRIPTION: KUWAIT MISSILE ASSEMBLY & DISASSEMBLY FACILITY

LOCATION: KUWAIT BLDG NO.:

CONDITION ASSESSED

CONDITION

FOUND?

MITIGATION

SECTION #

SUGGESTED MITIGATION

Visual Inspection and Tests

Domestic water unsafe based on testing?

Potable water Safe to be used

4-5.2.1

Contractor has been enclosed the revised quality test with clear states that the results comply with the given specification limits for potable

Any evidence of plumbing systems leaking? No 4-5.2.1 No leakages have been found in the plumbing system

Any domestic water system cross connections?

Potable water connection taken by tapping taken from fire suppression line

4-5.2.1

The tapping for the plumbing line can be taken from the main line and connected to pumps in fire pump room.

In the asbuilt drawing M PR-1, the water supply to the tank is given by a 2” CPVC pipe.The pipe is going underground and to check the continuation of the line excavation is required to check where the pipe is connected to.Probably only after checking the existing base line, the provision for connection for plumbing line can be determined.

HVAC system does not function properly, is unsafe or not operational?

N/A 4-5.2.5 N/A

Exposed or above-ceiling HVAC pipes leaking? N/A 4-5.2.6 N/A

Visual Inspection and Field Surveys

Hot water systems are not configured properly or do not have appropriate safety equipment?

N/A

4-5.2.2

Hot water equipment does not function properly or has inappropriate temperature settings?

4-5.2.2

INSPECTOR: MAJID ALI DATE/TIME:

DETAILED EVALUATION (continued)

PLUMBING AND MECHANICAL SYSTEM ISSUES INSPECTOR:

Additional Notes on Plumbing and Mechanical System Issues and Mitigation Actions:

The tapping for the plumbing line can be taken from the main line (Ductile Iron) without interfering with the fire water line, thru a saddle tee.

There is a need for adequate water treatment to comply with potable water standards.

There is a need to establish disinfection for the existing piping network for the facility as the service has been closed for a long time.

In the asbuilt drawing M PR-1, the water supply to the tank is given by a 2” CPVC pipe.The pipe is going underground and to check the continuation of the line excavation is required to check where the pipe is connected to.Probably only after checking the existing base line, the provision for connection for plumbing line can be determined.

Sanitary piping and venting is not configured properly and/or not all traps are sealed?

The sewer line from 5 Rooms (Room No.

102,102A, 104,105 &

107) is exiting thru 3 Nos 150 mm dia sleeve to the external sewer line whose continuation is mentioned in drawing SD-DS-06 which is not available.

4-5.2.3

Need As built Drawing No: SD-

DS-06

Vents through roof show signs of blockage? N/A 4-5.2.3 N/A

Roof and overflow drainage systems are obstructed by debris or not configured properly?

4-5.2.4

Fuel system components are inappropriate or unsafe to operate?

N/A 4-5.2.2 N/A

MAJID ALI

S.No Image Description Room No Need repair/replacements Of

The water closet's flush tank is not having lid upon it and needs to be covered with a new lid 104 Repair

The indian style water closet's flush tank is not having lid upon it and needs to be covered with a new lid 104 Repair

The water purifier's filters need to be replaced with new filters for better performance.

105 Replacement Of Filters

KU - MADF Life and Safety Assessment

CONTRACT NO: W912ER20D0002/W912ER22F0139

Life and Safety Assessment for Plumbing System List Of Fixtures to be Repaired/Replaced combustible material; unless specific documentation is provided to the contrary.

Combustible decorations must be removed from occupied areas.

4-4.2.9 Vertical Openings.

Vertical openings connecting more than 2 stories is not safe. The measures given in the section entitled, “Building Height” to only occupy two floors above grade level provides sufficient mitigation of a vertical opening issue. If it is desired to occupy levels more than two stories above grade, and a vertical opening exists within the planned space that is more than 2 stories, use Reachback assistance to see if the facility, considered in its entirety, can be occupied as planned.

One field measure that can be taken to resolve a vertical opening issue in buildings higher than two stories is enclosing the open shaft (for example, enclosing one level of a 3-story opening to create a 2-story vertical opening) with gypsum wall board. It should be confirmed that enclosing a shaft used for supplying air will allow the shaft to provide mechanical ventilation, and that this modification may not cause structural issues. Any construction modifications should be completed under the guidance of Reachback assistance.

4-5 PLUMBING AND MECHANICAL SYSTEMS.

This section includes assessment and risk mitigation of common deficiencies found with regard to plumbing and mechanical systems in existing facilities. A checklist for use during assessments for Detailed Evaluations is included in Appendix E.

All plumbing and mechanical system evaluations outlined in this section are performed by visual inspection and tests. Refer to TM 3-34.70/MCRP 3-17.7E, Plumbing, Pipe Fitting, and Sewerage, for assistance in these Plumbing and Mechanical inspections.

4-5.1 Features Evaluated.

The following features are to be evaluated by visual inspection and tests.

4-5.1.1 Domestic Water System.

Perform the following assessments on the domestic water system:

• Take samples and test domestic water to verify water is safe to use and safe to drink.

• Visually inspect facility water storage tank (when located on roof or inside the facility) and all exposed domestic water piping and examine condition of ceilings, walls, and floors for signs of domestic water piping leaks.

• Determine if cross connections exist in piping systems.

• Determine and record location of domestic water service and main shutoff valve.

4-5.1.2 Domestic Water Heating Equipment.

Perform the following assessments on the domestic water heating equipment:

• Examine domestic water heating systems to determine if the systems have the following safety features.

o Anti-siphon device, such as a cold water drip tube or a vacuum relief valve installed in the cold water supply line o Electrical disconnect or fuel supply shut off valve o Self-closing pressure relief and temperature valve o Pressure relief valve discharge pipe

• Determine if water is being heated and equipment is functioning properly, and if the hot water equipment consists of pressurized or non-pressurized tanks.

4-5.1.3 Sanitary Drainage and Vent System.

Perform the following assessments on the sanitary drainage and vent system:

• Visually inspect all exposed sanitary drainage and vent piping and examine condition of ceilings, walls, and floors for signs of sanitary system piping leaks.

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .